Modbus RTU
Metasys N2
Siemens Building Technologies P1 FLN
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online atwww.rockwellautomation.com/literature) describes some important differences
between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect
or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility
or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use
of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
http://
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
WARNING: Identifies information about practices or
circumstances that can cause an explosion in a hazardous
!
environment, which may lead to personal injury or death, property
damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
!
damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that dangerous voltage may be
present.
Burn Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that surfaces may be at
dangerous temperatures.
20-COMM-H RS-485 HVAC Adapter User Manual
PowerFlex, SMC Flex, DriveExplorer, DriveExecutive, DPI, DriveTools SP, and SCANport are either trademarks or registered trademarks
of Rockwell Automation, Inc.
Metasys is a trademark of Johnson Controls, Inc.
Modbus is a trademark of Schneider Automation.
P1 FLN is a trademark of Siemens Building Technologies.
Windows and Microsoft are registered trademarks of Microsoft Corporation.
Summary of Changes
The information below summarizes the changes made to this manual since
its last release (March 2004):
Description of ChangesPage
Reformatted document from half size (5.5 x 8.5 in.) to full size (8.5 x 11 in.)Throughout
Added SMC Flex to the list of compatible products, and Metasys N2 is compatible with
PowerFlex 700VC drive.
Added new Adapter Modbus Register Map section.4-2
Included information about using Modbus RTU mode to access 16-bit and 32-bit
parameters.
Added new Adapter Parameter Direct Access section.4-13
Added new Metasys N2 Device Identity subsection.5-1
Added new “Reference Setup Examples” subsection.5-4
Added tip about configuring Analog Data Integers (ADIs).5-9
Added Flashing Red/Green MOD status indicator information.8-3
Added new Parameter 32 - [RTU Param Mode] to select the 16-bit default mode or
optional 32-bit mode in which the adapter operates.
PowerFlex 700 User Manual
PowerFlex 700 Series B User Manual
PowerFlex 70/700 Reference Manual
PowerFlex 70EC/700VC Reference Manual
PowerFlex 700H Programming Manual
PowerFlex 700S with Phase I Control User Manual
PowerFlex 700S with Phase II Control User Manual
PowerFlex 700S Reference Manual
PowerFlex 700S Installation Instructions
PowerFlex 700S with Phase I Control User Manual
PowerFlex 700S with Phase II Control User Manual
PowerFlex 700S Reference Manual
P-1
—
—
20A-UM001
PFLEX-RM001
PFLEX-RM004
20B-UM001
20B-UM002
PFLEX-RM001
PFLEX-RM004
PFLEX-IN006
20C-PM001
20D-UM001
20D-UM006
PFLEX-RM002
PFLEX-IN006
20D-UM001
20D-UM006
PFLEX-RM002
You can view or download publications at
www.literature.rockwellautomation.com
documentation, contact your local Rockwell Automation distributor or sales
representative.
To find your local Rockwell Automation distributor or sales representative,
visit www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related
questions, go to the Drives Service & Support web site at www.ab.com/
support/abdrives and click on the “Downloads” or “Knowledgebase” link.
. To order paper copies of technical
.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
P-2About This Manual
Rockwell Automation
Support
Rockwell Automation, Inc. offers support services worldwide, with over 75
sales/support offices, over 500 authorized distributors, and over 250
authorized systems integrators located through the United States alone. In
addition, Rockwell Automation, Inc. representatives are in every major
country in the world.
Local Product Support
Contact your local Rockwell Automation, Inc. representative for:
• Sales and order support
• Product technical training
• Warranty support
• Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 8,
Troubleshooting
Allen-Bradley Technical Support web site at www.ab.com/support/abdrives
or contact Rockwell Automation, Inc.
, first. If you still have problems, then access the
Conventions Used in This
Manual
The following conventions are used throughout this manual:
• Parameter names are shown in the format Parameter xx - [*]. The xx
represents the parameter number. The * represents the parameter name—
for example Parameter 01 - [DPI Port].
• Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read “Select File > Open,” you
should click the File menu and then click the Open command.
• The firmware release is displayed as FRN X.xxx. The “FRN” signifies
Firmware Release Number. The “X” is the major release number. The
“xxx” is the minor update number.
• This manual provides information about the adapter and using it with
PowerFlex 7-Class (Architecture-Class) drives. The adapter can be used
with other products that support a DPI™ adapter, such as SMC™ Flex.
Refer to the documentation for your product for specific information
about how it works with the adapter.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Chapter 1
Getting Started
The adapter is a communication option intended for installation into a
PowerFlex 7-Class drive. It can also be used with other Allen-Bradley
products that support a DPI™ (Drive Peripheral Interface) adapter.
Status IndicatorsFour LEDs that indicate the status of the DPI, the adapter, and
➊
DPI ConnectorA 20-pin, single-row shrouded male header. An Internal Interface
➋
Terminal BlockA 6-screw terminal block connects the adapter to the network.
➌
Node Address SwitchesTwo switches set the node address.
➍
Network Selector SwitchSwitch selects the network protocol to which the adapter
➎
network connection. Refer to Chapter 8
cable is connected to this connector and a connector on the
drive.
operates.
➎
, Troubleshooting.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
1-2Getting Started
Features
The adapter features include:
• Typical mounting in a PowerFlex 7-Class drive using captive screws to
secure and ground the adapter to the drive.
• Compatibility with various configuration tools to configure the adapter
and connected drive. The tools include the PowerFlex HIM on the drive,
and drive-configuration software such as DriveExplorer (version 2.01 or
higher) or DriveExecutive (version 3.01 or higher).
• Status indicators that report the status of the drive communications, the
adapter, and network. They are visible when the drive cover is open or
closed.
• Parameter-configurable I/O (Logic Command/Reference and up to four
pairs of Datalinks) to meet application requirements.
• User-defined fault actions to determine how the adapter and PowerFlex
drive respond to communication disruptions on the network.
• Switches to allow setting a node address before applying power to the
drive. Alternatively, you can disable the switches and use a parameter to
configure the node address.
• A switch lets you select from the following three network protocols:
• Available read/write access to parameters, allowing parameter values to
be configured and monitored over the network.
• Support for DPI routing, enabling access to any networked PowerFlex
7-Class drive (with 20-COMM-H adapter) using DriveExplorer (version
2.01 or higher) to monitor and configure that drive and its connected
peripherals.
DPI is a second generation peripheral communication interface. The adapter
is compatible with Allen-Bradley PowerFlex 7-Class drives and other
products that support DPI. At the time of publication, compatible products
include:
Network
Protocol
Modbus RTU
Metasys N2
Siemens P1 FLN
The PowerFlex 70/700 are used for examples in this manual. Refer to a DPI
Host product’s user manual for additional information.
70700EC 700VC700H700S7000
Compatible PowerFlex DrivesSMC
Flex
✔✔✔✔✔✔✔
✔✔✔✔✔
✔✔✔✔✔
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Getting Started1-3
Required Equipment
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes:
❑ One adapter
❑ A 2.54 cm (1 in.) and a 15.24 cm (6 in.) Internal Interface cable (only
one cable is needed to connect the adapter to the drive)
User-Supplied Equipment
To install and configure the adapter, you must supply:
❑ A small flathead screwdriver
❑ Network-specific cable to connect the adapter to the network. Refer to
the network-specific documentation for the cable recommendations and
requirements.
❑ Configuration tool, such as:
– PowerFlex 7-Class HIM (20-HIM-*)
– DriveExplorer (version 2.01 or higher)
– DriveExecutive stand-alone software (version 3.01 or higher) or
bundled with the DriveTools SP suite (version 1.01 or higher)
– Third-party network configuration software
❑ A PC connection to the network
Safety Precautions
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
!
Remove all power from the PowerFlex drive, and then verify
power has been discharged before installing or removing an
adapter.
ATTENTION: Risk of injury or equipment damage exists. Only
personnel familiar with drive and power products and the
!
associated machinery should plan or implement the installation,
start up, configuration, and subsequent maintenance of the
product using an adapter. Read and understand this entire manual
before proceeding. Failure to comply may result in injury and/or
equipment damage.
ATTENTION: Risk of equipment damage exists. The adapter
contains ESD (Electrostatic Discharge) sensitive parts that can be
!
damaged if you do not follow ESD control procedures. Static
control precautions are required when handling the adapter. If
you are unfamiliar with static control procedures, refer to
Guarding Against Electrostatic Damage (publication
8000-4.5.2).
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault
!
when you reset the adapter. Determine how your drive will
respond before resetting an adapter.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
1-4Getting Started
ATTENTION: Risk of injury or equipment damage exists.
Parameter 15 - [Comm Flt Action] lets you determine the
!
action of the adapter and connected drive if communications are
disrupted. By default, this parameter faults the drive. You can set
this parameter so that the drive continues to run. Precautions
should be taken to ensure that the setting of this parameter does
not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected
cable).
ATTENTION: Risk of injury or equipment damage exists.
Parameter 11 - [Network Timeout] lets you determine how
!
long it will take the adapter to detect network communication
losses. By default, this parameter sets the timeout to ten seconds.
It can be set so that the duration is shorter, longer, or disabled.
Take precautions to ensure that the setting does not create a risk
of injury or equipment damage. When commissioning the drive,
verify that your system responds correctly to various situations
(for example, a disconnected cable).
ATTENTION: Risk of injury or equipment damage exists. DPI
or SCANport host products must not be directly connected via
!
1202 cables. Unpredictable behavior due to timing and other
internal procedures can result if two or more hosts are connected
in this manner.
ATTENTION: Risk of injury or equipment damage exists.
When a system is configured for the first time, there may be
!
unintended or incorrect machine motion. Disconnect the motor
from the machine or process during initial system testing.
ATTENTION: Risk of injury or equipment damage exists. The
examples in this publication are intended solely for purposes of
!
example. There are many variables and requirements with any
application. Rockwell Automation, Inc. does not assume
responsibility or liability (to include intellectual property
liability) for actual use of the examples shown in this publication.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Getting Started1-5
Quick Start
This section is provided to help experienced users quickly start using the
adapter. If you are unsure how to complete a step, refer to the referenced
chapter.
Step ActionRefer to…
1Review the safety precautions for the adapter.Throughout This Manual
2Verify that the PowerFlex drive is properly installed.Drive User Manual
3Commission the adapter.
Select the network protocol using the adapter Network Selector
switch. Set a unique node address using the adapter Node
Address switches or set both switches to “0” and configure the
node address later using an adapter parameter.
4Install the adapter.
Verify that the PowerFlex drive and network are not powered.
Then, connect the adapter to the network using a network-specific
cable and to the drive using the Internal Interface cable. Use the
captive screws to secure and ground the adapter to the drive.
5Apply power to the adapter.
A. The adapter receives power from the drive. Verify that the
adapter and network are installed correctly and then turn on the
network and apply power to the drive. The status indicators
should be green. If they flash red, there is a problem. Refer to
Chapter 8, Troubleshooting.
B. Configure/verify key drive parameters.
6Configure the adapter for your application.
Set adapter parameters for the following functions as required by
your application:
• Node address, data rate, and parity
• I/O configuration
• Fault actions
7Set up the master device to communicate with the adapter.
Use a network tool to configure the master device on the network.
Chapter 2
Installing the Adapter
Chapter 2,
Installing the Adapter
Chapter 2,
Installing the Adapter
Chapter 3,
Configuring the Adapter
Instruction manual for
your network tool
,
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
1-6Getting Started
Status Indicators
The adapter uses four status indicators to report its operating status. They
can be viewed on the adapter or through the drive cover
(Figure 1.2
Figure 1.2Status Indicators (location on drive may vary)
➊
➋
➌
➍
).
➊
➋
➌
➍
Item Name
PORT
➊
MOD
➋
NET A
➌
NET B
➍
After installing the adapter and applying power to the drive, refer to
Start-Up Status Indications
indications and their descriptions.
on page 2-7 for possible start-up status
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Chapter 2
Installing the Adapter
This chapter provides instructions for installing the adapter in a PowerFlex
7-Class drive.
TopicPage
Preparing for an Installation
Commissioning the Adapter2-1
Connecting the Adapter to the Drive2-3
Connecting the Adapter to the Network2-6
Applying Power2-7
2-1
Preparing for an Installation
Commissioning the Adapter
Before installing the adapter, verify that you have all required equipment.
Refer to Required Equipment
To commission the adapter, you must set a unique node address and select a
network protocol.
Important:New settings are recognized only when power is applied to the
adapter or it is reset. If you change a switch setting, cycle power
or reset the adapter to activate the changes.
ATTENTION: Risk of equipment damage exists. The adapter
contains ESD (Electrostatic Discharge) sensitive parts that can be
!
damaged if you do not follow ESD control procedures. Static
control precautions are required when handling the adapter. If
you are unfamiliar with static control procedures, refer to
Guarding Against Electrostatic Damage (publication
8000-4.5.2).
Important:To guard against device malfunction, it is recommended wear a
grounding wrist strap when installing the adapter.
on page 1-3.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-2Installing the Adapter
1. Set the adapter’s node address by rotating the node address switches to
the desired value for each digit.
Important:Each node on the network must have a unique address.
Figure 2.1Setting the Node Address
SettingDescription
01 – 99Node address used by the adapter.
00 (Default)If network protocols are capable of handling a node address of 0 or node
addresses higher than 99, these addresses can be configured by setting the
switches to 00 and then setting Parameter 03 - [Net Addr Cfg] to the
desired network node address.
The switch settings can be verified using a PowerFlex HIM, DriveExplorer
software, or DriveExecutive software, and viewing Diagnostic Device Item
numbers 40-42 (page 8-5
).
Installing the Adapter2-3
Connecting the Adapter to the
Drive
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
!
Remove power from the drive, and then verify power has been
discharged before installing or removing the adapter.
1. Remove power from the drive and network.
2. Use static control precautions.
3. Remove the drive cover or open the drive door.
4. Connect the Internal Interface cable to the DPI port on the drive and
then to the DPI connector on the adapter (see Figure 2.3
5. Secure and ground the adapter to the drive (see Figure 2.4
following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive
screws.
– On a PowerFlex 700, PowerFlex 700H or PowerFlex 700S drive,
mount the adapter on the drive using the four captive screws.
).
) by doing the
Important:Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 N•m (8.0 lb•in).
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-4Installing the Adapter
Figure 2.3DPI Ports and Internal Interface Cables
20-COMM-H Adapter
➋
➌
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
➊
PowerFlex 70 - All Frames
➍
PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6
Item Description
15.24 cm (6 in.) Internal Interface cable
➊
DPI Connector
➋
Ethernet cable
➌
2.54 cm (1 in.) Internal Interface cable
➍
HIM panel opens to
allow access to DPI
interface. To open
panel, remove screws
on left side of HIM
panel and swing open.
PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger
X2
X1
➍
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Figure 2.4Mounting and Grounding the Adapter
Drive
0.9 N•m
(8.0 lb•in)
4 Places
Adapter
Internal Interface Cable
folded behind the adapter
and in front of the drive.
Installing the Adapter2-5
PowerFlex 70 - All Frame Sizes
(Adapter mounts in drive.)
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
(Adapter mounts on door.)
0.9 N•m
(8.0 lb•in)
4 Places
Ground Tab Detail
Verify metal ground tab is bent 90°
and is under the adapter before
tightening screw. After tightening
the screw, verify continuity exists
between the head of the screw
and drive ground.
PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6
(Adapter mounts in drive.)
Ground Tab Detail
0.9 N•m
(8.0 lb•in)
4 Places
X2
X1
PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger
(Adapter mounts behind HIM panel.)
Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw, verify
continuity exists between the head of
the screw and drive ground.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-6Installing the Adapter
Connecting the Adapter to
the Network
ATTENTION: Risk of injury or death exists. The PowerFlex
drive may contain high voltages that can cause injury or death.
!
Remove power from the drive, and then verify power has been
discharged before installing or removing the adapter.
1. Remove power from the network and drive.
2. Use static control precautions.
3. Connect an RS-485 cable to the network, and route it through the
GND
).
B
COM
TERM
A
SHIELD
bottom of the PowerFlex drive (Figure 2.4
4. Connect a six-pin linear plug to the RS-485 cable. (See Figure 2.5
the terminal definitions.)
Figure 2.5Typical Network Connections
Node 1Node 2Node "n"
TERM
ABCOM
SHIELD
GND
TERMAB
COM
SHIELD
for
GND
TerminalSignalFunction
TERMTermination
ASignal ATxRxDBSignal BTxRxD+
COMCommonSignal Common
SHIELDShieldShield RC Termination
GNDGround
(1)
Jumper terminals TERM and A on the adapter at end of the RS-485 network. This enables a built-in
RC termination network on the adapter.
(2)
The shield must be grounded at a single point on the network (jumper terminals SHIELD and GND).
A 3-wire network using Belden 3106A cable or equivalent is recommended for Modbus RTU applications
and shown in Figure 2.3 above. A 2-wire network using Belden 3105A cable or equivalent (COM
terminal is not connected) can also be used for most applications. However, a 3-wire network is more
robust in noisy environments.
For Metasys N2 or Siemens P1 FLN applications, refer to published guidelines from Johnson Controls or
Siemens Building Technologies respectively.
(1)
(2)
Signal RC Termination
Shield GND Termination
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Installing the Adapter2-7
Applying Power
ATTENTION: Risk of equipment damage, injury, or death
exists. Unpredictable operation may occur if you fail to verify
!
that parameter settings are compatible with your application.
Verify that settings are compatible with your application before
applying power to the drive.
Install the drive cover or close the drive door, and apply power to the drive.
The adapter receives its power from the connected drive. When you apply
power to the adapter for the first time, its topmost “PORT” status indicator
should be steady green after an initialization. If it is red, there is a problem.
Refer to Chapter 8
Start-Up Status Indications
Status indicators for the drive and communications adapter can be viewed
on the front of the drive (Figure 2.6
start-up status indications are shown in Table 2.A
Figure 2.6Drive and Adapter Status Indicators (location on drive may vary)
➋
, Troubleshooting.
) after power has been applied. Possible
.
PORT
MOD
NET A
NET B
STS
Table 2.A Drive and Adapter Start-Up Status Indications
Item NameColorStateDescription
Drive STS Indicator
➊
STS
(Status)
GreenFlashingDrive ready but not running, and no faults are present.
An inhibit condition exists – the drive cannot be started.
Check drive Parameter 214 - [Start Inhibits].
An intermittent type 1 alarm condition is occurring.
Check drive Parameter 211 - [Drive Alarm 1].
A continuous type 1 alarm condition exists. Check drive
Parameter 211 - [Drive Alarm 1].
➊
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-8Installing the Adapter
Item NameColorStateDescription
Adapter Status Indicators
PORTGreenFlashingNormal Operation. The adapter is establishing an I/O
➋
SteadyNormal Operation. The adapter is properly connected
MODGreenFlashingNormal Operation. The adapter is operating but is not
SteadyNormal Operation. The adapter is operating and
NET AGreenFlashingNormal Operation. The adapter is properly connected
SteadyNormal Operation. The adapter is properly connected
NET BGreenOffNormal Operation. The adapter is properly connected
FlashingNormal Operation. The adapter is properly connected
Configuring/Verifying Key Drive Parameters
The PowerFlex 7-Class drive can be separately configured for the control
and Reference functions in various combinations. For example, you could
set the drive to have its control come from a peripheral or terminal block
with the Reference coming from the network. Or you could set the drive to
have its control come from the network with the Reference coming from
another peripheral or terminal block. Or you could set the drive to have
both its control and Reference come from the network.
connection to the drive. It will turn solid green or red.
and communicating with the drive
transferring I/O data.
transferring I/O data.
but does not have an I/O connection.
and communicating on the network.
but is idle.
and transmitting data packets on the network.
The following steps in this section assume that the drive will receive the
Logic Command and Reference from the network.
1. Use drive Parameter 090 - [Speed Ref A Sel] to set the drive speed
Reference to “22” (DPI Port 5).
2. If digital inputs are not used, change drive Parameters 361 - [Dig In1
Sel] through 366 - [Dig In6 Sel] to “0” (Not Used).
3. Verify that drive Parameter 213 - [Speed Ref Source] is reporting that
the source of the Reference to the drive is “22” (DPI Port 5). This
ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded Speed]. If a
problem occurs, this verification step provides the diagnostic capability
to determine whether the drive/adapter or the network is the cause.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Chapter 3
Configuring the Adapter
This chapter provides instructions and information for setting the
parameters in the adapter.
TopicPage
Configuration Tools
Using the PowerFlex 7-Class HIM3-2
Setting the Node Address3-3
Setting the Network Data Rate3-3
Setting the Network Parity3-4
Setting Stop Bits (Modbus RTU only)3-4
Setting the I/O Configuration3-5
Setting a Network Time-out3-6
Setting a Fault Action3-7
Resetting the Adapter3-8
Viewing the Adapter Status Using Parameters3-9
Flash Updating the Adapter3-10
3-1
Configuration Tools
For a list of parameters, refer to Appendix B, Adapter Parameters. For
definitions of terms in this chapter, refer to the Glossary
The adapter stores parameters and other information in its own non-volatile
memory. You must, therefore, access the adapter to view and edit its
parameters. The following tools can be used to access the adapter
parameters:
ToolRefer to…
PowerFlex HIMpage 3-2
DriveExplorer Software
(version 2.01 or higher)
DriveExecutive Software
(version 3.01 or higher)
http://www.ab.com/drives/driveexplorer, or
DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools, or
DriveExecutive online help (installed with the software)
.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-2Configuring the Adapter
Using the PowerFlex 7-Class
HIM
If your drive has either an LED or LCD HIM (Human Interface Module), it
can be used to access parameters in the adapter as shown below. It is
recommended that you read through the steps for your HIM before
performing the sequence. For additional information, refer to your
PowerFlex Drive User Manual or the HIM Quick Reference card.
Using an LED HIM
StepKey(s)Example Screens
1. Press ALT and then Sel (Device) to display
the Device Screen.
2. Press the Up Arrow or Down Arrow to scroll
to the adapter. Letters represent files in the
drive, and numbers represent ports. The
adapter is usually connected to port 5.
3. Press the Enter key to enter your selection.
A parameter database is constructed, and
then the first parameter is displayed.
4. Edit the parameters using the same
techniques that you use to edit drive
parameters.
ALT
Device
Sel
or
Using an LCD HIM
StepKey(s)Example Screens
1. In the main menu, press the Up Arrow or
Down Arrow to scroll to Device Select.
2. Press Enter to enter your selection.
3. Press the Up Arrow or Down Arrow to scroll
to the adapter (20-COMM-H).
4. Press Enter to select the adapter. A
parameter database is constructed, and
then the main menu for the adapter is
displayed.
5. Edit the parameters using the same
techniques that you use to edit drive
parameters.
or
or
NOTE: LCD HIM screens are shown throughout this chapter for example
configuration procedures.
F-> StoppedAuto
0.00Hz
Main Menu:
Diagnostics
Parameter
Device Select
Port 5 Device
20-COMM-H
Main Menu:
Diagnostics
Parameter
Device Select
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter3-3
Setting the Node Address
Setting the Network Data Rate
If the Node Address switches on the adapter are set to “00,” the value of
Parameter 03 - [Net Addr Cfg] determines the node address.
1. Set the value of Parameter 03 - [Net Addr Cfg] to a unique node
address.
Figure 3.1Example Net Addr Cfg 1 Screen
Port 5 Device
20-COMM-H
Parameter #: 03
Net Addr Cfg
1
0 <> 247
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual
node address is then displayed by Parameter 04 - [Net Addr Act].
The data rate at which the adapter operates varies based on the type of
network and your network configuration. Refer to the following table.
1. Set the value of Parameter 05 - [Net Rate Cfg] to the data rate at
which your network is operating.
Figure 3.2Example Net Rate Cfg Screen
Port 5 Device
20-COMM-H
Parameter #: 05
Net Rate Cfg
1
9600
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual
data rate is then displayed by Parameter 06 - [Net Rate Act].
ValueBaud
04800
19600 (default)
219200
338400
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-4Configuring the Adapter
Setting the Network Parity
The parity that the adapter uses to verify data integrity varies based on the
type of network and your network configuration. Refer to the following
table.
NetworkPossible Types of Parity
Modbus RTUNone, Even, or Odd
Metasys N2None
Siemens Building Technologies P1 FLNNone
1. Set the value of Parameter 07 - [Net Parity Cfg] to the type of parity
that is used on the network.
Figure 3.3Example Network Parity Screen
Port 5 Device
20-COMM-H
Parameter #: 07
Net Parity Cfg
0
None
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual
network parity is then displayed by Parameter 08 - [Net Parity Act].
ValueType of Parity
0None (default)
1Odd
2Even
Setting Stop Bits (Modbus
RTU only)
Parameter 30 - [Stop Bits Cfg] enables you to set 1 or 2 stop bits for the
Modbus RTU network protocol. When the adapter rotary switch is set to
“N2” or “P1,” the Stop Bits Cfg value is ignored and does not transfer to
read-only Parameter 09 - [Stop Bits Act] on power-up or reset (N2 and P1 are
fixed at 1 stop bit).
1. Set the value of Parameter 30 - [Stop Bits Cfg].
Figure 3.4Example Stop Bits Screen
Port 5 Device
20-COMM-H
Parameter #: 30
Stop Bits Cfg
1-bit
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual
stop bits is then displayed by Parameter 09 - [Stop Bits Act].
0
ValueType of Stop Bit
01-bit (default)
12-bits
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter3-5
Setting the I/O
Configuration
The I/O configuration determines the data that is sent to and from the drive.
Logic Command/Status, Reference/Feedback, and Datalinks may be
enabled or disabled. A “1” enables the I/O. A “0” disables the I/O.
1. Set the bits in Parameter 16 - [DPI I/O Cfg].
Figure 3.5Example DPI I/O Cfg Screen
Port 5 Device
20-COMM-H
Parameter #: 16
DPI I/O Cfg
xxxxxxxxxxx0000
Cmd/Refb00
Bit 0 is the right-most bit. In Figure 3.5, it is highlighted and equals “1.”
2. If Logic Command/Reference is enabled, configure the parameters in
the drive to accept the Logic Command and Reference from the adapter.
For example, set Parameter 90 - [Speed Ref A Sel] in a PowerFlex 70 or
700 drive to “22” (DPI Port 5) so that the drive uses the Reference from
the adapter. Also, verify that the mask parameters (for example,
Parameter 276 - [Logic Mask]) in the drive are configured to receive the
desired logic from the adapter. Refer to the documentation for your
drive for details.
BitDescription
0Logic Command/Reference (Default)
1Datalink A
2Datalink B
3Datalink C (not used with Metasys N2
1
4Datalink D (not used with Metasys N2
5 - 15 Not Used
3. If you enabled one or more Datalinks, configure parameters in the drive
to determine the source and destination of data in the Datalink(s). For
example, configure the Datalinks in PowerFlex 70 and 700 drives by
setting Parameters 300 - [Data In A1] to 317 - [Data Out D2]. Also,
ensure that this adapter is the only adapter using the enabled
Datalink(s).
4. Reset the adapter (see Resetting the Adapter
The adapter is ready to send and receive I/O. The following chapters
provide information about basic data transfer for each type of protocol.
NetworkRefer to…
Modbus RTUChapter 4
Metasys N2Chapter 5, Using Metasys N2
Siemens Building Technologies P1 FLNChapter 6, Using Siemens Building Technologies P1 FLN
For details about using Datalinks for all types of networks, refer to
Chapter 7
, Using Datalinks with All Protocols.
, Using Modbus RTU
on page 3-8).
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-6Configuring the Adapter
Setting a Network Time-out
The network timeout sets an interval within which the adapter must
communicate with its master. If this time is exceeded, the adapter
determines a loss of network communications has occurred and responds
with the action specified in Parameter 15 - [Comm Flt Action].
By default, the timeout is set to ten (10) seconds. You can increase or
decrease this value. Alternatively, you can set the value to zero (0) so that
the adapter does not detect communication losses.
ATTENTION: Risk of injury or equipment damage exists.
Parameter 11 - [Network Timeout] lets you determine how
!
long it will take your adapter to detect network communication
losses. By default, this parameter sets the timeout to ten (10)
seconds. You can set it so that the duration is shorter, longer, or
disabled. Take precautions to ensure that the setting does not
create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected
cable).
Set the network timeout in Parameter 11 - [Network Timeout].
Figure 3.6Example Network Timeout Screen
Port 5 Device
20-COMM-H
Parameter #: 11
Network Timeout
10Sec
0 <> 180
Changes to this parameter take effect immediately. A reset is not required.
Default = 10 seconds
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter3-7
Setting a Fault Action
By default, when I/O communications are disrupted (for example, a cable is
disconnected), the drive responds by faulting if it is using I/O from the
network. You can configure a different response to disrupted I/O
communication using Parameter 15 - [Comm Flt Action].
ATTENTION: Risk of injury or equipment damage exists.
Parameter 15 - [Comm Flt Action] lets you determine the action
!
of the adapter and connected drive if I/O communications are
disrupted. By default, this parameter faults the drive. You can set
this parameter so that the drive continues to run. Precautions
should be taken to ensure that the setting of this parameter does
not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable).
Changing the Fault Action
Set the value of Parameter 15 - [Comm Flt Action] to the desired
response:
ValueActionDescription
0FaultThe drive is faulted and stopped. (Default)
1StopThe drive is stopped, but not faulted.
2Zero DataThe drive is sent 0 for output data. (The command word and Reference are
set to zero.) This does not command a stop.
3Hold LastThe drive continues in its present state.
4Send Flt CfgThe drive is sent the data that you set in the fault configuration parameters
Changes to this parameter takes effect immediately. A reset is not required.
Setting the Fault Configuration Parameters
If you set Parameter 15 - [Comm Flt Action] to “Send Flt Cfg,” the values
in the following parameters are sent to the drive after an I/O
communications fault occurs. You must set these parameters to values
required by your application.
Parameter NameDescription
25Flt Cfg Logic A 16-bit value sent to the drive for Logic Command.
26Flt Cfg RefA 32-bit value (0 – 4294967295) sent to the drive as a Reference or
27 – 34Flt Cfg x1 In
or
Flt Cfg x2 In
Datalink.
Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most
significant word of the value must be set to zero (0) or a fault will occur.
Changes to these parameters take effect immediately. A reset is not required.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-8Configuring the Adapter
Resetting the Adapter
Changes to switch settings and some adapter parameters require that you
reset the adapter before the new settings take effect. You can reset the
adapter by cycling power to the drive or by using Parameter 14 - [Reset
Module].
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault
!
when you reset the adapter. Determine how your drive will
respond before resetting a connected adapter.
Set Parameter 14 - [Reset Module] to “1” (Reset Module).
Figure 3.8Example Reset Module Screen
Port 5 Device
20-COMM-H
Parameter #: 14
Reset Module
1
Reset Module
When you enter “1” (Reset Module), the adapter will be immediately reset.
When you enter “2” (Set Defaults), the adapter will set all adapter
parameters to their factory-default values. After performing a Set Defaults,
enter “1” (Reset Module) so that the new values take effect. The value of
this parameter will be restored to “0” (Ready) after the adapter is reset.
Value Description
0Ready (Default)
1Reset Module
2Set Defaults
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.