Schneider Electric DS301 User Manual

IL•1F CANopen DS301
Fieldbus interface Fieldbus manual
V2.01, 11.2008
0198441113586, V2.01, 11.2008
www.schneider-electric.com
Important information IL•1F CANopen DS301

Important information

This manual is part of the product.
Carefully read this manual and observe all instructions.
Keep this manual for future reference.
Hand this manual and all other pertinent product documentation over to all users of the product.
Carefully read and observe all safety instructions and the chapter "Be­fore you begin - safety information".
Some products are not available in all countries. For information on the availability of products, please consult the cata­log.
Subject to technical modifications without notice.
All details provided are technical data which do not constitute warranted qualities.
Most of the product designations are registered trademarks of their re­spective owners, even if this is not explicitly indicated.
2 Fieldbus interface
IL•1F CANopen DS301 Table of Contents

Table of Contents

Important information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Writing conventions and symbols. . . . . . . . . . . . . . . . . . . . . . . 7
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2 CAN-Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 Fieldbus devices networked via CAN bus . . . . . . . . . . . 10
1.4 Operating modes and functions in fieldbus mode . . . . . 10
1.5 Documentation and literature references . . . . . . . . . . . 11
2 Before you begin - safety information. . . . . . . . . . . . . . . . . . . 13
3 Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 CANopen technology . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.1 CANopen description language . . . . . . . . . . . . . . . . 15
3.1.2 Communication layers . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.3 Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.4 CANopen profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2 Communication profile. . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.1 Object dictionary. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.2 Communication objects . . . . . . . . . . . . . . . . . . . . . . 21
3.2.3 Communication relationships . . . . . . . . . . . . . . . . . . 24
3.3 Service data communication . . . . . . . . . . . . . . . . . . . . . 26
3.3.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3.2 SDO data exchange . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3.3 SDO message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.3.4 Reading and writing data . . . . . . . . . . . . . . . . . . . . . 28
3.4 Process data communication . . . . . . . . . . . . . . . . . . . . 31
3.4.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.4.2 PDO data exchange . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.5 Synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.6 Network management services . . . . . . . . . . . . . . . . . . . 46
3.6.1 NMT services for device control . . . . . . . . . . . . . . . . 46
3.6.2 NMT services for connection monitoring . . . . . . . . . 48
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Fieldbus interface 3
Table of Contents IL•1F CANopen DS301
5 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.1 Commissioning the device . . . . . . . . . . . . . . . . . . . . . . 53
5.2 Address and baud rate . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.3 Commissioning the fieldbus network . . . . . . . . . . . . . . 54
5.3.1 Starting fieldbus mode . . . . . . . . . . . . . . . . . . . . . . . 54
5.3.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.4 SyCon CANopen configuration software . . . . . . . . . . . 56
5.4.1 Creating a new network . . . . . . . . . . . . . . . . . . . . . . 56
5.4.2 Selecting the CANopen master . . . . . . . . . . . . . . . . 56
5.4.3 Setting the bus parameters . . . . . . . . . . . . . . . . . . . 57
5.4.4 Selecting and inserting nodes . . . . . . . . . . . . . . . . . 58
6 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.2 Using SDO commands . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.2.1 Writing parameters. . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.2.2 Reading a parameter . . . . . . . . . . . . . . . . . . . . . . . . 62
6.2.3 Synchronous errors . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.3 Changing operating states with PDO4 . . . . . . . . . . . . . 63
6.3.1 Switching the power stage on and off . . . . . . . . . . . 64
6.3.2 Triggering a "Quick Stop" . . . . . . . . . . . . . . . . . . . . . 64
6.3.3 Resetting faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.4 Examples for the operating modes with PDO4. . . . . . . 67
6.4.1 Operating mode Profile Position:
absolute positioning . . . . . . . . . . . . . . . . . . . . . . . . . 68
6.4.2 Operating mode Profile Position:
relative positioning . . . . . . . . . . . . . . . . . . . . . . . . . . 69
6.4.3 Operating mode Profile Velocity. . . . . . . . . . . . . . . . 69
6.4.4 Position setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6.4.5 Operating mode Homing . . . . . . . . . . . . . . . . . . . . . 71
6.5 Error signaling via PDO4 . . . . . . . . . . . . . . . . . . . . . . . 72
6.5.1 Synchronous errors . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.5.2 Asynchronous errors . . . . . . . . . . . . . . . . . . . . . . . . 72
7 Diagnostics and troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 75
7.1 Fieldbus communication error diagnostics . . . . . . . . . . 75
7.2 Error diagnostics via fieldbus . . . . . . . . . . . . . . . . . . . . 76
7.2.1 Message objects . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.2.2 Messages on the device status . . . . . . . . . . . . . . . . 76
7.3 CANopen error messages . . . . . . . . . . . . . . . . . . . . . . 77
7.3.1 Error register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.3.2 Error code table . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.3.3 SDO error message ABORT . . . . . . . . . . . . . . . . . . 78
4 Fieldbus interface
IL•1F CANopen DS301 Table of Contents
8 Object directory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.1.1 Specifications for the objects . . . . . . . . . . . . . . . . . . 79
8.1.2 Objects, overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
8.2 Objects of the product . . . . . . . . . . . . . . . . . . . . . . . . . . 81
9 Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.1 Units and conversion tables . . . . . . . . . . . . . . . . . . . . . 93
9.1.1 Length. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.1.2 Mass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.1.3 Force. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.1.4 Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.1.5 Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.1.6 Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.1.7 Moment of inertia . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.1.8 Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.1.9 Conductor cross section . . . . . . . . . . . . . . . . . . . . . . 94
9.2 Terms and Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . 95
10 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Fieldbus interface 5
Table of Contents IL•1F CANopen DS301
6 Fieldbus interface
IL•1F CANopen DS301 Writing conventions and symbols

Writing conventions and symbols

Work steps If work steps must be performed consecutively, this sequence of steps
is represented as follows:
쮿 Special prerequisites for the following work steps
Step 1
Specific response to this work step
Step 2
If a response to a work step is indicated, this allows you to verify that the work step has been performed correctly.
Unless otherwise stated, the individual steps must be performed in the specified sequence.
Bulleted lists The items in bulleted lists are sorted alphanumerically or by priority. Bul-
leted lists are structured as follows:
Item 1 of bulleted list
Item 2 of bulleted list
–Subitem for 2
–Subitem for 2
Item 3 of bulleted list
Making work easier Information on making work easier is highlighted by this symbol:
Sections highlighted this way provide supplementary information on making work easier.
SI units SI units are the original values. Converted units are shown in brackets
behind the original value; they may be rounded.
Example: Minimum conductor cross section: 1.5 mm
2
(AWG 14)
Fieldbus interface 7
Writing conventions and symbols IL•1F CANopen DS301
8 Fieldbus interface

IL•1F CANopen DS301 1 Introduction

1 Introduction

1.1 About this manual

This manual describes the fieldbus specifics for products in a fieldbus network addressed via CANopen DS301.

1.2 CAN-Bus

The CAN bus (Controller Area Network) was originally developed for fast, economical data transmission in the automotive industry. Today, the CAN bus is also used in industrial automation technology and has been further developed for communication at fieldbus level.
Features of the CAN bus The CAN bus is a standardized, open bus enabling communication be-
tween devices, sensors and actuators from different manufacturers. The features of the CAN bus comprise
Multimaster capability
Each device in the fieldbus can transmit and receive data independ­ently without depending on an "ordering" master functionality.
Message-oriented communication
Devices can be integrated into a running network without reconfigu­ration of the entire system. The address of a new device does not need to be specified on the network.
Prioritization of messages
Messages with higher priority are sent first for time-critical applica­tions.
Residual error probability
Various security features in the network reduce the probability of undetected incorrect data transmission to less than 10
Transmission technology In the CAN bus, multiple devices are connected via a bus cable. Each
network device can transmit and receive messages. Data between net­work devices are transmitted serially.
Network devices Examples of CAN bus devices are
Automation devices, e.g. PLCs
•PCs
-11
.
Input/output modules
•Drives
Analysis devices
Sensors and actuators
Fieldbus interface 9
1 Introduction IL•1F CANopen DS301
L
N

1.3 Fieldbus devices networked via CAN bus

Different fieldbus devices can be operated in the same fieldbus seg­ment. The CANopen bus provides a common basis for interchanging commands and data between the product described and other network devices.
Figure 1.1 Fieldbus devices in the network

1.4 Operating modes and functions in fieldbus mode

This manual only describes the protocol for the slave. See the chapters "Operation" and "Parameters" for descriptions of the operating modes, functions and all parameters of the slave:
Operating modes Profile Velocity
Profile position
•Homing
•Jog
Functions Definition of direction of rotation
Motion profile generation
•Quick Stop
Fast position capture
Settings The following settings can be made via the fieldbus:
Reading and writing parameters
Monitoring the inputs and outputs of the 24 V signal interface
Activating diagnostics and fault monitoring functions
Fieldbus mode
10 Fieldbus interface
IL•1F CANopen DS301 1 Introduction

1.5 Documentation and literature references

Manuals In addition to this fieldbus manual, the following manuals also belongs to
the product:
Product manual, describes the technical data, installation, com­missioning and all operating modes and functions.
CAN users and manufacturers
organization
CANopen standards CiA Standard 301 (DS301)
Literature Controller Area Network
CiA - CAN in Automation Am Weichselgarten 26 D-91058 Erlangen
http://www.can-cia.org/
CANopen application layer and communication profile V4.02, February 2002
CiA Standard 402 (DSP402) Device profile for drives and motion control V2.0, July 2002
ISO/DIS 11898: Controller Area Network (CAN) for high speed communication;1993
EN 50325-4: Industrial communications subsystem based on ISO 11898 for controller device interfaces (CANopen); 2002
Konrad Etschberger, Carl Hanser Verlag ISBN 3-446-19431-2
Fieldbus interface 11
1 Introduction IL•1F CANopen DS301
12 Fieldbus interface

IL•1F CANopen DS301 2 Before you begin - safety information

2 Before you begin - safety information
The information provided in this manual supplements the product man­ual. Carefully read the product manual before you begin.
Fieldbus interface 13
2 Before you begin - safety information IL•1F CANopen DS301
14 Fieldbus interface

IL•1F CANopen DS301 3 Basics

3Basics

3.1 CANopen technology

3.1.1 CANopen description language

CANopen is a device- and manufacturer-independent description lan­guage for communication via the CAN bus. CANopen provides a com­mon basis for interchanging commands and data between CAN bus devices.

3.1.2 Communication layers

CANopen uses the CAN bus technology for data communication.
CANopen is based on the basic network services for data communica­tion as per the ISO-OSI model model. 3 layers enable data communica­tion via the CAN bus.
Physical Layer
Data Link Layer
Application Layer
device communication
application Layer
data Link Layer
physical Layer
fielb bus communication
CAN-Bus
Figure 3.1 CANopen layer model
Physical Layer The physical layer defines the electrical properties of the CAN bus such
as connectors, cable length and cable properties such as bit-coding and bit-timing.
Data Link Layer The data link layer connects the network devices. It assigns priorities to
individual data packets and monitors and corrects errors.
Application Layer The application layer uses communication objects (COB) to exchange
data between the various devices. Communication objects are elemen­tary components for creating a CANopen application.
Fieldbus interface 15
3 Basics IL•1F CANopen DS301

3.1.3 Objects

All processes under CANopen are executed via objects. Objects carry out different tasks; they act as communication objects for data transport to the fieldbus, control the process of establishing a connection or mon­itor the network devices. If objects are directly linked to the device (de­vice-specific objects), the device functions can be used and changed via these objects.
Object dictionary The object dictionary of each network device allows for communication
between the devices. Other devices find all objects with which they can communicate in this dictionary.
CANopen
Communication
Process data
objects (PDO)
Service data
objects (SDO)
SYNC, EMCY
Network
management NMT
CAN-Bus
Object
directory
1000
h
3000
h
6000
h
FFFF
h
Device
functions
Application
Device profile
Specific functions
Powe r amplifier
Motor
Figure 3.2 Device model with object dictionary
Objects for describing the data types and executing the communication tasks and device functions under CANopen are included in the object dictionary.
Object index Every object is addressed by means of a 16 bit index, which is repre-
sented as a four-digit hexadecimal number. The objects are arranged in groups in the object dictionary.
Index (hex) Object groups Supported
by the drive
0000
h
0001
-009FhStatic and complex data types No
h
Reserved No
00A0h-0FFFhReserved No
1000h-1FFFhCommunication profile, standardized in DS 301 Yes
2000
-5FFFhManufacturer-specific device profiles Yes
h
6000h-9FFFhStandardized device profiles, e.g. in DSP 402 No
-FFFFhReserved No
A000
h
Table 3.1 Object index
See page 79, 8.2 "Objects of the product" for a list of the CANopen ob­jects.
Object group data types Data types are used so that the messages that are transmitted via the
network as bit streams have the same meaning for the transmitting and
16 Fieldbus interface
IL•1F CANopen DS301 3 Basics
receiving devices. Data types are declared by means of the objects of the data types.
Object groups of the profiles CANopen objects carry out various tasks in fieldbus mode. Profiles
group the objects by tasks.
Fieldbus interface 17
3 Basics IL•1F CANopen DS301

3.1.4 CANopen profiles

Standardized profiles Standardized profiles describe objects that are used with different de-
vices without additional configuration. The users and manufacturers or­ganization CAN in Automation has standardized various profiles. These include:
DS301 communication profile
DSP402 device profile
Application Layer
Application
Device Profile for Drives and Motion Control (CiA DSP 402)
CANopen Communication Profile (CiA DS 301)
Data Link Layer
Physical Layer
CAN-Bus
Figure 3.3 CANopen reference model
DS301 communication profile The DS301 communication profile is the interface between device pro-
files and CAN bus. It was specified in 1995 under the name DS301 and defines uniform standards for common data exchange between different device types under CANopen.
The objects of the communication profile in the device carry out the tasks of data exchange and parameter exchange with other network de­vices and initialize, control and monitor the device in the network.
Objects of the communication profile are:
Process Data Objects = PDO
Service Data Objects = SDO
Objects with special functions for synchronization SYNC and for error messages and error response EMCY
Network management NMT objects for initialization, error monitor­ing and device status monitoring.
DSP402 device profile The DSP402 device profile describes standardized objects for position-
ing, monitoring and settings of drives. The tasks of the objects include:
Device monitoring and status monitoring (Device Control)
Standardized parameterization
Changing, monitoring and execution of operating modes
IMPORTANT: The product does not support the CiA 402 device profile.
Vendor-specific profiles The basic functions of a device can be used with objects of standardized
device profiles standardized. Only vendor-specific device profiles offer the complete range of functions. The objects with which the special func­tions of a device can be used under CANopen are defined in these ven­dor-specific device profiles.
18 Fieldbus interface
IL•1F CANopen DS301 3 Basics

3.2 Communication profile

CANopen manages communication between the network devices with object dictionaries and objects. A network device can use process data objects (PDO) and service data objects (SDO) to request the object data from the object dictionary of another device and, if permissible, write back modified values.
The following can be done by accessing the objects of the network de­vices
Exchange parameter values
Start motion functions of individual CAN bus devices
Request status information

3.2.1 Object dictionary

Each CANopen device manages an object dictionary which contains all objects for communication.
Index, subindex The objects are addressed in the object dictionary via a 16 bit index.
One or more 8 bit subindex entries for each object specify individual data fields in the object. Index and subindex are shown in hexadecimal nota­tion with a subscript "
".
h
The following example shows the index entries and subindex entries for the object receive PDO4 mapping, 1603
Index Subindex Object Meaning
1603
1603
1603
1603
Table 3.2 Examples of index and subindex entries
00
h
h
01
h
h
02
h
h
03
h
h
Number of elements Number of subindexes 1st mapped object
R_PDO4 2nd mapped object
R_PDO4 3rd mapped object
R_PDO4
for mapping in R_PDO4.
h
First object for mapping in R_PDO4
Second object for mapping in R_PDO4
Third object for mapping in R_PDO4
Fieldbus interface 19
3 Basics IL•1F CANopen DS301
Structure of object dictionary The objects in the object dictionary are sorted by index values. Table 3.3
shows the index ranges of the object dictionary according to the CAN­open specifications.
Index range (hex)
0000
h
0001h-001FhStatic data types No
0020h-003FhComplex data types No
0040
-005FhManufacturer-specific data types No
h
0060h-007FhStatic data types for the device profiles No
0080h-009FhComplex data types for the device profiles No
00A0
-0FFFhReserved No
h
1000h-1FFFhCommunication profile Yes
2000h-5FFFhManufacturer-specific profiles Yes
6000
-9FFFhStandardized device profiles No
h
A000h-FFFFhReserved No
Table 3.3 Index ranges of the object dictionary
Object groups Supported
by the drive
Reserved No
Object descriptions inthe manual For CANopen programming of a product, the following object groups are
described in detail:
1xxx
3xxx
objects: Communication objects in this chapter
h
objects: Manufacturer-specific objects to the extent they are
h
required for controlling the product
All operating modes and functions of the product are controlled by means of manufacturer-specific objects. These functions and objects are described in the device documentation.
The manufacturer-specific objects are stored in the index range starting at 3000 documentation, it is sufficient to add 3000
. To derive the CAN index from the indexes given in the device
h
.
h
Example: The control word for a state transition has the index 28 and the subindex
1. In the CAN protocol, this results in the index 301C
28
]) and the subindex 1.
d
(3000h + 1Ch[=
h
20 Fieldbus interface
IL•1F CANopen DS301 3 Basics

3.2.2 Communication objects

Overview The communication objects are standardized with the DS301 CANopen
communication profile. The objects can be classified into 4 groups ac­cording to their tasks.
PDO T_PDO1 R_PDO1
T_PDO2 R_PDO2 T_PDO3 R_PDO3
T_PDO4 R_PDO4
Communication
SDO
T_SDO R_SDO
Figure 3.4 Communication objects; the following applies to the perspective
of the network device: T_..: "Transmit", R_..: "Receive"
objects
Special objects
SYNC EMCY
Network management
NMT Services NMT Node guarding
NMT Heartbeat
PDOs (process data objects) for real-time transmission of process data
SDOs (service data object) for read and write access to the object dictionary
Objects for controlling CAN messages:
– SYNC object (synchronization object) for synchronization of net-
work devices
– EMCY object (emergency object), for signaling errors of a device
or its peripherals.
Network management services:
– NMT services for initialization and network control (NMT: net-
work management)
– NMT Node Guarding for monitoring the network devices
– NMT Heartbeat for monitoring the network devices
Fieldbus interface 21
3 Basics IL•1F CANopen DS301
CAN message Data is exchanged via the CAN bus in the form of CAN messages. A
CAN message transmits the communication object and a variety of ad­ministration and control information.
CAN message
111 1 111 7
Data
Control
RTR-Bit
Identifier
Start-Bit
CRC
Acknowledge
>=36160..8 Byte
End-Bits
COB-ID
11 Bit
7 Bit4 Bit
CANopen message (simplified)
0..8 Byte
data carrier
1 2 3 4 5 6 70
Figure 3.5 CAN message and simplified representation of CANopen mes-
sage
CANopen message For work with CANopen objects and for data exchange, the CAN mes-
sage can be represented in simplified form because most of the bits are used for error correction. These bits are automatically removed from the receive message by the data link layer of the OSI model, and added to a message before it is transmitted.
The two bit fields "Identifier" and "Data" form the simplified CANopen message. The "Identifier" corresponds to the "COB ID" and the "Data" field to the data frame (maximum length 8 bytes) of a CANopen mes­sage.
COB ID The COB ID (Communication OBject Identifier) has 2 tasks as far as
controlling communication objects is concerned:
Bus arbitration: Specification of transmission priorities
Identification of communication objects
An 11 bit COB identifier as per the CAN 3.0A specification is defined for CAN communication; it comprises 2 parts
Function code, 4 bits
Node address (node ID), 7 bits.
Bit:10 0
1
COB-ID
2 3 4 1 2 3 4 5 6 7
Function code
0...15
Node-ID
0...127
Figure 3.6 COB ID with function code and node address
22 Fieldbus interface
IL•1F CANopen DS301 3 Basics
COB IDs of the communication
objects
The following table shows the COB IDs of all communication objects with the factory settings. The column "Index of object parameters" shows the index of special objects with which the settings of the com­munication objects can be read or modified via an SDO.
Communication object Function
code
NMT Start/Stop Service 0 0 0 0 0 0 0 0 0 0 0 0 (0
SYNC object 0 0 0 1 0 0 0 0 0 0 0 128 (80h) 1005h....1007
EMCY object 0 0 0 1 x x x x x x x 128 (80h) + node ID 1014h, 1015
T_PDO1
R_PDO1
T_PDO2
R_PDO2
T_PDO3
R_PDO3
1)
1)
1)
1)
1)
1)
0 0 1 1 x x x x x x x 384 (180h) + node ID 1800 0 1 0 0 x x x x x x x 512 (200h) + node ID 1400 0 1 0 1 x x x x x x x 640 (280h) + node ID 1801 0 1 1 0 x x x x x x x 768 (300h) + node ID 1401 0 1 1 1 x x x x x x x 896 (380h) + node ID 1802
1 0 0 0 x x x x x x x 1024 (400h) + node ID 1402 T_PDO4 1 0 0 1 x x x x x x x 1152 (480h) + node ID 1803 R_PDO4 1 0 1 0 x x x x x x x 1280 (500h) + node ID 1403 T_SDO 1 0 1 1 x x x x x x x 1408 (580h) + node ID ­R_SDO 1 1 0 0 x x x x x x x 1536 (600 NMT error control 1 1 1 0 x x x x x x x 1792 (700h) + node ID
LMT Services
NMT Identify Service
DBT Services
NMT Services
1) Not supported by the device
1)
1)
1)
1 1 1 1 1 1 0 0 1 0 x 2020 (7E4h), 2021 (7E5h)
1)
1 1 1 1 1 1 0 0 1 1 0 2022 (7E6h)
1 1 1 1 1 1 0 0 x x x 2023 (7E7h), 2024 (7F8h)
1 1 1 1 1 1 0 1 0 0 x 2025 (7E9h), 2026 (7EAh)
Node address, node ID [1...127]
COB ID decimal (hexadecimal) Index of object
parameters
)-
h
h
h
h
h
h
h
h
h
) + node ID -
h
h
h
Table 3.4 COB IDs of all communication objects
COB IDs of PDOs can be changed as required. The assignment pattern for COB IDs only specifies a basic setting.
Function code The function code classifies the communication objects. Since the bits
of the function code in the COB ID are more significant, the function code simultaneously controls the transmission priorities: Objects with a lower function code are transmitted with higher priority. For example, an object with function code "1" is transmitted prior to an object with func­tion code "3" in the case of simultaneous bus access.
Node address Every network device is configured before it is operated on the network.
The device is assigned a 7 bit node address (node ID) between 1 (01 and 127 (7F
). The device address "0" is reserved for "broadcast" trans-
h
missions which are used to send messages to all devices simultane­ously.
Fieldbus interface 23
)
h
3 Basics IL•1F CANopen DS301
Example Selection of a COB ID
For a device with the node address 5, the COB ID of the communication object T_PDO1 is:
384+node ID = 384 (180
Data frame The data frame of the CANopen message can hold up to 8 bytes of data.
In addition to the data frame for SDOs and PDOs, special frame types are specified in the CANopen profile:
Error data frame
Remote data frame for requesting a message
The data frames contain the respective communication objects.

3.2.3 Communication relationships

CANopen uses 3 relationships for communication between network de­vices:
Master-slave relationship
Client-server relationship
Producer-consumer relationship
Master-slave relationship A network master controls the message traffic. A slave only responds
when it is addressed by the master.
The master-slave relationship is used with network management ob­jects for a controlled network start and to monitor the connection of de­vices.
) + 5 = 389 (185h).
h
Slave
Master
Master
Figure 3.7 Master - slave relationships
data
request
data
Slave
Slave
Slave
Messages can be interchanged with and without confirmation. If the master sends an unconfirmed CAN message, it can be received by a single or by several slaves or by no slave.
To confirm the message, the master requests a message from a specific slave, which then responds with the desired data.
24 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Client-server relationship A client-server relationship is established between 2 devices. The
"server" is the device whose object dictionary is used during data ex­change. The "client" addresses and starts the exchange of messages and waits for a confirmation from the server.
A client-server relationship with SDOs is used to send configuration data and long messages.
Client
Figure 3.8 Client-server relationship
data
data
Server
The client addresses and sends a CAN message to a server. The server evaluates the message and sends the response data as an acknowl­edgement.
Producer-consumer relationship The producer-consumer relationship is used for exchanging messages
with process data, because this relationship enables fast data exchange without administration data.
A "Producer" sends data, a "Consumer" receives data.
Consumer
Producer
data
Consumer
Consumer
request
Producer
data
Figure 3.9 Producer-consumer relationships
Consumer
Consumer
The producer sends a message that can be received by one or more network devices. The producer does not receive an acknowledgement to the effect that the message was received. The message transmission can be triggered
by an internal event, e.g. "target position reached"
by the synchronization object SYNC
a request of a consumer
For details on the function of the producer-consumer relationship and on requesting messages see chapter 3.4 "Process data communication".
Fieldbus interface 25
3 Basics IL•1F CANopen DS301

3.3 Service data communication

3.3.1 Overview

Service Data Object(SDO: Service Data Object) can be used to access the entries of an object dictionary via index and subindex. The values of the objects can be read and, if permissible, also be changed.
Every network device has at least one server SDO to be able to respond to read and write requests from a different device. A client SDO is only required to request SDO messages from the object dictionary of a dif­ferent device or to change them there.
The T_SDO of an SDO client is used to send the request for data ex­change; the R_SDO is used to receive. The data frame of an SDO con­sist of 8 bytes.
SDOs have a higher COB ID than PDOs and therefore are sent over the CAN bus at a lower priority.

3.3.2 SDO data exchange

A service data object (SDO) sends parameter data between two de­vices. The data exchange conforms to the client-server relationship. The server is the device to whose object dictionary an SDO message refers.
Client
R_SDO T_SDO
(request)
COB-ID data
CAN
Figure 3.10 SDO message exchange with request and response
COB-ID
data
(response)
T_SDO
R_SDO
Server
Message types Client-server communication is triggered by the client to send parameter
values to the server or to get them from the server. In both cases, the cli­ent starts the communication with a request and receives a response from the server.
26 Fieldbus interface
IL•1F CANopen DS301 3 Basics

3.3.3 SDO message

Put simply, an SDO message consists of the COB ID and the SDO data frame, in which up to 4 bytes of data can be sent. Longer data se­quences are distributed over multiple SDO messages with a special pro­tocol.
The device sends SDOs of up to 4 bytes data length (data). Greater amounts of data such as 8 byte values of the data type "Visible String 8" can be distributed over multiple SDOs and are transmitted successively in 7 byte blocks.
Example The following illustration shows an example of an SDO message.
SDO
581
COB-ID (581h)
1 2 3 4 5 6 7
0
00
43 10 00 01 0292 00
Data
Subindex
Index
Command Code
Figure 3.11 SDO message, example
COB ID and data frame R_SDO and T_SDO have different COB IDs.
The data frame of an SDO messages consists of:
Command code (ccd) in which the SDO message type and the data length of the transmitted value are encrypted
Index and subindex which point to the object whose data is trans­ported with the SDO message
Data of up to 4 bytes
Evaluation of numeric values Index and data are transmitted left-aligned in Intel format. If the SDO
contains numerical values of more than 1 byte in length, the data must be rearranged byte-by-byte before and after a transmission.
581
Index:
1 2 3 4 5 6 7
0
00
43 10 00 01 0292 00
Data:
Hex:
10 00
h
00 02 01 92
h
Figure 3.12 Rearranging numeric values greater than 1 byte
Fieldbus interface 27
3 Basics IL•1F CANopen DS301

3.3.4 Reading and writing data

Writing data The client starts a write request by sending index, subindex, data length
and value.
The server sends a confirmation indicating whether the data was cor­rectly processed. The confirmation contains the same index and subindex, but no data.
Client
write request
COB-ID
COB-ID
ccd=
ccd
60h
ccd=
ccd=
ccd=
ccd=
Idx
1
ccd
23h
27h
2Bh
2Fh
2
Idx
2 3 4 5 6 70
1
Idx
Idx
2 3 4 5 6 70
Sidx
1
Sidx
2
1
data
data
data
data
data
data
write response
Server
Figure 3.13 Writing parameter values
Unused bytes in the data field are shown with a slash in the graphic. The content of these data fields is not defined.
ccd coding The table below shows the command code for writing parameter values.
It depends on the message type and the transmitted data length.
Message type Data length used
4 bytes 3 bytes 2 bytes 1 byte
Write request 23
Write response 60
Error response 80
27
h
60
h
80
h
2B
h
60
h
80
h
2F
h
60
h
80
h
Transmitting param-
h
eters
Confirmation
h
Error
h
Table 3.5 Command code for writing parameter values
28 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Reading data The client starts a read request by sending the index and subindex that
point to the object or the object value whose value it wants to read.
The server confirms the request by sending the desired data. The SDO response contains the same index and subindex. The length of the re­sponse data is specified in the command code "ccd".
Client
read request
COB-ID
ccd=
ccd=
ccd=
ccd=
COB-ID
ccd
43h
47h
4Bh
4Fh
ccd=
Idx
2 3 4 5 6 70
1
ccd
40h
1
Idx
2
Idx
Idx
2 3 4 5 6 70
Sidx
1
Sidx
2
1
data
data
data
data
read response
data
data
Server
Figure 3.14 Reading a parameter value
Unused bytes in the data field are shown with a slash in the graphic. The content of these data fields is not defined.
ccd coding The table below shows the command code for transmitting a read value.
It depends on the message type and the transmitted data length.
Message type Data length used
4
1 byte
bytes3 bytes2 bytes
read request 40
Read response 43
Error response 80
40
h
47
h
80
h
40
h
4B
h
80
h
40
h
4F
h
80
h
Request read value
h
Return read value
h
Error
h
Table 3.6 Command code for transmitting a read value
Fieldbus interface 29
3 Basics IL•1F CANopen DS301
Error response If a message could not be evaluated without errors, the server sends an
error message. For details on the evaluation of the error message see chapter 7 "Diagnostics and troubleshooting".
Client
2 3 4 5 6 70
1
Idx
COB-ID
ccd:
ccd
80
Idx
Sidx
1
2
data
Figure 3.15 Response with error message (error response)
Server
error response
Byte 4-7 error code
30 Fieldbus interface
IL•1F CANopen DS301 3 Basics

3.4 Process data communication

3.4.1 Overview

This chapter describes the flow of information from the perspective of your product in compliance with CiA standard DS301. The designation "receive" relates to a flow of data from the master to the product, while "transmit" represents a flow of data from the product to the master.
Process data objects (PDO: Process Data Object) are used for real-time data exchange of process data such as actual and reference or operat­ing state of the device. Transmission is very fast because the data is sent without additional administration data and a response from the recipient is not required.
The flexible data length of a PDO message also increases the data throughput. A PDO message can transmit up to 8 bytes of data. If only 2 bytes are assigned, only 2 data bytes are sent.
The length of a PDO message and the assignment of the data fields are specified by PDO mapping. For more information see chapter 3.4.2.1 "Dynamic and static PDO mapping".
PDO messages can be exchanged between devices that generate or process process data.
One PDO each is available for sending and receiving a PDO message:
T_PDO to transmit the PDO message (T: "Transmit"),
R_PDO to receive data (R: "Receive").
Fieldbus interface 31
3 Basics IL•1F CANopen DS301

3.4.2 PDO data exchange

PDO Consumer
COB-ID Data
T_PDO
PDO Producer
Figure 3.16 PDO data exchange
R_PDO
PDO Consumer
PDO Consumer
R_PDO
CAN
R_PDO
Data exchange with PDOs follows to the producer-consumer relation­ship and can be triggered in 3 ways
Synchronized
Event-driven, asynchronous
On request of a consumer, asynchronous
The SYNC object controls synchronized data processing. Synchronous PDO messages are transmitted immediately like the standard PDO messages, but are only evaluated on the next SYNC. For example, sev­eral drives can be started simultaneously via synchronized data ex­change.
The device immediately evaluates PDO messages that are called on re­quest or in an event-driven way.
The transmission type can be specified separately for each PDO with subindex 02
(transmission type) of the PDO communication parameter.
h
The objects are listed in 8 "Object directory".
Event-driven The "event" is a change of the PDO data. In this mode, the data is im-
mediately transmitted after a change. Please note that in the case of, for example, a positioning movement, the actual position changes con­stantly so that a large number of PDOs is transmitted. There are two ways to avoid such a large number of PDOs:
A) You can set an "Inhibit Timer" (object 1803
subindex 3). The
h
PDO is not sent until after this inhibit time has passed.
B) By using a bit mask, you can limit the check for changes (=event). See section "Bit mask for T_PDO4" for a description.
A further possibility of "creating" an event consists of activating an "Event Timer" (object 1803
subindex 5). You activate this counter by en-
h
tering a value not equal to zero. When this counter is reached, this rep­resents an additional event. This means that the PDO is transmitted when a value changes or when the counter event occurs.
Synchronized In the case of this transmission mode, a PDO is transmitted in relation
to a SYNC object. See 3.5 "Synchronization" for a detailed description.
32 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Remotely requested Transmission of an asynchronous PDO is triggered when an external re-
quest is received. Such a "Remote Request" is represented by a special bit in the CAN transmission frame; it has the same COB ID (communi­cation object identifier) as the requested communication object.
An overview of the individual transmission types can be found in the ob­ject dictionary, PDO parameters.
Bit mask for T_PDO4 A bit mask can be defined for the objects CAN.pdo4msk1 (30:9) and
CAN.pdo4msk2 (30:10) in T_PDO4. All bit positions containing a "zero"
are then no longer considered in the checks for changes (=event). This allows you, for example, to limit checks to changes of the driveStat in­formation.
NameIdx:Sub dec. (hex.)
30:9 (1E:09h) The default value 4294967295 corresponds to 0xFFFFFFFF. UINT32 -
30:10 (1E:0Ah)
MeaningBit assignment Data type UnitDe-
See object pdo4msk1 for a description. UINT32 -0 R/W/-
Table 3.7 Parameters for the CAN bus
Example In this example, setting the object CAN.pdo4msk2 to zero keeps modi-
fications to the current position from triggering an event.
pdo4msk2 pdo4msk1
FFhFFh FFhFFh
ByteT_PDO4
21 43 65 87
driveStat
00h00h 00h00h
reserved
modeStat
fault (dez.)
429496729 5
actual Position
R/W/ rem. Info
R/W/-
Figure 3.17 Setting the object CAN.pdo4msk2 to zero
Fieldbus interface 33
3 Basics IL•1F CANopen DS301
Requesting process data One or more network devices with consumer function can request PDO
messages from a producer. The producer is identified by the COB ID of the request and responds with the requested PDO.
RTR
Consumer
COB-Id
COB-Id
Figure 3.18 Requesting a message with RTR = 1
1
0
Daten
Producer
The RTR bit (RTR: Remote Transmission Request) of a CAN message is used to detect a request. The COB ID remains the same for both mes­sages:RTR = 0: transmission of dataRTR = 1: request for data.
Setting RTR request You can set for each PDO separately whether it responds to RTR re-
quests. This is switched on or off via subindex 01, bit 30 Subindex 02
(transmission type) of the objects defines the transmis-
h
of each PDO.
h
sion type. The PDO only responds to a request via bit RTR if RTR trans­mission is enabled for a PDO. The subindex values for the RTR bit are:
Objects 1403h, 1803h subindex 02h, "transmission type"
252 RTR active, synchronous
253 RTR active, asynchronous
Table 3.8 Subindexes for using the bit
Meaning
An overview of all values for the subindex 02h can be found in the object dictionary for the corresponding object.
The product cannot request PDOs, but it can respond to the request of PDOs.
3.4.2.1 Dynamic and static PDO mapping
Dynamic PDO mapping The settings for PDO mapping are defined in an assigned communica-
tion object for each PDO. If the PDO mapping settings for a PDO can be changed, this is referred to as dynamic PDO mapping for the PDO. Dy­namic PDO mapping enables flexible combination of different process data during operation.
Static PDO mapping Static PDO mapping means that all objects are mapped in accordance
with a fixed setting in the corresponding PDO.
Properties of the integrated drive. The integrated drive supports 2 PDOs, the communication objects
T_PDO4 and R_PDO4. These two PDO4 are enabled by default.
These PDOs are mapped statically, i.e. they cannot be configured but only read. The indexes for the permanently entered objects can be read from the PDO mapping object range:
•Object 1403
•Object 1603
•Object 1803
•Object 1A03
: receive PDO4 communication parameter
h
: receive PDO4 mapping
h
: transmit PDO4 communication parameter
h
: transmit PDO4 mapping
h
34 Fieldbus interface
IL•1F CANopen DS301 3 Basics
3.4.2.2 Receive PDO R_PDO4 (master -> slave)
The master device can execute the following actions via the PDO4 chan­nel to the slave:
Control the state machine of the slave
– Enable/disable the power stage of the product
– Trigger and reset a "Quick Stop"
– Resetting faults
Toggle the operating modes
– Profile Position operating mode, absolute and relative
– Profile Velocity operating mode
– Reference movement
– Position setting
Set reference values
– Reference position
Structure of R_PDO4:
– Reference speed
– Type of reference movement
Byte
Bit
Bit
21 43 65 87
Ref16 -> reference 16 bits - e.g. velocity
modeCtrl
driveCtrl
driveCtrl - 8 Bits
67 45 23 01 00 QR0 QSFR DIEN
Quickstop Release
modeCtrl - 8 Bits
67 45 23 01
MT ACTION 0 MODE
Ref32 -> reference 32 bits - e.g. position
Disable
Enable
Quickstop
Fault Reset
Requested Mode
Action within Mode
Mode Toggle
Figure 3.19 Structure of R_PDO4
Fieldbus interface 35
3 Basics IL•1F CANopen DS301
State machine – drivectrl
The state machine is controlled via PDO4 or the SDO object drivectrl, 28:1, in both cases via bits Bits 0 ... 4.
In PDO mode, a change form 0 to 1 triggers the corresponding function.
In the case of access via SDO, a write access with a set bit value is suf­ficient, i.e. a change of edge is not required.
Controlling the state machine PDO4Bits 0 ... 4 SDO object drivectrl, 28:1Bits 0 ... 4
Bit 0: Power stage Disable Triggered when 0 changes to 1 Triggered at write access if bit value = 1
Bit 1: Power stage Enable
Bit 2: Quickstop
Bit 3: Fault Reset
Bit 4: Quickstop Release
The value "0" is a special case: If during transmission all bits 0 ... 7 are "zero", the product interprets this as "Disable" command and disables the power stage. This applies to both PDO and SDO access.
Handling of errors If requests for controlling the state machine cannot be executed by the
product, the product ignores such request. There is no error response.
36 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Operating modes – modeCtrl
In PDO mode, the operating modes are controlled via object modeCtrl. The master must enter the following values to activate an operating mode or to change reference values:
Reference values in fields "Ref16" and "Ref32"
Select operating mode with modeCtrl, Bits 0 ... 2 (MODE)
Select action for this operating mode with modeCtrl, bits 4 ... 6
(ACTION)
Toggle modeCtrl, bit 7 (MT)
The following table shows the possible operating modes and the corre­sponding reference values:
Mode bits
0... 2
1 (JOG) 0 01h Jog 41:3 Start (as object 41:1) -
2 (REF) 0 02h Position setting 40:3 - Position for posi-
3 (PTP) 0 03h Absolute positioning 35:1 Reference speed Reference posi-
4 (VEL) 0 04h Profile Velocity 36:1 Reference speed -
1) Column corresponds to the value to be entered in byte modeCtrl, but without ModeToggle (bit 7)
2) Column shows Index:Subindex (decimal) of the corressponding operating mode objects modes which are described in more detail in the device documentation.
Action bits 4 ... 6
1 12h Reference movement 40:1 Type (as object 40:1) -
1 13h Relative positioning 35:3 Reference speed Reference posi-
2 23h Continue positioning 35:4 Reference speed -
modeCtrl
1)
. Bits 0
... 6
Description Corre-
sponds to object
Reference value Ref16 Reference
2)
value Ref32
tion setting
tion
tion
Fieldbus interface 37
3 Basics IL•1F CANopen DS301
Reference positions are entered in increments, reference speeds in
-1
[min
].
@ WARNING
UNINTENDED OPERATION
Note that any changes to the values of these parameters are exe­cuted by the drive controller immediately on receipt of the data set.
Verify that the system is free and ready for movement before changing these parameters.
Failure to follow these instructions can result in death, serious injury or equipment damage.
If operating mode, reference position and reference speed are transmit­ted simultaneously in one PDO, data consistency is required. For this reason, the product evaluates the operating mode data only if bit 7 was toggled. Toggling means that a "0 -> 1" or a "1 -> 0" change of edge was detected.
Bit 7 is mirrored in the response PDO4 from the product so that synchro­nized operation is possible via PDO4.
Handling of errors Requests for operating mode are triggered by toggling the bit 7 . If these
requests cannot be executed, the product provides an error response as described in section Transmit PDO4 - Handling of errors.
3.4.2.3 Transmit PDO T_PDO4 (product to master)
With the default product settings, the transmit PDO is sent asynchro­nously and in an "event-driven" way; an "Inhibit Time" can be set.
The product provides the master with the following information via PDO4:
State of state machine
Errors and warnings
Active operating mode
Status of active operating mode
– Operating mode terminated
– Error occurred
– Reference speed or reference position reached
– Actual position
Slave referenced
Acknowledgement of operating mode requests
Status of the 24 V inputs and outputs
38 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Structure of T_PDO4:
Byte
Bit
Bit
Bit
21 43 65 87
IO_act, 8 bits
modeStat, 8 bits
driveStat, 16 bits
driveStat
15 14 13 12 --- 8 7 6 5 3 --- 04
x err x_end x_info 0 0 0 0 0 warn Sig_SR FltSig cos0
modeStat
67 45
MEMT 0ref_ok
drive referenced
Mode Error
Mode Toggle
IO_act
67 45 23 01
STO_ASTO_B
23 01
0 mode
actual position (pact), 32 bits
actual operation mode
IO1IO2IO30
IO00
STO_A / STO_B
(PWRR_A / PWRR_B)
Figure 3.20 Structure of T_PDO4
Status word driveStat The information in the status word driveStat corresponds to bits 0
...15 of object Status.driveStat, 28:2.
Contents of information:
State of state machine
Warning and error bits
Status of the current operating mode
Fieldbus interface 39
3 Basics IL•1F CANopen DS301
Operating mode modeStat This field corresponds to bits 0 ... 2 of the object Status.xMode_act.
Bits 6 and 7 provide additional information that can be used for synchro­nized operating mode control via the PDOs.
The field contains the following information:
Bit Name Description
0...2 mode currently set operating mode as in R_PDO4
5 ref_ok Is set if homing of the product by means of a reference movement or position setting was
successful.
6 ME, ModeError Set if a request of the master via R_PDO4 data was rejected by the product.
7 MT, ModeToggle Mirrors bit 7 (Mode Toggle) of R_PDO4
3.4.2.4 Handshake with Mode Toggle Bit
Mode Toggle Synchronized processing is possible with the transmit data modeCtrl,
bit 7 (MT) and the receive data modeStat, bits 6 (ME) and 7 (MT). Syn­chronized processing means that the master waits for feedback mes­sages from the slave so it can respond appropriately.
Example of positioning The master starts a positioning movement at point in time t
time t
, t2 ..., the master checks the responses from the slave. It waits
1
for the end of the positioning movement by checking the Input Assembly for bit x_end = 1 (end of positioning).
Master Slave
t
0
t
1
t
2
Mode Toggle
1
Mode Toggle
x_end
2
Figure 3.21 Mode Toggle Handshake
3
(1) Master starts positioning with MT = 1 in byte modeCtrl (2) Slave signals that positioning is active with MT = 1 in
modeStat and simultaneously with x_end = 0 in driveStat
(4) Slave signals end of positioning with x_end = 1 in
driveStat
. At points in
0
t
3
40 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Example of short positioning The master starts a positioning movement that will only take a very short
time. The duration is shorter than the polling cycle of the master. At point in time t ter does not know whether the movement is already complete or has not yet been started. However, it detects this with the MT bit from the slave:
MasterMTSlaveMTSlave
1 0 1 Slave has not yet detected command
1 1 0 Slave has detected command, positioning
1 1 1 Slave signals that positioning is complete
The master may only evaluate data in which the received MT bit is iden­tical to the last bit transmitted by the master.
the movement is already complete. Using bit x_end, the mas-
1
x_end
running
Master Slave
t
0
t
1
t
2
Mode Toggle
1
Mode Toggle
x_end
3
2
Figure 3.22 Mode Toggle Handshake, short movement
(1) Master starts positioning with MT = 1 in byte modeCtrl (2+3) Slave signals that positioning is active with MT = 1 in
modeStat and simultaneously with x_end = 0 in driveStat
(4) Slave signals end of positioning with x_end = 1 in
driveStat
Fieldbus interface 41
3 Basics IL•1F CANopen DS301
Handling of errors If the master toggles bit 7 (MT), this is interpreted by the slave as a re-
quest to start an operating mode or to change data of the current oper­ating mode. If the request cannot be processed, the active operating mode is not changed and the slave sets bit 6 in modeStat (ME = ModeError).
The active operating mode is not changed and there is no state transi­tion.
Bit 6 (ME) remains set until the master toggles bit 7 (MT) in modeCtrl again, thus triggering a new command.
The master can read the corresponding error code by a read access to parameter ModeError.
Possible reasons for a failure of the operating mode request:
Reference values outside the value range
Change of the operating mode during processing (impossible)
Invalid operating mode requested
The device is not in state 6 (Operation Enable) of the state
machine.
For more information see the product manual.
42 Fieldbus interface
IL•1F CANopen DS301 3 Basics
3.4.2.5 Emergency service
The Emergency Service signals internal device errors via the CAN bus. The error is sent to all network devices with an EMCY object according to the "Consumer-Producer" relationship.
EMCY-Consumer
COB-ID
EMCY-Producer
Figure 3.23 Error message with the EMCY object
data
EMCY message Causes of an EMCY comprise:
asynchronous errors, error code = 1000 device error, the product switches to fault state in accordance with the device's state machine. At the same time, the product transmits an EMCY message with error register and error code.
PDO4 error during operating mode control, error code = 8200 the request for an operating mode via PDO4 fails, the product also sends an EMCY message.
CAN communication error, error code = 8100
1 2 3 4 5 6 7
81
0
22
12 00 00 00 0000 00
EMCY-Consumer
CAN
EMCY-Consumer
In the case of an internal
h
h
h
If
Manufacturer specific error field
Error register
Error code
COB-ID (80h+ Node-ID)
Figure 3.24 EMCY message
Error code
Bytes 0, 1 (error code): CANopen error codeThis value is 1000, 8200
or 8100h, depending on the cause of the error.
h
Byte 2: Error registerThe value is also stored in the object Error reg­ister, 1001
.
h
Byte 3 (Manufacturer-Specific Error Field):Manufacturer-specific error, error class
Bytes 6 and 7 are 0. Bytes 4,5 contain a manufacturer-specific error number.See the product manual for a list of the error numbers.
COB ID The COB ID for every device on the network supporting an EMCY object
is determined on the basis of the node address:
COB ID = Function code of EMCY object, 80
+ Node-Id
h
Fieldbus interface 43
0 1
12 22
22 12
h
3 Basics IL•1F CANopen DS301

3.5 Synchronization

The synchronization object SYNC controls the synchronous exchange of messages between network devices for purposes such as the simul­taneous start of multiple drives.
The data exchange conforms to the producer-consumer relationship. The SYNC object is transmitted to all devices by a network device and can be evaluated by all devices that support synchronous PDOs.
COB-ID
SYNC- Producer
Figure 3.25 SYNC message
SYNC-Consumer
SYNC-Consumer
SYNC-Consumer
CAN
Time values for synchronization Two time values define the behavior of synchronous data transmission:
The cycle time specifies the time intervals between 2 SYNC mes-
sages. It is set with the object Communication cycle
period(1006
).
h
The synchronous time window specifies the time span during which the synchronous PDO messages must be received and trnasmitted. The time window is defined with the object Synchronous window
length (1007
SYNC
).
h
T_PDO (status)
R_PDO (controller)
SYNC
CAN-Bus
synchronous
time window
cycle time
Figure 3.26 Synchronization times
process R_PDO data
Synchronous data transmission From the perspective of a SYNC recipient, in one time window the status
data is transmitted first in a T_PDO, then new control data is received via an R_PDO. However, the control data is only processed when the next SYNC message is received. The SYNC object itself does not transmit data.
44 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Cyclic ad acyclic data transmission Synchronous exchange of messages can be cyclic or acyclic.
T_PDO1: acyclical
T_PDO2: cyclical
SYNC
Figure 3.27 Cyclic and acyclic transmission
In the case of cyclic transmission, PDO messages are exchanged con­tinuously in a specified cycle, e.g. with every SYNC message.
If a synchronous PDO message is transmitted acyclically, it can be transmitted or received at any time; however, it will not be valid until the next SYNC message.
Cyclic or acyclic behavior of a PDO is specified in the subindex
transmission type (02
e.g. in the object 1st receive PDO parameter ( 1400 R_PDO1.
) of the corresponding PDO parameter,
h
:02h) for
h
COB ID, SYNC object For fast transmission, the SYNC object is transmitted unconfirmed and
with high priority.
The COB ID of the SYNC object is set to the value 128 (80
) by default.
h
The value can be changed after initialization of the network with the ob­ject COB-ID SYNC Message (1005
h
) .
Fieldbus interface 45
3 Basics IL•1F CANopen DS301

3.6 Network management services

Network management (NMT) is part of the CANopen communication profile; it is used to initialize the network and the network devices and to start, stop and monitor the network devices in network mode.
NMT services are executed in a master-slave relationship. The NMT master addresses individual NMT slaves via their node address. A mes­sage with node address "0" is directed to all NMT slaves simultaneously.
NMT-
Slave
CAN
Figure 3.28 NMT services via the master-slave relationship
The device can only take on the function of an NMT slave.
NMT services NMT services can be divided into two groups:
Services for device control, to initialize devices for CANopen com­munication and to control the behavior of devices in network mode
Services:for connection monitoring

3.6.1 NMT services for device control

NMT state machine The NMT state machine describes the initialization and states of an
NMT slave in mains operation.
NMT­Slave
COB-ID
data
NMT-
Master
NMT­Slave
NMT­Slave
NMT­Slave
Power on
Reset
Application
D
Reset
Communication
E
Initialization
Pre-Operational
Stopped
Operational
SDO, EMCY NMT
B
C
NMT
A
PDO, SDO, SYNC EMCY, NMT
Figure 3.29 NMT state machine and available communication objects
To the right, the graphic shows all communication objects that can be used in the specific network state.
46 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Initialization An NMT slave automatically runs through an initialization phase after
the supply voltage is switched on (power on) to prepare it for CAN bus operation. On completion of the initialization, the slave switches to the state "Pre-operational" and sends a boot-up message. From now on, an NMT master can control the operational behavior of an NMT slave in the network via 5 NMT services, represented in the above illustration by the letters A to E.
NMT service Transition Meaning
Start remote node (Start network node)
Stop remote node (Stop network node)
Enter Pre-Operational (Transition to "Pre-Opera­tional")
Reset node (Reset node)
Reset communication (Reset communication data)
A Transition to state "Operational"
Start normal network mode with all network devices
B Transition to state "Stopped"
Stops communication of the network device in the network. If connection mon­itoring is active, it remains on. If the power stage is active (state "Operation Enabled" or "QuickStop"), an error of error class 2 is triggered. The drive is stopped and switched off.
C Transition to "Pre-Operational"
All communication objects except for PDOs can be used.
The state "Pre-Operational" can be used for configuration by SDOs:
- PDO mapping
- Start of synchronization
- Start of connection monitoring
D Transition to state "Reset application"
Load stored data of the device profiles and automatically transition to "Pre­operational" via "Reset communication".
E Transition to state "Reset communication"
Load stored data of the communication profile and automatically switch to the state "Pre-Operational.". If the power stage is active (state "Operation Ena­bled" or "QuickStop"), an error of error class 2 is triggered. The drive is stopped and switched off.
Persistent data memory When the supply voltage is switched on (power on), the device loads the
saved object data from the non-volatile EEPROM for persistent data to the RAM.
Fieldbus interface 47
3 Basics IL•1F CANopen DS301
NMT message The NMT services for device control are transmitted as unconfirmed
messages with the COB ID = 0 . By default, they have the highest priority on the CAN bus.
The data frame of the NMT device service consists of 2 bytes.
NMT-
Master
Figure 3.30 NMT message
Byte 0 1
0
COB-ID
0001
Node-ID
Command specifier
NMT-
Slave
NMT­Slave
NMT­Slave
The first byte, the "Command specifier", indicates the NMT service used.
Command Specifier NMT service Transition
1 (01h) Start remote node A
2 (02h) Stop remote node B
128 (80
129 (81h) Reset node D
130 (82h) Reset communication E
) Enter Pre-Operational C
h
The second byte addresses the recipient of an NMT message with a node address between 1 and 127 (7F
). A message with the node ad-
h
dress "0" is directed to all NMT slaves.

3.6.2 NMT services for connection monitoring

Connection monitoring monitors the communication status of network devices, so a response to the failure of a device or an interruption in the network is possible.
Three NMT services for connection monitoring are available:
"Node guarding" for monitoring the connection of an NMT slave
"Life guarding" for monitoring the connection of an NMT master
3.6.2.1 Node/Life guarding
COB ID Communication object NMT error control (700
used for connection monitoring. The COB ID for every NMT slave is de­termined on the basis of the node address:
COB ID = function code NMTerror control (700
+node-Id) is
h
) + node-Id..
h
48 Fieldbus interface
IL•1F CANopen DS301 3 Basics
Structure of the NMT message After a request from the NMT master, the NMT slave responds with one
data byte.
Node-ID=04h
Slave
guard
time
COB-ID
...
704h
704h
704h
704h 85h
704h
704h 05h
0
05h
11
Bit 7 6 0
85h
111
000 0 0
Master
Bit 7 6
==
05h
00000 0
Figure 3.31 Acknowledgement of the NMT slave
Bits 0 to 6 identify the NMT state of the slave:
•4 (04
•5 (05
•127 (7F
): "Stopped"
h
): "Operational"
h
): "Pre-Operational"
h
After each "guard time" interval, bit 7 switches toggles between "0" and "1", so the NMT master can detect and ignore a second response within the "guard time" interval. The first request when connection monitoring is started begins with bit 7 = 0.
Connection monitoring must not be active during the initialization phase of a device. The status of bit 7 is reset as soon as the device runs though the NMT state "Reset communication".
Connection monitoring remains active in the NMT state "Stopped".
Configuration Node/Life Guarding is configured via:
Guard time (100C
Life time factor (100D
)
h
)
h
Fieldbus interface 49
3 Basics IL•1F CANopen DS301
Connection error The NMT master signals a connection error to the master program if:
the slave does not respond within the "guard time" period
the NMT state of the slave has changed without a request by the NMT master.
Figure 3.32 shows an error message after the end of the third cycle be­cause of a missing response from an NMT slave.
request
guard
time
Master
message
response
request
response
request
no
response
Slave
life
time
Figure 3.32 "Node Guarding" and "Life Guarding" with time intervals
Boot-up message The communication profile DS 301, version 4.0, defines an additional
task for the NMT services: sending a boot-up message.
A network device informs all other network devices that it is ready for op­eration using a boot-up message.
A boot-up message consists of the COB ID of the NMT object NMT Er- ror Control and is transmitted without data. The default setting of the COB ID is 1792 (700h) + node-Id
50 Fieldbus interface

IL•1F CANopen DS301 4 Installation

4 Installation
@ WARNING
LOSS OF CONTROL
The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are EMERGENCY STOP, overtravel stop, power outage and restart.
Separate or redundant control paths must be provided for critical functions.
System control paths may include communication links. Consid­eration must be given to the implication of unanticipated transmis­sion delays or failures of the link.
Observe the accident prevention regulations and local safety guidelines.
Each implementation of the product must be individually and thor­oughly tested for proper operation before being placed into serv­ice.
Failure to follow these instructions can result in death or serious injury.
1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation for Construction and Operation of Adjustable­Speed Drive Systems.
1)
@ WARNING
SIGNAL AND DEVICE INTERFERENCE
Signal interference can cause unexpected responses of device.
Install the wiring in accordance with the EMC requirements.
Verify compliance with the EMC requirements.
Failure to follow these instructions can result in death, serious injury or equipment damage.
For information on installation of the device and connecting the device to the fieldbus see the product manual.
Slave withDIP switches Before installing the slave in the system, you must set the network ad-
dress and the baud rate via the DIP switches in the connector housing.
See the chapter "Installation" in the product manual for information on the DIP switch settings.
Fieldbus interface 51
4 Installation IL•1F CANopen DS301
52 Fieldbus interface

IL•1F CANopen DS301 5 Commissioning

5 Commissioning
@ DANGER
UNINTENDED CONSEQUENCES OF EQUIPMENT OPERATION
When the system is started, the drives are usually out of the opera­tor's view and cannot be visually monitored.
Only start the system if there are no persons in the hazardous area.
Failure to follow these instructions will result in death or serious injury.
@ WARNING
UNINTENDED OPERATION
Do not write values to reserved parameters.
Do not write values to parameters unless you fully understand the function. For more information see the product manual.
Run initial tests without coupled loads.
Verify that the system is free and ready for the movement before changing parameters.
Verify the use of the bits with fieldbus communication: bit 0 is far right (least significant). Bit 15 is far left (most significant).
Verify the use of the word sequence with fieldbus communication.
Do not establish a fieldbus connection unless you have fully understood all communications principles.
Failure to follow these instructions can result in death, serious injury or equipment damage.

5.1 Commissioning the device

For installation in the network, the device must first be properly installed (mechanically and electrically) and commissioned.
Commission the device as per product manual. This prepares the device for operation in the network.
Fieldbus interface 53
5 Commissioning IL•1F CANopen DS301

5.2 Address and baud rate

Up to 32 devices can be addressed in one CAN bus network branch and up to 127 devices in the extended network. Each device is identified by a unique address. The default node address for a device is 127.
The default baud rate is 125 kbaud.
Each device must be assigned its own node address, i.e. any given node address may be assigned only once in the network.
Setting address and baud rate The address is set directly at the device via parameter canAddr and the
baud rate via parameter canBaud.
The baud rate must be the same for all devices in the fieldbus.

5.3 Commissioning the fieldbus network

5.3.1 Starting fieldbus mode

Configuration with SyCon Note on using the Hilscher configuration software SyCon:
Testing fieldbus operation After correct configuration of the transmission data, test fieldbus opera-
Do not change the setting Geräteprofil (value = 0) in the Knotenkonfiguration dialog box!
If this value is changed, communication with the drive will no longer work. However, the setting cannot be reset to the initial value.
To restore communication with the product:
Click the Knoten BootUp button in the Knotenkonfiguration
dialog box.
Click Prüfe Knoten Type and Profile in the Knoten Auf-
schaltreihenfolge dialog to skip this step.
tion.
This requires installation of a CAN configuration tool that displays CAN messages. The acknowledgement from the product is indicated by a boot-up message:
Switch the power supply of the product off and on again.
Observe the network messages shortly after switching on the
device. The positioning controller sends a 1 byte boot-up message after initialization of the bus: 128 (80
)+node-Id.
h
With the node address factory-set to 127 (7F (FF
) is transmitted via the bus. The drive can then be put into operation
h
via NMT services.
54 Fieldbus interface
), boot-up message 255
h
IL•1F CANopen DS301 5 Commissioning

5.3.2 Troubleshooting

Check the following settings if the slave does not respond:
Did you start the slave and switch on the master?
Are all cable connections ok (electrically and mechanically)?
Did you set the correct address at the slave? Check the DIP switch
and HEX switch settings. The settings are described in the product manual. Products without DIP switches have the following default settings: CAN address 127 (7F can change these settings via CAN itself or by means of the PC commissioning tool via the RS 485 interface.
Did you set the same baud rate and the same interface parameters
for the master and the slave?
If the slave still does not respond:
Open the cover of the connector housing.
When a slave works properly with the power stage disabled, the
LED in the connector housing flashes constantly at 0.5 Hz (1 sec­ond on, 1 second off). If this is not the case, the product is inopera­tive. See the product manual for information on errors and troubleshooting.
) and baud rate 125 [kBit/s]. You
h
Compare the behavior of LED with the information in the table
below.
Error Error class Cause of error Troubleshooting
LED off No supply voltage. Check supply voltage and fuses.
LED flashes at 0.5 Hz(1 s on, 1 s off)
LED flashes at 6 Hz. 4 Incorrect flash checksum. Reinstall firmware. Replace slave.
LED flashes at 10 Hz. Watchdog
.– Firmware works without errors,
power stage disabled.
4 Hardware error Switch slave off and on again.
Check cable connections. Check DIP switch settings.
Replace slave.
See the product manual for additional information on the cause of errors and on troubleshooting.
Fieldbus interface 55
5 Commissioning IL•1F CANopen DS301

5.4 SyCon CANopen configuration software

The CANopen network can be configured with the "SyCon" configura­tion software. An additional EDS file is included in the SYCON subdirec­tory on the product CD.
Procedure:

5.4.1 Creating a new network

Create a new network via the menu item "File - New".
Select CANopen as the fieldbus network.
Confirm your selection with "OK".

5.4.2 Selecting the CANopen master

Use the menu item "Insert - Master" to select the network master. The screenshot shows the example of a TSX CCP 110 board of a Premium PLC.
The node ID and a brief description can be entered in the appropriate fields.
Confirm your selection with "OK".
56 Fieldbus interface
IL•1F CANopen DS301 5 Commissioning

5.4.3 Setting the bus parameters

The menu item "Settings - Bus Parameter..." allows you to set the CAN­open communication parameters. Please also consult the operating in­structions of the SyCon configuration software.
Confirm your selection with "OK".
Fieldbus interface 57
5 Commissioning IL•1F CANopen DS301

5.4.4 Selecting and inserting nodes

Use the menu item "Insert - Node" to select the network nodes. The ex­ample shows a Lexium 05.
Confirm your selection with "OK".
58 Fieldbus interface

IL•1F CANopen DS301 6 Operation

6 Operation
@ WARNING
UNINTENDED OPERATION
Do not write values to reserved parameters.
Do not write values to parameters unless you fully understand the function. For more information see the product manual.
Run initial tests without coupled loads.
Verify that the system is free and ready for the movement before changing parameters.
Verify the use of the bits with fieldbus communication: bit 0 is far right (least significant). Bit 15 is far left (most significant).
Verify the use of the word sequence with fieldbus communication.
Do not establish a fieldbus connection unless you have fully understood all communications principles.
Failure to follow these instructions can result in death, serious injury or equipment damage.

6.1 Overview

The programming examples show hands-on applications for network operation. There are 2 access methods via the CANopen fieldbus: SDO "Service Data Objects" and PDO "Process Data Objects".
Using SDOs An SDO access is a write or a read access to an individual object. The
available objects are described in the product manual and also summa­rized in a table in the chapter "Parameters". This chapter describes the use of SDOs on the basis of just a small number of objects since this type of communication can be used with all available objects and the structure is very similar in all cases.
Using PDOs PDOs are recommended for positioning mode because the information
is transmitted much more efficiently. The chapter provides various hands-on examples of the application of PDO4 supported by the product and describes the general procedure.
The PDO from the master to the product is referred to as "R_PDO".
The PDO from the product to the master is referred to as "T_PDO".
Fieldbus interface 59
6 Operation IL•1F CANopen DS301
Structure of the examples The PDOs are described from the perspective of the slave:
The examples describe:
•Task
Initial conditions
Required commands in the transmit data frame
Response of the product in the receive data frame
Possible restrictions for command execution.
You should be familiar with the following to be able to understand the ex­amples:
Operating concept and functionality of the product. For more infor­mation see the product manual.
Fieldbus protocol and connection to the master controller
Functionality of the fieldbus profile.
Product manual The examples are intended to supplement the function descriptions in
the product manuals. The basic function principles of the operating modes and functions are described in the product manual.
All parameters for the operating modes and functions are also listed in the product manual.
See table 9.2, page 9-1 in the device manual for a description of the number format of the parameter values in a fieldbus command.
60 Fieldbus interface
IL•1F CANopen DS301 6 Operation

6.2 Using SDO commands

6.2.1 Writing parameters

Ta sk The parameter Motion.acc, 29:26 (acceleration) is to be set to a value
of 10,000.
Index and subindex must be converted to hexadecimal notation and the constant 3000
Index:29 = 1D
Subindex: 26 = 1A
Value:10000 = 00002710
The value 23h is to be entered as a CCD (Client Command Specifier) since the parameter has a 32 bit data type.
Transmit data
Object COB ID CCD Idx Sdx Data Description
Tx 301D
:1Ah Motion.acc 600h+ID 23h1Dh 30h1A
h
added to the index for the SDO access:
h
+ 3000h = 301D
h
h
h
10h 27h 00 00 Sets the acceleration to
h
h
10000 min value
-1
*s = 2710h as a 32 bit
Refer to the column "Data type" in the parameter description for the data type of the value to be written. The CAN protocol used transmits 16 bit values and 32 bit values in the format "lowest value byte first – highest value byte last". When an INT16 or a UINT16 value is transmitted, the CCD corresponding to the data type must be included. The value must be stored in the first two data bytes, the last two data bytes must be "0".
Receive data
Object COB ID CCD Idx Sdx Data Description
Rx 301D
:1Ah Motion.acc 580h+ID 60h1Dh 30h1A
h
h
XX XX XX XX The response data does not have
a meaning.
Fieldbus interface 61
6 Operation IL•1F CANopen DS301

6.2.2 Reading a parameter

Ta sk The parameter Status.n_act, 31:9 (actual speed) is to be read.
Index and subindex must be converted to hexadecimal notation and the constant 3000
Index:31 = 1F
Subindex 9 = 09
The value "40h" must be entered as the CCD. This value identifies a "Read Request".
Tra ns mi t d at a
Object COB ID CCD Idx Sdx Data Description
Tx 301Fh:09h Sta­tus.n_actT
600h+ID 40h1Fh 30h09
The 4 data bytes have no significance for a read request.
Receive data
added to the index for the SDO access:
h
+ 3000h = 301F
h
h
h
XX XX XX XX Reads the actual speed. The data
h
has no significance.
Object COB ID CCD Idx Sdx Data Description
Rx 301D
:09h Status.n_act 580h+ID 43h1Fh 30h09
h
h
E8 03 00 00 The data 000003E8 corresponds
to 1000 min
The product transmits the data as 32 bit values back to the master (CCD is "43
"). It also sends back data as a 32 bit value which are described
h
as INT16 or UINT16 data types in the product manual. When an INT16 or a UINT16 value is read, it is therefore possible to evaluate all 4 data bytes. However, for 16 bit data it is also correct to evaluate only the first two data bytes and to ignore the last two data bytes.

6.2.3 Synchronous errors

Receive data with error frame "Error
Response"
Object COB ID CCD Index Sub Data Description
Rx 3028h:20
h
580h+ID 80h28h 30h20
If an SDO write or read command fails, the product responds with an er­ror frame "Error Response". This may happen if, for example, you try to read or write a non-existent object. The transmitted error number pro­vides information on the exact cause.
h
00 00 02 06 Error value 06020000h means
"object does not exist in object dic­tionary"
The example shows the response to a write or read request for a non­existent object 40:32.
-1
.
The error number of a synchronous error message is stored as a UINT16 value and the corresponding CCD (Error Response) is as­signed the value 80
. Refer to 7.3.2 "Error code table" for a table with the
h
error numbers.
62 Fieldbus interface
IL•1F CANopen DS301 6 Operation

6.3 Changing operating states with PDO4

The product operates in different operating states. The individual oper­ating states are numbered from 1 to 9 . The operating states and the transition conditions are described in more detail in the product manual, chapters "Basics" and "Operation".
Operating state
4 Ready To Switch On off Passive operating state,
6 Operation Enable on Active operating state, current
7 Quick Stop active on Fault state, power stage
9 Fault off Fault state, power stage is
Table 6.1 Important operating states
Name Power
stage
Description
motor without current
available to motor
remains enabled
disabled
Requests for switching operating states are transmitted to the product in R_PDO4 in the field drivectrl. The product signals the current oper­ating state back to the master in T_PDO4, field driveStat.
Table 6.2 shows the bit assignment of the field drivectrl in the object R_PDO4:
Bit no. Value Meaning
001
102
204
308
410
h
h
h
h
h
Disable
Enable
Quick Stop
Fault Reset
Quick Stop release
Table 6.2 R_PDO4, drivectrl, bit assignment
Fieldbus interface 63
6 Operation IL•1F CANopen DS301

6.3.1 Switching the power stage on and off

The power stage is enabled by the transition from operating state 4 to 6 . For this purpose, the two bits Enable and Disable are available in the R_PDO4. One of them must be "1", the other "0".
Enabling the power stage Prerequisite: the product in in operating state 4.
To enable the power stage, a "0 -> 1" edge must be generated in drivectrl, bit 1 (Enable). This can be done by deleting bit 0 (Disable) and setting bit 1 . The master then waits until the product signals oper­ating state 6 . This may take a while (approx. 1 second) since various tests are run when the power stage is enabled.
Example
Master <---> Slave
Disable is requested ---> drivectrl01
Slave signals operating state 4
Request Enable ---> drivectrl02
Slave signals operating state 5
Slave signals operating state 6
<--- driveStat XXX4
<--- driveStat XXX5
<--- driveStat XXX6
h
h
h
h
h
Disabling the power stage Prerequisite: Product is in operating state 6 or 7.
To disable the power stage, a "0 -> 1" edge must be generated in drivec­trl, bit 0 (Disable). This can be done by setting Bit 0 (Disable) and de­leting bit 1 (Enable). The product switches to operating state 4.
Example
Enable is requested ---> drivectrl 02
Slave signals operating state 6
Request disable ---> drivectrl 01
Slave signals operating state 4

6.3.2 Triggering a "Quick Stop"

A running motion command can be interrupted via the fieldbus at any time with the Quick Stop command. The stop is triggered by a "0 -> 1" edge in drivectrl, bit 2. After the state transition to operating state 7 (Quick Stop), the product decelerates with the set EMERGENCY STOP ramp and comes to a standstill.
In order to start a new motion command, you must first set the product to operating state 6 . To achieve this, do one of the following:
Master <---> Slave
h
<--- driveStat XXX6
h
<--- driveStat XXX4
h
h
Fault Reset"0 -> 1" edge in drivectrl, bit 3
Quick Stop release"0 -> 1" edge in drivectrl , bit 4
64 Fieldbus interface
IL•1F CANopen DS301 6 Operation
Example
Master <---> Slave
"Enable" is requested ---> drivectrl 02
Slave signals operating
<--- driveStat XXX6
state 6
request "Quick Stop" and
---> drivectrl 06
"Enable"
Slave signals operating
<--- driveStat XXX7
state 7
Wait until the product has
---> come to a standstill and the system is to resume opera­tion
Request "Quick Stop
<--- drivectrl 12
Release" and "Enable"
Slave signals operating
---> driveStat XXX6 state 6
Cancel "Quick Stop
<--- drivectrl 02
Release"
h
h
h
h
h
h
h
Fieldbus interface 65
6 Operation IL•1F CANopen DS301

6.3.3 Resetting faults

If an error occurs during operation, the product switches to operating state 7 "Quick Stop" or operating state 9 "Fault", depending on the type of error.
After having remedied the cause of the fault, you can reset the error state with a Fault Reset ("0 -> 1" edge in drivectrl, bit 3).
If the product was originally in operating state 7, it will switch to operating state 6 after the "Fault Reset".
If the product was originally in operating state 9, it will switch to operating state 4 after the "Fault Reset". You then have to transmit a "0 -> 1" edge in drivectrl, bit 1 "Enable", in order to enable the power stage.
Example
Master <---> Slave
Request Enable ---> drivectrl 02
Slave signals operating state 9 (Fault)
Remedy cause of error
Request "Fault Reset" ---> drivectrl 08
Slave signals operating state 4
Request "Enable" ---> drivectrl 02
Slave signals operating state 5
Slave signals operating state 6
<--- driveStat XXX9
<--- driveStat XXX4
<--- driveStat XXX5
<--- driveStatXXXX6
h
h
h
h
h
h
h
Table 6.3 Disabling the power stage
Note: In this example, the master deletes the Bit 1"Enable" during the "Fault Reset" in order to implicitly effect a "0 -> 1" edge in Bit 1. This switches the product back to operating state 6.
66 Fieldbus interface
IL•1F CANopen DS301 6 Operation

6.4 Examples for the operating modes with PDO4

R_PDO4 With the R_PDO4 you can start motion commands and change them
while they are being processed. R_PDO4 provides three fields for these purposes:
modeCtrl Starting and changing operating modes
"Ref16" and "Ref32" Operating mode-dependent reference values
The specified values for these three fields are not taken over by the prod­uct until modeCtrl, bit 7 (ModeToggle) changes.
Proceed as follows to assign values to the product:
Enter the desired operating mode and the corresponding values in
the fields modeCtrl, "Ref16" or "Ref32".
Change modeCtrl, bit 7 (ModeToggle)
This avoids consistency problems within the R_PDO4.
T_PDO4 T_PDO4 allows you to monitor motion commands.
T_PDO4 provides three fields for this purpose:
modeStat For Handshake purposes
driveStat Signals motion status and errors
p_actActual position of the product
ModeToggle The bit ModeToggle is available in the R_PDO4 and in the T_PDO4. The
master provides this bit in the and the product mirrors is in the . This pro­cedure allows the master to detect whether the data transmitted by the slave is current.
Example The master starts a positioning movement that will only take a very short
time. The master waits for the end of the positioning movement by checking T_PDO4 for bit x_end = 1 (positioning end).
The master may receive data from the slave that still originate from a point in time before the positioning movement was started. This data also contains x_end = 1. The master detects that the data is obsolete because the included bit ModeToggle does not match that of its motion command.
The master may only evaluate data in which the received ModeToggle bit is identical to the last bit transmitted by the master.
Acceleration Prior to positioning, you can first set the desired acceleration with an
SDO access (object Motion.acc, 29:26). Note that the acceleration can only be changed when the product is at a standstill.
Assumptions The examples in this chapter are based on the following assumptions:
Operating state 6 "Operation Enable"
Homing has not yet been performed (bit ref_ok = 0)
p_act = 0 (actual position)
R_PDO4: modeCtrl, Bit 7 = 0 (ModeToggle)
Fieldbus interface 67
6 Operation IL•1F CANopen DS301

6.4.1 Operating mode Profile Position: absolute positioning

To start an absolute positioning movement, the following settings must be made in the R_PDO4:
Enter the reference speed in "Ref16" and the target position in
"Ref32".
Enter operating mode 03
lute positioning) in the field modeCtrl.
Change modeCtrl, bit 7, so the data is taken over by the product.
Example Absolute positioniing to position 100,000 (000186A0
at a reference speed of 1000 min
Master <---> Slave
Triggering positioning R_PDO4 ---> drivectrl
02
h
Positioning runningx_err = 0, x_end = 0
Positioning completex_err = 0, x_end = 1, x_info = 1
T_PDO4 <--- driveStat
0006
h
T_PDO4 <--- driveStat
6006
h
Table 6.4 Operating mode Profile Position, absolute positioning at constant ref-
erence speed
Note: The data frame "positioning running" can be sent several times; the current actual position is contained in the field p_act.
Example As the above example, but the reference speed is changed to 2000 min
1
(07D0h) during the movement.
(Profile Position operating mode, abso-
h
)
h
-1
(03E8h)
modeCtrl 83
h
modeStat 83
h
modeStat 83
h
Ref16 03E8
h
Ref32 000186A0
p_act XXXXXXXX
p_act 000186A0
h
h
h
-
Master <---> Slave
Triggering positioning R_PDO4 ---> drivectrl
02
h
Positioning runningx_err = 0, x_end = 0
T_PDO4 <--- driveStat
0006
h
Change reference speed R_PDO4 ---> drivectrl
02
h
Positioning runningx_err = 0, x_end = 0
Positioning complete x_err=0, x_end = 1, x_info = 1
T_PDO4 <--- driveStat
0006
h
T_PDO4 <--- driveStat
6006
h
Table 6.5 Operating mode Profile Position, absolute positioning with change of
reference speed
Note: The data frame "positioning running" can be sent several times. The current actual position is contained in the field p_act. When the ref­erence speed is changed, the same target position is sent because it does not change in this example.
modeCtrl 83
h
modeStat 83
h
modeCtrl 03
h
modeStat 03
h
modeStat 03
h
Ref16 03E8
Ref16 07D0
h
h
Ref32 000186A0
p_act XXXXXXXX
Ref32 000186A0
p_act XXXXXXXX
p_act 000186A0
h
h
h
h
h
68 Fieldbus interface
IL•1F CANopen DS301 6 Operation

6.4.2 Operating mode Profile Position: relative positioning

Relative positioning is similar to absolute positioning. You only need to enter the value 13 tioning) in field modeCtrl. Also note that several target positions trans­mitted in succession are added up.
(operating mode Profile Positioning, relative posi-
h
Example: Relative positioning by 100,000 (000186A0
1000 min
-1
(03E8h)
During the movement, the speed is to be changed to 2000 min (07D0
Triggering positioning R_PDO4 ---> drivectrl
Positioning runningx_err = 0, x_end = 0
Change reference speed Trans­mit relative postion "0"
Positioning runningx_err = 0, x_end = 0
Positioning completex_err = 0, x_end = 1, x_info = 1
T_PDO4 <--- driveStat
R_PDO4 ---> drivectrl
T_PDO4 <--- driveStat
T_PDO4 <--- driveStat
Table 6.6 Profile Position operating mode, relative positioning with change of
).
h
Master <---> Slave
reference speed
02
h
0006
02
h
0006
6006
h
h
h
Note: The data frame "positioning" running can be sent several times; the current actual position is contained in the field p_act. When the ref­erence speed is changed, the value "0" must be sent as the new target position because the new value is added to the previously calculated tar­get position.
modeCtrl 93
h
modeStat 83
h
modeCtrl 13
h
modeStat 03
h
modeStat 03
h
) increments at a speed of
h
-1
Ref16 03E8
h
Ref32 000186A0
h
p_act
Ref16 07D0
h
XXXXXXXX
Ref32 00000000
h
h
p_act XXXXXXXX
h
p_act 000186A0
h

6.4.3 Operating mode Profile Velocity

In Profile Velocity operating mode, a reference speed for the motor is set and a movement without a target position is started.
To start the Profile Velocity operating mode or to change the reference speed in Profile Velocity operating mode, you must make the following settings in R_PDO4:
Enter the reference speed in Ref16t. (Ref32 has no significance
here)
Enter the operating mode 04
modeCtrl.
Toggle modeCtrl, bit 7, so the data is taken over by the slave.
Fieldbus interface 69
(operating mode Profile Velocity) in
h
6 Operation IL•1F CANopen DS301
Start Profile Velocity operating mode with 1000 min
-1
Product accelerates xerr=0, xend=0, xinfo=0
Reference speed reached xerr=0, xend=0, xinfo=1
Change speed to 2000 min
-1
Product accelerates xerr=0, xend=0, xinfo=0
Reference speed reached xerr=0, xend=0, xinfo=1
Change speed to 0 min
-1
Product decelerates xerr=0, xend=0, xinfo=0
Profile Vel. mode terminated xerr=0, xend=1, xinfo=1
Example The Profile Velocity operating mode is started with a reference speed of
1000 min
The reference speed is changed to 2000 min
-1
(03E8h).
-1
(07D0h) during the
movement.
Master <---> Slave
R_PDO4 ---> drivectrl
02
h
T_PDO4 <--- driveStat
0006
T_PDO4 <--- driveStat
2006
R_PDO4 ---> drivectrl
02
h
T_PDO4 <--- driveStat
0006
T_PDO4 <--- driveStat
2006
R_PDO4 ---> drivectrl
02
h
T_PDO4 <--- driveStat
0006
T_PDO4 <--- driveStat
6006
h
h
h
h
h
h
modeCtrl 84
h
modeStat 84
h
modeStat 84
h
modeCtrl 04
h
modeStat 04
h
modeStat 04
h
modeCtrl 84
h
modeStat 84
h
modeStat 84
h
Ref16 03E8
Ref16 07D0
Ref16 0000
h
h
h
Ref32 XXXXXXXX
p_act XXXXXXXX
p_act XXXXXXXX
Ref32 XXXXXXXX
p_act XXXXXXXX
p_act XXXXXXXX
Ref32 XXXXXXXX
p_act XXXXXXXX
p_act XXXXXXXX
h
h
h
h
h
h
h
h
h
The Profile Velocity operating mode is terminated when the reference speed "0" is transmitted; standstill is waited for.
Note: The field p_act of the T_PDO4 contains the current position of the drive in increments.

6.4.4 Position setting

During position setting, a new position is assigned to the current motor position. This only shifts the coordinate system, the motor itself does not move.
You must make the following settings for position setting in the R_PDO4:
Enter the new position in Ref32. (Ref16 has no significance here)
Enter operating mode 02 ting").
Toggle modeCtrl, bit 7, so the data is taken over by the slave.
Example: The motor is at position -100,000 (FFFE7960
Position 200,000 is assigned to the motor (00030D40
Master <---> Slave
Product signals position-100,000 T_PDO4 <--- driveStat
XXXX
Position setting to 200,000 R_PDO4 ---> drivectrl
02
Position taken over x_err = 0, x_end = 1, x_info = 0
T_PDO4 <--- driveStat
4006
70 Fieldbus interface
in modeCtrl ("Homing", "Position Set-
h
).
h
).
h
modeStat XX
h
h
h
modeCtrl 82
h
Ref16 XXXX
modeStat A2
h
h
h
p_act FFFE7960
Ref32 00030D40
p_act 00030D40
h
h
h
IL•1F CANopen DS301 6 Operation

6.4.5 Operating mode Homing

During the reference movement a limit switch or reference switch is ap­proached and then a new value is assigned to this position.
Before a reference movement is started, the parameters must be set by means of SDO write access to satisfy the requirements. See the product manual for detailed information on parameterization and on performing a reference movement.
To start a reference movement the following settings must be made in the R_PDO4:
Enter the type of reference movement in Ref16 (Ref32 has no sig-
nificance here).
The available types of reference movement are described in the device manual.
•In modeCtrl, enter operating mode 12
Toggle modeCtrl, bit 7, so the data is taken over by the slave.
Example A reference movement to the negative limit switch (LIMN) is to be per-
formed; this is reference movement type 2.
Master <---> Slave
Trigger reference movement R_PDO4 ---> drivectrl
Reference movement runningx­err=0, xend=0
Reference movement complete xerr=0, xend=1
T_PDO4 <--- driveStat
T_PDO4 <--- driveStat
Table 6.7 Reference movement
02
h
0006
4006
h
h
modeCtrl 92
h
modeStat8 2
h
modeStat A2
h
"Homing".
h
Ref16 0002
h
Ref32 XXXXXXXX
p_act XXXXXXXX
p_act 00000000
h
h
h
Fieldbus interface 71
6 Operation IL•1F CANopen DS301

6.5 Error signaling via PDO4

6.5.1 Synchronous errors

If a request for an operating mode sent via R_PDO4 cannot be proc­essed by the product, the product rejects processing and sets modeStat, bit 6 ("ModeError") in the T_PDO4. This does not interrupt the current process. To determine the cause of the error, the master can read the error number from the object CAN.modeError, 30:11 with an SDO access.
Example The product rotates in Profile Velocity operating mode.
Master <---> Slave
Profile Velocity operating modex_end = 0
Request: Dimension setting to 0 R_PDO4 ---> drivectrl
Request rejected "ModeError" = 1T_PDO4 <--- driveStat
T_PDO4 <--- driveStat
0006
h
02
h
0006
h
modeStat 04
h
modeCtrl 82
h
modeStat C4
h
Ref16 XXXX
h
p_act XXXXXXXX
Ref32 00000000
p_act XXXXXXXXh
h
h

6.5.2 Asynchronous errors

Table 6.8 Synchronous error, invalid operating mode request
NOTE: When the request for position setting is rejected, the product continues to run in Profile Velocity operating mode; there is no change.
However, the product sends an EMCY message with the corresponding error number to the master .
Asynchronous errors are triggered by internal monitoring (e.g. temper­ature) or by external monitoring (e.g. limit switch). If an asynchronous er­ror occurs, the product responds by braking or by disabling the power stage.
Asynchronous errors are indicated in the following way:
Change to operating state 7 "Quick Stop" or to operating state 9 "Fault".
The change is represented in T_PDO4, driveStat, bits 0 ... 3.
Setting of driveStat, bit 5 (fault detected by internal monitoring) or driveStat, bit 6 (fault detected by internal monitoring)
In the event of an error message by internal monitoring:
Setting of the bit corresponding to the fault in object Status.FltSig_SR, 28:18.
In the event of an error message by external monitoring:Setting of the bit corresponding to the fault in object Status.Sign_SR, 28:15
In addition, an error number is assigned to each error. In the event of an asynchronous error, the corresponding error number can be read from the object Status.StopFault (32:7).
72 Fieldbus interface
IL•1F CANopen DS301 6 Operation
Example: External monitoring triggers a fault message; positive limit switch "LIMP"
was hit.
Master <---> Slave
Positioning running xerr=0, xend=0
Limit switch detected xerr=1, xend=0
Motor stopped xerr=1, xend=1 T_PDO4 <--- driveStat
T_PDO4 <--- driveStat
0006
h
T_PDO4 <--- driveStat
8047
h
C047
h
Table 6.9 Asynchronous error, triggering of an external
Note: When the limit switch is detected, the motor is decelerated with the EMERGENCY STOP ramp until it comes to a standstill and the bit x_err is set. After the motor has come to a standstill, bit x_end is set.
modeStat 03
h
modeStat 03
h
modeStat 03
h
p_act XXXXXXXX
p_act XXXXXXXX
p_act XXXXXXXX
h
h
h
Fieldbus interface 73
6 Operation IL•1F CANopen DS301
74 Fieldbus interface

IL•1F CANopen DS301 7 Diagnostics and troubleshooting

7 Diagnostics and troubleshooting

7.1 Fieldbus communication error diagnostics

A properly operating fieldbus is essential for evaluating operating and er­ror messages.
Connections for fieldbus mode If the product cannot be addressed via the fieldbus, first check the con-
nections. The product manual contains the technical data of the device and information on network and device installation. Check the following:
•24V
Power connections to the device
Fieldbus cable and fieldbus wiring
Network connection to the device
You can also use the commissioning software for troubleshooting.
Baud rate and address If it is impossible to connect to a device, check the baud rate and node
address.
The baud rate must be the same for all devices in the network.
The node address of each device must be between 1 and 127 and
To set the baud rate and node address see chapter 5.2 "Address and baud rate".
Fieldbus function test After correct configuration of the transmission data, test fieldbus mode.
This requires installation of a CAN configuration tool that displays CAN messages. Feedback from the product is indicated by a boot-up mes­sage:
Switch the power supply off and on again.
Observe the network messages after switching on. After initializa-
With the factory setting 127 (7F
If network operation cannot be started, the network function of the device must be checked by your local representative. Contact your local sales representative.
power supply
dc
unique for each device.
tion of the bus, the device sends a boot-up message (COB ID 700 + node ID and 1 data byte with the content 00
) for the node address, the boot-up message is sent via the bus . The device can then be put into oper­ation via NMT services.
h
).
h
h
Fieldbus interface 75
7 Diagnostics and troubleshooting IL•1F CANopen DS301

7.2 Error diagnostics via fieldbus

7.2.1 Message objects

A number of objects provide information on the operating and error state:
•Object Statusword (6041
Operating states, see product manual
•Object EMCY (80
Error message from a device with fault state and error code, see chapter 3.4.2.5 "Emergency service"
•Object Error register (1001
Fault state
•Object Error code (603F
Error code of the most recent error
Devices use the special SDO error message ABORT to signal errors in exchanging messages by SDO.

7.2.2 Messages on the device status

Synchronous and asynchronous errors are distinguished in the evalua­tion and handling of errors.
Synchronous errors The device signals a synchronous error directly as a response to a mes-
sage that cannot be evaluated. Possible causes comprise transmission errors or invalid data. For a list of synchronous errors see chapter 7.3.1 "Error register".
Asynchronous errors Asynchronous errors are signaled by the monitoring units in the device
as soon as a device fault occurs. An asynchronous error is signal via bit 3, "Fault", of the object statusword (6041 that cause a an interruption of the movement, the device transmits an EMCY message.
h
+ Node-ID)
h
h
)
)
h
)
). In the case of errors
h
Asynchronous errors are also reported via bits 5..7 of the object
driveStat (2041
).
h
76 Fieldbus interface
IL•1F CANopen DS301 7 Diagnostics and troubleshooting

7.3 CANopen error messages

CANopen error messages are signaled in the form of EMCY messages.

7.3.1 Error register

They are evaluated via the objects Error register (1001 Error code (603F
). For information on the object EMCY see chapter
h
3.4.2.5 "Emergency service".
CANopen signals errors that occur during data exchange via SDO with the special SDO error message ABORT.
The object Error register(1001h) indicates the error state of a de­vice in bit-coded form. The exact cause of error must be determined with the error code table. Bit 0 is set as soon as an error occurs.
Bit Message Meaning
0 Generic error An error has occurred
1- reserved
2- reserved
3- reserved
4 Communication Network communication error
5 Device profile-specific Error in execution as per device profile
6- reserved
7 Manufacturer-specific Vendor-specific error message
) and
h

7.3.2 Error code table

The error code is evaluated with the object error code (603Fh), an object of the DSP402 device profile, and output as a four-digit hexadec­imal value. The error code indicates the cause of the last interruption of movement. See the Troubleshooting chapter of the product manual for the meaning of the error code.
Fieldbus interface 77
7 Diagnostics and troubleshooting IL•1F CANopen DS301

7.3.3 SDO error message ABORT

An SDO error message is generated as a response to an SDO trans­mission error. The cause of error is contained in error code, byte 4 to byte 7.
Client
COB-ID
ccd:
ccd
80
Idx
2 3 4 5 6 70
1
Idx
Sidx
1
2
data
error response
Server
Byte 4-7 error code
Figure 7.1 SDO error message as a response to an SDO message
The table below shows all error messages that may occur during data exchange with the product.
Error code Meaning
0504 0000
0504 0001
0601 0000
0601 0001
0601 0002
0602 0000
0604 0041
0604 0042
0607 0010
0607 0012
0607 0013
0609 0011
0609 0030
0609 0031
0609 0032
0800 0000
0800 0022
Time-out during SDO transfer
h
Command specifier CS incorrect or unknown
h
Access to object impossible
h
No read access, because write-only object (wo)
h
No write access, because read object (ro)
h
Object does not exist in object dictionary
h
Object does not support PDO mapping
h
PDO mapping: number or length of objects exceed the byte
h
length of the PDO
Data type and parameter length do not match
h
Data type does not match, parameter too long
h
Data type does not match, parameter too short
h
Subindex not supported
h
Value range of parameter too large (relevant only for write
h
access)
Parameter values too great
h
Parameter values too small
h
General error
h
Device status keeps data from being transmitted and saved.
h
78 Fieldbus interface

IL•1F CANopen DS301 8 Object directory

8 Object directory

8.1 Overview

This object dictionary only describes the protocol for the product as per CANopen DS 301. The objects for controlling operating modes, func­tions and all parameters can be found in the product manual for the prod­uct.

8.1.1 Specifications for the objects

Index The index specifies the position of the object in the object dictionary. The
index value is specified as a hexadecimal value.
Object code The object code specifies the data structure of the object.
Object code Meaning Coding
VAR A single value, for example of the type
Integer8, Unsigned32 or Visible String8.
ARR (ARRAY) A data field in which every entry is of the
same data type.
REC (RECORD) A data field that contains entries that are
a combination of single data types.
7
8
9
Data type Value range Data length
Boolean 0 = false, 1 = true 1 byte
INT8 -128 ..+127 1 byte
INT16 -32768 ..+32767 2 byte
INT32 -2147483648 ..+2147483647 4 byte
UINT8 0 ..255 1 byte
UINT16 0 ..65535 2 byte
UINT32 0 ..4294967295 4 byte
Visible String8 ASCII characters 8 byte
Visible String16 ASCII characters 16 byte
Access ro: "Read Only"value can be read only
rw: "Read Write"value can be read and written
wo: "Write Only"value can be written only
PDO R_PDO: mapping for R_PDO possible
T_PDO: mapping for T_PDO possible
No specification: PDP mapping not possible with the object
Value ra n g e Specifies the permissible range in which the object value is defined and
valid.
Default value Load the saved factory settings to reset the product to the default values.
Fieldbus interface 79
8 Object directory IL•1F CANopen DS301
Can be saved yes: values can be saved to the memory of the product and are available
when the product is switched on again.
–: values are lost when the product is switched off.

8.1.2 Objects, overview

Index Subindex Designation Obj. code Data type Access
1000
h
1001
h
1008
h
100C
h
100D
h
1015
h
1018
h
1018
1018
1018
1403
1403
1403
1403
1403
1403
1403
1603
1603
1603
1603
1603
1603
1803
1803
1803
1803
1803
1803
1803
1A03
1A03
1A03
1A03
1A03
1A03
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
0 number of elements VAR UINT8 ro
1 Vendor id VAR UINT32 ro
2 product code VAR UINT8 ro
0 number of elements VAR UINT8 ro
1 COB ID used by R_PDO4 VAR UINT32 ro
2 transmission type R_PDO4 VAR UINT8 rw
3 inhibit time R_PDO4 VAR UINT16 rw
4 compatibility entry R_PDO4 VAR UINT8 rw
5 event timer R_PDO4 VAR UINT16 rw
0 number of elements VAR UINT8 ro
1 1st mapped object R_PDO4 VAR UINT32 ro
2 2nd mapped object R_PDO4 VAR UINT32 ro
3 3rd mapped object R_PDO4 VAR UINT32 ro
4 4th mapped object R_PDO4 VAR UINT32 ro
0 number of elements VAR UINT8 ro
1 COB ID used by T_PDO4 VAR UINT32 ro
2 transmission type T_PDO4 VAR UINT8 rw
3 inhibit time T_PDO4 VAR UINT16 rw
4 reserved T_PDO4 VAR UINT8 rw
5 event timer T_PDO4 VAR UINT16 rw
0 number of elements VAR UINT8 ro
1 1st mapped object T_PDO4 VAR UINT32 ro
2 2nd mapped object T_PDO4 VAR UINT32 ro
3 3rd mapped object T_PDO4 VAR UINT32 ro
4 4th mapped object T_PDO4 VAR UINT32 ro
80 Fieldbus interface
device type VAR UINT32 ro
error register VAR UINT8 ro
manufacturer device name VAR String ro
guard time VAR UINT16 rw
life time factor VAR UINT8 rw
inhibit time EMCY VAR UINT16 rw
identity object RECORD Identity ro
receive PDO4 communication parameter RECORD PDO_Com ro
receive PDO4 mapping RECORD PDO_Map ro
transmit PDO4 communication parameter RECORD PDO_Com ro
transmit PDO4 mapping RECORD PDO_Map ro
IL•1F CANopen DS301 8 Object directory

8.2 Objects of the product

1000h Device type
The object specifies the device profile used as well as the device type.
Object description
Value description
1001h Error register
Object description
Index 1000
Object name device type
Object code VAR
Data type Unsigned32
Subindex 00h, device type
Meaning Device type and profile
Access read-only
PDO mapping
Value range
Default value 0
Can be saved
h
The object specifies the error state of the product. The manufacturer­specific object Status.StopFault 32:7 provides detailed informa­tion on the cause of the error.
Errors are signaled by an EMCY message as soon as they occur.
Index 1001h
Object name error register
Object code VAR
Data type Unsigned8
Value description
Subindex 00h, error register
Meaning error register
Access read-only
PDO mapping
Value range
Default value
Can be saved
Fieldbus interface 81
8 Object directory IL•1F CANopen DS301
Bit coding, subindex 00h
1008h Manufacturer device name
Object description
Value description
Bit Access Value Meaning
0 ro Error! (generic error)
1 ro Current
2ro Voltage
3 ro Temperature
4 ro Communication profile (communication error)
5 ro Device profile (device profile error)
6ro Reserved
7 ro Manufacturer-specific
The object specifies the device name (e.g. “IFS ”)
Index 1008
Object name manufacturer device name
Object code VAR
Data type String
Subindex 00h, manufacturer device name
Meaning Manufacturer name
Access read-only
PDO mapping
Value range
Default value
Can be saved
h
100Ch Guard time
The object specifies the time span for node guarding of an NMT slave.
Object description
Value description
Index 100C
Object name guard time
Object code VAR
Data type Unsigned16
Subindex 00h, guard time
Meaning Time span for node guarding [ms]
Access read-write
PDO mapping
Value range 0...65535
Default value 0
Can be saved
h
82 Fieldbus interface
IL•1F CANopen DS301 8 Object directory
The time span for connection monitoring of an NMT master results from the time span "guard time" multiplied by the factor "life time", object Life time factor (100D
The time span can be changed in the NMT state "Pre-Operational".
100Dh Life time factor
The object specifies the factor that, together with the time span "guard time", results in the time interval for connection monitoring of an NMT master. Within this period, the NMT slave device expects a monitoring request via node guarding from the NMT master.
life time = guard time * life time factor
The value "0" deactivates monitoring of the NMT master.
).
h
Object description
Value description
1015h Inhibit time emergency message
Index 100D
Object name life time factor
Object code VAR
Data type Unsigned8
Subindex 00h, life time factor
Meaning Time factor for the node guarding protocol
Access read-write
PDO mapping
Value range 0...255
Default value 0
Can be saved
h
If there is no connection monitoring through the NMT master during the time interval "life time", #Variable:device-name# signals an error and switches to error state.
The time factor can be changed in the NMT state "Pre-Operational". The time span "guard time" is set with the object Guard time (100C
h
).
The object specifies the waiting time for the repeated transmission of EMCY messages as a multiple of 100μs.
Object description
Index 1015
Object name inhibit time EMCY
Object code VAR
Data type Unsigned16
h
Fieldbus interface 83
8 Object directory IL•1F CANopen DS301
Value description
1018h Identity Object
Value description
Subindex 00h, inhibit time EMCY
Meaning Waiting time for repeated transmission of an EMCY
Access read-write
PDO mapping
Value range 0...65535
Default value 0
Can be saved
The object provides information on the product. Subindex 01 Id) contains the vendor identification, subindex 02
(product Id) contains
h
(vendor
h
the vendor-specific product code.
Index 1018
Object name Identity Object
Object code RECORD
Data type Identity
Subindex 00h, number of elements
Meaning Number of subindexes
Access read-only
PDO mapping
Value range 1...4
Default value 2
Can be saved
h
Subindex 01
Meaning Vendor ID
Access read-only
PDO mapping
Value range 0...4294967295
Default value 0x0100002E
Can be saved
Subindex 02
Meaning Product identification
Access read-only
PDO mapping
Value range 0...4294967295
Default value 0x01
Can be saved
, vendor id
h
, product code
h
84 Fieldbus interface
IL•1F CANopen DS301 8 Object directory
1403h Receive PDO4 communication parameter
The object stores settings for the fourth receive PDO R_PDO4.
Object description
Value description
Index 1403
Object name receive PDO4 communication parameter
Object code RECORD
Data type PDO Communication parameter
Subindex 00h, number of elements
Meaning Number of subindexes
Access read-only
PDO mapping
Value range
Default value 5
Can be saved
Meaning Identifier of the R_PDO4
Subindex 01
Access read-only
PDO mapping
Value range
Default value 0x40000500+nodeID
Can be saved
h
, COB-ID R_PDO4
h
Subindex 02
Meaning Transmission type
Access read-write
PDO mapping
Value range
Default value 254
Can be saved
Subindex 03
Meaning Delay time for repeated transmissions (1=100 μsec)
Access read-write
PDO mapping
Value range 0...65535
Default value 0
Can be saved
, transmission type R_PDO4
h
, inhibit time R_PDO4
h
Fieldbus interface 85
8 Object directory IL•1F CANopen DS301
Subindex 04h, compatibility entry R_PDO4
Meaning For compatibility purposes only
Access read-write
PDO mapping
Value range
Default value
Can be saved
Bit assignment subindex 01h
Bit 31 A R_PDO can only be used if bit 31="0".
Subindex 05
Meaning Time setting for event triggering
Access read-write
PDO mapping
Value range
Default value 0
Can be saved
Bit AccessValue Meaning
31 rw 0
30 ro 0
29 ro 0
28-11 ro 0000
10-7 rw 0100
6-0 ro Node address, bit 6-0 of the COB ID
, event timer R_PDO4
h
b
b
b
0: PDO is active 1: PDO is inactive
0: RTR (see below) is possible 1: RTR is not per­mitted
0: 11 bit identifier (CAN 2.0A) 1: 29 bit identifier (CAN 2.0B)
Only relevant if bit 29=1 is not used by the product.
h
Function code, bit 10-7 of the COB ID
h
Bit 30 RTR bit If a device supports R_PDOs with RTR (remote transmission request),
it can request a PDO from a PDO producer with RTR = "0" in accordance with the producer-consumer relationship.
The product cannot request PDOs, but it can respond to the request for a PDO, see RTR bit for T_PDO1 settings (1800h).
Bit coding, subindex 02h The control for evaluating R_PDO data is specified via subindex 02h.
The values 241..251 are reserved.
Transmission type cyclic acyclic synchronous asynchronous RTR-controlled
0 – X X
1-240 X – X – –
252 – – X – X
253 – – – X X
254 – – – X –
255 – – – X –
86 Fieldbus interface
IL•1F CANopen DS301 8 Object directory
If an R_PDO is transmitted synchronously (transmission type=0..252), the product evaluates the received data depending on the SYNC object.
In the case of acyclic transmission (transmission type=0), the evalu­ation depends on the SYNC object, but not the transmission of the PDO. A received PDO message is evaluated with the following SYNC.
A value between 1 and 240 specifies the number of SYNC cycles after which a received PDO is evaluated.
The values 252 to 254 are relevant for updating T_PDOs, but not for sending them.
252: Updating of transmit data with receipt of the next SYNC
253: Updating of transmit data with receipt of a request from a PDO consumer
254: Updating of data in an event-controlled way, the triggering event is specified in a manufacturer-specific way
R_PDOs with the value 255 are updated immediately upon receipt of the PDOs. The triggering event is the data that is transmitted corresponding to the definition of the device profile in the PDO.
Subindex 03h The "Inhibit time" interval is only relevant for T_PDOs.
A T_PDO is retransmitted after expiration of the "Inhibit time" interval at the earliest. The value is specified as a multiple of 100 μs, however, it is rounded down to milliseconds as an integer value.
Subindex 04h The value is reserved and not used. Write or read access triggers an
SDO error message.
Subindex 05h The time interval "event timer" is only relevant for T_PDOs. A T_PDO is
transmitted after expiry of the time interval "event timer". At the same time, the time interval is restarted. The "transmission type" must be set to one of the values 254 or 255 via subindex 02h.
Settings R_PDO4 is processed asynchronously and in an event-controlled way.
The byte assignment of R_PDO4 is specified via PDO mapping with the object Receive PDO4 mapping (1603
) and cannot be modified. The
h
assignment is described in 3.4.2.2 "Receive PDO R_PDO4 (master -> slave)".
The COB ID of the object can be changed in the NMT state "Pre-Oper­ational".
1603h Receive PDO4 mapping
The object specifies the objects mapped in R_PDO4 and transmitted with the PDO. When the object is read, subindex 00
, the number of
h
mapped objects is read.
Object description
Index 1603h
Object name receive PDO4 mapping
Object code RECORD
Data type PDO Mapping
Fieldbus interface 87
8 Object directory IL•1F CANopen DS301
Value description
Subindex 00h, number of elements
Meaning Number of subindexes
Access read-only
PDO mapping
Value range
Default value 4
Can be saved
Subindex 01
, 1st mapped object R_PDO4
h
Meaning First object for mapping in R_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0108
Can be saved
Subindex 02
, 2nd mapped object R_PDO4
h
Meaning Second object for mapping in R_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0208
Can be saved
Subindex 03
, 3rd mapped object R_PDO4
h
Meaning Third object for mapping in R_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0510
Can be saved
Subindex 04
, 4th mapped object R_PDO4
h
Meaning Fourth object for mapping in R_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0620
Can be saved
88 Fieldbus interface
IL•1F CANopen DS301 8 Object directory
Bit coding from subindex 01h Every subindex entry from subindex 01h on specifies the object and the
byte length of the object. The object is identified via the index and the subindex, which refer to the object dictionary of the device.
Bit Meaning
31..16 Index
15..8 Subindex
7..0 Object length in bytes
Settings The assignment of the R_PDO4 is preset and cannot be modified.
The assignment is described in 3.4.2.2 "Receive PDO R_PDO4 (master
-> slave)".
1803h Transmit PDO4 communication parameter
The object stores settings for the fourth transmit PDO T_PDO4.
Object description
Value description
Index 1803
Object name Transmit PDO4 communication parameter
Object code RECORD
Data type PDO Communication Parameter
Subindex 00h, number of elements
Meaning Number of subindexes
Access read-only
PDO mapping
Value range
Default value 5
Can be saved
Subindex 01
Meaning Identifier of the T_PDO4
Access read-only
PDO mapping
Value range
Default value 0x00000480+nodeID
Can be saved
h
, COB ID used by T_PDO4
h
Subindex 02
Meaning Transmission type
Access read-write
PDO mapping
Value range
Default value 254
Can be saved
, transmission type T_PDO4
h
Fieldbus interface 89
8 Object directory IL•1F CANopen DS301
Subindex 03h, inhibit time T_PDO4
Meaning Delay time for repeated transmission (in [100μsec]). The
Access read-write
PDO mapping
Value range 0...65535
Default value 0
Can be saved
value is rounded down to milliseconds as an integer value.
Subindex 04
Meaning Reserved (for compatibility purposes only)
Access read-write
PDO mapping
Value range
Default value
Can be saved
Subindex 05h, event timer T_PDO4
Meaning Time setting for event triggering
Access read-write
PDO mapping
Value range
Default value 0
Can be saved
, reserved T_PDO4
h
The meaning of the bit states and subindex values is described with the object receive PDO4 communication parameter (1403
).
h
Settings R_PDO4 is transmitted asynchronously and in an event-driven way.
The byte assignment of T_PDO4 is specified via PDO mapping with the object transmit PDO4 mapping (1A03
) and cannot be modified.
h
The assignment is described in 3.4.2.3 "Transmit PDO T_PDO4 (prod­uct to master)".
The COB ID of the object can be changed in the NMT state "Pre-Oper­ational".
1A03h Transmit PDO4 mapping
The object specifies the objects mapped in T_PDO4 and transmitted with the PDO. When the object is read, subindex 00
, the number of
h
mapped objects is read.
Object description
Index 1A03
Object name transmit PDO4 mapping
Object code RECORD
Data type PDO Mapping
h
90 Fieldbus interface
IL•1F CANopen DS301 8 Object directory
Value description
Subindex 00h, number of elements
Meaning Number of subindexes
Access read-only
PDO mapping
Value range
Default value 4
Can be saved
Subindex 01
Meaning First object for the mapping in T_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0410
Can be saved
Subindex 02
Meaning Second object for the mapping in T_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0308
Can be saved
, 1st mapped object T_PDO4
h
, 2nd mapped object T_PDO4
h
Fieldbus interface 91
8 Object directory IL•1F CANopen DS301
Subindex 03h, 3rd mapped object T_PDO4
Meaning Third object for the mapping in T_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0708
Can be saved
Subindex 04
Meaning Fourth object for the mapping in T_PDO4
Access read-only
PDO mapping
Value range
Default value 0x301E0820
Can be saved
, 4th mapped object T_PDO4
h
The meaning of the bit states is described with the object receive PDO4 mapping (1603
).
h
Settings The PDO assignment for T_PDO4 cannot be modified. The assigne-
ment is described in 3.4.2.3 "Transmit PDO T_PDO4 (product to mas­ter)".
92 Fieldbus interface

IL•1F CANopen DS301 9 Glossary

9 Glossary

9.1 Units and conversion tables

The value in the specified unit (left column) is calculated for the desired unit (top row) with the formula (in the field).
Example: conversion of 5 meters [m] to yards [yd] 5 m / 0.9144 = 5.468 yd

9.1.1 Length

in ft yd m cm mm
in - / 12 / 36 * 0.0254 * 2.54 * 25.4
ft * 12 - / 3 * 0.30479 * 30.479 * 304.79
yd * 36 * 3 - * 0.9144 * 91.44 * 914.4
m / 0.0254 / 0.30479 / 0.9144 - * 100 * 1000
cm / 2.54 / 30.479 / 91.44 / 100 - * 10
mm / 25.4 / 304.79 / 914.4 / 1000 / 10 -

9.1.2 Mass

lb oz slug kg g
lb - * 16 * 0.03108095 * 0.4535924 * 453.5924
oz / 16 - * 1.942559*10
slug / 0.03108095 / 1.942559*10
kg / 0.45359237 / 0.02834952 / 14.5939 - * 1000
g / 453.59237 / 28.34952 / 14593.9 / 1000 -
-3
- * 14.5939 * 14593.9
-3
* 0.02834952 * 28.34952

9.1.3 Force

lb oz p dyne N
lb - * 16 * 453.55358 * 444822.2 * 4.448222
oz / 16 - * 28.349524 * 27801 * 0.27801
p / 453.55358 / 28.349524 - * 980.7 * 9.807*10
dyne / 444822.2 / 27801 / 980.7 - / 100*10
N / 4.448222 / 0.27801 / 9.807*10
-3
* 100*10
3
-
3

9.1.4 Power

-3
HP W
HP -* 746
W / 746 -
Fieldbus interface 93
9 Glossary IL•1F CANopen DS301

9.1.5 Rotation

min-1 (RPM) rad/s deg./s
-1
min
(RPM) -* π / 30 * 6
rad/s * 30 / π - * 57.295
deg./s / 6 / 57.295 -

9.1.6 Torque

lb·in lb·ft oz·in Nm kp·m kp·cm dyne·cm
lb·in - / 12 * 16 * 0.112985 * 0.011521 * 1.1521 * 1.129*10
lb·ft * 12 - * 192 * 1.355822 * 0.138255 * 13.8255 * 13.558*10
oz·in / 16 / 192 - * 7.0616*10-3* 720.07*10-6* 72.007*10-3* 70615.5
Nm / 0.112985 / 1.355822 / 7.0616*10-3- * 0.101972 * 10.1972 * 10*10
kp·m / 0.011521 / 0.138255 / 720.07*10-6/ 0.101972 - * 100 * 98.066*10
kp·cm / 1.1521 / 13.8255 / 72.007*10-3/ 10.1972 / 100 - * 0.9806*10
dyne·cm / 1.129*106/ 13.558*106/ 70615.5 / 10*10
6
/ 98.066*106/ 0.9806*106-
6
6
6
6
6

9.1.7 Moment of inertia

2
lb·in
2
lb·ft
2
kg·m
2
kg·cm
kp·cm·s
2
oz·in
2
lb·in
- / 144 / 3417.16 / 0.341716 / 335.109 * 16
* 144 - * 0.04214 * 421.4 * 0.429711 * 2304
* 3417.16 / 0.04214 - * 10*10
* 0.341716 / 421.4 / 10*10
2
* 335.109 / 0.429711 / 10.1972 * 980.665 - * 5361.74
/ 16 / 2304 / 54674 / 5.46 / 5361.74 -
lb·ft
2
kg·m
2
3
kg·cm
2
3
kp·cm·s
* 10.1972 * 54674
2
oz·in
- / 980.665 * 5.46
2

9.1.8 Temperature

°F °C K
°F - (°F - 32) * 5/9 (°F - 32) * 5/9 + 273.15
°C °C * 9/5 + 32 - °C + 273.15
K (K - 273.15) * 9/5 + 32 K - 273.15 -

9.1.9 Conductor cross section

AWG 12345678910111213
2
mm
42.4 33.6 26.7 21.2 16.8 13.3 10.5 8.4 6.6 5.3 4.2 3.3 2.6
AWG 14 15 16 17 18 19 20 21 22 23 24 25 26
2
mm
2.1 1.7 1.3 1.0 0.82 0.65 0.52 0.41 0.33 0.26 0.20 0.16 0.13
94 Fieldbus interface
IL•1F CANopen DS301 9 Glossary

9.2 Terms and Abbreviations

AC Alternating current
CAN (Controller Area Network), standardized open fieldbus as per ISO
11898, allows drives and other devices from different manufacturers to communicate.
CANopen Device- and manufacturer-independent description language for com-
munication via the CAN bus
CiA CAN in Automation, CAN interest group, standardization group for CAN
and CANopen.
COB ID Communication OBject IDentifier; uniquely identifies each communica-
tion object in a CAN network
DC Direct current
Default value Factory setting.
DriveCom Specification of the DSP402 state machine was created in accordance
with the DriveCom specification.
DS301 Standardizes the CANopen communication profile
DSP402 Standardizes the CANopen device profile for drives
E Encoder
EDS (Electronic Data Sheet); contains the specific properties of a product.
Electronic gear Calculation of a new output speed for the motor movement based on the
input speed and the values of an adjustable gear ratio; calculated by the drive system.
EMC Electromagnetic compatibility
EMCY object Emergency Object
Encoder Sensor for detection of the angular position of a rotating component. In-
stalled in a motor, the encoder shows the angular position of the rotor.
Error Discrepancy between a computed, observed or measured value or con-
dition and the specified or theoretically correct value or condition.
Error class Classification of errors into groups. The different error classes allow for
specific responses to faults, for example by severity.
Fault Operating state of the drive caused as a result of a discrepancy between
a detected (computed, measured or signaled) value or condition and the specified or theoretically correct value or condition.
Fault reset A function used to restore the drive to an operational state after a de-
tected error is cleared by removing the cause of the error so that the er­ror is no longer active (transition from operating state "Fault" to state "Operation Enable").
I/O Inputs/outputs
Input device A device that can be connected via the RS232 interface; either the hand-
held HMI device or a PC with commissioning software.
Limit switch Switches that signal overtravel of the permissible range of travel.
Fieldbus interface 95
9 Glossary IL•1F CANopen DS301
Power stage The power stage controls the motor. The power stage generates current
for controlling the motor on the basis of the positioning signals from the controller.
Heartbeat Used for unconfirmed connection acknowledgement messages from
network devices.
HMI Human Machine Interface: hand-held operating device.
Power amplifier See power stage
Life guarding For monitoring the connection of an NMT master
Mapping Assignment of object dictionary entries to PDOs
Node ID Node address assigned to a device on the network.
NMT Network Management (NMT), part of the CANopen communication pro-
file; tasks include initialization of the network and devices, starting, stop­ping and monitoring of devices
Node guarding Monitoring of the connection to the slave at an interface for cyclic data
traffic.
Object dictionary List of all parameters, values and functions available in the device. Each
entry is uniquely referenced via index (16 bit) and subindex (8 bit).
Parameter Device data and values that can be set by the user.
PDO Process Data Object
Persistent Indicates whether the value of the parameter remains in the memory af-
ter the device is switched off.
Quick Stop Function used to enable fast deceleration of the motor via a command
or in the event of an error.
R_PDO Receive PDO
SDO Service Data Object
SYNC object Synchronization object
T_PDO Transmit PDO
Warning If the term is used outside the context of safety instructions, a warning
alerts to a potential problem that was detected by a monitoring function. A warning is not an error and does not cause a transition of the operating state.
96 Fieldbus interface

IL•1F CANopen DS301 10 Index

10 Index
A
Abbreviations 95 ABORT 76, 78 Acyclic data transmission 45 Address 54
Checking 75
Asynchronous errors 76
B
Baud rate 54
Checking 75
Before you begin
Safety information 13 Bit field data 22 Bit field identifier 22 Bit fields
Data 22
Identifier 22 Boot Up
Message 47 Bus arbitration 22
C
CAN
message 22 CAN 3.0A 22 CANopen
Communication profile, NMT 46
error messages 77
Message 22
Standards 11 ccd
See command code Checking
Address 75
Baud rate 75 Client-Server 25 Client-server
SDO data exchange 26 COB ID 22
for node guarding 48
of communication objects 23
SDO 27
SYNC object 45 COB Id
bus arbitration 22
Identification of communication objects 22
tasks 22 Coding
Command code 28, 29 Command code
Fieldbus interface 97
10 Index IL•1F CANopen DS301
Read value 29 SDO 27 Write value 28
Command specifier 48 Command-code
See command code
Commissioning 53 Commissioning the device 53 Communication objects
COB IDs 23 Controlling 22 Identification 22 overview 21
Communication profile
DS301 18
Communication relationship
client - server 24 master - slave 24 producer - consumer 24
Connection error
Node guarding 50
Connection monitoring
NMT services 48
Cyclic data transmission 45
D
Data
Persistent data 47 Reading 29 SDO 27 Writing 28
Data frame 24
of the NMT device service 48 SDO 27
Data length
Flexible 31
Data transmission
Acyclic 45 Cyclic 45 Synchronous 44
Device profile
DS402 18
Diagnostics 75 Documentation and literature references 11 DS301
communication profile 18
DS402
Device profile 18
E
EMCY
object 21
Emergency object
See EMCY object
Error
98 Fieldbus interface
IL•1F CANopen DS301 10 Index
messages for CANopen 77
Response with SDO 30 Error code
table 77 Error diagnostics
Connections to for fieldbus operation 75
Function test of fieldbus 75 error register 77 Example
SDO message 27
Selection of a COB ID 24
F
Function code 23 function code
See Function code Function test
Fieldbus 75
G
Glossary 93
H
Homing 71
I
Identification
of communication objects 22 Index
SDO 27 Interruption of movement
Cause 77 Introduction 9
L
Layer model
Application Layer 15
Data Link Layer 15
Physical Layer 15 Life guarding 48
M
Master - Slave 24 Message 22
CANopen 22
NMT 48, 49
SDO 27 Message objects 76
EMCY(80h+ node ID) 76
Error code (603Fh) 76
error register (1001h) 76
Status word (6041h) 76 Message-oriented communication 9
Fieldbus interface 99
10 Index IL•1F CANopen DS301
Messages
Asynchronous errors 76 Error code (603Fh) 77 Error register (1001h) 77 on the device status 76 Synchronous errors 76
Mode Toggle 40 Multimaster capability 9
N
Network management
See NMT
NMT
Message 48 Network services 46 Recipient of a message 48 Services
Initialization 47 services 21, 46
for connection monitoring 48
for device control 46 State machine 46 State of slave 49 Structure of a message 49
Node address 22, 23, 48 Node guarding 48
COB ID 48 Connection error 50
Node ID 22
O
Object groups
overview 16
Operating mode
homing 71 profile velocity 69
Operation 59 Overview
communication objects 21 object groups 16
P
PDO 21, 31
Producer-consumer 32
Prioritization of messages 9 Process Data Object
see PDO
process data objects
see PDO
Producer-Consumer 25 Producer-consumer
PDO 32 SYNC 44
Profile velocity 69
100 Fieldbus interface
Loading...