Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature
some important differences between solid state equipment and hard-wired electromechanical devices. Because of this
difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying
this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting
from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables
and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility
or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
) describes
WARNING: Identifies information about practices or circumstances that can
cause an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and understanding of the product.
ATTENTION: Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic loss. Attentions
help you identify a hazard, avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that surfaces may be at dangerous
temperatures.
Allen-Bradley, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
2Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013
This manual provides information about the adapter and using it with PowerFlex
7-Class (Architecture-Class) drives or Bulletin 150 SMC Soft Starters. The
adapter can be used with other products that support a DPI™ adapter, such as the
DPI External Comms Kit (20-XCOMM-DC-BASE). See the documentation
for your product for specific information about how it works with the adapter.
The following conventions are used throughout this manual:
• Parameter names are shown in the format Parameter xx - [*]. The xx
represents the parameter number. The * represents the parameter name—
for example Parameter 01 - [DPI Port].
• Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read ‘Select File > Open’, you should click the File menu and then click the Open command.
7
Rockwell Automation
Support
• The firmware revision number (FRN) is displayed as FRN X.xxx, where
‘X’ is the major revision number and ‘xxx’ is the minor revision number.
• The screen images in this manual resulted from using the following
software:
– RSLinx
– RSLogix 5000 software, version 16
Different versions of the software may have screens that vary in
appearance, and differences in procedures.
Rockwell Automation offers support services worldwide, with over 75 sales and
support offices, over 500 authorized distributors, and over 250 authorized
systems integrators located through the United States alone. In addition,
Rockwell Automation representatives are in every major country in the world.
®
Classic software, version 2.51
Local Product Support
Contact your local Rockwell Automation representative for the following :
• Sales and order support
• Product technical training
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 20137
Preface
• Warranty support
• Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 7,
Troubleshooting
Technical Support website at www.ab.com/support/abdrives
Rockwell Automation.
, first. If you still have problems, then access the Allen-Bradley
or contact
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Industrial Automation wiring and grounding guidelines, publication 1770-4.1Provides general guidelines for installing a Rockwell
Product certifications website, http://www.ab.comProvides declarations of conformity, certificates, and
Industrial Security Best Practices, publication SECUR-AT001Provides further information and guidelines on product
PowerFlex 700 Series A User Manual, publication 20B-UM001
PowerFlex 700 Series B User Manual, publication 20B-UM002
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70EC/700VC Reference Manual, publication PFLEX-RM004
Information on the installation of PowerFlex
20-COMM-x Network Communication Adapters.
Information on the planning, installation, and techniques
used to implement an EtherNet/IP network.
Information on the Connected Components
Workbench™ software tool—and includes a link for free
software download.
HIM-A5, 20-HIM-C3S, and 20-HIM-C5S HIMs.
Information on the installation and use of the PowerFlex
20-HIM-A6 and 20-HIM-C6S HIMs.
Information on installing, programming, and technical
data of PowerFlex
Information on installing, programming, and technical
data of PowerFlex 700/700VC Series A and PowerFlex
700VC Series B drives.
Information on installing, programming, and technical
data of PowerFlex 700H drives.
70 and PowerFlex 70EC drives.
8Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013
Preface
ResourceDescription
PowerFlex 700S w/Phase I Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S w/Phase I Control Installation Manual (Frames 9 and 10), publication PFLEXIN006
PowerFlex 700S w/Phase I Control User Manual (All Frame Sizes), publication 20D-UM001
PowerFlex 700S w/Phase I Control Reference Manual, publication PFLEX-RM002
PowerFlex 700S w/Phase II Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S w/Phase II Control Installation Manual (Frames 9…14), publication PFLEXIN006
PowerFlex 700S w/Phase II Control Programming Manual (All Frame Sizes), publication 20DPM001
PowerFlex 700S w/Phase II Control Reference Manual, publication PFLEX-RM003
PowerFlex 700L User Manual, publication 20L-UM001Information on installing, programming, and technical
SMC Flex Smart Motor Controller User Manual, publication 150-UM008Information on installing, programming, and technical
SMC-50 Solid-State Smart Motor Controller User Manual, publication 150-UM011Information on installing, programming, and technical
PowerFlex Digital DC Drive User Manual, publication 20P-UM001Information on installing, programming, and technical
Getting Results with RSLinx Guide, publication LINX-GR001and online help
RSLogix Emulate 5/500 Getting Results Guide, publication EMULAT-GR002 and online helpInformation on how to install and navigate the RSLogix
RSLogix 500 Getting Results Guide, publication LG500-GR002 and online help
RSLogix 5000 PIDE Autotuner Getting Results Guide, publication PIDE-GR001 and online help
(1)
(1)
(1)
Information on installing, programming, and technical
data of PowerFlex 700S drives.
data of PowerFlex 700L Liquid-Cooled AC drives.
data of SMC Flex State Smart Motor Controller.
data of SMC-50 Solid-State Smart Motor Controller.
data of PowerFlex Digital DC drives.
Information on using RSLinx Classic software.
Emulate software for ladder logic programming with
Allen-Bradley
Information on using RSLogix 500 software tool.
Information on using RSLogix 5000 software tool.
®
PLC-5® and SLC™ 500 processors.
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001Information on using the ControlLogix® 1756-ENBT or
1756-EN2T EtherNet/IP communication modules with
your Logix5000 controller and communicating with
various devices on the EtherNet/IP network.
Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785UM012
MicroLogix 1100 Programmable Controllers User Manual, publication 1763-UM001
MicroLogix 1400 Programmable Controllers User Manual, publication 1766-UM001
Web Updates http://www.ab.com/support/abdrives/webupdate/Flash Update Files, Product Help Files, Control Bar
(1) Use this link to the ODVA EtherNet/IP library: http://odva.org/Home/ODVATECHNOLOGIES/EtherNetIP/EtherNetIPLibrary/tabid/76/Default.aspx
Information to help design, operate and maintain an
Enhanced and Ethernet PLC-5 programmable controller
system.
Information to install, wire, and troubleshoot the
MicroLogix™ 1100 and MicroLogix 1400 controllers
respectively.
Files, GSD Files, EDS File links, DriveTools SP / Drive
AOP Database Files, and other downloads to keep your
Allen-Bradley brand drive products up to date
Documentation can be obtained online at http://
literature.rockwellautomation.com. To order paper copies of technical
documentation, contact your local Rockwell Automation distributor or sales
representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations
.
For information such as firmware updates or answers to drive-related questions,
go to the Drives Service & Support web site at http://www.ab.com/support/
abdrives and click on the Downloads or Knowledgebase link.
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 20139
Preface
Notes:
10Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013
Chapter
➊
➋
➌
➍
➎
1
Getting Started
The adapter is intended for installation in a PowerFlex 7-Class drive or Bulletin
150 SMC soft starter and is used for network communication.
TopicPage
Components11
Features12
Compatible Products13
Required Equipment13
Safety Precautions15
Quick Start16
Components
Item PartDescription
Status IndicatorsFour status indicators that indicate the status of the DPI, the
➊
DPI ConnectorA 20-pin, single-row shrouded male header. An Internal Interface
➋
Ethernet ConnectorRJ-45 connector for the Ethernet network cable. The connector is
➌
Web Pages Switch
➍
(SW4)
Address/mode
➎
switches
adapter, and network connection. See Chapter 7
cable is connected to this connector and a connector on the drive.
CAT-5 compliant to ensure reliable data transfer on 100Base-TX
Ethernet connections.
Enables or disables the adapter web pages. See Setting the Web
Pages Switch on page 19.
Set IP address or DHCP/BootP mode.
, Troubleshooting.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201311
Chapter 1 Getting Started
Features
The features of the adapter include the following:
• Typical mounting in a PowerFlex 7-Class drive or SMC soft starter.
• Captive screws to secure and ground the adapter to the drive.
• Compatibility with various configuration tools to configure the adapter
and connected host drive, including the following tools:
– PowerFlex HIM (Human Interface Module) on the drive or SMC, if
available
– Connected Components Workbench software, version 1.02 or later
– DriveExplorer software, version 2.01 or later
– DriveExecutive software, version 3.01 or later
– RSLogix5000 version16 and later with Drives Add-on Profile version
4.05 and later
Additionally, you can use a BOOTP/DHCP server to configure the
network address for the adapter.
• Status indicators that report the status of the drive communications, the
adapter, and network. They are visible when the drive cover is open or closed.
• Parameter-configured I/O (Logic Command/Reference and up to four
pairs of Datalinks) to accommodate application requirements.
• Explicit Messaging support.
• Master-Slave or Peer-to-Peer hierarchy that can be configured to transmit
data to and from either a controller or another PowerFlex drive or SMC on
the network.
• User-defined fault actions to determine how the adapter and connected
PowerFlex drive respond to the following:
– I/O messaging communication disruptions (Comm Flt Action)
– Controllers in idle mode (Idle Flt Action)
• Web pages, viewed by using a web browser, that show information about the
adapter, its connected host drive, and DPI devices connected to the drive.
• Configurable e-mail messaging to desired addresses when selected drive
faults occur and/or are cleared, and/or when the adapter takes a
communication or idle fault action.
• Access to any PowerFlex drive or SMC and its connected peripherals on
the network to which the adapter is connected.
• Device Level Ring (DLR) or Star Topology support with Quality of
Service (QoS) support.
12Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Getting Started Chapter 1
Compatible Products
Required Equipment
At the time of publication, the adapter is compatible with the following products:
• PowerFlex 70/70EC drives• PowerFlex 700L drives
• PowerFlex 700/700VC drives• PowerFlex Digital DC drives
• PowerFlex 700H drives• DPI External Comms Kit
• PowerFlex 700S drives• SMC™-50
• PowerFlex 7000/7000-2 drives• SMC™ Flex
Note: The adapter is not compatible with PowerFlex 750 series drives.
Some of the equipment that is required for use with the adapter is shipped with
the adapter, but some you must supply yourself.
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes the following:
❑ One 20-COMM-ER EtherNet/IP adapter
❑ One 2.54 cm (1 in.) long and one 15.24 cm (6 in.) long Internal Interface
cable (only one cable is needed to connect the adapter to the drive; for which
cable to use, see Figure 3 - on page 2-21
)
❑ One PowerFlex 7-Class DPI (Drive Peripheral Interface) Network
Communication Adapter Installation Instructions, publication 20COMMIN004
❑ One LED Identification Label for use with Bulletin 150 SMC Flex and
Bulletin 700 PowerFlex drives
User-Supplied Equipment
To install and configure the adapter, you must supply the following:
❑ A small flathead screwdriver
❑ Ethernet cable (for details, see the EtherNet/IP Media Planning and
Installation Manual, ODVA publication 148 available on the ODVA
website at http://odva.org/Home/ODVATECHNOLOGIES/
. There
are no plans to provide future updates to this tool and the download is
being provided ‘as-is’ for users that lost their DriveExplorer CD, or need
to configure legacy products not supported by Connected Components
Workbench software.
– DriveExecutive software, version 3.01 or later
A Lite version of DriveExecutive software ships with RSLogix 5000,
RSNetWorx MD, FactoryTalk AssetCentre, and ItelliCENTER
software. All other versions are purchasable items:
• 9303-4DTE01ENE Drive Executive software
• 9303-4DTS01ENE DriveTools SP Suite (includes DriveExecutive
and DriveObserver software)
• 9303-4DTE2S01ENE DriveExecutive software upgrade to
DriveTools SP Suite (adds DriveObserver software)
DriveExecutive software updates (patches, and so forth) can be obtained
at http://www.ab.com/support/abdrives/webupdate/software.html
highly recommended that you periodically check for and install the latest
update.
– BOOTP server, version 2.1 or higher, for network setup only
❑ Controller configuration software, such as RSLogix 5/500/5000
❑ A computer connection to the EtherNet/IP network
. It is
14Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Getting Started Chapter 1
Safety Precautions
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may
contain high voltages that can cause injury or death. Remove all power
from the PowerFlex drive or SMC, and then verify power has been
discharged before installing or removing an adapter.
ATTENTION: Risk of injury or equipment damage exists. Only personnel
familiar with drive and power products and the associated machinery
should plan or implement the installation, start up, configuration, and
subsequent maintenance of the product using an adapter. Failure to comply
may result in injury and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The adapter contains
electrostatic discharge (ESD) sensitive parts that can be damaged if you do
not follow ESD control procedures. Static control precautions are required
when handling the adapter. If you are unfamiliar with static control
procedures, see Guarding Against Electrostatic Damage, publication 8000-
4.5.2.
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting control I/O to the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting an
adapter.
ATTENTION: Risk of injury or equipment damage exists. Parameters 21 -
[Comm Flt Action], 24 - [Idle Flt Action], and 43 - [Peer Flt Action] let
you determine the action of the adapter and connected drive if
communication is disrupted or the controller is idle. By default, these
parameters fault the drive. You may configure these parameters so that the
drive continues to run, however, precautions should be taken to ensure that
the settings of these parameters do not create a risk of injury or equipment
damage. When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable or a
controller in idle state).
ATTENTION: Risk of injury or equipment damage exists. When a system is
configured for the first time, there may be unintended or incorrect machine
motion. Disconnect the motor from the machine or process during initial
system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in
this publication are intended solely for purposes of example. There are
many variables and requirements with any application. Rockwell
Automation, Inc. does not assume responsibility or liability (to include
intellectual property liability) for actual use of the examples shown in this
publication.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201315
Chapter 1 Getting Started
Quick Start
This section is provided to help experienced users quickly start using the adapter.
If you are unsure how to complete a step, refer to the referenced chapter.
Step ActionSee
1Review the safety precautions for the drive or SMCDrive or SMC User
Manual
2Review the safety precautions for the adapterThroughout this manual
3Verify that the power control device is properly installed.Drive or SMC User
4Install the adapter.
a. Verify that the power control device is not powered.
b. Connect the adapter to the device with the Internal Interface
cable.
c. Use the captive screws to secure and ground the adapter to
the device.
d. Connect the adapter to the network with an Ethernet cable.
NOTE: When installing the adapter in the DPI External Comms
Kit—see the 20-XCOMM-DC-BASE Installation Instructions,
publication 20COMM-IN001, supplied with the kit.
5Apply power to the adapter.
a. Verify that the adapter is installed correctly.
b. The adapter receives power from the drive or SMC. Apply
power to the device.
The status indicators should be green. If they flash red, there
is a problem. See Chapter 7
c. Configure and verify key drive or SMC parameters.
6Configure the adapter for your application.
Set adapter parameters for the following functions as required by
your application:
• IP address, subnet mask, and gateway address
• Data rate
• I/O configuration
• Master-Slave or Peer-to-Peer hierarchy
• Fault actions
7Configure the controller to communicate with the adapter.
Use a controller configuration tool, such as RSLogix software, to
configure the master on the network to recognize the adapter and
drive or SMC.
8Create a ladder logic program.
Use a controller configuration tool, such as RSLogix software, to
create a ladder logic program that enables you to do the
following:
• Control the connected device, via the adapter, by using I/O.
• Monitor or configure the device or SMC by using explicit
messages.
, Troubleshooting.
Manual
PowerFlex 7-Class DPI
Network Communication
Adapter Installation
Instructions, publication
20COMM-IN004, and
Chapter 2
Installing the Adapter
Chapter 2
Installing the Adapter
Chapter 3,
Configuring the Adapter
Chapter 4
Configuring the I/O
Chapter 5
Using the I/O
Chapter 6,
Using Explicit
Messaging
,
,
,
,
16Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Chapter
Installing the Adapter
This chapter provides instructions for installing the adapter in a PowerFlex 7Class drive.
TopicPage
Preparing for an Installation
Setting the Web Pages Switch19
Connecting the Adapter to the Drive or SMC20
Connecting the Adapter to the Network23
Applying Power24
Commissioning the Adapter26
18
2
EMC Conformance
For all PowerFlex 70 and 700 drive installations that require CE conformance per
EN61800-3, a ferrite core must be installed on each EtherNet/IP cable connected
to the drive.
These ferrites are not required for installation on SMC products.
A ferrite core such as FAIR-RITE part number 2643803802 needs to be installed
according to the following diagram.
Note: the cable is wrapped 4 times around each core.
Figure 1 - Ferrite Core Installation
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201317
Chapter 2 Installing the Adapter
Preparing for an
Installation
Before installing the adapter, do the following:
• Make sure the Ethernet switch is the correct type. A ‘managed’ switch that
supports IGMP snooping is usually recommended. An ‘unmanaged’
switch can be used instead if RSLogix 5000 software, version 18.00 or
later, is used and all devices on the network are configured for ‘unicast’
I/O. For more details, see the following documents:
– EtherNet/IP Media Planning and Installation Manual,
The 20-COMM-ER adapter is a multicast device. In most situations, an
IGMP snooping (managed) switch is required. If more than one or two
20-COMM-ER adapters are connected to the switch, a managed switch is
required—otherwise the drive may fault on a DPI Port x network loss. The
20-COMM-ER, RSLogix 5000 software, version 18.00 or later, and a
ControlLogix or CompactLogix controller will support unicast. Unicast
setup is required when adding the drive to the I/O. When all adapters are
set up as unicast devices, then an IGMP snooping (managed) switch is not
needed.
Much of EtherNet/IP implicit (I/O) messaging uses IP multicast to
distribute I/O control data, which is consistent with the CIP producer/
consumer model. Historically, most switches have treated multicast
packets the same as broadcast packets. That is, all multicast packets are retransmitted to all ports.
IGMP snooping constrains the flooding of multicast traffic by dynamically
configuring switch ports so that multicast traffic is forwarded only to ports
associated with a particular IP multicast group.
Switches that support IGMP snooping (managed switches) ‘learn’ which
ports have devices that are part of a particular multicast group and only
forward the multicast packets to the ports that are part of the multicast
group.
Be careful as to what level of support a switch has of IGMP snooping.
Some layer 2 switches that support IGMP snooping require a router
(which could be a layer 3 switch) to send out IGMP polls to learn what
devices are part of the multicast group. Some layer 2 switches can use
IGMP snooping without a router sending polls. If your control system is a
standalone network or is required to continue performing if the router is
out of service, make sure the switch you are using supports IGMP
snooping without a router being present.
18Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Installing the Adapter Chapter 2
1
O
N
Web Pages
Switch
Up Position =
Disable
Down Position =
Enable
• See Appendix A for the number of CIP connections supported by the 20-
COMM-ER adapter.
Setting the Web Pages
Switch
• Verify that you have all required equipment. See Required Equipment
on
page 13.
To use the adapter web pages, the Web Pages Switch must be set to its ‘Enable
Web’ position. For information to enable or disable web pages for an adapter, see
Setting Web Access Control
ATTENTION: Risk of equipment damage exists. The adapter contains
electrostatic discharge (ESD) sensitive parts that can be damaged if you do
not follow ESD control procedures. Static control precautions are required
when handling the adapter. If you are unfamiliar with static control
procedures, see Guarding Against Electrostatic Damage, publication 8000-
4.5.2.
on page 42.
Important:A new switch setting is recognized only when power is applied
to the adapter, or the adapter is reset. If you change a switch
setting, cycle power or reset the adapter to apply the change.
Set the Web Pages Switch (SW4 in Figure 2
) to enable or disable the adapter web
pages. By default, the adapter web pages are disabled. For complete details on
adapter web pages, see Viewing the Adapter Web Pages
on page 153.
Figure 2 - Setting Web Pages Switch (only Series B Adapter)
SettingDescription
Down (OFF) positionWeb server enabled
Up (ON) positionWeb server disabled (as shipped)
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201319
Chapter 2 Installing the Adapter
Connecting the Adapter to
the Drive or SMC
ATTENTION: Risk of injury or death exists. The PowerFlex drive or SMC
may contain high voltages that can cause injury or death. Remove ALL
power from the drive or SMC, and then verify power has been discharged
before installing or removing the adapter.
1. Remove ALL power from the drive or SMC.
2. Use static control precautions.
3. Remove the drive or SMC cover or open the drive door.
4. Connect the Internal Interface cable to the DPI port on the drive and then
to the DPI connector on the adapter (see Figure 3
5. Secure and ground the adapter to the drive or SMC (see Figure 4
the following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive
screws.
– On an SMC Flex, put the wire lug between the mounting screw and
20-COMM-ER board
Important: Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 N•m (8.0 lb•in).
).
) by doing
20Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
➋
➌
➍
➊
X1
X2
➍
20-COMM-ER Adapter
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
PowerFlex 70 - All Frames
PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6
HIM panel opens to
allow access to DPI
interface. To open panel,
remove screws on left
side of HIM panel and
swing open.
PowerFlex 700H Frames 9 and Larger
SMC Flex
SMC-50
Place ground
wire tab
between
mounting
screw and
circuit board
Installing the Adapter Chapter 2
Figure 3 - DPI Ports and Internal Interface Cables
ItemDescription
➊
➋
➌
➍
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201321
15.24 cm (6 in.) Internal Interface cable
DPI Connector
Ethernet cable
2.54 cm (1 in.) Internal Interface cable
Chapter 2 Installing the Adapter
X1
X2
Drive
Adapter
Internal Interface Cable
folded behind the adapter
and in front of the drive.
PowerFlex 70 - All Frame Sizes
(Adapter mounts in drive.)
Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw,
verify continuity exists between the
head of the screw and drive ground.
Ground Tab Detail
PowerFlex 700 Frames 0 and 1
PowerFlex 700S Frames 0 and 1
(Adapter mounts on door.)
0.9 N•m
(8.0 lb•in)
PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6
(Adapter mounts in drive.)
0.9 N•m (8.0
lb•in) 4 Places
Verify metal ground tab is bent 90° and is under
the adapter before tightening screw. After
tightening the screw, verify continuity exists
between the head of the screw and drive ground.
0.9 N•m
(8.0 lb•in)
4 Places
PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger
(Adapter mounts behind HIM panel.)
Ground Tab Detail
Figure 4 - Mounting and Grounding the Adapter
22Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Installing the Adapter Chapter 2
Controller
(ControlLogix controller
shown with 1756-EN2TR Bridge)
Drive or SMC
(1)
(with 20-COMM-ER Option Modules)
Ethernet
Switch
Computer with
Ethernet Connection
To o ther
EtherNet/IP
networks
(1)
The option module’s ENET1 and
ENET2 network ports are used.
Control ler
(ControlLogix controller
shown with 1756-EN2TR Bridge)
Drive or SMC
(1)
(with 20-COMM-ER Option Modules)
Computer with
Ethernet Connection
To o th er
EtherNet/IP
networks
1783-ETAP
1783-ETAP
(1)
The option module’s ENET1 and
ENET2 network ports are used.
Connecting the Adapter to
the Network
ATTENTION: Risk of injury or death exists. The PowerFlex drive may
contain high voltages that can cause injury or death. Remove power from
the drive, and then verify power has been discharged before installing or
removing the adapter.
1. Remove power from the drive.
2. Use static control precautions.
3. Connect one end of an Ethernet cable to the network. See Figure 5
example of wiring to an EtherNet/IP network.
Figure 5 - Connecting the Ethernet Cable in a Linear Topology Network
for an
Figure 6 - Connecting the Ethernet Cable in a DLR Topology Network
4. For Linear or DLR Network Topology, route the other end of the Ethernet
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201323
cable from the network through the bottom of the first drive, and insert its
cable plug into the option module ENET1 network port.
Chapter 2 Installing the Adapter
➋
➊
PS
NS
STS
LS1
LS2
To connect to the second drive, attach another Ethernet cable between
the first drive’s option module ENET2 network port and the second
drive’s option module ENET1 network port.
To connect additional drives, repeat these daisy-chain connections in
the same way.
5. Route the other end of the Ethernet cable through the bottom of the
PowerFlex drive (Figure 4
) and insert its Ethernet cable plug into the mating
adapter receptacle.
Applying Power
ATTENTION: Risk of equipment damage, injury, or death exists.
Unpredictable operation may occur if you fail to verify that parameter
settings are compatible with your application. Verify that settings are
compatible with your application before applying power to the drive.
Install the device cover or close the drive door, and apply power to the device. The
adapter receives its power from the connected device. When you apply power to
the adapter for the first time, its topmost PORT status indicator should be steady
green or flashing green after an initialization. If it is red, there is a problem. See
Chapter 7
, Troubleshooting.
Start-Up Status Indications
After power has been applied, the status indicators for the device and
communications adapter can be viewed on the front of the device
(Figure 7
Figure 7 - Drive and Adapter Status Indicators (location will vary by device)
). Possible start-up status indications are shown in Ta b l e 1 .
24Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Table 1 - Drive and Adapter Start-Up Status Indications
ItemNameColorStateDescription
STS (Status)
➊
refer to drive
or SMC
manual for
status
indication
information)
PSOffSteadyNo power
➋
NSOffSteadyNo power OR no IP Address
LS1OffSteadyNo Network Activity
LS2OffSteadyNo Network Activity
GreenFlashingDevice ready but not running, and no faults are present.
SteadyDevice running, no faults are present.
YellowFlashing,
device stopped
Flashing,
device running
Steady,
device running
RedFlashingA fault has occurred.
SteadyA non-resettable fault has occurred.
Orange FlashingRequesting DPI I/O Connections
SteadyPeripheral is Connected to an incompatible product or no DPI ping events are detected.
GreenFlashingNormal Operation (DPI connected) - No I/O, or PLC in Program
RedFlashingDPI Problem, Bad CRC of Adapter Parameters or Flash Program
SteadyDPI Failure or Failed power-on diagnostic test (hardware failure)
Green/
Red
GreenFlashingAn IP address is configured, but no CIP connections are established, and an Exclusive Owner
RedFlashingConnection has timed out see the “The EtherNet Adaptation of CIP” Specification sections 9-4.4
Orange SteadyAdapter Failure (used in conjunction with PS orange)
Green/
Red
GreenFlashingNetwork activity at 100 Mbps
YellowFlashingNetwork activity at 10 Mbps
GreenFlashingNetwork activity at 100 Mbps
YellowFlashingNetwork activity at 10 Mbps
FlashingFlash update in progress
SteadyAt least one CIP connection (any transport class) is established, and an Exclusive Owner
SteadyDuplicate IP Address detected
FlashingSelf-test on power up
An inhibit condition exists – the drive cannot be started. Check device Parameter 214 - [Start
Inhibits].
An intermittent type 1 alarm condition is occurring. Check device Parameter 211 - [Drive Alarm 1].
A continuous type 1 alarm condition exists. Check device Parameter 211 - [Drive Alarm 1].
Adapter Status Indicators
connection has not timed out
connection has not timed out
for detailed behavior description
Installing the Adapter Chapter 2
Drive STS Indicator
After verifying correct operation, close or install the drive cover. For more details
on status indicator operation, see page 144
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201325
and page 145.
Chapter 2 Installing the Adapter
Configuring and Verifying Key Drive Parameters
The PowerFlex 7-Class drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the drive
to have its control come from a peripheral or terminal block with the Reference
coming from the network. Or you could set the drive to have its control come
from the network with the Reference coming from another peripheral or
terminal block. Or you could set the drive to have both its control and Reference
come from the network.
The following steps in this section assume that the drive will receive the Logic
Command and Reference from the network.
1. Use drive Parameter 090 - [Speed Ref A Sel] to set the drive speed
Reference to ‘22’ (DPI Port 5).
2. If hard-wired discrete digital inputs are not used to control the drive, verify
that unused digital input drive Parameters 361 - [Dig In1 Sel] and 362 [Dig In2 Sel] are set to ‘0’ (Not Used).
Commissioning the Adapter
3. Verify that drive Parameter 213 - [Speed Ref Source] is reporting that the
source of the Reference to the drive is ‘22’ (DPI Port 5).
This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded Speed]. If a
problem occurs, this verification step provides the diagnostic capability
to determine whether the drive/adapter or the network is the cause.
To commission the adapter, you must set a unique IP address on the network.
After installing the adapter and applying power, you can set the IP address by
using a BOOTP/DHCP server or adapter parameters. See Setting the IP
Address, Subnet Mask, and Gateway Address on page 32 for details.
By default, the adapter is configured so that you must set the IP address using a
BOOTP/DHCP server or by setting the adapter to a valid address, 1-254, via the
rotary switches on the adapter. An invalid address 0 or >254 will cause the
module to defer to the addressing mode selected by parameter 3 [BOOTP/
DHCP]. If disabled, the adapter will use the address information stored in the
adapters database. If that address is invalid, the adapter will try to contact a
DHCP server on the network. To use adapter parameters, you must disable the
BOOTP feature. For details, see Disable the BOOTP Feature
Important:New settings for some adapter parameters (for example,
Parameters 04 - [IP Addr Cfg 1] through 07 - [IP Addr Cfg
4]) are recognized only when power is applied to the adapter or
it is reset. After you change parameter settings, cycle power or
reset the adapter.
on page 32.
26Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Chapter
3
Configuring the Adapter
This chapter provides instructions and information for setting the parameters in
the adapter.
TopicPage
Configuration Tools
Using the PowerFlex 7-Class HIM28
Using BOOTP29
Setting the IP Address, Subnet Mask, and Gateway Address32
Setting the Data Rate34
Setting the I/O Configuration35
Selecting Master-Slave or Peer-to-Peer36
Setting the Reference Adjustment41
Setting a Fault Action41
Setting Web Access Control42
Resetting the Adapter43
Viewing the Adapter Status Using Parameters44
Updating the Adapter Firmware44
27
Configuration Tools
For a list of parameters, see Appendix
B, Adapter Parameters. For definitions of
terms in this chapter, see the .
The adapter stores parameters and other information in its own nonvolatile
storage (NVS) memory. You must, therefore, access the adapter to view and edit
its parameters. The following tools can be used to access the adapter parameters.
ToolSee
PowerFlex 7-Class HIMpage 28
BOOTP/DHCP serverpage 29
Connected Components Workbench
software, version 1.02 or later
http://www.ab.com/support/abdrives/webupdate/
software.html, or online help (installed with the software)
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201327
Chapter 3 Configuring the Adapter
F-> StoppedAuto
0.00Hz
Main Menu:
Diagnostics
Parameter
Device Select
Port 5 Device
20-COMM-ER
Main Menu:
Diagnostics
Parameter
Device Select
TIP
Using the PowerFlex 7Class HIM
If your drive has either an LED or LCD HIM (Human Interface Module), it can
be used to access parameters in the adapter as shown below. It is recommended
that you read through the steps for your HIM before performing the sequence.
For additional information, see the drive documentation or the PowerFlex 7Class HIM Quick Reference, publication 20HIM-QR001.
Using an LED HIM
StepExample Screens
1. Press the key and then the Device (Sel) key to
display the Device Screen.
2. Press the or key to scroll to the adapter. Letters
represent files in the drive, and numbers represent ports. The
adapter is usually connected to port 5.
3. Press the (Enter) key to enter your selection. A
parameter database is constructed, and then the first
parameter is displayed.
4. Edit the parameters using the same techniques that you use to
edit drive parameters.
ALT
Sel
28Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using an LCD HIM
StepExample Screens
1. In the main menu, press the or key to scroll to
Device Select.
2. Press the (Enter) key to enter your selection.
3. Press the or key to scroll to the adapter (20COMM-ER).
4. Press the (Enter) key to select the adapter.
A parameter database is constructed, and then the main
menu for the adapter is displayed.
5. Edit the parameters using the same techniques that you use to
edit drive parameters.
NOTE: All configuration procedures throughout this chapter use the PowerFlex
7-Class LCD HIM to access parameters in the adapter and show example LCD
HIM screens.
When using a PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, see its User Manual,
publication 20-HIM-UM001.
SMC Flex controllers require an external HIM (A3 or A6) to program the
adapter. The internal Human Interface of the SMC Flex does not allow
programming of the Adapter.
Configuring the Adapter Chapter 3
TIP
Using BOOTP
The IP address, subnet mask and gateway address can be configured multiple
ways depending on the setting of the three rotary switches on the adapter. The
switches are read on power up or reset.
1. If the switches are set to an address from 1…254, that value will be used as
the LSB of the IP address 192.168.1.xxx
2. If the switches are set to an invalid number (000 or a value greater than
254), the unit will check if DHCP is enabled. If DHCP is enabled, the
unit requests an address from a DHCP server.
If DHCP is not enabled and switches are set to an illegal value, the adapter
will use the IP address (along with other TCP configurable parameters)
stored in nonvolatile memory. If the unit finds that the stored IP
configuration is not usable (set to 0), then the unit will revert to the out-ofbox behavior of DHCP being enabled.
3. Any other switch setting will cause the adapter to use the IP address data
set in the adapter's database parameters.
By default, the adapter is configured so that you can set its IP address, subnet
mask, and gateway address by using a BOOTP or a DHCP server. There is a
variety of BOOTP servers available. The following instructions use Rockwell
Automation’s BOOTP Server, version 2.3 or later, a free standalone program that
incorporates the functionality of standard BOOTP utilities with a graphical
interface. It is available from http://www.software.rockwell.com/support/
download/detail.cfm?ID=3390. See the Readme file and online Help for
directions and more information.
If desired, you can disable BOOTP and configure the IP address, subnet mask, and
gateway address with adapter parameters. For details, see Setting the IP Address,
Subnet Mask, and Gateway Address on page 32.
Configure the Adapter Using a BOOTP Server
1. On the adapter label, note the adapter’s hardware Ethernet Address
(MAC), which will be used in step 6.
2. On a computer connected to the EtherNet/IP network, start the BOOTP
software.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201329
Chapter 3 Configuring the Adapter
The BOOTP Server window appears.
3. Select To o ls > Ne t wo r k S e tt in gs to display the Network Settings window.
To properly configure devices on your EtherNet/IP network, you must
configure settings in the BOOTP software to match the network.
4. Edit the following:
BoxType
(1)
Subnet Mask
Gateway
Primary DNSThe address of the primary DNS server to be used on the local end of
Secondary DNSOptional — the address of the secondary DNS server to be used on the
Domain NameThe text name corresponding to the numeric IP address that was
(1)
The subnet mask for the adapter’s network.
The IP address of the gateway device on the adapter’s network.
the link for negotiating with remote devices.
local end of the link for negotiating with remote devices when the primary
DNS server is unavailable.
assigned to the server that controls the network.
(1) For definitions of these terms, refer to the .
5. Click OK to apply the settings.
Devices on the network issuing BOOTP requests appear in the BOOTP
Request History list.
30Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the Adapter Chapter 3
TIP
6. In the BOOTP Request History list, either double-click the adapter’s
Ethernet Address (MAC) noted in Step 1, or click New in the Relation
List.
The New Entry dialog box appears.
In the first case, the Ethernet Address (MAC) is automatically entered. In
the latter case, you must manually enter it.
7. Edit the following:
Box Type
IP AddressA unique IP address for the adapter
Host NameOptional
DescriptionOptional
8. Click OK to apply the settings.
The adapter appears in the Relation List with the new settings.
9. To assign this configuration to the adapter permanently, select the device
in the Relation List and click Disable BOOTP/DHCP.
When power is cycled on the adapter, it will use the configuration you
assigned it and not issue new BOOTP requests.
To enable BOOTP for an adapter that has had BOOTP disabled, first select the
adapter in the Relation List, then click Enable BOOTP, and lastly reset the adapter
or power cycle the drive.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201331
Chapter 3 Configuring the Adapter
ValueSetting
0Disabled
1Enabled (Default)
Port 5 Device
20-COMM-ER
Parameter #: 03
BOOTP
0
Disabled
10. Select File > Save to save the Relation List.
Setting the IP Address,
Subnet Mask, and Gateway
Address
By default, the adapter is configured so that you set its IP address, subnet mask,
and gateway address using a BOOTP/DHCP server. To use adapter parameters
instead, you must disable BOOTP/DHCP and then set the associated adapter
parameters.
The IP address can be set using the rotary switches on the adapter to an address
from 1…254 that will be used as the lower byte of the IP address 192.168.1.xxx.
The Subnet mask will be set to 255.255.255.0.
If the rotary switches are set to any invalid address (0 or >254), the address
programmed in the adapter's internal data base will be used.
Disable the BOOTP Feature
1. Set the value of Parameter 03 - [BOOTP/DHCP] to ‘0’ (Disabled).
32Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Note: The internal port used by the adapter is different for different
products. The examples here show port 5, used by the SMC Flex and drive
products. The SMC-50 uses port 4.
2. Reset the adapter; see Resetting the Adapter
on page 43.
After disabling the BOOTP/DHCP feature, you can then configure the
IP address, subnet mask, and gateway address using adapter parameters.
Set an IP Address Using Parameters
1. Veri fy t ha t Parameter 03 - [BOOTP/DHCP] is set to ‘0’ (Disabled).
Configuring the Adapter Chapter 3
Port 5 Device
20-COMM-ER
Parameter #: 04
IP Addr Cfg 1
0
0 <> 255
Default = 0.0.0.0255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Port 5 Device
20-COMM-ER
Parameter #: 08
Subnet Cfg 1
0
0 <> 255
Default = 0.0.0.0
255.255.255.255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Port 5 Device
20-COMM-ER
Parameter #: 12
Gateway Cfg 1
0
0 <> 255
Default = 0.0.0.0
255.255.255.255
[Gateway Cfg
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
2. Set the value of Parameters 04 - [IP Addr Cfg 1] through 07 - [IP Addr
Cfg 4] to a unique IP address.
3. Reset the adapter; see Resetting the Adapter
on page 43.
The Network status indicator will be steady green or flashing green if
the IP address is correctly configured, and is connected to an operating
ethernet network.
Set a Subnet Mask Using Parameters
1. Veri fy t ha t Parameter 03 - [BOOTP/DHCP] is set to ‘0’ (Disabled).
2. Set the value of Parameters 08 - [Subnet Cfg 1] through 11 - [Subnet Cfg
4] to the desired value for the subnet mask.
3. Reset the adapter; see Resetting the Adapter
on page 43.
Set a Gateway Address Using Parameters
1. Veri fy t ha t Parameter 03 - [BOOTP] is set to ‘0’ (Disabled).
2. Set the value of Parameters 12 - [Gateway Cfg 1] through 15 - [Gateway
3. Reset the adapter; see Resetting the Adapter
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201333
Cfg 4] to the IP address of the gateway device.
on page 43.
Chapter 3 Configuring the Adapter
ValueData Rate
0Autodetect (default)
110 Mbps Full
210 Mbps Half
3100 Mbps Full
4100 Mbps Half
Port 5 Device
20-COMM-ER
Parameter #: 16
EN P1 Rate Config
0
Autodetect
TIP
ValueData Rate
0Autodetect (default)
110 Mbps Full
210 Mbps Half
3100 Mbps Full
4100 Mbps Half
Port 5 Device
20-COMM-ER
Parameter #: 18
EN P2 Rate Config
0
Autodetect
TIP
Setting the Data Rate
By default, the adapter is set to autodetect, so it automatically detects the data rate
and duplex setting used on the network. If you need to set a specific data rate and
duplex setting, the value of Parameter 16 - [EN P1 Rate Config] determines the
Ethernet data rate and duplex setting that the adapter will use to communicate. For
definitions of data rate and duplex, see Glossary on page 221
.
1. Set the value of Parameter 16 - [EN P1 Rate Config] to the data rate at
which your network is operating.
Auto detection of baud rate and duplex works properly only if the device (usually a
switch) on the other end of the cable is also set to automatically detect the baud
rate/duplex. If one device has the baud rate/duplex hard-coded, the other device
must be hard-coded to the same settings.
2. Reset the adapter; see Resetting the Adapter
on page 43.
By default, the adapter is set to autodetect, so it automatically detects the data rate
and duplex setting used on the network. If you need to set a specific data rate and
duplex setting, the value of Parameter 18 - [EN P2 Rate Config] determines the
Ethernet data rate and duplex setting that the adapter will use to communicate. For
definitions of data rate and duplex, see Glossary on page 221
.
1. Set the value of Parameter 18 - [ENEN P2 Rate Config] to the data rate
at which your network is operating.
Auto detection of baud rate and duplex works properly only if the device (usually a
switch) on the other end of the cable is also set to automatically detect the baud
rate/duplex. If one device has the baud rate/duplex hard-coded, the other device
must be hard-coded to the same settings.
2. Reset the adapter; see Resetting the Adapter
on page 43.
34Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the Adapter Chapter 3
BitDescription
0Logic Command/Reference (Default)
1Datalink A
2Datalink B
3Datalink C
4Datalink D
5…15Not Used
Port 5 Device
20-COMM-ER
Parameter #: 25
DPI I/O Cfg
xxxxxxxxxxx0000
1
Cmd/Refb00
Setting the I/O
Configuration
The I/O configuration determines the data that is sent to and from the drive.
Logic Command/Status, Reference/Feedback, and Datalinks may be enabled or
disabled. (Datalinks allow you to read/write directly to parameters in the drive
using implicit I/O.) A ‘1’ enables the I/O and a ‘0’ disables the I/O.
1. Set the bits in Parameter 25 - [DPI I/O Cfg].
Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.
2. If a controller is used to control the drive, set adapter Parameters 37 - [M-
S Input] and 38 - [M-S Output] for Master-Slave Hierarchy.
For details, see Setting a Master-Slave Hierarchy (Scanner-to-Drive
Communication) on page 36.
3. If Logic Command/Reference is enabled, configure the parameters in the
drive to accept the Logic Command and Reference from the adapter.
For example, set Parameter 90 - [Speed Ref A Sel] in a Po werFle x 70 or
700 drive to ‘22’ (DPI Port 5) so that the drive uses the Reference from
the adapter. Also, verify that the mask parameters (for example,
Parameter 276 - [Logic Mask]) in the drive are configured to recei ve the
desired logic from the adapter . See the documentati on for your drive for
details.
The the SMC devices do not currently use the reference data sent in the
IO frame. No reference configuration is required. Refer to the
applicable SMC user manual for the latest reference configuration
information.
4. If you enabled one or more Datalinks, configure parameters in the drive to
determine the source and destination of data in the Datalink(s).
When using Datalinks, up to 8 [Data In xx] parameters and/or up to 8
[Data Out xx] parameters must be assigned to point to the appropriate
parameters for your application. See Chapter 4
5. Reset the adapter; see Resetting the Adapter
for an example.
on page 43.
The adapter is ready to receive I/O. You must now configure the adapter to
receive I/O from a master or peer device. See Selecting Master-Slave or Peer-to-
Peer. If you select a Master-Slave hierarchy, you must also configure the master to
communicate with the adapter. See Chapter
4, Configuring the I/O.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201335
Chapter 3 Configuring the Adapter
BitDescription
0Logic Command/Reference (Default)
1Datalink A Input
2Datalink B Input
3Datalink C Input
4Datalink D Input
5…15Not Used
Port 5 Device
20-COMM-ER
Parameter #: 37
M-S Input
xxxxxxxxxxx0000
1
Cmd/Refb00
BitDescription
0Status/Feedback (Default)
1Datalink A Output
2Datalink B Output
3Datalink C Output
4Datalink D Output
5…15Not Used
Port 5 Device
20-COMM-ER
Parameter #: 38
M-S Output
xxxxxxxxxxx0000
1
Status/Fdbkb00
Selecting Master-Slave or
Peer-to-Peer
A hierarchy determines the type of device with which the adapter exchanges data.
In a Master-Slave hierarchy, the adapter exchanges data with a master, such as a
scanner or bridge (1756-ENBT, 1756-EN2T, 1747-L5-xxx, and so forth). In a
Peer-to-Peer hierarchy, the adapter exchanges data with one or more EtherNet/IP
adapters in other devices. (The devices must have compatible Logic Command/
Status words.)
For both Master-Slave and Peer-to-Peer hierarchies, the devices exchanging data
must be on the same IP subnet. See ‘IP Addresses’ in the for information about
IP subnets.
Setting a Master-Slave Hierarchy (Scanner-to-Drive
Communication)
1. Enable the desired I/O in Parameter 25 - [DPI I/O Cfg].
See Setting the I/O Configuration
2. Set the bits in Parameter 37 - [M-S Input].
This parameter determines the data received from the master by the
device. A ‘1’ enables the I/O and a ‘0’ disables the I/O.
on page 35.
36Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.
3. Set the bits in Parameter 38 - [M-S Output].
This parameter determines the data transmitted from the device to the
scanner. A ‘1’ enables the I/O and a ‘0’ disables the I/O.
Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.
4. Reset the adapter; see Resetting the Adapter
on page 43.
Configuring the Adapter Chapter 3
Value Setting
0Off (Default)
1On
Port 5 Device
20-COMM-ER
Parameter #: 53
Peer Out Enable
0
Off
Port 5 Device
20-COMM-ER
Parameter #: 51
Peer A Output
1
Cmd/Ref
ValueDescription
0Off (Default)
1Logic Command/Reference
2…5Datalink A, B, C, or D Input
6…9Datalink A, B, C, or D Output
Port 5 Device
20-COMM-ER
Parameter #: 52
Peer B Output
2
DL A Input
ValueDescription
0Off (Default)
1Logic Command/Reference
2…5Datalink A, B, C, or D Input
6…9Datalink A, B, C, or D Output
The adapter is ready to receive I/O from the master (that is, scanner). You must
now configure the scanner to recognize and transmit I/O to the adapter. See
Chapter
4, Configuring the I/O.
Setting the Adapter to Transmit Peer-to-Peer Data (Drive-to-Drive
Communication)
1. Veri fy t ha t Parameter 53 - [Peer Out Enable] is set to ‘0’ (Off).
This parameter must be Off while you configure peer output parameters.
2. Set Parameter 51 - [Peer A Output] to select the source of the data to
output to the network.
3. If desired, set Parameter 52 - [Peer B Output] to select an additional
4. Set Parameters 54 - [Peer Out Time] and 55 - [Peer Out Skip] to
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201337
source of the data to output to the network.
establish the minimum and maximum intervals between peer messages.
Chapter 3 Configuring the Adapter
Port 5 Device
20-COMM-ER
Parameter #: 54
Peer Out Time
2.00s
0 <> 10.00
Port 5 Device
20-COMM-ER
Parameter #: 55
Peer Out Skip
2
1 <>16
Default = 10.00 sDefault = 1
Value Setting
0Off (Default)
1On
Port 5 Device
20-COMM-ER
Parameter #: 49
Peer Inp Enable
0
Off
Because the adapter transmits peer messages when a change-of-state
condition occurs, minimum and maximum intervals are required.
– The minimum interval ensures that the adapter does not transmit
messages on the network too often, thus minimizing netwo rk traffic.
Set it with Parameter 54 - [Peer Out Time].
– The maximum interval ensures that the adapter transmits messages
often enough so that the receiving adapter(s) can receive recent data
and verify that communications are working or, if communications
are not working, can timeout. The maximum interval is the value of
Parameter 54 - [Peer Out Time] multiplied by the value of
Parameter 55 - [Peer Out Skip].
In the example below, the minimum interval is set to 2.00 seconds
(Parameter 54 - [Peer Out Time]), and the maximum interval is set to
4.00 seconds (2.00 x ‘2’ setting of Parameter 55 - [Peer Out Skip]).
5. Set Parameter 53 - [Peer Out Enable] to ‘1’ (On).
The adapter will transmit the data selected in Parameters 51 - [Peer A
Output] and 52 - [Peer B Output] to the network. Another adapter
must be configured to receive the peer I/O data.
Setting the Adapter to Receive Peer-to-Peer Data
1. Veri fy t ha t Parameter 49 - [Peer Inp Enable] is set to ‘0’ (Off ).
This parameter must be Off while you configure the peer input
parameters.
2. Set Parameters 44 - [Peer Inp Addr 1] through 47 - [Peer Inp Addr 4] to
the IP address of the node from which you want to receive data.
38Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the Adapter Chapter 3
Port 5 Device
20-COMM-ER
Parameter #: 44
Peer Inp Addr 1
0
0 <> 255
Default = 0.0.0.0
255.255.255.255
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]
IP Address of Node
Transmitting Peer I/O
Port 5 Device
20-COMM-ER
Parameter #: 40
Peer A Input
1
Cmd/Ref
ValueDescription
0Off (Default)
1Logic Command/Reference
2…5Datalink A, B, C, or D Input
Port 5 Device
20-COMM-ER
Parameter #: 41
Peer B Input
2
DL A Input
ValueDescription
0Off (Default)
1Logic Command/Reference
2…5Datalink A, B, C, or D Input
ValueDescription
0Ignore this command bit. (Default)
1Use this command bit.
Port 5 Device
20-COMM-ER
Parameter #: 42
Peer Cmd Mask
000000000000000
0
Bit 0B00
Valid nodes must have 20-COMM-ER ad apters connected to drives with
compatible Logic Command/Status words.
3. Set Parameter 40 - [Peer A Input] to select the destination of the data that
is input to the drive as Peer A.
Data is used from the least significant word in the event of a mismatch in
Reference or Datalink sizes.
4. If desired, set Parameter 41 - [Peer B Input] to select the destination of
the data to input to the device as Peer B.
5. If the adapter receives a Logic Command, set the bits in Parameter 42 -
[Peer Cmd Mask] that the device should use.
The bit definitions for the Logic Command word will depend on the
drive to which the adapter is connected. See Appendix
D or the device
documentation.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201339
If the adapter receives a Logic Command from both a master device and a
peer device, each command bit must have only one source. The source of
command bits set to ‘0’ will be the master device. The source of command
bits set to ‘1’ will be the peer device.
Chapter 3 Configuring the Adapter
Port 5 Device
20-COMM-ER
Parameter #: 48
Peer Inp Timeout
5.00s
0.01 <> 10.00
Default = 10.00 s
Port 5 Device
20-COMM-ER
Parameter #: 43
Peer Flt Action
0
Fault
ValueDescription
0Fault (Default)
1Stop
2Zero Data
3Hold Last
4Send Flt Cfg
6. Reset the adapter (see Resetting the Adapter on page 43) so that changes to
Parameter 42 - [Peer Cmd Mask] take effect.
7. Set Parameter 48 - [Peer Inp Timeout] to the maximum amount of time
the adapter will wait for a message before timing out.
Important:This value must be greater than the product of Parameter
54 - [Peer Out Time] multiplied by Parameter 55 - [Peer
Out Skip] in the adapter from which you are receiving I/O.
For example, if the value of Parameter 54 - [Peer Out Time] is 2.00
seconds and the value of Parameter 55 - [Peer Out Skip] is 2 (see
example screen in step 4 on page 37
), then Parameter 48 - [Peer Inp Timeout] needs to have a value greater than 4.00, such as 5.00 in the
example screen below.
8. Set Parameter 43 - [Peer Flt Action] to the action that the adapter will
take if it times out.
ATTENTION: Risk of injury or equipment damage exists. Parameter 43 [Peer Flt Action] lets you determine the action of the adapter and
connected device if peer communication is disrupted. By default, this
parameter faults the device. You can set this parameter so that the device
continues to run, however, precautions should be taken to ensure that the
setting of this parameter does not create a hazard of injury or equipment
damage. When commissioning the device, verify that your system responds
correctly to various situations (for example, a disconnected cable).
For more details, see Setting a Fault Action on page 41.
9. Set Parameter 49 - [Peer Inp Enable] to ‘1’ (On).
The adapter is now configured to receive peer I/O from the specified node.
Ensure that the specified node is configured to transmit peer I/O.
40Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the Adapter Chapter 3
Port 5 Device
20-COMM-ER
Parameter #: 39
Ref Adjust
100.00%
0.00 <> 200.00
Default = 100.00%
Setting the Reference
Adjustment
A Reference Adjustment is a percent scaling factor for the Reference from the
network. It can be set from 0.00…200.00% to allow the drive’s Reference to either
match the network Reference (= 100.00%), scale below the network Reference
(< 100.00%), or scale above the network Reference (> 100.00%).
The SMC controllers do not currently use the reference data sent in the IO frame.
No Reference configuration is required. Refer to the applicable SMC user manual
for the latest reference configuration information.
ATTENTION: To guard against equipment damage and/or personal injury,
note that changes to adapter Parameter 39 - [Ref Adjust] take effect
immediately. A drive receiving its Reference from the adapter will receive
the newly scaled Reference, resulting in a change of speed.
If the adapter is receiving a Reference, set Parameter 39 - [Ref Adjust] to the
desired scaling factor.
Setting a Fault Action
The adjustment takes effect as soon as it is entered.
By default, when I/O communication is disrupted (for example, a cable is
disconnected) or the controller is idle (in program mode or faulted), the drive
responds by faulting if it is using I/O from the network. You can configure a
different response to these events:
• Disrupted I/O communication by using Parameter 23 - [Comm Flt
Action]
• An idle controller by using Parameter 24 - [Idle Flt Action]
ATTENTION: Risk of injury or equipment damage exists. Parameters 23 -
[Comm Flt Action] and 24 - [Idle Flt Action] let you determine the action
of the adapter and connected device if I/O communication is disrupted or
the controller is idle. By default, these parameters fault the device. You can
set these parameters so that the device continues to run, however,
precautions should be taken to ensure that the settings of these
parameters do not create a risk of injury or equipment damage. When
commissioning the device, verify that your system responds correctly to
various situations (for example, a disconnected cable or faulted controller).
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201341
Chapter 3 Configuring the Adapter
Port 5 Device
20-COMM-ER
Parameter #: 23
Comm Flt Action
0
Fault
Port 5 Device
20-COMM-ER
Parameter #: 24
Idle Flt Action
0
Fault
Changing the Fault Action
Set the values of Parameters 23 - [Comm Flt Action] and 24 - [Idle Flt Action]
to any of these desired responses.
ValueActionDescription
0FaultThe device is faulted and stopped. (Default)
1StopThe device is stopped, but not faulted.
2Zero DataThe device is sent 0 for output data. This does not command a stop.
3Hold LastThe device continues in its present state.
4Send Flt CfgThe device is sent the data that you set in the fault configuration
Changes to these parameters take effect immediately. A reset is not required.
If communication is disrupted and then is re-established, the drive will
automatically take commands from the network again.
Setting the Fault Configuration Parameters
If you set Parameter 23 - [Comm Flt Action] or 24 - [Idle Flt Action] to ‘Send
Flt Cfg’, the values in the following parameters are sent to the drive after an I/O
communications fault and/or idle fault occurs. You must set these parameters to
values required by your application.
ParameterDescription
27 - [Flt Cfg Logic]A 16-bit value sent to the device for Logic Command.
28 - [Flt Cfg Ref]A 32-bit value (0…4294967295) sent to the device as a Reference or
29 - [Flt Cfg x1 In]
through
36 - [Flt Cfg x2 In]
Changes to these parameters take effect immediately. A reset is not required.
Datalink.
Important: If the device uses a 16-bit Reference or 16-bit Datalinks, the most
significant word of the value must be set to zero (0) or a fault will occur.
Setting Web Access
Control
42Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
By using a web browser to access the IP address set for the adapter, you can view
the adapter’s web pages for information about the adapter, its connected device,
and other DPI devices connected to the device, such as HIMs or converters.
Additionally, the adapter can be configured to automatically send e-mail messages
Configuring the Adapter Chapter 3
BitDescription
0E-mail Cfg (Default = 0 = Disabled)
1…7Not Used
Port 5 Device
20-COMM-ER
Parameter #: 57
Web Features
xxxxxxxxxxxxxxx
1
E-mail Cfgb00
ValueDescription
0Ready (Default)
1Reset Module
2Set Defaults
Port 5 Device
20-COMM-ER
Parameter #: 22
Reset Module
1
Reset Module
to desired addresses when selected device faults occur and/or are cleared, and/or
when the adapter takes a communication or idle fault action. For more details on
the adapter’s web pages, refer to Chapter
8, Viewing the Adapter Web Pages.
By default, the adapter web pages are disabled. See Figure 2
and set the Web Pages
Switch (SW4) to the ‘Enable Web’ (up) position. Parameter 56 [Web Enabled]
reflects the position of the web enable DIP switch on the adapter.
Important:For a change to the switch setting to take effect, the adapter
must be reset (see Resetting the Adapter
on page 43).
Bit 0 of Parameter 57 - [Web Features] is used to protect the configured settings
for e-mail messaging. By default, settings are not protected and the user can make
changes. To protect the configured settings, set the value of E-mail Cfg Bit 0 to ‘0’
(Disabled). You can unprotect the configuration by changing Bit 0 back to ‘1’
(Enabled). E-mail messaging will always remain active regardless of whether or
not its settings are protected—unless e-mail messaging was never configured. For
more information about configuring adapter e-mail messaging or to stop e-mail
messages, see Email Configuration Link
on page 162.
Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.
Resetting the Adapter
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201343
Changes to this parameter take effect immediately. A reset is not required.
Changes to switch settings and some adapter parameters require that you reset
the adapter before the new settings take effect. You can reset the adapter by power
cycling the drive or by using Parameter 22- [Reset Module].
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting control I/O to the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a
connected adapter.
Set Parameter 22 - [Reset Module] to ‘1’ (Reset Module).
Chapter 3 Configuring the Adapter
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A
Cmd/Ref
Defaultx x x 0 0 0 0 1
Bit76543210
0 = I/O disabled
1 = I/O enabled
When you enter ‘1’ (Reset Module), the adapter will be immediately reset. When
you enter ‘2’ (Set Defaults), the adapter will set all adapter parameters to their
factory-default values. After performing a Set Defaults, enter ‘1’ (Reset Module)
so that the new values take effect. The value of this parameter will be restored to
‘0’ (Ready) after the adapter is reset.
Viewing the Adapter Status
Using Parameters
The following parameters provide information about the status of the adapter.
You can view these parameters at any time.
ParameterDescription
17 - [EN P1 Rate Act]The data rate used on port 1 of the adapter
19 - [EN P2 Rate Act]The data rate used on port 2 of the adapter
20 - [Ref/Fdbk Size]The size of the Reference/Feedback. It will either be 16 bits or 32 bits. It
is set in the device and the adapter automatically uses the correct size.
21 - [Datalink Size]The size of the Datalinks. It will either be 16 bits or 32 bits. It is set in the
device and the adapter automatically uses the correct size.
26 - [DPI I/O Act]The Reference/Feedback and Datalinks used by the adapter. This value
is the same as Parameter 25 - [DPI I/O Cfg] unless the parameter was
changed and the adapter was not reset.
50 - [Peer Inp Status]The status of the consumed peer input connection.
44Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
The adapter firmware can be updated over the network or serially through a
direct connection from a computer to the drive using a 1203-USB or 1203-SSS
serial converter.
When updating firmware over the network, you can use the Allen-Bradley
ControlFLASH software tool, the built-in update capability of DriveExplorer
Full software, or the built-in update capability of DriveExecutive software.
When updating firmware through a direct serial connection from a computer to a
drive, you can use the same Allen-Bradley software tools described above, or you
can use terminal emulation software set to the X-modem protocol.
If using a direct serial connection, you can use DriveExplorer Lite software.
Configuring the Adapter Chapter 3
To obtain a firmware update for this adapter, go to http://www.ab.com/support/
abdrives/webupdate. This website contains all firmware update files and
associated Release Notes that describe the following items:
• Firmware update enhancements and anomalies
• How to determine the existing firmware revision
• How to update firmware using DriveExplorer, DriveExecutive,
ControlFLASH, or HyperTerminal software
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201345
Chapter 3 Configuring the Adapter
46Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Chapter
4
Configuring the I/O
This chapter provides instructions on how to configure a Rockwell Automation
ControlLogix or MicroLogix 1100/1400 controller to communicate with the
adapter and connected PowerFlex drive.
TopicPage
Using RSLinx Classic Software
ControlLogix Controller Example48
MicroLogix 1100/1400 Controller Example68
47
Using RSLinx Classic
Software
RSLinx Classic software, in all its variations (Lite, Gateway, OEM, and so forth),
is used to provide a communication link between the computer, network, and
controller. RSLinx Classic software requires its network-specific driver to be
configured before communication is established with network devices. To
configure the RSLinx driver, follow this procedure.
1. Start RSLinx Classic software and select Communications > Configure
Drivers to display the Configure Drivers screen.
2. From the Available Driver Types pull-down menu, choose EtherNet/IP
Driver.
3. Click Add New… to display the Add New RSLinx Driver screen.
4. Use the default name or type a new name and click OK. The ‘Configure
driver:’ screen appears.
5. Depending on your application, select either the browse local or remote
subnet option.
6. Click OK.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201347
Chapter 4 Configuring the I/O
IP Address 10.91.100.80
ControlLogix Controller
with 1756-ENBT Bridge
IP Address 10.91.100.79
PowerFlex 70 Drive with
20-COMM-ER Adapter
Computer with
Ethernet Connection
Ethernet
Switch
The Configure Drivers screen reappears with the new driver in the
Configured Drivers list.
7. Click Close to close the Configure Drivers screen.
8. Keep RSLinx running and verify that the computer recognizes the drive.
a. Select Communications > RSWho.
ControlLogix Controller
Example
b. In the menu tree, click ‘+’ next to the Ethernet driver.
If the ‘EtherNet/IP driver’ cannot see your drive, as an alternative, use
either the ‘Ethernet devices’ or ‘Remote Devices via Linx Gateway’ RSLinx
driver.
After the adapter is configured, the connected drive and adapter will be a single
node on the network. This section provides the steps needed to configure a simple
EtherNet/IP network (see Figure 8
). In our example, we will configure a
ControlLogix controller with 1756-ENBT (Series A) bridge to communicate
with a drive using Logic Command/Status, Reference/Feedback, and 16
Datalinks (8 to read and 8 to write) over the network.
Figure 8 - Example ControlLogix EtherNet/IP Network
48Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
Adding the Bridge to the I/O Configuration
To establish communications between the controller and adapter over the
network, you must first add the ControlLogix controller and its bridge to the I/O
configuration. This procedure is similar for all RSLogix 5000 versions.
1. Start RSLogix 5000 software.
2. Select File > New to display the New Controller screen.
a. Choose the appropriate choices for the fields in the screen to match
your application.
b. Click OK.
The RSLogix 5000 window reappears with the treeview in the left
pane.
3. In the treeview, right-click the I/O Configuration folder and choose New
Module…
The Select Module screen appears.
4. Expand the Communications group to display all of the available
communication modules.
5. In the list, select the EtherNet/IP bridge used by your controller.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201349
Chapter 4 Configuring the I/O
In this example, we use a 1756-ENBT EtherNet/IP Bridge (Series A),
so the 1756-ENBT/A option is selected.
6. Click OK.
7. In the Select Major Revision pop-up dialog box, select the major revision
of its firmware.
8. Click OK.
The bridge’s New Module screen appears.
9. Edit the following:
BoxSetting
NameA name to identify the EtherNet/IP bridge.
DescriptionOptional – description of the EtherNet/IP bridge.
IP AddressThe IP address of the EtherNet/IP bridge.
Host NameNot used.
SlotThe slot of the EtherNet/IP bridge in the rack.
RevisionThe minor revision of the firmware in the bridge. (You already set the major
Electronic
Keying
Open
Module
Properties
revision by selecting the bridge series in step 5.)
Compatible Keying. The ‘Compatible Keying’ setting for Electronic Keying
ensures the physical module is consistent with the software configuration
before the controller and bridge make a connection. Therefore, be sure that
you have set the correct revision in this screen. See the online Help for
additional information on this and other Electronic Keying settings. If keying is
not required, select ‘Disable Keying’. Disable keying is recommended.
When this box is checked, clicking OK opens additional module properties
screens to further configure the bridge. When unchecked, clicking OK closes
the bridge’s New Module screen. For this example, uncheck this box.
10. Click OK.
The bridge is now configured for the EtherNet/IP network, added to the
RSLogix 5000 project, and appears in the I/O Configuration folder. In
our example, a 1756-ENBT bridge appears under the I/O Conf iguration
folder with its assigned name.
50Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
For conv enience, keep the project open. Later in this chapter the project
will need to be downloaded to the controller.
There are three ways to add the adapter into the I/O configuration:
• Device Add-on Profiles (RSLogix 5000 software, version 16.00 or later)
• Generic Profile (RSLogix 5000 software, all versions)
These are described in separate sections below. If your version of RSLogix 5000
software supports device Add-on Profiles, we recommend that you use this
method.
Using RSLogix 5000 Device Add-on Profiles, Version 16.00 or Later
When compared to using the RSLogix 5000 Classic Profile (versions
13.00…15.00) or Generic Profile (all versions), the RSLogix 5000 device Add-on
Profiles provide the following advantages:
• Profiles for specific drives that provide descriptive controller tags for basic
control I/O words (Logic Command/Status and Reference/Feedback)
and Datalinks. Additionally, Datalinks automatically take the name of the
drive parameter to which they are assigned. These profiles virtually
eliminate I/O mismatch errors and substantially reduce drive
configuration time.
• New Drive tab eliminates the need for a separate drive software
configuration tool.
• Drive configuration settings are saved as part of the RSLogix 5000
software, version 16.00 or later, project file (.ACD) and also downloaded
to the controller.
• Unicast connection (RSLogix 5000 software, version 18.00 or later)
• Device Add-on Profiles can be updated anytime. When a new drive is used
or to benefit from new updates for Add-on Profiles, you will need the
newest Add-on Profile update. Go to www.ab.com/support/abdrives/
webupdate to download the latest RSLogix 5000 device Add-on Profile.
To determine your device Add-on Profile version, see Allen-Bradley
Knowledgebase document #65882.
Add the Drive/Adapter to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as a
child device to the parent bridge. In this example, RSLogix 5000 software,
version 16.00 is used with device Add-on Profile version 4.05 or later.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201351
Chapter 4 Configuring the I/O
TIP
TIP
1. In the treeview, right-click on the bridge and choose New Module… to
display the Select Module screen.
In our example, we right-click on the 1756-ENBT/A bridge. Expand the
Drives group to display all of the available drives with their
communication adapters.
If the PowerFlex drive is not shown, go to www.ab.com/support/abdrives/
webupdate and download the latest RSLogix 5000 device Add-on Profile.
2. From the list, select the drive and its connected adapter.
For this example, we selected ‘PowerFlex 70 EC-E’.
3. Click OK.
The drive’s New Module screen appears.
4. On the General tab, edit the following data about the drive/adapter.
BoxSetting
NameA name to identify the drive.
DescriptionOptional – description of the drive/adapter.
IP AddressThe IP address of the adapter.
5. On the New Module screen in the Module Definition section, click
Change… to launch the Module Definition screen and begin the drive/
adapter configuration process.
In this example, Datalinks are used to do the following.
Read…Write to…
Output Current (Parameter 3)Accel Time 1 (Parameter 140)
DC Bus Voltage (Parameter 12)Decel Time 1 (Parameter 142)
To get the latest RSLogix 5000 device Add-on Profile, go to
www.ab.com/support/abdrives/webupdate
.
52Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
6. In the Module Definition screen, edit the following information.
BoxSetting
RevisionThe major and minor revision of the firmware (database) in the drive. If the
drive’s major and minor revision is not available, the drive database is not
installed on your computer. To get the correct database revision, use one of the
following buttons at the bottom left of the Module Definition screen:
· Create Database: Creates a database from an online network drive. Clicking
this button displays an RSLinx software RSWho window. Browse to the
online drive (for this example, PowerFlex 70 EC), select it, and click OK. The
database will be uploaded and stored on the computer. Thereafter, close the
Module Definition screen and then re-open it to display the new revision.
· Web Update: When a drive is not available online, opens the Allen-Bradley
Drives Web Updates website to download a specific database file. After
downloading the file, close the Module Definition screen and then re-open it
to display the new revision.
· Match Drive: Use this button when the drive being added to the network
matches the drive profile (revision, rating, configuration settings, and so
forth) of an existing online network drive. Click this button to conveniently
create a duplicate drive profile from the online drive, and automatically load
this identical information into the Module Definition screen. This eliminates
the need to manually enter the information each time a new drive with a
matching profile is added to the network.
Electronic
Keying
Drive
Rating
ConnectionParameters via Datalinks. When selecting ‘Parameters via Datalinks’ (default),
Data
Format
Datalink
A, B, C, D
Sort Input/
Output
selection…
Use
Network
Reference
Compatible Module. The ‘Compatible Module’ setting for Electronic Keying
ensures that the physical module is consistent with the software configuration
before the controller and bridge make a connection. Therefore, be sure that you
have set the correct revision in this screen. See the online Help for additional
information on this and other Electronic Keying settings. If keying is not
required, select ‘Disable Keying’. Drives do not require keying, and so ‘Disable
Keying’ is recommended.
The voltage and current rating of the drive. If the drive rating is not listed, the
drive database is not installed on your computer. To get the correct drive rating,
use the Create Database, Web Update, or Match Drive button described
above.
the controller tags for the Datalinks use the drive parameter names to which
they are assigned. When selecting ‘Datalinks’, the controller tags for the
Datalinks have non-descriptive UserDefinedData[n] names like those used in
RSLogix 5000 software, version 15.00.
Parameters. When the Connection field is set to ‘Parameters via Datalinks’,
‘Parameters’ is automatically selected. When the Connection field is set to
‘Datalinks’, you must select the number of Datalinks required for your
application in the ‘Data Format’ field.
In the Input Data column, assigns selected drive parameters to be READ by the
controller. In the Output Data column, assigns selected drive parameters to be
WRITTEN by the controller.
When this box is checked, sorts the Input Data and Output Data assigned
parameters by name and then by number, and enables parameter search by
name. When unchecked, sorts the assigned parameters by parameter number
and then by name, and enables parameter search by number.
Conveniently selects the speed reference for the drive to come from the
network. This box is checked by default.
When a 32-bit parameter is selected for Input Data or Output Data for a
drive with 16-bit Datalinks, two contiguous Datalinks (for example, x1
and x2, where x = A, B, C or D) are automatically assigned as a pair to
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201353
Chapter 4 Configuring the I/O
represent that parameter. See Datalink examples in the screen shown on
the previous page. For more information on Datalinks, see Us ing
Datalinks on page 86.
On the Module Definition screen, notice that the automatically-assigned
controller tags DriveStatus, OutputFreq, DriveLogicRslt, and
CommandedFreq are always used.
When a Datalink is enabled, the following 20-COMM-ER adapter I/O
parameters are automatically set:
– Parameter 25 - [DPI I/O Cfg] turns on the enabled Datalink bit so
the 20-COMM-ER adapter will communicate that Datalink’s
information with the drive.
– Parameter 37 - [M-S Input] turns on the enabled Datalink bit so the
20-COMM-ER adapter will input that Datalink’s information from
the controller.
– Parameter 38 - [M-S Output] turns on the enabled Datalink bit so
the 20-COMM-ER adapter will output that Datalink’s information to
the controller.
7. Click OK on the Module Definition screen to save the drive and adapter
configuration and close the screen.
The drive’s New Module screen reappears.
54Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
Screen for
RSLogix 5000
software, version
16.00 or 17.00
Screen for
RSLogix 5000
software, version
18.00 or later
8. On the New Module screen, click the Connection tab.
9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0
milliseconds or greater.
This value determines the maximum interval t hat a controller should use
to move data to and from the adapter. To conserve bandwidth, use
higher values for communicating with low priority devices.
The ‘Inhibit Module’ box, when checked, inhibits the module from
communicating with the RSLogix 5000 project. When the ‘Major Fault on
…’ box is checked, a major controller fault will occur when the module’s
connection fails while the controller is in the Run Mode. For this example,
leave the ‘Inhibit Module’ and ‘Major Fault On …’ boxes unchecked.
Important:Unicast support has been added to RSLogix 5000 software,
version 18.00 or later . However, to also support unicast, the
controller firmware must be version 18.00 or later. Unicast
is recommended whenever possible. For the benefits of
unicast operation, see Preparing for an Installation
on
page 18.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201355
Chapter 4 Configuring the I/O
10. On the New Module screen, click the Port Configuration tab.
11. In the Port Configuration tab screen, edit the following information.
BoxSetting
IP AddressThe IP address of the adapter that was already set in the General tab. This
field is not configurable (grayed out).
Subnet MaskThe Subnet Mask configuration setting of the network. This setting must
match the setting of other devices on the network (for example,
255.255.255.0).
Gateway
Address
Enable BootPWhen this box is checked, BOOTP is enabled in the adapter and will ignore
The Gateway Address configuration setting of the network. This setting must
match the setting of other devices on the network (for example,
10.91.100.1).
the IP address set in the General tab. When unchecked, the controller uses
the set IP address. This is another method to enable/disable BOOTP in the
adapter. For this example, leave this box unchecked.
12. Click Set to save the Port Configuration information which sets the
corresponding offline Subnet Cfg x and Gateway Cfg x parameters in the
adapter.
13. Click OK on the New Module screen.
The new node (‘My_PowerFlex_70_EC_Drive’ in this example) now
appears under the bridge (‘My_EtherNet_IP_Bridge’ in this example) in
the I/O Configuration folder. If you double-click the Controller Tags,
you will see that module-defined data types and tags have been
automatically created (Figure 9
). Note that all tag names are defined and
Datalinks include the assigned drive parameter name. After you save
and download the configuration, these tags allow you to access the Input
and Output data of the drive via the controller’s ladder logic.
56Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Figure 9 - Controller Tags
Configuring the I/O Chapter 4
Save the I/O Configuration to the Controller
After adding the bridge and drive/adapter to the I/O configuration, you must
download the configuration to the controller. You should also save the
configuration to a file on your computer.
1. In the RSLogix 5000 window, select Communications > Download.
The Download dialog box appears.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201357
Chapter 4 Configuring the I/O
TIP
If a message box reports that RSLogix 5000 software is unable to go online,
select Communications > Who Active to find your controller in the Who
Active screen. After finding and selecting the controller, click Set Project Path to establish the path. If your controller does not appear, you need to add
or configure the EtherNet/IP driver with RSLinx software. See Using RSLinx
Classic Software on page 47 and RSLinx online help for details.
2. Click Download to download the configuration to the controller.
When the download is successfully completed, RSLogix 5000 software
goes into the Online mode and the I/O Not Responding box in the
upper-left of the window should be flashing green. Also, a yellow
warning symbol should be displayed on the I/O Conf iguration folder
in the treeview and on the drive profile.
If the controller was in Run Mode before clicking Download, RSLogix
5000 software prompts you to change the controller mode back to
Remote Run. In this case, choose the appropriate mode for your
application. If the controller was in Program Mode before clicking
Download, this prompt will not appear.
3. Select File > Save.
If this is the first time you saved the project, the Save As dialog box
appears.
a. Navigate to a folder.
b. Type a file name.
c.Click Save to save the configuration to a file on your computer.
To be sure that the present project configuration values are saved,
RSLogix 5000 software prompts you to upload them. Click Yes to
upload and save the values.
Correlate the Drive with the Controller
You must now correlate the drive settings to the RSLogix 5000 project I/O
settings so that they match. This requires loading the project I/O settings into the
drive.
1. In the treeview under I/O Configuration, right-click on the drive profile
(for this example, My_PowerFlex_70_EC_Drive) and choose Properties.
58Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
TIP
2. Click the Drive tab.
3. Click Connect to Drive to begin the correlation process.
After the drive conf iguration data has been verif ied, a pop-up dialog box
appears, which synchronizes ports from the online drive to the project to
be sure that correct Datalinks are assigned.
4. Click OK.
If the Differences Found screen appears—which is typical, click
Download. This will download the project settings from the controller
to the drive and its connected adapter. If Upload is clicked, the drive
and adapter settings are uploaded to the controller.
On subsequent connections to the drive (after initial download), click Upload.
5. When the Reset Comm Module screen appears, click Ye s to reset the
communication adapter so that the new I/O settings take effect.
After resetting the communication module, which may take up to a minute
to complete, the I/O OK box in the upper-left of the RSLogix 5000
window should now be steady green and the yellow warning symbols in
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201359
Chapter 4 Configuring the I/O
TIP
the treeview under the I/O Configuration folder and drive profile should
be gone.
If the yellow warning symbol for your drive remains displayed, first try
power cycling the drive. Otherwise, double-click the drive under the I/O tree and
click the Connection tab to find the cause of the problem.
6. The Module Properties Drive Tab screen re-appears.
You can view the drive’s Parameter List, Diagnostic Items List, and lists
for any connected peripheral, including the 20-COMM-ER. While
connected to the drive, you can dynamically change values of
parameters. Diagnostic items and diagram views can be used for
troubleshooting. Table 24 on page 147
provides diagnostic items for
troubleshooting the adapter.
7. Click OK when finished to close the Module Properties screen for the
drive.
Using the RSLogix 5000 Classic Profile, Versions 13.00…15.00
When compared to using the RSLogix 5000 Generic Profile (all versions), the
RSLogix 5000 Classic Profile provides these advantages:
• Profiles for specific drives (Figure 10
tags for basic control I/O words (Logic Command/Status and Reference/
Feedback). The controller tags for Datalinks, however, have nondescriptive UserDefinedData[n] names.
• Improved I/O configuration—no I/O assembly configuration required.
Basic control I/O is defined, but Datalinks still need to be configured/
mapped.
60Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
) that provide descriptive controller
Configuring the I/O Chapter 4
TIP
• The Setup tab includes a DriveExecutive icon link to conveniently launch
DriveExecutive software (when installed on computer) to match the
adapter I/O configuration with the controller, and to assign the Datalink
parameters in the drive. This reduces I/O mismatches.
Since the RSLogix 5000 Classic Profile has been significantly improved upon by
RSLogix 5000 Device Add-on Profiles, version 16.00 or later, we recommend using
RSLogix 5000 Device Add-on Profiles to take advantage of its benefits (more
intuitive, time saving, and less likely to make I/O configuration errors).
Figure 10 - Classic Profile Screens for Drives
When Datalinks are used, you must enable the desired Datalinks and assign
names to their non-descriptive controller tags. When a Datalink is enabled, you
must set the following adapter I/O parameters:
• Parameter 25 - [DPI I/O Cfg] turns on the enabled Datalink bit so the
20-COMM-ER adapter will communicate that Datalink’s information
with the drive.
• Parameter 37 - [M-S Input] turns on the enabled Datalink bit so the 20-
COMM-ER adapter will input that Datalink’s information from the
controller.
• Parameter 38 - [M-S Output] turns on the enabled Datalink bit so the
20-COMM-ER adapter will output that Datalink’s information to the
controller.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201361
Chapter 4 Configuring the I/O
When using Datalinks, up to 8 [Data In xx] parameters and/or up to 8 [Data Out
xx] parameters must be assigned to point to the appropriate drive parameters for
your application.
Using the RSLogix 5000 Generic Profile, All Versions
We recommend that you use the basic RSLogix 5000 Generic Profile for only the
following reasons:
• A specific drive profile in other versions of RSLogix 5000 software is
unavailable.
• Users are already familiar with a drive Generic Profile and do not want to
convert an existing project to a Classic Profile, versions 13.00…15.00, or to
a device Add-on Profile (RSLogix 5000 software, version 16.00 or later).
• A project must maintain specific revision level control.
• The controller cannot be taken offline. RSlogix 5000 software, version
16.00 or later, enables the drive Generic Profile to be added while the
controller is online and in the Run mode.
Add the Drive/Adapter to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as a
child device to the parent bridge.
1. In the treeview, right-click the bridge and select New Module… to display
the Select Module screen.
In our example, we right-click on the 1756-ENBT/A bridge.
2. Expand the Communications group to display all of the available
communication modules.
62Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
3. Select “ETHERNET-MODULE” from the list to configure the drive and
its connected 20-COMM-ER adapter.
4. Click OK.
The drive’s New Module screen appears.
5. Edit the following information about the drive and adapter.
BoxSetting
NameA name to identify the drive and adapter.
DescriptionOptional – description of the drive/adapter.
Comm FormatData - INT (This setting formats the data in 16-bit words.)
IP AddressThe IP address of the adapter.
Open Module
Properties
When this box is checked, clicking OK opens additional module properties
screens to further configure the drive/adapter. When unchecked, clicking
OK closes the drive’s New Module screen. For this example, check this box.
6. Under Connection Parameters, edit the following information.
BoxAssembly InstanceSize
Input1
(This value is required.)
Output2
(This value is required.)
Configuration 6
(This value is required.)
The value will vary based on your application
(setting of Parameters 25 - [DPI I/O Cfg] and 38 - [M-S Output]) and the size (16-bit or 32-bit) of the
Reference/Feedback and Datalinks in the drive.
See Table 2
The value will vary based on your application
(setting of Parameters 25 - [DPI I/O Cfg] and 37 - [M-S Input]) and the size (16-bit or 32-bit) of the
Reference/Feedback and Datalinks in the drive.
See Table 2
0 (This value is required.)
, Table 3, or Table 4 on page 64.
, Table 3, or Table 4 on page 64.
The following tables define the n umber of 16-bit wo rds that you need to
enter for the Input Size and Output Size boxes depending on your
configuration.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201363
Chapter 4 Configuring the I/O
TIP
Table 2 - Devices with 16-bit Reference/Feedback and 16-bit Datalinks
These products include the following:
· PowerFlex 70 drives with standard or enhanced control· SMC Flex smart motor controllers
· PowerFlex 700 drives with standard control· SMC-50 smart motor controllers
· PowerFlex 700H drives
Logic
Command/
Status
✔✔42…0 0001…0 0001…0 0001
✔✔✔64…0 0011…0 0011…0 0011
✔✔✔✔ 86…0 0111…0 0111…0 0111
✔✔✔✔✔108…0 1111…0 1111…0 1111
✔✔✔✔✔✔1210…1 1111…1 1111…1 1111
Ref/Fdbk
(16-bit)
Datalinks (16-bit) User Configured Settings
ABCD
Size in WordsPar. 23 -
Input Output
[DPI I/O Cfg]
Par. 35 [M-S Input]
Par. 36 [M-S Output]
Table 3 - Devices with 16-bit Reference/Feedback and 32-bit Datalinks
These products include the following:
· PowerFlex 700 drives with vector control· PowerFlex Digital DC drives
· PowerFlex 700L drives with 700 control· SMC Controllers
Logic
Command/
Status
✔✔42…0 0001…0 0001…0 0001
✔✔✔86…0 0011…0 0011…0 0011
✔✔✔✔ 1210…0 0111…0 0111…0 0111
✔✔✔✔✔1614…0 1111…0 1111…0 1111
✔✔✔✔✔✔2018…1 1111…1 1111…1 1111
Ref/Fdbk
(16-bit)
Datalinks (32-bit) User Configured Settings
ABCD
Size in WordsPar. 23 -
Input Output
[DPI I/O Cfg]
Par. 35 [M-S Input]
Par. 36 [M-S Output]
Table 4 - Drives with 32-bit Reference/Feedback and 32-bit Datalinks
These products include the following:
· PowerFlex 700S drives with Phase I or Phase II control· PowerFlex 753 drives
· PowerFlex 700L drives with 700S control· PowerFlex 755 drives
Logic
Command/
Status
✔✔64…0 0001…0 0001…0 0001
✔✔✔108…0 0011…0 0011…0 0011
✔✔✔✔ 1412…0 0111…0 0111…0 0111
✔✔✔✔✔1816…0 1111…0 1111…0 1111
✔✔✔✔✔✔2220…1 1111…1 1111…1 1111
Ref/Fdbk
(32-bit)
Datalinks (32-bit) User Configured Settings
ABCD
Size in WordsPar. 23 -
Input Output
[DPI I/O Cfg]
For instructions on configuring the I/O for the adapter using Parameter 25 [DPI I/O Cfg] and its Master-Slave Hierarchy using Parameters 37 - [M-S
Input] and 38 - [M-S Output], see
Setting the I/O Configuration
64Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
on page 35.
Par. 35 [M-S Input]
Par. 36 [M-S Output]
Configuring the I/O Chapter 4
When using Datalinks, up to 8 [Data In xx] parameters and/or up to 8
[Data Out xx] parameters must be assigned to point to the appropriate
device parameters for your application.
7. After setting the information in the device’s New Module screen, click OK.
The Module Properties screen appears.
8. Click the Connection tab.
9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0 ms or
greater.
This value determines the maximum interval t hat a controller should use
to move data to and from the adapter. To conserve bandwidth, use
higher values for communicating with low priority devices. For this
example, leave the ‘Inhibit Module’ and ‘Major Fault …’ boxes
unchecked.
10. Click OK.
The new node (‘My_PowerFlex_70_EC_Drive’ in this example) now
appears under the bridge (‘My_EtherNet_IP_Bridge’ in this e xample) in
the I/O Configuration folder. If you double-click the Controller Tags,
you will see that module-defined data types and tags have been
automatically created (Figure 11
). After you save and download the
configuration, these tags allow you to access the Input and Output data
of the drive via the controller’s ladder logic.
For this example, all Datalinks (A, B, C, and D) are enabled. The Input
Size is set to 12 words and the Output Size is set to 10 words. Also, the
following adapter I/O parameters are set to the following values.
Adapter Parameter No.Setting
25 - [DPI I/O Cfg]xxxx xxxx xxx1 1111
37 - [M-S Input]xxxx xxxx xxx1 1111
38 - [M-S Output]xxxx xxxx xxx1 1111
11. Reset the adapter (see Resetting the Adapter
on page 43) or power cycle
the device.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201365
Chapter 4 Configuring the I/O
TIP
For the device speed reference and Datalink parameter values and the
adapter setup parameter values, see Drive and Adapter Parameter
Settings on page 90.
Figure 11 - Controller Tags
Save the I/O Configuration to the Controller
After adding the bridge and drive/adapter to the I/O configuration, you must
download the configuration to the controller. You should also save the
configuration to a file on your computer.
When using RSLogix 5000 software, version 16.00 or later, you can add the I/O
configuration of a Generic Profile while the controller is online and in the Run
mode.
1. In the RSLogix 5000 window, select Communications > Download.
The Download dialog box appears.
66Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
TIP
If a message box reports that RSLogix 5000 software is unable to go online, select
Communications > Who Active to find your controller in the Who Active
screen. After finding and selecting the controller, click Set Project Path to
establish the path. If your controller does not appear, you need to add or configure
the EtherNet/IP driver with RSLinx software. See Using RSLinx Classic
Software on page 47 and RSLinx online help for details.
2. Click Download to download the configuration to the controller.
When the download is successfully completed, RSLogix 5000 software
goes into the Online mode and the I/O OK box in the upper-left of the
screen should be steady green.
3. Select File > Save.
If this is the first time you saved the project, the Save As dialog box
appears. Navigate to a folder, type a file name, and click Save to save
the configuration to a file on your computer.
To be sure that the present project configuration values are saved, RSLogix
5000 software prompts you to upload them. Click Ye s to upload and save
the values.
4. Configure any Datalinks in the drive (for example, Datalink parameters
300…317 in PowerFlex 70 drives) that were enabled in the controller and
adapter during I/O configuration (Ta b l e 2
, Ta b l e 3 , or Ta b l e 4 ).
Each Datalink being used must be assigned to a specific parameter in the
drive or connected peripheral. If this is not done, the controller will receive
or send placeholder data instead of actual drive or peripheral parameter
values.
5. Place the controller in Remote Run or Run Mode.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201367
Chapter 4 Configuring the I/O
Limitations Using a
MicroLogix 1100/1400
Controller
Controlling I/O with explicit messages is relatively complex compared to
normal implicit I/O control.
ControlLogix and CompactLogix controllers with EtherNet/IP provide the
easiest and most integrated form of implicit I/O control for a device.
RSLogix 5000 software, version 16.00 or later, for ControlLogix and
CompactLogix controllers contains integrated profiles for PowerFlex drives
that, with a few clicks of the mouse, automatically create all controller tags
and an implicit connection at the specified Requested Packet Interval to
control the drive. This connection is monitored at both ends to verify that
the controller and drive are communicating. A watchdog will cause a drive
fault if the drive does not respond within approximately 100 milliseconds.
Therefore, using a ControlLogix or CompactLogix controller is by far the
much preferred method of controlling drives on EtherNet/IP.
If you are not using either of these type of controllers, then devices on
EtherNet/IP can be controlled with explicit messages using MicroLogix
1100/1400 controllers with the following limitations:
· An explicit message is a much slower form of control and is nondeterministic. This means that you cannot guarantee how long the device
will take to start up or stop when the command is given. Therefore, all
equipment used in this manner should be subject to a risk assessment,
taking into account the mechanical and electrical implementation.
MicroLogix 1100/1400
Controller Example
· A timeout value (in seconds) in the EtherNet/IP adapter will issue a
device fault if a message is not received from the controller within the
specified time. However, the controller has no way of detecting a loss of
communication to the device until the next cycle of explicit messages.
This is another factor in the risk assessment.
· Any additional devices to be controlled will require additional explicit
messages for their control, and the y need to be carefully s equenced. Most
controllers have small communication queues (see the User Manual),
which need to be carefully managed if messages are not to be lost.
· Each controller has a limited number of communication connections (see
its User Manual for maximum connections), which will limit the number
of drives that can be connected.
In summary, unlike a ControlLogix or CompactLogix controller, programming a
MicroLogix 1100/1400 controller by using RSLogix 500 software with explicit
messages is more difficult, and produces a more complex program.
After the adapter is configured, the connected drive and adapter will be a single
node on the network. This section provides the steps needed to configure a
simple EtherNet/IP network (see Figure 12
MicroLogix 1100 controller to communicate with a drive using Logic
Command/Status, Reference/Feedback, and Datalinks over the network.
). In our example, we will configure a
68Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
IP Address 10.91.100.81
MicroLogix 1100/1400 Controller
IP Address 10.91.100.79
PowerFlex 70 Drive with
20-COMM-ER Adapter
Computer with
Ethernet Connection
Ethernet
Switch
TIP
Figure 12 - Example MicroLogix 1100/1400 Controller EtherNet/IP Network
Information for PowerFlex 750-Series drives has been added where applicable.
Configuring Parameters for Network I/O
Because the I/O for the drive is message-based, there is no need to configure any
I/O inside the RSLogix 500 project, version 7.00 or later, until using the I/O as
described in Chapter 5
However, to get the adapter to operate with the I/O created in Chapter 5
need to configure the adapter to accept the I/O and drive to point to the
appropriate Datalinks.
1. For this example, the following adapter I/O parameters are set to the
following values.
Adapter Parameter No.Setting
25 - [DPI I/O Cfg]xxxx xxxx xxx1 1111
37 - [M-S Input]xxxx xxxx xxx1 1111
38 - [M-S Output]xxxx xxxx xxx1 1111
2. Reset the adapter (see Resetting the Adapter
the drive.
For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, refer to Drive and Adapter Parameter
Settings on page 96.
.
on page 43) or power cycle
, we
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201369
Chapter 4 Configuring the I/O
Creating RSLogix 500 Project, Version 7.00 or Later
To transmit (read and write) data between the controller and drive, you must create
message instructions that allocate data table addresses in the controller for Logic
Command/Status, Reference/Feedback, and Datalinks.
Select the Controller
1. Start RSLogix 500 software.
The RSLogix 500 window appears.
2. Select File > New to display the Select Processor Type screen.
3. Assign a name for the processor.
4. In the list, select the MicroLogix 1100.
5. Choose the appropriate choices for the fields in the screen to match your
application.
6. Click OK.
The RSLogix 500 project window appears.
70Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Configuring the I/O Chapter 4
Steps 2…5
Steps 6…9
Step 10
Create MicroLogix 1100/1400 Ladder Logic for the Control Timeout
1. In the RSLogix 500 project window treeview under Program Files double-
click on LAD 2.
2. Insert a ladder rung.
3. Double-click on the rung to display the rung editor.
4. Enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG10:n), and
n is an unused element of the data file chosen for xx (for example, MG10:0
5. Press Enter.
6. Insert another separate rung.
7. Double-click on the rung to display the rung editor.
8. Enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ER BND OTU
MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element
(for example, MG10
:0) for the message created in steps 2…5.
)
Important:The information must be entered with appropriate numbers
for ‘xx’ and ‘n’ for your application, and with spaces and
forward slashes exactly as shown.
9. Press Enter.
10. In the MSG instruction (Figure 13
the message configuration screen (Figure 14
Figure 13 - MicroLogix 1100/1400 Ladder Logic for the Control Timeout
), double-click Setup Screen to launch
).
11. Configure the General tab fields by entering or verifying the information
shown in the message configuration screen.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201371
Chapter 4 Configuring the I/O
TIP
General Tab BoxSetting
This Controller (data for MicroLogix 1100)
Channel1 (integral). Controller port to which the network is connected.
Communication Command500CPU Write. The controller type and command type for the controller to read or write data.
Data Table Address
Size in Elements
Target Device (data for adapter/drive)
Message Timeout5. Message timeout duration in seconds.
Data Table Address
Routing Information FileRI9:0. An unused routing information file for the controller.
MultiHop Tab BoxSetting
To Address10.91.100.79. The IP address of the adapter connected to the drive.
Figure 14 - MicroLogix 1100/1400 Message Configuration Screens for the Control
Timeout
Because the MicroLogix 1100 is part of the SLC-500 controller family, the ‘500CPU’ controller type
was selected. The ‘Write’ command type was selected to write the control timeout value to the drive.
(1)
(2)
(3)
N20:0. An unused controller data table address containing the control timeout value to be written.
1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N42:3. Specific starting address of the destination file in the drive.
(1) For details on data table addresses for this example project, see Table 11…Tab le 1 4 starting on page 98.
(2) For details to determine element size for a specific drive, see Understanding Controller Data Table Addresses
(3) For details on setting the control timeout value and its function, see N-Files
COMM-ER adapter is power cycled, the Control Timeout Message must be re-sent. If the Control Timeout is not changed from a non-zero value, the
control message (page 75
) will error out.
The Control Timeout (N42:3) must be changed to a non-zero value (5…20 seconds
recommended). If the Control Timeout is not changed from a non-zero value, the
control message (page 75
) will error out. The Control Timeout is stored in RAM. If
the adapter is power cycled, the Control Timeout Message must be re-sent.
72Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
on page 97.
on page 192. The Control Timeout (N42:3) is stored in RAM. If the 20-
Configuring the I/O Chapter 4
Steps 1…4
Steps 5…8
Step 9
Create MicroLogix 1100/1400 Ladder Logic for the Logic Status, Feedback,
and Datalink Out
1. Insert another separate rung.
2. Double-click on the rung to display the rung editor.
3. Enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG11:n), and
n is an unused element of the data file chosen for xx (for example, MG11:0
4. Press Enter.
5. Insert another separate rung.
6. Double-click on the rung to display the rung editor.
7. Enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ER BND OTU
MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element
(for example, MG11
:0) for the message created in steps 1…4.
Important:The information must be entered with appropriate numbers
for ‘xx’ and ‘n’ for your application, and with spaces and
forward slashes exactly as shown.
)
8. Press Enter.
9. In the MSG instruction (Figure 15
the message configuration screen (Figure 16
Figure 15 - MicroLogix 1100/1400 Ladder Logic for the Logic Status, Feedback, and
Datalink Out
), double-click Setup Screen to launch
).
10. Configure the General tab fields by entering or verifying the information
shown in the message configuration screen.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201373
Chapter 4 Configuring the I/O
General Tab BoxSetting
This Controller (data for MicroLogix 1100)
Channel1 (integral). Controller port to which the network is connected.
Communication Command500CPU Read. The controller type and command type for the controller to read or write data.
Data Table Address
Size in Elements
Target Device (data for adapter/drive)
Message Timeout5. Message timeout duration in seconds.
Data Table Address
Routing Information FileRI9:1. An unused routing information file for the controller.
MultiHop Tab BoxSetting
To Address10.91.100.79. The IP address of the adapter connected to the drive.
Figure 16 - MicroLogix 1100/1400 Message Configuration Screens for the Logic
Status, Feedback, and Datalink Out
Because the MicroLogix 1100 is part of the SLC-500 controller family, the ‘500CPU’ controller
type was selected. The ‘Read’ command type was selected to read data from the drive.
(1)
(2)
(3)
N20:1. An unused controller data table address containing the data to be read from the drive.
19. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N41:0. Specific starting address of the source file in the drive.
(1) For details on data table addresses for this example project, see Ta bl e 1 1…Table 14 starting on page 98.
(2) For details to determine element size for a specific drive, see Understanding Controller Data Table Addresses
(3) For N-File details, see N-Files
on page 192.
74Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
on page 97.
Configuring the I/O Chapter 4
Steps 1…4
Steps 5…8
Step 9
Create MicroLogix 1100/1400 Ladder Logic for the Logic Command,
Reference, and Datalink In
1. Insert another separate rung.
2. Double-click on the rung to display the rung editor.
3. Enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG12:n), and
n is an unused element of the data file chosen for xx (for example, MG12:0
4. Press Enter.
5. Insert another separate rung.
6. Double-click on the rung to display the rung editor.
7. Enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ER BND OTU
MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element
(for example, MG12
:0) for the message created in steps 1…4.
Important:The information must be entered with appropriate numbers
for ‘xx’ and ‘n’ for your application, and with spaces and
forward slashes exactly as shown.
)
8. Press Enter.
9. In the MSG instruction (Figure 17
the message configuration screen (Figure 18
Figure 17 - MicroLogix 1100/1400 Ladder Logic for the Logic Command, Reference,
and Datalink In
), double-click Setup Screen to launch
).
10. Configure the General tab fields by entering or verifying the information
shown in the message configuration screen.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201375
Chapter 4 Configuring the I/O
TIP
TIP
General Tab BoxSetting
This Controller (data for MicroLogix 1100)
Channel1 (integral). Controller port to which the network is connected.
Communication Command500CPU Write. The controller type and command type for the controller to read or write data.
Data Table Address
Size in Elements
Target Device (data for adapter/drive)
Message Timeout5. Message timeout duration in seconds.
Data Table Address
Routing Information FileRI9:2. An unused routing information file for the controller.
MultiHop Tab BoxSetting
To Address10.91.100.79. The IP address of the adapter connected to the drive.
Figure 18 - MicroLogix 1100/1400 Message Configuration Screens for the Logic
Command, Reference, and Datalink In
Because the MicroLogix 1100 is part of the SLC-500 controller family, the ‘500CPU’ controller
type was selected. The ‘Write’ command type was selected to write data to the drive.
(1)
(2)
(3)
N20:20. An unused controller data table address containing the data to be written to the drive.
19. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N41:0. Specific starting address of the destination file in the drive.
(1) For details on data table addresses for this example project, see Table 11…Tab le 1 4 starting on page 98.
(2) For details to determine element size for a specific drive, see Understanding Controller Data Table Addresses
(3) For N-File details, see N-Files
on page 192.
This message will error out if the Control Timeout value is not changed from a nonzero value. Refer to page 71
for writing a value to the Control Timeout.
If the controller is controlling more than one drive, it is recommended to
intersperse the control I/O messaging for each drive to conserve network
bandwidth and decrease response time. That is, sequence the message
instructions for each drive so that its group of messages will occur at a different
time than those for another drive.
76Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
on page 97.
Notes:
Configuring the I/O Chapter 4
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201377
Chapter 4 Configuring the I/O
78Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Chapter
5
Using the I/O
This chapter provides information and examples that explain how to control,
configure, and monitor a PowerFlex 7-Class drive or SMC using the configured
I/O.
TopicPage
About I/O Messaging
Understanding the I/O Image80
Using Logic Command/Status84
Using Reference/Feedback84
Using Datalinks86
Example Ladder Logic Program Information87
ControlLogix Controller Example88
79
About I/O Messaging
ATTENTION: Risk of injury or equipment damage exists. The examples in
this publication are intended solely for purposes of example. There are
many variables and requirements with any application. Rockwell
Automation, Inc. does not assume responsibility or liability (to include
intellectual property liability) for actual use of the examples shown in this
publication.
On CIP-based networks, including EtherNet/IP, I/O connections are used to
transfer the data which controls the PowerFlex drive or SMC and sets its
Reference. I/O can also be used to transfer data to and from Datalinks.
The adapter provides many options for configuring and using I/O, including the
following:
• Configuring the size of I/O by enabling or disabling the Logic Command/
Reference and Datalinks.
• Setting a Master-Slave or Peer-to-Peer hierarchy.
Chapter 3
discuss how to configure the adapter and controller on the network for these
options. The defines the different options. This chapter discusses how to use I/O
after you have configured the adapter and controller.
, Configuring the Adapter, and Chapter 4, Configuring the I/O,
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201379
Chapter 5 Using the I/O
Understanding the I/O
Image
The terms ‘input’ and ‘output’ are defined from the controller’s point of view.
Therefore, output I/O is data that is produced by the controller and consumed by
the adapter. Input I/O is status data that is produced by the adapter and
consumed as input by the controller. The I/O image will vary based on the
following:
• Size (either 16-bit or 32-bit) of the Reference/Feedback words and
Datalink words used by the device. To determine the size of the Reference/
Feedback and Datalinks, view adapter Parameters 20 - [Ref/Fdbk Size]
and 21- [Datalink Size]. For information to access parameters, see Using
the PowerFlex 7-Class HIM on page 28.
• Configuration of I/O (Parameter 25 - [DPI I/O Cfg]). If all I/O is not
enabled, the image is truncated. The image always uses consecutive words
starting at word 0.
• ControlLogix/CompactLogix Controllers only—The drive profile used
in RSLogix 5000 software (device Add-on Profile in version 16.00 or later,
Classic Profile in versions 13.00…15.00, or Generic Profile in all versions).
ControlLogix Controller Image
Since the device Add-on Profile in RSLogix 5000 software, version 16.00 or later,
and the Classic Profile, versions 13.00…15.00, provide descriptive controller tags,
the I/O image (tag size and location) is automatically configured based on the
device being used. When using the Generic Profile (page 62
software, however, controller tags are not descriptive or defined.
The ControlLogix controller I/O image changes depending on the size of the
device’s Reference/Feedback and Datalinks. Ta b l e
O image when using various PowerFlex 7-Class drives, and all Datalinks enabled.
, Ta b l e , and Ta b l e show the I/
) in RSLogix 5000
80Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
Table 5 - ControlLogix Controller I/O Image for Devices with 16-bit Reference/
Feedback and 16-bit Datalinks – Using Generic Profile
These products include the following:
· PowerFlex 70 drives with standard or enhanced control· SMC Flex smart motor controllers
· PowerFlex 700 drives with standard control· SMC-50 smart motor controllers
· PowerFlex 700H drives
WordOutput I/OWordInput I/O
0Logic Command0Pad Word
1Reference1Pad Word
2Datalink In A12Logic Status
3Datalink In A23Feedback
4Datalink In B14Datalink Out A1
5Datalink In B25Datalink Out A2
6Datalink In C16Datalink Out B1
7Datalink In C27Datalink Out B2
8Datalink In D18Datalink Out C1
9Datalink In D29Datalink Out C2
10Datalink Out D1
11Datalink Out D2
Table 6 - ControlLogix Controller I/O Image for Devices with 16-bit Reference/
Feedback and 32-bit Datalinks – Using Generic Profile
These products include the following:
· PowerFlex 700 drives with vector control· PowerFlex Digital DC drives
· PowerFlex 700L drives with 700 control· SMC-50 smart motor controllers
WordOutput I/OWordInput I/O
0Logic Command0Pad Word
1Reference1Pad Word
2Datalink In A1 (LSW)2Logic Status
3Datalink In A1 (MSW)3Feedback
4Datalink In A2 (LSW)4Datalink Out A1 (LSW)
5Datalink In A2 (MSW)5Datalink Out A1 (MSW)
6Datalink In B1 (LSW)6Datalink Out A2 (LSW)
7Datalink In B1 (MSW)7Datalink Out A2 (MSW)
8Datalink In B2 (LSW)8Datalink Out B1 (LSW)
9Datalink In B2 (MSW)9Datalink Out B1 (MSW)
10Datalink In C1 (LSW)10Datalink Out B2 (LSW)
11Datalink In C1 (MSW)11Datalink Out B2 (MSW)
12Datalink In C2 (LSW)12Datalink Out C1 (LSW)
13Datalink In C2 (MSW)13Datalink Out C1 (MSW)
14Datalink In D1 (LSW)14Datalink Out C2 (LSW)
15Datalink In D1 (MSW)15Datalink Out C2 (MSW)
16Datalink In D2 (LSW)16Datalink Out D1 (LSW)
17Datalink In D2 (MSW)17Datalink Out D1 (MSW)
18Datalink Out D2 (LSW)
19Datalink Out D2 (MSW)
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201381
Chapter 5 Using the I/O
Table 7 - ControlLogix Controller I/O Image for Drives with 32-bit Reference/
Feedback and 32-bit Datalinks – Using Generic Profile
These products include the following:
·
PowerFlex 700S drives with Phase I or Phase II control· PowerFlex 753 drives
· PowerFlex 700L drives with 700S control· PowerFlex 755 drives
WordOutput I/OWordInput I/O
0Logic Command0Pad Word
1Not Used1Pad Word
2Reference (LSW)2Logic Status
3Reference (MSW)3Not Used
4Datalink In A1 (LSW)4Feedback (LSW)
5Datalink In A1 (MSW)5Feedback (MSW)
6Datalink In A2 (LSW)6Datalink Out A1 (LSW)
7Datalink In A2 (MSW)7Datalink Out A1 (MSW)
8Datalink In B1 (LSW)8Datalink Out A2 (LSW)
9Datalink In B1 (MSW)9Datalink Out A2 (MSW)
10Datalink In B2 (LSW)10Datalink Out B1 (LSW)
11Datalink In B2 (MSW)11Datalink Out B1 (MSW)
12Datalink In C1 (LSW)12Datalink Out B2 (LSW)
13Datalink In C1 (MSW)13Datalink Out B2 (MSW)
14Datalink In C2 (LSW)14Datalink Out C1 (LSW)
15Datalink In C2 (MSW)15Datalink Out C1 (MSW)
16Datalink In D1 (LSW)16Datalink Out C2 (LSW)
17Datalink In D1 (MSW)17Datalink Out C2 (MSW)
18Datalink In D2 (LSW)18Datalink Out D1 (LSW)
19Datalink In D2 (MSW)19Datalink Out D1 (MSW)
20Datalink Out D2 (LSW)
21Datalink Out D2 (MSW)
MicroLogix 1100/1400 Controller Image
The I/O image for these controllers always has 19 words of output and 19 words
of input. However, depending on the size of the device’s Reference/Feedback and
Datalinks, specific words in the I/O image may not be used. Ta b l e 8
Ta b l e 1 0
all Datalinks enabled.
82Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
show the I/O image when using various PowerFlex 7-Class drives, and
, Ta b l e 9 , and
Using the I/O Chapter 5
Table 8 - MicroLogix 1100/1400 I/O Image for PowerFlex 70/ 700/700H Drives and
SMC Flex (16-bit Reference/Feedback and 16-bit Datalinks)
WordOutput I/OWordInput I/O
0Logic Command0Logic Status
1Not used1Not used
2Reference (MSW)2Feedback (MSW)
3Not used3Not used
4Datalink In A1 (MSW)4Datalink Out A1 (MSW)
5Not used5Not used
6Datalink In A2 (MSW)6Datalink Out A2 (MSW)
7Not used7Not used
8Datalink In B1 (MSW)8Datalink Out B1 (MSW)
9Not used9Not used
10Datalink In B2 (MSW)10Datalink Out B2 (MSW)
11Not used11Not used
12Datalink In C1 (MSW)12Datalink Out C1 (MSW)
13Not used13Not used
14Datalink In C2 (MSW)14Datalink Out C2 (MSW)
15Not used15Not used
16Datalink In D1 (MSW)16Datalink Out D1 (MSW)
17Not used17Not used
18Datalink In D2 (MSW)18Datalink Out D2 (MSW)
Table 9 - MicroLogix 1100/1400 I/O Image for PowerFlex 700 VC Drives and SMC-50
Controllers (16-bit Reference/Feedback and 32-bit Datalinks)
WordOutput I/OWordInput I/O
0Logic Command0Logic Status
1Not used1Not used
2Reference (MSW)2Feedback (MSW)
3Datalink In A1 (LSW)3Datalink Out A1 (LSW)
4Datalink In A1 (MSW)4Datalink Out A1 (MSW)
5Datalink In A2 (LSW)5Datalink Out A2 (LSW)
6Datalink In A2 (MSW)6Datalink Out A2 (MSW)
7Datalink In B1 (LSW)7Datalink Out B1 (LSW)
8Datalink In B1 (MSW)8Datalink Out B1 (MSW)
9Datalink In B2 (LSW)9Datalink Out B2 (LSW)
10Datalink In B2 (MSW)10Datalink Out B2 (MSW)
11Datalink In C1 (LSW)11Datalink Out C1 (LSW)
12Datalink In C1 (MSW)12Datalink Out C1 (MSW)
13Datalink In C2 (LSW)13Datalink Out C2 (LSW)
14Datalink In C2 (MSW)14Datalink Out C2 (MSW)
15Datalink In D1 (LSW)15Datalink Out D1 (LSW)
16Datalink In D1 (MSW)16Datalink Out D1 (MSW)
17Datalink In D2 (LSW)17Datalink Out D2 (LSW)
18Datalink In D2 (MSW)18Datalink Out D2 (MSW)
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201383
Chapter 5 Using the I/O
Table 10 - MicroLogix 1100/1400 I/O Image for PowerFlex 700S Series Drives (32-bit
Reference/Feedback and 32-bit Datalinks)
WordOutput I/OWordInput I/O
0Logic Command0Logic Status
1Reference (LSW)1Feedback (LSW)
2Reference (MSW)2Feedback (MSW)
3Datalink In A1 (LSW)3Datalink Out A1 (LSW)
4Datalink In A1 (MSW)4Datalink Out A1 (MSW)
5Datalink In A2 (LSW)5Datalink Out A2 (LSW)
6Datalink In A2 (MSW)6Datalink Out A2 (MSW)
7Datalink In B1 (LSW)7Datalink Out B1 (LSW)
8Datalink In B1 (MSW)8Datalink Out B1 (MSW)
9Datalink In B2 (LSW)9Datalink Out B2 (LSW)
10Datalink In B2 (MSW)10Datalink Out B2 (MSW)
11Datalink In C1 (LSW)11Datalink Out C1 (LSW)
12Datalink In C1 (MSW)12Datalink Out C1 (MSW)
13Datalink In C2 (LSW)13Datalink Out C2 (LSW)
14Datalink In C2 (MSW)14Datalink Out C2 (MSW)
15Datalink In D1 (LSW)15Datalink Out D1 (LSW)
16Datalink In D1 (MSW)16Datalink Out D1 (MSW)
17Datalink In D2 (LSW)17Datalink Out D2 (LSW)
18Datalink In D2 (MSW)18Datalink Out D2 (MSW)
Using Logic Command/
Status
Using Reference/Feedback
The Logic Command is a 16-bit word of control data produced by the scanner
and consumed by the adapter. The Logic Status is a 16-bit word of status data
produced by the adapter and consumed by the scanner.
This manual contains the bit definitions for most compatible products available
at the time of publication in Appendix
D, Logic Command/Status Words. For
other products, see their documentation.
The Reference is produced by the controller and consumed by the adapter. The
Feedback is produced by the adapter and consumed by the controller. The size of
the Reference/Feedback is determined by the drive and displayed using adapter
Parameter 20 - [Ref/Fdbk Size].
SizeValid Values
16-bit-32768 to 32767
32-bit-2147483648 to 2147483647
When the Reference and Feedback are enabled and a ControlLogix controller
with a device Add-on Profile or Classic Profile is used, specific controller tags are
automatically created, sized (16-bit or 32-bit), and placed in the I/O image.
84Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
0
0 Hz
Par. 55 - [Maximum Freq]
Par. 82 - [Maximum Speed]
130 Hz
90 Hz
60 Hz
327672268515123
Scaling = (Parameter 82 ÷ Parameter 55) * 32767
PowerFlex 7-Class Drives
The Reference value is an unscaled value; it is NOT in Hertz or RPM. The
Reference uses a ‘32767’ scale. The ‘32767’ endpoint of the scale is equal to the
value of drive parameter 55 - [Maximum Freq], which has a default value of 130
Hz. For all PowerFlex 70/700 drives, default scaling is 0…15123 which is equal to
0…60.0 Hz. This is based on the formula shown below. Reference scaling is
limited by drive parameter 82 - [Maximum Speed]. If the default value of 60 Hz.
for parameter 82 - [Maximum Speed] is changed, the speed Reference scaling also
changes. To determine Reference scaling, use the following formula:
(Parameter 82 ÷ Parameter 55) * 32767 = Scaling
Using drive parameter 82 and 55 default values, speed Reference scaling is:
(60 Hz ÷ 130 Hz) * 32767 = 15123
Therefore, 0…15123 = 0…60.0 Hz.
If parameter 82 - [Maximum Speed] is changed to 90 Hz, then:
(90 Hz ÷ 130 Hz) * 32767 = 22685
Therefore, 0…22685 = 0…90.0 Hz.
A graphic representation of this Reference scaling is shown below.
For PowerFlex 70 EC drives, firmware 2.xxx or later, or PowerFlex 700 VC drives,
firmware 3.xxx or later, drive parameter 298 - [DPI Ref Select] was added to
simplify scaling for the speed Reference. When drive parameter 298 - [DPI Ref
Select] is set to its default ‘0’ (Max Freq), the speed Reference scaling is as shown
above. However, when parameter 298 - [DPI Ref Select] is set to ‘1’ (Max Speed),
the speed Reference scaling is equal to parameter 82 - [Max Speed]:
Parameter 82 = Scaling
Using the parameter 82 default value, speed Reference scaling is:
0…32767 = 0…60.0 Hz.
If parameter 82 - [Maximum Speed] is changed to 90 Hz, then:
90 Hz = 32767
Speed Feedback uses the same scaling as the speed Reference.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201385
Chapter 5 Using the I/O
TIP
For PowerFlex 700 VC drives, firmware 3.xxx or later, parameter 299 - [DPI Fdbk Select]
enables you to select the feedback data coming from the drive over DPI. The default is
‘Speed Fdbk’ in Hz or RPM determined by parameter 079 - [Speed Units]. The data
selection for parameter 299 is also displayed on the 1st line of the HIM and on
DriveExplorer and DriveExecutive software screens in the drive status area of the screen.
The controller in the system sends a reference to the SMC, but it is not used for
control purposes in the current release.
The SMC products use the feedback to send motor current information.
Using Datalinks
A Datalink is a mechanism used by PowerFlex drives and SMCs to transfer data
to and from the controller. Datalinks allow a device parameter value to be read or
written without using an Explicit Message. When enabled, each Datalink
occupies two 16-bit or 32-bit words in both the input and output image. Use
adapter Parameter 21 - [Datalink Size] to determine whether the drive uses 16-
bit or 32-bit words for Datalinks.
Rules for Using Datalinks
• Each set of Datalink parameters in a device can be used by only one
adapter. If more than one adapter is connected to a single device, multiple
adapters cannot use the same Datalink.
• Parameter settings in the device determine the data passed through the
Datalink mechanism. See the documentation for your device.
• When you use a Datalink to change a value, the value is NOT written to
the Nonvolatile Storage (NVS). The value is stored in volatile memory and
lost when the device loses power. Therefore, use Datalinks when you need
to change a value of a parameter frequently.
Using 16-Bit Datalinks to Read/Write 32-Bit Parameters
This subsection only pertains to the SMC Flex and PowerFlex 70 (SC or EC),
PowerFlex 700 (SC), and PowerFlex 700H drives which use 16-bit Datalinks. To
read or write a 32-bit parameter using 16-bit Datalinks, typically both Datalinks
of a pair (A, B, C, D) are set to the same 32-bit parameter. For example, to read
parameter 10 - [Elapsed Run Time] in a PowerFlex 70 drive, both Datalink A1
Out (Parameter 310) and Datalink A2 Out (Parameter 311) are set to ‘10’.
Datalink A1 Out will contain the least significant word (LSW) and Datalink A2
Out will contain the most significant word (MSW).
86Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
32-bit data is stored in binary as follows:
MSW231 through 2
LSW215 through 2
16
0
In this example, the parameter 10 - [Elapsed Run Time] value of 6553.9 Hrs is
read as ‘6553.9’ in Datalink A1 Out (Parameter 310) and Datalink A2 Out
(Parameter 311).
Regardless of the Datalink combination, Datalink x1 Out will always contain the
LSW and Datalink x2 Out will always contain the MSW. In the following
example, the PowerFlex 70 drive parameter 242 - [Power Up Marker] contains a
value of 88.4541 hours.
The example ladder logic programs in the sections of this chapter are intended for
and operate PowerFlex 7-Class drives and SMC Flex controllers.
Functions of the Example Programs
The example programs enable you to do the following:
• Receive Logic Status information from the drive.
• Send a Logic Command to control the drive (for example, start, stop).
• Send a Reference to the drive and receive Feedback from the drive.
• Send/receive Datalink data to/from the drive.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201387
Chapter 5 Using the I/O
Logic Command/Status Words
These examples use the Logic Command word and Logic Status word for
PowerFlex 70/700 drives. See Appendix
bits in these words may vary if you are using a different DPI device. See the
documentation for your device.
D to view details. The definition of the
ControlLogix Controller
Example
Creating Ladder Logic Using the RSLogix 5000 Device Add-on
Profiles, Version 16.00 or Later
Because the device Add-on Profile automatically created descriptive controller tags
(Figure 9
control and monitor the device without creating any ladder logic program.
However, if you intend to use Human Machine Interface devices (PanelView, and
so forth) to operate the device and view its status, you will need to create descriptive
user-defined Program tags (Figure 19
Controller tag data to the Program tags.
Figure 19 - ControlLogix Program Tags for Device Add-on Profile Ladder Logic
Program Example
) for the entire I/O image in Chapter 4, you can use these tags to directly
) and a ladder logic program that will pass the
An example ladder logic program that uses the automatically created descriptive
Controller tags and passes their data to the user-defined Program tags is shown in
Figure 20
determined by the name assigned when configuring the I/O (Chapter 4
88Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
and Figure 21. Note that the prefix for the device Controller tags is
).
Using the I/O Chapter 5
Figure 20 - ControlLogix Example Ladder Logic Program Using a Device Add-on
Profile for Logic Status/Feedback
Figure 21 - ControlLogix Example Ladder Logic Program Using a Device Add-on
Profile for Logic Command/Reference
Creating Ladder Logic Using the RSLogix 5000 Classic Profile,
Versions 1300…15.00
Since the RSLogix 5000 Classic Profile has been significantly improved upon by
RSLogix 5000 device Add-on Profiles, version 16.00 or later, we highly
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201389
Chapter 5 Using the I/O
…
…
TIP
DeviceParameterValueDescription
PowerFlex 70 EC
Drive
20-COMM-ER
Adapter
recommended using the RSLogix 5000 device Add-on Profiles to take advantage
of their benefits (more intuitive, time saving, and less likely to make ladder logic
program errors).
Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All
Versions
Drive and Adapter Parameter Settings
The following drive and adapter settings were used for the example ladder logic
program in this section.
90 - [Speed Ref A Sel]22 (DPI Port 5)Assigns 20-COMM-ER to be used for the Reference.
300 - [Data In A1]140Points to Par. 140 - [Accel Time 1]
301 - [Data In A2]142Points to Par. 142 - [Decel Time 1]
302 - [Data In B1]100Points to Par. 100 - [Jog Speed]
303 - [Data In B2]155Points to Par. 155 - [Stop Mode A]
304 - [Data In C1]101Points to Par. 101 - [Preset Speed 1]
305 - [Data In C2]102Points to Par. 102 - [Preset Speed 2]
306 - [Data In D1]103Points to Par. 103 - [Preset Speed 3]
307 - [Data In D2]104Points to Par. 104 - [Preset Speed 4]
310 - [Data Out A1]140Points to Par. 140 - [Accel Time 1]
311 - [Data Out A2]142Points to Par. 142 - [Decel Time 1]
312 - [Data Out B1]100Points to Par. 100 - [Jog Speed]
313 - [Data Out B2]155Points to Par. 155 - [Stop Mode A]
314 - [Data Out C1]101Points to Par. 101 - [Preset Speed 1]
315 - [Data Out C2]102Points to Par. 102 - [Preset Speed 2]
316 - [Data Out D1]103Points to Par. 103 - [Preset Speed 3]
317 - [Data Out D2]104Points to Par. 104 - [Preset Speed 4]
04 - [IP Addr Cfg 1]
07 - [IP Addr Cfg 4]
08 - [Subnet Cfg 1]
10.91.100.79IP address for the adapter.
255.255.248.0Subnet mask for the adapter.
11 - [Subnet Cfg 4]
23 - [DPI I/O Cfg]xxx1 1111Enables Cmd/Ref and Datalinks A…D.
35 - [M-S Input]xxx1 1111Configures the I/O Data to be transferred from the controller on
the network to the drive.
36 - [M-S Output]xxx1 1111Configures the I/O Data to be transferred from the drive to the
controller on the network.
Data In parameters are inputs into the device that come from controller
outputs (for example, data to write to a device parameter). Data Out
parameters are outputs from the device that go to controller inputs (for
example, data to read a device parameter).
90Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
PowerFlex 70 Drive
16-bit Speed Feedback and
Datalinks
PowerFlex 700S-Series Drive
32-bit Speed Feedback and
Datalinks
Controller Tags
When you add the adapter and drive to the I/O configuration (Chapter 4),
RSLogix 5000 software automatically creates generic (non-descriptive) controller
tags for them. In this example program, the following controller tags are used.
Figure 22 - ControlLogix Controller Tags for Drive Generic Profile Example Ladder
Logic Program
You can expand the Input and Output tags to reveal the input and output
configuration.
Figure 23 - ControlLogix Input Image for Drive Generic Profile Example Ladder
Logic Program
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201391
Chapter 5 Using the I/O
PowerFlex 70 Drive
16-bit Speed Reference and
Datalinks
PowerFlex 700S-Series Drive
32-bit Speed Reference and
Datalinks
Figure 24 - ControlLogix Output Image for Drive Generic Profile Example Ladder
Logic Program
Program Tags
To use the Controller tags that are automatically created, you need to create the
following Program tags for this example program.
Figure 25 - ControlLogix Program Tags for Drive Generic Profile Example Ladder
Logic Program
For information on speed Reference and Feedback scaling, see PowerFlex 7-Class
Drives on page 85.
92Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
PowerFlex 70
Series Drives
PowerFlex 70
Drive Speed
Feedback
PowerFlex
Drive Speed
Feedback
Figure 26 - ControlLogix Example Ladder Logic Program Using a Drive Generic
Profile for Logic Status/Feedback
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201393
Chapter 5 Using the I/O
PowerFlex 70
Series Drives
PowerFlex 70
Drive Speed
Reference
PowerFlex
Drive Speed
Reference
Figure 27 - ControlLogix Example Ladder Logic Program Using a Drive Generic
Profile for Logic Command/Reference
Example Datalink Data
The Datalink data used in the example program is shown in Figure 28. Note that
to describe the parameters to which the Datalinks are assigned, you may want to
add descriptions to the automatically-created generic controller tags or create a
User Defined Data Types (UDDT).
94Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
PowerFlex 70 Drive
PowerFlex 700S-Series Drive
Figure 28 - ControlLogix Example Datalinks for Ladder Logic Program Using a Drive
Generic Profile
For PowerFlex 7-Class drives, the scaling may need to be multiplied by 10 or 100,
depending on the parameter. For more information, see Using Datalinks
page 86.
on
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201395
Chapter 5 Using the I/O
…
…
TIP
TIP
32
MicroLogix 1100/1400
Controller Example
DeviceParameterValueDescription
PowerFlex 70 EC
Drive
20-COMM-ER
Adapter
90 - [Speed Ref A Sel]22 (DPI Port 5)Assigns 20-COMM-ER to be used for the Reference.
300 - [Data In A1]140Points to Par. 140 - [Accel Time 1]
301 - [Data In A2]142Points to Par. 142 - [Decel Time 1]
302 - [Data In B1]100Points to Par. 100 - [Jog Speed]
303 - [Data In B2]155Points to Par. 155 - [Stop Mode A]
304 - [Data In C1]101Points to Par. 101 - [Preset Speed 1]
305 - [Data In C2]102Points to Par. 102 - [Preset Speed 2]
306 - [Data In D1]103Points to Par. 103 - [Preset Speed 3]
307 - [Data In D2]104Points to Par. 104 - [Preset Speed 4]
310 - [Data Out A1]140Points to Par. 140 - [Accel Time 1]
311 - [Data Out A2]142Points to Par. 142 - [Decel Time 1]
312 - [Data Out B1]100Points to Par. 100 - [Jog Speed]
313 - [Data Out B2]155Points to Par. 155 - [Stop Mode A]
314 - [Data Out C1]101Points to Par. 101 - [Preset Speed 1]
315 - [Data Out C2]102Points to Par. 102 - [Preset Speed 2]
316 - [Data Out D1]103Points to Par. 103 - [Preset Speed 3]
317 - [Data Out D2]104Points to Par. 104 - [Preset Speed 4]
04 - [IP Addr Cfg 1]
07 - [IP Addr Cfg 4]
08 - [Subnet Cfg 1]
Drive and Adapter Parameter Settings
The following drive and adapter settings were used for the example ladder logic
program in this section.
10.91.100.79IP address for the adapter.
255.255.248.0Subnet mask for the adapter.
11 - [Subnet Cfg 4]
23 - [DPI I/O Cfg]xxx1 1111Enables Cmd/Ref and Datalinks A…D.
35 - [M-S Input]xxx1 1111Configures the I/O Data to be transferred from the controller
on the network to the drive.
36 - [M-S Output]xxx1 1111Configures the I/O Data to be transferred from the drive to
the controller on the network.
Data In parameters are inputs into the drive that come from controller outputs (for
example, data to write to a drive parameter). Data Out parameters are outputs from the
drive that go to controller inputs (for example, data to read a drive parameter).
When using a drive that has 16-bit Datalinks (PowerFlex 70, PowerFlex 700, and
PowerFlex 700H drives) to transfer a 32-bit parameter, two contiguous drive Datalink
parameters (for example, Data Out A1/A2, B1/B2, etc.) are required. To determine if a
parameter is a 32-bit parameter, see the Parameter section in the drive documentation
and look for a symbol in the ‘No.’ column. (All parameters in PowerFlex 700 Series B
drives are 32-bit parameters.) For example, parameter 3 - [Output Current] in a PowerFlex
70 EC drive is a 32-bit parameter. When using a drive that has 32-bit Datalinks (PowerFlex
700 VC and PowerFlex 700S), only one drive Datalink parameter is required to transfer any
parameter.
96Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
Understanding Controller Data Table Addresses
Because MicroLogix 1100/1400 controllers are 16-bit platforms and are used
with the 32-bit 20-COMM-ER adapter, the data will be transposed from the
least-significant word (LSW) to the most-significant word (MSW) in the
controller.
When the I/O was configured (Chapter 4
was used. Figure 29
Figure 29 - Data File Table for Example Ladder Logic Program
shows the entire data file address structure for this example.
), an available data table address (N20)
Important:The N20:0 data table address in this example is used to set a
control timeout value (in seconds) which determines how long
it will take the adapter to detect a communication loss. Enter a
valid value (1…32767) for N20:0. A value of zero (0) is not
valid, because it disables the timeout and all I/O connections
(Logic Command/Status, Reference/Feedback, and Datalinks)
intended for the drive will not execute. A timeout value of
5…20 seconds is recommended.
Depending on the drive you are using, Ta b l e 1 1
show the I/O definitions as they relate to the N20 data table (Figure 29
, Ta b l e 1 2 , Ta b l e 1 3 , or Ta b l e 1 4
) being
used in this example.
When using PowerFlex 70 or 70 EC, PowerFlex 700, PowerFlex 700VC drives, or
SMC Flex controllers—which all contain INT (16-bit format) data types, you
will read from and write to the MSW data table address in the controller.
When using PowerFlex 700 VC drives or SMC-50 controllers, which contain
DINT (32-bit format) data types, you will read from and write to the LSW data
table address in the controller.
When using PowerFlex 700S drives, which contain both DINT (32-bit format)
and REAL (floating point format) data types, you will always read from and write
to the LSW data table address in the controller first. Then if the data value
exceeds 16 bits, the remaining value will be in the MSW data table address.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201397
Chapter 5 Using the I/O
Table 11 - Controller Data Table Addresses for PowerFlex 70/70 EC,
PowerFlex 700 Drives, and SMC Flex Controllers
Data Table Address Description
N20:1Logic Status (see Appendix D)
N20:2Reserved
N20:3Speed Feedback
N20:4Value of parameter assigned to Parameter 310 [Data Out A1] LSW
N20:5Value of parameter assigned to Parameter 310 [Data Out A1] MSW
N20:6Value of parameter assigned to Parameter 311 [Data Out A2] LSW
N20:7Value of parameter assigned to Parameter 311 [Data Out A2] MSW
N20:8Value of parameter assigned to Parameter 312 [Data Out B1] LSW
N20:9Value of parameter assigned to Parameter 312 [Data Out B1] MSW
N20:10Value of parameter assigned to Parameter 313 [Data Out B2] LSW
N20:11Value of parameter assigned to Parameter 313 [Data Out B2] MSW
N20:12Value of parameter assigned to Parameter 314 [Data Out C1] LSW
N20:13Value of parameter assigned to Parameter 314 [Data Out C1] MSW
N20:14Value of parameter assigned to Parameter 315 [Data Out C2] LSW
N20:15Value of parameter assigned to Parameter 315 [Data Out C2] MSW
N20:16Value of parameter assigned to Parameter 316 [Data Out D1] LSW
N20:17Value of parameter assigned to Parameter 316 [Data Out D1] MSW
N20:18Value of parameter assigned to Parameter 317 [Data Out D2] LSW
N20:19Value of parameter assigned to Parameter 317 [Data Out D2] MSW
N20:20Logic Command (see Appendix
N20:21Reserved
N20:22Speed Reference
N20:23Value of parameter assigned to Parameter 300 [Data In A1] LSW
N20:24Value of parameter assigned to Parameter 300 [Data In A1] MSW
N20:25Value of parameter assigned to Parameter 301 [Data In A2] LSW
N20:26Value of parameter assigned to Parameter 301 [Data In A2] MSW
N20:27Value of parameter assigned to Parameter 302 [Data In B1] LSW
N20:28Value of parameter assigned to Parameter 302 [Data In B1] MSW
N20:29Value of parameter assigned to Parameter 303 [Data In B2] LSW
N20:30Value of parameter assigned to Parameter 303 [Data In B2] MSW
N20:31Value of parameter assigned to Parameter 304 [Data In C1] LSW
N20:32Value of parameter assigned to Parameter 304 [Data In C1] MSW
N20:33Value of parameter assigned to Parameter 305 [Data In C2] LSW
N20:34Value of parameter assigned to Parameter 305 [Data In C2] MSW
N20:35Value of parameter assigned to Parameter 306 [Data In D1] LSW
N20:36Value of parameter assigned to Parameter 306 [Data In D1] MSW
N20:37Value of parameter assigned to Parameter 307 [Data In D2] LSW
N20:38Value of parameter assigned to Parameter 307 [Data In D2] MSW
D)
98Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Using the I/O Chapter 5
Table 12 - Controller Data Table Addresses for PowerFlex 700 VC Drives and SMC50 Controllers
Data Table Address Description
N20:1Logic Status (see Appendix D)
N20:2Reserved
N20:3Speed Feedback
N20:4Value of parameter assigned to Parameter 310 [Data Out A1] LSW
N20:5Value of parameter assigned to Parameter 310 [Data Out A1] MSW
N20:6Value of parameter assigned to Parameter 311 [Data Out A2] LSW
N20:7Value of parameter assigned to Parameter 311 [Data Out A2] MSW
N20:8Value of parameter assigned to Parameter 312 [Data Out B1] LSW
N20:9Value of parameter assigned to Parameter 312 [Data Out B1] MSW
N20:10Value of parameter assigned to Parameter 313 [Data Out B2] LSW
N20:11Value of parameter assigned to Parameter 313 [Data Out B2] MSW
N20:12Value of parameter assigned to Parameter 314 [Data Out C1] LSW
N20:13Value of parameter assigned to Parameter 314 [Data Out C1] MSW
N20:14Value of parameter assigned to Parameter 315 [Data Out C2] LSW
N20:15Value of parameter assigned to Parameter 315 [Data Out C2] MSW
N20:16Value of parameter assigned to Parameter 316 [Data Out D1] LSW
N20:17Value of parameter assigned to Parameter 316 [Data Out D1] MSW
N20:18Value of parameter assigned to Parameter 317 [Data Out D2] LSW
N20:19Value of parameter assigned to Parameter 317 [Data Out D2] MSW
N20:20Logic Command (see Appendix
N20:21Reserved
N20:22Speed Reference
N20:23Value of parameter assigned to Parameter 300 [Data In A1] LSW
N20:24Value of parameter assigned to Parameter 300 [Data In A1] MSW
N20:25Value of parameter assigned to Parameter 301 [Data In A2] LSW
N20:26Value of parameter assigned to Parameter 301 [Data In A2] MSW
N20:27Value of parameter assigned to Parameter 302 [Data In B1] LSW
N20:28Value of parameter assigned to Parameter 302 [Data In B1] MSW
N20:29Value of parameter assigned to Parameter 303 [Data In B2] LSW
N20:30Value of parameter assigned to Parameter 303 [Data In B2] MSW
N20:31Value of parameter assigned to Parameter 304 [Data In C1] LSW
N20:32Value of parameter assigned to Parameter 304 [Data In C1] MSW
N20:33Value of parameter assigned to Parameter 305 [Data In C2] LSW
N20:34Value of parameter assigned to Parameter 305 [Data In C2] MSW
N20:35Value of parameter assigned to Parameter 306 [Data In D1] LSW
N20:36Value of parameter assigned to Parameter 306 [Data In D1] MSW
N20:37Value of parameter assigned to Parameter 307 [Data In D2] LSW
N20:38Value of parameter assigned to Parameter 307 [Data In D2] MSW
D)
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 201399
Chapter 5 Using the I/O
Table 13 - Controller Data Table Addresses for PowerFlex 700S Drives with Phase I
Control
Data Table Address Description
N20:1Logic Status (see Appendix D)
N20:2Speed Feedback LSW
N20:3Speed Feedback MSW
N20:4Value of parameter assigned to Parameter 724/725 [Data Out A1] LSW
N20:5Value of parameter assigned to Parameter 724/725 [Data Out A1] MSW
N20:6Value of parameter assigned to Parameter 726/727 [Data Out A2] LSW
N20:7Value of parameter assigned to Parameter 726/727 [Data Out A2] MSW
N20:8Value of parameter assigned to Parameter 728/729 [Data Out B1] LSW
N20:9Value of parameter assigned to Parameter 728/729 [Data Out B1] MSW
N20:10Value of parameter assigned to Parameter 730/731 [Data Out B2] LSW
N20:11Value of parameter assigned to Parameter 730/731 [Data Out B2] MSW
N20:12Value of parameter assigned to Parameter 732/733 [Data Out C1] LSW
N20:13Value of parameter assigned to Parameter 732/733 [Data Out C1] MSW
N20:14Value of parameter assigned to Parameter 734/735 [Data Out C2] LSW
N20:15Value of parameter assigned to Parameter 734/735 [Data Out C2] MSW
N20:16Value of parameter assigned to Parameter 736/737 [Data Out D1] LSW
N20:17Value of parameter assigned to Parameter 736/737 [Data Out D1] MSW
N20:18Value of parameter assigned to Parameter 738/739 [Data Out D2] LSW
N20:19Value of parameter assigned to Parameter 738/739 [Data Out D2] MSW
N20:20Logic Command (see Appendix
N20:21Speed Reference LSW
N20:22Speed Reference MSW
N20:23Value of parameter assigned to Parameter 707/708 [Data In A1] LSW
N20:24Value of parameter assigned to Parameter 707/708 [Data In A1] MSW
N20:25Value of parameter assigned to Parameter 709/710 [Data In A2] LSW
N20:26Value of parameter assigned to Parameter 709/710 [Data In A2] MSW
N20:27Value of parameter assigned to Parameter 711/712 [Data In B1] LSW
N20:28Value of parameter assigned to Parameter 711/712 [Data In B1] MSW
N20:29Value of parameter assigned to Parameter 713/714 [Data In B2] LSW
N20:30Value of parameter assigned to Parameter 713/714 [Data In B2] MSW
N20:31Value of parameter assigned to Parameter 715/716 [Data In C1] LSW
N20:32Value of parameter assigned to Parameter 715/716 [Data In C1] MSW
N20:33Value of parameter assigned to Parameter 717/718 [Data In C2] LSW
N20:34Value of parameter assigned to Parameter 717/718 [Data In C2] MSW
N20:35Value of parameter assigned to Parameter 719/720 [Data In D1] LSW
N20:36Value of parameter assigned to Parameter 719/720 [Data In D1] MSW
N20:37Value of parameter assigned to Parameter 721/722 [Data In D2] LSW
N20:38Value of parameter assigned to Parameter 721/722 [Data In D2] MSW
D)
100Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.