Rockwell Automation 20-HIM-C6S User Manual

User Manual
PowerFlex 20-HIM-A6 and 20-HIM-C6S HIM (Human Interface Module)
FRN 1.xxx - 2.xxx

Important User Information

IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, TechConnect, and PowerFlex are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual contains new and updated information.

Summary of Changes

New and Updated Information

This table contains the changes made to this revision.
Top ic Pa ge
Revised steps in various procedures to add clarity. Throughout
manual
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 3
Summary of Changes
Notes:
4 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Table of Contents

Preface
Getting Started
Installing the HIM
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Technical Product Assistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
HIM Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 2
Installing the 20-HIM-A6 HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
In the Drive HIM Bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Using Drive Port 2 Connection for Hand-Held Operation . . . . . . 16
In a Remote-Mount HIM Bezel (20-HIM-B1). . . . . . . . . . . . . . . . . . 17
Installing the 20-HIM-C6S HIM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Removing the HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 3
HIM Components
HIM Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Soft Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Navigation and Number Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Single-function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
LCD Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Status Bar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Data Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Soft Key Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Main Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Process Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Control Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Folder Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fault Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 5
Table of Contents
Chapter 4
Using the HIM
Initial HIM Operation on New Drive Powerup. . . . . . . . . . . . . . . . . . . . . 31
Selecting Display Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Setting the Date/Time for PowerFlex 750-Series Drives . . . . . . . . . . . . . 33
Creating a User-Defined Drive/Peripheral Name . . . . . . . . . . . . . . . . . . . 35
Customizing the Process Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Selecting Multi-Line or Single-Line View . . . . . . . . . . . . . . . . . . . . . . . 36
Changing Displayed Items, Adding a Scale Factor,
or Customizing Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Resetting the Drive/Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Setting Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Setting PowerFlex 750-Series Drives/Peripherals
to Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Setting PowerFlex 7-Class Drives/Peripherals
to Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Setting Display Flashing for Fault Indication . . . . . . . . . . . . . . . . . . . . . . . 40
Setting Display Flashing for Alarm Indication . . . . . . . . . . . . . . . . . . . . . . 41
Viewing/Editing Drive or Peripheral Parameters . . . . . . . . . . . . . . . . . . . . 42
Selecting File-Group-Parameter or Linear List View . . . . . . . . . . . . . 42
Direct Parameter Access Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Alternate Linear List Access Method . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Viewing/Clearing Drive Faults or Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Viewing Peripheral Diagnostic Items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Viewing/Clearing Peripheral Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Checking Drive and Peripheral Firmware Revisions . . . . . . . . . . . . . . . . . 47
Using the CopyCat Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Creating CopyCat Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Renaming CopyCat Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Deleting CopyCat Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Changing PowerFlex 750-Series Drive Parameter Associations . . . . . . . 52
Using Individual Screen Entry Method. . . . . . . . . . . . . . . . . . . . . . . . . 52
Using Direct Numeric Entry Method . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Linking Parameters in PowerFlex 700/700S Drives . . . . . . . . . . . . . . . . . 55
Establishing a Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Deleting an Established Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Using a Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Setting/Changing the Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Changing Password-protected Drive/Peripheral Parameters. . . . . . 58
Disabling Password Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Initiating PowerFlex 750-Series Drive Port Verification . . . . . . . . . . . . . 60
Conflict Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Resolving ‘Changed’ or ‘Requires Configuration’ Conflicts. . . . . . . 61
Resolving ‘Not Functioning’, ‘Not Supported’,
or ‘Invalid Duplicate’ Conflicts. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Changing Language for the Display Text . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Updating the HIM Firmware or Language . . . . . . . . . . . . . . . . . . . . . . . . . 63
6 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Appendix A
Table of Contents
Specifications
HIM Parameters
History of Changes
Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Regulatory Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Appendix B
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Appendix C
20HIM-UM001C-EN-P, January 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
20HIM-UM001B-EN-P, October 2010 . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
20HIM-UM001A-EN-P, January 2009 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Index
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 7
Table of Contents
Notes:
8 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Preface

This manual provides information about the enhanced PowerFlex 20-HIM-A6 and 20-HIM-C6S Human Interface Modules, and using them with PowerFlex 750-Series drives and PowerFlex® 7-Class drives.

Conventions Used in This Manual

Rockwell Automation Support

The following conventions are used throughout this manual:
Parameter names are shown in the format Parameter xx - [*]. The xx represents the parameter number. The * represents the parameter name— for example Parameter 01 - [Port Number].
The HIM or drive firmware revision number (FRN) is displayed as FRN X.xxx, where ‘X’ is the major revision number and ‘xxx’ is the minor revision number.
Rockwell Automation offers support services worldwide, with over 75 sales and support offices, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation representatives are in every major country in the world.

Local Product Support

Contact your local Rockwell Automation representative for the following:
Sales and order support
Product technical training
Wa rr an ty sup po rt
Support service agreements

Technical Product Assistance

For technical assistance, please review the information in Chapter 4, Using the HIM, first. If you still have problems, then access the Allen-Bradley Technical Support website at http://www.ab.com/support/abdrives Automation.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 9
or contact Rockwell
Preface

Additional Resources

Resource Description
PowerFlex 750-Series AC Drive Installation Instructions, publication 750-IN001 Information on installing and programming PowerFlex 750-Series AC drives
PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001
PowerFlex 750-Series AC Drives Technical Data, publication 750-TD001
PowerFlex 70 User Manual, publication 20A-UM001
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70 Enhanced Control and 700 Vec tor Control Reference Manual, publication PFLEX-RM004
PowerFlex 700 Series A User Manual, publication 20B-UM001
PowerFlex 700 Series B User Manual, publication 20B-UM002
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70 Enhanced Control and 700 Vec tor Control Reference Manual, publication PFLEX-RM004
PowerFlex 700H Installation Instructions, publication PFLEX-IN006 Information on installing and programming PowerFlex 700H drives.
PowerFlex 700H Programming Manual, publication 20C-PM001
PowerFlex 700S with Phase I Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S with Phase I Control Installation Manual (Frames 9 and 10), publication PFLEX-IN006
PowerFlex 700S with Phase I Control User Manual (All Frame Sizes), publication 20D-UM001
PowerFlex 700S with Phase I Control Reference Manual, publication PFLEX-RM002
PowerFlex 700S with Phase II Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S with Phase II Control Installation Manual (Frames 9…14), publication PFLEX-IN006
PowerFlex 700S with Phase II Control Programming Manual (All Frame Sizes), publication 20D-PM001
PowerFlex 700S with Phase II Control Reference Manual, publication PFLEX-RM003
PowerFlex 700L User Manual, publication 20L-UM001 Information on installing and programming PowerFlex 700L Liquid-Cooled
PowerFlex Digital DC Drive User Manual, publication 20P-UM001
These documents contain additional information concerning related products from Rockwell Automation.
Information on installing and programming PowerFlex 70 standard control
and enhanced control drives.
Information on installing and programming PowerFlex 700 standard control
and vector control Series A drives, and PowerFlex 700 vector control Series B drives.
Information on installing and programming PowerFlex 700S drives.
AC dri ves.
Information on installing and programming PowerFlex Digital DC drives.
You can view or download publications at http://
literature.rockwellautomation.com. To order paper copies of technical
documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related questions, go to the Drives Service & Support website at http://www.ab.com/support/
abdrives and click the Downloads or Knowledgebase link.
10 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
.

Chapter 1

Getting Started

The PowerFlex 20-HIM-A6 and 20-HIM-C6S HIMs provide a communication interface to configure and monitor PowerFlex 753 and PowerFlex 755 AC drives and their connected peripherals. These HIMs are also backward compatible with all PowerFlex 7-Class drives, but with limited functionality.
Top ic Pa ge

HIM Types

Featu res

Compatible Produ cts
Safety Precautions 12
11
11
12
HIM Types
Features
At the time of publication, the following enhanced PowerFlex 7-Class HIMs are available.
HIM Catalog Number Description
20-HIM-A6
20-HIM-C6S
(1) Supports English, Portuguese, French, Italian, German, Spanish, and Dutch
The enhanced PowerFlex 20-HIM-A6 and 20-HIM-C6S HIMs provide the following benefits over the more basic PowerFlex 7-Class HIMs (catalog numbers 20-HIM-A3, 20-HIM-A5, 20-HIM-C3S, and 20-HIM-C5S):
(1)
(1)
languages. The HIM firmware can be updated in the field to support other available languages. Important: The language selected for download at the Rockwell Automation Web Updates website at http://www.ab.com/support/abdrives/
webupdate will replace all other supported languages—except English, which will
always remain as the default language.
Full-numeric keypad with fully-integrated navigation capability to more easily configure and monitor the drive and its connected peripherals.
Better keypad touch response and improved tactile feel to provide more gratifying, error-free data entry.
NEMA Type 1 HIM
Remote-Mount NEMA Type 4X/12 HIM
More intuitive access and new menu structures that increase HIM operating efficiency.
Simplified custom name assignments for drive/peripherals (for example, Pump 1) to reduce required key presses.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 11
Chapter 1 Getting Started
Support for English, and customary European and Asian languages.
Dynamic soft keys that change functions/names based on screen or data
entry mode to reduce keypad keys and simplify HIM operation.
Customizable drive monitoring items that can be displayed as a list on the process screen or as individual screens.
New flashing LCD screen to provide enhanced visibility when faults or alarms are detected.

Compatible Products

Safety Precautions

At the time of publication, the 20-HIM-A6 and 20-HIM-C6S HIMs are compatible with the following products:
PowerFlex 753 drives
PowerFlex 755 drives
PowerFlex 70 drives with standard or enhanced control
PowerFlex 700 drives with standard or vector control
PowerFlex 700H drives
PowerFlex 700S drives with Phase I or Phase II control
PowerFlex 700L drives with 700 vector control or 700S control
PowerFlex 700AFE (Active Front End)
PowerFlex Digital DC drives
PowerFlex 7000 drives
SMC™ Flex smart motor controllers
SMC-50 smart motor controllers
Please read the following safety precautions carefully.
AT TE NT IO N: Risk of injury or death exists from machine motion when using the HIM to Start/Stop/Jog or configure the drive.
AT TE NT IO N: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the associated machinery should plan or implement the installation, startup, configuration, and subsequent maintenance of the product using the HIM. Failure to comply may result in injury and/or equipment damage.
12 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Chapter 2

20-HIM-A6 HIM 20-HIM-C6S HIM

Installing the HIM

This chapter provides instructions for installing and removing the HIM.
Top ic Pa ge
Installing the 20-HIM-A6 HIM 14
Installing the 20-HIM-C6S HIM 18
Removing the HIM
There are two types of enhanced PowerFlex 7-Class HIM:
NEMA Type 1 (catalog number 20-HIM-A6)
Remote-mount NEMA Type 4X/12 (catalog number 20-HIM-C6S),
which also includes a 1202-C30 interface cable for connection to the drive
20
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 13
Chapter 2 Installing the HIM
TIP
(PowerFlex 755 drive shown)
Drive HIM Bezel
20-HIM-A6 HIM
IN
DOWN

Installing the 20-HIM-A6 HIM

The 20-HIM-A6 (NEMA Type 1) HIM is normally installed in the HIM bezel (drive Port 1) on the front of the drive. For temporary hand-held operation, the HIM can be plugged into drive Port 2 (near the bottom of the drive control pod for PowerFlex 750-Series drives, or on the bottom of the drive for PowerFlex 7­Class drives) using a 1 m/3.28 ft. long 20-HIM-H10 cable. For applications requiring the HIM to be located remotely, the HIM can be installed in a remote­mount HIM bezel (catalog number 20-HIM-B1) in a suitable location. The 20­HIM-B1 remote-mount HIM bezel includes a 3 m/9.8 ft. long 1202-C30 cable.
In the Drive HIM Bezel
PowerFlex 750-Series IP20, NEMA/UL Open Type Drives
Place the HIM into the drive HIM bezel by inserting it straight back into the top of the bezel and then sliding it down into the base of the bezel onto the mating connector.
The HIM can be installed in the drive HIM bezel with the drive powered or unpowered.
14 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Installing the HIM Chapter 2
2x: M4 x 0.7
PowerFlex 750-Series IP54, NEMA/UL Type 12 Drives
1. Unfasten and remove the cover as shown below using the following recommended tools:
Screwdriver: 6.4 mm (0.25 in.) flat or T20 Hexalobular
Hex socket: 7 mm
2. Place the HIM into the drive HIM bezel by inserting it straight back into
the top of the bezel and then sliding it down into the base of the bezel onto the mating connector as shown on page 14
3. Replace the cover and the fasteners.
4. Tighten all screws and nuts to the recommended torque of 0.68 N•m (6.0
lb•in).
.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 15
Chapter 2 Installing the HIM
PE
PE
20-HIM-A6 HIM
20-HIM-H10 Cable (1 m/3.28 ft. long)
Port 2
(PowerFlex 755 drive
shown with cover
removed)
Port 2
(PowerFlex 70
drive shown)
20-HIM-A6 HIM
20-HIM-H10 Cable (1 m/3.28 ft. long)
Using Drive Port 2 Connection for Hand-Held Operation
PowerFlex 750-Series Drive
Attach a 20-HIM-H10 cable to the bottom of the HIM. Then plug the other end of the cable into Port 2 near the bottom of the drive control pod.
PowerFlex 7-Class Drive
Attach a 20-HIM-H10 cable to the bottom of the HIM. Then plug the other end of the cable into Port 2 on the bottom of the drive.
16 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Installing the HIM Chapter 2
PowerFlex 755 drive shown
(without HIM in drive HIM bezel)
20-HIM-B1
Remote-Mount
HIM Bezel
3 m/9.8 ft. long 1202-C30 bezel cable included with 20-HIM-B1 remote-mount HIM bezel. Distances can be increased up to 75 m/246 ft.
(1)
(1) To increase this distance, use one of the following cables:
1202-H03 Extension cable (0.3 m/0.98 ft. long)
1202-H13 Extension cable (1.0 m/3.28 ft. long)
1202-H30 Extension cable (3.0 m/9.8 ft. long)
1202-CBL-KIT-100M cable
Note that a cable distance greater than 30 m/98.4 ft. is not CE compliant.
20-HIM-A6 HIM
b. Sl ide down .
a. Push in.
In a Remote-Mount HIM Bezel (20-HIM-B1)
1. If the remote-mount HIM bezel is not mounted, see the HIM Bezel Installation Instructions, publication 20HIM-IN002, for mounting details.
2. Route the 3 m/9.8 ft. long 1202-C30 bezel cable (included with the 20­HIM-B1 remote-mount HIM bezel) to the drive.
3. Connect the bezel cable to the DPI Port 2 on the drive as shown on
page 16
4. Install the HIM into the remote-mount HIM bezel.
for a PowerFlex 750-Series drive or a PowerFlex 7-Class drive.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 17
Chapter 2 Installing the HIM
TIP
Dimensions are in millimeters and (inches).

Installing the 20-HIM-C6S HIM

The 20-HIM-C6S (NEMA Type 4X/12) HIM is designed for remote installation and includes a 3 m/9.8 ft. long 1202-C30 cable. See Figure 1 overall HIM dimensions. Choose an appropriate location to mount the 20-HIM­C6S HIM. The distance between the HIM and drive can be increased up to 75 m/246 ft. by using a 1202-Hxx extension cable or 1202-CBL-KIT-100M cable kit. However, a cable distance greater than 30 m/98.4 ft. is not CE compliant.
Figure 1 - 20-HIM-C6S HIM Dimensions
25.0
(0.98)
3.0 m/9.8 ft. long 1202-C30 cable (included with 20-HIM-C6S HIM)
93.0
(3.66)
for
180.0 (7.08)
1202-Hxx Extension Cable
(supplied separately, and only
needed if required distance
exceeds 1202-C30 Cable length)
1. Drill the required hole pattern in the panel. See Figure 2 for dimensions.
A conversion template (part number 336745-C01), provided with the 20-HIM-C6S HIM, includes a drilling pattern and mounting instructions to assist with HIM installation.
1202-H03 = 0.3 m/0.98 ft. long 1202-H10 = 1.0 m/3.28 ft. long 1202-H30 = 3.0 m/9.80 ft. long
18 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Figure 2 - Hole Pattern to Mount the 20-HIM-C6S HIM
IMPORTANT
Dimensions are in millimeters and (inches).
Front View
0.68 N•m (6.0 lb•in)
Mounting Panel
67.0
(2.63)
60.0
(2.36)
Ø 19.1
(0.75)
Ø 4.8
(0.19)
Installing the HIM Chapter 2
77.0
(3.03)
59
(2.32)
77.0
(3.03)
2. Peel the protective film from the gasketed surface on the back of the HIM.
Adhesive coated gasket is designed for one-time only installation.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 19
Chapter 2 Installing the HIM
IMPORTANT
3. Insert the supplied 3 m/9.8 ft. long 1202-C30 HIM cable into the mating socket on the back of the HIM.
4. Install the supplied O-ring into the cable routing hole on the panel to protect the cable.
5. Route the HIM cable through the cable routing hole on the panel.
6. Align the six threaded studs of the HIM with the panel clearance holes,
and place the HIM against the panel.
7. Tighten the nuts onto the six threaded studs of the HIM extending behind the panel.
Recommended torque is 0.68 N•m (6.0 lb•in).
8. Route the HIM cable to the drive.
9. Connect the HIM cable to the DPI Port 2 on the drive as shown on
page 16
for a PowerFlex 750-Series drive or a PowerFlex 7-Class drive.

Removing the HIM

ATTENTION: Risk of injury or equipment damage exists. If the HIM cable or
remote-mount HIM bezel cable is disconnected from DPI Port 2 on the drive, the drive may fault. Determine how the drive will respond before disconnecting the cable.
The Host drive can remain powered when removing the HIM. However, a fault will occur if the HIM is not the last controlling device and does not have Manual control of the Host drive. To avoid a fault in this case, access the HIM Control
screen (shown on page 28 from the Host drive.
Remove the HIM from the drive HIM bezel or the remote-mount HIM bezel in reverse order of how it was installed.
), press the key, and then remove the HIM
20 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

HIM Components

This chapter describes the components of the HIM.
Top ic Pag e
HIM Keypad 21
LCD Di spla y Ele ment s 24
Main Screens
26

Chapter 3

HIM Keypad

The keypad consists of soft keys, navigation and number keys, and single-function keys, which are described in their respective subsections that follow.
Soft Keys
The soft keys on the HIM are located at the top of the keypad and highlighted below. Depending on the screen being displayed or the data entry mode being used, a soft key name and its function changes. When a dynamic soft key (up to a maximum of five keys) is active, its present function and corresponding Soft Key Label (Figure 3 soft keys, their names, and corresponding functions, see Soft Key Labels
page 25.
) is shown at the bottom of the HIM screen. For a list of possible
on
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 21
Chapter 3 HIM Components
Navigation and Number Keys
The five blue multi-function keys (2, 4, 5, 6, and 8) shown below are used to do the following:
Enter their respective numeric value
Scroll menus/screens
Perform corresponding functions displayed in the Data Area (see page 24
Multi-function Key Name Function
2/Down Arrow Enters the numeric val ue ‘2’.
Scrolls down to select an item.
4/Left Arrow Enters the numeric val ue ‘4’.
Scrolls left to selec t an item.
5/Enter Enters the numeric val ue ‘5’.
Displays the next level of a selected menu item.
Enters new values.
Performs intended actions.
6/Right Arrow Enters the numeric val ue ‘6’.
Scrolls right to select an item.
8/Up Arrow Enters the numeric value ‘8’.
Scrolls up to select an item.
)
The five gray number keys (0, 1, 3, 7, and 9) are used only to enter their respective numeric value.
22 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
HIM Components Chapter 3
Single-function Keys
There are four single-function keys, which are highlighted below and listed in the table below. Each single-function key always performs only its dedicated function.
Single-function Key Name Func tion
Start Starts the drive.
(1)
(1)
(1) During drive Start Up these keys are temporarily inactive.
Folders Accesses folders for parameters, diagnostics, memory functions,
preferences, and other tasks.
Controls Accesses jog, direction, auto/manual, and other control functions.
Stop Stops the drive or clears a fault.
This key is always active.
This key is controlled by drive parameter 307 [Start Stop Mode].
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 23
Chapter 3 HIM Components
Status Bar
Data Area
Soft Key Labels
Stopped
0.00 Hz
AUTO
Host Drive 240V 4.2A 20G...D014
ESC REF TEXT
F
PAR#
Stopped
0.00 Hz
AUTO
F
00
Host Drive 240V 4.2A 20G...D014

LCD Display Elements

The basic HIM screen is divided into three display zones, which are shown in
Figure 3
Figure 3 - HIM Display Zones
and described in their respective subsections that follow.
00
Status Bar
The Status Bar provides operating status information for the host drive.
Status Bar Element Meaning
Host Icon A small image of the connected host drive.
Stopped Status Text Indicates present host drive operating status.
Text flashes when a fault is present.
0.00 Hz Feedback Indicates drive output feedback (for example, Hz, RPM, amps, etc.)
AUTO/MAN Mode Indication Indicates Auto or Manual HIM status.
Alarm Indication Bell icon indicates that an alarm is present.
F or R (not shown) Rotation Indication Indicates Forward or Reverse direction of host drive operation.
DLX (not shown) DeviceLogix Indication Indicates when the host drive DeviceLogix feature is enabled.
Data Area
The Data Area displays the data or function presently being acted upon.
Data Area Element Meaning
Host or Device Icon Image of the host drive or image of the device connected to the port
00
Host Drive User-Definable Text Top line of text in the Data Area can be edited by the user.
Port Selection Indicates selected port. Use the or navigation keys to
selected.
select a port.
24 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
ESC VIEW REF TEXTPAR#
Soft Keys
Soft Key Labels
HIM Components Chapter 3
Soft Key Labels
The Soft Key Labels identify the present function of a corresponding Soft Key on the Key Pad. Different screens may show different Soft Key Labels.
Soft Key Label Name Function
. Decimal Point Adds decimal point to the right-most position of a numeric value.
Backspace Deletes the charac ter to the left of the cursor.
+ / - Sign Changes the sign of a parameter value.
# Number Selects the Direct Numeric Entry Method to change PowerFlex 750-Series drive parameter associations.
Language Directly accesses the Sele ct Language To Use screen.
Scroll Up Scrolls up through display lines.
Scroll Down Scrolls down through display lines.
Scroll Left Scrolls left through display lines.
Scroll Right Scrolls right through display lines.
ACK Acknowledge Acknowledges the fault or alarm on the pop-up screen, stops the backlight from flashing, and keeps the pop-up
ALL All Clears all faults, alarms or events when a pop-up box appears from a queue screen.
CLR Clear Deletes an entire text string.
DEL Delete Deletes a highl ighted character.
EDIT Ed it Accesses a displayed parameter to edit.
END End Displays the end (least recent) fault, alarm or event in a queue
ENTER Enter Displays the next level of a selected menu item.
ESC Escape Cancels port verification conflict pop-up box during procedure to resolve a conflict.
EXP Exponent Allows data entry using scientific notation for 32-bit REAL (floating point) values.
FIX Fix Fixes ‘Changed’ or ‘Requires Configuration’ por t verification conflicts upon power up.
INFO Information Shows additional information about a selected port verification conflict upon power up.
INS Insert Inser ts a space to the left of a highlighted character.
LINK Link Displays a Link Edit pop-up box to link parameters (only PowerFlex 7-Class drives).
LOWER L
wer Displays the lower 16 bits (bits 0…15) of a 32-bit Bit-type parameter.
o
Increases a value.
Decreases a value.
screen active.
Restores all Host or Port device parameters to factory defaults.
Displays the Select Action pop-up box used to clear the selected fault, alarm or event, or the entire fault,
alarm or event queue.
Accesses the Edit Process Display screen.
Scrolls to the end line of data on the Device Version information screen.
Enters new values.
Performs the intended action.
Cancels the existing screen and returns to the previous screen.
Cancels an entr y.
Cancels pop-up Fault Display screen.
Displays the time zone groups list screen (only when the Date/Time Set Edit Mode screen is shown).
Shows additional information about Set Default actions.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 25
Chapter 3 HIM Components
For PowerFlex 750-Series Drive For PowerFlex 7-Class Drive
Stopped
0.00 Hz
AUTO
Host Drive 240V 4.2A 20G...D014
ESC REF TEXT
F
PAR#
00
Stopped
0.00 Hz
AUTO
Host Drive 240V 4.2A Rev 3.002 Ser. A
ESC REF TEXT
F
PAR#
Soft Key Label Name Func tion
MOST Most Restores most Host or Port device parameters to factory defaults.
PAR# Parameter Number Navigates directly to a parameter.
PGDN Page Down Scrolls down to the next page of data lines on the Device Version information screen.
PGUP Page Up Scrolls up to the previous page of data lines on the Device Version information screen.
REF Reference Enters the speed reference for the Host Drive.
RESET Reset Resets the Process screen’s displayed monitoring items to the factory default monitoring items listed on page 36
TEXT Text Edits user-definable text for the device se lected.
TOP To p Displays the top (most recent) fault, alarm or event in a queue.
UPPER Upper Displays the upper 16 bits (bits 16…31) of a 32-bit Bit-type parameter.
VIEW Vi ew Toggles between select screens and views.
ZONES Zones Disp lays the Selec t Time Zone screen.
.
Scrolls to the top line of data on the Device Version information screen.
Displays the time stamp screen from a fault, alarm or event queue screen.

Main Screens

The HIM main screens include the Status screen, Process screen, Control screen, Folder screens, and Fault Display screens, which are described in their respective subsections that follow.
Status Screen
On power up, the Status screen (Figure 4) is shown by default. Depending on the type of host drive, the Status screen displays the following information.
Displayed Information
Selected device icon and port number ✔✔
Device name
Rating text (volts, amps) ✔✔
Drive catalog text not applicable
Firmware version and hardware series
(1) The displayed default device name is dependent on the host drive. The device name can be
(2) The firmware version and hardware series for a PowerFlex 750-Series drive can be shown using
(1)
changed, for example, to Host Drive as shown in the screens below. See Creating a User-Defined
Drive/Peripheral Name on page 35 for details.
HIM me nu screens. Fo r details, s ee Checking Drive and Peripheral Firmware Revisions
Host PowerFlex Drive
750-Series 7-Class
✔✔
(2)
on page 47.
26 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Figure 4 - Example Status Screens
00
00
Stopped
0.00 Hz
AUTO
0.00
0.000
0.00
VIEWFREF PAR#
Amps Bus VDC Out Vlts
EDITESC
HIM Components Chapter 3
Status Screen Soft Keys
Label Name Function
ESC Escape Toggles between the Status and Process Display screens.
Language Icon Directly accesses the Select Language To Use screen.
REF Reference Enters the speed reference for the Host Drive.
PAR# Parameter Number Directly accesses a parameter for the device on selected port. (This soft key is
not available if the device has no parameters.)
TEXT Text Edits user-definable text for the device on selected port.
Status Screen Navigation/Number Keys
Key Name Function Screen Element
4/Left Arrow Selects the device on previous port.
6/Right Arrow Selects the device on next port.
If you would rather see the Process screen (shown below) as the initial power-up screen, change the HIM Parameter 03 - [Initial Screen] value to ‘1’ (Process Scrn). By default, when the HIM keys are not used for the time period set in Parameter 07 - [User Dspy Time], the screen being displayed at that time will revert back to the initial screen. You can disable this feature by setting Parameter 06 - [User Dspy Enable] to ‘1’ (Disable).
Process Screen
To display the Process screen, press the ESC soft key on the Status screen (Figure 4 line and Single-line views can be selected by pressing the VIEW soft key. The displayed default monitoring parameters can be changed. See Customizing the
Process Screen on page 36 for details.
). The Process screen shows various drive monitoring parameters. Multi-
Process Screen Soft Keys
Label Name Function
ESC Escape Toggles between the Process Display and Status screens.
VIEW View Toggles between the multi-line and single-line views.
REF Reference Enters the speed reference for the Host Drive.
PAR# Parameter Number Directly accesses a parameter for the selected port device.
EDIT Edit Directly accesses the Edit Process Display screen.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 27
Chapter 3 HIM Components
IMPORTANT
ESC
REF
MANUAL
FBKREF
REMOVE
HIM
EDIT
REF
FWDREV 
REF
JOG HELP
Control Sc reen Key Functio n Map
corresponds to Navigation/Number Keys
See table below for key functions
Stopped
0.00 Hz
AUTO
F
Process Screen Navigation/Number Keys
Key Name Function Screen Element
8/Up Arrow Scrolls up through the display lines.
2/Down Arrow Scrolls down through the display lines.
Control Screen
The Control screen (shown below) is used to directly control the drive. It displays vertical bar graphs of the drive’s speed Reference and Feedback values, and a Key Function Map that corresponds to the navigation/number keys for drive control.
Press the (Controls) key to display the Control screen.
To navigate from the Control screen to another HIM menu screen, you must always press the ESC soft key to deactivate the Control screen and display the previous screen.
Control Screen Soft Key
Label Name Function
ESC Escape D eactivates the Control S creen and reverts back to the previous screen.
Control Screen Navigation/Number Keys
Label Key Function
JOG Jogs the host drive.
28 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
REF HELP Displays Rockwell Automation Drives Technical Support direct phone number, website
REV Sets the direction to reverse for the host drive.
EDIT REF
FWD Sets the direction to forward for the host drive.
REMOVE HIM
REF
MANUAL Switches between Auto and Manual modes.
Decreases the speed reference for the host drive.
address, and email address.
Allows direct data entry of the speed reference for the host drive.
Allows HIM removal without causing a fault if the HIM is not the last controlling device. (The REMOVE HIM label is not available when the HIM has manual control of the host drive. In this case, a fault will occur if the HIM is removed.)
Increases the speed reference for the host drive.
HIM Components Chapter 3
ESC
DEV PARAM
Linear List
File-Group Changed Parameters Param Access Level
Stopped
0.00 Hz
AUTO
F
Folder Screens
The drive and each connected peripheral has its own set of Folder screens:
Folder Screen Description
PORTS Displays a list of host drive por ts to which peripherals are connected. The host drive is always Port
DEV PARAM Displays a list of available methods to access the device’s parameters.
HOST PARAM
DIAGNOSTIC Displays a list of available diagnostic information items for the device.
MEMORY Displays a list of available memory storage items for the device.
PROPERTIES Displays a list of available user-defined convenience functions for the device.
START UP Displays a list of available host drive start-up routines. This folder is not applicable for peripheral
(1) The HOST PARAM folder screen is only available for PowerFlex 750-Series peripherals that support use of Host Dri ve parameters (for
example, the 20-750-DNET DeviceNet network communication option module).
To display the last-viewed Folder screen, press the (Folders) key. The Folder screen Data Area displays:
Selected device and port number
Host drive and peripheral folders
00. An icon appears for the device occupying the selected port.
(1)
Displays a list of available methods to access the host drive parameters.
devices and is not shown.
Figure 5 - Example Folder Screen (Device Parameters)
00
Folder Screen Soft Key
Label Name Function
ESC Escape Reverts back to the Status or Process D isplay screen.
Folder Screen Navigation/Number Keys
Key Name Function Screen Element
2/Down Arrow Scrolls down through the folder items.
4/Left Arrow Scrolls to the previous folder.
5/Enter Displays the next level screen for a selected folder item. Not applicable
6/Right Arrow Scrolls to the next folder.
8/Up Arrow Scrolls up through the folder items.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 29
Chapter 3 HIM Components
Fault Code 81 DPI Port1 Loss
Elapsed Time 01:26:37
CLR
– – FAULTED – –
Stopped
0.00 Hz
AUTO
F
ESC
Fault Display Screen
The pop-up Fault Display screen automatically appears when a fault condition is detected for the host drive or any connected peripheral. The pop-up Fault Display screen flashes to alert that a fault condition exists. The Fault Display screen (example shown below) provides the following information:
Fault Code number
Fault description
Elapsed time (in hh:mm:ss format) from fault detection
The flash mode for the Fault Display screen can be changed. For details, see
Setting Display Flashing for Fault Indication
on page 40.
Fault Display Screen Soft Keys
Label Name Function
ESC Escape Reverts back to the previous screen without clearing the fault.
CLR Clear Removes the pop-up Fault Display screen from the display and clears the fault.
Fault Display Screen Single Function Key
Key Name Func tion
Stop Removes the pop-up Fault Display screen from the display, clears the fault, and
sends a STOP command to the Host drive.
30 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Using the HIM

This chapter provides information about using the HIM.
Top ic Pag e
Initial HIM Operation on New Drive Powerup 31
Selecting Display Contrast 32
Setting the Date/Time for PowerFlex 750-Series Drives
Creating a User-Defined Drive/Peripheral Name 35
Customizing the Process Screen 36
Resetting the Drive/Peripherals
Setting Factory Defaults 38
Setting Display Flashing for Fault Indication 40
Setting Display Flashing for Alarm Indication
Viewing/Editing Drive or Peripheral Parameters 42
Viewing/Clearing Drive Faults or Alarms 44
Viewing Peripheral Diagnostic Items
Viewing/Clearing Peripheral Events 46
Checking Drive and Peripheral Firmware Revisions 47
Using the CopyCat Function
Changing PowerFlex 750-Series Drive Parameter Associations 52
Linking Parameters in PowerFlex 700/700S Drives 55
Using a Password
Initiating PowerFlex 750-Series Drive Port Verification
Changing Language for the Display Text 62
Updating the HIM Firmware or Language
33
38
41
45
48
57
60
63

Chapter 4

Initial HIM Operation on New Drive Powerup

Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 31
For a list of parameters, see Appendix
When powering up a new drive for the first time, the HIM runs through an initial operating routine that does the following :
Prompts you to select a language.
Initiates a drive start-up routine.
Initiates a port verification check (only for PowerFlex 750-Series drives). If
a port conflict is detected, see page 60
B, HIM Parameters.
for information to resolve it.
Chapter 4 Using the HIM
Stopped
0.00 Hz
AUTO
Host Drive 240V 4.2A 20G...D014
ESC REF TEXT
F
PAR#

Selecting Display Contrast

The contrast of the HIM display can be adjusted for optimal viewing. Follow these steps to change the contrast.
1. Access the Status screen, which is displayed on HIM power up.
Figure 6 - Status Screen
00
2. Use the or key to scroll to the port to which the HIM is connected.
Port Location
01 HIM cradle on the front of the drive.
02 DPI port near the bottom of the drive control pod (PowerFlex 750-Series drives) or
at the bottom of the drive (PowerFlex 7-Class drives).
03 Splitter cable port when the cable is plugged into the DPI port near the bottom of the drive control
pod (PowerFlex 750-Series drives) or at the bottom of the drive (PowerFlex 7-Class drives).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Adjust Contrast.
6. Press the (Enter) key to display the Set LCD Contrast edit pop-up
box.
7. Use the or soft key to adjust contrast to the desired setting.
8. Press the ESC soft key to set the contrast and exit the screen.
32 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
IMPORTANT
AUTO
ESC EDIT
F
Port 00 Date / Time Set
Monday 2008/05/12 10:38:47 (GMT-06:00) Chicago
Stopped
0.00 Hz
AUTO
ES C ZONES
F
Stopped
0.00 Hz
Port 00 Date / Time Set
Monday 2008/05/12 10:38:47
(GMT-06:00) Chicago

Setting the Date/Time for PowerFlex 750-Series Drives

The information in this section does not apply to PowerFlex 7­Class drives.
The PowerFlex 750-Series drive has a real-time clock which supports its time stamp feature for faults and alarms. This clock must be accurately set to provide meaningful time stamp data. Follow these steps to set the date and time.
1. Access the Status screen (see Figure 6
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Set Date and Time.
6. Press the (Enter) key to display the Date/Time Set screen.
).
The top line shows the present date and time in this format:
yyyy/mm/dd hh:mm:ss
Note that the time is always displayed in a 24-hour format. For example, 6:00 pm is shown as 18:00:00.
7. Press the EDIT soft key to access the Date/Time Set Edit Mode screen, which highlights the present time zone line.
8. To select the time zone: a. Press the ZONES soft key to display the Select Time Zone screen.
b. Use the or key to select your time zone region (for
example, Americas).
c. Press the (Enter) key to enter your selection.
d. Use the or key to select your specific time zone (for
example, Chicago).
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 33
Chapter 4 Using the HIM
TIP
e. Press the (Enter) key to enter your selected time zone.
9. To set the date: a. Press the soft key to select the year in the top line. b. Use the numeric keys to enter the correct year.
To delete an erroneous date (or time) entry, use the soft key. Also, a partial or complete date (or time) value will not update until you press the soft key to advance to another field or press the ESC soft key to return to the previous screen.
c. Press the soft key to select the month in the top line. d. Use the numeric keys to enter the correct month. e. Press the soft key to select the day in the top line. f. Use the numeric keys to enter the correct day.
10. To set the time:
a. Press the soft key to select the hour in the top line. b. Use the numeric keys to enter the correct hour. c. Press the soft key to select the minutes in the top line. d. Use the numeric keys to enter the correct minute. e. Press the soft key to select the seconds in the top line. f. Use the numeric keys to enter the correct seconds.
11. Press the ESC soft key to return to the previous screen.
34 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
IMPORTANT
E S C ENTER
Stopped
0.00 Hz
AUTO
F
INS DEL
,=Move Cursor =Char Set
CLR
Edit User Defined Text
PowerFlex 755

Creating a User-Defined Drive/Peripheral Name

The host drive and each of its connected peripherals has a default name. You can change any of these default names, but each new user-defined name cannot exceed 16 characters in length. Follow these steps to change a default name.
Text editing is not supported when using Asian language characters. Only characters in the ISO 8859-1 Latin 1 Character Set, which is supported by U.S. and European personal computers, are available. If a software tool is used for text editing Asian characters, the HIM will replace all unsupported characters with a [] (narrow rectangle) mark.
1. Access the Status screen (see Figure 6
2. Use the or key to scroll to the Port of the device whose name
you want to change (for example, Port 00 for the host drive).
3. Press the TEXT soft key to display the Edit User Defined Text pop-up box.
).
4. Use the or key to move the cursor to the desired character position in the displayed name.
5. Press the key to access the last-viewed character set.
6. Press the appropriate numeric key to access the desired character set.
Numeric Key Function
Selects the numeric character set.
Selects the symbols character set.
Selects the upper case letter character set.
Selects the lower case letter character set.
Also, use the appropriate soft keys to help create the new name.
Soft Key Function
DEL Deletes a highlighted character.
INS Inserts a space to the left of a highlighted character.
CLR Deletes an entire text string.
7. With the desired character selected in that character position, press the
key to select and enter the character.
8. Repeat steps 4 through 7 for each character position.
9. When the desired name is displayed on the edit pop-up box, press the
ENTER soft key to enter and save the new name.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 35
Chapter 4 Using the HIM
0.00
0.000
0.00
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Amps Bus VDC Out Vlts
EDIT
For PowerFlex 750-Series Drive
0.00
0.000
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Amps Bus VDC
EDIT
For PowerFlex 7-Class Drive
0.00
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Amps
0.000
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Bus VDC
0.00
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Out Vlts
EDIT EDIT EDIT

Customizing the Process Screen

The Process screen can be displayed as a multi-line or single-line view screen, and can be customized to show different drive monitoring items, apply a scale factor, or change text for the displayed drive parameter. These modifications are described in their respective subsections that follow.
Selecting Multi-Line or Single-Line View
By default, the Process screen shows a multi-line view of these drive monitoring items.
Drive Monitoring Item Host PowerFlex Drive
Screen Text Description 750-Series 7-Class
Amps Output Amps ✔✔
Bus DC DC Bus Volts ✔✔
Out Vlts Output Volts
Out Pwr Output Power
Elp kWHr Elapsed kWHr
Trq Cur Torque Current
Figure 7 - Multi-Line View Process Screen
not applicable
1. Press the ESC soft key until the Process screen appears.
2. For PowerFlex 750-Series drives only, use the or key to scroll
to the hidden line items on the multi-line view screen.
3. To change the multi-line view Process screen to show each of the drive monitoring items in a larger single-line view, press the VIEW soft key.
4. Use the or key to scroll to each single-line view Process screen.
Figure 8 - Single-Line View Process Screen Examples
36 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
5. To return to the multi-line view Process screen, press the VIEW soft key again.
Using the HIM Chapter 4
AUTO
ESC EDIT
F
Stopped
0.00 Hz
Port 00 Proc Display 1
Param: 7 Output Current Scale:+/- 1.00 Text: Amps Value: 0.00 Amps
RESET
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Proc Dspy 1 Param
7
1 << 1474
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Proc Dspy 1 Scale
1.00
0.00 << 300.00
ES C ENTER
Stopped
0.00 Hz
AUTO
F
INS DEL
,=Move Cursor =Char Set
CLR
.
Edit Proc Dspy 1 Text
Amps
Changing Displayed Items, Adding a Scale Factor, or Customizing Text
You can further customize the Process screen by:
Changing a displayed parameter to a different parameter.
Applying a scale factor to the displayed parameter.
Customizing text for the displayed parameter.
To do any or all of the above modifications, follow these steps.
1. With either the multi-line view Process screen (Figure 7
view Process screen (Figure 8
) displayed, use the or key to
) or the single-line
select the drive monitoring item you want to change.
2. Press the EDIT soft key.
For example, suppose you want to change the first drive monitoring item. In this case, the Process Display 1 Edit screen is shown.
3. Use the soft key to select what you want to change (parameter, scale, or text) for the drive monitoring item.
4. Press the EDIT soft key to display its respective edit pop-up box (see examples below).
5. For parameter or scale editing, use the numeric keys and available soft keys, and press the ENTER soft key to enter and save the item.
For text editing, use the numeric keys, available soft keys, and the key to enter each character. Then press the ENTER soft key to enter and save
the complete text string.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 37
Chapter 4 Using the HIM
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 Set Defaults
Host and Ports (Preferred)
This Port Only
INFO
Stopped
0.00 Hz
AUTO
ESC
F
Port xx Set Defaults
This Port Only
INFO
For Host Drive
For Connecte d Periphera l

Resetting the Drive/ Peripherals

Setting Factory Defaults

The drive or any of its connected peripherals can be reset by removing and restoring power to the drive (power cycling). If this is not convenient or cannot be done because of application circumstances, the HIM can be used to reset the drive/peripherals. Follow these steps to reset the drive or any of its peripherals.
1. Access the Status screen (see Figure 6
2. Use the or key to scroll to the Port of the device you want to
reset (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Reset Device.
6. Press the (Enter) key to display a pop-up box asking if you want to
reset the device.
7. Press the ENTER soft key to affirm and reset the device, or press the ESC soft key to cancel.
The procedure to set a PowerFlex 750-Series drive and its connected peripherals to factory defaults is slightly different than the procedure used for a PowerFlex 7­Class drive and its peripherals. See the respective subsection for instructions.
).
Setting PowerFlex 750-Series Drives/Peripherals to Factory Defaults
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to set to factory defaults (for example, Port 00 for the host drive or the respective port number for one of the drive’s connected peripherals).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults pop-up box (see
examples below).
38 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
TIP
Stopped
0.00 Hz
AUTO
F
WARNING
Sets most parameters in the Host device and all ports to factory defaults. Continue?
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
MOSTALL
WARNING
Use MOST to reset typical settings on this port (preferred). Use ALL to reset all settings.
ESC
Stopped
0.00 Hz
AUTO
F
WARNING
Sets all parameters to factory defaults. Continue?
ESC
ENTER
7. Use the or key to select the appropriate action.
• Host and Ports (Preferred): Selects the host device and all ports for a
factory default action.
•This Port Only: Selects only this port for a factory default action.
For a description of a selected menu item, press the INFO soft key.
8. Press the (Enter) key to display the warning pop-up box to reset defaults.
Figure 9 - ‘Host and Ports (Preferred)’ Pop-Up Box
Press the ENTER soft key to affirm and set most parameters for the host drive and port devices to factory defaults. In this case, see the host drive and port device documentation for the settings that will not be restored—or press the ESC soft key to cancel.
Setting PowerFlex 7-Class Drives/Peripherals to Factory Defaults
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to set to factory defaults (for example, Port 00 for the host drive or the respective port number for one of the drive’s connected peripherals).
Figure 10 - ‘This Port Only’ Pop-Up Box
Press the MOST soft key to set most settings for the selected port device to factory defaults. In this case, see the host drive documentation for the settings that will not be restored. Press the ALL soft key to set all settings for the selected port device to factory defaults—or press the ESC soft key to cancel.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults pop-up box.
7. Press the ENTER soft key to affirm and set all device parameter values to
factory defaults—or press the ESC soft key to cancel.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 39
Chapter 4 Using the HIM
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Fault Dspy Type
Flash Bklite 0
0<<2

Setting Display Flashing for Fault Indication

Whenever a fault for the host drive or any of its connected peripherals is detected, a pop-up Fault Display screen (see page 30 the Status Bar flashes to alert the operator. However, you can change the flash mode for the Fault Display screen to one of the following modes:
Flash Bklite; selects the entire LCD screen to flash.
Flash Status (default); selects only the Status Bar (item 1, Figure 3
Flash None; selects no flashing for the Fault Display screen.
Follow these steps to change the flash mode for the Fault Display screen.
1. Access HIM Parameter 04 - [Fault Dspy Type] using either the Direct Parameter Access method (page 42 (page 43
2. Press the EDIT soft key to display the Edit Fault Dspy Type pop-up box.
).
) or Alternate Linear List method
) appears. By default, only
) to flash.
3. Use the and soft keys to select the desired flash mode. To delete an erroneous entry, use the soft key.
4. Press the ENTER soft key to enter your selection and return to the parameter screen.
40 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Alarm Dspy Type
Flash Status 1
0<<2

Setting Display Flashing for Alarm Indication

Whenever an alarm for the Host Drive is detected, an alarm bell icon appears in the Status Bar. By default, only the Status Bar flashes to alert the operator. However, you can change the flash mode for alarm indication to one of the following modes:
Flash Bklite; selects the entire LCD screen to flash.
Flash Status (default); selects only the Status Bar (item 1, Figure 3
Flash None; selects no flashing for alarm indication.
Follow these steps to change the flash mode for alarm indication.
1. Access HIM Parameter 05 - [Alarm Dspy Type] using either the Direct Parameter Access method (page 42 (page 43
2. Press the EDIT soft key to display the Edit Alarm Dspy Type pop-up box.
).
) or Alternate Linear List method
) to flash.
3. Use the and soft keys to select the desired flash mode.
To delete an incorrect entry, use the soft key.
4. Press the ENTER soft key to enter your selection and return to the parameter screen.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 41
Chapter 4 Using the HIM
TIP
TIP
TIP

Viewing/Editing Drive or Peripheral Parameters

The PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM can show host drive parameters in a File-Group-Parameter view or by Linear List. To access drive or peripheral parameters for viewing or editing, use either the direct parameter access method or the alternate linear list access method. See the respective subsections that follow for instructions.
Selecting File-Group-Parameter or Linear List View
Not all peripheral devices support viewing parameters in a File-Group­Parameter view.
Follow these steps to change viewing between File-Group-Parameter and Linear List.
1. Access the Status screen (see Figure 6
2. Use the or key to scroll to the Port of the device whose
parameters you want to access (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DEV PARAM or HOST
PARA M fol der.
5. Use the or key to select Linear List or File-Group.
).
6. Press the (Enter) key to display the last-viewed or first parameter in the Linear List, or the last-viewed or first parameter in the first Group.
Direct Parameter Access Method
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to access (for example, Port 00 for the host drive).
3. Press the PAR# soft key to display the Jump to Param # entry pop-up box.
Some devices have two sets of parameters (Device and Host parameters). In this case, a pop-up box will appear enabling you to first choose the parameter set in which the parameter that you want to access resides.
4. Use the numeric keys to enter the desired parameter number, or use the or soft key to scroll to the desired parameter number.
Pressing and holding the or soft key for 1 second or longer provides continuous scrolling until you release the key.
5. Press the ENTER soft key to display the parameter.
42 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
TIP
TIP
Edit Accel Time 1
5.0 Secs
0.00 << 3600.00
ESC
.
Stopped
0.00 Hz
AUTO
F
ENTER
6. Press the EDIT soft key (for editable parameters only) to display the Edit Parameter pop-up box.
Figure 11 - Example Edit Parameter Pop-Up Box
7. Use the numeric keys, decimal soft key, and soft key to edit the parameter.
When the decimal soft key is pressed while editing a numeric value, this key temporarily changes to an EXP soft key to allow exponential entry.
8. Press the ENTER soft key to enter the new parameter value and return to the parameter screen.
Alternate Linear List Access Method
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to access (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PARAMETER folder.
5. Use the or key to select Linear List.
6. Press the (Enter) key to display either the device’s last-viewed
parameter or the first parameter in the linear list.
7. Use the or key to scroll to the desired parameter.
8. Press the EDIT soft key (for editable parameters only) to display the Edit
Parameter pop-up box (Figure 11
9. Use the numeric keys, decimal soft key, and soft key to edit the parameter.
When the decimal soft key is pressed while editing a numeric value, this key temporarily changes to an EXP soft key to allow exponential entry.
).
10. Press the ENTER soft key to enter the new parameter value and return to the parameter screen.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 43
Chapter 4 Using the HIM
Faulted
0.00 Hz
AUTO
ESC TOP ENDFCLR
Port 00 Faults
01 82 Port 2 DPI Loss 02 49 Drive Powerup 03 9 Trnsistr OvrTemp 04 8 Heatsink OvrTemp
ENTER

Viewing/Clearing Drive Faults or Alarms

Follow these steps to view/clear drive faults or alarms.
1. Access the Status screen (see Figure 6
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Faults or Alarms.
6. Press the (Enter) key to display the numbered fault/alarm queue.
Faults/alarms are listed from the most recent to occur (line 01) to the least recent. The fault/alarm number and name are shown at the right.
).
7. Use the or key or the following soft keys to navigate within the fault/alarm queue.
Soft Key Function
ENTER Displays the Time Stamp pop-up box for the fault/alarm. Note that the real-time clock in a
TOP Displays the first (most recent) fault/alarm in the queue.
END Displays the last (least recent) fault/alarm in the queue.
8. To clear faults/alarms, press the CLR soft key.
In the Select Action pop-up box, select the appropriate action using the
fault/alarm or clear the fault/alarm queue. To cancel the pop-up box, press the ESC soft key or select Cancel from the list and press the (Enter)
key.
PowerFlex 750-Series drive must be accurately set to provide meaningful time stamp data. For details, see Setting the Date/Time for PowerFlex 750-Series Drives on page 33.
Use the or (if supported by device).
or key and press the (Enter) key to clear the active
key to scroll to all para meters related to the displayed fault/alarm
44 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4

Viewing Peripheral Diagnostic Items

If you encounter unexpected communication problems, diagnostic items for the drive’s connected peripherals—including the HIM—can help you or Rockwell Automation personnel troubleshoot the problem. Follow these steps to view peripheral diagnostic items.
1. Access the Status screen (see Figure 6
2. Use the or key to scroll to the Port of the device whose
diagnostic items you want to view (for example, Port 02 for the connected HIM).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Diagnostic Items.
6. Press the (Enter) key to display either the device’s last-viewed
diagnostic item or the first diagnostic item in the list.
Ta b l e 1
Diagnostic Items, use the procedure described above.
Table 1 - 20-HIM-A6 and 20-HIM-C6S HIM Diagnostic Items
shows all possible Diagnostic Items for the HIM. To view the HIM
).
No. Name Description
1 LCD Contrast The present value of the HIM LCD contrast level, and ability to set the contrast level
from this screen.
2 Common Logic Cmd The present value of the Common Logic Command being transmitted to the drive by
the HIM.
3 Prod Logic Cmd The present value of the Product Specific Logic Command being transmitted to the
drive by the HIM.
4 Common Logic Sts The present value of the Common Logic Status being received from the drive by the
HIM.
5 Prod Logic Sts The present value of the Product Specific Logic Status being received from the drive by
the HIM.
6 Reference The present value of the Product Specific Reference being transmitted to the drive by
the HIM.
7 Feedback The present value of the Product Specific Feedback being received from the drive by
the HIM.
8 Boot Flash Count The present value of the Boot Flash Counter.
9 App Flash Count The present value of the App Flash Counter.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 45
Chapter 4 Using the HIM
Stopped
0.00 Hz
AUTO
ESC TOP ENDFCLR
Port 06 Events
01 14 DPI Online 500k 02 26 SI Online 03 29 Net Link Up 04 4 EEPROM Sum Error
ENTER

Viewing/Clearing Peripheral Events

Events for the host drive’s connected peripherals—including the HIM—are logged into their respective event queues. Many events in an event queue occur under normal operation. If you encounter unexpected problems, the events may help you or Allen-Bradley personnel troubleshoot the problem. Follow these step to view or clear the events of a connected peripheral.
1. Access the Status screen (see Figure 6
2. Use the or key to scroll to the Port of the device whose events
you want to view (for example, Port 06 for a network communication option module).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Events.
6. Press the (Enter) key to display the device’s numbered event queue.
).
Events are listed from the most recent to occur (line 01) to the least recent. The event number and name are shown at the right.
7. Use the or key or the following soft keys to navigate within the event queue.
Soft Key Function
ENTER Displays the Time Stamp pop-up box for the event. Note that the real-time clock in a
PowerFlex 750-Series drive must be accurately set to provide meaningful time stamp data. For details, see Setting the Date/Time for PowerFlex 750-Series Drives on page 33.
TOP Displays the first (mos t recent) event in the queue.
END Displays the last (least recent) event in the queue.
8. To clear events, press the CLR soft key.
In the Select Action pop-up box, select the appropriate action using the
or key and press the (Enter) key to clear the event or
clear event queue. To cancel the pop-up box, press the ESC soft key or select Cancel from the list and press the (Enter) key.
The PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM maintains an event queue that reports the history of its actions. Ta b l e 2 view the HIM events, use the procedure described above.
46 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
shows all possible events for the HIM. To
Stopped
0.00 Hz
AUTO
ESC
F
PowerFlex 755
Product Revision 1.007 Product Ser Num 00000000
Product Series A
–Main Control Board
FW Revision 1.007
TOP END PGUP PGDN
Using the HIM Chapter 4
Table 2 - 20-HIM-A6 and 20-HIM-C6S HIM Events
Code Event Description
1Reserved
2 Device Power Up A normal power up.
3 Device Reset The HIM was reset due to a manual reset command or program crash.
4 EEPROM CRC Error The HIM EEPROM Data Storage Device is corrupt.
5 App Updated The HIM application firmware has been updated.
6 Boot Updated The HIM boot firmware has been updated.
7 Watchdog Timeout A program crash has occurred.
8 DPI Bus Off A DPI Bus Off fault was detected.
9 DPI Ping Timeout A DPI Ping Timeout fault was detected.
10 DPI Port Invalid A DPI Port ID fault was detected.
11 DPI Port Changed A DPI Port Changed fault was detected.
12 DPI Host Reset The host has sent a reset message.
13 DPI Baud 125K The DPI data rate is detected at 125K bits/second.
14 DPI Baud 500K The DPI data rate is detected at 500K bits/second.
15 DPI Host Invalid The HIM will not connect to this type of host.
16 DPI D up Port Another DPI device is already connected to this port.
17 DPI Type 0 Logon The DPI log on was completed successfully.
18 DPI Type 0 Time A DPI Type 0 Command has timed out.
19-23 Reserved
24 DPI Msg Timeout A message to a DPI device has timed out.
25 DPI Manual Reset A reset command was sent through a fault object.

Checking Drive and Peripheral Firmware Revisions

Follow these steps to check the firmware revision of the drive or its peripherals.
1. Access the Status screen (see Figure 6
2. Use the or key to scroll to the Port of the device whose firmware
version you want to view (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Device Version.
6. Press the (Enter) key to display device version information.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 47
).
Chapter 4 Using the HIM
TIP
IMPORTANT

Using the CopyCat Function

PowerFlex 750-Series drives and PowerFlex 7-Class drives provide a CopyCat function that enables you to upload individual parameter sets for the host drive or any of its connected peripherals into the HIM. Furthermore, an Upload All Ports function enables you to conveniently upload multiple parameter sets for the host drive and all of its connected peripherals in one single file. In either case, this information can then be used as backup or can be transferred to another drive or peripheral device by downloading the file from the HIM’s memory.
The Upload All Ports and Download All Ports functions are only available for the host drive (Port 00) due to their unique functionality.
The CopyCat function also enables you to rename or delete individual or multiple parameter sets stored in the HIM.
The HIM can store up to 50 individual parameter sets or up to 5 multiple parameter sets. Due to the memory capacity of the HIM, these maximums will vary when storing combinations of individual and multiple parameter sets.
Generally, the upload or download transfer process manages all conflicts. However, the download will stop and a text message will appear if any of the following conditions exist:
A device mismatch, such as firmware revision, device type, or device series is detected.
The drive is password protected.
The drive is running.
You then have the option to completely stop the download or continue after noting the discrepancy for the parameters that could not be downloaded. These parameters can then be manually adjusted.
When using the HIM with a PowerFlex 753 drive with firmware revision 1.05 or earlier, or a PowerFlex 755 drive with firmware revision 1.10 or earlier, the CopyCat function cannot upload/download DeviceLogix values for DLX Out xx and DLX In xx parameters and DeviceLogix program routines. Drives with a later firmware revision support this function, but the HIM does not support screen formatting for the DeviceLogix program.
Creating CopyCat Files
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameter set you want to copy (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select HIM CopyCat.
48 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
TIP
TIP
IMPORTANT
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device Delete CopyCat File Rename CopyCat File
6. Press the (Enter) key to display the CopyCat Files selection screen.
Before any CopyCat files are created, only the ‘CopyCat From Device to HIM’ menu item is shown. When Port 00 for the Host Drive is selected in Step 2, the ‘Upload All Ports’ menu item also appears.
7. Use the or key to select the appropriate action and press the (Enter) key to initiate that action.
8. With New File selected on the Select Upload File screen, press the
(Enter) key to create the file. A pop-up box will appear to confirm that the CopyCat file was successfully created. Press the ENTER soft key to complete the procedure.
When a CopyCat file is created, its default file name corresponds to the device whose file is being copied. For example, a newly created CopyCat file for a PowerFlex 755 drive has a default file name of ‘PowerFlex 755’.
When selecting an item row that is an existing CopyCat file—not a ‘New File’ row—to create a new CopyCat file, an Overwrite pop-up box will appear. Press the ENTER soft key to affirm and overwrite the existing CopyCat file—or press the ESC soft key to cancel.
Renaming CopyCat Files
Text editing is not supported when using Asian language characters. Only characters in the ISO 8859-1 Latin 1 Character Set, which is supported by U.S. and European personal computers, are available. If a software tool is used for text editing Asian characters, the HIM will replace all unsupported characters with a [] (narrow rectangle) mark.
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
CopyCat file you want to rename (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select HIM CopyCat.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 49
Chapter 4 Using the HIM
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device Delete CopyCat File Rename CopyCat File
E S C ENTER
Stopped
0.00 Hz
AUTO
F
INS DEL
,=Move Cursor =Char Set
CLR
Edit CopyCat File Text
PowerFlex 755
6. Press the (Enter) key to display the CopyCat Files selection screen.
7. Use the or key to select Rename CopyCat File.
8. Press the (Enter) key to display the Select File To Rename pop-up
box.
9. Use the or key to select the file to be renamed.
10. Press the (Enter) key to display the Edit CopyCat File Text pop-up box.
11. Use the or key to move the cursor to the desired character
position in the displayed name.
12. Press the key to access the last-viewed character set.
13. Press the appropriate numeric key to access the desired character set.
Numeric Key Function
Selects the numeric character set.
Selects the symbols character set.
Selects the upper case letter character set.
Selects the lower case letter character set.
Also, use the appropriate soft keys to help create the new name.
Soft Key Function
DEL Deletes a highlighted character.
INS Inserts a space to the left of a highlighted character.
CLR Deletes an entire text string.
14. With the desired character selected in that character position, press the
key to select and enter the character.
15. Repeat steps 11 through 14 for each character position.
50 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
16. When the desired name is displayed on the edit pop-up box, press the ENTER soft key to enter and save the new name.
Using the HIM Chapter 4
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device Delete CopyCat File Rename CopyCat File
Stopped
0.00 Hz
AUTO
F
Select File To Delete
PowerFlex 755 Cfg
Delete All Files
ESC
Deleting CopyCat Files
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameter set you want to delete (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select HIM CopyCat.
6. Press the (Enter) key to display the CopyCat Files selection screen.
7. Use the or key to select Delete CopyCat File.
8. Press the (Enter) key to display the Select File To Delete pop-up box.
9. Use the or key to select the file (or all files) to delete.
10. Press the (Enter) key to display the confirmation pop-up box.
11. Press the ENTER soft key to affirm and delete the selected CopyCat file, or
press the ESC soft key to cancel.
Another pop-up box will appear to confirm that the CopyCat file was successfully deleted.
12. Press the ENTER soft key to affirm and complete the procedure.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 51
Chapter 4 Using the HIM
TIP
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871 Port PowerFlex 755
PAR#
Changing PowerFlex 750­Series Drive Parameter Associations
PowerFlex 750-Series drives have special parameters (indirect selector parameters and reference parameters) which are always associated with other parameters. The values for these special parameters are actually pointers to other parameters in the drive or to Host parameters in connected peripherals. To change a parameter association, first access the indirect selector or reference parameter. Second, select the port number of the device whose parameter you want to target for association. Then, select the target parameter of that device. If the target parameter is a bit parameter, you must also select the appropriate bit you want to associate with the indirect selector or reference parameter.
Parameter associations can be changed using one of these methods:
Individual Screen Entry Method—where individual pop-up screens are used to enter the required parameter association data.
Direct Numeric Entry Method—where the required parameter association data is entered as a number string on a single pop-up screen.
The following example illustrates how to use each method to change a parameter association. Suppose you want the drive speed reference to come from the network controller via the embedded EtherNet/IP adapter on the Main Control Board in a PowerFlex 755 drive.
Using Individual Screen Entry Method
1. Access the indirect selector or reference parameter whose association you want to change (for this example, drive Parameter 545 - [Spd Ref A Sel] as shown below).
In this example, the Port field is shown selected. Use the or key to select the Port, Parameter, or Bit (if applicable) fields.
Depending on the indirect selector or reference parameter selected, you may see more available ports in the list.
52 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
TIP
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
Select Port To Use
Zero Speed
Port 00 PowerFlex755
E S C ENTER
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
Select Param To Use Par 0546 Spd Ref A Stpt Par 0571 Preset Speed 1 Par 0572 Preset Speed 2
E S C ENTER
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871 Port PowerFlex 755
PAR#
2. Press the EDIT soft key to display the edit pop-up box for the selected field (in this case, the port number field).
3. Use the or key to scroll to the port number of the device whose parameter you want to target for the association (for this example,
Port 00, where the speed Reference parameters for the available drive ports are located).
The ‘Zero Speed’ setting may be available to select for specific applications that require a safe-state speed Reference.
4. Press the ENTER soft key to enter the selected port number.
The target parameter selection pop-up box appears (see example screen below), showing a list of available target parameters that can be associated.
5. Use the or key to scroll to the target parameter you want to associate.
For this example, we selected drive Parameter 877 - [Port 13 Reference]).
6. Press the ENTER soft key to enter the selected target parameter.
If the target parameter:
•Is not a bit parameter, the parameter association is now changed and
the indirect selector or reference parameter screen re-appears with the associated parameter information shown.
•Is a bit parameter, a list of available bit numbers is displayed. Use the
or key to scroll to the bit number of the target parameter
you want to associate, and press the ENTER soft key. The parameter
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 53
Chapter 4 Using the HIM
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871 Port PowerFlex 755
PAR#
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871 Port PowerFlex 755
PAR#
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
871
0 << 159999
E S C ENTER
association is now changed and the indirect selector or reference parameter screen re-appears with the associated parameter information shown.
Using Direct Numeric Entry Method
1. Access the indirect selector or reference parameter whose association you want to change (for this example, drive Parameter 545 - [Spd Ref A Sel] as shown below).
2. With any field (port, parameter, or bit) selected, press the # soft key to display the Direct Numeric Entry pop-up box.
3. Use the numeric keys to enter a number string that represents the target parameter’s device port number, parameter number and, only when the target parameter is a bit parameter, its bit number.
The number string format is PPpppp.bb, where:
PP = device port number pppp = target parameter number bb = bit number (only used when target parameter is a bit parameter)
4. Press the ENTER soft key to enter the number string and complete the parameter association.
The indirect selector or reference parameter screen re-appears with the associated parameter information.
54 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Link Accel Time 1
0
0 << 1179
ESC
Stopped
0.00 Hz
AUTO
F
Port 00 Dev Param #140 Accel Time 1
10.0 Secs
LINK PAR#

Linking Parameters in PowerFlex 700/700S Drives

Most parameter values are entered directly by the user. However, specific parameters can be ‘linked’, so the value of one parameter becomes the value of another. For example, the value of an analog input can be linked to an acceleration time. Rather than entering an acceleration time directly (via the HIM), the link allows the value to change by varying the analog input signal. This can provide additional flexibility for advanced applications.
Each link has two components:
Source parameter—sender of information
Destination parameter—receiver of information
Most parameters can be a source of data for a link, except parameters that use an integer value representing an ENUM (text selection). These are not allowed, since the integer is not actual data (it represents a value). See the drive documentation for a list of parameters that can be destinations. All links must be established between equal data types (parameter value formatted in floating point can only source data to a destination parameter value that is also a floating point).
Establishing a Link
1. Access a valid destination parameter to be linked (for example, the Accel Time 1 parameter 140 for a PowerFlex 700 drive or parameter 32 for a PowerFlex 700S drive).
2. Press the LINK soft key to display the Link pop-up box for that parameter.
3. Enter the source parameter number (for example, the Analog In1 Value
parameter 16 for a PowerFlex 700 drive or parameter 801 for a PowerFlex 700S drive) to which you want to link the destination parameter.
4. Press the ENTER soft key.
The destination parameter screen reappears with the respective source parameter value now mapped over the destination parameter range, and is shown in destination parameter units. In this example, the value for Analog Input 1 is 10.000 volts for a PowerFlex 700 drive, and is shown as
10.0 seconds.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 55
Chapter 4 Using the HIM
Deleting an Established Link
Follow these steps to delete an established link.
1. Access the screen for the destination parameter.
2. Press the LINK soft key.
3. In the Link pop-up box, enter a value of zero.
4. Press the ENTER soft key to delete the established link.
56 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter New Password
0
0 << 65535

Using a Password

All parameter configuration settings for the drive and its connected peripherals can be protected from unauthorized access using a password.
Setting/Changing the Password
1. Access the Status screen (see Figure 6).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Change Password.
6. Press the (Enter) key to display the Enter New Password pop-up box.
7. Use the numeric keys to enter a desired password value.
Use the soft key to delete an erroneous entry.
For your convenience, write down your assigned password and store it in a safe place.
Password = ____ ____ ____ ____ ____
8. Press the ENTER soft key to enter the new password.
9. After the password verification screen appears, confirm the new password
by re-entering its value.
Thereafter, the HIM immediately logs in to the drive, which is indicated by the Log Out menu line in the PROPERTIES folder. All drive/ peripheral parameters are accessible to view or edit.
10. To initiate password protection, do the following:
a. Use the or key to select Log Out from the PROPERTIES
folder menu.
b. Press the (Enter) key to display the log out verification pop-up
box.
c. Press the ENTER soft key to affirm and log out—or press the ESC soft
key to cancel.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 57
Chapter 4 Using the HIM
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter Password
0
0 << 65535
Changing Password-protected Drive/Peripheral Parameters
When the host drive is password protected, parameter settings for the drive and its connected peripherals can be viewed—but not changed until after the correct password value is entered.
When attempting to edit a parameter value while logged out, the HIM will prompt you for the password before allowing access.
Password protection also applies to:
Drive start-up procedure
Factory defaults
User sets
CopyCat function
Follow these steps to edit password-protected parameters.
1. Access the Status screen (see Figure 6
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Log In.
6. Press the (Enter) key to display the Enter Password pop-up box.
7. Use the numeric keys to enter the existing password value.
Use the soft key to delete an erroneous entry.
8. Press the ENTER soft key to enter the existing password.
).
Thereafter, any parameter setting can be changed.
58 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter Password
0
0 << 65535
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter New Password
0
0 << 65535
Disabling Password Protection
1. Access the Status screen (see Figure 6).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Log In.
6. Press the (Enter) key to display the Enter Password pop-up box.
7. Use the numeric keys to enter the existing password value.
Use the soft key to delete an erroneous entry.
8. Press the ENTER soft key to enter the existing password.
9. Use the or key to select Change Password.
10. Press the (Enter) key to display the Enter New Password pop-up box.
11. Use the numeric keys and the soft key to enter ‘0’, the default value to
disable the password protection feature.
12. Press the ENTER soft key to enter the ‘0’ (disable) default value.
13. After the password protection verification pop-up box appears, confirm
the new password by re-entering ‘0’.
14. Press the ENTER soft key to disable password protection.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 59
Chapter 4 Using the HIM
IMPORTANT
IMPORTANT
Initiating PowerFlex 750­Series Drive Port Verification
The information in this section does not apply to PowerFlex 7­Class drives.
Upon powerup, the HIM verifies that the PowerFlex 750-Series drive has initiated Port Verification. The host drive then checks for port conflicts. If any conflicts are present, a Device Conflicts pop-up box appears listing all devices with conflicts.
Conflict Types
If the conflict can be resolved, a ‘!’ symbol precedes the port number. If the conflict cannot be resolved without removing or replacing the device, an ‘X’ symbol precedes the port number. There are five possible conflict types.
Symbol Conflict Type
! Changed
! Requires Configuration
X Not Functioning
X Not Supported
X Invalid Duplicate
In the Device Conflicts pop-up box, scroll up or down to highlight/select an individual device row and press the INFO soft key. Another pop-up box appears for the selected device showing the type of conflict and related information.
If information is available for the device that previously occupied that port, it will also be shown.
Use the FIX soft key—displayed only if all conflict types are ‘Changed’ or ‘Requires Configuration’—to resolve conflicts. After pressing the FIX soft key, a pop-up box will appear asking to confirm that the new device(s) should be accepted. Press the ENTER soft key to affirm and resolve the conflicts for all devices. Thereafter, the HIM will re-read the drive Port Verification information to ensure that no further conflicts exist.
Please note the following important conflict resolution information:
The Device Conflict pop-up window remains on the screen until all conflicts are resolved.
All conflicts must be resolved to access a Folder screen or Control screen. Only the (Stop) key and the assigned soft keys (INFO and FIX) will be functional until no conflicts exist.
The host drive will not be able to run while any conflicts are present.
60 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
Stopped
0.00 Hz
AUTO
Device Conflicts:
! Port 05: I/O Module 24 V ! Port 06: Device Not Found
FIXFINFO
! Port 04: Encoder
Stopped
0.00 Hz
AUTO
! 04: Encoder Changed Prev: I/O Module 24 V
F
Example screen when the INFO soft key is pressed.
ENTER
Stopped
0.00 Hz
AUTO
About to permanently erase the previous device(s) configuration
Continue?
F
Example screen when the FIX soft key is pressed.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
INFO
Device Conflicts:
! Port 04: Encoder
! Port 06: Device Not Found
X Port 05: Not Functioning
Resolving ‘Changed’ or ‘Requires Configuration’ Conflicts
When a ‘Changed’ or ‘Requires Configuration’ conflict exists on powerup, a ‘!’ symbol precedes the port number in the Device Conflicts pop-up box.
1. Select a port device (in this example, the Encoder card) and press either the INFO soft key to show additional information about the conflict, or press the FIX soft key to resolve all device conflicts.
2. Press the ENTER soft key to affirm and re-display the Device Conflicts pop-up box.
Press the ENTER soft key to affirm and resolve all device conflicts, or press the ESC soft key to cancel.
Resolving ‘Not Functioning’, ‘Not Supported’, or ‘Invalid Duplicate’ Conflicts
When a ‘Not Functioning’, ‘Not Supported’, or Invalid Duplicate’ conflict exists on powerup, an ‘X’ symbol precedes the port number in the Device Conflicts pop-up box.
1. Select the port preceded with an ‘X’ (in this example, Port 05) and press the INFO soft key to show additional information about the conflict (see example below).
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 61
Chapter 4 Using the HIM
Stopped
0.00 Hz
AUTO
X05: Not Functioning This device must be removed or replaced. Prev: Encoder
F
ENTER
TIP
2. Follow the screen prompts to resolve the port conflict.
Or press the ENTER soft key to affirm and re-display the Device Conflicts pop-up box.

Changing Language for the Display Text

All HIM screen text can be displayed in one of the supported languages. The default language is English.
If the drive is set to a language not supported by the HIM, a pop-up box appears asking you to select another language.
Follow these steps to select another supported language.
1. Access the Status screen (see Figure 6
2. Press the (Language) soft key to display the list of available languages.
3. Use the or key to select the desired language.
4. Press the (Enter) key to enter the selected language.
All HIM screen text now appears in the selected language.
).
62 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Using the HIM Chapter 4
IMPORTANT

Updating the HIM Firmware or Language

The HIM firmware can be updated over the network or serially through a direct connection from the drive to the computer using a 1203-USB or 1203-SSS serial converter.
When updating firmware over the network, you can use the Allen-Bradley ControlFLASH software tool, the built-in update capability of DriveExplorer Lite or Full software, or the built-in update capability of DriveExecutive software.
When updating firmware through a direct serial connection from the drive to the computer, you can use the same Allen-Bradley software tools described above, or you can use HyperTerminal software set to the X-modem protocol.
To obtain a firmware or language update for the HIM, go to http://
www.ab.com/support/abdrives/webupdate. This website contains all firmware
update files, supported language files, and associated Release Notes that describe the following items:
Firmware update enhancements and anomalies
How to determine the existing firmware revision
How to update the firmware using ControlFLASH, DriveExplorer,
DriveExecutive, or HyperTerminal software
When the HIM firmware is updated in the field to support another available language, the language selected for download will replace all other supported languages—except English, which always remains as the default language.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 63
Chapter 4 Using the HIM
Notes:
64 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Specifications

This appendix provides the specifications for the HIM.
Top ic Pag e

Communications

Electrical

Mechanical

Environmental

Regulatory Compliance 66
65
65
65
65

Appendix A

Communications
Electrical
Mechanical
Environmental
Protocol Drive Peripheral Interface (DPI)
Data Rates 125 kbps or 500 kbps
Consumption 140 mA at 12V DC supplied by the Host Drive
Dimensions
Height Widt h Depth
Weight 91 g (3.2 oz.) 173 g (5.7 oz.)
Temperature
Operating Storage
Relative Humidity 5…95% non-condensing
Atmosph ere Important: The HIM must not be installed in an area where the ambient atmosphere
Vibration
Operating Non-Operating
Shock
Operating Non-Operating
20-HIM-A6 20-HIM-C6S
116.0 mm (4.57 in.) 180.0 mm (7.08 in.)
70.0 mm (2.75 in.) 93.0 mm (3.66 in.)
16.0 mm (0.63 in.) 25.0 mm (0.98 in.)
0…50 °C (32…122 °F)
-40…85 °C (-40…185 °F)
contains volatile or corrosive gas, vapors or dust. If the HIM is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
2.5 g @ 5 Hz…2 kHz 5 g @ 5 Hz…2 kHz
30 g peak acceleration, 11 (±1) ms pulse width 50 g peak acceleration, 11 (±1) ms pulse width
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 65
Appendix A Specifications

Regulatory Compliance

Certification Specification
UL cUL CE CTick
NOTE: This is a product of category C2 according to IEC 61800-3. In a domestic environment this product may cause radio interference in which case supplementary mitigation measures may be required.
UL508C CAN / CSA C22.2 No. 14-M91 EN50178 and EN61800-3 EN61800-3
66 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Appendix B

HIM Parameters

This appendix provides information about the HIM parameters.
Besides the HIM, the following configuration tools can also be used to monitor or change parameter values of the HIM, drive, and other connected peripherals:
Connected Components Workbench software, version 1.02 or later
DriveExplorer software, version 6.01 or later
DriveExecutive software, version 5.01 or later

Parameter List

Parameter
No. Name and Description Details
01 [Port Number]
Displays the port on the drive to which the HIM is connected.
02 [DPI Data Rate]
Displays the DPI data rate at which the HIM is communicating with the drive.
03 [Initial Screen]
Selects the initial HIM screen to be displayed on power up.
04 [Fault Dspy Type]
Selects the type of display flash to be shown when a drive or peripheral fault is detected.
05 [Alarm Dspy Type]
Selects the type of display flash to be shown when a drive alarm is detected.
06 [User Dspy Enable]
Enables/disables the HIM’s automatic user display time function, which is configured using Parameter 07 - [User Dspy Time].
07 [User Dspy Time]
Sets the amount of time that a screen will remain displayed as long as the HIM keys are not used. After this time elapses, the screen is automatically replaced by the initial screen, which is selected using Parameter 03 - [Initial Screen].
Minimum: 1 Maximum: 7 Typ e: Rea d Onl y
Values: 0 = 125 kbps
Typ e: Rea d Onl y
Default: 0 = Status Scrn Value: 0 = Sta tus S crn
Typ e: R ea d/ Wri te Reset Required: Yes
Default: 1 = Flash Status Values: 0 = Flash Bklite
Typ e: R ea d/ Wri te Reset Required: No
Default: 1 = Flash Status Values: 0 = Flash Bklite
Typ e: R ea d/ Wri te Reset Required: No
Default: 1 = Enable Values: 0 = Dis able
Typ e: R ea d/ Wri te Reset Required: Yes
Default: 60 sec Minimum: 10 sec Maximum: 300 sec Typ e: R ea d/ Wri te Reset Required: Yes
1 = 500 kbps
1 = Process Scrn
1 = Flash Status 2 = Flash None
1 = Flash Status 2 = Flash None
1 = Enable
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 67
Appendix B HIM Parameters
Notes:
68 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Appendix C

History of Changes

Top ic Pag e
20HIM-UM001C-EN-P, January 2012 69
20HIM-UM001B-EN-P, October 2010 70
20HIM-UM001A-EN-P, January 2009
This appendix summarizes the revisions to this manual. Reference this appendix if you need information to determine what changes have been made across multiple revisions. This may be especially useful if you are deciding to upgrade your hardware or software based on information added with previous revisions of this manual.
70

20HIM-UM001C-EN-P, January 2012

This table contains the changes, which were the result of HIM firmware revision
2.001.
Top ic
In Chapter 3:
Added the Status Bar element ‘DLX’ to indicate that the Host Drive DeviceLogix feature is enabled.
Added new soft key labels ‘ACK’, ‘PGDN’, and ‘PGUP’ on the Device Version information screen to enhance navigation.
In Chapter 4:
Changed the Fault Display screen flash mode default from ‘Flash Bklite’ to ‘Flash Status’.
Added a TIP statement that holding the or soft key while using the Direct Parameter Access method to view/
edit a parameter provides continuous scrolling until the key is released.
Revised Example Device Version Information Screen to show the added soft key labels ‘Top’, ‘End’, ‘PGUP’, and ‘PGDN’.
In Appendix B, changed the default for Parameter 04 - [Fault Dspy Type] from ‘0’ (Flash Bklite) to ‘1’ (Flash Status).
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 69
Appendix C History of Changes

20HIM-UM001B-EN-P, October 2010

20HIM-UM001A-EN-P, January 2009

Top ic
In Chapter 2, added new subsection ‘PowerFlex 750-Series IP54, NEMA/UL Type 12 Drives’ with instructions to install the HIM.
In Chapter 3:
In the ‘Single Function Keys’ subsection, added footnote to the single function keys Folders and Controls explaining that these keys are temporarily inactive during drive Start Up.
In the ‘Soft Key Labels’ subsection, added new RESET soft key label to the table.
In the ‘Folder Screens’ subsection, added new Param Access Level menu item to the DEV PARAM folder screen.
In Chapter 4:
In the ‘Setting the Date/Time for the Drive (only PowerFlex 750-Series Drives)’ subsection, revised the Date/Time and Date/Time Set Edit Mode screens.
In the ‘Changing Displayed Items, Adding a Scale Factor or Customizing Tex t’ subsection, revised the Process Display 1 screen.
In the ‘Direct Parameter Access’ subsection, revised the Edit Parameter pop-up box, added a TIP to step 7.
In the ‘Alternate Linear List’ subsection, added a TIP to step 9.
In the ‘Using the CopyCat Function’ section, added an Important statement describing the limitations of the CopyCat
feature with DeviceLogix functions in PowerFlex 750-Series drives.
In the ‘Using Individual Screen Entry Method’ subsection, revised Port Number Selection and Target Parameter Selection pop-up boxes.
Top ic
This was the first release of this manual.
70 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Index

A
accessing parameters
alternate linear list method direct parameter access method
adjusting display contrast Alarm Dspy Type parameter alarm/fault queues for the drive attentions
12
43
42
32
67
44
C
changing PowerFlex 750-Series drive
parameter associations
checking drive/peripheral firmware revisions
47
clearing
drive faults/alarms peripheral events
compatible products contrast adjustment for display CopyCat function creating user-defined drive/peripheral name
35
customizing the Process screen
44 46 12
48
52
32
36
D
date/time setting for PowerFlex 750-Series
33
drives diagnostic items for 20-HIM-A6/-C6S HIMs dimensions direct parameter access method disabling password protection display contrast adjustment DPI Data Rate parameter DPI data rates drive fault/alarm queues drive/peripheral firmware revisions - viewing
65
42
59
32
67
65
44
47
45
H
HIM (Human Interface Module)
adjusting display contrast changing PowerFlex 750-Series drive
checking drive/peripheral firmware revisions
compatible products CopyCat function 48 creating user-defined drive/peripheral name
customizing the Process screen 36 diagnostic items events features 11 firmware or language updating installing
keypad key descriptions LCD display elements/descriptions 24 linking parameters in PowerFlex 700/700S
main screens/descriptions 26 parameter list for HIM port verification (only PowerFlex 750-Series
removing resetting the drive/peripherals selecting language for display text 62 setting date/time for PowerFlex 750-Series
setting display flashing for
setting factory defaults specifications 65 updating HIM firmware or language using a password viewing peripheral diagnostic items viewing/clearing
viewing/editing drive and peripheral
parameter associations
47
35
47
20-HIM-A6 HIM 20-HIM-C6S HIM
drives
drives)
20
drives
alarm indication fault indication
drive faults/alarms peripheral events
parameters
32
52
12
45
63
14
18
21
55
67
60
38
33
41
40
38
63
57
45
44
46
42
E
events for 20-HIM-A6/-C6S HIMs 47
Initial Screen parameter 67 installing
F
factory defaults 38
63
67
44
keypad key descriptions 21
language
Fault Dspy Type parameter fault/alarm queues for the drive
11
features firmware
9
revision update guidelines
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013 71
I
20-HIM-A6 HIM 20-HIM-C6S HIM
14
18
K
L
selecting for display text
63
updating
62
Index
LCD display elements/descriptions 24 linear list access method to parameters linking parameters in PowerFlex 700/700S
55
drives
43
M
main screens/descriptions 26 manual
conventions related documentation 10 website
9
10
P
parameters
convention list of
password protection
changing parameters disabling 59 setting
peripheral diagnostic items - viewing Port Number parameter PowerFlex 750-Series drive port verification
products compatible with HIM
9
67
58
57
45
67
60
12
R
regulatory compliance 66 related documentation removing the HIM resetting the drive/peripherals restoring the drive/peripherals to factory
defaults
10
20
38
38
S
safety precautions 12 screens (main)/descriptions selecting a language setting
display flashing for alarm indication display flashing for fault indication factory defaults password 57
specifications
65
26
62
38
T
technical support 9 time/date setting for PowerFlex 750-Series
33
drives
U
updating HIM firmware or language 63 User Dspy Enable parameter User Dspy Time parameter using the CopyCat function
67
67
48
V
verification of ports for PowerFlex 750-Series
60
drives viewing peripheral diagnostic items viewing/clearing
drive faults/alarms peripheral events
viewing/editing drive and peripheral
parameters
44
46
42
W
website for related documentation 10
41
40
45
72 Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel : (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacic: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel : (852) 2887 4788, Fax: (852) 2508 1846
www.rockwel lautomation.com
Rockwell Automation provides technical information on the Web to assist you in using its products.
http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
At application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Wo rld wide Loca tor
Automation representative.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication
RA-DU002, available at http://www.rockwellautomation.com/literature/.
Publication 20HIM-UM001D-EN-P - February 2013
Supersedes Publication 20HIM-UM001C-EN-P - January 2012 Copyright © 2013 Rockwell Auto mation, Inc. All rights reserved. Pr inted in the U.S.A.
Loading...