Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
The information below summarizes the changes made to this manual since
its last release (March 2002).
Description of ChangesPage
Reformatted document from half size (5.5 x 8.5 in.) to full size (8.5 x 11 in.)Throughout
Added information about Connected Components Workbench software configuration
tool for drives and connected peripherals.
Revised the ‘DPI Ports and Internal Interface Cables’ figure, and the ‘Mounting and
Grounding the Adapter’ figure to show PowerFlex 700H/S Frames 9 and larger.
In the ‘Applying Power’ section in Chapter 2, added new subsections ‘Start-Up
Status Indications’ and ‘Configuring and Verifying Key Drive Parameters’.
In Chapter 3, added new section ‘Updating the Adapter Firmware’. 3-10
In the subsection ‘Reference/Feedback in Discrete I/O Image’ in Chapter 4, added
the following new sub-subsections:
• ‘PowerFlex 70/700/700H, and PowerFlex 700L Drives with 700 Control’
• ‘PowerFlex 700S and PowerFlex 700L Drives with 700S Control’
• ‘PowerFlex 753/755 Drives’
• ‘PowerFlex Digital DC Drives’
In the section ‘Block Transfer I/O Image’ in Chapter 4, added the new subsection
‘Datalink Scaling’.4-9
Revised Appendix D to include the following new sections:
• ‘PowerFlex 70/700/700H, and 700L (with 700 Control) Drives’.
• ‘PowerFlex 700S (Phase II Control) and 700L (with 700S Control) Drives’.
This manual provides information about the adapter and using it with
PowerFlex 7-Class (Architecture-Class) drives. The adapter can be used
with other products that support a DPI™ adapter. See the documentation for
your product for specific information about how it works with the adapter.
P-1
P-2
P-2
Conventions Used in This
Manual
The following conventions are used throughout this manual:
• Parameter names are shown in the format Parameter xx - [*]. The xx
represents the parameter number. The * represents the parameter name
— for example Parameter 01 - [DPI Port].
• Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read ‘Select File > Open’, you
should click the File menu and then click the Open command.
• The firmware revision number (FRN) is displayed as FRN X.xxx, where
‘X’ is the major revision number and ‘xxx’ is the minor revision number.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
P-2About This Manual
Rockwell Automation
Support
Rockwell Automation offers support services worldwide, with over 75 sales
and support offices, over 500 authorized distributors, and over 250
authorized systems integrators located throughout the United States alone.
In addition, Rockwell Automation representatives are in every major
country in the world.
Local Product Support
Contact your local Rockwell Automation representative for:
• Sales and order support
• Product technical training
• Warranty support
• Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 6,
Troubleshooting
Allen-Bradley Technical Support website at www.ab.com/support/abdrives
or contact Rockwell Automation.
, first. If you still have problems, then access the
PowerFlex 20-HIM-A3/-A5/-C3S/-C5S HIM Quick Reference, publication 20HIM-QR001
PowerFlex 20-HIM-A6/C6S HIM (Human Interface Module) User Manual, publication 20HIM-UM001
PowerFlex 70 User Manual, publication 20A-UM001
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70 Enhanced Control and 700 Vector Control Reference Manual, publication PFLEX-RM004
PowerFlex 700 Series A User Manual, publication 20B-UM001
PowerFlex 700 Series B User Manual, publication 20B-UM002
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70 Enhanced Control and 700 Vector Control Reference Manual, publication PFLEX-RM004
These documents contain additional information concerning related
products from Rockwell Automation.
Information on installing PowerFlex
Communication Adapters.
Information on the Connected Components Workbench
software tool—and includes a link for free software download.
, and online help
, and online help
(1)
(1)
Information on using PowerFlex 20-HIM-A3, 20-HIM-A5,
Information on using the DriveExplorer™ software tool.
Information on using the DriveExecutive™ software tool.
20-HIM-C3S, and 20-HIM-C5S HIMs.
Information on installing and using PowerFlex 20-HIM-A6 and
20-HIM-C6S HIMs.
Information on installing and programming PowerFlex 70
standard control and enhanced control drives.
Information on installing and programming PowerFlex 700
standard control and vector control Series A drives, and
PowerFlex 700 vector control Series B drives.
Information on installing and programming PowerFlex 700H
drives.
®
20-COMM-x Network
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
ResourceDescription
PowerFlex 700S w/Phase I Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S w/Phase I Control Installation Manual (Frames 9 and 10), publication PFLEX-IN006
PowerFlex 700S w/Phase I Control User Manual (All Frame Sizes), publication 20D-UM001
PowerFlex 700S w/Phase I Control Reference Manual, publication PFLEX-RM002
PowerFlex 700S w/Phase II Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S w/Phase II Control Installation Manual (Frames 9…14), publication PFLEX-IN006
PowerFlex 700S w/Phase II Control Programming Manual (All Frame Sizes), publication 20D-PM001
PowerFlex 700S w/Phase II Control Reference Manual, publication PFLEX-RM003
Information on installing and programming PowerFlex 700L
Information on installing and programming PowerFlex Digital
, and online help
, and online help
(1)
, and online help
(1)
, and online help
Information on installing and programming PowerFlex 700S
drives.
Liquid-Cooled AC drives.
Information on installing and programming PowerFlex
750-Series AC drives.
DC drives.
Information on using RSLinx® Classic software.
(1)
Information on installing and navigating the RSLogix Emulate
software for ladder logic programming with Allen-Bradley
PLC-5 and SLC 500 processors.
Information on using the RSLogix™ 500 software tool.
(1)
Information on using the RSLogix™ 5000 software tool.
About This ManualP-3
Documentation can be obtained online at http://
literature.rockwellautomation.com. To order paper copies of technical
documentation, contact your local Rockwell Automation distributor or sales
representative.
To find your local Rockwell Automation distributor or sales representative,
visit http://www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related
questions, go to the Drives Service & Support website at http://
www.ab.com/support/abdrives and click on the Downloads or
Knowledgebase link.
.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
P-4About This Manual
Notes:
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
➊
➋
➌
➍
➎
Chapter 1
Getting Started
The adapter is intended for installation into a PowerFlex 7-Class drive and
is used for network communication.
When used with PowerFlex 750-Series drives, the 20-COMM-R adapter
must have firmware revision 1.010 or later, and must be installed using the
20-750-20COMM or 20-750-20COMM-F1 Communication Carrier Card.
This manual does include some information on using the 20-COMM-R
adapter with PowerFlex 750-Series drives—but there are operating
limitations. For details, see Compatible Products
TopicPage
Components
Features
Compatible Products
Required Equipment
Safety Precautions
Quick Start
1-1
1-2
1-3
1-3
1-5
1-6
on page 1-3.
Components
Item PartDescription
Status IndicatorsThree status indicators that indicate the status of the DPI, adapter,
➊
DPI ConnectorA 20-pin, single-row shrouded male header. An Internal Interface
➋
Remote I/O ConnectorA standard 3-pin connector to connect to the network.
➌
Rack Address Rotary
➍
Switches
Configuration DIP
➎
Switches
and network connection. See Chapter 6
cable is connected to this connector and a connector on the drive.
Switches to set the rack address. See Setting the Rack Address
Rotary Switches on page 2-2.
Switches to set the starting module group, last rack, rack size, and
baud rate. See Setting the Configuration DIP Switches
, Troubleshooting.
on page 2-3.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
1-2Getting Started
Features
The features of the adapter include the following:
• Typical mounting in a PowerFlex 7-Class drive.
• Captive screws to secure and ground the adapter to the drive.
• Compatibility with various configuration tools to configure the adapter
and connected host drive, including the following tools:
– PowerFlex HIM (Human Interface Module) on the drive, if available
– Connected Components Workbench software, version 1.02 or later
– DriveExplorer software, version 2.01 or later
– DriveExecutive software, version 3.01 or later
• Rotary switches to set a rack address before applying power to the
PowerFlex drive. Or, you can disable the switches and use an adapter
parameter to set the rack address.
• DIP switches to configure the adapter for starting module group, last/not
last RIO group within the rack, 1/4 or 1/2 rack, and baud rate. Or, you
can disable the switches and use adapter parameters to configure the
adapter.
• Status indicators that report the status of the drive communications, the
adapter, and network. They are visible when the drive cover is open or
closed.
• Parameter-configured I/O (Logic Command/Reference and up to four
pairs of Datalinks) to accommodate application requirements. The
adapter can be configured to use a 1/4 rack (two 16-bit words) or 1/2
rack (four 16-bit words) of discrete I/O. Additionally, up to eighteen
16-bit words of I/O can be transferred using the Block Transfer I/O
image without increasing the size of the discrete I/O rack. See Chapter 4
Using Discrete and Block Transfer I/O
for more information.
,
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
• Block Transfer Messaging support.
• User-defined fault actions to determine how the adapter and connected
PowerFlex drive respond to the following:
– I/O messaging communication disruptions (Comm Flt Action)
– Controllers in idle mode (Idle Flt Action)
• Access to any PowerFlex drive and its connected peripherals on the
network to which the adapter is connected.
Getting Started1-3
Compatible Products
Required Equipment
At the time of publication, the adapter is compatible with the following
products:
• PowerFlex 70 drives with standard or enhanced control• PowerFlex 750-Series drives
• PowerFlex 700 drives with standard or vector control• PowerFlex Digital DC drives
• PowerFlex 700H drives• SMC™ Flex smart motor controllers
• PowerFlex 700S drives with Phase I or Phase II control• SMC-50 smart motor controllers
• PowerFlex 700L drives with 700 vector control or 700S control
(1)
The 20-COMM-R adapter can be used with PowerFlex 750-Series drives, but the adapter must have firmware revision 1.01
or later. Also, the adapter has the following limitations and differences:
- Only the first 16 bits of the Logic Command and Logic Status words are used.
- Only drive Ports 0…6 are supported.
- Controller must be capable of reading/writing 32-bit floating point (REAL) values.
- Speed Reference/Feedback scaling are Hz (or RPM) x 1000 (depending on the setting of drive parameter 300 - [Speed
Units].
See the PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001, for drive parameter information.
Some of the equipment that is required for use with the adapter is shipped
with the adapter, but some you must supply yourself.
(1)
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes the
following:
❑ One 20-COMM-R adapter
❑ One 2.54 cm (1 in.) long and one 15.24 cm (6 in.) long Internal
Interface cable (only one cable is needed to connect the adapter to the
drive; for which cable to use, see Figure 2.3 on page 2-5
❑ One 3-pin Remote I/O plug (connected to the Remote I/O connector on
the adapter)
❑ Two termination resistors (one 82 ohm and one 150 ohm resistor)
❑ One PowerFlex 7-Class DPI (Drive Peripheral Interface) Network
Communication Adapter Installation Instructions, publication
20COMM-IN004
TIP: When mounting the 20-COMM-R adapter in a PowerFlex 750-Series
drive, you must use a 20-750-20COMM or 20-750-20COMM-F1
Communication Carrier Card, publication 750COM-IN001—and the
20-COMM-R adapter must have firmware revision 1.010 or later.
)
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
1-4Getting Started
User-Supplied Equipment
To install and configure the adapter, you must supply the following:
❑ A small flathead screwdriver
❑ Remote I/O cable
❑ Drive and adapter configuration tool, such as the following:
– PowerFlex 20-HIM-xx HIM
– Connected Components Workbench software, version 1.02 or later
Connected Components Workbench is the recommended
stand-alone software tool for use with PowerFlex drives. You can
obtain a free copy by:
• Internet download at http://www.ab.com/support/abdrives/
webupdate/software.html
• Requesting a DVD at http://www.ab.com/onecontact/controllers/
micro800/
Your local distributor may also have copies of the DVD available.
Connected Components Workbench software cannot be used to
configure SCANport-based drives or Bulletin 160 drives.
– DriveExplorer software, version 2.01 or later
This software tool has been discontinued and is now available as
freeware at http://www.ab.com/support/abdrives/webupdate/
software.html. There are no plans to provide future updates to this
tool and the download is being provided ‘as-is’ for users that lost
their DriveExplorer CD, or need to configure legacy products not
supported by Connected Components Workbench software.
– DriveExecutive software, version 3.01 or later
A Lite version of DriveExecutive software ships with RSLogix
5000, RSNetWorx MD, FactoryTalk AssetCentre, and
ItelliCENTER software. All other versions are purchasable items:
• 9303-4DTE01ENE Drive Executive software
• 9303-4DTS01ENE DriveTools SP Suite (includes
DriveExecutive and DriveObserver software)
• 9303-4DTE2S01ENE DriveExecutive software upgrade to
DriveTools SP Suite (adds DriveObserver software)
DriveExecutive software updates (patches, and so forth) can be
obtained at http://www.ab.com/support/abdrives/webupdate/
software.html. It is highly recommended that you periodically check
for and install the latest update.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
❑ Controller configuration tool, such as RSLogix 5, RSLogix 500, or
RSLogix 5000 software
❑ A computer connection to the Remote I/O network by way of a
1203-USB serial converter
Getting Started1-5
!
!
!
!
!
!
!
!
Safety Precautions
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
Remove all power from the PowerFlex drive, and then verify
power has been discharged before installing or removing an
adapter.
ATTENTION: Risk of injury or equipment damage exists. Only
personnel familiar with drive and power products and the
associated machinery should plan or implement the installation,
start up, configuration, and subsequent maintenance of the
product using an adapter. Failure to comply may result in injury
and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The adapter
contains electrostatic discharge (ESD) sensitive parts that can be
damaged if you do not follow ESD control procedures. Static
control precautions are required when handling the adapter. If
you are unfamiliar with static control procedures, see Guarding
Against Electrostatic Damage, publication 8000-4.5.2.
ATTENTION: Risk of injury or equipment damage exists. DPI
or SCANport host products must not be directly connected
together using 1202 cables. Unpredictable behavior due to timing
and other internal procedures can result if two or more devices
are connected this way.
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault
when you reset the adapter. Determine how your drive will
respond before resetting an adapter.
ATTENTION: Risk of injury or equipment damage exists.
Parameters 10 - [Comm Flt Action] and 11 - [Idle Flt Action]
let you determine the action of the adapter and connected drive if
I/O communication is disrupted or the controller is idle. By
default, these parameters fault the drive. You can set these
parameters so that the drive continues to run, however,
precautions should be taken to verify that the settings of these
parameters do not create a risk of injury or equipment damage.
When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable
or a faulted controller).
ATTENTION: Risk of injury or equipment damage exists.
When a system is configured for the first time, there may be
unintended or incorrect machine motion. Disconnect the motor
from the machine or process during initial system testing.
ATTENTION: Risk of injury or equipment damage exists. The
examples in this publication are intended solely for purposes of
example. There are many variables and requirements with any
application. Rockwell Automation does not assume responsibility
or liability (to include intellectual property liability) for actual
use of the examples shown in this publication.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
1-6Getting Started
Quick Start
This section is provided to help experienced users quickly start using the
adapter. If you are unsure how to complete a step, see the referenced chapter.
Step ActionSee
1Review the safety precautions for the adapter.Throughout this manual
2Verify that the PowerFlex drive is properly installed.Drive User Manual
Chapter 2
Installing the Adapter
PowerFlex 7-Class DPI
Network Communication
Adapter Installation
Instructions, publication
20COMM-IN004) and
Chapter 2
Installing the Adapter
Chapter 2
Installing the Adapter
Chapter 3,
Configuring the Adapter
Chapter 4
Using Discrete and
Block Transfer I/O
Chapter 5,
Using Block Transfer
Messaging
Chapter 6,
Troubleshooting
3Commission the adapter.
a. With power removed, use the adapter Rack Address Rotary
Switches to set a unique rack address on the network.
b. Use the Configuration DIP Switches to set the following:
• Starting remote I/O module group (SW1 and SW2)
• Last rack (SW3)
• Rack size (SW4)
• Remote I/O baud rate (SW7 and SW8)
NOTE: If desired, the Rack Address Rotary Switches and
Configuration DIP Switches can be disabled so that adapter
parameters can be used instead to set these items. To disable all
hardware switch settings, set Configuration DIP Switches SW7
and SW8 both to the ‘On’ position. Then configure the appropriate
adapter parameters after applying power to the adapter.
4Install the adapter.
a. Verify that the PowerFlex drive is not powered.
b. Connect the adapter to the drive with the Internal Interface
cable.
c. Use the captive screws to secure and ground the adapter to
the drive.
d. Connect the adapter to the network with a Remote I/O cable.
NOTE: When installing the adapter in a PowerFlex 750-Series
drive, see the 20-750-20COMM and 20-750-20COMM-F1
Communication Carrier Cards Installation Instructions,
publication 750COM-IN001, supplied with the card.
5Apply power to the adapter.
a. Verify that the adapter is installed correctly.
The adapter receives power from the drive.
b. Apply power to the drive.
The status indicators should be green. If they flash red, there
is a problem. See Chapter 6
c. Configure and verify key drive parameters.
6Configure the adapter for your application.
Set adapter parameters for the following functions as required by
your application:
• Rack address, starting module group, last rack, rack size, and
baud rate (only when Configuration DIP Switches SW7 and
SW8 are both disabled—set to ‘On’)
• I/O configuration
• Fault actions
7Create a ladder logic program.
Use a controller configuration tool such as RSLogix software to
create a ladder logic program that lets you to do the following:
• Control the connected drive, by way of the adapter, by using
Discrete I/O and Block Transfer I/O.
• Monitor or configure the drive using Block Transfer Explicit
messages.
, Troubleshooting.
,
,
,
,
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
Chapter 2
Installing the Adapter
This chapter provides instructions for installing the adapter in a PowerFlex
7-Class drive.
TopicPage
Preparing for an Installation
Selecting Remote I/O Cables
Commissioning the Adapter
Connecting the Adapter to the Drive
Connecting the Adapter to the Network
Applying Power
2-1
2-1
2-2
2-4
2-7
2-8
Preparing for an Installation
Selecting Remote I/O Cables
Before installing the adapter, verify that you have all required equipment.
See Required Equipment
Remote I/O adapters are connected to the Remote I/O network or link with
twinaxial cable used for Remote I/O and Data Highway Plus (DH+)
communications. When selecting a cable, remember these points:
• Only 1770-CD Belden #9463 is tested and approved for Remote I/O and
DH+ installations. Use other cables at your own risk.
• The maximum cable length depends on the baud rate.
Baud RateMaximum Cable Length
57.6 Kbps3,048 m (10,000 ft)
115.2 Kbps1,524 m (5,000 ft)
230.4 Kbps762 m (2,500 ft)
• All three connectors (blue, shield, and clear) must be connected at each
node.
• Do not use a star topology. Only two cables may be connected at any
wiring point. You can use a series topology and daisy-chain two wires at
a point.
on page 1-3.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
2-2Installing the Adapter
!
!
Commissioning the Adapter
To commission the adapter, set the Rack Address Rotary Switches and the
Configuration DIP Switches. Either set these switches to the desired
settings or disable them by sliding Configuration DIP Switches SW7 and
SW8 to the ‘On’ position so that adapter parameters can be used instead.
Important: New switch settings are recognized only when power is applied
to the adapter or it is reset. After you change a switch setting,
cycle power or reset the adapter.
ATTENTION: Risk of equipment damage exists. The adapter
contains electrostatic discharge (ESD) sensitive parts that can be
damaged if you do not follow ESD control procedures. Static
control precautions are required when handling the adapter. If you
are unfamiliar with static control procedures, see Guarding
Against Electrostatic Damage, publication 8000-4.5.2.
ATTENTION: Risk of equipment damage exists. Pen ink or
pencil lead may damage the adapter switches. Do not use a pen or
pencil to set the switches.
Setting the Rack Address Rotary Switches
The adapter accepts a rack address between 00 and 77 octal. The default
setting is 01. See Table 3.A on page 3-3
of the octal address to be used. Set the Rack Address Rotary Switches
(Figure 2.1
octal value, but is internally converted to a decimal address. Each Remote I/
O device must have a unique rack address that the controller can recognize.
Note the following points:
) to the octal address. The address is entered and displayed as an
to determine the decimal equivalent
• Although the adapter supports rack addresses up to 77 octal, not all
controllers recognize all of the addresses, and a Remote I/O channel can
support only 32 devices.
• If Configuration DIP Switches SW7 and SW8 are both set to ‘On’, the
adapter uses the decimal rack address set in Parameter 3 - [RIO Addr
2
1
0
9
8
on page 3-3.
3
7
2
1
4
5
0
6
9
8
3
4
5
6
7
Cfg]. See Setting the Rack Address
• PLC-2 controllers identify rack addresses differently than other
controllers. PLC-2 controllers identify the adapter rack address as one
plus the value of the switch settings.
Figure 2.1Setting the Rack Address Rotary Switches (Octal)
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
Installing the Adapter2-3
ON
1
2
3
4
5
6
7
8
On = 1
Off = 0
The Rack Address Rotary Switch settings can be verified (as a decimal
value) by viewing Diagnostic Device Item number 29 (page 6-4
Setting the Configuration DIP Switches
Set the Configuration DIP Switches (Figure 2.2) to match your application
specifics for the controller and network.
Figure 2.2Setting the Configuration DIP Switches
).
SwitchesSetting Description
SW1 and SW212 SW1 and SW2 are used together to set the starting module group:
00 Group 0 (Default)
10 Group 2
01 Group 4
11 Group 6 – Only used if SW4 is set to “0” (1/4 rack).
SW30Not the last RIO rack (Default)
1Last RIO group within the rack
SW401/4 rack (Default)
11/2 rack
SW50Not Used
SW60Not Used
SW7 and SW878 SW7 and SW8 are used together to set the Remote I/O baud rate:
00 57.6 kbps (Default)
10 115.2 kbps
01 230.4 kbps
11 Disables all hardware switches. Instead, the adapter uses the values
of the following parameters:
• Parameter 3 - [RIO Addr Cfg] for the rack address
• Parameter 5 - [RIO Rate Cfg] for the baud rate
• Parameter 25 - [Start RIO Group] for the starting module group
• Parameter 26 - [Last RIO Rack] for the last physical rack
• Parameter 27 - [Rack Size] for the rack size
The Configuration DIP Switches SW7 and SW8 settings can be verified by
viewing Parameter 24 - [Switches] with any of the following drive
configuration tools:
• PowerFlex HIM
• Connected Components Workbench software, version 1.02 or later
• Drive Explorer software, version 2.01 or later
• DriveExecutive software, version 3.01 or later
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
2-4Installing the Adapter
!
The settings for all of the Configuration DIP Switches can be verified by
viewing Diagnostic Item number 28 (page 6-4
).
Connecting the Adapter to
the Drive
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
Remove power from the drive, and then verify power has been
discharged before installing or removing the adapter.
1.Remove power from the drive.
2.Use static control precautions.
3.Remove or open the drive cover.
4.Connect the Internal Interface cable to the DPI port on the drive and
then to the DPI connector on the adapter (see Figure 2.3
5.Secure and ground the adapter to the drive (see Figure 2.4
following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive
screws.
– On a PowerFlex 700, PowerFlex 700H, or PowerFlex 700S drive,
mount the adapter on the drive using the four captive screws.
).
) by doing the
Important: Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 N•m (8.0 lb•in).
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
PowerFlex 70 - All Frames
PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6
HIM panel opens to
allow access to DPI
interface. To open
panel, remove screws
on left side of HIM
panel and swing open.
PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger
20-COMM-R Adapter
Installing the Adapter2-5
Figure 2.3DPI Ports and Internal Interface Cables
➊
➋
➌
➍
ItemDescription
15.24 cm (6 in.) Internal Interface cable
➊
DPI Connector
➋
Remote I/O cable
➌
2.54 cm (1 in.) Internal Interface cable
➍
X2
X1
➍
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
2-6Installing the Adapter
X1
X2
Drive
Adapter
Internal Interface Cable
folded behind the adapter
and in front of the drive.
PowerFlex 70 - All Frame Sizes
(Adapter mounts in drive.)
Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw, verify
continuity exists between the head of
the screw and drive ground.
Ground Tab Detail
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
(Adapter mounts on door.)
0.9 N•m
(8.0 lb•in)
4 Places
PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6
(Adapter mounts in drive.)
0.9 N•m
(8.0 lb•in) 4
Places
Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw, verify
continuity exists between the head of
the screw and drive ground.
0.9 N•m
(8.0 lb•in)
4 Places
PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger
(Adapter mounts behind HIM panel.)
Ground Tab Detail
Figure 2.4Mounting and Grounding the Adapter
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
NOTE: When installing the adapter in a PowerFlex 750-Series drive, see
the 20-750-20COMM and 20-750-20COMM-F1 Communication Carrier
Card Installation Instructions, publication 750COM-IN001, supplied with
the card.
Installing the Adapter2-7
!
Clear
Shield
Blue
Clear
Shield
Blue
Single ConnectionDaisy-Chain Connection
Connecting the Adapter to
the Network
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
Remove power from the drive, and then verify power has been
discharged before installing or removing the adapter.
1.Remove power from the drive.
2.Use static control precautions.
3.Connect a Remote I/O cable to the controller or create a daisy-chain
from another device on the Remote I/O network (see Figure 2.5
Important: Maximum cable length depends on the Remote I/O baud
rate. See Selecting Remote I/O Cables
details.
Figure 2.5Connecting a Remote I/O Cable to the Network
on page 2-1 for
).
4.Route the other end of the Remote I/O cable through the bottom of the
drive (Figure 2.4
5.Connect a 3-pin Remote I/O plug to the cable.
Figure 2.6Connecting a 3-Pin Remote I/O Plug to the Cable
).
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
2-8Installing the Adapter
!
6.If the adapter is at the end of the Remote I/O link, connect a termination
resistor (see Figure 2.7
The resistor should have a value of 82 or 150 ohms (82 ohms is
preferred).
Important: If the Remote I/O network is operating at 230.4 Kbps, an
82 ohm termination resistor must be used.
Important: If any of the following products, which cannot operate at
230.4 Kbps, are on the Remote I/O network, a 150 ohm
termination resistor must be used.
• 1771-SN scanner• 6008-SQH1 scanner
• 1772-SD scanner• 6008-SQH scanner
• 1772-SD2 scanner• 1771-AS adapter
• 1772-SR scanner• 1772-ASB (Ser. A) adapter
• 1775-S4A scanner• 1771-DCM adapter
• 1775-S4B scanner• 1771-AF device
Figure 2.7Connecting a Termination Resistor (if required)
).
Applying Power
Clear
Shield
Blue
7.Connect the Remote I/O cable plug to the adapter’s mating connector.
ATTENTION: Risk of equipment damage, injury, or death
exists. Unpredictable operation may occur if you fail to verify
that parameter settings are compatible with your application.
Verify that settings are compatible with your application before
applying power to the drive.
Install the drive cover or close the drive door, and apply power to the drive.
The adapter receives its power from the connected drive. When you apply
power to the adapter for the first time, its topmost ‘PORT’ status indicator
should be steady green or flashing green after an initialization. If it is red,
there is a problem. See Chapter 6
Start-Up Status Indications
Termination Resistor
(82 Ohms or 150 Ohms)
, Troubleshooting.
Status indicators for the drive and communication adapter can be viewed on
the front of the drive (Figure 2.8
start-up status indications are shown in Table 2. A
) after power has been applied. Possible
.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
Installing the Adapter2-9
Figure 2.8Drive and Adapter Status Indicators (location on drive may vary)
PORT
MOD
➋
Table 2.A Drive and Adapter Start-Up Status Indications
NET A
NET B
➊
STS
Item NameColorStateDescription
Drive STS Indicator
STS
➊
(Status)
PORTGreenFlashingNormal operation. The adapter is establishing an I/O
➋
MODGreenFlashingNormal operation. The adapter is operating but is not
NET AGreenFlashingThe adapter is properly connected, but the controller is
NET B——Not used by Remote I/O adapter.
GreenFlashingDrive ready but not running, and no faults are present.
SteadyDrive running, no faults are present.
YellowFlashing,
drive stopped
Flashing,
drive running
Steady,
drive running
RedFlashingA fault has occurred.
SteadyA non-resettable fault has occurred.
Adapter Status Indicators
SteadyNormal operation. The adapter is properly connected
SteadyNormal operation. The adapter is operating and
SteadyNormal operation. The adapter is properly connected
An inhibit condition exists – the drive cannot be
started. Check drive Parameter 214 - [Start Inhibits].
An intermittent type 1 alarm condition is occurring.
Check drive Parameter 211 - [Drive Alarm 1].
A continuous type 1 alarm condition exists. Check
drive Parameter 211 - [Drive Alarm 1].
connection to the drive. It will turn steady green or red.
and communicating with the drive.
transferring I/O data to a controller.
transferring I/O data to a controller.
resetting, in test mode, in program mode, or not
properly configured to communicate with the adapter.
and communicating on the network.
For more details on status indicator operation, see page 6-2 and page 6-3.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
2-10Installing the Adapter
Configuring and Verifying Key Drive Parameters
The PowerFlex 7-Class drive can be separately configured for the control
and Reference functions in various combinations. For example, you could
set the drive to have its control come from a peripheral or terminal block
with the Reference coming from the network. Or you could set the drive to
have its control come from the network with the Reference coming from
another peripheral or terminal block. Or you could set the drive to have both
its control and Reference come from the network.
The following steps in this section assume that the drive will receive the
Logic Command and Reference from the network.
1.Use drive Parameter 090 - [Speed Ref A Sel] to set the drive speed
Reference to ‘22’ (DPI Port 5).
2.If hard-wired discrete digital inputs are not used to control the drive,
verify that unused digital input drive Parameters 361 - [Dig In1 Sel] and
362 - [Dig In2 Sel] are set to ‘0’ (Not Used).
3.Verify that drive Parameter 213 - [Speed Ref Source] is reporting that
the source of the Reference to the drive is ‘22’ (DPI Port 5).
This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded Speed]. If a
problem occurs, this verification step provides the diagnostic capability
to determine whether the drive/adapter or the network is the cause.
TIP: For PowerFlex 750-Series drives, use drive Parameter 545 [Speed Ref A Sel] to set the drive speed Reference:
a.Set the Port field to ‘Port 0 - PowerFlex 75x’.
b.Set the Parameter field to point to the port in which the
20-COMM-R adapter/20-750-20COMM Communication Carrier
Card are installed (for example, ‘876 - Port 6 Reference’).
The number ‘876’ in the Parameter field of the example is the
parameter in the drive that points to the port.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
Chapter 3
Configuring the Adapter
This chapter provides instructions and information for setting the
parameters to configure the adapter.
TopicPage
Configuration Tools
Using the PowerFlex 7-Class HIM to Access Parameters
Setting the Rack Address
Setting the Baud Rate
Setting the Starting Module Group
Setting the Last Rack
Setting the Rack Size
Setting the I/O Configuration
Setting a Fault Action
Resetting the Adapter
Viewing the Adapter Status Using Parameters
Updating the Adapter Firmware
3-1
3-2
3-3
3-4
3-4
3-5
3-5
3-6
3-7
3-8
3-9
3-10
Configuration Tools
For a list of parameters, see Appendix
definitions of terms in this chapter, see the Glossary
The adapter stores parameters and other information in its own nonvolatile
storage (NVS) memory. You must, therefore, access the adapter to view and
edit its parameters. The following tools can be used to access the adapter
parameters.
ToolSee
PowerFlex 7-Class HIMpage 3-2
Connected Components Workbench
software, version 1.02 or later
DriveExplorer software,
version 2.01 or later
DriveExecutive software,
version 3.01 or later
B, Adapter Parameters. For
.
http://www.ab.com/support/abdrives/webupdate/
software.html, or online help (installed with the software)
http://www.ab.com/drives/driveexplorer
DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools
DriveExecutive online help (installed with the software)
, or
, or
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
3-2Configuring the Adapter
ALT
Sel
F-> StoppedAuto
0.00Hz
Main Menu:
Diagnostics
Parameter
Device Select
Por t 5 Device
20-COMM-R
Main Menu:
Diagnostics
Parameter
Using the PowerFlex 7-Class
HIM to Access Parameters
If your drive has either an LED or LCD HIM (Human Interface Module), it
can be used to access parameters in the adapter as shown below. We
recommend that you read through the steps for your HIM before performing
the sequence. For additional information, see the drive documentation or the
PowerFlex 7-Class HIM Quick Reference, publication 20HIM-QR001.
Using an LED HIM
StepExample Screens
1. Press the key and then the Device (Sel) key to
display the Device Screen.
2. Press the or key to scroll to the adapter.
Letters represent files in the drive, and numbers represent
ports. The adapter is usually connected to port 5.
3. Press the (Enter) key to enter your selection.
A parameter database is constructed, and then the first
parameter is displayed.
4. Edit the parameters using the same techniques that you use
to edit drive parameters.
Using an LCD HIM
StepExample Screens
1. In the main menu, press the or key to scroll to
Device Select.
2. Press the (Enter) key to enter your selection.
3. Press the or key to scroll to the adapter
(20-COMM-R).
4. Press the (Enter) key to select the adapter.
A parameter database is constructed, and then the main
menu for the adapter is displayed.
5. Edit the parameters using the same techniques that you use
to edit drive parameters.
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
NOTE: All configuration procedures throughout this chapter use the
PowerFlex 7-Class LCD HIM to access parameters in the adapter and show
example LCD HIM screens.
TIP: When using a PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, see its
User Manual, publication 20HIM-UM001.
Configuring the Adapter3-3
Por t 5 Device
20-COMM-R
Parameter #: 03
RIO Addr Cfg
1
0 <> 63
Default = 01
Setting the Rack Address
If adapter Configuration DIP Switches SW7 and SW8 (Figure 2.2) are both
set to ‘On’, the value of Parameter 03 - [RIO Addr Cfg] determines the
rack address. Note these points:
•Although the adapter supports rack addresses between 00 and 77 octal,
not all controllers recognize all of the addresses, and a Remote I/O
channel can support only 32 devices.
•PLC-2 controllers identify rack addresses differently than other
controllers. PLC-2 controllers identify the adapter rack address as one
plus the value of the parameter setting.
1.See Tab le 3. A
be used.
The rack address must be unique.
Table 3.A Rack Addresses (Decimal Equivalent versus Octal)
to determine the decimal equivalent of the octal address to
2.Set the value of Parameter 03 - [RIO Addr Cfg] to the decimal
equivalent of the octal address to be used.
The address is entered and displayed as a decimal value, but is
internally converted to an octal address.
Important: The HIM and software tools, such as DriveExplorer or
DriveExecutive, will display the address as a decimal value.
3.Reset the adapter (see Resetting the Adapter
on page 3-8).
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
3-4Configuring the Adapter
Por t 5 Device
20-COMM-R
Parameter #: 05
RIO Rate Cfg
0
57.6 kbps
ValueBaud Rate
057.6 Kbps (default)
1115.2 Kbps
2230.4 Kbps
Por t 5 Device
20-COMM-R
Parameter #: 25
Start RIO Group
0
Group 0
ValueBaud Ra te
0Group 0 (default)
1Group 2
2Group 4
3Group 6
Do not use this value if the
adapter uses a 1/2 rack, which
results in an error.
Setting the Baud Rate
Setting the Starting Module
Group
If adapter Configuration DIP Switches SW7 and SW8 (Figure 2.2) are both
set to ‘On’, the value of Parameter 05 - [RIO Rate Cfg] determines the
Remote I/O baud rate.
1.Set the value of Parameter 05 - [RIO Rate Cfg] to the baud rate at which
your network is operating.
2.Reset the adapter (see Resetting the Adapter
If adapter Configuration DIP Switches SW7 and SW8 (Figure 2.2) are both
set to ‘On’, the value of Parameter 25 - [Start RIO Group] determines the
starting module group.
1.Set the value of Parameter 25 - [Start RIO Group] to the desired
starting group.
on page 3-8).
2.Reset the adapter (see Resetting the Adapter
on page 3-8).
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
Loading...
+ 98 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.