Schneider Electric Direct Coupled SmartX Actuators are
designed to be used in both damper and valve control
applications. The following general instructions are for
damper applications; refer to the Applicable Literature
table for valve literature.
The MF4x-7xx3 series spring return actuators are used
by SPDT floating controller for modulating dampers and
valves in HVAC systems.
MF40-7043 Series
MF41-7073 Series
MF41-7153 Series
SmartX Actuators
Spring Return Floating
General Instruction
Features
• Floating actuator controlled by SPDT floating controllers
• 133 lb-in (15 N-m), 60 lb-in (7 N-m), or 35 lb-in (4 N-m)
of torque
• Rugged die cast housings rated for NEMA 2 / IP54
• Provides 95° of rotation
• Visual position indicator provided
• Optional built-in auxiliary switch to provide for interfacing
or signaling
• Provides true mechanical clockwise or counterclockwise
spring return operation for reliable spring return
application and positive close-off in air tight damper
applications
• Direct mount to round or square damper shafts
• Rotation limiting available
• MF41-7153 series actuators can be doublemounted
(gang mounting) to accommodate high torque
application requirements
LISTED
MF40-7043
MF40-7043-501
MF41-7073
MF41-7153
MF41-7073-502
MF41-7153-502
• Five year warranty
• MF41-707x and MF41-715x equipped with manual
override
Schneider Electric
F-26644-9August 2014
2
Applicable Literature
F-NumberDescriptionAudiencePurpose
F-26750MA4x-xxxx-2xx, MF4x-xxxx-2xx, MS4x-xxxx-
2xx Series Actuator/Linkage Assemblies General
Instructions
– Installers
– Service Personnel
– Start-up Technicians
Describes the globe valve
actuator/linkage assembly’s
features, specifications, and
possible applications. Provides
step-by-step mounting
instructions.
Describes the actuator/linkage/
ball valve assembly’s features,
specifications, and possible
applications. Provides stepbystep mounting instructions.
Provides actuator specifications
and part number cross
referencing of phased out
actuators with the new
Schneider Electric directcoupled actuators.
Provides part number cross
referencing of phased out globe
and ball valve assemblies with
the new Schneider Electric
direct-coupled actuators.
Describes Schneider Electric
approved water treatment
practices.
Provides charts, equations,
and diagrams to assist in the
configuration of valve system
applications. TOOL-150,
valve sizing slide rule may be
purchased separately.
Schneider Electric
F-26644-8 August 2014
Schneider Electric
F-26644-9August 2014
SPECIFICATIONS
3
Actuator Inputs
Control Signal: Floating control, 24 Vac.
Power Input: See Table-1. All 24 Vac circuits are Class 2.
Connections: 3 ft. (91 cm) plenum rated cable for MF40-7043-xxx and 3 ft. (91 cm)
appliance cable for MF41-7153-xxx or MF41-7073-xxx, 1/2” (13 mm) conduit connector.
For M20 Metric conduit, use AM-756 adaptor.
Actuator Outputs
Electrical:
Auxiliary Switch:
MF40-7043-501 One SPDT 6A (1.5A) @24 Vac, Switch adjustable 15 to 95°
(MIN to 1 scale).
MF41-7153-502 or MF41-7073-502 Two SPDT 7A (2.5A) @250 Vac, One fixed @
5° and one adjustable 25 to 85°.
Mechanical:
Stroke, Angle of rotation 95° ±5°. Adjustable 30° to 95° with AM-689 installed on
MF41-7153-xxx or MF41-7073-xxx. MF40-7043-xxx models are adjustable 40° to
95° by adjusting the stop block position on the actuator.
Damper Shaft Clamp,
MF40-7043-xxx The factory installed universal clamp is used for shafts up to
5/8” (15 mm) diameter or up to 1/2” (13 mm) square. AM-710 accessory clamp is
required when mounting actuators to shafts up to 3/4” (19 mm) diameter or up to
1/2” (13 mm) square.
MF41-7153-xxx or MF41-7073-xxx The factory installed universal clamp is used
for shafts up to 3/4” (19 mm) diameter or up to 1/2” (13 mm) square. AM-687
accessory clamp is required when mounting actuators to shafts up to 1.05” (27
mm) in diameter or up to 5/8” (15 mm) square.
Position Indicator, Visual indicator.
MF41-7153 and MF41-7073, -5 to 90° (-5° is spring return position).
MF40-7043, 0 to 1 (0 is spring return position).
Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specifications.
Direction of Rotation, Clockwise or counterclockwise rotation determined by
actuator mounting.
Manual Override, MF41-7073 and MF41-7153 are equipped with a manual rotation
adjustment from -5 to 85°.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 160°F (-40 to 71°C).
Operating, -22 to 140°F (-30 to 60°C).
Humidity: 15 to 95% RH, non-condensing.
Location:
MF41-7153-xxx and MF41-7073-xxx, NEMA 1 (IEC IP30). NEMA 2 (IEC IP54)
with conduit connector in the down position.
MF40-7043-xxx, NEMA 2 (IEC IP54) no restrictions.
Agency Listings
UL 873: Underwriters Laboratories (File # E9429 Category Temperature-Indicating and
Regulating Equipment).
CUL: UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards
C22.2 No. 24-93.
European Community: EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
Australia: This product meets requirements to bear the C-Tick Mark according to the
terms specified by the Communications Authority under the Radiocommunications Act
1992.
Schneider Electric
F-26644-9August 2014
4
Table-1 Model Chart.
Approximate
Part
Numbers
Voltage
Actuator Power Input
RunningHolding
50 Hz60 Hz
VAWVAWW
Amps
DC
50/60
Timing in Seconds
Powered
Hz
@ 70° (21°C)
Spring
Return
a
Auxiliary
Switch
MF41-7153
MF41-7153-502
MF41-7073
MF41-7073-502
24 Vac ± 20%
22 to 30 Vdc
MF40-7043
MF40-7043-501One
a
Timing was measured with no load applied to the actuator.
b
De-rating is required at low temperatures.
c
One adjustable from 25° to 85 rotation and one set to operate @ 5° xed.
d
One adjustable from 15° to 95° rotation (MIN to 1 scale).
9.87.79.77.70.303.3<190<30
6.24.86.24.80.182.8<195<30
5.94.45.94.40.172.9<130<25
ACCESSORIES
For use with MF40-7xx3:
AM-671 Universal Mounting Bracket, AM-693 is required
AM-672 Universal Mounting Bracket, AM-693 is required
AM-673 Adjustable Mounting Bracket for multiple actuators
AM-674 Weather Shield
AM-675 Base Mounting Plate for AM-674
AM-676 Universal Shaft Extension
AM-714 Weather Shield (polycarbonate)
AM-756 Metric Conduit Adapter M20 x 1.5 to 1/2” NPT
AM-761 7-inch Anti-rotation Bracket
AM-762 9-inch Anti-rotation Bracket
No
Two
No
Two
No
Output Tor que Rating
lb.-in. (N-m)
Minimum
133
c
(15)
60
c
(7)
35
d
(4)
b
Maximum
Stall
350 (40)
250 (28)
150 (17)
For use with MF40-7043:
AM-709 Position Indicator and Stroke Limiter
AM-710 Universal Clamp for up to 3/4” diameter shafts
AM-711 Crankarm for up to 1/2” round shaft
AM-712 Crankarm Adaptor Kit
AM-713 Mounting Bracket for Honeywell Mod IV, M6415 type actuators and new
installations
AM-715 Crankarm Adaptor Kit for Honeywell Mod IV, M6415 type actuators and new
installations
AM-717 Replacement Universal V-Clamp for 1/2” diameter shafts
For use with MF41-7073, MF41-7153:
AM-686 Damper Position Indicator
AM-687 Universal Clamp for up to 1.05” (27 mm) diameter shafts.
AM-688 Replacement Universal V-clamp
AM-689 Rotation Limiter
AM-690 Crankarm for round shafts up to 3/4” (19 mm)
AM-691 Crankarm for jackshafts up to 1.05” (27 mm)
AM-692 V-bolt Kit for AM-690 and AM-691 Crankarm
AM-693 Damper Linkage Kit
AM-758 Short “U” Mounting Bracket
AM-759 Tall “U” Mounting Bracket
AM-760 Slotted “L” Mounting Bracket
AM-763 1/8” Hex Crank for Manual Override
Schneider Electric
F-26644-9August 2014
TYPICAL APPLICATIONS (wiring diagrams)
1 For end position indication, interlock control
Figure-1 through Figure-5 illustrate typical wiring diagrams for spring return floating
actuators. See Table-1 for model selection.
Caution: This product contains a half-wave rectifier power supply and must
not be powered off transformers used to power other devices utilizing
non-isolated full-wave rectifier power supplies. Refer to EN-206, Guidelines
for Powering Multiple Devices from a Common Transformer, F-26363 for
detailed information.
24 Vac Transformer
1
Line
Volts
or 22-30 Vdc
Typical
Floating
Controller
Black
Red
Blue
Yellow/Black
Common
Hot (+DC)
3
3
CCW
Green/Yellow
CW
MF41-7153
MF41-7073
2
Figure-1 Floating Point Control.
1 Provide overload protection and
disconnect as required.
2 Actuators may be wired in parallel.
All actuator black wires are
connected to the transformer
common and all red wires are
connected to the hot lead. Power
consumption must be observed.
3 As viewed from "L" side.
5
Optional Auxiliary Switches
Org
Vio
Yel
Org/Wht
Vio/Wht
Yel/Wht
COM
NC
NO
COM
NC
NO
MF41-707x-502 and MF41-715x-502 units manufactured prior to the date code 0141 (October 6, 2001) used the following color coding for the auxiliary switches:
Auxiliary Switch 1
Orange: Fixed auxiliary switch common (com)
Yellow: Fixed auxiliary switch normally closed (NC)
Violet: Fixed auxiliary switch normally open (NO)
Auxiliary Switch 2
Orange/white: Adjustable auxiliary switch common (com)
Violet/white: Adjustable auxiliary switch normally closed (NC)
Yellow/white: Adjustable auxiliary switch normally open (NO)
The label information on these units is incorrect. If replacing these units, the auxiliary switch
operation of the replacement actuator will be per the product label.
Aux Switches
MF4x-7073-502
MF4x-7153-502
Aux Switch 1
25 to 85°
Adjustable
1
Aux Switch 2
5° Fixed
fan startup, etc., MF4x-7xx3-50x models
incorporate one or two built-in auxiliary
switches. See Specifications section
for details.
Model #
MF41-7153-502
MF41-7073-502
MF40-7043-501
Switch
Switch
Type
AAdjustable, 25° - 85°
BFixed at 5°
AAdjustable, MIN - 1 scale
BNone
Figure-2 Optional Auxiliary Switches.
Schneider Electric
F-26644-9August 2014
6
24 Vac Transformer
1
or 22-30 Vdc
Line
Volts
24 Vac Transformer
1
Line
Volts
Controller
or 22-30 Vdc
Common
Hot
Controller
Hot
Common
Black
Red
Blue
Yellow/Black
3
Green/Yellow
Figure-3 Triac source.
Black
Red
Blue
Yellow/Black
Hot (+DC)
Green/Yellow
Figure-4 Triac Sink.
Common
Hot (+DC)
CW
CCW
Common
5
5
CCW
As viewed from "L" Side
5
CW
MF41-7153
MF40-7043
MF41-7073
MF41-7153
MF40-7043
MF41-7073
2
4
1 Provide overload protection
and disconnect as required.
2 If the controller uses a full-
23
3
wave power supply and does
not provide isolated outputs, a
separate transformer is
required.
3 As viewed from "L" side.
1 Provide overload protection and
disconnect as required.
2 Actuators may be wired in
parallel. All actuator black wires
are connected to the
transformer common and all
red wires are connected to the
hot lead. Power consumption
must be observed.
3 The Common connection from
the actuator must be connected
to the Hot connection of the
controller. The actuator Hot
must be connected to the
controller Common.
4 If the controller uses a full-
wave power supply and does
not provide isolated outputs, a
separate transformer is
required.
24 Vac Transformer
1
Line
Volts
or 22-30 Vdc
Hot
Common
24 Vac Transformer
1
or 22-30 Vdc
Line
Volts
Black
Common
Hot (+DC)
Red
Blue CW
5
MF41-7153
MF40-7043
MF41-7073
2
3
4
1 Provide overload protection
and disconnect as required.
2 Actuators may be wired in
parallel. All actuator black
wires are connected to the
transformer common and all
red wires are connected to the
hot lead. Power consumption
must be observed.
3 The actuator Hot must be
connected to the controller
Common.
4 If the controller uses a full-
Yellow/Black
5
CCW
wave power supply and does
not provide isolated outputs, a
separate transformer is
Green/Yellow
Controller
required.
5 As viewed from "L" side.
Figure-5
Schneider Electric
F-26644-9August 2014
INSTALLATION
7
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier
immediately. If undamaged, open the package and inspect the device for obvious
damage. Return damaged products.
Requirements •Job wiring diagrams
• Tools (not provided)
– #8 sheet metal screws
– 10mm open end wrench or socket wrench
– 1/8 inch, allen wrench
– Appropriate screwdriver(s)
• Appropriate accessories
• Training: Installer must be a qualified, experienced technician
Precautions General
Warning:
• Electrical shock hazard! Disconnect the power supply (line power) before
installation to prevent electric shock and equipment damage.
• Make all connections in accordance with the job wiring diagram and in
accordance with national and local electrical codes. Use copper conductors
only.
Caution:
• Avoid electrical noise interference. Do not install near large contactors,
electrical machinery, or welding equipment.
• Do not drill holes in actuator body. Six pre-drilled holes are located on each
side, under the label, to accept #10-24 thread-forming screws for mounting
accessories.
Caution: The MF41-707x and MF41-715x actuators are equipped with a manual
override.
• The manual override is to be used only when power is not applied to the unit.
• If the universal clamp is not set to 0° on the position indicator, manually wind
the actuator in the direction indicated with hex wrench from -5° to 0° and
lock with a screwdriver.
• When operating manual override, back off 5° from full open mechanical stop
to ensure proper release.
• Do not attempt to use the manual override with actuators mounted in
tandem. Damage to the gear train could occur.
Note: When operating manual override, back off 5° from full open mechanical
stop to ensure proper release.
Federal Communications Commission (FCC)
Note: This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in
residential installations. This equipment generates, uses, and can radiate radio
frequency energy and may cause harmful interference if not installed and used
in accordance with the instructions. Even when instructions are followed, there
is no guarantee that interference will not occur in a particular installation. If this
equipment causes harmful interference to radio or television equipment—which
can be determined by turning the equipment off and on—the user is encouraged
to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment to an outlet on a circuit different from that to which
the receiver is connected.
• Consult the dealer or an experienced radio/television technician for help.
Schneider Electric
F-26644-9August 2014
8
Canadian Department of Communications (DOC)
Note: This Class B digital apparatus meets all requirements of the Canadian
Interference- Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le
material broilleur du Canada.
European Standard EN 55022
Warning: This is a Class B digital (European Classification) product. In a domestic
environment this product may cause radio interference in which case the user may be
required to take adequate measures.
LocationCaution: Avoid locations where excessive moisture, corrosive fumes, vibration, or
explosive vapors are present.
MountingCaution: To remain in NEMA 2/IP54 compliance, the MF40-7153 and MF40-7073 series
actuators must be mounted with conduit end down.
Mount the Schneider Electric SmartX Actuator directly on the damper shaft in locations
that clear the maximum dimensions of the actuator case and allow the actuator to be
mounted flush to the surface of the terminal box and perpendicular to the damper shaft.
Caution: Mx41-707x and Mx4x-715x: Do not attempt to use the manual override if
actuators are mounted in tandem. Damage to the gear train could occur.
Note: Some terminal boxes have sheet metal screw heads or other protrusions near the
damper shaft. In these cases, a spacer or shim may be added under the anti-rotation
bracket of the actuator to make the actuator perpendicular to the shaft.
Damper Actuator Sizing
Correct sizing of the actuator is necessary for proper control of dampers. The area
of damper that can be controlled by a given actuator is dependent upon the type of
damper, the quality of the damper, the pressure drop across the damper in the closed
position, and the velocity of the air flow through the damper. To obtain actual damper
torque requirements, contact the damper manufacturer.
Damper Shaft Sizing
Use the “Long Damper Shaft” mounting instructions if the damper shaft is at least 3-1/2”
(90 mm) long.
Use the “Short Damper Shaft” mounting instructions if the damper shaft is shorter than
3-1/2” (90 mm) or the area around the damper shaft is too narrow to allow standard
mounting, as described in the “Short Damper Shaft” mounting section.
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.