Installation Guide
30-3001-882 rev B
The DO-20 provides a connection to 20 Form-C relays from the Continuum DM-20
or the AEclipse DO80-LED option. The DO-20 module can be mounted via a
DIN Rail or directly to a panel. The DO-20 includes individually fused relays.
External Power Supply Requirements
The DO-20 requires an external 24VDC ±10% power source. The current requirement is 500mA max.
What You Received
The DO-20 module is shipped with the
following parts:
• DO-20 Printed Circuit Board
• Two Plastic PCB Mounting Brackets
• Two plastic DIN Rail mounting Brackets.
• Installation guide (this document)
Additional Items Required
Items not included yet necessary for
installation are the following:
• CX 9400 (AEclipse) controller
or Continuum NetController
• DO80-LED Output module
or Continuum DM-20 I/O module
• 24 VDC Power Source
• Output Wires
• 25-pin Interface cable
• Two DIN End Clamps
• Standard 35mm DIN Rail
•Enclosure
Mechanical Installation
The DO-20 is designed to be mounted to either
a DIN Rail or directly to a bulkhead.
Mounting to a DIN Rail
End Clamp
DIN Rail
DIN Rail
Mounting
Bracket
1. Slide an end clamp into position on the DIN
Rail. Tighten the holding screws.
2. Slide a DIN Rail Mounting Bracket
t
he PCB Mounting bracket until ush on t
k side.
bac
3. Slide the DIN Rail Mounting Bracket/PCB
Bracket assembly onto the DIN Rail until
ush with the end clamp.
PCB
Mounting
Bracket
under
he
Mounting to a DIN Rail
(continued)
4 Insert one end of the module PCB into the PCB Bracket. Slide the board
into the middle channel of the Mounting Bracket.
Mount bracket here
Slide brackets under board
Slide this bracket to trap board
5 Slide another DIN Rail Mounting Bracket onto a PCB Bracket.
6 Slide the DIN Rail/PCB Mounting Bracket assembly onto the board and DIN
Rail. Carefully slide the assembled brackets into the center of the module
board.
7 Slide the remaining bracket onto the DIN Rail and position it at the end of
the board.
8 Mount another end clamp. Tighten the screws on the end clamp.
DO-20 Specications
Power:
Current:
Input:
24VDC ±10%
500 mA
25-pin D connector
Input Connector Pinout:
1 OUT 1
2 OUT 2
3 OUT 3
.
.
.
20 OUT 20
21-25 GND
Fuse Ratings:
Main Power: 0.75A,125V
ACC P/N: 01-2180-014
Output: 3.5A,125V
ACC P/N: 01-2180-410
Mounting Directly to a Panel
There are seven #6-sized holes (0.156 (4mm)) provided for mounting
using stand-os directly to a at surface. The illustration on the right
shows the mounting dimensions of the module.
Output
Fuses
Status
Main Power
LED
Fuse
LEDs
9.45 (240) x2
3.10 (79) x2
9.80 (249)
6.30 (160)
24VDC *
Connection
25-pin D Cable
from
20 Module
DM-
Output 1
typical
0.17 x2
(4)
Schneider Electric
© 2010, Schneider Electric
0.17 x3
(4)
0.17 x4
(4)
4.33 (110)