Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature) describes some important differences between solid state equipment and
hard-wired electromechanical devices. Because of this difference, and also because
of the wide variety of uses for solid state equipment, all persons responsible for
applying this equipment must satisfy themselves that each intended application of
this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
WARNING: Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or circumstances
that can lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid the hazard, and
recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that surfaces may be at dangerous
temperatures.
Allen-Bradley, PowerFlex, DPI, SCANport, DriveExplorer, DriveExecutive, DriveTools SP, and ControlFLASH are either
registered trademarks or trademarks of Rockwell Automation, Inc.
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
Summary of Changes
The information below summarizes the changes made to this manual
since its last release (May 2006):
Description of ChangesPage(s)
In the “Quick Start” section:
• In Step 4, removed connecting the adapter to the network.
• In Step 5, added two new sub-steps (B and C).
• Added a new Step 6 “Connect the adapter to the network.”
• Incremented old Steps 6 and 7 to Steps 7 to 8.
Reorganized Chapter 2:
• Moved the “Connecting the Adapter to the Drive” section after the
“Commissioning the Adapter” section.
• Moved the “Applying Power” section after the “Connecting the Adapter to
the Drive” section.
• In the “Applying Power” section, added three new subsections:
– “Start-Up Status Indications”
– “Verifying/Setting Key Adapter Parameters”
– “Configuring/Verifying Key Drive Parameters.”
• Moved the “Connecting the Drive/Adapter to the Network” section to the
end of the chapter.
In Chapter 3, moved the “Setting the Device Instance Number” section after
the “Using the PowerFlex 7-Class HIM” section. Included additional
information to the “Setting the Device Instance Number” section.
Added new Appendix D “Routing Capability for Networked Drives.”D-1
1-6
Chapter
3-3
2
The information below summarizes the changes made to this manual
since its last release (April 2006):
Description of ChangesPage(s)
In the Features section — first bullet, removed text “... and can be used with
the kit’s optional I/O board.” Also, added an Important statement regarding
this information.
In the Viewing the Adapter Configuration table, added a third bullet in the
Parameter 07 - [Baud Rate Act] row.
For Parameter 05 - [Flt Cfg Ref], corrected its detail information from being a
bit parameter to a numeric parameter.
DriveExplorer™http://www.ab.com/drives/driveexplorer, and
DriveTools™ SP (includes
DriveExecutive™)
HIMHIM Quick Reference 20HIM-QR001…
PowerFl ex
(Std. and enhanced control)
PowerFl ex
Powe rFlex
*Standard and vector control
PowerFl ex
®
70 Drive
®
700 Drive*
®
700 Ser. B Drive*
®
700H DrivePowerFlex 700H Installation Manual
DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools, and
DriveExecutive online help (installed with the software)
PowerFlex 70 User Manual
PowerFlex 70/700 Reference Manual
PowerFlex 700 User Manual
PowerFlex 700 Series B User Manual
PowerFlex 70/700 Reference Manual
PowerFlex 700H Programming Manual
P-1
—
—
20A-UM001…
PFLEX-RM001…
20B-UM001…
20B-UM002…
PFLEX-RM001…
PFLEX-IN006…
20C-PM001…
Documentation can be obtained online at
http://www.rockwellautomation.com/literature.
P-2About This Manual
Rockwell Automation Support
Rockwell Automation, Inc. offers support services worldwide, with over
75 sales/support offices, over 500 authorized distributors, and over 250
authorized systems integrators located throughout the United States
alone. In addition, Rockwell Automation, Inc. representatives are in
every major country in the world.
Local Product Support
Contact your local Rockwell Automation, Inc. representative for:
• Sales and order support
• Product technical training
• Warranty support
• Support service agreements
Technical Product Assistance
If you need to contact Rockwell Automation, Inc. for technical
assistance, please review the information in Chapter
first. If you still have questions, then access the Allen-Bradley Technical
Support web site at www.ab.com/support/abdrives
5, Troubleshooting
.
Conventions Used in This Manual
The following conventions are used throughout this manual:
• Parameter names are shown in the format Parameter xx - [*]. The xx
represents the parameter number, and the * represents the parameter
name — for example, Parameter 01 - [Reset Module].
• Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read “Select File > Open,”
you should click the File menu and then click the Open command.
• The firmware release is displayed as FRN X.xxx. The “FRN”
signifies Firmware Release Number. The “X” is the major release
number. The “xxx” is the minor update number.
• This manual provides information about the 20-COMM-B BACnet
MS/TP adapter and using it with PowerFlex 7-Class drives. The
adapter can be used with other products that support a DPI adapter,
such as the DPI External Comms Kit (20-XCOMM-DC-BASE).
Refer to the documentation for your product for specific information
about how it works with the adapter.
Chapter 1
Getting Started
The 20-COMM-B BACnet MS/TP adapter is a communication option
intended for installation into a PowerFlex 7-Class drive. It can also be
used with other Allen-Bradley products that support an internal DPI ™
(Drive Peripheral Interface) adapter, such as the DPI External Comms
Kit (20-XCOMM-DC-BASE).
TopicPageTopicPage
Components
Features1-2Quick Start1-6
Compatible Products1-3Status Indicators1-7
Required Equipment1-3
1-1Safety Precautions1-4
Components
Figure 1.1 Components of the Adapter
➊
➋
➌
Item PartDescription
Status Indicators Four LEDs that indicate the status of the network connection,
➊
DPI ConnectorA 20-pin, single-row shrouded male header. An Internal Interface
➋
Terminal BlockA 3-pin terminal block with mating 3-pin linear plug connects
➌
TERM, -BIAS, and
➍
+BIAS Switches
MAC Address
➎
Switches
➍
➎
DPI, and the adapter. Refer to Chapter
cable connects to this connector and a connector on the drive.
the adapter to the network.
Switches for turning on/off the adapter’s internal termination
resistor and bias resistors. See Setting the TERM, -BIAS, and
+BIAS Switches on page 2-4 for details.
Switches for setting the MAC address. See Setting the MAC
Address on page 2-2 for details.
5, Troubleshooting.
1-2Getting Started
Features
The 20-COMM-B BACnet MS/TP adapter features the following:
• The adapter is normally mounted in the PowerFlex 7-Class drive. It
can also be installed in a DPI External Comms Kit
Important: Due to inherent operating limitations, the adapter cannot
• Switches let you:
– Set a MAC address before applying power to the drive.
– Turn on/off the adapter’s built-in termination resistor and bias
resistors for optimizing operation on the network.
• Captive screws secure and ground the adapter to the drive or, when
mounted in a DPI External Comms Kit, to the kit’s metal enclosure.
• A number of configuration tools can be used to configure the adapter
and connected drive. The tools include the PowerFlex HIM on the
drive and drive-configuration software such as DriveExplorer (version
3.01 or higher) or DriveExecutive (version 3.01 or higher).
be used with the kit’s optional I/O board.
• Status indicators report the status of drive communications, the
adapter, and network. They are visible when the drive cover is opened
or closed.
• Read/write access to parameters is available. You can configure and
monitor parameter values over the network.
• User-defined fault actions let you determine how the adapter and drive
respond to communication disruptions on the network.
Getting Started1-3
Compatible Products
The 20-COMM-B BACnet MS/TP adapter is compatible with most
Allen-Bradley PowerFlex 7-Class (Architecture-Class) drives and other
products that support DPI. DPI is a second generation peripheral
communication interface and functional enhancement to SCANport. At
the time of publication, compatible products include:
• PowerFlex 70 drives (standard and enhanced control)
• PowerFlex 700 drives (standard and vector control)
• PowerFlex 700 Series B drives (standard and vector control)
• PowerFlex 700H drives
• DPI External Comms Kit
Required Equipment
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes:
❑ One 20-COMM-B BACnet MS/TP adapter
❑ A 2.54 cm (1 in.) and a 15.24 cm (6 in.) Internal Interface cable
(only one cable is needed to connect the adapter to the drive)
❑ One 3-pin linear plug (plugged into the adapter socket)
❑ This manual
User-Supplied Equipment
To install and configure the adapter, you must supply:
❑ A small flathead screwdriver
❑ A shielded, twisted wire pair to connect the adapter to the network
❑ A configuration tool, such as:
–PowerFlex HIM
– DriveExplorer (version 3.01 or higher)
– DriveExecutive stand-alone software (version 3.01 or higher) or
bundled with the DriveTools SP suite (version 1.01 or higher)
– Third-party network configuration software
1-4Getting Started
Safety Precautions
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive
may contain high voltages that can cause injury or death. Remove
!
power from the PowerFlex drive, and then verify power has been
discharged before installing or removing an adapter.
ATTENTION: Risk of injury or equipment damage exists. Only
personnel familiar with drive and power products and the associated
!
machinery should plan or implement the installation, start up,
configuration, and subsequent maintenance of the product using an
adapter. Failure to comply may result in injury and/or equipment
damage.
ATTENTION: Risk of equipment damage exists. The adapter
contains ESD (Electrostatic Discharge) sensitive parts that can be
!
damaged if you do not follow ESD control procedures. Static control
precautions are required when handling the adapter. If you are
unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage, Publication 8000-4.5.2.
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault when
!
you reset the adapter. Determine how your drive will respond before
resetting an adapter.
ATTENTION: Risk of injury or equipment damage exists.
Parameter 02 - [Comm Loss Action] lets you determine the action of
!
the adapter and connected PowerFlex drive if communications are
disrupted. By default, this parameter faults the PowerFlex drive. You
can set this parameter so that the drive continues to run. Precautions
should be taken to ensure that the setting of this parameter does not
create a risk of injury or equipment damage. When commissioning the
drive, verify that your system responds correctly to various situations
(for example, a disconnected cable).
ATTENTION: Risk of injury or equipment damage exists. When a
system is configured for the first time, there may be unintended or
!
incorrect machine motion. Disconnect the motor from the machine or
process during initial system testing.
Getting Started1-5
ATTENTION: Risk of injury or equipment damage exists. Parameter
03 - [Comm Loss Time] lets you determine how long it will take the
!
adapter to detect network communication losses. By default, this
parameter sets the timeout to ten seconds. You can set it so that the
duration is shorter, longer, or disabled. When set to disabled, this also
disables adapter Parameter 02 - [Comm Loss Action]. Therefore, a
communications fault action will be ignored. Take precautions to ensure
that the setting does not create a risk of injury or equipment damage.
When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable).
ATTENTION: Risk of injury or equipment damage exists. The
examples in this publication are intended solely for purposes of
!
example. There are many variables and requirements with any
application. Rockwell Automation, Inc. does not assume responsibility
or liability (to include intellectual property liability) for actual use of
the examples shown in this publication.
1-6Getting Started
Quick Start
This section is provided to help experienced users quickly start using the
adapter. If you are unsure how to complete a step, refer to the referenced
chapter.
StepActionRefer to…
1Review the safety precautions for the adapter.Throughout this manual
2Verify that the PowerFlex drive is properly installed. Drive User Manual
3Commission the adapter.
Set a unique MAC address and, depending on where the
PowerFlex drive nodes are located on the network,
appropriately set the TERM, -BIAS, and +BIAS switches.
4Install the adapter.
Verify that the PowerFlex drive is not powered. Then,
connect the adapter to the drive using the Internal
Interface cable. Use the captive screws to secure and
ground the adapter to the drive.
When installing the adapter in a DPI External Comms
Kit, refer to the 20-XCOMM-DC-BASE Installation Instructions (Publication No. 20COMM-IN001…)
supplied with the kit.
5Apply power to the adapter and verify key settings.
A. The adapter receives power from the drive. Verify
that the adapter is installed correctly and then apply
power to the drive. The PORT status indicator should
be solid green. If it is red, there is a problem. Refer to
Chapter
B. Verify/set key adapter parameters.
C. Configure/verify key drive parameters.
6Connect the adapter to the network.
Verify that the PowerFlex drive is not powered. Then,
connect the adapter to the network using a shielded,
twisted wire pair.
7Configure the adapter for your application.
Set adapter parameters for the following functions as
required by your application:
• Fault actions
• Baud rate
8Set up the controller to communicate with the
adapter.
Use the controller’s programming software to program
the controller.
5, Troubleshooting.
Chapter
2,
Installing the Adapter
Chapter
2,
Installing the Adapter
2,
Chapter
Installing the Adapter
Chapter 2,
Installing the Adapter
Chapter 3,
Configuring the Adapter
Instruction manual for
your controller’s
programming software
Getting Started1-7
PWR
STS
PORT
MOD
NET A
NET B
Status Indicators
The adapter uses four status indicators to report its operating status. They
can be viewed on the adapter or through the drive cover (Figure 1.2).
Figure 1.2 Status Indicators (location on drive may vary)
➊
➋
➌
➍
➊
➋
➌
➍
Adapter Status
Item
Indicator Name
PORT
➊
MOD
➋
NET A
➌
NET B
➍
After installing the adapter and applying power to the drive, refer to
Start-Up Status Indications on page 2-8 for possible start-up status
indications and their descriptions.
1-8Getting Started
Notes:
Chapter 2
Installing the Adapter
Chapter 2 provides instructions for installing the adapter in a PowerFlex
7-Class drive. This adapter can also be installed in a DPI External
Comms Kit. In this case, refer to the 20-XCOMM-DC-BASE Installation Instructions (Publication No. 20COMM-IN001…) supplied with the kit.
TopicPage
Preparing for an Installation
Commissioning the Adapter2-1
Connecting the Adapter to the Drive2-6
Applying Power2-8
Connecting the Drive/Adapter to the Network2-10
2-1
Preparing for an Installation
Before installing the adapter, verify that you have all required
equipment. Refer to Required Equipment
on page 1-3.
Commissioning the Adapter
To commission the adapter, you must set a unique MAC address and,
depending on where the PowerFlex drive nodes are located on the
network (starting and ending network nodes versus other node
locations), appropriately set the TERM, -BIAS, and +BIAS switches.
Important: New settings are recognized only when power is applied to
the adapter or it is reset. If you change a switch setting,
cycle power or reset the adapter to invoke the change.
ATTENTION: Risk of equipment damage exists. The adapter
contains ESD (Electrostatic Discharge) sensitive parts that can be
!
damaged if you do not follow ESD control procedures. Static control
precautions are required when handling the adapter. If you are
unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage, Publication 8000-4.5.2.
2-2Installing the Adapter
Setting the MAC Address
Set the MAC address using the MAC Address switches (Figure 2.1).
Refer to Table 2.A
Important: Each node on the network must have a unique MAC
address. The MAC address must be set before power is
applied because the adapter uses the MAC address it detects
when it first receives power. To change a MAC address, you
must set the new value. Then remove and reapply power to
the adapter, or reset the adapter.
Figure 2.1 Setting the Adapter MAC Address Switches
for specific MAC address switch settings.
MAC Address Switches
(SW1 - SW7)
1
2
Switches DescriptionDefault
SW1Least Significant Bit (LSB) of MAC Address0
SW2Bit 1 of MAC Address0
SW3Bit 2 of MAC Address0
SW4Bit 3 of MAC Address0
SW5Bit 4 of MAC Address0
SW6Bit 5 of MAC Address0
SW7Most Significant Bit (MSB) of MAC Address0
SW8Mode (reserved for future use)——
TIP: The MAC address can be verified using a PowerFlex 7-Class HIM,
DriveExplorer software, or DriveExecutive software to view Parameter 08 - [MAC Address] or Diagnostic Item number 16 (page 5-6).
The adapter’s TERM, -BIAS, and +BIAS switches (Figure 2.2) are used
to turn on/off its built-in termination resistor and bias resistors.
Switch Setting
MAC
Address
SW1 SW2 SW3 SW4 SW5 SW6 SW7
120 0001111
121 1001111
122 0101111
123 1101111
Switch Setting
Figure 2.2 Setting the TERM, -BIAS, and +BIAS Switches
-BIAS Switch (SW2)+BIAS Switch (SW3)
TERM Switch (SW1)
RSRV Switch (SW4)
Reserved for future use
1
2
3
4
UP = OFF
Switches DescriptionDefault
SW1Turns on/off the termination resistorUp (Off)
SW2Turns on/off the -bias resistorUp (Off)
SW3Turns on/off the +bias resistorUp (Off)
SW4Reserved (not used)—
Since nodes on a BACnet MS/TP network are typically a mix of
Allen-Bradley PowerFlex drives and other brands of building automation
products, the network node locations for the PowerFlex drives will
determine how their adapter’s TERM, -BIAS, and +BIAS switches
should be set.
Installing the Adapter2-5
Network with PowerFlex Drives at Starting and/or Ending Nodes
For a network with PowerFlex drives at the starting and/or ending nodes
(Figure 2.3
switches to the “Down” (On) position. All other PowerFlex drive
network nodes must have these switches set to the “Up” (Off) position.
Figure 2.3 Example Network with PowerFlex Drives at Starting and/or Ending Nodes
), set their 20-COMM-B adapter’s TERM, -BIAS, and +BIAS
Node 1
(Starting Node)
BACnet MS/TP Network
20-COMM-B Adapter Settings for
TERM, -BIAS, and +BIAS Switches
"Down" (On) Positions"Up" (Off) Positions
Network with PowerFlex Drives at Other Nodes
For a network with PowerFlex drives at other node locations — not
starting and/or ending nodes (Figure 2.4
+BIAS switches to the “Up” (Off) position. In this network scenario,
other brands of building automation products at the starting and/or
ending nodes require appropriate termination and bias resistors. Refer to
their instruction documentation for details.
Figure 2.4 Example Network with PowerFlex Drives at Other Nodes
Node 1
(Starting Node)
Node 2 Node 3 Node 4
■ ■ ■
), set the TERM, -BIAS, and
PowerFlex 7-Class Drives
Node 2 Node 3 Node 4
n
Node
(Ending Node)
"Down" (On) Positions
Node
(Ending Node)
n
Other Brand
Building Automation
Product
BACnet MS/TP Network
Requires
Termination and
Bias Resistors
20-COMM-B Settings
for TERM, -BIAS, and
+BIAS Switches
Building Automation
■ ■ ■
"Up" (Off) Positions
Other Brand
Product
Requires
Termination and
Bias Resistors
2-6Installing the Adapter
Connecting the Adapter to the Drive
1. Remove power from the drive.
2. Use static control precautions, and remove or open the drive cover.
3. Connect the Internal Interface cable to the DPI port on the drive and
then to the DPI connector on the adapter.
Figure 2.5 DPI Ports and Internal Interface Cables
20-COMM-B Adapter
➋
➊
➌
PowerFlex 70 Drive
➍
PowerFlex 700 Drive
Frames 0 - 1
Item DescriptionItem Description
15.24 cm (6 in.) Internal Interface cable
➊
➋
DPI Connector
➌
➍
PowerFlex 700 Drive
Frames 2 and Larger
RS-485 serial cable connection
2.54 cm (1 in.) Internal Interface cable
Installing the Adapter2-7
4. Secure and ground the adapter to the drive by doing the following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind
the adapter and mount the adapter on the drive using the four
captive screws.
– On a PowerFlex 700 or PowerFlex 700H drive, just mount the
adapter on the drive using the four captive screws.
Important: Tighten all screws since the adapter is grounded via the
screws. Recommended torque is 0.9 N-m (8.0 lb.-in.).
Figure 2.6 Mounting and Grounding the Adapter
Drive
Adapter
Internal Interface Cable
folded behind the adapter
and in front of the drive.
All Frame Sizes:
Adapter mounts in drive.
PowerFlex 700 Drive
Frames 0 and 1:
Adapter mounts on door.
PowerFlex 70 Drive
Frames 2 and Larger:
Adapter mounts in drive.
2-8Installing the Adapter
PWR
STS
PORT
MOD
NET A
NET B
Applying Power
ATTENTION: Risk of equipment damage, injury, or death exists.
Unpredictable operation may occur if you fail to verify that
!
parameter settings are compatible with your application. Verify that
settings are compatible with your application before applying power
to the drive.
Install or close the drive cover, and apply power to the drive. The adapter
receives its power from the connected drive. When you apply power to
the adapter for the first time, its topmost status indicator “PORT” should
be solid green after an initialization. If it is red, there is a problem. Refer
to Chapter
Start-Up Status Indications
Status indicators for the drive and communications adapter can be
viewed on the front of the drive (Figure 2.7) after power has been
applied. Possible start-up status indications are shown in Table 2.B.
Figure 2.7 Drive and Adapter Status Indicators (location on drive may vary)
5, Troubleshooting.
➊
➋
Installing the Adapter2-9
Table 2.B Drive and Adapter Start-Up Status Indications
Item NameColorStateDescription
Drive STS Indicator
STS
➊
➋
Green FlashingDrive ready but not running, and no faults are present.
(Status)
PORTGreen FlashingNormal Operation. The adapter is establishing an I/O
MODGreenFlashingNormal Operation. The adapter is operating but is not
NET A GreenFlashingNormal Operation. The adapter is properly connected and
NET B Green OffNormal Operation. The adapter is properly connected but
SteadyDrive running, no faults are present.
Yellow Flashing,
Drive Stopped
Flashing,
Drive Running
Steady,
Drive Running
RedFlashingA fault has occurred.
SteadyA non-resettable fault has occurred.
SteadyNormal Operation. The adapter is properly connected and
SteadyNormal Operation. The adapter is operating and
FlashingNormal Operation. The adapter is transmitting data.
An inhibit condition exists – the drive cannot be started.
Check drive Parameter 214 - [Start Inhibits].
An intermittent type 1 alarm condition is occurring. Check
drive Parameter 211 - [Drive Alarm 1].
A continuous type 1 alarm condition exists. Check drive
Parameter 211 - [Drive Alarm 1].
Adapter Status Indicators
connection to the drive. It will turn solid green or red.
communicating with the drive
transferring I/O data.
transmitting I/O data.
communicating on the network.
is idle.
Verifying/Setting Key Adapter Parameters
To access adapter parameters when using the LCD HIM, navigate to the
Device Select screen. Then select the BACnet communications adapter
(20-COMM-B) and press the Enter function key.
1. Verify that adapter Parameter 08 - [MAC Address] is reporting the
MAC address set in Setting the MAC Address on page 2-2
2. Set adapter Parameter 11 - [Device Instance] to a unique number
for representation to the Building Automation Controller. For more
information, see Setting the Device Instance Number
3. Reset the adapter by setting adapter Parameter 01 - [Reset Module]
to “1” (Reset Module) so that the new Device Instance Number takes
effect.
.
on page 3-3.
2-10Installing the Adapter
Configuring/Verifying Key Drive Parameters
The PowerFlex 7-Class drive can be separately configured for the control
and reference functions in various combinations. For example, you
could set the drive to have its control come from a peripheral or terminal
block with the reference coming from the BACnet MS/TP network. Or
you could set the drive to have its control come from the BACnet MS/TP
network with the reference coming from another peripheral or terminal
block. Or you could set the drive to have both its control and reference
come from the BACnet MS/TP network.
The following steps in this section assume that the drive will receive the
Logic Command and Reference from the BACnet MS/TP network.
1. Using drive Parameter 090 - [Speed Ref A Sel], set the drive speed
Reference to “22” (DPI Port 5).
2. Verify that drive Parameter 213 - [Speed Ref Source] is reporting
that the source of the Reference to the drive is “22” (DPI Port 5).
This ensures that any Reference commanded from the network can
be monitored by using drive Parameter 002 - [Commanded Speed]. If a problem occurs, this verification step provides the
diagnostic capability to determine whether the drive/adapter or the
network is the cause.
Connecting the Drive/Adapter to the Network
ATTENTION: Risk of injury or death exists. The PowerFlex drive
may contain high voltages that can cause injury or death. Remove
!
power from the drive, and then verify power has been removed before
installing or removing an adapter.
1. Remove power from the drive.
2. Use static control precautions, and remove or open the drive cover.
3. Connect a shielded, twisted wire pair to the network, and route it
through the bottom of the drive (see Figure 2.6
4. Connect the twisted wire pair and its shield to the 3-pin linear plug
(provided with the adapter). See Figure 2.8
and typical terminal connections.
).
for terminal designations
Installing the Adapter2-11
Figure 2.8 Typical Network Terminal Connections
Node 1Node 2Node "n"
SHLD
+B
-A
TerminalSignalFunction
SHLD Termination Shield Termination
+BSignal BTxRxD+
-ASignal ATxRxD-
5. Insert the 3-pin linear plug into the mating adapter socket.
6. Install or close the drive cover.
7. Apply power to the drive.
8. Verify that adapter Parameter 07 - [Baud Rate Act] is reporting the actual network baud rate. If not, use Parameter 06 - [Baud Rate
Cfg] to set the adapter to a fixed baud rate that matches the network
baud rate.
SHLD
+B
-A
SHLD
+B
-A
TIP: After the drive is connected and communicating on the BACnet
MS/TP network, it may be necessary to set additional adapter parameters
to meet your application requirements. For example:
• Parameter 02 - [Comm Loss Action]
• Parameter 03 - [Comm Loss Time]
To access adapter parameters when using the LCD HIM, navigate to the
Device Select screen. Then select the BACnet adapter (20-COMM-B)
and press the Enter function key.
For adapter parameter configuration details, please refer to Chapter
3.
2-12Installing the Adapter
Notes:
Chapter 3
Configuring the Adapter
Chapter 3 provides instructions and information for setting the
parameters in the adapter.
TopicPage
Configuration Tools
Using the PowerFlex 7-Class HIM3-2
Setting the Device Instance Number3-3
Setting a Comm Loss Action3-5
Setting the Comm Loss Time3-6
Setting the Baud Rate3-7
Resetting the Adapter3-7
Viewing the Adapter Configuration3-8
3-1
For a list of parameters, refer to Appendix
definitions of terms in this chapter, refer to the Glossary.
Configuration Tools
The adapter stores parameters and other information in its own
Non-Volatile Storage (NVS) memory. You must, therefore, access the
adapter to view and edit its parameters. The following tools can be used
to access the adapter parameters:
ToolRefer to…
PowerFlex 7-Class HIM
(20-HIM-*)
DriveExplorer Software
(version 3.xx or higher)
DriveExecutive Software
(version 3.xx or higher)
page 3-2
http://www.ab.com/drives/driveexplorer, or
DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools, or
DriveExecutive Online help (installed with the software)
B, Adapter Parameters. For
3-2Configuring the Adapter
Using the PowerFlex 7-Class HIM
If your drive has either an LED or LCD HIM (Human Interface Module),
you can use it to access parameters in the adapter as shown below. It is
recommended that you read through the steps for your HIM before
performing the sequence. For additional HIM information, refer to your
PowerFlex Drive User Manual or the HIM Quick Reference card.
Using an LED HIM
StepKey(s)Example Screens
1. Press ALT and then Sel (Device)
to display the Device Screen.
2. Press the Up Arrow or Down
Arrow to scroll to the
20-COMM-B adapter. Letters
represent files in the drive, and
numbers represent ports. The
adapter is usually connected to
port 5.
3. Press the Enter key to enter your
selection. A parameter database
is constructed, and then the first
parameter is displayed.
4. Edit the parameters using the
same techniques that you use to
edit drive parameters.
ALT
AND
OR
Device
Sel
Using an LCD HIM
StepKey(s)Example Screens
1. In the main menu, press the Up
Arrow or Down Arrow to scroll to
Device Select.
2. Press Enter to enter your
selection.
3. Press the Up Arrow or Down
Arrow to scroll to the
20-COMM-B adapter.
4. Press Enter to select the adapter.
A parameter database is
constructed, and then the main
menu for the adapter is
displayed.
5. Edit the parameters using the
same techniques that you use to
edit drive parameters.
OR
OR
F-> StoppedAuto
0.00Hz
Main Menu:
Diagnostics
Param ete r
Device Select
Por t 5 Device
20-COMM-B
Main Menu:
Diagnostics
Param ete r
Device Select
Configuring the Adapter3-3
Setting the Device Instance Number
While there are many ways to implement Device Instance and network
strategies, the example shown in Figure 3.1 illustrates one logical
approach.
In this example, two individual Floor Level Networks are connected to
the Building Level Network through a router which allows devices on
each network to share the same MAC address. However, each device on
the network must have a unique Device Instance which, in this case,
consists of 4 digits. The first digit (in bold) represents the Building or
Floor number. The last 3 digits represent the device’s set MAC address.
Figure 3.1 Building Automation Network Example
Building Level Network 1
Bldg 1/Flr 1
MAC Address 1
Device Instance 1001
MAC Address 1
Device Instance 2001
Building
Controller 1
Floor Level Network 1 (BACnet MS/TP)
Other Brand
Building Automation
Product
MAC Address 2
Device Instance 1002
Bldg 2/Flr 2
Router
MAC Address 50
Device Instance 1050
Floor Level Network 2 (BACnet MS/TP)
Other Brand
Building Automation
Product
MAC Address 2
Device Instance 2002
Building Level Network 2
MAC Address 50
Device Instance 2050
Other Brand
Building Automation
Product
MAC Address 127
Device Instance 1127
Other Brand
Building Automation
MAC Address 127
Device Instance 2127
Building
Controller 2
Product
3-4Configuring the Adapter
1. Set the value of Parameter 11 - [Device Instance] to a unique
Device Instance Number.
Figure 3.2 Device Instance Screen on an LCD HIM
Port 5 Device
20-COMM-B
Parameter #: 11
Device Instance
160000
2. Reset the adapter (see Resetting the Adapter on page 3-7) so that the
new Device Instance Number takes effect.
Default = 160000
Configuring the Adapter3-5
Setting a Comm Loss Action
By default, when communications are disrupted (for example, a cable is
disconnected), the drive responds by faulting if it is using I/O from the
network. You can configure a different response to communication
disruptions using Parameter 02 - [Comm Loss Action].
ATTENTION: Risk of injury or equipment damage exists.
Parameter 02 - [Comm Loss Action] lets you determine the action of
!
the adapter and connected drive if communications are disrupted. By
default, this parameter faults the drive. You can set this parameter so
that the drive continues to run. Take precautions to ensure that the
setting of this parameter does not create a risk of injury or equipment
damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected
cable).
To change the Comm Loss Action
Set the value of Parameter 02 - [Comm Loss Action] to the desired
response action:
Value ActionDescription
0FaultThe drive is faulted and stopped. (Default)
1StopThe drive is stopped, but not faulted.
2Zero DataThe drive is sent 0 for output data. This does not command a stop.
3Hold LastThe drive continues in its present state.
4Send Flt Cfg The drive is sent the data that you set in the fault configuration
Figure 3.3 Comm Loss Action Screen on an LCD HIM
Port 5 Device
20-COMM-B
Parameter #: 02
Comm Loss Action
0
Fault
Changes to this parameter take effect immediately. A reset is not
required.
If you set Parameter 02 - [Comm Loss Action] to “Send Flt Cfg,” the
values in the following parameters are sent to the drive after a
communications fault occurs. You must set these parameters to values
required by your application.
ParameterNameDescription
04Flt Cfg LogicA 16-bit value sent to the drive for Logic Command.
05Flt Cfg RefA 32-bit value (0 – 4294967295) sent to the drive as a
Changes to these parameters take effect immediately. A reset is not required.
Setting the Comm Loss Time
Set Parameter 03 - [Comm Loss Time] to a communication loss
timeout period suitable for your application. By default, the timeout is
set to ten (10) seconds. You can increase or decrease this value.
Alternatively, you can set the value to zero (0) to disable this timeout
feature so that the adapter does not detect communication losses.
Reference.
Important: If the drive uses a 16-bit Reference, the
most significant word of the value must be set to zero (0)
or a fault will occur.
ATTENTION: Risk of injury or equipment damage exists. Parameter
03 - [Comm Loss Time] lets you determine how long it will take the
!
adapter to detect network communication losses. By default, this
parameter sets the timeout to ten (10) seconds. You can set it so that the
duration is shorter, longer, or disabled. When set to disabled, this also
disables adapter Parameter 02 - [Comm Loss Action]. Therefore, a
communications fault action will be ignored. Take precautions to ensure
that the setting does not create a risk of injury or equipment damage.
When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable).
Figure 3.4 Comm Loss Time Screen on an LCD HIM
Port 5 Device
20-COMM-B
Parameter #: 03
Network Timeout
10Sec
0 <> 180
Changes to this parameter take effect immediately. A reset is not required.
Default = 10 Seconds
Configuring the Adapter3-7
Setting the Baud Rate
The value of Parameter 06 - [Baud Rate Cfg] determines the baud rate
used by the adapter. The Autobaud setting will detect the baud rate used
on the network if another device is setting the baud rate. Your application
may require a different setting.
1. Set the value of Parameter 06 - [Baud Rate Cfg] to the baud rate at
which your network is operating.
Figure 3.5 Baud Rate Screen on PowerFlex 4-Class HIM (22-HIM-*)
Port 5 Device
20-COMM-B
Parameter #: 06
Baud Rate Cfg
Autobaud
2. Reset the adapter (see Resetting the Adapter) so that the new baud
rate takes effect.
0
Value Description
0Autobaud (Default)
19600
219200
338400
476800
Resetting the Adapter
Changes to switch settings or some adapter parameters require that you
reset the adapter before the new settings take effect. You can reset the
adapter by cycling power to the drive or by using Parameter 01 - [Reset
Module].
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault when
!
you reset the adapter. Determine how your drive will respond before
resetting a connected adapter.
Set Parameter 01 - [Reset Module] to Reset Module.
Figure 3.6 Reset Screen on an LCD HIM
Port 5 Device
20-COMM-B
Parameter #: 01
Reset Module
1
Reset Module
Value Description
0Ready (Default)
1Reset Module
2Set Defaults
3-8Configuring the Adapter
When you enter 1 = Reset Module, the adapter will be immediately
reset. When you enter 2 = Set Defaults, the adapter will set all adapter
parameters to their factory-default settings. After performing a Set
Defaults, enter 1 = Reset Module so that the new values take effect. The
value of this parameter will be restored to 0 = Ready after the adapter is
reset.
Viewing the Adapter Configuration
The following read-only parameters provide information about how the
adapter is configured. You can view these parameters at any time.
Number NameDescription
07Baud Rate Act The baud rate used by the adapter. This will be one of the
08MAC Address The MAC address used by the adapter that was set by the
following values:
• The value of Parameter 06 - [Baud Rate Cfg].
• An old baud rate if Parameter 06 - [Baud Rate Cfg] has
been changed and the adapter has not been reset.
• The value “0” (Unknown) if Parameter 06 - [Baud Rate Cfg]
is set to “0” (Autobaud) and the adapter has not yet detected
the baud rate.
MAC Address Switches SW1-SW7 (Figure 2.1
).
Chapter 4
Using BACnet Objects
Chapter 4 provides information about controlling a compatible
PowerFlex 7-Class drive using BACnet objects.
TopicPage
Understanding BACnet Objects
Basic Drive Operation on the Network4-2
Supported BACnet Objects4-3
Understanding BACnet Objects
BACnet nodes are controlled and monitored by the use of several types
of objects. The BACnet controller performs read and write commands to
these objects, and the adapter transfers/translates the data between these
objects and the drive.
When a read or write command occurs to a specific object, data in the
object is refreshed from or transferred to the drive.
4-1
The BACnet object types that are supported by the adapter are:
• Analog Input (AI)
• Analog Output (AO)
• Analog Value (AV)
• Binary Input (BI)
• Binary Output (BO)
• Binary Value (BV)
4-2Using BACnet Objects
Basic Drive Operation on the Network
This section describes how to operate a drive on the network using a
combination of BACnet object types for basic control.
ATTENTION: Control information written to the adapter by a BACnet
controller is volatile. That is, it will not survive an adapter reset or
!
power cycle. For example, if a BACnet controller writes to a Binary
Output (BO) object to energize an output relay on the drive and then
that drive is reset or power cycled, the drive will return the relay to its
default (de-energized) state. The adapter will not attempt to restore the
relay to the energized state unless a BACnet controller writes to it again.
Basic Drive Control (Start/Stop)
1. Write a speed reference value (in %) to the Reference 1 Analog
Value object (AV0) Present Value property.
2. To start the drive, write a value of “1” to the Run/Stop Binary Value
object (BV10) Present Value property.
3. To stop the drive, write a value of “0” (zero) to the Run/Stop Binary
Value object (BV10) Present Value property.
Using an Alternate Speed Reference
To assign an alternate speed reference to the drive:
1. Write a speed reference value (in %) to the Reference 2 Analog
Value object (AV1) Present Value property.
2. Write a value of “1” to the Ref2/Ref1 Binary Value object (BV12)
Present Value property.
Changing Motor Rotation Direction
To command a reverse direction of motor rotation when the drive is
running, write a value of “1” to the Rev/Fwd Binary Value object
(BV11) Present Value property. To command a forward direction when
the drive is running, write a value of “0” (zero) to the Rev/Fwd Binary
Value object (BV11) Present Value property.
Clearing a Drive Fault
To clear a drive fault, write a value of “1” to the Clear Faults Binary Value
object (BV13) Present Value property.
Using BACnet Objects4-3
Supported BACnet Objects
The type of drive used on the network determines the specific BACnet
objects that are supported. Refer to Table 4.A for descriptions of the
BACnet objects and the drives supporting those objects.
Compatible PowerFlex Drives
70 Std. 70 EC 700 Std. 700 VC 700 H
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
—✔—✔✔
—— — ✔✔
✔✔ ✔ ✔✔
Table 4.A BACnet Object Descriptions and Supported Drives
Analog Input (AI) Objects
I/O terminal block.
AI0Analog Input 1 (%)Read the value of Analog Input 1 (voltage or current) on the drive’s
Object NameUse This Object to…
Analog Output (AO) Objects
block. The drive must be configured to accept the value of this
output from the network. This is done by setting drive parameter 342
AO0Analog Output 1 (%)Read/write the value of Analog Output 1 on the drive’s I/O terminal
- [Analog Out1 Sel] to the value “24” (Param Cntl).
AO1Analog Output 2 (%)Read/write the value of Analog Output 2 on the drive’s I/O terminal
I/O terminal block.
AI1Analog Input 2 (%)Read the value of Analog Input 2 (voltage or current) on the drive’s
block. The drive must be configured to accept the value of this
output from the network. This is done by setting drive parameter 345
- [Analog Out2 Sel] to the value “24” (Param Cntl).
Analog Value (AV) Objects
must be configured to accept its speed reference from the
network. This is typically done by setting drive parameter 90 -
[Speed Ref A Sel] to the value “22” (DPI Port 5).
AV0Reference 1 (%)Read/write the Reference 1 and Reference 2 values. The drive
AV1Reference 2 (%)✔✔ ✔ ✔✔
AV2Output Frequency (Hz) Read the drive’s output frequency.✔✔ ✔ ✔✔
AV3Output Current (Amps) Read the drive’s output current.✔✔ ✔ ✔✔
4-4Using BACnet Objects
Compatible PowerFlex Drives
70 Std. 70 EC 700 Std. 700 VC 700 H
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object NameUse This Object to…
AV4Output Voltage (VAC) Read the drive’s output voltage.✔✔ ✔ ✔✔
AV5Output Power (kW)Read the drive’s output power.✔✔ ✔ ✔✔
Binary Input (BI) Objects
Note: When writing, this object accepts only a value of “0” (zero).
AV6Output Energy (kWh) Read/write the drive’s accumulated output energy.
AV7DC Bus Voltage (VDC) Read the drive’s DC bus voltage.✔✔ ✔ ✔✔
AV8Drive Temp (°C)Read the drive’s temperature.✔✔ ✔ ✔✔
AV9PID Feedback (%)Read the drive’s PID feedback.✔✔ ✔ ✔✔
AV10PID Error (%)Read the drive’s PID error.✔✔ ✔ ✔✔
AV11Run Time (Hours)Read/write the drive’s accumulated run time.
Note: When writing, this object accepts only a value of “0” (zero).
AV12Fault 1Read the code for the drive’s most recent fault.✔✔ ✔ ✔✔
AV13Fault 2Read the code for the drive’s second most recent fault.✔✔ ✔ ✔✔
AV14Fault 3Read the code for the drive’s third most recent fault.✔✔ ✔ ✔✔
AV15Accel Time 1 (Sec)Read/write the drive’s Accel Time 1 setting.✔✔ ✔ ✔✔
AV16Decel Time 1 (Sec)Read/write the drive’s Decel Time 1 setting.✔✔ ✔ ✔✔
AV17Mailbox ParamRead/write any drive parameter. To read a drive parameter, write the
number for the desired parameter to the Mailbox Param object, and
then read the Mailbox Value object. To write a drive parameter, write
AV18Mailbox Value✔✔ ✔ ✔✔
the number for the desired parameter to the Mailbox Param object,
and then write the desired value to the Mailbox Value object.
BI0Digital Input 1Read the state of Digital Input 1 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
BI1Digital Input 2Read the state of Digital Input 2 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
BI2Digital Input 3Read the state of Digital Input 3 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
Using BACnet Objects4-5
Compatible PowerFlex Drives
70 Std. 70 EC 700 Std. 700 VC 700 H
—✔—✔✔
—✔—✔✔
—— — ✔✔
✔✔ ✔ ✔✔
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object NameUse This Object to…
BI3Digital Input 4Read the state of Digital Input 4 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
BI4Digital Input 5Read the state of Digital Input 5 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
BI5Digital Input 6Read the state of Digital Input 6 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
BI10Digital Output Act 1Read the state of Digital Output 1 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
Binary Output (BO) Objects
BI11Digital Output Act 2Read the state of Digital Output 2 on the drive’s I/O terminal block.✔✔ ✔ ✔✔
BI12Digital Output Act 3Read the state of Digital Output 3 on the drive’s I/O terminal block.———✔✔
BO0Digital Output Cmd 1Read/write the state of Digital Output 1 on the drive’s I/O terminal
block. The drive must be configured to accept the value of this output
from the network. This is done by setting drive parameter 380 - [Digital
Binary Value (BV) Objects
Out1 Sel] to the value “30” (Param Cntl).
block. The drive must be configured to accept the value of this output
from the network. This is done by setting drive parameter 384 - [Digital
Out2 Sel] to the value “30” (Param Cntl).
block. The drive must be configured to accept the value of this output
from the network. This is done by setting drive parameter 388 - [Digital
Out3 Sel] to the value “30” (Param Cntl).
BO1Digital Output Cmd 2Read/write the state of Digital Output 2 on the drive’s I/O terminal
BO2Digital Output Cmd 3Read/write the state of Digital Output 3 on the drive’s I/O terminal
accept a run command.
BV1RunningRead the drive’s Running status, which is active if the drive is running.✔✔ ✔ ✔✔
BV0ReadyRead the drive’s Ready status, which is active if the drive is ready to
4-6Using BACnet Objects
Compatible PowerFlex Drives
✔✔ ✔ ✔✔
70 Std. 70 EC 700 Std. 700 VC 700 H
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
✔✔ ✔ ✔✔
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object NameUse This Object to…
typically done by setting drive parameter 90 - [Speed Ref A Sel] to the
to clear the drive fault. Turning off this object does nothing.
value “22” (DPI Port 5).
BV13Clear FaultsRead/write the adapter’s Clear Faults command. Turn on this object
select the Reference 2 instance of the AV object as the drive’s speed
reference. Turn off this object to select Reference 1. The drive must
command the reverse direction when the drive is running. Turn off this
object to command Forward.
start the drive. Turn off this object to stop the drive.
running at the specified speed reference.
BV3FaultRead the drive’s Fault status, which is active if the drive is faulted.✔✔ ✔ ✔✔
BV4AlarmRead the drive’s Alarm status, which is active if the drive has an
alarm.
BV11Rev/FwdRead/write the adapter’s Rev/Fwd command. Turn on this object to
BV10Run/StopRead/write the adapter’s Run/Stop command. Turn on this object to
BV5At ReferenceRead the drive’s At Reference status, which is active if the drive is
running in the reverse direction.
BV2Running ReverseRead the drive’s Running Reverse status, which is active if the drive is
be configured to accept its speed reference from the network. This is
BV12Ref2/Ref1Read/write the adapter’s Ref2/Ref1 command. Turn on this object to
Chapter 5
PWR
STS
PORT
MOD
NET A
NET B
Troubleshooting
Chapter 5 provides information for diagnosing and troubleshooting
potential problems with the adapter and network.
TopicPage
Understanding the Status Indicators
PORT Status Indicator5-2
MOD Status Indicator5-3
NET A Status Indicator5-4
NET B Status Indicator5-4
Viewing and Clearing Adapter Diagnostic Items5-5
Viewing and Clearing Events5-7
5-1
Understanding the Status Indicators
The adapter has four status indicators. They can be viewed on the
adapter or through the drive cover. See Figure 5.1
.
Figure 5.1 Status Indicators (location on drive may vary)
➊
➋
➌
➍
Item Status Indicator DescriptionPage
PORTDPI Connection Status5-2
➊
➋
➌
➍
MODAdapter Status5-3
NET ASerial Communication Status5-4
NET BSerial Communication Traffic Status5-4
➊
➋
➌
➍
5-2Troubleshooting
PORT Status Indicator
StateCauseCorrective Actions
OffThe adapter is not powered or
Flashing
Red
Solid RedThe drive has refused an I/O
OrangeThe adapter is connected to a
Flashing
Green
Solid Green The adapter is properly
is not properly connected to
the drive.
The adapter is not receiving a
ping message from the drive.
connection from the adapter.
Another DPI peripheral is
using the same DPI port as
the adapter.
product that does not support
Rockwell Automation DPI
communications.
The adapter is establishing an
I/O connection to the drive.
connected and is
communicating with the drive.
• Securely connect the adapter to the drive
using the Internal Interface (ribbon)
cable.
• Apply power to the drive (or adapter if
mounted in a DPI External Comms Kit).
• Verify that cables are securely connected
and not damaged. Replace cables if
necessary.
• Cycle power to the drive (or adapter if
mounted in a DPI External Comms Kit).
Important: Cycle power to the drive (or
adapter if mounted in a DPI External
Comms Kit) after making the following
correction:
• Verify that all DPI cables on the drive are
securely connected and not damaged.
Replace cables if necessary.
Connect the adapter to a product that
supports Allen-Bradley DPI
communications (for example, a PowerFlex
70 or PowerFlex 700 drive).
No action required.
No action required.
Troubleshooting5-3
MOD Status Indicator
StateCauseCorrective Actions
OffThe adapter is not powered or
Flashing
Red
Flashing
Green
Solid Green The adapter is operational and
is not properly connected to
the drive.
The adapter has failed the
firmware test.
The adapter is operational, but
is not transferring I/O data.
transferring I/O data.
• Securely connect the adapter to the drive
using the Internal Interface (ribbon)
cable.
• Apply power to the drive (or adapter if
mounted in a DPI External Comms Kit).
• Cycle power to the drive (or adapter if
mounted in a DPI External Comms Kit).
• If cycling power does not correct the
problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.
• If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
Enable the network device that is providing
control to the adapter.
No action required.
5-4Troubleshooting
NET A Status Indicator
StateCauseCorrective Actions
OffThe adapter is not powered or
Flashing
Red
Flashing
Green
is not properly connected to
the network.
A network connection has
timed out.
The adapter is properly
connected and communicating
on the network.
NET B Status Indicator
• Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable.
• Correctly connect the network cable to
the adapter’s network connector.
• Apply power to the drive (or adapter if
mounted in a DPI External Comms Kit)
and network.
• Enable the network device that is
providing control to the adapter.
• Check the amount of traffic on the
network.
No action required. The LED will flash
green each time the token is passed to the
adapter by another BACnet device.
StateCauseCorrective Actions
OffAdapter is not powered, or is
not transmitting on the
network.
Flashing
Green
The adapter is transmitting on
the network.
If NET A indicator is off:
• Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable,
and to the network using the appropriate
network cable.
• Correctly connect the network cable to
the adapter’s network connector.
Normal condition if the adapter is idle.
No action required.
Troubleshooting5-5
Viewing and Clearing Adapter Diagnostic Items
The following adapter diagnostic items can be viewed using
DriveExplorer (version 3.01 or higher) or DriveExecutive (version 3.01
or higher) software, or an LCD PowerFlex HIM (Diagnostic/Device
Items).
To view and clear adapter diagnostic items
StepKeysExample Screen
Viewing Diagnostic Items
1. Access parameters in the adapter.
Refer to Using the PowerFlex
7-Class HIM on page 3-2.
2. Press the Up Arrow or Down Arrow
to scroll to Diagnostics.
3. Press Enter to display the
Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the
Device Items option.
5. Press the Up Arrow or Down Arrow
to scroll through the items.
Clearing Diagnostic Items
1. Access parameters in the Adapter.
Refer to Using the PowerFlex
7-Class HIM on page 3-2.
2. Press the Up Arrow or Down Arrow
to scroll to Para met er.
3. Press Enter to display the list of
parameters in the adapter.
4. Repeat steps 2 and 3 to select
Parameter 28 - [Clear Counters].
5. Set the value to 1 = Clear and then
press Enter to clear the following
diagnostic items: 24, 25, 26, 27, and
28.
OR
OR
OR
Main Menu:
Diagnostics
Param ete r
Device Select
Device Item #13
MAC Addr SW
1
Main Menu:
Diagnostics
Param ete r
Device Select
Parameter #: 28
Clear Counters
1
Clear
5-6Troubleshooting
Adapter Diagnostic Items
If you encounter unexpected communications problems, diagnostic
items can help you or Rockwell Automation personnel troubleshoot the
problem.
No. NameDescription
1Common Logic
Cmd
2Prod Logic CmdThe present value of the Product Logic Command being transmitted to the
3ReferenceThe present value of the Reference being transmitted to the drive by this
4Common Logic
Sts
5Prod Logic StsThe present value of the Product Logic Status being received from the drive
6FeedbackThe present value of the Feedback being received from the drive by this
7DPI PortThe port to which the adapter is connected (usually port 5).
8DPI Data RateThe data rate used by the drive and detected by the adapter.
9Ref/Fdbk SizeThe size of the Reference/Feedback used by the drive.
10 DPI Rx ErrorsThe present value of the DPI CAN Receive error counter register.
11 DPI Rx Error Max The maximum value of the DPI CAN Receive error counter register.
12 DPI Tx ErrorsThe present value of the DPI CAN Transmit error counter register.
13 DPI Tx Error Max The maximum value of the DPI CAN Transmit error counter register.
14 Boot Flash Count The number of times the boot firmware in this adapter has been flash
15 App Flash Count The number of times the application firmware in this adapter has been flash
16 MAC Addr SWThe MAC Address selected by the DIP switches (SW1-SW7) on the adapter.
17 BN Rx PacketsThe number of BACnet packets received by the adapter.
18 BN Tx PacketsThe number of BACnet packets transmitted by the adapter.
19 BN Overrun Errs A count of the number of BACnet receive overrun errors.
20 BN Framing Errs A count of the number of BACnet receive framing errors.
21 BN CRC ErrsA count of the number of BACnet receive CRC errors.
The present value of the Common Logic Command being transmitted to the
drive by this adapter.
drive by this adapter.
adapter. Note that a 16-bit value will be sent as the Most Significant Word of
the 32-bit field.
The present value of the Common Logic Status being received from the
drive by this adapter.
by this adapter.
adapter. Note that a 16-bit value will be sent as the Most Significant Word of
the 32-bit field.
Because the CAN interface controller on the adapter does not track the
maximum error register values, the adapter periodically polls the CAN
controller’s Receive error counter register and reports the maximum value it
has read in this diagnostic instance.
Because the CAN interface controller on the adapter does not track the
maximum error register values, the adapter periodically polls the CAN
controller’s Transmit error counter register and reports the maximum value it
has read in this diagnostic instance.
updated.
updated.
This value is not latched when the adapter powers up, and will update as the
switch settings are changed.
Troubleshooting5-7
Viewing and Clearing Events
The adapter maintains an event queue that reports the history of its
actions. You can view this event queue using an LCD PowerFlex HIM,
DriveExplorer software (3.01 or higher), or DriveExecutive software
(3.01 or higher).
To view and clear events
StepKeysExample Screen
Viewing Events
1. Access parameters in the adapter.
Refer to Using the PowerFlex
7-Class HIM on page 3-2.
2. Press the Up Arrow or Down Arrow
to scroll to Diagnostics.
3. Press Enter to display the
Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the
Events option and then View Event
Queue option.
5. Press the Up Arrow or Down Arrow
to scroll through the events. The
most recent event is Event 1.
OR
OR
Main Menu:
Diagnostics
Param ete r
Device Select
Event Q: 3E3
Ping Time Flt
Clearing Events
1. Access parameters in the adapter.
Refer to Using the PowerFlex
7-Class HIM on page 3-2.
2. Press the Up Arrow or Down Arrow
to scroll to Diagnostics.
3. Press Enter to display the
Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the
Events option and then the Clear
Event option or Clr Event Queue
option. A message will pop up to
confirm that you want to clear the
message or queue.
5. Press Enter to clear all events out of
the event queue. All event queue
entries will then display “No Event.”
OR
Dgn: Events
View Event Queue
Clear Event
Clr Event Queue
5-8Troubleshooting
Events
Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
Code Event Description
1No EventEmpty event queue entry.
2DPI Bus Off FltA bus-off condition was detected on DPI. This event may be caused by
3Ping Time FltA ping message was not received on DPI within the specified time.
4Port ID FltThe adapter is not connected to a correct port on a DPI product.
5Port Change FltThe DPI port changed after start up.
6Host Sent ResetThe drive sent a reset event message.
7EEPROM Sum Flt The EEPROM in the adapter is corrupt.
8Online @ 125 kbps The adapter detected the drive communicating at 125 kbps.
9Online @ 500 kbps The adapter detected the drive communicating at 500 kbps.
10Bad Host FltThe adapter was connected to an incompatible product.
11Dup Por t FltAnother peripheral with the same port number is already in use.
12Type 0 LoginThe adapter has logged in for Type 0 control.
13Type 0 Time FltThe adapter has not received a Type 0 status message within the
14DL LoginThe adapter has logged into a Datalink.
15DL Reject FltThe drive rejected an attempt to log in to a Datalink because the Datalink
16DL Time FltThe adapter has not received a Datalink message within the specified time.
17Reserved—
18Control DisabledThe adapter has sent a “Soft Control Disable” command to the drive.
19Control EnabledThe adapter has sent a “Soft Control Enable” command to the drive.
20Message Timeout A client-server message sent by the adapter was not completed within 1 sec.
21Fault Cfg ErrorOne of the Flt Cfg XX In parameters is set to a value greater than 65535
22App UpdatedNew application firmware was detected.
23Net Comm FltThe adapter detected a communications fault on the network.
24Net Sent ResetThe adapter received a fault from the network.
25Net Close FltAn I/O connection from the network to the adapter was closed.
26Net Idle FltThe adapter is receiving “idle” packets from the network.
27Net OpenAn I/O connection from the network to the adapter has been opened.
28Net TImeout FltAn I/O connection from the network to the adapter has timed out.
29PCCC IO CloseThe device sending PCCC Control messages to the adapter has set the
30PCCC IO OpenThe adapter has begun receiving PCCC Control messages.
31PCCC IO Time Flt The adapter has not received a PCCC Control message for longer than
32Watchdog T/O FltThe software detects a failure.
33EEPROM InitA blank EEPROM map revision was detected.
34Normal StartupThe adapter successfully started up.
35Manual ResetThe adapter was reset by changing its Reset Module parameter.
loose or broken cables or by noise.
specified time.
is not supported or is used by another peripheral.
and the drive requires a 16-bit value.
PCCC Control Timeout to zero.
the PCCC Control Timeout.
Specifications
Appendix A presents the specifications for the adapter.
TopicPage
Communications
ElectricalA-1
MechanicalA-1
EnvironmentalA-2
Regulatory ComplianceA-2
Communications
A-1
Network
Protocols
Data Rates
Drive
Protocol
Data Rates
BACnet MS/TP
9600, 19200, 38400 or 76800 baud
DPI
125 kbps or 500 kbps
Appendix A
Electrical
Consumption
Drive
Network
Mechanical
Dimensions
Height
Length
Width
Weight85g (3 oz.)
150 mA at 5 VDC
None
19 mm (0.75 in.)
86 mm (3.39 in.)
78.5 mm (3.09 in.)
A-2Specifications
Environmental
Temperature
Operating
Storage
Relative Humidity5 to 95% non-condensing
AtmosphereImportant: The adapter must not be installed in an area
where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the adapter is not going
to be installed for a period of time, it must be stored in an
area where it will not be exposed to a corrosive
atmosphere.
NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in
which case supplementary mitigation measures may be required.
Appendix B
Adapter Parameters
Appendix B provides information about the BACnet MS/TP adapter
parameters.
TopicPage
About Parameter Numbers
Parameter ListB-1
About Parameter Numbers
The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.
Configuration ToolNumbering Scheme
• DriveExplorer
• DriveExecutive
• HIM
B-1
The adapter parameters begin with parameter 1. For
example, Parameter 01 - [Reset Module] is parameter
1 as indicated by this manual.
Parameter List
Parameter
No. Name and DescriptionDetails
01 [Reset Module]
No action if set to “Ready.” Resets the adapter if
set to “Reset Module.” Restores the adapter to its
factory default settings if set to “Set Defaults.” This
parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
!
adapter.
Default:0 = Ready
Values0 = Ready
Type:Read/Write
Reset Required: No
1 = Reset Module
2 = Set Defaults
B-2Adapter Parameters
Parameter
No. Name and DescriptionDetails
02 [Comm Loss Action]
Sets the action that the adapter and drive will take
if the adapter detects that network
communications have been disrupted. This setting
is effective only if I/O that controls the drive is
transmitted through the adapter.
ATTENTION: Risk of injury or equipment damage exists. Parameter 02 - [Comm
Loss Action] lets you determine the action of the adapter and connected drive if
communications are disrupted. By default, this parameter faults the drive. You
!
can set this parameter so that the drive continues to run. Precautions should be
taken to ensure that the setting of this parameter does not create a risk of injury
or equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected drive).
Default:0 = Fault
Values:0 = Fault
Type:Read/Write
Reset Required: No
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
03 [Comm Loss Time]
Sets the communication loss timeout period in
seconds. The value zero disables this feature.
ATTENTION: Risk of injury or equipment damage exists. Parameter 03 - [Comm
Loss Time] lets you determine how long it will take the adapter to detect network
communication losses. By default, this parameter sets the timeout to ten (10)
!
seconds. You can set it so that the duration is shorter, longer, or disabled. When
set to disabled, this also disables adapter Parameter 02 - [Comm Loss Action].
Therefore, a communications fault action will be ignored. Take precautions to
ensure that the setting does not create a risk of injury or equipment damage.
When commissioning the drive, verify that your system responds correctly to
various situations (for example, a disconnected cable).
04 [Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if Parameter 02 - [Comm Loss Action] is
set to “Send Flt Cfg” and network communications
are disrupted.
The bit definitions will depend on the product to
which the adapter is connected. See the
documentation for the drive being used.
05 [Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
Parameter 02 - [Comm Loss Action] is set to
“Send Flt Cfg” and communications are disrupted.
06 [Baud Rate Cfg]
Sets the baud rate (kilobits per second) at which
the adapter communicates. (Updates Parameter 07 - [Baud Rate Act] after a reset.)
The table below lists the object types supported by the 20-COMM-B.
Dynamic object creation and deletion is not supported. The property
access rules use the following key:
R = Read Only: the property is supported for this object type
W = Read/Write: the property is supported for this object type
C = Commandable: the property is supported for this object type
Analog
Analog
Analog
Binary
Binary
Property
APDU TimeoutR
Application Software VersionR
Database RevisionR
DescriptionRRRRRRW
Device Address BindingR
Event StateRRRRRR
Firmware RevisionR
LocationW
Max APDU Length AcceptedR
Max Info FramesW
Max MasterW
Model NameR
Number of APDU RetriesR
Object IdentifierRRRRRRR
Object ListR
Object NameRRRRRRR
Object TypeRRRRRRR
Out of ServiceRRRRRR
Polar ityRR
Present ValueRCC
Priority ArrayRR
Protocol Object Types SupportedR
Protocol RevisionR
Protocol Services SupportedR
Protocol VersionR
Relinquish DefaultRR
Segmentation SupportedR
Status FlagsRRRRRR
System StatusR
UnitsRRR
Vendor IdentifierR
Vendor NameR
(1)
This property will accept a maximum of 16 characters when written.
(2)
This property will accept a maximum of 32 characters when written.
(3)
This property will accept a value between 1 and 255 inclusive when written.
(4)
This property will accept a value between 0 and 127 inclusive when written.
(5)
This property is commandable for some instances of this object. Otherwise it is read/write.
(6)
This property is supported only for instances of this object where the Present Value property is commandable.
Appendix D provides information about the unique routing capability for
up to 127 PowerFlex 7-Class drives on a BACnet MS/TP network when
using the DriveExplorer (Full version only) drive software tool.
First, configure the 20-COMM-B adapter in each networked drive using
the procedures described in Chapter 2
1203-SSS converter to connect the first networked drive to a laptop or
desktop PC with DriveExplorer Full. Thereafter, you can use
DriveExplorer Full to route to any drive on the BACnet MS/TP network
to configure or monitor the drive or any of its connected peripherals.
Use DriveExplorer Full to route through DPI to drives
connected directly on BACnet (Up to 127 drives!)
D-2Routing Capability for Networked Drives
Notes:
AAdapter
Devices such as drives, controllers, and computers usually require an
adapter to provide a communication interface between them and a
network such as BACnet MS/TP. An adapter reads data on the network
and transmits it to the connected device. It also reads data in the device
and transmits it to the network.
The 20-COMM-B adapter connects PowerFlex 7-Class drives to a
BACnet MS/TP network. Adapters are sometimes also called “cards,”
“embedded communication options,” “gateways,” “modules,” and
“peripherals.”
BBACnet MS/TP
BACnet is a data communication protocol for b
control networks. BACnet MS/TP (master-slave/token-passing) is a
specific type of BACnet network designed to run at speeds of 1 Mbps or
less over twisted pair wiring.
Baud Rate
The speed at which data is transferred on the network. Each device on a
network must be set for the same baud rate.
uilding automation and
Glossary
Bus Off
A condition that occurs when an abnormal rate of errors is detected in a
device. The bus off device cannot receive or transmit messages on the
network. This condition is often caused by corruption of the network
data signals due to noise or data rate mismatch.
CControlFLASH
DDPI (Drive Peripheral Interface)
ControlFLASH is an Allen-Bradley software tool that lets users
electronically update firmware on printed circuit boards. The tool takes
advantage of the growing use of flash memory (electronic erasable
chips) across industrial control products.
A second generation peripheral communication interface used by various
Allen-Bradley drives and power products, such as PowerFlex 7-Class
drives. It is a functional enhancement to SCANport.
Glossary-2
DPI Peripheral
A device that provides an interface between DPI and a network or user.
Peripheral devices are also referred to as “adapters” and “modules.” The
20-COMM-B, 1203-SSS or 1203-USB converter, and PowerFlex
7-Class HIMs (20-HIM-xxx) are examples of DPI peripherals.
DPI Product
A device that uses the DPI communications interface to communicate
with one or more peripheral devices. For example, a motor drive such as
a PowerFlex 7-Class drive is a DPI product. In this manual, a DPI
product is also referred to as “drive” or “host.”
DriveExplorer Software
DriveExplorer software is a tool for monitoring and configuring
Allen-Bradley products and adapters. It can be run on computers running
various Microsoft Windows operating systems. DriveExplorer (version
3.xx or higher) can be used to configure this adapter and PowerFlex
drives. Information about DriveExplorer software and a free lite version
can be accessed at http://www.ab.com/drives/driveexplorer.
DriveTools SP Software
A software suite designed for running on various Microsoft Windows
operating systems. This software suite provides a family of tools,
including DriveExecutive (version 3.01 or higher), that you can use to
program, monitor, control, troubleshoot, and maintain Allen-Bradley
products. DriveTools SP (version 1.01 or higher) can be used with
PowerFlex drives. Information about DriveTools SP can be accessed at
http://www.ab.com/drives/drivetools.
EEDS (Electronic Data Sheet) Files
EDS files are simple text files that are used by network configuration
tools to describe products so that you can easily commission them on a
network. EDS files describe a product device type, revision, and
configurable parameters. EDS files for many Allen-Bradley products can
be found at http://www.ab.com/networks/eds.
FFault Action
A fault action determines how the adapter and connected drive act when
a communications fault (for example, a cable is disconnected) occurs.
Fault Configuration
When communication is disrupted (for example, a cable is
disconnected), the adapter and PowerFlex drive can respond with a
user-defined fault configuration. The user sets the data that is sent to the
drive using specific fault configuration parameters in the adapter. When
a fault action parameter is set to use the fault configuration data and a
fault occurs, the data from these parameters is sent as the Logic
Command and Reference.
Flash Update
The process of updating firmware in a device. The adapter can be flash
updated using the Allen-Bradley software tool ControlFLASH, the
built-in flash capability of DriveExplorer (version 4.01 or higher), or
when the adapter is installed in a DPI External Comms Kit, the
X-Modem protocol and a 1203-SSS converter (version 3.xx or higher
firmware).
HHIM (Human Interface Module)
A device that can be used to configure and control a drive. PowerFlex
7-Class HIMs (20-HIM-xxx) can be used to configure PowerFlex
7-Class drives and connected peripherals.
Hold Last
When communication is disrupted (for example, a cable is
disconnected), the adapter and PowerFlex drive can respond by holding
last. Hold last results in the drive receiving the last data received via the
network connection before the disruption. If the drive was running and
using the Reference from the adapter, it will continue to run at the same
Reference.
Glossary-3
II/O Data
I/O data, sometimes called “implicit messages” or “input/output,”
transmit time-critical data such as a Logic Command and Reference. The
terms “input” and “output” are defined from the controller’s point of
view. Output is produced by the controller and consumed by the adapter.
Input is produced by the adapter and consumed by the controller.
LLogic Command/Logic Status
The Logic Command is used to control the PowerFlex drive (for
example, start, stop, direction). It consists of one 16-bit word of output to
the adapter from the network. The definitions of the bits in this word
depend on the drive.
The Logic Status is used to monitor the PowerFlex drive (for example,
operating state, motor direction). It consists of one 16-bit word of input
Glossary-4
from the adapter to the network. The definitions of the bits in this word
depend on the drive.
MMAC Address
Each device on a network must have a unique MAC address to identify
it. On BACnet MS/TP networks, devices can have MAC addresses
between 0 and 127 if the network is set up to accommodate that number
of devices.
NNVS (Non-Volatile Storage)
NVS is the permanent memory of a device. Devices such as the adapter
and drive store parameters and other information in NVS so that they are
not lost when the device loses power. NVS is sometimes called
“EEPROM.”
PCCC is the protocol used by some controllers to communicate with
devices on a network. Some software products (for example,
DriveExplorer and DriveExecutive) also use PCCC to communicate.
Ping
A message that is sent by a DPI product to its peripheral devices. They
use the ping to gather data about the product, including whether it can
receive messages and whether they can log in for control.
PowerFlex 7-Class (Architecture-Class) Drives
The Allen-Bradley PowerFlex 7-Class (Architecture-Class) family of
drives for use on BACnet MS/TP networks include the PowerFlex 70
(standard and enhanced control), PowerFlex 700 (standard and vector
control), PowerFlex 700 Series B (standard and vector control), and
PowerFlex 700H. These drives can be used for applications ranging from
0.37 kW (0.5 HP) to 3,000 kW (4,000 HP).
RReference/Feedback
The Reference is used to send a setpoint (for example, speed, frequency,
torque) to the drive. It consists of one word of output to the adapter from
the network. The size of the word (either a 16-bit word or 32-bit word) is
determined by the drive.
Feedback is used to monitor the speed of the drive. It consists of one
word of input from the adapter to the network. The size of the word
(either a 16-bit word or 32-bit word) is determined by the drive.
SStatus Indicators
Status indicators are LEDs that are used to report the status of the
adapter, network, and drive. They are on the adapter and can be viewed
on the front cover of the drive when the drive is powered.
TType 0 Control
When transmitting I/O, the adapter can use different types of messages
for control. The Type 0 events help Allen-Bradley personnel identify the
type of messages that an adapter is using.
ZZero Data
When communications are disrupted (for example, a cable is
disconnected), the adapter and drive can respond with zero data. Zero
data results in the drive receiving zero as values for Logic Command and
Reference data. If the drive was running and using the Reference from
the adapter, it will stay running but at zero Reference.
Glossary-5
Glossary-6
Index
Numerics
3-pin linear plug, 2-11
A
adapter
applying power, 2-8
commissioning, 2-1
compatible products, 1-3
components, 1-1
connecting to a drive, 2-6
connecting to the network, 2-10
definition, G-1
features, 1-2
grounding, 2-7
installation, 2-1 to 2-11
mounting on a drive, 2-7
parameters, B-1 to B-3
resetting, 3-7
setting the baud rate, 3-7
setting the MAC address, 2-2
specifications, A-1
viewing its configuration, 3-8
applying power to the adapter, 2-8
attentions, 1-4
B
BACnet MS/TP network, G-1
BACnet objects
for basic drive control, 4-2
supported by the adapter, 4-3
types, 4-1
baud rate
definition, G-1
setting, 3-7
Baud Rate Act parameter, B-3
Baud Rate Cfg parameter, B-2
bus off, G-1
C
cables
DPI Internal Interface, 2-6
network, 2-11
required for installation, 1-3
Comm Loss Action parameter, B-2
Comm Loss Time parameter, B-2
commissioning the adapter, 2-1
compatible products, 1-3
components of the adapter, 1-1
configuration tools, 3-1
configuring parameters, 3-1 to 3-8
connecting
adapter to the drive, 2-6
adapter to the network, 2-10
ControlFLASH, G-1
D
Device Instance parameter, B-3
diagnostic device items
list of, 5-6
viewing and clearing, 5-5
dimensions, A-1
DPI
definition, G-1
peripheral, G-2
ports on adapter and drive, 2-6
products, 1-3, G-2
drive, see DPI products
DriveExecutive software
accessing parameters with, 3-1
definition, G-2
web site, G-2
DriveExplorer software
accessing parameters with, 3-1
definition, G-2
free lite version, G-2
web site, G-2
DriveTools SP software, G-2
Index-2
E
EDS (Electronic Data Sheet) files
definition, G-2
web site, G-2
EEPROM, see Non-Volatile Storage
(NVS)
electrical specifications, A-1
environmental specifications, A-2
equipment required, 1-3
events
list of, 5-8
viewing and clearing, 5-7
F
factory-default settings, 3-7
fault action
configuring the adapter for, 3-5
definition, G-2
fault configuration
configuring the adapter for, 3-6
definition, G-2
features of the adapter, 1-2
firmware release, P-2
flash update, G-3
Flt Cfg Logic parameter, B-2
Flt Cfg Ref parameter, B-2
G
grounding the adapter, 2-7
H
HIM (Human Interface Module)
definition, G-3
LCD model to access parameters,
3-2
LED model to access parameters,
3-2
hold last
configuring the adapter for, 3-5
definition, G-3
I
I/O data, G-3
installation
applying power to the adapter, 2-8
connecting to the drive, 2-6
connecting to the network, 2-10
preparing for, 2-1
Internal Interface cables
connecting to adapter and drive,
2-6
shipped with adapter, 1-3
L
LCD HIM to access parameters, 3-2
LED HIM to access parameters, 3-2
LEDs, see status indicators
Logic Command/Status, G-3
M
MAC address
definition, G-4
setting with switches, 2-2
MAC Address parameter, B-3
manual
conventions, P-2
related documentation, P-1
Max Info Frames parameter, B-3
Max Master parameter, B-3
mechanical dimensions, A-1
MOD status indicator
locating, 1-7
troubleshooting with, 5-3
mounting the adapter, 2-7
N
NET A status indicator
locating, 1-7
troubleshooting with, 5-4
Index-3
NET B status indicator
locating, 1-7
troubleshooting with, 5-4
network cable - connecting to 3-pin
plug, 2-11
Non-Volatile Storage (NVS)
accessing parameters in, 3-1
definition, G-4
P
parameters
accessing, 3-1
configuring, 3-1 to 3-8
list of, B-1 to B-3
numbering scheme, B-1
restoring to factory-default
settings, 3-7
PCCC (Programmable Controller
Communications
Command), G-4
ping, G-4
plug for network cable, 2-11
PORT status indicator
locating, 1-7
troubleshooting with, 5-2
power consumption, A-1
PowerFlex drives compatible with
adapter, 1-3
preparing for installation, 2-1
ribbon cable, see Internal Interface
cable
routing capability for networked
drives, D-1
S
safety precautions, 1-4
specifications for the adapter, A-1
status indicators
definition, G-5
locating, 1-7
MOD, 1-7, 5-3
NET A, 1-7, 5-4
NET B, 1-7, 5-4
normal operation, 2-8
PORT, 1-7, 5-2
troubleshooting with, 5-2 to 5-4
understanding, 5-1
switches
MAC address, 2-2
TERM, -BIAS, and +BIAS, 2-4
T
technical support, P-2
three-pin linear plug, 2-11
tools required, 1-3
troubleshooting, 5-1 to 5-8
Q
quick start, 1-6
R
Reference/Feedback, G-4
regulatory compliance, A-2
related documentation, P-1
required equipment, 1-3
Reset Module parameter, B-1
resetting the adapter, 3-7
U
update, see flash update
V
viewing adapter configuration, 3-8
Index-4
W
web site
DriveExecutive software, G-2
DriveExplorer software, G-2
DriveTools SP software, G-2
EDS files, G-2
PowerFlex manuals, P-1
Z
zero data
configuring the adapter for, 3-5
definition, G-5
Notes:
Index-5
Index-6
Notes:
A
A
U.S. Allen-Bradley Drives Technical Support
Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
mericas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444