SAMSUNG AS09A1VE Service Manual

5 (1)

ROOM AIR CONDITIONER

INDOOR UNIT

OUTDOOR UNIT

AS07A1VE

US07A1VE

AS09A1VE/B

US09A1VE/B

AS12A1VE/B

US12A1VE/B

 

 

SERVICE Manual

AIR CONDITIONER

CONTENTS

1. Precautions

2. Product Specifications

3. Operating Instructions and

Installation

4. Disassembly and Reassembly

5. Troubleshooting

6. Exploded Views and Parts List

7. Block Diagrams

8. PCB Diagrams

9. Wiring Diagrams

10. Schematic Diagrams

©Samsung Electronics Co., Ltd. OCT. 1998. Printed in Korea.

Code No. DB81-10196A(1)

1. Precautions

1.Warning: Prior to repair, disconnect the power cord from the circuit breaker.

2.Use proper parts: Use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.)

3.Use the proper tools: Use the proper tools and test equipment, and know how to use them. Using defective tools or test equipment may cause problems later-intermittent contact, for example.

4.Power Cord: Prior to repair, check the power cord and replace it if necessary.

5.Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.

6.After completing repairs and reassembly, check the insulation resistance. Procedure: Prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megohms.

7.Make sure that the grounds are adequate.

8.Make sure that the installation conditions are satisfactory. Relocate the unit if necessary.

9.Keep children away from the unit while it is being repaired.

10.Be sure to clean the unit and its surrounding area.

Fig. 1-1 Avoid Dangerous Contact

Fig. 1-2 No Tapping and No Extension Cords

Fig. 1-3 No Kids Nearby!

Fig. 1-4 Clean the Unit

Samsung Electronics

1-1

M E M O

1-2

Samsung Electronics

2. Product Specifications

2-1 Table

 

 

 

 

 

 

 

 

Model

AS07A1VE

AS09A1VE

AS12A1VE

AS09A1VB

AS12A1VB

Item

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

Outdoor unit

Indoor unit

 

Outdoor unit

Indoor unit

 

Outdoor unit

Indoor unit

 

Outdoor unit

Indoor unit

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

 

 

 

-

Wall-mounting

Wall-mounting

Wall-mounting

Wall-mounting

Wall-mounting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

BTU/h

 

7,500

 

9,000

12,000

 

 

9,000

 

12,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumiditying

 

 

 

I/h

 

1.2

 

1.6

1.9

 

 

1.6

 

1.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Perfor-

Air volume

 

 

Cooling

m3/min

 

6.0

 

6.1

7.8

 

 

6.1

 

7.8

mance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise

 

 

Cooling

dB

35

 

45

35

 

45

38

 

49

36

 

47

39

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency ratio

Cooling

BTU/h.W

 

11.2

 

10.2

10.2

 

 

10.2

 

9.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

V/Hz

1/220 - 240~/50

1/220 - 240~/50

1/220 - 240~/50

1/220/60

1/200/60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Consumption

Cooling

W

 

670

 

880

1180

 

 

880

 

1280

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Current

Cooling

A

 

2.8

 

4.0

5.0

 

 

4.0

 

5.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

 

Cooling

%

 

99.7

 

91.7

98.3

 

 

99.9

 

99.9

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting current

 

A

 

17.0

 

22.0

30.0

 

 

24.0

 

31.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power cord

 

 

Length

m

2

 

-

2

 

-

2

 

-

2

 

-

2

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of core wire

250V 10/16A

250V 10/16A

250V 10/16A

250V 10/16A

250V 10/16A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse capacity

 

 

 

A

3.15

 

-

3.15

 

-

3.15

 

-

3.15

 

-

3.15

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

Width x Height

mm

815x298x182

 

720x532x245

815x298x182

 

720x532x245

815x298x182

 

720x532x245

815x298x182

 

720x532x245

815x298x182

 

720x532x245

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dimension

 

 

x Depth

inch

32.08x11.73x7.17

 

28.35x20.94x9.65

32.08x11.73x7.17

 

28.35x20.94x9.65

32.08x11.73x7.17

 

28.35x20.94x9.65

32.08x11.73x7.17

 

28.35x20.94x9.65

32.08x11.73x7.17

 

28.35x20.94x9.65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

 

 

kg

9.6

 

27

9.6

 

28

9.6

 

31

9.6

 

27

9.6

 

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe

Liquid

OD(mm)x L(m)

ø6.35 x 5

ø6.35 x 5

ø6.35 x 5

ø6.35 x 5

ø6.35 x 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS

 

ø9.52 x 5

ø9.52 x 5

ø12.7 x 5

ø9.52 x 5

ø12.7 x 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

Drain hose

 

 

 

ID(mm)x L(m)

ø17 x 2000

ø17 x 2000

ø17 x 2000

ø17 x 2000

ø17 x 2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

Type

 

 

-

 

Rotary

-

 

Rotary

-

 

Rotary

-

 

Rotary

-

 

Rotary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

Type

 

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output

W

-

 

675

-

 

895

-

 

1210

-

 

879

-

 

1300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower

 

Type

 

 

Cross-fan

 

Propeller

Cross-fan

 

Propeller

Cross-fan

 

Propeller

Cross-fan

 

Propeller

Cross-fan

 

Propeller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

Type

 

Resin

 

Steel

Resin

 

Steel

Resin

 

Steel

Resin

 

Steel

Resin

 

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output

W

35

 

15

35

 

15

35

 

20

35

 

20

35

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

2Row 12Step

 

1Row 20Step

2Row 12Step

 

1Row 20Step

2Row 12Step

 

2Row 20Step

2Row 12Step

 

1Row 20Step

2Row 12Step

 

2Row 20Step

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant control unit

 

 

 

 

CAPILLARY TUBE

CAPILLARY TUBE

CAPILLARY TUBE

CAPILLARY TUBE

CAPILLARY TUBE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Freezer oil capacity

 

 

 

 

 

280

 

360

410

 

 

360

 

410

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant to change(R-22)

 

 

 

670

 

680

930

 

 

660

 

880

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection device

 

 

 

 

-

 

MST24AMN-12008

-

 

MRA12037-12007

-

 

MRA12030-12008

-

 

MRA12093-12007

-

 

MRA12002-9200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling test Condition

 

 

 

 

 

 

INDOOR UNIT : DB27°C WB19°C

 

OUTDOOR UNIT : DB35°C WB24°C

 

INDOOR UNIT : DB27°C WB19.5°C

OUTDOOR UNIT : DB35°C WB24°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum operation Condition

 

 

 

 

INDOOR UNIT : DB32°C WB23°C

 

OUTDOOR UNIT : DB43°C WB26°C

 

INDOOR UNIT : DB32°C WB22.5°C

OUTDOOR UNIT : DB43°C WB25.5°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Samsung Electronics

2-1

 

SAMSUNG AS09A1VE Service Manual

2-2 Dimensions

2-2-1 Indoor Unit

(Front view)

(Remote control)

Air

in

Air out

Installation plate

(Rear view)

2-2-1 Outdoor Unit

 

(Front view)

(Rear view)

2-2

Samsung Electronics

2-3 Refrigerating Cycle Block Diagram

INDOOR UNIT

OUTDOOR UNIT

 

Capillary tube

T

2-way valve

 

 

Liquid side

Heat

Heat

exchanger

exchanger

(Evaporator)

(Condenser)

T

Gas side

 

 

3-way valve

 

Cooling

 

Compressor

 

Gas leak check point

Samsung Electronics

2-3

M E M O

2-4

Samsung Electronics

3. Operating Instructions and Installation

3-1 Operating Instructions

3-1-1 Name & Function of Key in remote controller

NO

 

 

NAMED OF KEY

 

 

FUNCTION OF KEY

 

 

 

 

 

 

 

 

 

1

 

 

 

 

On/Off Button. Use this button to start and stop air conditioner.

 

 

 

 

 

 

 

 

 

 

2

 

 

 

(UP)

Temp. up button. If the

button is pressed once,

 

 

 

 

 

 

the setting temperature is increased by 1°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(DOWN)

Temp. up button. If the

button is pressed once,

 

 

 

 

 

 

the setting temperature is decreased by 1°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

Each time you press this button,

 

: Auto Mode

: Fan Only

 

 

MODE

MODE is changed in the following order.

: Cool Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Dry Mode

 

 

 

 

 

 

 

4

 

TURBO

Use this button to provide heavy duty cooling & Heating for 30 minutes.

 

 

 

 

 

 

 

 

5

 

OFF

 

 

Set up the reserve or cancel the timer on and timer off quickly

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

Use this button for sleep operation.

 

 

 

 

 

 

 

 

(The SLEEP mode can be selected at COOL and HEAT mode.)

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

Adjusts air flow vertically.

 

 

 

 

 

 

 

 

 

Each time you press this button.

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

Each time you press this button,

 

 

 

 

 

 

 

FAN SPEED is changed in the following order.

 

 

 

 

 

 

 

 

 

 

 

9

C

 

ON TIMER

Set up the time that operation start.

 

 

 

 

O

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

V

 

OFF TIMER

Set up the time that operation stop.

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

R

 

SET

Use this button to reserve the timer on.

 

 

 

 

T

 

 

 

 

 

 

 

 

12

 

CANCEL

Use this button to reserve or cancel the timer on and timer off.

 

 

I

 

 

 

M

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

E

 

(UP)

If the

button is pressed once, the time increase by one minute

 

 

 

R

 

during the time set mode, and ten minutes during the timer set mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

(DOWN)

If the

button is pressed once, the time decrease by one minute

 

 

 

 

 

 

 

 

 

 

during the time set mode, and ten minutes during the timer set mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

Without regard to ON/OFF condition in remote controller,

 

 

 

 

 

 

 

 

 

 

TIME

use this button to set current time.

 

 

 

 

 

 

Adjust the current time using

button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Data can be transmitted after setting up the time)

 

 

 

 

 

 

 

 

 

 

 

 

 

Samsung Electronics

3-1

Operating Instructions and Installation

3-1-1 Name & Function of Key in remote controller

1.AUTO MODE : In this mode, operation COOL mode is selected automatically by the room temperature of initial operation.

Operation Type

Room Temp

 

 

 

 

Cool Operation

 

Tr³ 24.5°C+DT

Compressor ON

 

 

 

 

Tr£ 24°C+DT

Compressor OFF

 

 

 

 

 

 

DT= -1°, -2°C, 0°C+1°C+2°C

DT is controlled by setting temperature up/down key of remote controller

*FAN SPEED : AUTO

2.COOL MODE : The unit operates according to the difference between the setting and room temperature. (18°C~30°C)

3.DRY MODE : Has 3 states, each determined by room temperature.

The unit operates in DRY mode. *Compressor ON/OFF Time is controlled compulsorily(can not set up the fan speed, always breeze).

*Protective function : Low temperature release. (Prevention against freeze)

4.TURBO MODE : This mode is available in AUTO, COOL, DRY, FAN MODE.

When this button is pressed at first, the air conditioner is operated “powerful” state for 30 minutes regardless of the set temperature, room temperature.

When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode.

*But, if you press the TURBO button in DRY or FAN mode that is changed with AUTO mode automatically.

5.SLEEP MODE : Sleep mode is available only in COOL mode.

The operation will stop after 6 hours.

*In COOL mode : The setting temperature is automatically raised by 1°C each 1hour When the temperature has been raised by total of 2°C, that temperature is maintained.

6.FAN SPEED : Manual (3 step), Auto (4 step) Fan speed automatically varies depending on both the difference between setting and the room temperature.

3-2

Samsung Electronics

OFF TIMER

7.COMPULSORY OPERATION :

For operating the air conditioner without the remote controller.

*AUTO : The operating is the same function that AUTO MODE in the remote controller.

8.SWING : BLADE-H is rotated vertically by the stepping motor.

*Memory louver : When ON/OFF button is pressed at stop state, the BLADE-H returns to its original location which is operating state before stop

*Swing Set : Press the

button under the

remote control is

on LCD the

and the blades move up and down, about

If the one more time press the button, blatles location is stop.

9.Quick OFF TIMER: OFF timer (quick timer) allows reservation or cancel the timer on and timer off quickly

When OFF timer button is pressed at operating state, LCD displays the polling state sequentially.

The LCD also displays the time remaining.

10.24-Hour ON/OFF Real Setting Timer. : The air conditioner is turned ON at a specified time using ON TIMER .

Operating Instructions and Installation

OFF TIMER : The air Conditioner is turned OFF at a specified time using . *ON TIMER : Only timer LED lights on.

*OFF TIMER : Both timer and operation LED lights on.

*3 minutes delay timer.

11.

SELF Diagnosis

 

 

 

 

LED DISPLAY

Check Point

 

 

 

oper-

TIMER FAN Turbo

 

ation

 

Interruption of electric power and Power on.

Abnormal condition of the room sensor.

Abnormalconditionoftheindoorunit'sheatexchangersensor.

Indoor unit fan motor lock.

: LED

: LED off

blinking

 

12.BUZZER SOUND : Whenever the ON/OFF button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep"

Samsung Electronics

3-3

3-2 Installation

3-2-1 Selecting Area for Installation

Select an area for installation that is suitable to the customer's needs.

3-2-1(a) Indoor Unit

1.Make sure that you install the indoor unit in an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.

2.Make sure that you install the indoor unit in an area allowing good air handling and endurance of vibration of the indoor unit.

3.Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.

4.Make sure that you install the indoor unit in an area from which hot or cool air is spread evenly in a room.

5.Make sure that you install the indoor unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).

6.Make sure that you install the indoor unit in an area which provides easy pipe connection with the outdoor unit, and easy drainage for condensed water.

7.Make sure that you install the indoor unit in an area which is large enough to accomodate the measurements shown in figure on the next page.

3-2-1(b) Outdoor Unit

1.Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.

(Install a separate sunblind if exposed to direct sun light.)

2.Make sure that you install the outdoor unit in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.

(Fix the unit firmly if it is mounted in a high place.)

3.Make sure that you install the outdoor unit in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.

4.Make sure that you install the outdoor unit in area free from animals or plants.

5.Make sure that you install the outdoor unit in area not blocking the traffic.

6.Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit.

7.Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(10 meters).

Note

1.Add 10 grams of refrigerant (R-22) for every 1 meter if the pipe length exceeds the standard pipe length of 5 meters.

2.Maintain a height between the indoor and outdoor units of less than 3 meters.

8.Make sure that you install the outdoor unit in an area which is large enough to accommodate the measurements

shown in figure on the next page.

3-2-1(c) Remote Control Unit

1.Make sure that you install the remote control unit in an area free from obstacles such as curtains etc, which may block signals from the remote control unit.

2.Make sure that you install the remote control unit in an area not exposed to

direct sunlight, and where there is no source of heat.

3.Make sure that you install the remote control unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).

Caution :

It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.

3-4

Samsung Electronics

Operating Instructions and Installation

3-2-2 Installation diagram of indoor unit and outdoor unit

A Indoor unit gas leak test check point

 

Piping may be laid to the rear, left,

 

 

 

right or down .

 

Indoor unit

3

 

 

 

 

 

 

 

Right

 

Left

 

2

 

Rear

Down

Rear

Piping

 

 

 

 

 

 

 

 

 

 

1

Tape vinyl

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B Drain hose installation

200mm or more

250mm or more

Cut the piping hole sloped slightly

5 6

Remote control

Remote control holder

4

10

1

 

Piping (Liquid) 1/4"

6

Clamper tube

 

 

 

 

 

2

7K/9K BTU

Piping(Gas)3/8”

7

Installation plate

12K BTU

 

Piping(Gas)1/2”

 

 

 

 

3

 

Installation tube

8

Pipe-connection

 

 

 

 

 

 

4

 

Vinyl tape

9

Screw

 

 

 

 

 

 

5

 

Putty

10

Drain hose

 

 

 

 

 

 

Samsung Electronics

3-5

Operating Instructions and Installation

3-2-2(a) Fixing the Installation Plate

Installation plate

Pipe hole (ø65mm)

(Unit : mm)

280

340

1.Determine the position of the pipe and drain hose hole using the right figure and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.

2.If you are fixing the indoor unit to a… Then follow Steps…

Wall

3.

Window frame

4 to 6.

3.Fix the installation plate to the wall in a manner appropriate to the weight of the indoor unit.

If you are mounting the plate on a concrete wall with anchor bolts, the anchor bolts must not project by more than 20mm.

(Unit : mm)

3-2-2(b) Purging the Unit

4.Determine the positions of the wooden uprights to be attached to the window frame.

5.Attach the wooden uprights to the window frame in a manner appropriate to the weight of the indoor unit.

6.Using tapped screws, attach the installation plate to the wooden uprights, as illustrated in the last figure opposite.

On delivery, the indoor unit is loaded with an inert gas. All this gas must therefore be purged before connecting the assembly piping. To purge the inert gas, proceed as fol - lows.

Unscrew the caps at the end of each pipe.

Result : All inert gas escapes from the indoor unit.

To prevent dirt or foreign objects from getting into the pipes during installation, do NOT remove the caps completely until you are ready to connect the piping.

3-6

Samsung Electronics

Operating Instructions and Installation

3-2-2(c) Connecting the Assembly Cable.

< AS09A1VB / AS12A1VB >

Indoor unit

Outdoor unit

< The others >

The outdoor unit is powered from the indoor unit via the assembly cable. If the outdoor unit is more than five metres away from the indoor unit, the cable must first be extended to a maximum of

ten metres.

1.Extend the assembly cable if necessary.

2.Open the front grille by pulling on the tabs on the lower right and left sides of the indoor unit.

3.Remove the screw securing the connector cover.

4.Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals 1, 3, 5(1,2,3,5).

• Each wire is labelled with the corresponding terminal number.

5.Pass the other end of the cable through the 65mm hole in the wall.

6.Replace the connector cover, carefully tightening the screw.

7.Close the front grille.

8.For further details on how to plug the other end of the assembly cable into the outdoor unit, refer to page 12.

Indoor unit

Outdoor unit

Samsung Electronics

3-7

Operating Instructions and Installation

3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose

Care must be taken when installing the drain hose for the indoor unit to ensure that any condensa - tion water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled in the wall, check that none of the following situations occur.

 

 

 

 

 

 

 

The hose must

The end of the drain

 

Do NOT bend the

 

Keep a clearance of at

NOT slope upw

hose must NOT be

 

hose in different

 

least 5cm between the

ards.

placed in water.

 

directions.

 

end of the hose and the

 

 

 

 

 

 

ground.

Do NOT place the end of the drain hose in a hollow.

To install the drain hose, proceed as follows.

1.If necessary, connect the 2-metre extension to the drain hose.

2.If you are using the extension, insulate the inside part of the extension drain hose with a shield.

3.Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.

4.Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as shown in the illustrations above.

Shield

Drain hose

Extension drain hose

The hose will be fixed permanently into position once the whole installation has been tested for gas leaks; refer to page 16 for further details.

3-2-2(e) Outdoor unit installation

Wiring connection

1.Remove the cover-E parts.

2.Firmly connect the cable connector in the terminal block.

3.Fasten the M4 ring terminal to the hole marked

4.Firmly fix the ass'y cable with clamp wire holder.

5.Assemble the cover-E parts.

6.To prevent the entry of water, form a trap of the ass'y cable as illustrated in the installation diagram of indoor and outdoor unit.

Cover-E parts

Cover-E parts

Screw

Screw

<AS12A1VB/AS09A1VB ONLY>

<OTHERS MODEL>

3-8

Samsung Electronics

Operating Instructions and Installation

3-2-2(f) Flare Modification

• Tools used

Flare modification procedure

1) Cut the pipe using a pipe cutter.

 

2) Remove burrs at the tip of the pipe cut.

 

 

Caution : Burrs not removed may result in

 

 

leakage of gas.

 

 

Pipe

Oblique Raughness

Burr

Reamer

 

3) Insert a flare nut into the pipe and

 

 

 

 

 

 

modifty flare.

D

 

 

 

 

 

Outer diameter

A(mm)

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

ø6.35mm

1.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø9.52mm

1.8

 

 

 

 

 

 

 

 

 

 

 

 

ø12.7mm

2.0

 

 

 

 

 

 

 

* Unproper flaring

Inclined

 

Surface

 

Cracked

Uneven

 

 

damaged

 

 

thickness

 

 

 

 

 

 

 

 

 

Samsung Electronics

3-9

Operating Instructions and Installation

3-2-2(g) Air-Purge Procedure

Use the refrigerant of the outdoor unit to purge air inside indoor unit and pipe.

1.Remove the caps from the 2-way valve(B) and the 3-way valve(A).

2Turn the 2-way valve cock approx. 45° counterclockwise to open it. Close it about 10 seconds later.

Valve stem

Valve stem

Stopper

3Check refrigerant leakage of each joint parts (A, B, C & D in right figure)

Leaking

not

leaking If leaking, tighten the flare nut one more time. If continues to leak, although the pipe fixing area has been tightened again,

repair the leaking area.

4.Open the 2-way valve again.

5.Open the service valve cap of the 3-way valve and press the needle valve to discharge gas for 3 seconds and leave it for about 1 minute.

Repeat the above procedure for 3 times to purge air.

Indoor Unit

Liquid pipe side

Gas pipe side

6.Open the 2-way valve and 3-way valve completely

2-way valve

3-way valve

Outdoor Unit

7.Close the cap of each valve.

8.Check each valve for leakage.

3-10

Samsung Electronics