Schneider Electric Class 615 User Manual

Compact® NSF and NSJ
150 to 600 A Circuit Breakers
Class 615
CONTENTS Page
Section 1—The Compact
Section 2—General Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section 3—Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Section 4—Trip Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Section 5—Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 6—Motor Circuit Protectors . . . . . . . . . . . . . . . . . . . . . . . . . 19
Section 7—Mounting Configurations . . . . . . . . . . . . . . . . . . . . . . . . 21
Section 8—Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Section 9—Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Section 10—Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Section 11—Connection Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 53
Section 12—Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Section 13—Supplementary Technical Information . . . . . . . . . . . . . 57
®
TABLE OF CONTENTS
THE COMPACT® CIRCUIT BREAKER LINE ....................................................................................... 4
GENERAL CHARACTERISTICS .......................................................................................................... 5
Compliance with Standards ............................................................................................................. 5
CIRCUIT BREAKERS ........................................................................................................................... 8
Ratings and Interrupting Ratings ..................................................................................................... 8
TRIP UNITS ........................................................................................................................................ 10
Trip Units for Compact® NSF150 and NSF250 Circuit Breakers .................................................. 10
Trip Units for Compact
Electronic Trip Unit Test Kits ......................................................................................................... 16
SWITCHES ......................................................................................................................................... 17
Ratings and Interrupting Ratings ................................................................................................... 17
MOTOR CIRCUIT PROTECTORS ..................................................................................................... 19
Ratings and Interrupting Ratings ................................................................................................... 19
MOUNTING CONFIGURATIONS ....................................................................................................... 21
Fixed Mounting .............................................................................................................................. 21
Connections .................................................................................................................................. 21
Plug-in Mounting ........................................................................................................................... 21
Drawout Mounting ......................................................................................................................... 22
CONNECTIONS ................................................................................................................................. 24
Front Connection ........................................................................................................................... 24
Rear Connection ........................................................................................................................... 25
ACCESSORIES .................................................................................................................................. 26
Location ......................................................................................................................................... 26
Connections .................................................................................................................................. 26
Automatic Secondary Disconnecting Blocks ................................................................................. 27
Auxiliary and Alarm Switches ........................................................................................................ 28
Shunt Trip and Undervoltage Trip ................................................................................................. 30
Motor Operator .............................................................................................................................. 31
Rotary Operating Handles ............................................................................................................. 33
Cable Operating Handles .............................................................................................................. 35
Locking Systems ........................................................................................................................... 36
Interlocking Accessories ................................................................................................................ 37
Front Panel Escutcheons .............................................................................................................. 39
DIMENSIONS ..................................................................................................................................... 41
Fixed Mounted ............................................................................................................................... 41
Plug-in and Drawout Mounting ...................................................................................................... 43
Cable Operating Handles .............................................................................................................. 47
Rotary Operating Handles ............................................................................................................. 48
Front Accessories .......................................................................................................................... 51
Interlocking Systems ..................................................................................................................... 52
CONNECTION DIMENSIONS ............................................................................................................ 53
WIRING DIAGRAMS .......................................................................................................................... 55
SUPPLEMENTARY TECHNICAL INFORMATION ............................................................................. 57
Reflex Tripping .............................................................................................................................. 62
Let-through Curves ........................................................................................................................ 63
Current Limiting Curves ................................................................................................................. 65
UL 489 Test Procedure ................................................................................................................. 67
IEC 947-2 Test Procedure ............................................................................................................. 70
Routine and Maintenance Guidelines ........................................................................................... 73
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Table of Contents
®
NSJ400 and NSJ600 Circuit Breakers ................................................... 11
© 1995–2003 Schneider Electric All Rights Reserved
3
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 1—The Compact® Circuit Breaker Line
SECTION 1—THE COMPACT® CIRCUIT BREAKER LINE
CIRCUIT BREAKERS—PAGE 8
06153032
h s u p o t p i r t
Rated Current (A)
COMPACT
Interrupting Rating at 480 V
®
15–100 15–250 150–600 400–1200 1250–2500
NSE100
18 35 35 50
N
—65656585
H
——100150—
L
SWITCHES—PAGE 17
Rated Current (A)
06153032
h s u p o t p i tr
COMPACT
®
70 150, 250 400, 600 800, 1200 1600–2500
NSE100A
MOTOR CIRCUIT PROTECTORS—PAGE 19
3–75 100–250 400–600 800–1200
NSE100A
06153033
Rated Current (A)
COMPACT
®
NSF150
NSF250
NSF150A
NSF250A
NSF150A
NSF250A
NSJ400
NSJ600
NSJ400A
NSJ600A
CK400–CK1200 CM1250–CM2500
CK800NA
NSJ400A
NSJ600A
CK800NA
CM1600HA
CM2000HA
CM2500HA
h s u p o t ip tr
For NSE, CK and CM circuit breakers see appropriate catalog.
4
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
SECTION 2—GENERAL CHARACTERISTICS
COMPLIANCE WITH STANDARDS
MERLIN
compact
06153060
NSF 250 N
600Y/347V 50/60Hz
UL/CSA interrupting ratings RMS sym. Amps
240V ac 480V ac 600Y/347V ac
current limiting (see curves in catalog)
IEC947.2
220/240V 380/415V~
Ics=100% Icu Ui 750V
cat A
UTE VDE BS CEI UNE NEMA
~
65k 35k 18k
85kA 36kA
Uimp 8kV
Icu
Section 2—General Characteristics
Compliance with North American Standards
Compliance with International Standards
Compliance with the Specifications of Marine Classification Organizations
Compact® NS circuit breakers are built in accordance with Underwriters Laboratories Inc. UL 489 Standard and Canadian Standards Association CSA C22.2 No. 5.02 Standard. Circuit breakers, switches and their accessories, except where noted, are Listed under UL files E63335, E103740, E103955, and Certified under CSA files LR69561 and LR88980.
Compact NS circuit breakers and their accessories comply also with the following international standards:
IEC 60947-1: general rules
IEC 60947-2: circuit breakers
IEC 60947-3: switches, disconnectors, switch disconnectors, etc.
In that these standards are applied in most countries, Compact circuit breakers and their accessories comply with European (EN 60947-1 and EN 60947-2) and the corresponding national standards:
France NF
Germany VDE
U.K. BS
Australia AS
Italy CEI
Compact NS circuit breakers have been approved for marine application by the American Bureau of Shipping, Bureau Veritas, Lloyd’s Register of Shipping, Registro Italiano Navale, Germanischer Lloyd’s and Det Norske Veritas.
They comply with the following standards:
UL 489 Supplement SA. Marine use on vessels over 65 feet in length
US Coast Guard specifications
IEC 92-504 and marine specifications: inclination, vibrations, insulation resistance
IEC 803 Electromagnetic Disturbance Immunity
© 1995–2003 Schneider Electric All Rights Reserved
5
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 2—General Characteristics
Tropicalization Compact
humidity at 45° C or 80% at 55° C, hot and humid climate conditions). The materials used in Compact NS circuit breakers will not support the growth of fungus or mold.
They also comply with the following standards:
®
NS circuit breakers comply with NF C 63-100 standard level 2 conditions (95% relative
IEC 68-2-30 damp heat
IEC 68-2-2 dry heat
IEC 68-2-11 salt spray
IEC 68-2-1 low temperatures
Pollution Degree Compact NS circuit breakers are certified for operation in pollution degree III environments as defined
by IEC standard 947 (industrial environments).
Environmental Protection
Compact NS circuit breakers take into account concerns for environmental protection. Most components are recyclable and parts are marked as specified in applicable standards.
Suitability for Isolation (Positive Contact Indication)
06153037
Installation in Class II Switchboards
All Compact NS circuit breakers and switches are suitable for isolation as defined in the IEC 947-2 Standard:
The isolation position corresponds to the O (OFF position).
The operating handle cannot indicate the OFF position unless the contacts are open.
Padlocks may not be installed unless the contacts are open
Installation of a rotary handle or a motor mechanism does not alter the functionality of the position indication system.
The isolation function is certified by tests guaranteeing:
The mechanical reliability of the position indication system
The absence of leakage currents
Overvoltage withstand capacity between upstream and downstream connections
Circuit Breaker Marking
06153038
All Compact NS circuit breakers, even when fitted with a rotary handle or a motor mechanism, can be installed through the door of Class II IEC switchboards (as per IEC 664 Standard). Refer to circuit breaker installation instructions prior to installing circuit breaker.
Installation requires no special insulation because Compact NS circuit breakers provide Class II insulation between the front face and all internal circuits.
Switch Marking
06153039
6
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 2—General Characteristics
Suitability for Isolation (Positive Contact Indication)
The limiting capacity of a circuit breaker is its ability to limit short-circuit currents.
Isc
06153040
The exceptional limiting capacity of the Compact
Prospective Isc Peak
Limited Isc Peak
Limited Isc
tsc
Actual Current
Prospective Current
Prospective Isc
t
®
NS line is due to the double break technique (rapid
natural repulsion of contacts and the appearance of two arc voltages in series with a steep wavefront).
The limiting capacity of the Compact NS line greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. In particular, the service breaking capacity Ics is equal to 100% of Icu.
The Ics value, defined by IEC 947-2, is guaranteed by tests comprising the following operations:
Breaking a fault current equal to 100% of Icu three times consecutively
Checking that the device continues to function normally
Conduction of rated current without abnormal temperature rise
Protection functions perform within the limits specified by the standard
Suitability for isolation is not impaired
Longer Service
Current limiting circuit breakers greatly reduce the negative effects of short circuits on installations.
Life of Electrical Installations
Thermal Effects Less temperature rise in conductors, therefore longer service life for cables.
Mechanical Effects Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being distorted or
broken.
Electromagnetic Effects
Less disturbance for measuring devices located near electrical circuits.
© 1995–2003 Schneider Electric All Rights Reserved
7
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 3—Circuit Breakers
SECTION 3—CIRCUIT BREAKERS
RATINGS AND INTERRUPTING RATINGS
UL 489 Listed Ratings
Compact® Circuit Breakers NSF150 NSF250
06153061
06153062
Number of Poles
Rated Voltage (V)
h s u p o t p i r t
Rated Current (A) In
Interrupting Ratings (kA rms)
*Oversized Neutral Protection: four-pole OSN 125/250N and 150/250N are same ratings as NSF250A.
AC 50/60 Hz 600Y/347 600Y/347
40° C 150 250
240 V 65 100 65 100
480 V 35 65 35 65
600 Y/ 347 V 18 25 18 25
600 V
IEC 947-2 and EN 60947-2 Ratings
Compact® Circuit Breakers NSF150 NSF250
Number of Poles
Rated Insulation Voltage (V) Ui
Rated Impulse Withstand Voltage (kV)
Rated Operational Voltage (V) Ue
Rated Current (A) In
Ultimate Breaking Capacity (kA rms) Icu
Service Breaking Capacity Ics
Utilization Category
*Oversized Neutral Protection: four-pole OSN 125/250N and 150/250N are same ratings as NSF250A.
Uimp
AC 50/60 Hz 690 690
DC 500 500
40° C 150 250
AC 50/50 Hz 220/ 240 V 85 100 85 100
380/ 415 V 36 70 36 70
440 V 35 65 35 65
500 V 30 50 30 50
525 V 22 35 22 35
600/ 690 V 8 10 8 10
DC 250 V (1 pole) 50 85 50 85
500 V (2 pole in series)
(% Icu) 100% 100% 100% 100%
3, 4, 4 OSN* 3, 4
N H N H
3, 4, 4 OSN* 3, 4
750 750
88
N H N H
50 85 50 85
A A A A
8
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 3—Circuit Breakers
UL 489 Listed Ratings
Compact® Circuit Breakers NSJ400 NSJ600
06153061
h s u p o t p i r t
Number of Poles
Rated Voltage (V)
Rated Current (A) In
Interrupting Ratings (kA rms)
AC 50/60 Hz 600 600
40° C 400 (100% Rated Circuit Breaker) 600
240 V 65 100 150 65 100 150
480 V 35 65 100 35 65 100
600 Y/ 347 V
600 V 182525182525
*Oversized Neutral
IEC 947-2 and EN 60947-2 Ratings
Compact® Circuit Breakers NSJ400 NSJ600
Number of Poles
06153063
Rated Insulation Voltage (V) Ui
Rated Impulse Withstand Voltage (kV)
Uimp
Rated Operational Voltage (V) Ue
Rated Current (A) In
Ultimate Breaking Capacity (kA rms)
Icu
Service Breaking Capacity Ics
Utilization Category
*Oversized Neutral
AC 50/60 Hz 690 690
DC 500 500
40° C 400 600
AC 50/50 Hz 220/240 V 85 100 150 85 100 150
380/415 V 45 70 150 45 70 150
440 V 42 65 130 42 65 130
500 V 30 50 70 30 50 70
525 V 22 35 50 22 35 50
600/690 V 10 20 35 10 20 35
DC 250 V (1 pole) — 85 85
500 V (2 pole in series)
(% Icu) 100% 100% 100% 100% 100%
3, 4, 4 OSN* 3, 4
N H L N H L
3, 4, 4 OSN* 3, 4
750 750
88
N H L N H L
—85—— 85—
A A A A — A
© 1995–2003 Schneider Electric All Rights Reserved
9
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
SECTION 4—TRIP UNITS
TRIP UNITS FOR COMPACT® NSF150 AND NSF250 CIRCUIT BREAKERS
Compact NSF150 and NSF250 circuit breakers are equipped with thermal-magnetic (TM) trip units.
Protection Against overload (1) with a fixed thermal protection
Against short circuits (2) with fixed (on NSF150) or adjustable (on NSF250) magnetic protection
t
06153064
21
1
Ir
250 A
Trip Units for Compact® NSF150–NSF250 Circuit Breakers
Rating (A) In
3P 50° C 14.2 19 28.5 38 47.5 57 66.5 76 85 95 118 142 166 190 213 237
4P3T 60° C 13.5182736455463728190112 135158180203225
4P4T 70° C 12.8 17 25.6 34.2 43 51 60 68 77 85 107 128 150 171 192 214
Circuit Breaker
Rating (A) In
4P OSN 50° C 95 142 118 237 142 237
Overload Protection
Thermal
Short-circuit Protection
Magnetic
Neutral Protection
*Oversized Neutral
Compact® NSF150 N/H ■■■■■■■■■■ ■ ■
Compact® NSF250 N/H ■ ■■■
®
Compact
NSF150 400 500 1000 1250 1500
Compact® NSF250 5–10 x In
Im
10
9
TM15DP–TM250DP Trip Units
40° C 152030405060708090100125150 175200225250
TM100OSN–TM150OSN Trip Units
Phase Neutral Phase Neutral Phase Neutral
40° C 100 150 125 250 150 250
60° C 90 135 112 225 135 225
70° C 85 128 107 214 128 214
3P Non-adjustable
4P3T
4P4T
4P OSN*
Non-adjustable Adjustable
4P3T No Neutral Protection
4P4T 1000 1250 1500 5–10 x In
4P OSN*
8
7
x 250 A
5
6
Ir Im
TM 250 D
250A / 40°C
2
0
Ir Im
Non-adjustable, No Neutral Protection
Non-adjustable
Non-adjustable
1000 1250 1500
I
10
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
TRIP UNITS FOR COMPACT® NSJ400 AND NSJ600 CIRCUIT BREAKERS
Compact NSJ400 and NSJ600 circuit breakers are equipped with current sensors and electronic trip units.
Current Sensors Four different sizes are available and can be mounted with all trip units:
NSJ400—150, 250 and 400 A
NSJ600—600 A
Trip Units STR23SP, STR53UP and STR23SP-OSN
Protection for loads, from 60 to 600 A — STR23SP and STR53UP for standard protection — STR23SP-OSN for oversized neutral protection (factory-installed only) — STR53UP for generator supplied network protection and long cable runs
Trip units STR23SP and STR53UP can be mounted on all Compact NSJ400 and NSJ600 circuit
breaker types N, H and L
Trip unit STR53UP offers a greater number of optional indication and measurement functions,
protection settings and ground-fault protection
STR23SP and STR53UP available on four-pole circuit breakers with sealable, 3-position neutral
protection setting: — 4P 3D (neutral unprotected)
— 4P 3D + N/2 (neutral protection at 0.5 x Ir) where Ir is trip unit current setting — 4P 4D (neutral protection at Ir) where Ir is trip unit current setting
Trip Units for Compact® NSJ400 and NSJ600 Circuit Breakers
Overload Protection (Long Time)
Tripping Threshold (A)
Tripping Time (s) (Min–Max)
Short-circuit Protection (Short Time)
Tripping
Time Delay (ms)
Short-circuit Protection (Instantaneous)
Tripping Threshold (A)
Adjustable Neutral Protection (Three Position Switch)
Other Functions
Indication of Fault Type (Standard)
Equipment Ground-fault Protection (T)
Built-in Ammeter (I)
Zone-selective Interlocking (ZSI)
Communication (COM)
Ir
Im / Isd
Accuracy ± 15%
Max. Overcurrent Time Before Tripping Fixed ≤ 40
Total Breaking Time ≤ 60 ≤ 60 ≤ 140 ≤ 230 ≤ 350 ≤ 60
Switch Settings Protection Level
Position 1 4P 3D No Protection No Protection No Protection No Protection
Position 2 4P 3D + N/2 0.5 x Ir 0.5 x Ir 0.8 x Ir 0.75 x Ir
Position 3 4P 4D 1.0 x Ir 1.0 x Ir 1.6 x Ir 1.5 x Ir
20–70° C Adjustable (48 Settings) 0.4–1 x In
At 1.5 x Ir 120–180 17–25 34–50 69–100 138–200 277–400 120–180
At 6 x Ir 5–7.5 0.8–1 1.6–2 3.2–4 6.4–8 12.8–16 5–7.5
At 7.2 x Ir 3.2–5.0 0.5–0.7 1.1–1.4 2.2–2.8 4.4–5.5 8.8–11 3.2–5.0
STR23SP STR53UP
Fixed Adjustable Fixed
Adjustable (7 Settings) 2–9 x Ir
Fixed 9 x In Adjustable (7 Settings) 1.5–9 x In Fixed 9 x In
Adjustable (7 Settings) 1.5–7 x Ir Adjustable (7 Settings) 2–9 x Ir
Adjustable (4 Settings + Constant I2t Function)
15 ≤ 60 ≤ 140 ≤ 230
STR23SP OSN (Oversized Neutral)
Fixed ≤ 40
NSJ250/400N NSJ400/600N
© 1995–2003 Schneider Electric All Rights Reserved
11
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
Electronic Trip Unit STR23SP and STR23SP-OSN (Oversized Neutral)
t
7
06153065
1
6
3
1
2
3
4
5
Ir Im
test
+
Io = sensor
.7
.63
.5
-
short time
Im
56
4
3
2
90
%Ir
105
7
9
x Ir
ImIr
STR 23 SP
long time
Ir
.8
x In
.9
1
.85
.88
.93
.9
.95
.98
.8
1
x Io
alarm
0
Protection Long-time (LT) overload protection, adjustable threshold, based on the actual rms current
— Adjustable threshold (1) using six lo base settings (0.5–1) and fine adjustment Ir with eight
settings ranging from (0.8–1)
— Non-adjustable tripping time (2)
Short-time (ST) short-circuit protection
— Adjustable threshold Im (3) — Fixed time delay (4)
Instantaneous (I) short-circuit protection, fixed threshold (5)
Neutral protection available on standard four-pole circuit breakers; protection level controlled using
three-position switch — 4P 3D: no protection — 4P 3D + N/2: neutral protection at 0.5 Ir — 4P 4D: neutral protection at Ir
Neutral protection for STR23SP-OSN (oversized neutral) available on four-pole circuit breakers
equipped with oversized neutral protection; protection level controlled using three-position switch
I
12
NSJ250/400N: NSJ400/600N:
— 4P 3D: no protection — 4P 3D: no protection
— 4P 3D + N/2: neutral protection at 0.8 x Ir — 4P 3D + N/2: neutral protection at 0.75 x Ir
— 4P 4D: neutral protection at 1.6 x Ir — 4P 4D: neutral protection at 1.5 x Ir
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
Indications Load indication (LED) in front (6):
Lights solid at 90% of Ir threshold
Flashes at >105% or greater of Ir threshold
Test Test connector in front (7) for connection to test kit to check circuit breaker operation after fitting the trip
unit or other accessories.
Setting Example Question: What is the overload protection threshold of a Compact NSJ400 circuit breaker equipped
with trip unit STR23SP where Io = 0.5 and Ir = 0.8?
Answer: In x Io x Ir = 400 x 0.5 x 0.8 = 160 A
The same trip unit with the same settings, mounted on an NSJ600 circuit breaker will have the following tripping threshold: In x Io x Ir = 600 x 0.5 x 0.8 = 240 A.
.7
.8
Io
.9
1
06153066
.63
.5
x In
400 x 0.5 x 0.8 = 160 A
.88
.85
.8
.9
Ir
.93
.95
.98
1
x Io
© 1995–2003 Schneider Electric All Rights Reserved
13
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
Electronic Trip Unit STR53UP
t
4
8
test
1
Io
.7
.6
.5
Ir
.9
.8
x In
+
.90 .93
.88
1
.85
1
.8
x Io
tr
8
4
-
2
0,5
(s) @ 6 Ir
06153067
Protection Long-time (LT) overload protection, adjustable threshold, based on actual rms current, as defined
2
STR 53 UP
.95
.98
1
tsd
8
Isd
(s)
3
4 5
3
6
2
7
1.5
x Ir
.3 .3
.2
.2
.1
0
0
on
I2t
off
5
%Ir >Ir >Isd >Ig
Ii
4 6
3
8
9
2
7
.1
9
1.5
x In
6
Ig
.4
.3
.2
tg
.3
(s)
.2
.1
on
.4 .4
.5
x In
I2t
9
.6
.7
.8
1
.3
.2
.1
off
7
test
μ P
> Ir
> Im
> Ih
In I1 I2 I3
1
2
6
7
A
tr
tsd
IsdIr li
0
Ir Isd I
3
4
5
by IEC 947-2, appendix F — Adjustable threshold (1) using six lo base settings (0.5–1) and fine adjustment Ir with eight
settings ranging from (0.8–1)
— Adjustable tripping time (2)
Short-time (ST) short-circuit protection
— Adjustable threshold Isd (3) — Adjustable time delay (4), with or without constant I
2
t function
Instantaneous (Ii) short-circuit protection, adjustable threshold (5)
Neutral protection available on standard four-pole circuit breakers; protection level controlled using
three-position switch — 4P 3D: no protection — 4P 3D + N/2: neutral protection at 0.5 Ir — 4P 4D: neutral protection at Ir
I
Overload Indications (%Ir)
LED (9) lights solid when current exceeds 0.9 Ir
LED (9) flashes when current exceeds long-time threshold Ir
Fault Indications LEDs indicate the type of fault that caused tripping:
Overload (LT protection) or abnormal component temperature (>Ir)
Short-circuit (ST or instantaneous protection) (>Isd)
Ground-fault (if earth-fault protection option is present) (>Ig)
Microprocessor malfunction—both (>Ir) and (>Isd) LEDs go on, plus the (>Ig) LED, if the ground-
fault protection option is present
The LEDs are battery powered with spare batteries supplied in the adapter box. When a fault occurs, the LED indicating type of fault shuts off after approximately 10 minutes to conserve battery power. The fault data is stored in memory and the LED can be re-illuminated by pressing the battery/LED test button (9). The LED automatically goes off and memory is cleared when the circuit breaker is reset.
Test
Test connector in front (8) for connection to test kit (see page 16); used to check circuit breaker
operation after fitting trip unit or other accessories
Test button (9) for (%Ir), (>Ir), (>Im) and (>Ig) LEDs and battery
Self-monitoring The circuit breaker trips for both microprocessor faults and abnormal temperatures.
14
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
Options for Electronic Trip Unit STR53UP
Equipment Ground-fault Protection (T)—see (6) and (7), page 14
Type
Tripping threshold
Tripping time (ms)
Ig Adjustable (8 Settings) 0.2–1 x In
Accuracy ± 15%
Max. overcurrent time before tripping (Tg) Adjustable (4 Settings + Constant I2t Function) 60, 140, 230, 350
Total Breaking Time -140, -230, -350, -500
Residual Current
Ammeter (I) A digital display continuously indicates the current of the phase with the greatest load. By pressing a
scroll button, it is also possible to display successively the readings of I1, I2, I3 and I neutral. LEDs indicate the phase for which the current is displayed.
06153068
A
In I1 I2 I3
Zone-selective Interlocking (ZSI)
A number of circuit breakers are interconnected one after another by a pilot wire. In the event of a short-time or earth fault:
If a given trip unit STR53UP detects the fault, it informs the upstream circuit breaker which applies
the set time delay
If the trip unit STR53UP does not detect the fault, the upstream circuit breaker trips after its shortest
time delay
Opto-electronic Outputs
Communication (COM)
Possible Combinations
In this way, the fault is cleared rapidly by the nearest circuit breaker. In addition, thermal stresses on the circuits are minimized and time discrimination is maintained throughout the installation.
The use of opto-transistors ensures total isolation between the internal circuits of the trip unit and the circuits wired by the user.
®
Transmission of the following data to Digipact
distribution monitoring and control modules:
Settings
Phase and neutral currents (rms values)
Highest current of the three phases
Overload condition alarm
I
T
I + T
I + COM
I + T + COM
ZSI
ZSI + I
ZSI + T
ZSI + I + T
ZSI + I + COM
ZSI + I + T + COM
© 1995–2003 Schneider Electric All Rights Reserved
15
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 4—Trip Units
ELECTRONIC TRIP UNIT TEST KITS
The test kits presented below are compatible with Compact® and Masterpact® MP/MC/M circuit breakers.
Tests performed by test kits are only functional tests designed to electrically test the operating integrity of the trip unit, the flux shifter and the mechanical operation of the circuit breaker. Tests are not designed to calibrate the circuit breaker.
Mini Test Kit and Hand-held Test Kit
Portable Test Kit and Full-function Test Kit
The Mini Test Kit and the new generation Hand-held Test Kit are portable units which require no external power supply. Both are powered by five 9 V alkaline batteries, not supplied. These test kits are used to check operation of the electronic trip unit and circuit breaker tripping. Connection of either test kit is made via the test port on the front of the trip unit.
06153069
Mini Test Kit
06133786
Hand-held Test Kit
The Portable Test Kit and the new generation Full-function Test Kit are calibration units. Both require a power supply of 110 or 240 Vac, 50/60 Hz (two-position selector). These test kits are used to check the operation of the trip unit by measuring actual trip times:
At 1.5 x Ir for long-time protection
At 15 x Ir for short-time protection
At 0.8 x In for ground-fault protection
16
06153070
Portable Test Kit
06133014
Full-function Test Kit
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
SECTION 5—SWITCHES
RATINGS AND INTERRUPTING RATINGS
UL 1087 Listed Ratings
Section 5—Switches
06153061
h s u p o t p i tr
Number of Poles
Rated Voltage (V)
Rated Current (A)
AC 50/60 Hz 600Y/ 347 600Y/ 347
*Oversized Neutral Protection: four-pole OSN 125/250 and 150/250 are same ratings as NSF250A.
3, 4, 4P OSN* 3, 4
150 250
IEC 947-3 Ratings
Compact® Switches NSF150A NSF250A
Compact® Switches NSF150A NSF250A
Number of Poles
Rated Insulation Voltage (V) Ui
Rated Impulse Withstand Voltage (kV)
Uimp
Rated Operational Voltage (V) Ue
Rated Operational Current (V) Ie
Making Capacity (kA peak)
Short-time Withstand Current (kA rms)
*Oversized Neutral Protection
Icw
AC 50/60 Hz 690 690
DC 500 500
AC23A 690 V 160 250
DC23A 250 V 160 250
DC23A 500 V (2 poles in series) 160 250
Icw (kA rms) 2.5 3.5
Duration (s) 3 3
3, 4, 4P OSN* 3, 4
750 750
88
3.6 4.9
© 1995–2003 Schneider Electric All Rights Reserved
17
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 5—Switches
UL 489 Listed Ratings
06153061
h s u p o t p i r t
Number of Poles
Rated Voltage (V)
AC 50/60 Hz 600 600
Rated Current (A)
*Oversized Neutral Protection: four-pole OSN 125/250 and 150/250 are same ratings as NSF250A.
3, 4, 4P OSN* 3, 4
400 600
IEC 947-3 Ratings
Compact® Switches NSF150A NSF250A
Compact® Switches NSJ400A NSJ600A
Number of Poles
Rated Insulation Voltage (V) Ui
Rated Impulse Withstand Voltage (kV)
Uimp
Rated Operational Voltage (V) Ue
Rated Operational Current (V) Ie
Making Capacity (kA peak)
Short-time Withstand Current (kA rms)
*Oversized Neutral Protection
Icw
AC 50/60 Hz 690 690
DC 500 500
AC23A 690 V 400 630
DC23A 250 V 400 630
DC23A 500 V (2 poles in series) 400 630
Icw (kA rms) 5 8
Duration (s) 3 3
3, 4, 4P OSN* 3, 4
750 750
88
7.1 8.5
Short-circuit Withstand Current
Molded case switches are identical to molded case circuit breakers, except they are not equipped with trip units and sensors. Molded case switches open when the handle is switched to the OFF position or in response to an auxiliary tripping device such as a shunt trip or an undervoltage release.
These switches open instantaneously at a non-adjustable, factory preset, magnetic trip point calibrated to protect only the molded case switch itself. Magnetic settings:
NSF150/250 A switches: 2000 A
NSJ 400/600 A switches: 6000 A
These switches are suitable for use on a circuit capable of delivering not more than:
240 V: 100 kA for NSF switches and 150 kA for NSJ switches
480 V: 65 kA for NSF switches and 100 kA for NSJ switches
600 V (600Y/347 for NSF switches): 25 kA
Switches are Listed under UL file E103740 and Certified under CSA file LR 88980.
18
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
SECTION 6—MOTOR CIRCUIT PROTECTORS
RATINGS AND INTERRUPTING RATINGS
UL 489 Recognized Component
Compact® Circuit Breakers NSF150HC NSF250HC
06153033
h s u p o t p i tr
Number of Poles
Rated Voltage (V)
Rated Current (A) In
AC 50/60 Hz 600Y/347 600Y/347
40° C 150 200 250
Magnetic Trip Setting Im
IEC 947-2 and EN 60947-2 Ratings
Compact® Circuit Breakers NSF150HC NSF250HC
Number of Poles
Rated Insulation Voltage (V) Ui
Rated Impulse Withstand Voltage (kV)
Rated Operational Voltage (V) Ue
Rated Current (A) In
Ultimate Breaking Capacity Icu
(kA rms) 380/415 V 70 70
Service Breaking Capacity Ics
Utilization Category
Uimp
AC 50/60 Hz 690 690
DC 500 500
40° C 150 200 250
AC 50/60 Hz 220/240 V 100 100
440 V 65 65
500 V 50 50
525 V 35 35
660/690 V 10 10
DC 250 V (1 pole) 85 85
500 V (2 poles in series) 85 85
(% Icu) 100% 100%
Section 6—Motor Circuit Protectors
33
900-1800
33
750 750
88
1000– 2000
HC HC
AA
1250– 2500
© 1995–2003 Schneider Electric All Rights Reserved
19
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 6—Motor Circuit Protectors
UL 489 Recognized Component
Compact® Circuit Breakers NSJ400HC NSJ600HC
06153033
h s u p o t p i tr
Number of Poles
Rated Voltage (V)
Rated Current (A) In
AC 50/60 Hz 600 600
40° C
Magnetic Trip Setting Im
IEC 947-2 and EN 60947-2 Ratings
Compact® Circuit Breakers NSF150HC NSF250HC
Number of Poles
Rated Insulation Voltage (V) Ui
Rated Impulse Withstand Voltage (kV)
Rated Operational Voltage (V) Ue
Rated Current (A) In
Ultimate Breaking Capacity Icu
(kA rms) 380/415 V 70 70
Service Breaking Capacity Ics
Utilization Category
Uimp
AC 50/60 Hz 690 690
DC 500 500
40° C 400 600
AC 50/60 Hz 220/240 V 100 100
440 V 65 65
500 V 30 30
525 V 35 35
660/690 V 20 20
DC 250 V (1 pole) 85 85
500 V (2 poles in series) 85 85
(% Icu) 100% 100%
33
400 (100% Rated Circuit Breaker)
600
2000–4000 3000–6000
33
750 750
88
HC HC
AA
20
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
SECTION 7—MOUNTING CONFIGURATIONS
Refer to circuit breaker installation instructions before installing circuit breaker, accessories or wiring.
FIXED MOUNTING
Section 7—Mounting Configurations
CONNECTIONS
Mounting on Rails
06153071
h
s pu to trip
Mounting on Backplate
06153072
h s u
p
o t p i r
t
Flush Mounting
06153073
h s
pu
to ip r t
See Section 8—Connections for details. Compact® NSF and NSJ circuit breakers suitable for reverse feeding.
Front Connection
06153074
h s u
p
to
p i tr
Rear Connection
06153075
h
s u p
o t
p
i r t
PLUG-IN MOUNTING
06153076
© 1995–2003 Schneider Electric All Rights Reserved
Mounting through Front Panel
06153077
Mounting on Rails
06153078
21
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 7—Mounting Configurations
The plug-in configuration makes it possible to:
Extract and/or rapidly replace the circuit breaker without having to touch connections
Allow for addition of future circuits at a later date
When the circuit breaker is in the connected position, the primary voltage is fed through the circuit breaker by means of multiple finger disconnects. Control voltage of internal accessories is provided through secondary disconnects.
Parts of a Plug-in Configuration
Compact® circuit breaker (fixed mounted)
Set of power and secondary disconnects that are added to the circuit breaker
Plug-in base for mounting through a front panel or on rails
Safety trip, to be installed on the circuit breaker, which causes automatic tripping if the circuit
breaker is ON before engaging or withdrawing it; the safety trip does not prevent circuit breaker operation, even when the circuit breaker is disconnected
Mandatory short terminal shields
The plug-in mounting is Listed under UL file E113555 and Certified under CSA file LR 69561.
DRAWOUT MOUNTING
The chassis is made up of two side plates installed on the base and two other plates mounted on the circuit breaker.
06153079
06153080
Connected
RemovedDisconnected
Chassis Functions All functions of the plug-in base, plus:
Disconnected position: the power circuits are disconnected, the circuit breaker is simply
"withdrawn" and may still be operated (on, off, push-to-trip)
Circuit breaker may be locked using 1 to 3 padlocks—diameter 0.19 to 0.31 inch (5 to 8 mm)—to
prevent connection
Auxiliaries can be tested using manual auxiliary connector
Mounting On a backplate, through a front panel or on rails
Horizontally or vertically
22
© 1995–2003 Schneider Electric All Rights Reserved
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section 7—Mounting Configurations
Accessories Auxiliary switches for installation on the fixed part of the chassis, indicating the "connected" and
"disconnected" positions
Toggle collar for circuit breakers with toggle through front panel, intended to maintain the degree of
protection whatever the position of the circuit breaker (supplied with a toggle extension)
Keylock which, depending on the bolt fitted, can be used to:
— Prevent insertion for connection — Lock the circuit breaker in connected or disconnected position
Telescopic shaft for extended rotary handles
Connection of Auxiliaries
Control voltage is provided through automatic secondary disconnects in the connected position only. See Section 8—Connections for more details. Electrical accessories can be tested in the disconnected position with an external wiring harness.
The drawout-mounted chassis is Listed under UL file E113555 and Certified under CSA file LR 69561.
© 1995–2003 Schneider Electric All Rights Reserved
23
Loading...
+ 53 hidden pages