Rockwell Automation 20-COMM-H User Manual

20-COMM-H RS-485 HVAC Adapter
Firmware Version 2.xxx
Modbus RTU Metasys N2 Siemens Building Technologies P1 FLN
User Manual
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
http://
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
!
environment, which may lead to personal injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures.
20-COMM-H RS-485 HVAC Adapter User Manual
PowerFlex, SMC Flex, DriveExplorer, DriveExecutive, DPI, DriveTools SP, and SCANport are either trademarks or registered trademarks
of Rockwell Automation, Inc. Metasys is a trademark of Johnson Controls, Inc. Modbus is a trademark of Schneider Automation. P1 FLN is a trademark of Siemens Building Technologies. Windows and Microsoft are registered trademarks of Microsoft Corporation.

Summary of Changes

The information below summarizes the changes made to this manual since its last release (March 2004):
Description of Changes Page
Reformatted document from half size (5.5 x 8.5 in.) to full size (8.5 x 11 in.) Throughout
Added SMC Flex to the list of compatible products, and Metasys N2 is compatible with PowerFlex 700VC drive.
Added new Adapter Modbus Register Map section. 4-2 Included information about using Modbus RTU mode to access 16-bit and 32-bit
parameters. Added new Adapter Parameter Direct Access section. 4-13 Added new Metasys N2 Device Identity subsection. 5-1 Added new “Reference Setup Examples” subsection. 5-4 Added tip about configuring Analog Data Integers (ADIs). 5-9 Added Flashing Red/Green MOD status indicator information. 8-3 Added new Parameter 32 - [RTU Param Mode] to select the 16-bit default mode or
optional 32-bit mode in which the adapter operates.
manual
1-2
4-10 and 4-12
B-4
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
soc-ii Summary of Changes
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Preface About This Manual
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Chapter 1 Getting Started
Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Chapter 2 Installing the Adapter
Preparing for an Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Commissioning the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Connecting the Adapter to the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Connecting the Adapter to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Applying Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7

Table of Contents

Chapter 3 Configuring the Adapter
Chapter 4 Using Modbus RTU
Configuration Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Using the PowerFlex 7-Class HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Setting the Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Setting the Network Data Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Setting the Network Parity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Setting Stop Bits (Modbus RTU only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Setting the I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Setting a Network Time-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Setting a Fault Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Resetting the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Viewing the Adapter Status Using Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Flash Updating the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Understanding Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Adapter Modbus Register Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Using the Modbus RTU Point Map for I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Accessing Drive Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Using Broadcast Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Adapter Parameter Direct Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Chapter 5 Using Metasys N2
Understanding Metasys N2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Using the Metasys N2 Point Map for I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Using Metasys Configurable Objects to Access Parameters. . . . . . . . . . . . . . . . . . . . . . . 5-8
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
ii Table of Contents
Chapter 6 Using Siemens Building Technologies P1 FLN
Understanding Siemens Building Technologies P1 FLN . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Using the P1 FLN Point Map for I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Using the P1 FLN Point Map to Access Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Chapter 7 Using Datalinks with All Protocols
Using Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Using Datalinks with Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Using Datalinks with Metasys N2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Using Datalinks with Siemens P1 FLN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Chapter 8 Troubleshooting
Understanding the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
PORT Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
MOD Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
NET A Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
NET B Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Viewing Adapter Diagnostic Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Viewing and Clearing Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Appendix A Specifications
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Mechanical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Appendix B Adapter Parameters
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Appendix C Logic Command/Status Words
PowerFlex 7-Class Drives (except PowerFlex 700S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
PowerFlex 700S Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
Glossary
Index
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Related Documentation

Preface

About This Manual

Topic Page
Related Documentation Rockwell Automation Support P-2 Conventions Used in This Manual P-2
For: Refer to: Publication
DriveExplorer™ http://www.ab.com/drives/driveexplorer, and
DriveTools™ SP (includes DriveExecutive™)
HIM HIM Quick Reference 20HIM-QR001 PowerFlex
PowerFlex PowerFlex® 700 Series B Drive
PowerFlex
PowerFlex (Frames 1 through 6)
PowerFlex (Frames 9 and higher)
PowerFlex Modbus RTU Protocol Specification www.modicon.com/techpubs/TechPubNew PI_MBUS_300.pdf
®
70/70EC Drive PowerFlex 70 User Manual
®
700/700VC Drive
®
700H Drive PowerFlex 700H Installation Instructions
®
700S Drive
®
700S Drive
®
700L Drive PowerFlex 700L User Manual 20L-UM001
DriveExplorer online help (installed with the software) http://www.ab.com/drives/drivetools, and
DriveExecutive online help (installed with the software)
PowerFlex 70/700 Reference Manual PowerFlex 70EC/700VC Reference Manual
PowerFlex 700 User Manual PowerFlex 700 Series B User Manual PowerFlex 70/700 Reference Manual PowerFlex 70EC/700VC Reference Manual
PowerFlex 700H Programming Manual PowerFlex 700S with Phase I Control User Manual
PowerFlex 700S with Phase II Control User Manual PowerFlex 700S Reference Manual
PowerFlex 700S Installation Instructions PowerFlex 700S with Phase I Control User Manual PowerFlex 700S with Phase II Control User Manual PowerFlex 700S Reference Manual
P-1
20A-UM001 PFLEX-RM001 PFLEX-RM004
20B-UM001 20B-UM002 PFLEX-RM001 PFLEX-RM004
PFLEX-IN006 20C-PM001
20D-UM001 20D-UM006 PFLEX-RM002
PFLEX-IN006 20D-UM001 20D-UM006 PFLEX-RM002
You can view or download publications at
www.literature.rockwellautomation.com
documentation, contact your local Rockwell Automation distributor or sales representative.
To find your local Rockwell Automation distributor or sales representative, visit www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related questions, go to the Drives Service & Support web site at www.ab.com/
support/abdrives and click on the “Downloads” or “Knowledgebase” link.
. To order paper copies of technical
.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
P-2 About This Manual

Rockwell Automation Support

Rockwell Automation, Inc. offers support services worldwide, with over 75 sales/support offices, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation, Inc. representatives are in every major country in the world.
Local Product Support
Contact your local Rockwell Automation, Inc. representative for:
Sales and order support
Product technical training
Warranty support
Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 8,
Troubleshooting
Allen-Bradley Technical Support web site at www.ab.com/support/abdrives or contact Rockwell Automation, Inc.
, first. If you still have problems, then access the

Conventions Used in This Manual

The following conventions are used throughout this manual:
Parameter names are shown in the format Parameter xx - [*]. The xx
represents the parameter number. The * represents the parameter name— for example Parameter 01 - [DPI Port].
Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read “Select File > Open,” you should click the File menu and then click the Open command.
The firmware release is displayed as FRN X.xxx. The “FRN” signifies
Firmware Release Number. The “X” is the major release number. The “xxx” is the minor update number.
This manual provides information about the adapter and using it with
PowerFlex 7-Class (Architecture-Class) drives. The adapter can be used with other products that support a DPI™ adapter, such as SMC™ Flex. Refer to the documentation for your product for specific information about how it works with the adapter.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 1

Getting Started

The adapter is a communication option intended for installation into a PowerFlex 7-Class drive. It can also be used with other Allen-Bradley products that support a DPI™ (Drive Peripheral Interface) adapter.
Topic Page
Components Features 1-2 Compatible Products 1-2 Required Equipment 1-3 Safety Precautions 1-3 Quick Start 1-5 Status Indicators 1-6
1-1

Components

Figure 1.1 Components of the Adapter
Item Part Description
Status Indicators Four LEDs that indicate the status of the DPI, the adapter, and
DPI Connector A 20-pin, single-row shrouded male header. An Internal Interface
Terminal Block A 6-screw terminal block connects the adapter to the network.
Node Address Switches Two switches set the node address.
Network Selector Switch Switch selects the network protocol to which the adapter
network connection. Refer to Chapter 8
cable is connected to this connector and a connector on the drive.
operates.
, Troubleshooting.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
1-2 Getting Started

Features

The adapter features include:
Typical mounting in a PowerFlex 7-Class drive using captive screws to
secure and ground the adapter to the drive.
Compatibility with various configuration tools to configure the adapter
and connected drive. The tools include the PowerFlex HIM on the drive, and drive-configuration software such as DriveExplorer (version 2.01 or higher) or DriveExecutive (version 3.01 or higher).
Status indicators that report the status of the drive communications, the
adapter, and network. They are visible when the drive cover is open or closed.
Parameter-configurable I/O (Logic Command/Reference and up to four
pairs of Datalinks) to meet application requirements.
User-defined fault actions to determine how the adapter and PowerFlex
drive respond to communication disruptions on the network.
Switches to allow setting a node address before applying power to the
drive. Alternatively, you can disable the switches and use a parameter to configure the node address.
A switch lets you select from the following three network protocols:
Modbus™ RTUMetasys™ N2Siemens Building Technologies P1 FLN™

Compatible Products

Available read/write access to parameters, allowing parameter values to
be configured and monitored over the network.
Support for DPI routing, enabling access to any networked PowerFlex
7-Class drive (with 20-COMM-H adapter) using DriveExplorer (version
2.01 or higher) to monitor and configure that drive and its connected peripherals.
DPI is a second generation peripheral communication interface. The adapter is compatible with Allen-Bradley PowerFlex 7-Class drives and other products that support DPI. At the time of publication, compatible products include:
Network Protocol
Modbus RTU Metasys N2 Siemens P1 FLN
The PowerFlex 70/700 are used for examples in this manual. Refer to a DPI Host product’s user manual for additional information.
70 700EC 700VC 700H 700S 7000
Compatible PowerFlex Drives SMC
Flex
✔✔✔✔✔✔✔ ✔✔✔✔ ✔ ✔✔✔✔
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Getting Started 1-3

Required Equipment

Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes:
One adapterA 2.54 cm (1 in.) and a 15.24 cm (6 in.) Internal Interface cable (only
one cable is needed to connect the adapter to the drive)
User-Supplied Equipment
To install and configure the adapter, you must supply:
A small flathead screwdriverNetwork-specific cable to connect the adapter to the network. Refer to
the network-specific documentation for the cable recommendations and requirements.
Configuration tool, such as:
– PowerFlex 7-Class HIM (20-HIM-*) – DriveExplorer (version 2.01 or higher) – DriveExecutive stand-alone software (version 3.01 or higher) or
bundled with the DriveTools SP suite (version 1.01 or higher)
– Third-party network configuration software
A PC connection to the network

Safety Precautions

Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death.
!
Remove all power from the PowerFlex drive, and then verify power has been discharged before installing or removing an adapter.
ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the
!
associated machinery should plan or implement the installation, start up, configuration, and subsequent maintenance of the product using an adapter. Read and understand this entire manual before proceeding. Failure to comply may result in injury and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The adapter contains ESD (Electrostatic Discharge) sensitive parts that can be
!
damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage (publication 8000-4.5.2).
ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive may fault
!
when you reset the adapter. Determine how your drive will respond before resetting an adapter.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
1-4 Getting Started
ATTENTION: Risk of injury or equipment damage exists. Parameter 15 - [Comm Flt Action] lets you determine the
!
action of the adapter and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
ATTENTION: Risk of injury or equipment damage exists. Parameter 11 - [Network Timeout] lets you determine how
!
long it will take the adapter to detect network communication losses. By default, this parameter sets the timeout to ten seconds. It can be set so that the duration is shorter, longer, or disabled. Take precautions to ensure that the setting does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected via
!
1202 cables. Unpredictable behavior due to timing and other internal procedures can result if two or more hosts are connected in this manner.
ATTENTION: Risk of injury or equipment damage exists. When a system is configured for the first time, there may be
!
unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of
!
example. There are many variables and requirements with any application. Rockwell Automation, Inc. does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Getting Started 1-5

Quick Start

This section is provided to help experienced users quickly start using the adapter. If you are unsure how to complete a step, refer to the referenced chapter.
Step Action Refer to…
1 Review the safety precautions for the adapter. Throughout This Manual 2 Verify that the PowerFlex drive is properly installed. Drive User Manual 3 Commission the adapter.
Select the network protocol using the adapter Network Selector switch. Set a unique node address using the adapter Node Address switches or set both switches to “0” and configure the node address later using an adapter parameter.
4 Install the adapter.
Verify that the PowerFlex drive and network are not powered. Then, connect the adapter to the network using a network-specific cable and to the drive using the Internal Interface cable. Use the captive screws to secure and ground the adapter to the drive.
5 Apply power to the adapter.
A. The adapter receives power from the drive. Verify that the
adapter and network are installed correctly and then turn on the network and apply power to the drive. The status indicators should be green. If they flash red, there is a problem. Refer to
Chapter 8, Troubleshooting.
B. Configure/verify key drive parameters.
6 Configure the adapter for your application.
Set adapter parameters for the following functions as required by your application:
Node address, data rate, and parity
I/O configuration
Fault actions
7 Set up the master device to communicate with the adapter.
Use a network tool to configure the master device on the network.
Chapter 2 Installing the Adapter
Chapter 2, Installing the Adapter
Chapter 2, Installing the Adapter
Chapter 3, Configuring the Adapter
Instruction manual for your network tool
,
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
1-6 Getting Started

Status Indicators

The adapter uses four status indicators to report its operating status. They can be viewed on the adapter or through the drive cover (Figure 1.2
Figure 1.2 Status Indicators (location on drive may vary)
➊ ➋ ➌ ➍
).
➊ ➋
Item Name
PORT
MOD
NET A
NET B
After installing the adapter and applying power to the drive, refer to
Start-Up Status Indications
indications and their descriptions.
on page 2-7 for possible start-up status
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 2

Installing the Adapter

This chapter provides instructions for installing the adapter in a PowerFlex 7-Class drive.
Topic Page
Preparing for an Installation Commissioning the Adapter 2-1 Connecting the Adapter to the Drive 2-3 Connecting the Adapter to the Network 2-6 Applying Power 2-7
2-1

Preparing for an Installation

Commissioning the Adapter

Before installing the adapter, verify that you have all required equipment. Refer to Required Equipment
To commission the adapter, you must set a unique node address and select a network protocol.
Important:New settings are recognized only when power is applied to the
adapter or it is reset. If you change a switch setting, cycle power or reset the adapter to activate the changes.
ATTENTION: Risk of equipment damage exists. The adapter contains ESD (Electrostatic Discharge) sensitive parts that can be
!
damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage (publication 8000-4.5.2).
Important:To guard against device malfunction, it is recommended wear a
grounding wrist strap when installing the adapter.
on page 1-3.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-2 Installing the Adapter
1. Set the adapter’s node address by rotating the node address switches to
the desired value for each digit.
Important:Each node on the network must have a unique address.
Figure 2.1 Setting the Node Address
Setting Description
01 – 99 Node address used by the adapter. 00 (Default) If network protocols are capable of handling a node address of 0 or node
addresses higher than 99, these addresses can be configured by setting the switches to 00 and then setting Parameter 03 - [Net Addr Cfg] to the desired network node address.
2. Set the network protocol switch.
Figure 2.2 Setting the Network Protocol
2
3
1
0
9
4
6
7
8
2
3
1
0
5
9
4
5
6
7
8
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
RTU
N2
P1
Setting Description
RTU (Default) Modbus RTU N2 Metasys N2 P1 Siemens Building Technologies P1 FLN
The switch settings can be verified using a PowerFlex HIM, DriveExplorer software, or DriveExecutive software, and viewing Diagnostic Device Item numbers 40-42 (page 8-5
).
Installing the Adapter 2-3

Connecting the Adapter to the Drive

ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death.
!
Remove power from the drive, and then verify power has been discharged before installing or removing the adapter.
1. Remove power from the drive and network.
2. Use static control precautions.
3. Remove the drive cover or open the drive door.
4. Connect the Internal Interface cable to the DPI port on the drive and
then to the DPI connector on the adapter (see Figure 2.3
5. Secure and ground the adapter to the drive (see Figure 2.4
following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive screws.
– On a PowerFlex 700, PowerFlex 700H or PowerFlex 700S drive,
mount the adapter on the drive using the four captive screws.
).
) by doing the
Important:Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 Nm (8.0 lb•in).
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-4 Installing the Adapter
Figure 2.3 DPI Ports and Internal Interface Cables
20-COMM-H Adapter
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
PowerFlex 70 - All Frames
PowerFlex 700 Frames 2 and Larger PowerFlex 700S Frames 2 through 6
Item Description
15.24 cm (6 in.) Internal Interface cable
DPI Connector
Ethernet cable
2.54 cm (1 in.) Internal Interface cable
HIM panel opens to allow access to DPI interface. To open panel, remove screws on left side of HIM panel and swing open.
PowerFlex 700H Frames 9 and Larger PowerFlex 700S Frames 9 and Larger
X2
X1
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Figure 2.4 Mounting and Grounding the Adapter
Drive
0.9 N•m
(8.0 lb•in)
4 Places
Adapter
Internal Interface Cable folded behind the adapter and in front of the drive.
Installing the Adapter 2-5
PowerFlex 70 - All Frame Sizes
(Adapter mounts in drive.)
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
(Adapter mounts on door.)
0.9 N•m
(8.0 lb•in)
4 Places
Ground Tab Detail
Verify metal ground tab is bent 90° and is under the adapter before tightening screw. After tightening the screw, verify continuity exists between the head of the screw and drive ground.
PowerFlex 700 Frames 2 and Larger PowerFlex 700S Frames 2 through 6
(Adapter mounts in drive.)
Ground Tab Detail
0.9 N•m
(8.0 lb•in)
4 Places
X2
X1
PowerFlex 700H Frames 9 and Larger PowerFlex 700S Frames 9 and Larger
(Adapter mounts behind HIM panel.)
Verify metal ground tab is bent 90° and is under the adapter before tightening screw. After tightening the screw, verify continuity exists between the head of the screw and drive ground.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-6 Installing the Adapter

Connecting the Adapter to the Network

ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death.
!
Remove power from the drive, and then verify power has been discharged before installing or removing the adapter.
1. Remove power from the network and drive.
2. Use static control precautions.
3. Connect an RS-485 cable to the network, and route it through the
GND
).
B
COM
TERM
A
SHIELD
bottom of the PowerFlex drive (Figure 2.4
4. Connect a six-pin linear plug to the RS-485 cable. (See Figure 2.5
the terminal definitions.)
Figure 2.5 Typical Network Connections
Node 1 Node 2 Node "n"
TERM
ABCOM
SHIELD
GND
TERMAB
COM
SHIELD
for
GND
Terminal Signal Function
TERM Termination A Signal A TxRxD­B Signal B TxRxD+ COM Common Signal Common SHIELD Shield Shield RC Termination GND Ground
(1)
Jumper terminals TERM and A on the adapter at end of the RS-485 network. This enables a built-in RC termination network on the adapter.
(2)
The shield must be grounded at a single point on the network (jumper terminals SHIELD and GND).
A 3-wire network using Belden 3106A cable or equivalent is recommended for Modbus RTU applications and shown in Figure 2.3 above. A 2-wire network using Belden 3105A cable or equivalent (COM terminal is not connected) can also be used for most applications. However, a 3-wire network is more robust in noisy environments.
For Metasys N2 or Siemens P1 FLN applications, refer to published guidelines from Johnson Controls or Siemens Building Technologies respectively.
(1)
(2)
Signal RC Termination
Shield GND Termination
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Installing the Adapter 2-7

Applying Power

ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify
!
that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
Install the drive cover or close the drive door, and apply power to the drive. The adapter receives its power from the connected drive. When you apply power to the adapter for the first time, its topmost “PORT” status indicator should be steady green after an initialization. If it is red, there is a problem. Refer to Chapter 8
Start-Up Status Indications
Status indicators for the drive and communications adapter can be viewed on the front of the drive (Figure 2.6 start-up status indications are shown in Table 2.A
Figure 2.6 Drive and Adapter Status Indicators (location on drive may vary)
, Troubleshooting.
) after power has been applied. Possible
.
PORT
MOD
NET A
NET B
STS
Table 2.A Drive and Adapter Start-Up Status Indications
Item Name Color State Description
Drive STS Indicator
STS (Status)
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing,
Drive Stopped Flashing, Drive Running Steady, Drive Running
Red Flashing A fault has occurred.
Steady A non-resettable fault has occurred.
An inhibit condition exists – the drive cannot be started. Check drive Parameter 214 - [Start Inhibits]. An intermittent type 1 alarm condition is occurring. Check drive Parameter 211 - [Drive Alarm 1]. A continuous type 1 alarm condition exists. Check drive Parameter 211 - [Drive Alarm 1].
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
2-8 Installing the Adapter
Item Name Color State Description
Adapter Status Indicators
PORT Green Flashing Normal Operation. The adapter is establishing an I/O
Steady Normal Operation. The adapter is properly connected
MOD Green Flashing Normal Operation. The adapter is operating but is not
Steady Normal Operation. The adapter is operating and
NET A Green Flashing Normal Operation. The adapter is properly connected
Steady Normal Operation. The adapter is properly connected
NET B Green Off Normal Operation. The adapter is properly connected
Flashing Normal Operation. The adapter is properly connected
Configuring/Verifying Key Drive Parameters
The PowerFlex 7-Class drive can be separately configured for the control and Reference functions in various combinations. For example, you could set the drive to have its control come from a peripheral or terminal block with the Reference coming from the network. Or you could set the drive to have its control come from the network with the Reference coming from another peripheral or terminal block. Or you could set the drive to have both its control and Reference come from the network.
connection to the drive. It will turn solid green or red.
and communicating with the drive
transferring I/O data.
transferring I/O data.
but does not have an I/O connection.
and communicating on the network.
but is idle.
and transmitting data packets on the network.
The following steps in this section assume that the drive will receive the Logic Command and Reference from the network.
1. Use drive Parameter 090 - [Speed Ref A Sel] to set the drive speed
Reference to “22” (DPI Port 5).
2. If digital inputs are not used, change drive Parameters 361 - [Dig In1
Sel] through 366 - [Dig In6 Sel] to “0” (Not Used).
3. Verify that drive Parameter 213 - [Speed Ref Source] is reporting that
the source of the Reference to the drive is “22” (DPI Port 5). This ensures that any Reference commanded from the network can be monitored by using drive Parameter 002 - [Commanded Speed]. If a problem occurs, this verification step provides the diagnostic capability to determine whether the drive/adapter or the network is the cause.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 3

Configuring the Adapter

This chapter provides instructions and information for setting the parameters in the adapter.
Topic Page
Configuration Tools Using the PowerFlex 7-Class HIM 3-2 Setting the Node Address 3-3 Setting the Network Data Rate 3-3 Setting the Network Parity 3-4 Setting Stop Bits (Modbus RTU only) 3-4 Setting the I/O Configuration 3-5 Setting a Network Time-out 3-6 Setting a Fault Action 3-7 Resetting the Adapter 3-8 Viewing the Adapter Status Using Parameters 3-9 Flash Updating the Adapter 3-10
3-1

Configuration Tools

For a list of parameters, refer to Appendix B, Adapter Parameters. For definitions of terms in this chapter, refer to the Glossary
The adapter stores parameters and other information in its own non-volatile memory. You must, therefore, access the adapter to view and edit its parameters. The following tools can be used to access the adapter parameters:
Tool Refer to…
PowerFlex HIM page 3-2 DriveExplorer Software
(version 2.01 or higher) DriveExecutive Software
(version 3.01 or higher)
http://www.ab.com/drives/driveexplorer, or DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools, or DriveExecutive online help (installed with the software)
.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-2 Configuring the Adapter

Using the PowerFlex 7-Class HIM

If your drive has either an LED or LCD HIM (Human Interface Module), it can be used to access parameters in the adapter as shown below. It is recommended that you read through the steps for your HIM before performing the sequence. For additional information, refer to your PowerFlex Drive User Manual or the HIM Quick Reference card.
Using an LED HIM
Step Key(s) Example Screens
1. Press ALT and then Sel (Device) to display the Device Screen.
2. Press the Up Arrow or Down Arrow to scroll to the adapter. Letters represent files in the drive, and numbers represent ports. The adapter is usually connected to port 5.
3. Press the Enter key to enter your selection. A parameter database is constructed, and then the first parameter is displayed.
4. Edit the parameters using the same techniques that you use to edit drive parameters.
ALT
Device
Sel
or
Using an LCD HIM
Step Key(s) Example Screens
1. In the main menu, press the Up Arrow or Down Arrow to scroll to Device Select.
2. Press Enter to enter your selection.
3. Press the Up Arrow or Down Arrow to scroll to the adapter (20-COMM-H).
4. Press Enter to select the adapter. A parameter database is constructed, and then the main menu for the adapter is displayed.
5. Edit the parameters using the same techniques that you use to edit drive parameters.
or
or
NOTE: LCD HIM screens are shown throughout this chapter for example configuration procedures.
F-> Stopped Auto
0.00 Hz
Main Menu: Diagnostics Parameter
Device Select
Port 5 Device 20-COMM-H Main Menu:
Diagnostics
Parameter
Device Select
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter 3-3

Setting the Node Address

Setting the Network Data Rate

If the Node Address switches on the adapter are set to “00,” the value of
Parameter 03 - [Net Addr Cfg] determines the node address.
1. Set the value of Parameter 03 - [Net Addr Cfg] to a unique node
address.
Figure 3.1 Example Net Addr Cfg 1 Screen
Port 5 Device 20-COMM-H Parameter #: 03
Net Addr Cfg
1
0 <> 247
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual node address is then displayed by Parameter 04 - [Net Addr Act].
The data rate at which the adapter operates varies based on the type of network and your network configuration. Refer to the following table.
Network Possible Data Rates
Modbus RTU 4800, 9600, 19200, 38400 Metasys N2 9600 Siemens Building Technologies P1 FLN 4800, 9600
Default = 1
1. Set the value of Parameter 05 - [Net Rate Cfg] to the data rate at which your network is operating.
Figure 3.2 Example Net Rate Cfg Screen
Port 5 Device 20-COMM-H Parameter #: 05
Net Rate Cfg
1
9600
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual data rate is then displayed by Parameter 06 - [Net Rate Act].
Value Baud
0 4800 1 9600 (default) 2 19200 3 38400
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-4 Configuring the Adapter

Setting the Network Parity

The parity that the adapter uses to verify data integrity varies based on the type of network and your network configuration. Refer to the following table.
Network Possible Types of Parity
Modbus RTU None, Even, or Odd Metasys N2 None Siemens Building Technologies P1 FLN None
1. Set the value of Parameter 07 - [Net Parity Cfg] to the type of parity
that is used on the network.
Figure 3.3 Example Network Parity Screen
Port 5 Device 20-COMM-H Parameter #: 07
Net Parity Cfg
0
None
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual network parity is then displayed by Parameter 08 - [Net Parity Act].
Value Type of Parity
0 None (default) 1Odd 2Even

Setting Stop Bits (Modbus RTU only)

Parameter 30 - [Stop Bits Cfg] enables you to set 1 or 2 stop bits for the Modbus RTU network protocol. When the adapter rotary switch is set to “N2” or “P1,” the Stop Bits Cfg value is ignored and does not transfer to read-only Parameter 09 - [Stop Bits Act] on power-up or reset (N2 and P1 are fixed at 1 stop bit).
1. Set the value of Parameter 30 - [Stop Bits Cfg].
Figure 3.4 Example Stop Bits Screen
Port 5 Device 20-COMM-H Parameter #: 30
Stop Bits Cfg
1-bit
2. Reset the adapter (see Resetting the Adapter on page 3-8). The actual stop bits is then displayed by Parameter 09 - [Stop Bits Act].
0
Value Type of Stop Bit
0 1-bit (default) 12-bits
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter 3-5

Setting the I/O Configuration

The I/O configuration determines the data that is sent to and from the drive. Logic Command/Status, Reference/Feedback, and Datalinks may be enabled or disabled. A “1” enables the I/O. A “0” disables the I/O.
1. Set the bits in Parameter 16 - [DPI I/O Cfg].
Figure 3.5 Example DPI I/O Cfg Screen
Port 5 Device 20-COMM-H Parameter #: 16
DPI I/O Cfg xxxxxxxxxxx0000 Cmd/Ref b00
Bit 0 is the right-most bit. In Figure 3.5, it is highlighted and equals “1.”
2. If Logic Command/Reference is enabled, configure the parameters in
the drive to accept the Logic Command and Reference from the adapter. For example, set Parameter 90 - [Speed Ref A Sel] in a PowerFlex 70 or 700 drive to “22” (DPI Port 5) so that the drive uses the Reference from the adapter. Also, verify that the mask parameters (for example, Parameter 276 - [Logic Mask]) in the drive are configured to receive the desired logic from the adapter. Refer to the documentation for your drive for details.
Bit Description
0 Logic Command/Reference (Default) 1 Datalink A 2 Datalink B 3 Datalink C (not used with Metasys N2
1
4 Datalink D (not used with Metasys N2 5 - 15 Not Used
3. If you enabled one or more Datalinks, configure parameters in the drive
to determine the source and destination of data in the Datalink(s). For example, configure the Datalinks in PowerFlex 70 and 700 drives by setting Parameters 300 - [Data In A1] to 317 - [Data Out D2]. Also, ensure that this adapter is the only adapter using the enabled Datalink(s).
4. Reset the adapter (see Resetting the Adapter
The adapter is ready to send and receive I/O. The following chapters provide information about basic data transfer for each type of protocol.
Network Refer to…
Modbus RTU Chapter 4 Metasys N2 Chapter 5, Using Metasys N2 Siemens Building Technologies P1 FLN Chapter 6, Using Siemens Building Technologies P1 FLN
For details about using Datalinks for all types of networks, refer to
Chapter 7
, Using Datalinks with All Protocols.
, Using Modbus RTU
on page 3-8).
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-6 Configuring the Adapter

Setting a Network Time-out

The network timeout sets an interval within which the adapter must communicate with its master. If this time is exceeded, the adapter determines a loss of network communications has occurred and responds with the action specified in Parameter 15 - [Comm Flt Action].
By default, the timeout is set to ten (10) seconds. You can increase or decrease this value. Alternatively, you can set the value to zero (0) so that the adapter does not detect communication losses.
ATTENTION: Risk of injury or equipment damage exists. Parameter 11 - [Network Timeout] lets you determine how
!
long it will take your adapter to detect network communication losses. By default, this parameter sets the timeout to ten (10) seconds. You can set it so that the duration is shorter, longer, or disabled. Take precautions to ensure that the setting does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
Set the network timeout in Parameter 11 - [Network Timeout].
Figure 3.6 Example Network Timeout Screen
Port 5 Device 20-COMM-H Parameter #: 11
Network Timeout
10 Sec
0 <> 180
Changes to this parameter take effect immediately. A reset is not required.
Default = 10 seconds
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter 3-7

Setting a Fault Action

By default, when I/O communications are disrupted (for example, a cable is disconnected), the drive responds by faulting if it is using I/O from the network. You can configure a different response to disrupted I/O communication using Parameter 15 - [Comm Flt Action].
ATTENTION: Risk of injury or equipment damage exists. Parameter 15 - [Comm Flt Action] lets you determine the action
!
of the adapter and connected drive if I/O communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
Changing the Fault Action
Set the value of Parameter 15 - [Comm Flt Action] to the desired response:
Value Action Description
0 Fault The drive is faulted and stopped. (Default) 1 Stop The drive is stopped, but not faulted. 2 Zero Data The drive is sent 0 for output data. (The command word and Reference are
set to zero.) This does not command a stop. 3 Hold Last The drive continues in its present state. 4 Send Flt Cfg The drive is sent the data that you set in the fault configuration parameters
(Parameters 18 - [Flt Cfg Logic] through 27 - [Flt Cfg D2 In]).
Figure 3.7 Example Fault Action Screen
Port 5 Device 20-COMM-H Parameter #: 15
Comm Flt Action
0
Fault
Changes to this parameter takes effect immediately. A reset is not required.
Setting the Fault Configuration Parameters
If you set Parameter 15 - [Comm Flt Action] to “Send Flt Cfg,” the values in the following parameters are sent to the drive after an I/O communications fault occurs. You must set these parameters to values required by your application.
Parameter Name Description
25 Flt Cfg Logic A 16-bit value sent to the drive for Logic Command. 26 Flt Cfg Ref A 32-bit value (0 – 4294967295) sent to the drive as a Reference or 27 – 34 Flt Cfg x1 In
or Flt Cfg x2 In
Datalink. Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most
significant word of the value must be set to zero (0) or a fault will occur.
Changes to these parameters take effect immediately. A reset is not required.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-8 Configuring the Adapter

Resetting the Adapter

Changes to switch settings and some adapter parameters require that you reset the adapter before the new settings take effect. You can reset the adapter by cycling power to the drive or by using Parameter 14 - [Reset
Module].
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault
!
when you reset the adapter. Determine how your drive will respond before resetting a connected adapter.
Set Parameter 14 - [Reset Module] to “1” (Reset Module).
Figure 3.8 Example Reset Module Screen
Port 5 Device 20-COMM-H Parameter #: 14
Reset Module
1
Reset Module
When you enter “1” (Reset Module), the adapter will be immediately reset. When you enter “2” (Set Defaults), the adapter will set all adapter parameters to their factory-default values. After performing a Set Defaults, enter “1” (Reset Module) so that the new values take effect. The value of this parameter will be restored to “0” (Ready) after the adapter is reset.
Value Description
0 Ready (Default) 1 Reset Module 2 Set Defaults
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Configuring the Adapter 3-9

Viewing the Adapter Status Using Parameters

The following parameters provide information about the status of the adapter. You can view these parameters at any time.
Parameter Description 04 - [Net Add Act] Displays the actual network address of the adapter. 06 - [Net Rate Act] Displays the network data rate actually used by the adapter. Only valid
08 - [Net Parity Act] Displays the actual network parity used by the adapter. Only valid values
09 - [Stop Bits Act] Displays the actual number of stop bits used by the selected protocol.
10 - [Net Chksum Type] Displays the type of checksum used by the selected protocol. The values
17 - [DPI I/O Act] Displays the Reference/Feedback and Datalinks used by the adapter. This
values for the specified network are displayed.
for the specified network are displayed.
This value is network-dependent:
ModBus RTU Protocol – The number of stop bits used depends on the
value set by Parameter 30 - [Stop Bits Cfg]). If the value is “0,” the adapter uses 1 stop bit; otherwise, it uses 2 stop bits.
Metasys N2 Protocol – Uses only 1 bit, so the adapter shows only this
value.
Siemens Building Technologies P1 FLN Protocol – Uses only 1 bit, so
the adapter shows only this value.
are as follows:
CRC16 (0) is Cyclic Redundancy Check with 0 as a seed value. The
Siemens Building Technologies P1 FLN protocol uses this checksum.
RLC is Run Length Checksum. The Metasys N2 protocol uses this
checksum.
CRC16 (-1) is Cyclic Redundancy Check with -1 as a seed value. The Modbus RTU protocol uses this checksum.
value is the same as Parameter 16 - [DPI I/O Cfg] unless the parameter was changed and the adapter was not reset.
Bit Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A Default xxx00001 Bit 76543210
Cmd/Ref
0 = I/O disabled 1 = I/O enabled
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
3-10 Configuring the Adapter

Flash Updating the Adapter

The adapter can be flash updated over the network or serially through a direct connection from a computer to the drive using a 1203-USB or 1203-SSS serial converter.
When flashing over the network, you can use the Allen-Bradley software tool ControlFLASH, the built-in flash capability of DriveExplorer Lite or Full, or the built-in flash capability of DriveExecutive.
When flashing through a direct serial connection from a computer to a drive, you can use the same Allen-Bradley software tools described above, or you can use HyperTerminal set to the X-modem protocol.
To obtain a flash update for this adapter, go to http://www.ab.com/support/
abdrives/webupdate. This site contains all firmware update files and
associated Release Notes that describe firmware update enhancements/ anomalies, how to determine the existing firmware version, and how to flash update using DriveExplorer, DriveExecutive, ControlFLASH or HyperTerminal.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 4

Using Modbus RTU

This chapter provides information about controlling a PowerFlex 7-Class drive, setting its Reference, and accessing its parameters through configurable objects when the Modbus RTU network protocol is selected.
Topic Page
Understanding Modbus RTU Using the Modbus RTU Point Map for I/O 4-4 Accessing Drive Parameters 4-9 Using Broadcast Messages 4-12
TIP: Datalinks can also be used for accessing parameters. For information about using Datalinks, refer to Chapter 7
Protocols.
4-1
, Using Datalinks with All

Understanding Modbus RTU

The Modbus RTU protocol is a messaging structure used to establish master-slave communication between intelligent devices. The protocol defines the format of the messages.
Messages from a master to a slave contain the address of the slave, a function code defining the requested action, any data to be sent, and an error-checking field. Messages from a slave to a master contain fields confirming the action taken, any data to be returned, and an error-checking field. If an error occurred in the receipt of the message or if the slave is unable to perform the requested action, the slave will construct an error message and send it as its response.
Modbus RTU can access a single address or multiple addresses simultaneously, either reading or writing single-bit values or 16-bit values.
Modbus RTU Data Formats
Modbus data types are 1-bit and 16-bit values. Refer to Table 4.A.
Table 4.A Modbus RTU Data Formats
Modbus Type Description Reference
Coil Status 1-bit Discrete Output 0x Input Status 1-bit Discrete Input 1x Holding Register 16-bit Output Register 4x Input Register 16-bit Input Register 3x
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-2 Using Modbus RTU
Supported Modbus RTU Commands
The adapter supports the Modbus RTU commands listed in Table 4.B.
Table 4.B Modbus RTU Commands Supported by RS-485 Adapter
Function Code Description
01 Read Coil Status 02 Read Input Status 03 Read Holding Registers 04 Read Input Registers 05 Force Single Coil 06 Write Single Register 08 Diagnostics
Subfunction 00 Only - Return Query Data (loop back) 16 Write Multiple Registers 23 Read/Write 4x Registers
Data Addresses in Modbus Messages
All data addresses in Modbus messages are referenced to zero. That is, the first occurrence of a data item is addressed as item number zero. Therefore, when you create a message, you must address it to one less than the Modbus address in the manual. The following are examples:

Adapter Modbus Register Map

Logic Command is Holding Register address 4x0001 in Table 4.F on
page 4-7, so you address it as register “0000” in the data address field of
the message.
Feedback Hi is Input Register address 3x0003 in Table 4.H on page 4-8
so you address it as register “0002” in the data address field of the message.
Start is Coil address 0x0002 in Table 4.E on page 4-6
as coil “0001” in the data address field of the message.
At Speed is Input address 1x0009 in Table 4.G on page 4-7
address it as input “0008” in the data address field of the message.
, so you address it
Table 4.C provides an overview of the Modbus register addresses and their
related functions.
Table 4.C Adapter Modbus Register Map
Modbus Register Function
Write Product Command Word Bits
0x0001 Stop 0x0002 Start 0x0003 Jog 0x0004 Clear Faults 0x0005 Direction 0x0006 0x0007 Local Control 0x0008 MOP Increment
,
, so you
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Modbus RTU 4-3
Table 4.C Adapter Modbus Register Map (Continued)
Modbus Register Function
0x0009 Accel Rate 0x0010 0x0011 Decel Rate 0x0012 0x0013 Reference Select 0x0014 0x0015 0x0016 MOP Decrement
Read Product Status Word Bits
1x0001 Ready 1x0002 Active 1x0003 Command Direction 1x0004 Actual Direction 1x0005 Accel 1x0006 Decel 1x0007 Alarm 1x0008 Fault 1x0009 At Speed 1x0010 Local Control 1x0011 1x0012 1x0013 Reference 1x0014 1x0015 1x0016
Read Various Input Registers
3x0001 Product Status Word 3x0002 Feedback Lo (Bits 0…15 of 32-bit Feedback) 3x0003 Feedback Hi (Bits 16…31 of 32-bit Feedback or whole 16-bit Feedback) 3x0004 Read USER IN 1 3x0005 Read USER IN 2 3x0006 Read USER IN 3 3x0007 Read USER IN 4 3x0008 Read USER IN 5 3x0009 Read USER IN 6 3x0010 Read USER IN 7 3x0011 Read USER IN 8 3x0012 Read Datalink A1 Out 3x0013 3x0014 Read Datalink A2 Out 3x0015 3x0016 Read Datalink B1 Out 3x0017 3x0018 Read Datalink B2 Out 3x0019 3x0020 Read Datalink C1 Out 3x0021 3x0022 Read Datalink C2 Out 3x0023 3x0024 Read Datalink D1 Out 3x0025 3x0026 Read Datalink D2 Out 3x0027
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-4 Using Modbus RTU
Table 4.C Adapter Modbus Register Map (Continued)
Modbus Register Function
Write Various Holding Registers
4x0001 Product Logic Command 4x0002 Reference Lo (Bits 0…15 of 32-bit Reference) 4x0003 Reference Hi (Bits 16…31 of 32-bit Reference or whole 16-bit Reference) 4x0004 Parameter # for USER IN1 4x0005 Parameter # for USER IN2 4x0006 Parameter # for USER IN3 4x0007 Parameter # for USER IN4 4x0008 Parameter # for USER IN5 4x0009 Parameter # for USER IN6 4x0010 Parameter # for USER IN7 4x0011 Parameter # for USER IN8 4x0012 Write USER OUT1 4x0013 Write USER OUT2 4x0014 Write USER OUT3 4x0015 Parameter # for USER OUT1 4x0016 Parameter # for USER OUT2 4x0017 Parameter # for USER OUT3 4x0018 Write Datalink A1 In 4x0019 4x0020 Write Datalink A2 In 4x0021 4x0022 Write Datalink B1 In 4x0023 4x0024 Write Datalink B2 In 4x0025 4x0026 Write Datalink C1 In 4x0027 4x0028 Write Datalink C2 In 4x0029 4x0030 Write Datalink D1 In 4x0031 4x0032 Write Datalink D2 In 4x0033
Direct Parameter Access
4x0100 + param # 20-COMM-H Parameter Direct Access (with adapter in 16-bit mode) 4x0100 + (param # x 2) 20-COMM-H Parameter Direct Access (with adapter in 32-bit mode)
4x1000 + param # Drive Parameter Direct Access (with adapter in 16-bit mode) 4x1000 + (param # x 2) Drive Parameter Direct Access (with adapter in 32-bit mode)

Using the Modbus RTU Point Map for I/O

20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
On Modbus, data transfers are used to transfer the I/O data that controls the drive and sets its Reference. Note that output I/O is data that the master device sends and the adapter receives. Input I/O is status data that the adapter sends and the master device receives.
Important:In order for the drive to use the I/O and Reference from the
Modbus RTU network, you must set parameters in it and the adapter to receive the I/O and Reference. For details, refer to
Setting the I/O Configuration
on page 3-5.
Using Modbus RTU 4-5
Setting the Logic Command and Reference
ATTENTION: Select and use either the “Product Logic Command Discrete Outputs (0x000x)” or the “Product Logic
!
Command Register Output (4x0001)” as a control method, but not both. Conflicts caused from using both methods can result in dangerous operation. Failure to observe this caution could cause bodily injury and/or damage to equipment.
On Modbus RTU, there are two ways to set the logic command: discrete outputs (Table 4.E on page 4-6
page 4-7).
When you need to set only one bit in the logic command word, you can
use a discrete output. For example, to stop a PowerFlex 70/700 drive (bit
0), you can use a discrete output (Modbus Address 0x0001).
When you need to set multi-bit fields in the logic status word or to set the
entire logic status word, you must use the register output to maintain data integrity. For example, to set the direction of a PowerFlex 70/700 drive (bits 4 and 5), you must use a register output (Modbus Address 4x0001).
) and register outputs (Table 4.F on
A 16-bit product logic word is buffered in the adapter, holding the last logic command sent to the drive regardless of whether it was sent through the discrete outputs or through the product logic command register output. When a bit is updated through the discrete outputs or the register output, a new logic command is generated and sent to the drive.
To set the Reference, you must use a register output (Modbus Address 4x0002 and/or 4x0003 in Table 4.F on page 4-7 is a scaled value; it is not an engineering value. For example, in PowerFlex 70/ 700 drives, the reference is scaled based on the value of Parameter 55 - [Maximum Freq], but the commanded maximum speed can never exceed the value of Parameter 82 - [Maximum Speed]. Tabl e 4.D References and their results on a PowerFlex 70/700 drive that has its
Parameters 55 - [Maximum Freq] set to 130 Hz and 82 - [Maximum Speed] set to 60 Hz.
Table 4.D Example Speed Reference and Feedback for a PowerFlex 70/700
Reference Value
32767 16384 50% 65 Hz 60 Hz 8192 25% 32.5 Hz 32.5 Hz 8192 0 0% 0 Hz 0 Hz 0
(1)
A value of 32767 is equivalent to 100%. The effects of values greater than 32767 depend on whether the DPI product uses a bipolar or unipolar direction mode. Refer to the documentation for your DPI product.
(2)
The drive runs at 60 Hz instead of 130 Hz or 65 Hz because Parameter 82 - [Maximum Speed] sets 60 Hz as the maximum speed.
(3)
The Feedback value is also scaled based on the value of Parameter 55 - [Maximum Freq], For example, 60/130 = 0.46 so 32767 x 0.46 = 15123.
Scale
(1)
100% 130 Hz 60 Hz
). Remember that the Reference value
shows example
Feedback
Output Speed
(2)
(2)
15123
ValuePercent Value
15123
(3)
(3)
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-6 Using Modbus RTU
Table 4.E shows that there are 16 discrete points to represent the command
word bit by bit. These points can be used only for writing single-bit commands.
Table 4.E Logic Command: Discrete Outputs (to Drive from Controller)
Modbus Address
0x0001 0 Stop 0 = Not Stop
0x0002 1 Start
0x0003 2 Jog 0 = Not Jog
0x0004 3 Clear Faults
0x0005 4 Direction Modbus Address 0x0006 5 06 05
0x0007 6 Local Control 0 = No Local Control
0x0008 7 MOP Increment 0 = Not Increment
0x0009 8 Accel Rate Modbus Address 0x0010 9 10 09
Logic Command Bit
0x0011 10 Decel Rate Modbus Address 0x0012 11 12 11
0x0013 12 Reference Select Modbus Address 0x0014 13 15 14 13 0x0015 14 0 0 0 = No Command
0x0016 15 MOP Decrement 0 = Not Decrement
(1)
A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.
(2)
To perform this command, the value must change from “0” to “1.”
PowerFlex 70/700 Example Description Values
(1) (2)
(2)
1 = Stop 0 = Not Start 1 = Start
1 = Jog 0 = Not Clear Faults 1 = Clear Faults
0 0 = No Command 0 1 = Forward Command 1 0 = Reverse Command 1 1 = Hold Direction Control
1 = Local Control
1 = Increment
0 0 = No Command 0 1 = Accel Rate 1 Command 1 0 = Accel Rate 2 Command 1 1 = Hold Accel Rate
0 0 = No Command 0 1 = Decel Rate 1 Command 1 0 = Decel Rate 2 Command 1 1 = Hold Decel Rate
0 0 1 = Ref 1 (Ref A Select) 0 1 0 = Ref 2 (Ref B Select) 0 1 1 = Ref 3 (Preset 3) 1 0 0 = Ref 4 (Preset 4) 1 0 1 = Ref 5 (Preset 5) 1 1 0 = Ref 6 (Preset 6) 1 1 1 = Ref 7 (Preset 7)
1 = Decrement
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Modbus RTU 4-7
Table 4.F shows the register outputs. These outputs must be used for writing
multi-bit commands and the Reference.
Table 4.F Logic Command and Reference: Register Outputs
Modbus Address Output Description Values
4x0001 Product Logic Command 16-bit word. Bit definitions for PowerFlex 70/700 drives are in
Tabl e 4 .E
4x0002 Reference Lo Bit 0…15 of 32-bit reference.
(1)
4x0003
(1)
The reference value is sent only when accessing address 4x0003. If a 32-bit reference is used, the 32-bit value will be merged together by register 4x0002 and 4x0003 when accessing address 4x0003.
Viewing the Logic Status and Feedback
On Modbus RTU, there are two ways to view the logic status: discrete inputs (Table 4.G discrete inputs when you need to view only one bit in the logic status word. For example, to view whether a PowerFlex 70/700 drive is Ready (bit 0), you can use a discrete input (Modbus Address 1x0001).
Reference Hi Bit 16…31 of 32-bit reference or the whole 16-bit reference.
) and register inputs (Table 4.H on page 4-8). You can use
. For other products, refer to their documentation.
When you need to view multi-bit fields in the logic status word or to view the entire logic status word, you must use a register input to maintain data integrity. For example, to view the local control of a PowerFlex 70/700 drive (bits 9…11), you must use a register input (Modbus Address 3x0001).
To view the Feedback, you must also use a register input (Modbus Address 3x0002 and/or 3x0003). For details about how the feedback is scaled, refer to the Setting the Logic Command and Reference
Table 4.G
word bit by bit. These points can be used only for reading single-bit status.
Table 4.G Logic Status: Discrete Inputs (to Controller from Drive)
Modbus Address Logic Status Bit
1x0001 0 Ready 0 = Not Ready
1x0002 1 Active 0 = Not Running
1x0003 2 Command Direction 0 = Reverse
1x0004 3 Actual Direction 0 = Reverse
1x0005 4 Accel 0 = Not Accelerating
1x0006 5 Decel 0 = Not Decelerating
1x0007 6 Alarm 0 = No Alarm
1x0008 7 Fault 0 = No Fault
1x0009 8 At Speed 0 = Not At Reference
shows that there are 16 discrete points to represent the status
PowerFlex 70/700 Example Description Values
1 = Ready
1 = Running
1 = Forward
1 = Forward
1 = Accelerating
1 = Decelerating
1 = Alarm
1 = Fault
1 = At Reference
on page 4-5.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-8 Using Modbus RTU
Table 4.G Logic Status: Discrete Inputs (to Controller from Drive) (Continued)
Modbus Address Logic Status Bit
1x0010 9 Local Control Modbus Address 1x0011 10 12 11 10 1x0012 11 0 0 0 = Port 0 (TB)
1x0013 12 Reference Modbus Address 1x0014 13 16 15 14 13 1x0015 14 0 0 0 0 = Ref A Auto 1x0016 15 0 0 0 1 = Ref B Auto
PowerFlex 70/700 Example Description Values
001= Port 1 010= Port 2 011= Port 3 100= Port 4 101= Port 5 110= Port 6 1 1 1 = No Local
0 0 1 0 = Preset 2 Auto 0 0 1 1 = Preset 3 Auto 0 1 0 0 = Preset 4 Auto 0 1 0 1 = Preset 5 Auto 0 1 1 0 = Preset 6 Auto 0 1 1 1 = Preset 7 Auto 1000= Term Blk Manual 1 0 0 1 = DPI 1 Manual 1 0 1 0 = DPI 2 Manual 1 0 1 1 = DPI 3 Manual 1 1 0 0 = DPI 4 Manual 1 1 0 1 = DPI 5 Manual 1 1 1 0 = DPI 6 manual 1111= Jog Ref
Table 4.H shows the register inputs. These inputs must be used for reading
multi-bit status fields and the Feedback.
Table 4.H Logic Status and Feedback: Register Inputs
Modbus Address Input Description Values
3x0001 Product Status Word 16-bit word. Bit definitions for PowerFlex 70/700 drives are in
Tabl e 4 .G
3x0002 Feedback Lo Bit 0…15 of 32-bit feedback
(1)
Feedback Hi Bit 16…31 of 32-bit feedback or the whole 16-bit feedback.
3x0003
(1)
The Feedback value is refreshed only when accessing address 3x0003. This is to maintain data integrity.
. For other products, refer to their documentation.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Modbus RTU 4-9

Accessing Drive Parameters

There are two methods for accessing drive parameters: the direct access method and the pointer access method.
Direct Access Method
You can use Function Code 03 to read and Function Codes 06 (single) and 16 (multiple) to write, to directly access the drive parameters (see
Table 4.B on page 4-2
read or write as opposed to first having to write the “Param# for INx” or “Param# for OUTx” using the Pointer Access Method.
When a 41000 or higher Modbus address is used, the adapter assumes the controller is accessing the drive’s parameters directly. The address is determined by:
16-bit Adapter Mode: Modbus Address = 41000 + (Drive Parameter #) 32-bit Adapter Mode: Modbus Address = 41000 + (Drive Parameter # x 2)
For example, with the adapter in 16-bit mode, Parameter 1 is accessed by Modbus Address 41000. In the 32-bit mode, Parameter 1 is accessed by Modbus Address 41002. Any attempts to access a parameter number that does not exist will return an error.
). This allows direct access of parameters in a single
The 32-bit adapter mode requires a minimum of two registers to read or write, and is always an even number since two 16-bit registers are read for each 32-bit data item.
Pointer Access Method
Reading Parameter Values
With a configurable input point, you can read any 16-bit parameter in the drive. The sequence for reading parameter values is as follows:
1. Set one or more Param# for INx points in the controller to the parameter
number(s) that you want to read. You can set up to eight Param# for INx points. Refer to Table 4.I on page 4-10
2. Send a message with a Write Single Register (code 06) or Write
Multiple Register (code 16) function. You need to send the Param# for INx point(s) to the adapter only one time per power cycle because, when the adapter receives the Param# for INx point(s), it stores them in its RAM. The adapter then continuously reads the values for the drive parameters specified in the Param# for INx points.
3. Send a message with a Read Input Registers (code 04) function. The
adapter reads the drive parameter(s) that have been configured in the Param# for IN point(s) and returns their values in the User INx point(s). It can return up to eight User INx points. Refer to Table 4.I on
page 4-10. You can perform Read Input Registers continuously, if
desired.
.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-10 Using Modbus RTU
Figure 4.1 Configurable Input Point Operations
Controller Adapter
Param#
for INx
With the adapter in 16-bit mode, 8 User IN items are available.
Table 4.I Configurable Objects Inputs with Adapter in 16-bit Mode
Modbus Address Data Direction Description Values
3x0004 Register Input User IN1 Depends on parameter selected 0 3x0005 User IN2 3x0006 User IN3 3x0007 User IN4 3x0008 User IN5 3x0009 User IN6 3x0010 User IN7 3x0011 User IN8
4x0004 Register Output Param # for IN1 0 = Not in use 4x0005 Param # for IN2 4x0006 Param # for IN3 4x0007 Param # for IN4 4x0008 Param # for IN5 4x0009 Param # for IN6 4x0010 Param # for IN7 4x0011 Param # for IN8
Write Single Register (code 06)
Write Multiple Register (code 16)
Read Input Registers (code 04) Request
Response Data
or
User
INx
- or ­1 to maximum parameter #
and
Drive
User Default
0
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
16-bit Mode Example: Write a value of “12” to register 4x0004. Read register 3x0004 to read the 16-bit data value from drive parameter 12.
With the adapter in 32-bit mode, 4 User IN items are available.
Table 4.J Configurable Objects Inputs with Adapter in 16-bit Mode
Modbus Address Data Direction Description Values
3x0004 3x0005 3x0006 3x0007 3x0008 3x0009 3x0010 3x0011
4x0004 Register Output Param # for IN1 0 = Not in use 4x0005 Param # for IN2 4x0006 Param # for IN3 4x0007 Param # for IN4
32-bit Mode Example: Write a value of “12” to register 4x0004. Read register 3x0004 and store the returned 16-bit data. Read register 3x0005 and
Register Input User IN1 Lo
User IN1 Hi User IN2 Lo User IN2 Hi User IN3 Lo User IN3 Hi User IN4 Lo User IN4 Hi
Depends on parameter selected 0
- or ­1 to maximum parameter #
User Default
0
Using Modbus RTU 4-11
store the returned 16-bit data. Use both 16-bit data items to make one 32-bit value for drive parameter 12.
Writing Parameter Values
ATTENTION: Risk of equipment damage exists. If configurable output points are programmed to write parameter
!
data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS. Datalinks do not write to NVS and should be used for frequently changed parameters.
With a configurable output point, you can write a new value for any 16-bit parameter in the drive. The sequence for writing parameter values is as follows:
1. Set one or more Param# for OUTx points in the controller to the
parameter number(s) to which you want to write. A value of zero in the Param# field disables the writing of data for that specific point. Refer to the drive user manual for the desired parameter number(s). You can set up to three Param# for OUTx points at a time. Refer to Table 4.K on
page 4-12.
2. Send a message with a Write Single Register (code 06) or Write
Multiple Register (code 16) function. You need to send the Param# for OUTx point(s) to the adapter only one time per power cycle because, when the adapter receives the Param# for OUTx point(s), it stores them in its RAM.
3. Set the values that you want to write to the parameters in the User
OUTx points. You can set up to three User OUTx points at a time. Refer to Table 4.K on page 4-12
4. Send a message with a Write Single Register (code 06) or Write
Multiple Register (code 16) function. Each time that the adapter receives the values in the User OUTx points, it writes them to the drive parameters.
Figure 4.2 Configurable Output Point Operations
Controller Adapter
Param#
for OUTx
User
OUTx
.
Write Single Register (code 06)
or
Write Multiple Register (code 16)
Write Single Register (code 06)
or
Write Multiple Register (code 16)
and
Drive
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-12 Using Modbus RTU
Table 4.K Configurable Objects: Outputs with Adapter in 16-bit Mode

Using Broadcast Messages

Modbus Address Data Direction Description Values
4x0012 Register Output User OUT1 Depends on parameter selected 0 4x0013 User OUT2 4x0014 User OUT3 4x0015 Param # for OUT1 0 = Not in use 4x0016 Param # for OUT2 4x0017 Param # for OUT3
16-bit Mode Example: Write a value of “101” to register 4x0015. Write a value of “123” to register 4x0012. The drive parameter 101 value now equals 12.3.
32-bit Mode: User OUT items are not supported when using the adapter in the 32-bit mode.
A Modbus RTU global broadcast feature enables you to send a command (start, stop, etc.) to all drives on the network at the same time by using Modbus Address “0.” This feature can also be used to write the same message to each network drive via a single message, for example setting Accel Time to 5 seconds in every drive.
Important:Every node capable of receiving a broadcast message will act
upon the message, so it is required that broadcast messages are used only on networks of similar devices. For example, PowerFlex 70 and 700 drives use the same Logic Command structure, Reference format and the same Modbus addressing, so these could be controlled together using a broadcast message. Always check the Modbus addressing, Logic Command structure, Reference format, etc. for every node device type before designing a system with broadcast messages.
- or ­1 to maximum parameter #
User Default
0
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
The adapter also enables you to independently scale the broadcast message Reference of its connected drive by using Parameter 31 - [RTU Ref. Adjust]. The scaling factor can be set from 0…200.0%. This lets the drive Reference either match the broadcast message Reference (= 100%), scale below the broadcast message Reference (<100%), or scale above the broadcast message Reference (>100%).
Using Modbus RTU 4-13

Adapter Parameter Direct Access

Table 4.L provides an overview of the Modbus register addresses for
directly accessing the adapter parameters.
Table 4.L Adapter Parameter Direct Access Modbus Register Map
Modbus Register Parameter Description
4x0101 DPI Port 4x0102 DPI Data Rate 4x0103 Net Addr Cfg 4x0104 Net Addr Act 4x0105 Net Rate Cfg 4x0106 Net Rate Act 4x0107 Net Parity Cfg 4x0108 Net Parity Act 4x0109 Stop Bits Act 4x0110 Net Chksum Type 4x0111 Network Timeout 4x0112 Ref/Fdbk Size 4x0113 Datalink Size 4x0114 Reset Module 4x0115 Comm Flt Action 4x0116 DPI I/O Cfg 4x0117 DPI I/O Act 4x0118 Flt Cfg Logic 4x0119 Flt Cfg Ref Lo
(1)
4x0120 4x0121 Flt Cfg A1 In Lo
(1)
4x0122 4x0123 Flt Cfg A2 In Lo
(1)
4x0124 4x0125 Flt Cfg B1 In Lo
(1)
4x0126 4x0127 Flt Cfg B2 In Lo
(1)
4x0128 4x0129 Flt Cfg C1 In Lo
(1)
4x0130 4x0131 Flt Cfg C2 In Lo
(1)
4x0132 4x0133 Flt Cfg D1 In Lo
(1)
4x0134 4x0135 Flt Cfg D2 In Lo
(1)
4x0136 4x0137 Clear Counters 4x0138 N2 Ref Scale Lo
(1)
4x0139 4x0140 Stop Bits Cfg 4x0141 RTU Ref Adjust
(1)
A write access to this register triggers a store/update of this parameter value to the internal adapter EEPROM as a 32-bit value.
Flt Cfg Ref Hi
Flt Cfg A1 In Hi
Flt Cfg A2 In Hi
Flt Cfg B1 In Hi
Flt Cfg B2 In Hi
Flt Cfg C1 In Hi
Flt Cfg C2 In Hi
Flt Cfg D1 In Hi
Flt Cfg D2 In Hi
N2 Ref Scale Hi
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
4-14 Using Modbus RTU
Notes:
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 5

Using Metasys N2

This chapter provides information about controlling a PowerFlex 7-Class drive, setting its Reference, and accessing its parameters through configurable objects when the Metasys N2 network protocol is selected.
Topic Page
Understanding Metasys N2 Using the Metasys N2 Point Map for I/O 5-3 Using Metasys Configurable Objects to Access Parameters 5-8
TIP: Datalinks can also be used for accessing parameters. For information about using Datalinks, refer to Chapter 7
Protocols.
, Using Datalinks with All
5-1

Understanding Metasys N2

Metasys nodes are built up by the use of several virtual objects. The Metasys N2 master performs read and write commands to these virtual objects, and the adapter transfers/translates the data between these virtual objects and the drive.
When a read or write command occurs to a certain dedicated virtual object, data in the virtual objects is refreshed from or transferred to the drive.
The Metasys N2 master performs read and write commands to the virtual objects one at a time. The data types that are used in the virtual objects are binary input (BI), binary output (BO), analog input (AI), analog output (AO), and internal integer (ADI), which is a 16-bit data value.
The Metasys master also performs cyclic polling of all the virtual objects.
Device Identity
The 20-COMM-H adapter must be configured in the master controller as a Vendor device (VND) Code 10 hex.
Metasys N2 Virtual Objects
A Metasys N2 node may contain up to 256 virtual objects in each of its seven different data types, called regions (Table 5.A
).
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
5-2 Using Metasys N2
Table 5.A Description of the Regions of a Virtual Object
Region Type Short Description
Region 1 Analog Input AI 32-bit, IEEE-standard floats Region 2 Binary Input BI 1-bit Region 3 Analog Output AO 32-bit, IEEE-standard floats Region 4 Binary Output BO 1-bit Region 5 Internal Float ADF 32-bit, IEEE-standard floats (Analog Data Float) Region 6 Internal Integer ADI 16-bit (Analog Data Integer) Region 7 Internal Byte DB 8-bit (Analog Data Byte)
Metasys N2 Data Types
Table 5.B Internal Structure of Metasys N2 Analog Input (AI)
Attribute Type Description
1 Byte Object Configuration 2 Byte Object Status 3 Float Analog Input Value 8 Float Low Alarm Limit 9 Float Low Warning Limit 10 Float High Warning Limit 11 Float High Alarm Limit 12 Float Differential
Table 5.C Internal Structure of Metasys N2 Binary Input (BI)
Attribute Type Description
1 Byte Object Configuration 2 Byte Object Status
Table 5.D Internal Structure of Metasys N2 Analog Output (AO)
Attribute Type Description
1 Byte Object Configuration 2 Byte Object Status 3 Float Current Value
Table 5.E Internal Structure of Metasys N2 Binary Output (BO)
Attribute Type Description
1 Byte Object Configuration 2 Byte Object Status 3 Integer Minimum On-Time 4 Integer Minimum Off-Time 5 Integer Maximum Cycle/Hour
Table 5.F Internal Structure of Metasys N2 Internal Integer (ADI)
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Attribute Type Description
1 Byte Object Status 2 Integer Current Value. Signed 16-bit.
Using Metasys N2 5-3

Using the Metasys N2 Point Map for I/O

On Metasys N2, data transfers are used to transfer the I/O data that controls the drive and sets its Reference. Note that Output I/O is data that the master device sends and the adapter receives. Input I/O is status data that the adapter sends and the master device receives.
Important:In order for the drive to use the I/O and Reference from the
Metasys N2 network, you must set parameters in it and the adapter to receive the I/O and Reference. For details, refer to
Setting the I/O Configuration
Setting the Logic Command and Reference
ATTENTION: Select and use either the point type Digital (BO) or the word type Analog (AO) as a control method, but not both.
!
Conflicts caused from using both methods can result in dangerous operation. Failure to observe this precaution could cause bodily injury and/or damage to equipment.
On Metasys N2, there are two ways to set the logic command: binary outputs (Table 5.L on page 5-5
page 5-6).
) and an analog output (Table 5.M on
on page 3-5.
When you need to set only one bit in the Logic Command word, you can
use binary outputs. For example, to stop a PowerFlex 70/700 drive (bit
0), you can use a binary output (BO#1).
When you need to set multi-bit fields in the Logic Command word or to
set the entire Logic Command word, you must use the analog output to maintain data integrity. For example, to set the Reference Selection of a PowerFlex 70/700 drive (bits 12…14), you must use an analog output (AO#1).
A 16-bit product logic word is buffered in the adapter, holding the last Logic Command sent to the drive regardless of whether it was sent through the binary outputs or through product logic command outputs (AO#1). When a bit is updated through either of these outputs, a new Logic Command will be generated and sent to the drive.
To set the Reference, you must use an analog output (AO#2). Table 5.G shows example References and their results on a PowerFlex 70/700 drive that has its Parameters 55 - [Maximum Freq] set to 70 Hz and 82 -
[Maximum Speed] set to 60 Hz, and adapter Parameter 29 - [N2 Ref Scale] is set to 32,767.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
5-4 Using Metasys N2
Table 5.G Example Speed Reference and Feedback for a PowerFlex 70/700 Drive
Reference Percent Speed Speed Percent
100% 70 Hz 60 Hz 50% 35 Hz 35 Hz 50% 25% 17.5 Hz 17.5 Hz 25% 0% 0 Hz 0 Hz 0%
(1)
(2)
(3)
(1)
The actual value transmitted over the network is an engineering unit where 100% equals sending the value in the adapter Parameter 29 - [N2 Ref Scale], and 0% equals sending a zero.
The Feedback percent value is also scaled based on the value of adapter Parameter 29 - [N2 Ref Scale].
The drive runs at 60 Hz instead of 70 Hz because Parameter 82 - [Maximum Speed] sets 60 Hz as the maximum speed.
Feedback
(2)
(3)
85.7%
Reference Setup Examples
Table 5.H PowerFlex 70EC and PowerFlex 700VC Default Example
Drive Parameters 20-COMM-H Parameter Number Value Number Value
55 - [Maximum Freq] 130
29 - [N2 Ref Scale] 1512382 - [Maximum Speed] 60
298 - [DPI Ref Sel] 0 (Max Freq)
(1)
This value is calculated as follows: 60 ÷ 130 x 32767 = 15123.
Table 5.I Maximum Freq = 70 Hz Example
Drive Parameters 20-COMM-H Parameter Number Value Number Value
55 - [Maximum Freq] 70
29 - [N2 Ref Scale] 2808682 - [Maximum Speed] 60
298 - [DPI Ref Sel] 0 (Max Freq)
(1)
This value is calculated as follows: 60 ÷ 70 x 32767 = 28086.
(1)
(1)
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Table 5.J Maximum Speed = 80 Hz Example
Drive Parameters 20-COMM-H Parameter Number Value Number Value
55 - [Maximum Freq] 130
29 - [N2 Ref Scale] 2016482 - [Maximum Speed] 80
298 - [DPI Ref Sel] 0 (Max Freq)
(1)
This value is calculated as follows: 80 ÷ 130 x 32767 = 20164.
Table 5.K DPI Reference Scaling = Max Speed Example
Drive Parameters 20-COMM-H Parameter Number Value Number Value
55 - [Maximum Freq] 130
29 - [N2 Ref Scale] 3276782 - [Maximum Speed] 60
298 - [DPI Ref Sel] 1 (Max Speed)
(1)
When drive parameter 298 - [DPI Ref Sel] = 1 (Max Speed), the Reference and Feedback scaling is always defined as 32767, which will cause the drive to run at the value of drive parameter 82 ­[Maximum Speed]. In this example, the drive will run at 60 Hz.
(1)
(1)
Using Metasys N2 5-5
Table 5.L shows that there are 16 binary outputs to represent the command
word bit by bit. These outputs can be used only for writing single-bit commands.
Table 5.L Logic Command: Binary Outputs (Inputs to a Drive)
Network Point Type (NPT)
BO 1 0 Stop 0 = Not Stop
BO 2 1 Start
BO 3 2 Jog 0 = Not Jog
BO 4 3 Clear
BO 5 4 Direction Network Point Addresses BO 6 5 06 05
BO 7 6 Local Control 0 = No Local Control
BO 8 7 MOP
BO 9 8 Accel Rate Network Point Addresses BO 10 9 10 09
BO 11 10 Decel Rate Network Point Addresses BO 12 11 12 11
BO 13 12 Reference BO 14 13 15 14 13 BO 15 14 0 0 0 = No Command
BO 16 15 MOP
(1)
A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.
(2)
To perform this command, the value must change from “0” to “1.”
Network Point Address (NPA)
Logic Command Bit
PowerFlex 70/700 Example Description Values
(1) (2)
Faults
Increment
Select
Decrement
1 = Stop 0 = Not Start 1 = Start
1 = Jog 0 = Not Clear Faults
(2)
1 = Clear Faults
0 0 = No Command 0 1 = Forward Command 1 0 = Reverse Command 1 1 = Hold Direction Control
1 = Local Control 0 = Not Increment 1 = Increment
0 0 = No Command 0 1 = Accel Rate 1 1 0 = Accel Rate 2 1 1 = Hold Accel Rate
0 0 = No Command 01= Decel Rate 1 10= Decel Rate 2 1 1 = Hold Decel Rate
Network Point Addresses
0 0 1 = Ref 1 (Ref A Select) 0 1 0 = Ref 2 (Ref B Select) 0 1 1 = Ref 3 (Preset 3) 1 0 0 = Ref 4 (Preset 4) 1 0 1 = Ref 5 (Preset 5) 1 1 0 = Ref 6 (Preset 6) 1 1 1 = Ref 7 (Preset 7)
0 = Not Decrement 1 = Decrement
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
5-6 Using Metasys N2
Table 5.M shows the analog outputs. These outputs must be used for writing
multi-bit commands and the Reference.
Table 5.M Logic Command and Reference: Analog Outputs
Network Point Type (NPT)
AO 1 Product Logic
AO 2 Reference -100.0…100.0%
Additional Configuration Specific for Metasys N2
The Reference (AO#2) for Metasys N2 is set as a percentage from
-100…100%. However, the actual value transmitted over DPI is in an engineering unit that equals the entered percentage. Parameter 29 - [N2 Ref Scale] determines the engineering unit value sent when AO#2 is set to 100%. The relationship is linear, where:
Network Point Address (NPA)
100%
Parameter Description Range
16-bit word. Bit definitions for PowerFlex 70/700
Command
drives are in Table 5.L their documentation.
. For other products, refer to
0%
0
Pr. 29 Value
By default, Parameter 29 - [N2 Ref Scale] equals 32,767, which is the maximum Reference value for PowerFlex 70/700 drives. Note that additional scaling is performed in the PowerFlex 70/700 drive, where 32,767 equals the frequency selected in drive Parameter 55 - [Maximum Freq]. For other DPI hosts, refer to the documentation of the specific DPI host product.
Viewing the Logic Status and Feedback
On Metasys N2, there are two ways to view the Logic Status: binary inputs (Table 5.N on page 5-7 can use binary inputs when you need to view only one bit in the Logic Status word. For example, to view whether a PowerFlex 70/700 drive is ready (bit 0), you can use a binary input (BI 1).
When you need to view multi-bit fields in the Logic Status word, to view the entire Logic Status word, or to view the Feedback word, you must use an analog input. For example, to view the local control of a PowerFlex 70/ 700 drive (bits 9…11), you must use an analog input (AI #1). To view the Feedback, you must use an analog input (AI #2 or AI #3).
) and an analog input (Table 5.O on page 5-8). You
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Metasys N2 5-7
Table 5.N shows that there are 16 binary inputs to represent the status word
bit by bit. These inputs can be used only for reading single-bit status.
Table 5.N Logic Status: Binary Inputs (Output from a Drive)
Network Point Type (NPT)
BI 1 0 Ready 0 = Not Ready
BI 2 1 Active 0 = Not Running
BI 3 2 Command
BI 4 3 Actual Direction 0 = Reverse
BI 5 4 Accel 0 = Not Accelerating
BI 6 5 Decel 0 = Not Decelerating
BI 7 6 Alarm 0 = No Alarm
BI 8 7 Fault 0 = No Fault
BI 9 8 At Speed 0 = Not At Reference
BI 10 9 Local Control Network Point Addresses BI 11 10 12 11 10 BI 12 11 0 0 0 = Port 0 (TB)
BI 13 12 Reference BI 14 13 16 15 14 13 BI 15 14 0 0 0 0 = Ref A Auto BI 16 15 0 0 0 1 = Ref B Auto
Network Point Address (NPA)
Logic Status Bit
PowerFlex 70/700 Example Description Values
1 = Ready
1 = Running
Direction
(typically used when commanding drive speed from source other than Metasys)
0 = Reverse 1 = Forward
1 = Forward
1 = Accelerating
1 = Decelerating
1 = Alarm
1 = Fault
1 = At Reference
001= Port 1 010= Port 2 011= Port 3 100= Port 4 101= Port 5 110= Port 6 1 1 1 = No Local Network Point Addresses
0 0 1 0 = Preset 2 Auto 0 0 1 1 = Preset 3 Auto 0 1 0 0 = Preset 4 Auto 0 1 0 1 = Preset 5 Auto 0 1 1 0 = Preset 6 Auto 0 1 1 1 = Preset 7 Auto 1000= Term Blk Manual 1 0 0 1 = DPI 1 Manual 1 0 1 0 = DPI 2 Manual 1 0 1 1 = DPI 3 Manual 1 1 0 0 = DPI 4 Manual 1 1 0 1 = DPI 5 Manual 1 1 1 0 = DPI 6 Manual 1111= Jog Ref
Table 5.O on page 5-8
for reading multi-bit status fields and the Feedback.
shows the analog inputs. These inputs must be used
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
5-8 Using Metasys N2
Table 5.O Logic Status and Feedback: Analog Inputs

Using Metasys Configurable Objects to Access Parameters

Network Point Type (NPT)
AI 1 Product Status
AI 2 Feedback Lo -100.0…100.0%
Configurable objects are inputs and outputs that let you read and write parameter values. These objects handle only 16-bit parameter values.
Reading Parameter Values
The configurable points may show any 16-bit parameter in the drive by configuring the Param# point. The Param# for INx points are stored in the RAM in the adapter and need to be written to only one time per power cycle.
The adapter reads the value of the drive parameter configured in the Param# point and shows the result in the User INx point. The adapter reads the parameter values from the drive continuously one at a time when Param# is set to a non-zero value. See Figure 5.1
Figure 5.1 Configurable Input Point Operation Objects Inputs
Network Point Address (NPA)
Parameter Description Range
16-bit word. Bit definitions for PowerFlex 70/700
Word
drives are in Tab l e 5 . N to their documentation.
and Table 5.P.
. For other products, refer
Controller Drive
Param#
for INx
Request
Response Data
Table 5.P Configurable Objects: Inputs
Network Point Type (NPT)
AI 3 User IN1 User-defined Input 1 0 AI 4 User IN2 User-defined Input 2 0 AI 5 User IN3 User-defined Input 3 0 AI 6 User IN4 User-defined Input 4 0
ADI 1 Param # for IN1 0 (not in use), 1 to maximum # of drive
ADI 2 Param # for IN2 0 (not in use), 1 to maximum # of drive
ADI 3 Param # for IN3 0 (not in use), 1 to maximum # of drive
ADI 4 Param # for IN4 0 (not in use), 1 to maximum # of drive
Network Point Address (NPA) Name Description Default
ADI
AI
parameters
parameters
parameters
parameters
User
INx
0
0
0
0
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Table 5.Q Example of Configurable Objects: Inputs
Using Metasys N2 5-9
Network Point Type (NPT)
AI 3 Output Frequency -400…400 Hz [0.1 Hz] 60.0 AI 4 Output Current 0.0 to Drive Related Amps [0.1 A] 14.0 AI 5 Output Voltage 0.0 to Drive Related Volts [0.1 VAC] 460.0 AI 6 Output Power 0.0 to Drive Related kW [0.1 kW] 7.5
ADI 1 Param # for IN1 Integer # of drive parameter 1 ADI 2 Param # for IN2 Integer # of drive parameter 3 ADI 3 Param # for IN3 Integer # of drive parameter 6 ADI 4 Param # for IN4 Integer # of drive parameter 7
Writing Parameter Values
!
These outputs are written from the adapter each time the User OUT point is written from the network.
Network Point Address (NPA) Name Description Default
ATTENTION: Risk of equipment damage exists. If configurable outputs are programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS. Datalinks do not write to NVS and should be used for frequently changed parameters.
TIP: Analog Data Integers (ADIs) are configured by first selecting an Analog Output (AO) setpoint and then selecting the ADI.
A value of zero in the Param# field disables the writing of data for that specific point. Refer to the drive user manual for the desired parameter number.
Figure 5.2 Configurable Objects: Outputs
Controller Drive
Param#
for OUTx
User
OUTx
Table 5.R Configurable Objects: Outputs
Network Point Type (NPT)
AO 3 User OUT1 User-defined Output 1 0 AO 4 User OUT2 User-defined Output 2 0 ADI 5 Param# for OUT1 0 (not in use), 1 to maximum # of
ADI 6 Param# for OUT2 0 (not in use), 1 to maximum # of
Network Point Address (NPA) Description Range Default
ADI
AO
0
drive parameters
0
drive parameters
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
5-10 Using Metasys N2
Notes:
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 6

Using Siemens Building Technologies P1 FLN

This chapter provides information about controlling a PowerFlex 7-Class drive, setting its Reference, and accessing its parameters through points when the Siemens Building Technologies P1 FLN network protocol is selected.
Topic Page
Understanding Siemens Building Technologies P1 FLN Using the P1 FLN Point Map for I/O 6-5 Using the P1 FLN Point Map to Access Parameters 6-9
TIP: Datalinks can also be used for accessing parameters. For information about using Datalinks, refer to Chapter 7
Protocols.
6-1
, Using Datalinks with All

Understanding Siemens Building Technologies P1 FLN

ATTENTION: Risk of injury or equipment damage exists. On P1 FLN networks, 16-bit values are truncated to 15-bit values.
!
Unpredictable operation may result from using non-15-bit drive parameters with the configurable points. Recognize the data range limitation of P1 FLN and understand the data value ranges of each parameter to be accessed over the network. Refer to the drive user manual for information about drive parameter sizes.
P1 FLN nodes are built by the use of several points. The P1 FLN master controller performs read and write commands to these points, and the adapter transfers/translates the data between these points and the drive.
All values (byte-sized, Boolean, and true integers) are represented in a 16-bit word over the network, where the sign bit is always positive. The actual range allowed by P1 FLN, however, is always 15 bits: 0…32767 for integers, 0…255 for bytes, and 0 or 1 for Boolean. The limit of 15 bits prevents the use of the adapter’s P1 FLN mode with 32-bit DPI hosts, where either Reference/Feedback or Datalink values are represented in 32-bit format. 16-bit real values will be truncated to show only 15-bit values.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
6-2 Using Siemens Building Technologies P1 FLN
P1 FLN Point Types
Logic analog and digital I/O points are used for controlling the drive, monitoring status, and reading/writing parameters. Table 6.A point types.
Table 6.A Point Types
Abbreviation Name Used for
LDI Logical Digital Inputs Reading bit level points (0 or 1) such as drive status. For
LDO Logical Digital Outputs Writing bit-level points (0 or 1) such as drive commands. For
LAI Logical Analog Inputs Reading word-level points such as FREQ OUTPUT (Point
LAO Logical Analog Outputs Writing word-level points such as REFERENCE (Point 92)
Some points can be unbundled. Unbundle means that you can characterize the subpoint so that three additional items can be enabled for that specific subpoint:
shows the four
example, FWD.REV MON (point 21) provides the status of the rotation direction of the drive.
example, CMD RUN.STOP (Point 24) commands the drive to run.
03) and CURRENT (Point 06).
and acceleration (Point 31).
The subpoint can be monitored for COV (Change of Value). All
unbundled points are reported for any change of value when a “Scan for COV” command is issued. (Analog points may have COV limits defined to reduce network traffic.)
The subpoint can be overridden by the operator.
Unbundling a point allows the operator to set up a virtual point in the
controller's database, which when commanded, can also affect the subpoints in the device.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Siemens Building Technologies P1 FLN 6-3
Siemens Building Technologies P1 FLN Point Map
Description
(4)
momentary Stop command to the drive.
0 – 255 No Current limit of the drive. Min value 0.9; max value 6.0
(3)
value 3276.7
value 3276.7
0 – 32767 No Acceleration time of the drive. Min value 0.1; max
0 – 32767 No Deceleration time of the drive. Min value 0.1; max
(3)
(3)
English
Point
Point
Table 6.B Siemens Building Technologies P1 FLN Point List
Units Slope Intercept ON Text OFF Text Default Range COV
Descriptor
(2)
Type
(1)
Number
01 LAO CTRL ADDRESS 1 0 99 0 – 255 No Node address of this device.
02 LAO APPLICATION 1 0 2718 0 – 32767 No Firmware application number.
{03} LAI FREQ OUTPUT HZ 0.01 -163.83 0 0 – 32767 Yes Drive speed in frequency (Hertz).
{04} LAI PCT OUTPUT PCT 0.1 0 0 0 – 32767 Yes Drive speed in percentage of max.
{05} LAI SPEED RPM 1 0 0 0 – 32767 Yes Drive speed in RPM.
{06} LAI CURRENT AMPS 0.1 0 0 0 – 32767 Yes Drive current consumption in amps.
{07} LAI TORQUE PCT 0.1 -1638.3 0 0 – 32767 Yes Drive torque in percentage of max.
{08} LAI POWER KW 0.1 0 0 0 – 32767 Yes Drive power in kW.
{09} LAI DRIVE TEMP DEG C 0.1 -1638.3 0 0 – 32767 Yes Drive temperature in degree C.
{11} LAI DRIVE MWH MWH 0.1 0 0 0 – 32767 Yes Drive total power consumption in MWH.
{12} LAI RUN TIME HRS 0.1 0 0 0 – 32767 Yes Drive total run time in hours.
{13} LAI DC BUS VOLT VOLTS 0.1 0 0 0 – 32767 Yes Drive DC bus voltage.
{20} LAO OVRD TIME 1 0 0 0 – 255 Yes Not used by this application.
{21} LDI FWD.REV MON 1 0 REV FWD 0 (FWD) 0 – 1 Yes Monitor the rotation direction of the drive.
{22} LDO CMD FWD.REV 1 0 REV FWD 0 (FWD) 0 – 1 Yes Command the rotation direction of the drive.
{23} LDI RUN.STOP MON 1 0 RUN STOP 0 (STOP) 0 – 1 Yes Monitor the Run/Stop status of the drive.
{24} LDO CMD RUN.STOP 1 0 RUN STOP 0 (NO) 0 – 1 Yes Command Run to the drive. A STOP issues a
{25} LDI READY 1 0 READY NOTRDY 0 (NOTRDY) 0 – 1 Yes Monitor the Ready status of the drive.
{26} LDO RUN ENABLE 1 0 ENABLE STOP 0 (NO) 0 – 1 Yes Must be set to ENABLE to allow controlling the drive.
{29} LDO DAY.NGT 1 0 NIGHT DAY 0 (DAY) 0 – 1 Yes Not used by this application.
{30} LAO CURRNT LIMIT 0.1 0
{31} LAO ACCEL TIME 0.1 0
{32} LAO DECEL TIME 0.1 0
36 LAO PARAM IN 1 0 0 0 – 32767 No Parameter number to User In point.
{37} LAI USER IN 1 0 0 0 – 32767 Yes User-defined input.
38 LAO PARAM OUT 1 0 0 0 – 32767 No Parameter number to USER IN point.
39 LAO USER OUT 1 0 0 0 – 32767 No User-defined output.
{44} LAI DLNK A1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out A1.
For a description of point types, refer to Table 6.A on page 6-2. Note that the outputs and inputs are from the network perspective, not the drive perspective. For example, an LAO is an output from the controller on
(1)
(2)
COV indicates whether the points is able to support COVs and overrides.
Depends on DPI Host product connected to (PowerFlex 70, etc.) and HP size.
(4)
(3)
the network, but it is an input to the drive.
Points not listed are not used in this application. Point numbers that appear in braces { } may be unbundled.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
6-4 Using Siemens Building Technologies P1 FLN
Description
(3)
Will return to NORMAL (0) automatically.
English
Units Slope Intercept ON Text OFF Text Default Range COV
Descriptor
(2)
Point
Type
(1)
Point
Number
{46} LAI DLNK A2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out A2.
{48} LAI DLNK B1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out B1.
{50} LAI DLNK B2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out B2.
Table 6.B Siemens Building Technologies P1 FLN Point List (Continued)
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
{52} LAI DLNK C1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out C1.
{54} LAI DLNK C2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out C2.
{56} LAI DLNK D1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out D1.
the network, but it is an input to the drive.
Points not listed are not used in this application. Point numbers that appear in braces { } may be unbundled.
For a description of point types, refer to Table 6.A on page 6-2. Note that the outputs and inputs are from the network perspective, not the drive perspective. For example, an LAO is an output from the controller on
{58} LAI DLNK D2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out D2.
{60} LAI INPUT REF 1 0.001 -16.383 0 0 – 32767 Yes Shows the Input Reference 1 parameter.
{61} LAI INPUT REF 2 0.001 -16.383 0 0 – 32767 Yes Shows the Input Reference 2 parameter.
{62} LAO DLNK A1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In A1.
{64} LAO DLNK A2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In A2
{66} LAO DLNK B1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In B1.
{68} LAO DLNK B2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In B2.
{70} LAO DLNK C1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In C1.
{72} LAO DLNK C2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In C2.
{74} LAO DLNK D1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In D1.
{76} LAO DLNK D2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In D2.
{89} LAO LOGIC CMD LO 1 0 0 0 – 255 Yes Lower 8 bits of Product Logic Command Word.
{90} LAO LOGIC CMD HI 1 0 0 0 – 255 Yes Higher 8 bits of Product Logic Command Word.
{91} LAI FEEDBACK 1 0 0 0 – 32767 Yes Feedback value bits 0-14 (absolute value).
{92} LAO REFERENCE 1 0 0 0 – 32767 Yes Reference value bits 0-14.
{93} LDI OK.FAULT 1 0 FAULT OK 0 (OK) 0 – 1 Yes Shows if the drive is faulted or not.
{94} LDO RESET FAULT 1 0 RESET NORMAL 0 (NORMAL) 0 – 1 Yes Resets the fault condition in the drive. Special point.
{95} LAI LOGIC STS LO 1 0 0 0 – 255 Yes Lower 8 bits of Product Logic Status Word.
{96} LAI LOGIC STS HI 1 0 0 0 – 255 Yes Higher 8 bits of Product Logic Status Word.
{99} LAO ERROR STATUS 1 0 0 0 – 255 Yes Not used by this application.
(1)
COV indicates whether the points is able to support COVs and overrides.
(2)
(3)
Using Siemens Building Technologies P1 FLN 6-5

Using the P1 FLN Point Map for I/O

On Siemens Building Technologies P1 FLN, data transfers are used to transfer the I/O data that controls the drive and sets its Reference. Note that
Output I/O is data that the master device sends and the adapter receives. Input I/O is status data that the adapter sends and the master device receives.
Important:In order for the drive to use the I/O and Reference from the P1
FLN network, you must set parameters in it and the adapter to receive the I/O and Reference. For details, refer to
Setting the I/O Configuration
Setting the Logic Command and Reference
ATTENTION: Select and use either the point type Digital (LDO) or the word type Analog (LAO) as a control method, but
!
not both. Conflicts caused from using both methods can result in
dangerous operation. Failure to observe this precaution could cause bodily injury and/or damage to equipment.
On Siemens Building Technologies P1 FLN, there are two ways to control a drive and set its Reference.
The more common way uses points such as CMD RUN.STOP (point 24)
and RUN ENABLE (point 26). Refer to Table 6.B on page 6-3 of points. For example, to start a PowerFlex 70/700 drive, you can set CMD RUN.STOP (point 24) to “RUN.” To stop it, you can set CMD RUN.STOP (point 24) to “STOP” or RUN ENABLE (point 26) to “STOP.”
on page 3-5.
for a list
ATTENTION: LOGIC CMD LO (point 89) must be written prior to LOGIC CMD HI (point 90) to maintain data integrity of
!
the Logic Command word. Failure to observe this precaution could result in bodily injury and/or damage to equipment.
The second way uses LOGIC CMD HI (point 90) and LOGIC CMD LO
(point 89). The LOGIC CMD LO and LOGIC CMD HI points are both 8-bit points. The adapter joins these two words together to make a 16-bit command word. Refer to Appendix for definitions of the bits in the command word. The command word in the adapter’s buffer is updated with the content of LOGIC CMD LO and LOGIC CMD HI points. It is transferred to the drive when LOGIC CMD HI is written. Therefore, to maintain data integrity of the command word, LOGIC CMD LO must be written prior to writing LOGIC CMD HI. For example, to start a PowerFlex 70/700 drive, you can write a value of “2” to LOGIC CMD LO and a value of “0” to LOGIC CMD HI. To stop it, you can write a value of “1” to LOGIC CMD LO and a value of “0” to LOGIC CMD HI.
The Reference value is a 16-bit value in the drive but will only use 15 bits due to the P1 FLN protocol limitation. You can send the reference using REFERENCE (point 92). Remember that the Reference value is a scaled
C, Logic Command/Status Words,
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
6-6 Using Siemens Building Technologies P1 FLN
engineering value. For example, in PowerFlex 70/700 drives, the Reference is scaled based on the value of Parameter 55 - [Maximum Freq], but the commanded maximum speed can never exceed the value of Parameter 82 - [Maximum Speed]. Table 6 .C on a PowerFlex 70/700 drive that has its Parameters 55 - [Maximum Freq] set to 130 Hz and 82 - [Maximum Speed] set to 60 Hz.
Table 6.C Example Speed Reference and Feedback for a PowerFlex 70/700
Reference Value
32767 100% 130 Hz 60 Hz 16384 50% 65 Hz 60 Hz 8192 25% 32.5 Hz 32.5 Hz 8192 0 0% 0 Hz 0 Hz 0
(1)
The drive runs at 60 Hz instead of 130 Hz because Parameter 82 - [Maximum Speed] sets 60 Hz as the maximum speed.
(2)
The Feedback value is also scaled based on the value of Parameter 55 - [Maximum Freq]. For example, 60/130 = 0.46 so 32767 x 0.46 = 15123.
Scale
shows example References and their results
Output Speed
(1)
(1)
Feedback ValuePercent Value
(2)
15123 15123
Table 6.D
shows the commands that you can execute on a PowerFlex 70/
700 drive and the point(s) that you can use to execute them.
Table 6.D Logic Commands
PowerFlex 70/700 Example
Point Number(s) Point
24 CMD RUN.STOP 0 Stop 26 RUN ENABLE 89 LOGIC CMD LO bit 0 24 CMD RUN.STOP 1 Start 89 LOGIC CMD LO bit 0 89 LOGIC CMD LO bit 2 2 Jog 0 = Not Jog
94 RESET FAULTS 3 Clear 89 LOGIC CMD LO bit 3 22 CMD FWD.REV 4 and 5 Direction Bits 89 LOGIC CMD LO
bits 4, 5
89 LOGIC CMD LO bit 6 6 Local
89 LOGIC CMD LO bit 7 7 MOP
90 LOGIC CMD HI
bits 0, 1
90 LOGIC CMD HI
bits 3, 2
Logic Command Bit
8 and 9 Accel Rate LOGIC CMD HI Bits
10 and 11 Decel Rate LOGIC CMD HI Bits
Descriptio nValues
(1)
(1) (2)
(2)
Faults
Control
Increment
0 = Not Stop
(3)
1 = Stop
0 = Not Start 1 = Start
1 = Jog 0 = Not Clear Faults 1 = Clear Faults
05 04 0 0 = No Command 0 1 = Forward Command 1 0 = Reverse Command 1 1 = Hold Direction Control 0 = No Local Control
1 = Local Control 0 = Not Increment 1 = Increment
01 00 0 0 = No Command 0 1 = Accel Rate 1 1 0 = Accel Rate 2 1 1 = Hold Accel Rate
03 02 0 0 = No Command 0 1 = Decel Rate 1 1 0 = Decel Rate 2 1 1 = Hold Decel Rate
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Siemens Building Technologies P1 FLN 6-7
Table 6.D Logic Commands (Continued)
PowerFlex 70/700 Example Point Number(s) Point
90 LOGIC CMD HI bits
6, 5, 4
90 LOGIC CMD HI
(1)
A 0 = Not Stop condition (Logic Command bit 0) must first be present before a 1 = Start condition will start the drive.
(2)
To perform this command, the value must change from “0” to “1.”
(3)
Setting CMD RUN.STOP to STOP issues a momentary Stop command to the drive. Logic Command Bit 0 is momentarily set to 1 (STOP) to initiate a Stop and then set to 0 (Not Stop).
bit 7
Logic Command Bit
12, 13, and 14 Reference
15 MOP
Descriptio
nValues
Select
Decrement
Bits 06 05 04 000= No Command 001= Ref 1 (Ref A Select) 010= Ref 2 (Ref B Select) 011= Ref 3 (Preset 3) 100= Ref 4 (Preset 4) 101= Ref 5 (Preset 5) 110= Ref 6 (Preset 6) 111= Ref 7 (Preset 7) 0 = Not Decrement
1 = Decrement
The P1 FLN point map provides points to execute other commands on an adapter or drive. These points include CTRL ADDRESS (point 01), CURRENT LIMIT (point 30), ACCEL TIME (point 31), and DECEL TIME (point 32). Refer to Table 6.E on page 6-8 various points.
Viewing the Logic Status and Feedback
There are two ways to determine drive status:
The more common way uses points such as RUN.STOP MON (point 23)
and FWD.REV MON (point 21) that represent individual bits in the Logic Status word. Refer to Table 6.B on page 6-3 example, to view if a PowerFlex 70/700 drive is running, you can read RUN.STOP MON (point 23) to see if it is “RUN” or “STOP.” To view its direction, you can read FWD.REV MON (point 21) to see if it is “FWD” or “REV.”
The second way uses LOGIC STS LO (point 95) and LOGIC STS HI
(point 96). The LOGIC STS LO and LOGIC STS HI are both 8-bit points that the adapter can use to report its 16-bit status word. Refer to
Appendix
the status word. Since LOGIC STS LO gets updated only when LOGIC STS HI is read, you must read LOGIC STS HI prior to reading LOGIC STS LO to maintain the data integrity of the status word. For example, to view if a PowerFlex 70/700 drive is running, you can read LOGIC STS HI and LOGIC STS LO and determine if bit 1 is “0” (Not Running) or “1” (Running). To view its direction, you can read LOGIC STS LO and LOGIC STS HI and determine if bit 3 is “0” (Reverse) or “1” (Forward).
C, Logic Command/Status Words, for definitions of the bits in
for a description of the
for a list of points. For
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
6-8 Using Siemens Building Technologies P1 FLN
The Feedback can also be viewed in two ways:
FREQ OUTPUT (point 03), PCT OUTPUT (point 04), and SPEED
(point 05) report the feedback in values such as Hz, percent of maximum speed, and RPM, respectively.
FEEDBACK (point 91) reports the feedback as a scaled value. For an
explanation of how the Reference/Feedback is scaled, refer to the Setting
the Logic Command and Reference on page 6-5.
Table 6.E
and the points that you can use to view them.
Table 6.E Logic Status
Point Number(s) Point Name
25 READY 0 Ready 0 = Not Ready 95 LOGIC STS LO bit 0 23 RUN.STOP MON 1 Active 0 = Not Running 95 LOGIC STS LO bit 1 95 LOGIC STS LO bit 2 2 Command
21 FWD.REV MON 3 Actual 95 LOGIC STS LO bit 3 95 LOGIC STS LO bit 4 4 Accel 0 = Not Accelerating
95 LOGIC STS LO bit 5 5 Decel 0 = Not Decelerating
95 LOGIC STS LO bit 6 6 Alarm 0 = No Alarm
93 OK.FAULT 7 Fault 0 = No Fault 95 LOGIC STS LO bit 7 96 LOGIC STS HI bit 0 8 At Speed 0 = Not At Reference
96 LOGIC STS HI
shows the status that you can view on a PowerFlex 70/700 drive
PowerFlex 70/700 Example
Logic Status Bit
9, 10, and 11 Local
bits 3, 2, 1
Descriptio n Values
1 = Ready
1 = Running
0 = Reverse
Direction
Direction
Control
1 = Forward 0 = Reverse
1 = Forward
1 = Accelerating
1 = Decelerating
1 = Alarm
1 = Fault
1 = At Reference LOGIC STS HI Bits 03 02 01 000= Port 0 (TB) 001= Port 1 010= Port 2 011= Port 3 100= Port 4 101= Port 5 110= Port 6 111= No Local
(1)
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Siemens Building Technologies P1 FLN 6-9
Table 6.E Logic Status (Continued)
PowerFlex 70/700 Example
Point Number(s) Point Name
96 LOGIC STS HI
bits 7, 6, 5, 4
(1)
The values in this column are for LOGIC STS LO (point 95) and LOGIC STS HI (point 96). For details about other point values, refer to Table 6.B on page 6-3
Logic Status Bit
12, 13, 14, and 15
Descriptio n Values
Reference LOGIC STS HI Bits
07 06 05 04 0000= Ref A Auto 0001= Ref B Auto 0010= Preset 2 Auto 0011= Preset 3 Auto 0100= Preset 4 Auto 0101= Preset 5 Auto 0110= Preset 6 Auto 0111= Preset 7 Auto 1000= Term Blk Manual 1001= DPI 1 Manual 1010= DPI 2 Manual 1011= DPI 3 Manual 1100= DPI 4 Manual 1101= DPI 5 Manual 1110= DPI 6 Manual 1111= Jog Ref
.
(1)

Using the P1 FLN Point Map to Access Parameters

The P1 FLN point map provides points to monitor a number of other features in the drive. These points include CURRENT (point 06), TORQUE (point 07), and POWER (point 08). Refer to Table 6.E the various points.
Drive parameters can be accessed using Configurable Points or Datalinks (Chapter 7
Reading Parameter Values
Configurable points USER IN (point 37) and PARAM IN (point 36) are points that enable any parameter in the drive to be monitored. The USER IN shows only 15-bit values; therefore, only 16-bit drive parameters can be used (however, only values between 0…32767 would be used).
The PARAM IN is used to configure which parameter is to be monitored, and the value ends up in the USER IN. For example, for a PowerFlex 70 or 700 drive, writing the value of “1” into PARAM IN point (reading drive parameter 1) would provide the Output Frequency in USER IN point.
, Using Datalinks with All Protocols).
for a description of
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
6-10 Using Siemens Building Technologies P1 FLN
Writing Parameter Values
!
Configurable Points USER OUT (point 39) and PARAM OUT (point 38) are points that enable write access to any parameter in the drive. However, due to the 15-bit limitation, only 16-bit drive parameters should be accessed.
For example, for a PowerFlex 70/700 drive, writing a value of “140” in PARAM OUT (writing drive parameter 140) and the value of “200” in USER OUT would set drive Parameter 140 - [Accel Time 1] to 20.0 seconds.
ATTENTION: Risk of equipment damage exists. If configurable points are programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable points to write parameter data to NVS. Datalinks do not write to NVS and should be used for frequently changed parameters.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 7

Using Datalinks with All Protocols

This chapter provides information and examples showing how to use Datalinks.
Topic Page
Using Datalinks Using Datalinks with Modbus 7-3 Using Datalinks with Metasys N2 7-4 Using Datalinks with Siemens P1 FLN 7-5
7-1

Using Datalinks

A Datalink is a mechanism used by PowerFlex drives to transfer data to and from the controller. Datalinks “point” to specific drive parameters to be accessed. When enabled, each Datalink occupies two 16-bit or two 32-bit words in both the input and output image. Adapter Parameter 19 - [Datalink Size] indicates whether the drive uses 16-bit or 32-bit words for Datalinks.
Rules for Using Datalinks
Each set of Datalink parameters in a PowerFlex drive can be used by
only one adapter. If more than one adapter is connected to a single drive, multiple adapters must not try to use the same Datalink.
Parameter settings in the drive determine the data passed through the
Datalink mechanism. Refer to the documentation for your drive.
When you use a Datalink to change a value, the value is NOT written to
the Non-Volatile Storage (NVS). The value is stored in volatile memory and lost when the drive loses power. Thus, use Datalinks when you need to change a value of a parameter frequently.
32-Bit Parameters using 16-Bit Datalinks
This subsection only pertains to PowerFlex 70 (SC or EC), PowerFlex 700 (SC), and PowerFlex 700H drives which use 16-bit Datalinks. To read (and/ or write) a 32-bit parameter using 16-bit Datalinks, typically both Datalinks of a pair (A, B, C, D) are set to the same 32-bit parameter. For example, to read Parameter 10 - [Elapsed Run Time] in a PowerFlex 70 drive, both Datalink A1 Out and Datalink A2 Out are set to “10.” Datalink A1 Out will contain the least significant word (LSW) and Datalink A2 Out will contain the most significant word (MSW).
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
7-2 Using Datalinks with All Protocols
32-bit data is stored in binary as follows:
MSW 231 through 2 LSW 215 through 2
In this example, the Parameter 10 - [Elapsed Run Time] value of 6553.9 Hrs is read as “6553.9” in Datalink A1 Out and Datalink A2 Out.
Datalink Word Parameter Data (Hex)
A1 Out LSW 10 0003 A2 Out MSW 10 0001
Conversion Example:
Parameter 010 - [Elapsed Run Time] = 6553.9 Hrs MSW = 0001 LSW = 0003 Engineering Value = 65536 + 3 = 65539 Parameter 10 Displayed Value = 6553.9 Hrs
Regardless of the Datalink combination, Datalink x1 Out will always contain the LSW and Datalink x2 Out will always contain the MSW. In the following example, the PowerFlex 70 drive Parameter 242 - [Power Up Marker] contains a value of 88.4541 hours.
Datalink Word Parameter Data (Hex)
A2 Out MSW 242 000D B1 Out LSW 242 7F3D
hex
hex
= 0001
=3
16
0
= 216 = 65536
binary
Conversion Example:
Parameter 242 - [Power Up Marker] = 88.4541 hours MSW = 000D LSW = 7F3D Engineering Value = 851968 + 32573 = 884541 Parameter 242 Displayed Value = 88.4541 Hrs
Configuring Datalinks
Configuring Datalinks from the drive side is a two-step process:
1. Configure the datalink parameters in the drive. For example, in a PowerFlex 70 or 700 drive, set Parameters 300 - [Data In A1] to 317 - [Data Out D2] to “point” to the parameters to be accessed. For instance, to read drive Parameter 1 - [Output Freq], set Parameter
310 - [Data Out A1] to “1.”
2. Enable the desired Datalinks in Parameter 16 - [DPI I/O Cfg] in the
adapter. This tells the adapter to transfer Datalink data to and from the drive. For example, to enable Datalink A1, set bit 1 to “1.” For details, refer to Setting the I/O Configuration
= 1101
hex
= 32573
hex
= 219 + 218 + 216 = 851968
binary
on page 3-5.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Using Datalinks with All Protocols 7-3

Using Datalinks with Modbus

This section presents information about using Datalinks with Modbus networks. For information about using Datalinks for Metasys N2 networks or Siemens P1 FLN networks, refer to the Using Datalinks with Metasys N2 or Using Datalinks with Siemens P1 FLN
sections in this chapter.
Modbus Datalinks Out: A…D
Table 7.A Modbus Datalinks Out - A1, A2
Modbus Address Data Direction
3x0012 Register Input Datalink A1 Out Not used LSW of 32-bit
(1)
3x0013 3x0014 Register Input Datalink A2 Out 3x0015
(1)
A read access to address 3x0013 initiates a refresh of Datalink A1 value before reading.
(2)
A read access to address 3x0015 initiates a refresh of Datalink A2 value before reading.
Table 7.B Modbus Datalinks Out - B1, B2
Modbus Address Data Direction
3x0016 Register Input Datalink B1 Out 3x0017 3x0018 Register Input Datalink B2 Out 3x0019
(1)
A read access to address 3x0017 initiates a refresh of Datalink B1 value before reading.
(2)
A read access to address 3x0019 initiates a refresh of Datalink B2 value before reading.
Register Input Datalink A1 Out 16-bit value MSW of 32-bit
(2)
Register Input Datalink A2 Out 16-bit value MSW of 32-bit
(1)
Register Input Datalink B1 Out 16-bit value MSW of 32-bit
(2)
Register Input Datalink B2 Out 16-bit value MSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit
Not used LSW of 32-bit
Table 7.C Modbus Datalinks Out - C1, C2
Modbus Address Data Direction
3x0020 Register Input Datalink C1 Out
(1)
3x0021 3x0022 Register Input Datalink C2 Out 3x0023
(1)
A read access to address 3x0021 initiates a refresh of Datalink C1 value before reading.
(2)
A read access to address 3x0023 initiates a refresh of Datalink C2 value before reading.
Table 7.D Modbus Datalinks Out - D1, D2
Modbus Address Data Direction
3x0024 Register Input Datalink D1 Out 3x0025 3x0026 Register Input Datalink D2 Out 3x0027
(1)
A read access to address 3x0025 initiates a refresh of Datalink D1 value before reading.
(2)
A read access to address 3x0027 initiates a refresh of Datalink D2 value before reading.
Register Input Datalink C1 Out 16-bit value MSW of 32-bit
(2)
Register Input Datalink C2 Out 16-bit value MSW of 32-bit
(1)
Register Input Datalink D1 Out 16-bit value MSW of 32-bit
(2)
Register Input Datalink D2 Out 16-bit value MSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit
Not used LSW of 32-bit
Not used LSW of 32-bit
Not used LSW of 32-bit
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
7-4 Using Datalinks with All Protocols
Modbus Datalinks In: A…D
Table 7.E Modbus Datalinks In - A1, A2
Modbus Address Data Direction
4x0018 Register Output Datalink A1 In
(1)
4x0019 4x0020 Register Output Datalink A2 In 4x0021
(1)
A write access to address 4x0019 initiates an update of the Datalink A1 field in the DPI I/O image.
(2)
A write access to address 4x0021 initiates an update of the Datalink A2 field in the DPI I/O image.
Table 7.F Modbus Datalinks In - B1, B2
Modbus Address Data Direction
4x0022 Register Output Datalink B1 In Not used LSW of 32-bit 4x0023 4x0024 Register Output Datalink B2 In 4x0025
(1)
A write access to address 4x0023 initiates an update of the Datalink B1 field in the DPI I/O image.
(2)
A write access to address 4x0025 initiates an update of the Datalink B2 field in the DPI I/O image.
Table 7.G Modbus Datalinks In - C1, C2
Modbus Address Data Direction
4x0026 Register Output Datalink C1 In Not used LSW of 32-bit 4x0027 4x0028 Register Output Datalink C2 In 4x0029
(1)
A write access to address 4x0027 initiates an update of the Datalink C1 field in the DPI I/O image.
(2)
A write access to address 4x0029 initiates an update of the Datalink C2 field in the DPI I/O image.
Register Output Datalink A1 In 16-bit value MSW of 32-bit
(2)
Register Output Datalink A2 In 16-bit value MSW of 32-bit
(1)
Register Output Datalink B1 In 16-bit value MSW of 32-bit
(2)
Register Output Datalink B2 In 16-bit value MSW of 32-bit
(1)
Register Output Datalink C1 In 16-bit value MSW of 32-bit
(2)
Register Output Datalink C2 In 16-bit value MSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit
Not used LSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit

Using Datalinks with Metasys N2

20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Table 7.H Modbus Datalinks In - D1, D2
Modbus Address Data Direction
4x0030 Register Output Datalink D1 In
(1)
4x0031 4x0032 Register Output Datalink D2 In 4x0033
(1)
A write access to address 4x0031 initiates an update of the Datalink D1 field in the DPI I/O image.
(2)
A write access to address 4x0033 initiates an update of the Datalink D2 field in the DPI I/O image.
Register Output Datalink D1 In 16-bit value MSW of 32-bit
(2)
Register Output Datalink D2 In 16-bit value MSW of 32-bit
Parameter Description 16-Bit Datalink 32-Bit Datalink
Not used LSW of 32-bit
Not used LSW of 32-bit
This section presents information about using Datalinks with Metasys N2 networks. For information about using Datalinks for Modbus networks or Siemens P1 FLN networks, refer to the Using Datalinks with Modbus
Using Datalinks with Siemens P1 FLN
sections in this chapter.
and
Using Datalinks with All Protocols 7-5
Metasys N2 Datalinks Out: A and B (No Datalinks C and D)
Table 7.I Metasys N2 Datalinks Out - A1, A2
Network Point Type (NPT)
AI 7 Input Datalink A1 Out 16-bit
AI 8 Input Datalink A2 Out 16-bit
Table 7.J Metasys N2 Datalinks Out - B1, B2
Network Point Type (NPT)
AI 9 Input Datalink B1 Out 16-bit
AI 10 Input Datalink B2 Out 16-bit
Network Point Address (NPA) Direction
Network Point Address (NPA) Direction
Parameter Description
Parameter Description
16-Bit Datalink 32-Bit Datalink
Limited to
value
value
16-Bit Datalink 32-Bit Datalink
value
value
-16,777,215…16,777,215 Limited to
-16,777,215…16,777,215
Limited to
-16,777,215…16,777,215 Limited to
-16,777,215…16,777,215
Metasys N2 Datalinks In: A and B (No Datalinks C and D)
Table 7.K Metasys N2 Datalinks In - A1, A2
Network Point Type (NPT)
AO 5 Output Datalink A1 In 16-bit
AO 6 Output Datalink A2 In 16-bit
Network Point Address (NPA) Direction
Parameter Description
16-Bit Datalink 32-Bit Datalink
Limited to
value
value
-16,777,215…16,777,215 Limited to
-16,777,215…16,777,215

Using Datalinks with Siemens P1 FLN

Table 7.L Metasys N2 Datalinks In - B1, B2
Network Point Type (NPT)
AO 7 Output Datalink B1 In 16-bit
AO 8 Output Datalink B2 In 16-bit
This section presents information about using Datalinks with Siemens P1 FLN networks. For information about using Datalinks for Modbus networks or Metasys N2 networks, refer to the Using Datalinks with Modbus
Using Datalinks with Metasys N2
DLNK A1 OUT to DLNK D2 OUT contain the Datalink Out A1 to D2 parameters from the drive. DLNK A1 IN to DLNK D2 IN contain the Datalink In A1 to D2 parameter values to the drive.
For example, a PowerFlex 70 or 700 drive enabling Datalink A for the adapter and configuring drive Parameter 310 - [Data Out A1] to “1” will provide drive Parameter 1 - [Output Frequency] at the DLNK A1 OUT point. Configuring Parameter 300 - [Data In A1] to “140” in the drive will transfer the value of the DLNK A1 IN point value to drive Parameter 140 - [Accel Time 1] when accessed.
Network Point Address (NPA) Direction
Parameter Description
sections in this chapter.
16-Bit Datalink 32-Bit Datalink
value
value
Limited to
-16,777,215…16,777,215 Limited to
-16,777,215…16,777,215
or
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
7-6 Using Datalinks with All Protocols
Note that certain drives may utilize 32-bit datalinks. In this case, Datalinks are not supported by the adapter. The adapter will support only 15-bit Datalink values.
ATTENTION: Risk of injury or equipment damage exists. On P1 FLN networks, 16-bit values are truncated to 15-bit values.
!
Unpredictable operation may result from using non-16-bit drive parameters with the configurable points. Recognize the data range limitation of P1 FLN and understand the data value ranges of each parameter to be accessed over the network. Refer to the drive user manual for information about drive parameter sizes.
Siemens P1 FLN Datalinks Out: A…D
P1 FLN devices work only with 15-bit integer values; therefore, these points only show 15-bit values. If an adapter is connected to a host using 32-bit Datalinks, the adapter will be prevented from using Datalinks. The DPI host determines if 16- or 32-bit Datalink values are used.
Table 7.M Siemens P1 FLN Datalinks Out: A…D
Point Number
{44} LAI DLINK A1 OUT 0 Bit 0…14 of Datalink Out A1 {46} LAI DLINK A2 OUT 0 Bit 0…14 of Datalink Out A2 {48} LAI DLINK B1 OUT 0 Bit 0…14 of Datalink Out B1 {50} LAI DLNK B2 OUT 0 Bit 0…14 of Datalink Out B2 {52} LAI DLNK C1 OUT 0 Bit 0…14 of Datalink Out C1 {54} LAI DLNK C2 OUT 0 Bit 0…14 of Datalink Out C2 {56} LAI DLNK D1 OUT 0 Bit 0…14 of Datalink Out D1 {58} LAI DLNK D2 OUT 0 Bit 0…14 of Datalink Out D2
(1)
Point numbers that appear in braces { } may be unbundled at the field panel.
Siemens P1 FLN Datalinks In: A…D
P1 FLN devices work only with 15-bit integer values; therefore, these points only show 15-bit values. If an adapter is connected to a host using 32-bit Datalinks, the adapter will be prevented from using Datalinks. The DPI host determines if 16- or 32-bit Datalink values are used.
Table 7.N Siemens P1 FLN Datalinks In: A…D
Point Number
{62} LAO DLNK A1 IN 0 Bits 0…14 of Datalink In A1 {64} LAO DLNK A2 IN 0 Bits 0…14 of Datalink In A2 {66} LAO DLNK B1 IN 0 Bits 0…14 of Datalink In B1 {68} LAO DLNK B2 IN 0 Bits 0…14 of Datalink In B2 {70} LAO DLNK C1 IN 0 Bits 0…14 of Datalink In C1 {72} LAO DLNK C2 IN 0 Bits 0…14 of Datalink In C2 {74} LAO DLNK D1 IN 0 Bits 0…14 of Datalink In D1 {76} LAO DLNK D2 IN 0 Bits 0…14 of Datalink In D2
(1)
Point numbers that appear in braces { } may be unbundled at the field panel.
Point
(1)
Type Descriptor
Point
(1)
Type Descriptor
Factory Default Description
Factory Default Description
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Chapter 8

Troubleshooting

This chapter provides information for diagnosing and troubleshooting potential problems with the adapter and network.
Topic Page
Understanding the Status Indicators PORT Status Indicator 8-2 MOD Status Indicator 8-2 NET A Status Indicator 8-3 NET B Status Indicator 8-3 Viewing Adapter Diagnostic Items 8-4 Viewing and Clearing Events 8-6
8-1

Understanding the Status Indicators

The adapter has four status indicators. They can be viewed on the adapter or through the drive cover. See Figure 8.1
Figure 8.1 Status Indicators (location on drive may vary)
➊ ➋
➊ ➋ ➌ ➍
.
Item Status Indicator Description Page
PORT DPI Connection Status 8-2
MOD Adapter Status 8-2
NET A Serial Communication Status 8-3
NET B Serial Communication Traffic Status 8-3
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
8-2 Troubleshooting

PORT Status Indicator

Status Cause Corrective Action
Off The adapter is not powered or is not properly
connected to the drive.
Flashing Red The adapter is not receiving a ping message from
the drive.
Steady Red The drive has refused an I/O connection from the
adapter.
Another DPI peripheral is using the same DPI port as the adapter.
Steady Orange The adapter is connected to a product that does not
support Rockwell Automation DPI communications.
A connection to a host with a 32-bit reference or 32-bit Datalinks is detected when the peripheral has been configured to use the P1 FLN protocol. The peripheral doesn’t support 32-bit devices when using the P1 FLN network protocol.
Flashing Green The adapter is establishing an I/O connection to the
drive or I/O has been disabled.
Steady Green The adapter is properly connected and is
communicating with the drive.
This red/green bicolor LED indicates the status of the adapter’s DPI connection to the drive as shown in the table below.
Securely connect the adapter to the drive using the Internal
Apply power to the drive.
Verify that cables are securely connected and not damaged.
Cycle power to the drive.
Important: Cycle power to the drive after making any of the following corrections:
Verify that all DPI cables on the drive are securely connected and
Verify that the DPI drive supports Datalinks.
Configure the adapter to use a Datalink that is not already being
Connect the adapter to a product that supports Allen-Bradley DPI
Connect the adapter to a product that uses a 16-bit reference and
Verify the settings of Parameter 16 - [DPI I/O Cfg].
Normal behavior if all I/O is disabled in Parameter 16 - [DPI I/O
No action required.
Interface (ribbon) cable.
Replace cables if necessary.
not damaged. Replace cables if necessary.
used by another peripheral.
communications (for example, a PowerFlex 7-Class drive).
16-bit Datalinks.
Cfg].

MOD Status Indicator

Status Cause Corrective Action
Off The adapter is not powered or is not properly
connected to the drive.
Flashing Red Bad CRC of adapter parameters or flash program;
other recoverable fault condition.
Steady Red The adapter has failed the hardware test. Cycle power to the drive.
This red/green bicolor LED indicates the status of the adapter as shown in the table below.
Securely connect the adapter to the drive using the Internal
Interface (ribbon) cable.
Apply power to the drive.
Clear faults in the adapter.
Cycle power to the drive.
If cycling power does not correct the problem, the adapter
parameter settings may have been corrupted. Reset defaults and reconfigure the adapter.
If resetting defaults does not correct the problem, flash the adapter
with the latest firmware release.
Replace the adapter.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Status Cause Corrective Action
Flashing Green The adapter is operational, but is not transferring I/O
Flashing Red/ Green
Steady Green The adapter is operational and transferring I/O data. No action required.
data.
The adapter has detected a framing error. Check Parameter 09 -[Stop Bits Act] and Parameter 30 - [Stop Bits
Place the scanner in RUN mode.
Program the controller to recognize and transmit I/O to the adapter.
Configure the adapter for the program in the controller.
Normal behavior if all I/O has been disabled in Parameter 16 - [DPI
I/O Cfg].
Cfg].
Troubleshooting 8-3

NET A Status Indicator

Status Cause Corrective Actions
Off The adapter is not powered or is not properly connected
to the network.
The first incoming network command is not yet recognized.
Flashing Red A network connection has timed out. Set the timeout in Parameter 11 - [Network Timeout].
Steady Red The device has detected an error that has made it
incapable of communication on the network.
Flashing Green Online to network, but not producing or consuming I/O.
If Parameter 11 - [Network Timeout] has not been set to “0” (zero), this indicates that the adapter has not received any messages within the interval, but it has not yet timed out. The LED will turn steady green when communication resumes.
Steady Green The adapter is properly connected and communicating
on the network.
This red/green bicolor LED indicates the receive status of the adapter as shown in the table below.
Securely connect the adapter to the drive using the
Internal Interface (ribbon) cable.
Correctly connect the RS-485 cable to the connector.
Apply power to the drive.
Set the baud rate and/or parity to match the controller.
Set the correct network protocol.
Place the scanner in RUN mode.
Verify that there is not too much traffic on the network.
Select the correct network protocol.
Select correct data rate.
Verify node address is correct.
Cycle power to apply changes.
Place the scanner in RUN mode.
Program the scanner to send messages to this specific
adapter within the specified timeout.
Configure the adapter for the program in the controller.
No action required.

NET B Status Indicator

Status Cause Corrective Actions
Off The adapter is not powered or is not transmitting on the
network.
Steady Green The adapter is transmitting data on the network. No action required.
This green LED indicates the transmit status of the adapter as shown in the table below.
Program a controller to recognize and transmit I/O to
the adapter.
Place the controller in RUN mode or apply power.
Configure the adapter for the program in the controller.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
8-4 Troubleshooting

Viewing Adapter Diagnostic Items

If you encounter unexpected communications problems, the adapter’s diagnostic items may help you or Rockwell Automation personnel troubleshoot the problem. Adapter diagnostic items can be viewed using an LCD PowerFlex 7-Class HIM (Diagnostics/Device Items), DriveExplorer software (version 2.01 or higher), or DriveExecutive software (version 1.01 or higher).
Using the HIM to View Adapter Diagnostic Items
Step Keys Example Screen
1. Access parameters in the adapter. Refer to Using the PowerFlex 7-Class HIM on
page 3-2.
2. Press the Up Arrow or Down Arrow to scroll to Diagnostics.
3. Press Enter to display the Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the Device Items option.
5. Press the Up Arrow or Down Arrow to scroll through the items.
or
or
Main Menu:
Diagnostics
Parameter Device Select
Device Item # 27 Net Packet Rcvd
1022
Table 8.A Adapter Diagnostic Items
No. Name Description
1 Common Logic Cmd The present value of the Common Logic Command being transmitted to
the drive by this adapter.
2 Prod Logic Cmd The present value of the Product Logic Command being transmitted to
3 Reference The present value of the Reference being transmitted to the drive by this
4 Common Logic Sts The present value of the Common Logic Status being received from the
5 Prod Logic Sts The present value of the Product Logic Status being received from the
6 Feedback The present value of the Feedback being received from the drive by this
7 Datalink A1 In The present value of respective Datalink In being transmitted to the 8 Datalink A2 In 9 Datalink B1 In 10 Datalink B2 In 11 Datalink C1 In 12 Datalink C2 In 13 Datalink D1 In 14 Datalink D2 In
the drive by this adapter.
adapter. Note that a 16-bit value will be sent as the Most Significant Word of the 32-bit field.
drive by this adapter.
drive by this adapter.
adapter. Note that a 16-bit value will be sent as the Most Significant Word of the 32-bit field.
drive by this adapter. (If not using a Datalink, this parameter should have a value of zero. Refer to Chapter 7 information about Datalinks.)
, Using Datalinks with All Protocols for
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Troubleshooting 8-5
Table 8.A Adapter Diagnostic Items (Continued)
No. Name Description
15 Datalink A1 Out The present value of respective Datalink Out being received from the 16 Datalink A2 Out 17 Datalink B1 Out 18 Datalink B2 Out 19 Datalink C1 Out 20 Datalink C2 Out 21 Datalink D1 Out 22 Datalink D2 Out 23 Field Flash Cntr The number of times this device has been flash updated. 24 DPI Rx Errors The present value of the DPI CAN Receive error counter. 25 DPI Tx Errors The present value of the DPI CAN Transmit error counter. 26 Net Packet Sent Number of packets sent by the adapter. 27 Net Packet Rcvd Number of OK packets received by the adapter. 28 Net Bad Packet Number of BAD packets received by the adapter. 29 User IN 1 Current value of configurable point User IN 1 (RTU / N2 / P1 FLN). 30 User IN 2 Current value of configurable point User IN 2 (RTU / N2). 31 User IN 3 Current value of configurable point User IN 3 (RTU / N2). 32 User IN 4 Current value of configurable point User IN 4 (RTU / N2). 33 User IN 5 Current value of configurable point User IN 5 (RTU). 34 User IN 6 Current value of configurable point User IN 6 (RTU). 35 User IN 7 Current value of configurable point User IN 7 (RTU). 36 User IN 8 Current value of configurable point User IN 8 (RTU). 37 User OUT 1 Current value of configurable point User OUT 1 (RTU / N2 / P1 FLN). 38 User OUT 2 Current value of configurable point User OUT 2 (RTU / N2). 39 User OUT 3 Current value of configurable point User OUT 3 (RTU). 40 Switch 1 Current value of Rotary Switch 1 (Protocol Select) which can be “1” =
41 Switch 2 Current value of Rotary Switch 2 (Node Address ones digit). 42 Switch 3 Current value of Rotary Switch 3 (Node Address tens digit).
drive by this adapter. (If the drive indicates a 16-bit datalink size, the value appears in the least significant 16 bits of this diagnostic item, and the most significant 16 bits of this diagnostic item are zero. Refer to
Chapter 7
Datalinks.)
RTU, “0” = N2, or “9” = P1.
, Using Datalinks with All Protocols for information about
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
8-6 Troubleshooting

Viewing and Clearing Events

The adapter has an event queue to record significant events that occur in the operation of the adapter. When such an event occurs, an entry is put into the event queue. You can view the event queue using an LCD PowerFlex 7-Class HIM, DriveExplorer (2.01 or higher) software, DriveExecutive (1.01 or higher) software or other clients using the DPI Fault object.
The event queue can contain up to 32 entries. Eventually the event queue will become full, since its contents are retained through adapter resets. At that point, a new entry replaces the oldest entry. Only an event queue clear operation or adapter power cycle will clear the event queue contents.
Resetting the adapter to defaults has no effect on the event queue.
Using the HIM to View and Clear Events
Step Keys Example Screen Viewing Events
1. Access parameters in the adapter. Refer to Using the PowerFlex 7-Class HIM
page 3-2.
2. Press the Up Arrow or Down Arrow to scroll to Diagnostics.
3. Press Enter to display the Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the Events option and then View Event Queue option.
5. Press the Up Arrow or Down Arrow to scroll through the events. The most recent event is Event 1.
Clearing Events
1. Access parameters in the adapter. Refer to Using the PowerFlex 7-Class HIM
page 3-2.
2. Press the Up Arrow or Down Arrow to scroll to Diagnostics.
3. Press Enter to display the Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the Events option and then the Clear Event option or Clr Event Queue option. A message will pop up to confirm that you want to clear the message or queue.
5. Press Enter to confirm your request. If Clr Event Queue was selected, all event queue entries will then display “No Event.”
on
on
Main Menu:
or
or
or
Diagnostics
Parameter Device Select
Event Q: 1 E3 Ping Time Flt
Dgn: Events View Event Queue Clear Event
Clr Event Queue
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Troubleshooting 8-7
Events
Many events in the event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Allen-Bradley personnel troubleshoot the problem. The following events may appear in the event queue:
Table 8.B Adapter Events
Code Event Description
1 No Event Empty event queue entry. 2 DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be caused by
loose or broken cables or by noise. 3 Ping Time Flt A ping message was not received on DPI within the specified time. 4 Port ID Flt The adapter is not connected to a correct port on a DPI product. 5 Port Change Flt The DPI port changed after start up. 6 Host Sent Reset The drive sent a reset event message. 7 EEPROM Sum Flt The EEPROM in the adapter is corrupt. 8 Online @ 125kbps The adapter detected that the drive is communicating at 125 kbps. 9 Online @ 500kbps The adapter detected that the drive is communicating at 500 kbps. 10 Bad Host Flt The adapter was connected to an incompatible product. 11 Dup Port Flt Another peripheral with the same port number is already in use. 12 Type 0 Login The adapter has logged in for Type 0 control. 13 Type 0 Time Flt The adapter has not received a Type 0 status message within the
specified time. 14 DL Login The adapter has logged into a Datalink. 15 DL Reject Flt The drive rejected an attempt to log in to a Datalink because the
Datalink is not supported or is used by another peripheral. 16 DL Time Flt The adapter has not received a Datalink message within the specified
time. 17 Control Disabled The adapter has sent a “Soft Control Disable” command to the drive. 18 Control Enabled The adapter has sent a “Soft Control Enable” command to the drive. 19 Message Timeout A Client-Server message sent by the adapter was not completed within
1 sec. 20 DPI Fault Msg The drive has faulted. 21 DPI Fault Clear The drive issued this because a fault was cleared. 22 Normal Startup The adapter successfully started up. 23 Flt Cfg Error The adapter detected a 32-bit fault configuration reference when the
drive supports only a 16-bit reference, or detected a 32-bit fault
configuration Datalink value when the drive supports only 16-bit
Datalinks. 24 Net Comm Flt The adapter detected a communications fault on the network. 25 Net Detected The adapter has detected network communication. 26 Net TImeout Flt The adapter has detected a network timeout. The timeout period is
configured in Parameter 11- [Network Timeout]. 27 Lang CRC Bad The CRC of the language text file is incorrect.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
8-8 Troubleshooting
Notes:
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Specifications

Appendix A presents the specifications for the adapter.
Topic Page
Communications Electrical A-1 Mechanical A-1 Environmental A-1 Regulatory Compliance A-2
A-1

Appendix A

Communications

Electrical

Mechanical

Network
Protocols
Data Rates
- Modbus RTU
- Metasys N2
- Siemens Building Technologies P1 FLN
Drive
Protocol Data Rates
Consumption
Drive Network
Dimensions
Height Length Width
Weight 85g (3 oz.)
Modbus RTU Metasys N2 Siemens Building Technologies P1 FLN
4800, 9600, 19200, or 38400 baud 9600 baud 4800 or 9600 baud
DPI 125 kbps or 500 kbps
150 mA at 5 VDC supplied by the host (for example, drive) None
19 mm (0.75 inches) 86 mm (3.39 inches)
78.5 mm (3.09 inches)

Environmental

Temperature
Operating Storage
Relative Humidity 5…95% non-condensing Atmosphere Important: The adapter must not be installed in an area where the
-10…50°C (14…122°F)
-40…85°C (-40…185°F)
ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the adapter is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
A-2 Specifications

Regulatory Compliance

Certification Specification
UL UL508C cUL CAN / CSA C22.2 No. 14-M91 CE EN50178 and EN61800-3 CTick EN61800-3
NOTE: This is a product of category C2 according to IEC 61800-3. In a domestic environment this product may cause radio interference in which case supplementary mitigation measures may be required.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Appendix B

Adapter Parameters

Appendix B provides information about the adapter parameters.
Topic Page

Parameter List

B-1
Parameter List
Parameter No. Name and Description Details
01 [DPI Port]
Displays the port to which the adapter is connected. This will usually be port 5.
02 [DPI Data Rate]
Displays the data rate used by the drive. This data rate is set in the drive and the adapter detects it.
03 [Net Addr Cfg]
Configures the network node address if the network switches on the adapter are set to “00.”
04 [Net Addr Act]
Displays the network address actually used by the adapter.
05 [Net Rate Cfg]
Configures the network data rate at which the adapter communicates.
The available values for this parameter depend on the network protocol selected. Only valid values for the specified network are displayed.
06 [Net Rate Act]
Displays the network data rate actually used by the adapter.
07 [Net Parity Cfg]
Configures the network parity.
The available values for this parameter depend on the network protocol selected. Only valid values for the specified network are displayed.
08 [Net Parity Act]
Displays the actual network parity used by the adapter.
Default: 5 Minimum: 0 Maximum: 7 Type: Read Only
Default: 0 = 125 kbps Values: 0 = 125 kbps
Type: Read Only Default: 1
Minimum: 0 Maximum: 247 Type: Read/Write Reset Required: Yes
Default: 1 Minimum: 0 Maximum: 247 Type: Read Only
Default: 1 = 9600 Values: 0 = 4800
Type: Read/Write Reset Required: Yes
Default: 1 = 9600 Values: 0 = 4800
Type: Read Only Default: 0 = None
Values: 0 = None
Type: Read/Write Reset Required: Yes
Default: 0 = None Values: 0 = None
Type: Read Only
1 = 500 kbps
1 = 9600 2 = 19200 3 = 38400
1 = 9600 2 = 19200 3 = 38400
1 = Odd 2 = Even
1 = Odd 2 = Even
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
B-2 Adapter Parameters
Parameter No. Name and Description Details
09 [Stop Bits Act]
Displays the actual number of stop bits used by the selected protocol.
This value is network-dependent:
ModBus RTU Protocol – The number of stop bits
used depends on the value set by Parameter 30 - [Stop Bits Cfg].
Metasys N2 Protocol – Uses only 1 bit, so the
adapter shows only this value.
Siemens Building Technologies P1 FLN Protocol –
Uses only 1 bit, so the adapter shows only this value.
10 [Net Chksum Type]
Displays the type of checksum used by the selected protocol. The value is network dependent:
Modbus RTU Protocol – Uses CRC16 (-1) which is
Cyclic Redundancy Check with -1 as a seed value.
Metasys N2 Protocol – Uses RLC which is Run
Length Checksum.
Siemens Building Technologies P1 FLN – Uses
CRC16 (0) which is Cyclic Redundancy Check with 0 as a seed value.
11 [Network Timeout]
Configures the time in seconds to be used to detect network communication loss.
Default: 0 = 1-bit Values: 0 = 1-bit
1 = 2-bits
Type: Read Only
Default: 0 = CRC16 (0) Values: 0 = CRC16 (0)
1 = RLC 2 = CRC16 (-1)
Type: Read Only
Default: 10 seconds Minimum: 0 seconds Maximum: 180 seconds Type: Read/Write Reset Required: No
12 [Ref/Fdbk Size]
13 [Datalink Size]
14 [Reset Module]
ATTENTION: Risk of injury or equipment damage exists. Parameter 11 ­[Network Timeout] lets you determine how long it will take your adapter to detect
!
network communication losses. By default, this parameter sets the timeout to ten seconds. You can set it so that the duration is shorter, longer, or disabled. Take precautions to ensure that the setting does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
Displays the size of the Reference/Feedback. The drive determines the size of the Reference/Feedback.
Displays the size of each Datalink word. The drive determines the size of Datalinks.
No action if set to “0” (Ready). Resets the adapter if set to “1” (Reset Module). Restores the adapter to its factory default settings if set to “2” (Set Defaults). This parameter is a command. It will be reset to “0” (Ready) after the command has been performed.
ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting I/O that controls the drive, the drive may fault when you reset the
!
adapter. Determine how your drive will respond before resetting a connected adapter.
Default: 0 = 16-bit Values: 0 = 16-bit
1 = 32-bit
Type: Read Only Default: 0 = 16-bit
Values: 0 = 16-bit
1 = 32-bit
Type: Read Only Default: 0 = Ready
Values: 0 = Ready
1 = Reset Module
2 = Set Defaults Type: Read/Write Reset Required: No
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Parameter No. Name and Description Details
15 [Comm Flt Action]
Sets the action that the adapter will take if it detects a network failure because it has not communicated with its master within the interval specified in Parameter 11
- [Network Timeout]. This action takes effect only if I/O that controls the drive is transmitted through the adapter.
ATTENTION: Risk of injury or equipment damage exists. Parameter 15 - [Comm Flt Action] lets you determine the action of the adapter and connected drive if I/O
!
communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
Default: 0 = Fault Values: 0 = Fault
Type: Read/Write Reset Required: No
Adapter Parameters B-3
1 = Stop 2 = Zero Data 3 = Hold Last 4 = Send Flt Cfg
16 [DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.
17 [DPI I/O Act]
Displays the I/O that the adapter is actively transmitting. The value of this parameter will usually be equal to the value of Parameter 16 - [DPI I/O Cfg].
18 [Flt Cfg Logic]
Sets the Logic Command data that is sent to the drive if Parameter 15 - [Comm Flt Action] is set to “4” (Send Flt Cfg) and the adapter times out.
The bit definitions will depend on the product to which the adapter is connected. See Appendix documentation for the drive being used.
19 [Flt Cfg Ref]
Sets the Reference data that is sent to the drive if Parameter 15 - [Comm Flt Action] is set to “4” (Send Flt Cfg) and the adapter times out.
C or the
Default: xxx0 0001 Bit Values: 0 = I/O disabled
1 = I/O enabled Type: Read/Write Reset Required: Yes
Bit Definition
Not Used
Not Used
Not Used
Datalink D*
Datalink C*
Datalink B
Datalink A Default xxx00001 Bit 76543210
*Not used with Metasys N2.
Default: xxx0 0001 Bit Values: 0 = I/O disabled
Not Used
Not Used
1 = I/O enabled
Not Used
Datalink D*
Datalink C*
Datalink B
Datalink A
Type: Read Only
Bit Definition
Default xxx00001 Bit 76543210
*Not used with Metasys N2.
Default: 0000 0000 0000 0000 Minimum: 0000 0000 0000 0000 Maximum: 1111 1111 1111 1111 Type: Read/Write Reset Required: No
Default: 0 Minimum: 0 Maximum: 4294967295 Type: Read/Write Reset Required: No
Important: If the drive uses a 16-bit Reference, the most significant word of this value must be set to zero (0) or a fault will occur.
Cmd/Ref
Cmd/Ref
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
B-4 Adapter Parameters
Parameter No. Name and Description Details
[Flt Cfg A1 In]
20
[Flt Cfg A2 In]
21
[Flt Cfg B1 In]
22
[Flt Cfg B2 In]
23
[Flt Cfg C1 In]
24
[Flt Cfg C2 In]
25
[Flt Cfg D1 In]
26
[Flt Cfg D2 In]
27
Sets the data that is sent to the Datalink in the drive if Parameter 15 - [Comm Flt Action] is set to “4” (Send Flt Cfg) and the adapter times out.
28 [Clear Counters]
Clears the network diagnostic counters.
29 [N2 Ref Scale]
Only used if Metasys N2 protocol is selected. Determines the engineering unit sent over DPI for the Reference when 100% is set for AO#2.
30 [Stop Bits Cfg]
Sets the number of stop bits used by the adapter when the network protocol switch is set to “Modbus RTU.” When any other protocol is selected, this parameter setting has no effect.
31 [RTU Ref Adjust]
Sets the percent scale factor for the Reference from the network when the network protocol switch is set to “Modbus RTU,” and broadcast messages (Modbus address “0”) are sent. This lets the drive’s Reference either match the broadcast message Reference (=100%), scale below it (<100%), or scale above it (>100%). When any other protocol is selected, this parameter setting has no effect.
Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Minimum: 0 Maximum: 4294967295 Type: Read/Write Reset Required: No
Important: If the drive uses 16-bit Datalinks, the most significant word of this value must be set to zero (0) or a fault will occur.
Default: 0 = Ready Values: 0 = Ready
1 = Clear Type: Read/Write Reset Required: No
Default: 32767 Minimum: 0 Maximum: 4294967295 Type: Read/Write Reset Required: No
Default: 0 = 1 bit Values: 0 = 1 bit
1 = 2 bits Type: Read/Write Reset Required: Yes
Default: 100.0% Minimum: 0.0% Maximum: 200.0% Type: Read/Write Reset Required: No
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
32 [RTU Param Mode]
Sets the mode in which the adapter operates.
ATTENTION: To guard against equipment damage and/or personal injury, note that changes to Parameter 31 - [RTU Ref Adjust] take effect immediately. A drive
!
receiving a broadcast message Reference from the adapter will receive the newly scaled Reference, resulting in a change of speed.
Default: 0 = 16-bit Mode Values: 0 = 16-bit Mode
1 = 32-bit Mode Type: Read/Write Reset Required: Yes

Appendix C

Logic Command/Status Words

Appendix D presents the definitions of the Logic Command and Logic Status words that are used for some products that can be connected to the adapter. If you do not see the Logic Command/Logic Status for the product that you are using, refer to your product’s documentation.

PowerFlex 7-Class Drives (except PowerFlex 700S)

Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description
x x x Reference
x MOP Decrement 0 = Not Decrement
(1)
A “0 = Not Stop” condition (logic 0) must first be present before a “1 = Start” condition will start the drive. The Start command acts as a momentary Start command. A “1” will start the drive, but returning to “0” will not
(2)
This Start will not function if a digital input (parameters 361-366) is programmed for 2-Wire Control (option 7, 8 or 9).
(3)
This Reference Select will not function if a digital input (parameters 361-366) is programmed for “Speed Sel 1, 2 or 3” (option 15, 16 or 17). Note that Reference Select is “Exclusive Ownership” – see drive User Manual for more information.
Logic Command Word
xStop
xStart
xJog 0 = Not Jog
x Clear Faults 0 = Not Clear Faults
x x Direction 00 = No Command
x Local Control 0 = No Local Control
x MOP Increment 0 = Not Increment
x x Accel Rate 00 = No Command
x x Decel Rate 00 = No Command
(1)
Select
stop the drive.
(1)(2)
(3)
0 = Not Stop 1 = Stop 0 = Not Start 1 = Start
1 = Jog
1 = Clear Faults
01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control
1 = Local Control
1 = Increment
01 = Accel Rate 1 Command 10 = Accel Rate 2 Command 11 = Hold Accel Rate
01 = Decel Rate 1 Command 10 = Decel Rate 2 Command 11 = Hold Decel Rate
000 = No Command 001 = Ref. 1 (Ref A Select) 010 = Ref. 2 (Ref B Select) 011 = Ref. 3 (Preset 3) 100 = Ref. 4 (Preset 4) 101 = Ref. 5 (Preset 5) 110 = Ref. 6 (Preset 6) 111 = Ref. 7 (Preset 7)
1 = Decrement
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
C-2 Logic Command/Status Words
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Description
x x x x Reference 0000 = Ref A Auto
(1)
See “Owners” in drive User Manual for further information.
Logic Status Word
x Ready 0 = Not Ready
x Active 0 = Not Active
x Command
Direction
x Actual Direction 0 = Reverse
x Accel 0 = Not Accelerating
x Decel 0 = Not Decelerating
x Alarm 0 = No Alarm
x Fault 0 = No Fault
x At Speed 0 = Not At Reference
x x x Local Control
1 = Ready
1 = Active 0 = Reverse
1 = Forward
1 = Forward
1 = Accelerating
1 = Decelerating
1 = Alarm
1 = Fault
1 = At Reference
(1)
000 = Port 0 (TB) 001 = Port 1 010 = Port 2 011 = Port 3 100 = Port 4 101 = Port 5 110 = Port 6 111 = No Local
0001 = Ref B Auto 0010 = Preset 2 Auto 0011 = Preset 3 Auto 0100 = Preset 4 Auto 0101 = Preset 5 Auto 0110 = Preset 6 Auto 0111 = Preset 7 Auto 1000 = Term Blk Manual 1001 = DPI 1 Manual 1010 = DPI 2 Manual 1011 = DPI 3 Manual 1100 = DPI 4 Manual 1101 = DPI 5 Manual 1110 = DPI 6 Manual 1111 = Jog Ref
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Logic Command/Status Words C-3

PowerFlex 700S Drives

Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description
x Spd Ref Sel1
x Spd Ref Sel2
Logic Command Word (Phase II Control)
x Normal Stop 0 = Not Normal Stop
xStart
x Jog 1 0 = Not Jog using [Jog Speed 1]
x Clear Fault
xx Unipolar
xReserved
x Jog 2 0 = Not Jog using [Jog Speed 2]
x Current Limit
x Coast Stop 0 = Not Coast to Stop
xReserved
xReserved
x Spd Ref Sel0
(1)
Direction
Stop
1 = Normal Stop 0 = Not Start
1 = Start
1 = Jog using [Jog Speed 1]
(2)
0 = Not Clear Fault 1 = Clear Fault
00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control
1 = Jog using [Jog Speed 2] 0 = Not Current Limit Stop
1 = Current Limit Stop
1 = Coast to Stop
Bits
14 13 12
000=Spd Ref A 001=Spd Ref B 010=Preset 2 0 1 1 = Ref. 3 (Preset 3) 1 0 0 = Ref. 4 (Preset 4) 1 0 1 = Ref. 5 (Preset 5) 1 1 0 = Ref. 6 (Preset 6) 1 1 1 = Ref. 7 (Preset 7)
xReserved
(1)
A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition will start the drive.
(2)
To perform this command, the value must switch from “0” to “1.”
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
C-4 Logic Command/Status Words
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Description
x At Setpt Spd 0 = Not At Setpoint Speed
x Enable 0 = Not Enabled
(1)
See Parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.
Logic Status Word (Phase II Control)
x Active 0 = Not Active
1 = Active
x Running 0 = Not Running
1 = Running
x Command
Direction
x Actual Direction 0 = Reverse
x Accel 0 = Not Accelerating
x Decel 0 = Not Decelerating
x Jogging 0 = Not Jogging
x Fault 0 = No Fault
x Alarm 0 = No Alarm
x Flash Mode 0 = Not in Flash Mode
x Run Ready 0 = Not Ready to Run
x At Limit
x Tach Loss Sw 0 = Not Tach Loss Sw
x At Zero Spd 0 = Not At Zero Speed
(1)
0 = Reverse 1 = Forward
1 = Forward
1 = Accelerating
1 = Decelerating
1 = Jogging
1 = Fault
1 = Alarm
1 = In Flash Mode
1 = Ready to Run 0 = Not At Limit
1 = At Limit
1 = Tach Loss Sw
1 = At Zero Speed
1= At Setpoint Speed
1 = Enabled
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
A Adapter
Devices such as drives, controllers, and computers usually require an adapter to provide a communication interface between them and a network. An adapter reads data on the network and transmits it to the connected device. It also reads data in the device and transmits it to the network.
The 20-COMM-H RS-485 HVAC adapter connects a PowerFlex 7-Class drive to the network. Adapters are sometimes also called “cards,” “embedded communication options,” “gateways,” “modules,” and “peripherals.”
B Bus Off
A condition that occurs when an abnormal rate of errors is detected in a device. The bus off device cannot receive or transmit messages on the network. This condition is often caused by corruption of the network data signals due to noise or data rate mismatch.
C ControlFLASH
An Allen-Bradley software tool that lets users electronically update firmware on printed circuit boards. The tool takes advantage of the growing use of flash memory (electronic erasable chips) across industrial control products.

Glossary

D Data Rate
Controller
A controller, also called programmable logic controller, is a solid-state control system that has a user-programmable memory for storage of instructions to implement specific functions such as I/O control, logic, timing, counting, report generation, communication, arithmetic, and data file manipulation. A controller consists of a central processor, input/output interface, and memory. See also Scanner.
The speed at which data is transferred on the network. Each device on a network must be set to the same data rate.
Datalinks
A Datalink is a type of pointer used by some PowerFlex drives to transfer data to and from the controller. Datalinks allow specified parameter value(s) to be accessed or changed without using explicit messages. When enabled, each Datalink consumes either four bytes or eight bytes in both the input and output image table of the controller. The drive determines the size of Datalinks.
DPI (Drive Peripheral Interface)
A second generation peripheral communication interface used by various Allen-Bradley drives and power products, such as PowerFlex 7-Class drives.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
G-2 Glossary
DPI Peripheral
A device that provides an interface between DPI and a network or user. Peripheral devices are also referred to as “adapters” or “modules.” The 20-COMM-H adapter and PowerFlex 7-Class HIMs (20-HIM-xxx) are examples of DPI peripherals.
DPI Product
A device that uses the DPI communications interface to communicate with one or more peripheral devices. For example, a motor drive such as a PowerFlex 7-Class drive is a DPI product. In this manual, a DPI product is also referred to as “drive” or “host.”
DriveExplorer Software
A tool for monitoring and configuring Allen-Bradley products and adapters. It can be run on computers running various Microsoft Windows operating systems. DriveExplorer (version 3.xx or higher) can be used to configure this adapter and PowerFlex drive. Information about DriveExplorer software and a free lite version can be accessed at http://www.ab.com/
drives/driveexplorer.
DriveTools SP Software
A software suite designed for running on various Microsoft Windows operating systems. This software suite provides a family of tools, including DriveExecutive, that you can use to program, monitor, control, troubleshoot, and maintain Allen-Bradley products. DriveTools SP can be used with PowerFlex drives. Information about DriveTools SP can be accessed at
http://www.ab.com/drives/drivetools
F Fault Action
A fault action determines how the adapter and connected drive act when a communications fault (for example, a cable is disconnected) occurs.
Fault Configuration
When communications are disrupted (for example, a cable is disconnected), the adapter and PowerFlex drive can respond with a user-defined fault configuration. The user sets the data that is sent to the drive using specific fault configuration parameters in the adapter. When a fault action parameter is set to use the fault configuration data and a fault occurs, the data from these parameters is sent as the Logic Command, Reference, and/or Datalink(s).
Flash Update
The process of updating firmware in a device. The adapter can be flash updated using various Allen-Bradley software tools. Refer to Flash
Updating the Adapter on page 3-10 for more information.
.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Glossary G-3
H HIM (Human Interface Module)
A device that can be used to configure and control a drive. PowerFlex 7-Class HIMs (20-HIM-xxx) can be used to configure PowerFlex 7-Class drives and their connected peripherals.
Hold Last
When communication is disrupted (for example, a cable is disconnected), the adapter and PowerFlex drive can respond by holding last. Hold last results in the drive receiving the last data received via the network connection before the disruption. If the drive was running and using the Reference from the adapter, it will continue to run at the same Reference.
I I/O Data
I/O data, sometimes called “ implicit messages” or “input/output,” is time-critical data such as a Logic Command and Reference. The terms “input” and “output” are defined from the controller’s point of view. Output is produced by the controller and consumed by the adapter. Input is produced by the adapter and consumed by the controller.
L Logic Command/Logic Status
The Logic Command is used to control the PowerFlex 7-Class drive (for example, start, stop, direction). It consists of one 16-bit word of output to the adapter from the network. The definitions of the bits in this word depend on the drive, and are shown in Appendix
The Logic Status is used to monitor the PowerFlex 7-Class drive (for example, operating state, motor direction). It consists of one 16-bit word of input from the adapter to the network. The definitions of the bits in this word depend on the drive, and are shown in Appendix
N Node Address
Each device on a network must have a unique node address to identify it. On Modbus RTU, Metasys N2, and Siemens Building Technologies P1 FLN networks, devices can have node addresses between 1 and 255 if the network is set up to accommodate that number of devices.
NVS (Non-Volatile Storage)
NVS is the permanent memory of a device. Devices such as the adapter and drive store parameters and other information in NVS so that they are not lost when the device loses power. NVS is sometimes called “EEPROM.”
C.
C.
P Parity Check
When the adapter uses a parity check, a non-data bit is added to each binary word that it sends and receives. Devices on the network verify the data integrity of the transmitted data by checking that the sum of the number of ones in a word is always even or odd.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
G-4 Glossary
Ping
A message that is sent by a DPI product to its peripheral devices. They use the ping to gather data about the product, including whether it can receive messages and whether they can log in for control.
PowerFlex 7-Class (Architecture Class) Drives
The Allen-Bradley PowerFlex 7-Class family of drives supports DPI and includes the PowerFlex 70, PowerFlex 700, PowerFlex 700H, PowerFlex 700S, PowerFlex 700L, and PowerFlex 7000. These drives can be used for applications ranging from 0.37…3000 kW (0.5…4000 HP).
R Reference/Feedback
The Reference is used to send a setpoint (for example, speed, frequency, torque) to the drive. It consists of one word of output to the adapter from the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.
Feedback is used to monitor the speed of the drive. It consists of one word of input from the adapter to the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.
S Scanner
A scanner is a separate module (of a multi-module controller) or a built-in component (of a single-module controller) that provides communication with adapters connected to a network. See also Controller.
Status Indicators
Status indicators are LEDs that are used to report the status of the adapter, network, and drive. They are on the adapter and can be viewed on the front cover of the drive when the drive is powered.
T Type 0/Type 1/Type 2 Control
When transmitting I/O, the adapter can use different types of messages for control. The Type 0, Type 1, and Type 2 events help Allen-Bradley personnel identify the type of messages that an adapter is using.
Z Zero Data
When communications are disrupted (for example, a cable is disconnected), the adapter and drive can respond with zero data. Zero data results in the drive receiving zero as values for Logic Command, Reference, and Datalink data. If the drive was running and using the Reference from the adapter, it will stay running but at zero Reference.
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P

Index

A
adapter
applying power, 2-7 commissioning, 2-1 compatible products, 1-2 components, 1-1 configuration tools, 3-1 configuring I/O for, 3-5 connecting to a drive, 2-3 connecting to the network, 2-6 definition, G-1 features, 1-2 flash updating, 3-10 grounding, 2-5 installation, 2-1 to 2-8 mounting on the drive, 2-5 parameters, B-1 to B-4 resetting, 3-8 selecting operating mode, B-4 specifications, A-1
viewing its status, 3-9 applying power to the adapter, 2-7 attentions, 1-3
B
baud rate, see data rate bit definitions of Logic Command/Status word for
PowerFlex 70/700/700H drives, C-1
PowerFlex 700S drives, C-3 bus off, G-1
C
cables
DPI Internal Interface, 2-3, 2-4
network, 2-6 Clear Counters parameter, B-4 Comm Flt Action parameter, B-3 commissioning the adapter, 2-1 communications module, see adapter compatible products, 1-2 components of the adapter, 1-1 configuration tools, 3-1 connecting adapter to the
network, 2-6 connecting adapter to the drive, 2-3 connector on adapter, 1-1
ControlFLASH, G-1 controller, G-1
D
data rate
definition, G-1 setting, 3-3
data transfers
advanced (all protocols), 7-1 to 7-6 Metasys N2, 5-1 to 5-9 Modbus RTU, 4-1 to 4-13 Siemens Building Technologies P1 FLN, 6-1
to 6-10
Datalink Size parameter, B-2 Datalinks
definition, G-1 Metasys N2, 7-4 Modbus RTU, 7-3 to 7-4 Siemens Building Technologies P1 FLN, 7-5
to 7-6
using with all protocols, 7-1 to 7-6 diagnostic items, 8-4 dimensions, A-1 DPI
connector on adapter, 1-1
data rates, A-1
definition, G-1
Internal Interface cable, 2-3, 2-4
peripheral, G-2
products, 1-2, G-2 DPI Data Rate parameter, B-1 DPI I/O Act parameter, B-3 DPI I/O Cfg parameter, B-3 DPI Port parameter, B-1 DriveExecutive software
adapter configuration tool, 3-1
definition/web site, G-2 DriveExplorer software
adapter configuration tool, 3-1
definition/web site, G-2
free lite version, G-2 drives, see PowerFlex drives DriveTools SP software, G-2
E
EEPROM, see Non-Volatile Storage (NVS)
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Index-2
environmental specifications, A-1 equipment required, 1-3 events
clearing/viewing, 8-6 list of, 8-7
F
fault action
configuring the adapter for, 3-7 definition, G-2
fault configuration
configuring the adapter for, 3-7 definition, G-2
faults, see events features, 1-2 firmware release, P-2 flash update
definition, G-2
guidelines, 3-10 Flt Cfg A1-D2 In parameters, B-4 Flt Cfg Logic parameter, B-3 Flt Cfg Ref parameter, B-3
G
grounding the adapter, 2-5
H
HIM (Human Interface Module)
accessing parameters with, 3-2
definition, G-3
LCD model, 3-2
LED model, 3-2 hold last
configuring the adapter for, 3-7
definition, G-3
I
I/O
configuring the adapter for, 3-5
definition, G-3 installation
applying power to the adapter, 2-7
connecting to the drive, 2-3
connecting to the network, 2-6
preparing for, 2-1
Internal Interface cables
connecting to the adapter, 2-4 connecting to the drive, 2-4 illustration, 2-4
L
LCD HIM, 3-2 LED HIM, 3-2 LEDs, see status indicators Logic Command/Status
bit definitions for
PowerFlex 70/700/700H drives, C-1
PowerFlex 700S drives, C-3 definition, G-3 on Metasys N2, 5-3 to 5-6 on Modbus RTU, 4-7 to 4-8 on Siemens Building Technologies P1 FLN,
6-5 to 6-9
M
manual
conventions, P-2 related documentation, P-1 web site, P-1
mechanical dimensions, A-1 Metasys N2
data transfers, 5-1 to 5-9 Datalinks, 7-4 point map, 5-3 to 5-6 selecting with a switch, 2-2
MOD status indicator
locating, 1-6 troubleshooting with, 8-2
Modbus RTU
accessing drive parameters, 4-9 broadcast messages, 4-12 data transfers, 4-1 to 4-13 Datalinks, 7-3 to 7-4 point map, 4-4 to 4-8 selecting with a switch, 2-2
mounting the adapter, 2-5
N
N2 Ref Scale parameter, B-4 NET A status indicator
locating, 1-6 troubleshooting with, 8-3
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Index-3
Net Addr Act parameter, B-1 Net Addr Cfg parameter, B-1 NET B status indicator
locating, 1-6
troubleshooting with, 8-3 Net Chksum Type parameter, B-2 Net Parity Act parameter, B-1 Net Parity Cfg parameter, B-1 Net Rate Act parameter, B-1 Net Rate Cfg parameter, B-1 network
cable, 2-6
data rates, A-1
protocols
Metasys N2, 5-1 Modbus RTU, 4-1 selecting with a switch, 2-2 Siemens Building Technologies P1 FLN,
6-1
Network Timeout parameter, B-2 node address
definition, G-3
setting with a parameter, 3-3
setting with switches, 2-2 Non-Volatile Storage (NVS)
definition, G-3
in adapter, 3-1
O
operating mode selection for adapter, B-4
P
parameters
accessing, 3-1
convention, P-2
list of, B-1 to B-4
restoring to factory-default settings, 3-8 parity check, G-3 parity setting, 3-4 ping, G-4 point map
Metasys N2, 5-3 to 5-6
Modbus RTU, 4-4 to 4-8
Siemens Building Technologies P1 FLN, 6-3 PORT status indicator
locating, 1-6
troubleshooting with, 8-2
power consumption, A-1 PowerFlex drives
compatible with adapter, 1-2 definition, G-4 HIM, 3-2
preparing for an installation, 2-1 processor, see controller programmable logic controller, see controller
Q
quick start, 1-5
R
Ref/Fdbk Size parameter, B-2 Reference/Feedback, G-4 regulatory compliance, A-2 related documentation, P-1 Reset Module parameter, B-2 ribbon cable, see Internal Interface cable RTU Param Mode parameter, B-4 RTU Ref Adjust parameter, B-4
S
safety precautions, 1-3 scanner, G-4 selecting adapter operating mode, B-4 Siemens Building Technologies P1 FLN
data transfers, 6-1 to 6-10 Datalinks, 7-5 to 7-6 selecting with a switch, 2-2
specifications for the adapter, A-1 status indicators
definition, G-4 locating, 1-6 MOD, 1-6, 8-2 NET A, 1-6, 8-3 NET B, 1-6, 8-3 normal operation, 2-7 PORT, 1-6, 8-2 troubleshooting with, 8-2 to 8-3
understanding, 8-1 Stop Bits Act parameter, B-2 Stop Bits Cfg parameter, B-4 switches
network protocol, 2-2
node address, 2-2
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Index-4
T
technical support, P-2 tools required, 1-3 troubleshooting, 8-1 to 8-7 Type 0/Type 1/Type 2 control, G-4
U
update, see flash update
W
web site
DriveExecutive software, G-2 DriveExplorer software, G-2 DriveTools SP software, G-2 manuals, P-1
wiring, see cables
Z
zero data
configuring the adapter for, 3-7 definition, G-4
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 20COMM-UM009D-EN-P – September, 2009
Supersedes 20COMM-UM009C-EN-P – March, 2004 Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in USA.
Loading...