Rockwell Automation 20-750-CNETC User Manual

User Manual
PowerFlex 20-750-CNETC Coaxial ControlNet Option Module
Firmware Revision Number 1.xxx

Important User Information

IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, TechConnect, PowerFlex, Connected Components Workbench, DriveExplorer, DriveTools, DriveExecutive, RSLinx, RSLogix, Studio 5000, and ControlLogix are trademarks of Roc kwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual contains new and updated information.

Summary of Changes

New and Updated Information

This table contains the changes made to this revision.
Top ic Pag e
Added information about the Connected Components Workbench software configuration tool for drives and connected peripherals.
In the Chapter 3 subsection ‘Enable Datalinks To Write Data’, revised step 3 for better understanding. 27
In the Chapter 4 sub-subsection ‘Add the Drive/Option Module to the I/O Configuration’, included new information for the Create Database, Web Update, and Match Drive buttons on the Module Definition dialog box, which are described in the step 6 table.
In Chapter 6 Explicit Messaging, added Table 4. Also added footnotes about limitations when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F to tables below message configuration dialog boxes.
Throughout manual
41
7484
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 3
Summary of Changes
Notes:
4 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Table of Contents

Preface
Getting Started
Installing the Option Module
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Understanding Parameter Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chapter 2
Preparing for an Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Setting the Node Address Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connecting the Option Module to the Drive . . . . . . . . . . . . . . . . . . . . . . . 19
Connecting the Option Module to the Network. . . . . . . . . . . . . . . . . . . . 19
Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Commissioning the Option Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Configuring the Option Module
Configuring the I/O
Chapter 3
Configuration Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM to
Access Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Setting the Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Setting a Master-Slave Hierarchy (Optional) . . . . . . . . . . . . . . . . . . . . . . . 26
Setting a Fault Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Resetting the Option Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Restoring Option Module Parameters to Factory Defaults . . . . . . . . . . . 32
Viewing the Option Module Status Using Parameters . . . . . . . . . . . . . . . 33
Updating the Option Module Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 4
Using RSLinx Classic Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
ControlLogix Controller Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 5
Table of Contents
Chapter 5
Using the I/O
Using Explicit Messaging
Troubleshooting
About I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Understanding the ControlLogix Controller I/O Image. . . . . . . . . . . . . 62
Using Logic Command/Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Using Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Using Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Example Ladder Logic Program Information . . . . . . . . . . . . . . . . . . . . . . . 65
ControlLogix Controller Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Chapter 6
About Explicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Performing Explicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
ControlLogix Controller Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Chapter 7
Understanding the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
PORT Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
MOD Status Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
NET A and NET B Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Viewing Option Module Diagnostic Items . . . . . . . . . . . . . . . . . . . . . . . . . 92
Viewing and Clearing Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Specifications
Option Module Parameters
Appendix A
Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Regulatory Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Appendix B
Parameter Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
About Parameter Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
How Parameters Are Organized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Device Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Host Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Appendix C
Table of Contents
ControlNet Objects
Logic Command/Status Words: PowerFlex 750-Series Drives
History of Changes
Identity Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Register Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
PCCC Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
DPI Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
DPI Parameter Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
DPI Fault Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
DPI Alarm Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
DPI Diagnostic Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
DPI Time Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Host DPI Parameter Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Appendix D
Logic Command Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Logic Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Appendix E
750COM-UM003A-EN-P, September 2009 . . . . . . . . . . . . . . . . . . . . . . 137
Glossary
Index
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 7
Table of Contents
Notes:
8 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Preface

This manual provides information about the 20-750-CNETC ControlNet option module for network communication and how to use the module with PowerFlex® 750-Series drives.

Conventions Used in This Manual

Rockwell Automation Support

The following conventions are used throughout this manual:
Parameter names are shown in the format Device Parameter xx - [*] or Host Parameter xx - [*]. The xx represents the parameter number. The *
represents the parameter name—for example Device Parameter 01 - [DPI Por t].
The firmware revision number (FRN) is displayed as FRN X.xxx, where
X’ is the major revision number and ‘xxx’ is the minor revision number.
The dialog box images in this manual resulted from using the following software:
RSLinx® Classic software, version 2.52RSNetWorx for ControlNet software, version 8.00RSLogix™ 5000 software, version 16.00
Different versions of the software may have dialog boxes that vary in appearance, and differences in procedures.
Rockwell Automation offers support services worldwide, with over 75 sales and support offices, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation representatives are in every major country in the world.

Local Product Support

Contact your local Rockwell Automation representative for the following:
Sales and order support
Product technical training
Wa r r a nt y s up po rt
Support service agreements

Technical Product Assistance

For technical assistance, please review the information in Chapter 7, Troubleshooting, first. If you still have problems, then access the Allen-Bradley Technical Support website at http://www.ab.com/support/abdrives Rockwell Automation.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 9
or contact
Preface

Additional Resources

Resource Description
Network Communication Option Module Installation Instructions, publication 750COM-IN002 Information on the installation of PowerFlex 750-Series Network
ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002 Information on the required components of a ControlNet coax media system,
Connected Components Wo rkbench we bsite http://www.ab.com/support/abdrives/webupdate/
software.html, and online help
DriveExplorer website http://www.ab.com/drives/driveexplorer
DriveExecutive website http://www.ab.com/drives/drivetools, and online help
RSNetWorx for ControlNet Getting Results Guide, publication CNET-GR001, and online help
PowerFlex 750-Series Drive Installation Instructions, publication 750-IN001
PowerFlex 750-Series Drive Programming Manual, publication 750-PM001
PowerFlex 750-Series Drive Technical Data, publication 750-TD001
PowerFlex 20-HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication 20HIM-UM001
Getting Results with RSLinx Guide, publication LINX-GR001, and online help
RSLogix 5000 PIDE Autotuner Getting Results Guide, publication PIDE-GR001, and online help
ControlNet Network Configuration User Manual, publication CNET-UM001
(1)
(1) The online help is installed with the software.
These documents contain additional information concerning related products from Rockwell Automation.
Commun ication mo dules.
which is useful in determining your system and for installing the required components.
Information on the Connected Components Workbench™ software tool—and includes a link for free software download.
, and online help
(1)
(1)
(1)
Information on installing, programming, and technical data of PowerFlex®
(1)
Information on how to use ControlNet communication modules with a
Information on using the DriveExplorer™ software tool.
Information on using the DriveExecutive™ software tool.
Information on using RSNetWorx™ for ControlNet.
750-Series drives.
Information on the installation and use of PowerFlex 20-HIM-A6 or 20-HIM-
C6S HIMs.
Information on using RSLinx Classic software.
(1)
Information on using the RSLogix 5000 software tool.
ControlLogix controller.
You can view or download publications at http://
www.rockwellautomation.com/literature. To order paper copies of technical
documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related questions, go to the Drives Service & Support website at http://www.ab.com/support/
abdrives and click on the Downloads or Knowledgebase link.
.
10 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Chapter 1

Item Part Description
Status Indicators Four status indicators that indicate the
status of the option module and network communication. See
Chapter 7, Troubleshooting.
Node Address Switche s
Sets the node address of the option module. See Setting the Node Address
Switches on page 18.
Channel A Coax R eceptacle
BNC connector for the Channel A network coaxial cable.
Channel B Coax R eceptacle
BNC connector for the Channel B (redundant) network coaxial cable.

Getting Started

The 20-750-CNETC option module is intended for installation into a PowerFlex 750-Series drive and is used for network communication.
Top ic Pa ge

Components

Featu res
Compatible Produ cts
Required Equipment
Safety Precautions 15
Quick Start 16
11
12
13
13
Components
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 11
Chapter 1 Getting Started

Features

The features of the option module include the following:
Captive screws to secure and ground the module to the drive.
Switches to set a node address before applying power to the drive—or you
can disable the switches and use an option module parameter to configure the node address.
Compatibility with the following configuration tools to configure the option module and host drive:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM (Human Interface
Module) on the drive, if available
Connected Components Workbench software, version 1.02 or laterDriveExplorer software, version 6.01 or laterDriveExecutive software, version 5.01 or later
Status indicators that report the status of the option module and network
communication. They are visible when the drive cover is removed.
Parameter-configured 32-bit Datalinks in the I/O to meet application requirements (16 Datalinks to write data from the network to the drive, and 16 Datalinks to read data to the network from the drive).
Explicit Messaging support.
Master-Slave hierarchy that can be set up so that the option module and
PowerFlex 750-Series drive transmit data to and from a scanner on the network.
User-defined fault actions to determine how the option module and its connected host drive respond to the following:
I/O messaging communication disruptions (Comm Flt Action)Controllers in Idle mode (Idle Flt Action)Explicit messaging disruptions for drive control via PCCC, the CIP
Register Object, or the CIP Assembly object (Msg Flt Action)
Access to any PowerFlex drive and its connected peripherals on the network to which the option module is connected.
12 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Getting Started Chapter 1

Understanding Parameter Types

The option module has two types of parameters:
Device parameters are used to configure the option module to operate on the network.
Host parameters are used to configure the option module Datalink transfer and various fault actions with the drive.
Yo u can vi ew op ti on m od u le Device parameters and Host parameters with any of the following drive configuration tools:
PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM—use the or key to scroll to the drive port in which the module resides, press the (Folders) key, and use the or key to scroll to the DEV PARA M or H OST PAR AM fo lder.
Connected Components Workbench software—click the tab for the option module at the bottom of the window, click the Parameters icon in the tool bar, and click the Device or Host Parameters tab.
DriveExplorer software—find the option module in the treeview and open its Parameters folder.

Compatible Products

Required Equipment

DriveExecutive software—find the option module in the treeview, expand the module in the tree, and open its Parameters folder.
At the time of publication, the option module is compatible with the following products:
PowerFlex 753 drives (all firmware revisions)
PowerFlex 755 drives (all firmware revisions)
Some of the equipment that is required for use with the option module is shipped with the module, but some you must supply yourself.
Equipment Shipped with the Option Module
When you unpack the option module, verify that the package includes the following:
One 20-750-CNETC Coaxial ControlNet Option Module
One Network Communication Option Module Installation Instructions,
publication 750COM-IN002
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 13
Chapter 1 Getting Started
User-Supplied Equipment
To install and configure the option module, you must supply the following:
A small screwdriver
ControlNet cable—for details, see the ControlNet Coax Media Planning
and Installation Guide, publication CNET-IN002
Drive and option module configuration tool, such as the following:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
– Connected Components Workbench software, version 1.02 or later
Connected Components Workbench is the recommended stand-alone software tool for use with PowerFlex drives. You can obtain a free copy by:
Internet download at http://www.ab.com/support/abdrives/
webupdate/software.html
Requesting a DVD at http://www.ab.com/onecontact/
controllers/micro800/
Your local distributor may also have copies of the DVD available.
Connected Components Workbench software cannot be used to configure SCANport-based drives or Bulletin 160 drives.
– DriveExplorer software, version 6.01 or later
This software tool has been discontinued and is now available as freeware at http://www.ab.com/support/abdrives/webupdate/
software.html. There are no plans to provide future updates to this tool
and the download is being provided ‘as-is’ for users that lost their DriveExplorer CD, or need to configure legacy products not supported by Connected Components Workbench software.
– DriveExecutive software, version 5.01 or later
A Lite version of DriveExecutive software ships with RSLogix 5000, RSNetworx MD, FactoryTalk AssetCentre, and IntelliCENTER software. All other versions are purchasable items:
9303-4DTE01ENE Drive Executive software
9303-4DTS01ENE DriveTools SP Suite (includes
DriveExecutive and DriveObserver software)
9303-4DTE2S01ENE DriveExecutive software upgrade to DriveTools SP Suite (adds DriveObserver software)
DriveExecutive software updates (patches, and so forth) can be obtained at http://www.ab.com/support/abdrives/webupdate/software.html is highly recommended that you periodically check for and install the latest update.
RSNetWorx for ControlNet network configuration software, version 8.00
or later
14 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
. It
Getting Started Chapter 1
Controller configuration software, such as RSLogix 5000 software, version 20.00
or earlier, or Studio 5000™ Logix Designer application, version 21.00 or later
A computer communication card, such as 1784-PCC, 1784-KTCX, or
1770-KFC, for connection to the ControlNet network

Safety Precautions

Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove all power from the PowerFlex drive, and then verify power has been discharged before installing or removing the option module.
ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the associated machinery should plan or implement the installation, startup, configuration, and subsequent maintenance of the drive using the option module. Failure to comply may result in injury and/ or equipment damage.
ATTENTION: Risk of equipment damage exists. The option module contains electrostatic discharge (ESD) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the option module. If you are unfamiliar with static control procedures, see Guarding Against Electrostatic Damage, publication 8000-4.5.2
ATTENTION: Risk of injury or equipment damage exists. If the option module is transmitting control I/O to the drive, the drive may fault when you reset the option module. Determine how your drive will respond before resetting the module.
.
ATTENTION: Risk of injury or equipment damage exists. Host Parameters 33 ­[Comm Flt Action], 34 - [Idle Flt Action], and 36 - [Msg Flt Action] let you
determine the action of the option module and connected drive if I/O communication is disrupted, the controller is idle, or explicit messaging for drive control is disrupted. By default, these parameters fault the drive. You may configure these parameters so that the drive continues to run, however, precautions should be taken to verify that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable or a controller in idle state).
ATTENTION: Risk of injury or equipment damage exists. When a system is configured for the first time, there may be unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of example. There are many variables and requirements with any application. Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 15
Chapter 1 Getting Started

Quick Start

This section is provided to help experienced users quickly start using the option module. If you are unsure how to complete a step, refer to the referenced chapter.
Step Action See
1 Review the safety precautions for the option module. Throughout this manual
2 Verify that the PowerFlex drive is properly installed. PowerFlex 750-Series AC Drive
3 Install the option module.
a. Verify that the PowerFlex drive is not powered.
b. Insert the option module in drive Port 4, 5, or 6.
c. Use the captive crews to secure and ground the option module to
the drive.
d. Connect the option module to the network with a ControlNet
cable.
4 Apply power to the option module.
a. Verify that the option module is installed correctly.
The option module receives power from the drive.
b. Apply power to the drive.
The status indicators should be green. If they flash red, there is a problem. See Chapter 7
c. Configure and verify key drive parameters.
5 Configure the option module for your application.
Set option module parameters for the following functions as required by your application:
Node address
I/O configuration
Master-Slave hierarchy
Fault actions
6 Configure the controller to communicate with the option module.
Use the network configuration tool RSNetWorx for ControlNet software, and a controller configuration tool, such as RSLogix software, to configure the master on the network to recognize the option module and drive.
7 Create a ladder logic program.
Use a controller configuration tool, such as RSLogix software, to create a ladder logic program that enables you to do the following:
Control the connected drive, via the option module, by using I/O.
Monitor or configure the drive by using explicit messages.
, Troubleshooting.
Installation Instructions, publication 750-IN001
Network Communication Option Module Installation Instructions, publication 750COM-IN002
Chapter 2,
Installing the Option Module
Chapter 2,
Installing the Option Module
Chapter 3,
Configuring the Option Module
,
Chapter 4
Configuring the I/O
,
Chapter 5
Using the I/O
,
Chapter 6
Using Explicit Messaging
and
16 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Chapter 2

Installing the Option Module

This chapter provides instructions for installing the option module in a PowerFlex 750-Series drive.
Top ic Pa ge

Preparing for an Installation

Setting the Node Address Switches
Connecting the Option Module to the Drive
Connecting the Option Module to the Network
Applying Power 20
Commissioning the Option Module 23
17
18
19
19
Preparing for an Installation
Before installing the option module, do the following:
Read the ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002 selecting cables, setting up a network, and network basics.
Verify that you have all required equipment. See Required Equipment
page 13.
ATTENTION: Risk of equipment damage exists. The option module contains electrostatic discharge (ESD) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the option module. If you are unfamiliar with static control procedures, see Guarding Against Electrostatic Damage, publication 8000-4.5.2
. This publication provides information on
.
on
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 17
Chapter 2 Installing the Option Module
IMPORTANT
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
ONES
Posi tion
TENS
Posi tion

Setting the Node Address Switches

Set the option module Node Address switches (Figure 1) by rotating the switches to the desired value for each digit.
Each node on the ControlNet network must have a unique address. Set the node address before power is applied because the option module uses the node address it detects when it first receives power. To change a node address, you must set the new value and then remove and reapply power to (or reset) the option module.
Figure 1 - Setting Node Address Switches
Settings Description
00 If the Node Address switches are set to ‘00’, the option module uses the value stored in Device Parameter
01…99 Node address used by the option module. The default switch setting is 02.
05 - [Net Addr Cfg] for the node address. See Setting the Node Address
The switch settings can be verified by viewing Device Parameter 06 - [Net Addr Act] or Diagnostic Device Item number 58 (page 93
drive configuration tools:
PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
Connected Components Workbench software, version 1.02 or later
DriveExplorer software, version 6.01 or later
DriveExecutive software, version 5.01 or later
on page 26.
) with any of the following
18 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Installing the Option Module Chapter 2
IMPORTANT
IMPORTANT
Control Logix Controller
(with 1756-CNBR Bridge)
PowerFlex 755 Drives
(with 20-750-CNETC Option Modules)
(optional redundancy)
Channel A
Channel B
Control Net Network

Connecting the Option Module to the Drive

Connecting the Option Module to the Network

Remove power from the drive before installing the option module in the drive control pod.
Install the option module in the PowerFlex 750-Series Drive control pod in Port 4, 5, or 6. For more installation details, see the Network Communication Option Module Installation Instructions, publication 750COM-IN002 the option module.
After inserting the option module into Port 4, 5, or 6, make sure to tighten the module screws to the drive control pod to properly ground the module to the drive. Torque both screws to 0.45…0.67 N•m (4.0…6.0 lb•in).
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before connecting the option module to the network.
1. Remove power from the drive.
, provided with
2. Remove the drive cover and lift up the drive HIM bezel to its open
3. Use static control precautions.
4. Connect one end of the ControlNet cable to the network.
5. Route the other end of the ControlNet cable through the bottom of the
position to access the drive control pod.
Figure 2 - Coax Network Wiring Example
drive, and insert its ControlNet cable plug into the mating option module receptacle. We recommend using a 1786-TPS straight tap.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 19
Chapter 2 Installing the Option Module
See Tab le 1 for
possible start-up
status indications.
Drive Control Pod
(drive shown with cover removed)

Applying Power

ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable
operation may occur if you fail to verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
Apply power to the drive. The option module receives its power from the drive. When you apply power to the option module for the first time, its topmost ‘PORT’ status indicator should be steady green or flashing green after an initialization. If it is red, there is a problem. See Chapter 7
, Troubleshooting.
Start-Up Status Indications
After power has been applied, the drive STS (status) indicator can be viewed on the front of the drive and the option module status indicators can be viewed with the drive cover open or removed (Figure 3 are shown in Ta b l e 1
Figure 3 - Drive and Option Module Status Indicators
.
). Possible start-up status indications
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
20 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Table 1 - Drive and Option Module Start-Up Status Indications
Item Name Color State Description
Drive STS Indicator
STS
(Status)
PORT Green Flashing Normal operation. The option module is establishing an I/O
MOD Green Flashing Normal operation. The option module is operating but is not
NET A
NET B
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing When running, a type 2 (non-configurable) alarm condition exists
Steady A type 1 (user configurable) alarm condition exists, but the drive
Red Flashing A major fault has occurred. Drive will stop. Drive cannot be started
Steady A non-resettable fault has occurred.
Red/Yellow Flashing Alternately A minor fault has occurred. Use drive parameter 950 - [Minor Flt
Yellow/Green Flashing Alternately When running, a type 1 alarm exists.
Green/Red Flashing Alternately Drive is firmware updating.
Option Module Status Indicators
Steady Normal operation. The option module is properly connected and
Steady Normal operation. The option module is operating and transferring
Green Flashing A temporary channel error has occurred or the channel is in ‘listen-
Steady Normal operation for that channel. The option module is properly
Red Flashing The channel is not receiving network activity.
Green/Red Flashing Alternately There is an invalid link configuration for that channel.
Installing the Option Module Chapter 2
– drive continues to run. When stopped, a start inhibit condition exists and the drive cannot be started (see drive parameter 933 ­[Start Inhibits]).
continues to run.
until fault condition is cleared.
Config] to enable. If not enabled, acts like a major fault. When running, the drive continues to run. System is brought to a stop under system control. The fault must be cleared to continue.
connection to the drive. It will turn steady green or red.
communicating with the drive.
transferring I/O data to a controller.
I/O data to a controller.
only’ mode.
connected and communicating on the network.
After verifying correct operation, swing down the drive HIM bezel to its closed position and install the drive cover. For more details on status indicator operation, see page 90
and page 91.
Configuring and Verifying Key Drive Parameters
The PowerFlex 750-Series drive can be separately configured for the control and Reference functions in various combinations. For example, you could set the drive to have its control come from a peripheral or terminal block with the Reference coming from the network. Or you could set the drive to have its control come from the network with the Reference coming from another peripheral or terminal block. Or you could set the drive to have both its control and Reference come from the network.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 21
Chapter 2 Installing the Option Module
The following steps in this section assume that the drive will receive the Logic Command and Reference from the network.
1. Verify that drive Parameter 301 - [Access Level] is set to ‘1’ (Advanced) or ‘2’ (Expert) to access the required parameters in this procedure.
2. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed Reference.
a. Set the Port field to ‘0’ as shown below.
b. Set the Parameter field to point to the port (slot) in which the option
module is installed (for this example, Port 4 Reference). The number ‘874’ in the Parameter field of the example dialog box
above is the parameter in the drive that points to the port.
3. Verify that drive Parameter 930 - [Speed Ref Source] is reporting that the source of the Reference to the drive (Port 0) is the port in which the option module is installed (for this example, Port 4 Reference).
This ensures that any Reference commanded from the network can be monitored by using drive Parameter 002 - [Commanded SpdRef]. If a problem occurs, this verification step provides the diagnostic capability to determine whether the drive/option module or the network is the cause.
4. If hard-wired discrete digital inputs are not used to control the drive, verify that all unused digital input drive parameters are set to ‘0’ (Not Used).
22 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Installing the Option Module Chapter 2
IMPORTANT

Commissioning the Option Module

To commission the option module, you must set a unique network node address. See the Glossary switches, see Setting the Node Address Switches
for details about node addresses. When using the Node Address
on page 18 for details.
New settings are recognized only when power is applied to the option module or it is reset. After you change parameter settings, cycle power or reset the option module.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 23
Chapter 2 Installing the Option Module
Notes:
24 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
IMPORTANT

Chapter 3

Configuring the Option Module

This chapter provides instructions and information for setting the parameters to configure the option module.
Top ic Pa ge

Configuration Tools

Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM to Access Parameters
Setting the Node Address
Setting a Master-Slave Hierarchy (Optional)
Setting a Fault Action 29
Resetting the Option Module 31
Restoring Option Module Parameters to Factory Defaults
Viewing the Option Module Status Using Parameters 33
Updating the Option Module Firmware 33
25
26
26
26
32
Configuration Tools
For a list of parameters, see Appendix definitions of terms in this chapter, see the Glossary
The option module stores parameters and other information in its own nonvolatile storage (NVS) memory. You must, therefore, access the option module to view and edit its parameters. The following tools can be used to access the option module parameters.
Too l Se e
PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM page 26
Connected Components Workbench software, version 1.02 or later
DriveExplorer software, version 6.01 or later
DriveExecutive software, version 5.01 or later
For the HIM screens shown throughout this chapter, the option module was installed in drive Port 4. If your option module is installed in a different drive port, that port would appear instead of Port 4.
B, Option Module Parameters. For
.
http://www.ab.com/support/abdrives/webupdate/ software.html, or online help (installed with the software)
http://www.ab.com/drives/driveexplorer, or online help
(installed with the software)
http://www.ab.com/drives/drivetools
(installed with the software)
, or online help
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 25
Chapter 3 Configuring the Option Module
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Net Addr Cfg
2
1<<99
Using the PowerFlex 20-HIM­A6 or 20-HIM-C6S HIM to Access Parameters

Setting the Node Address

If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it can be used to access parameters in the option module.
1. Display the Status screen, which is shown on HIM power up.
2. Use the or key to scroll to the Port in which the option
module is installed.
3. Press the PAR# soft key to display the Jump to Param # entry pop-up box.
4. Use the numeric keys to enter the desired parameter number, or use the
or soft key to scroll to the desired parameter number.
For details on viewing and editing parameters, see the PowerFlex 20-HIM-A6/­C6S HIM (Human Interface Module) User Manual, publication 20HIM-
UM001.
When the option module Node Address switches (Figure 1) are set to ‘00’ (Program) the value of Device Parameter 05 - [Net Addr Cfg] determines the node address. When the Node Address switches are in any other combination of positions, these switches determine the node address.

Setting a Master-Slave Hierarchy (Optional)

1. Set the value of Device Parameter 05 - [Net Addr Cfg] to a unique node address.
2. Reset the option module; see Resetting the Option Module
This procedure is only required if Datalinks are used to write or read data of the drive or its connected peripherals. A hierarchy determines the type of device with which the option module exchanges data. In a Master-Slave hierarchy, the option module exchanges data with a master, such as a bridge or scanner (1756-CNB, 1756-CNBR, 1747-SCNR, and so forth).
Enable Datalinks To Write Data
on page 31.
The controller output image (controller outputs-to-drive) can have 0 to 16 additional 32-bit parameters (Datalinks). The Datalinks are configured using
Host Parameters 01 - [DL From Net 01] through Parameter 16 - [DL From Net 16]. The number of Datalinks actively used is controlled by the connection
size in the controller. See the respective controller example sections in Chapter 4 for more information on setting the connection size.
26 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
IMPORTANT
TIP
Configuring the Option Module Chapter 3
Always use the Datalink parameters in consecutive numerical order, starting with the first parameter. For example, use Host Parameters 01, 02, and 03 to configure three Datalinks to write data. Otherwise, the network I/O connection will be larger than necessary, which needlessly increases controller response time and memory usage.
When using a ControlLogix controller and an RSLogix 5000 drive Add-On Profile (version 16 or later), there is no need to configure Datalink parameters at this time. They will be assigned when configuring the RSLogix 5000 drive Add-On Profile (see Add the Drive/Option Module to the I/O Configuration
page 39).
When using a ControlLogix controller and the Generic Profile—or a PLC-5 or SLC 500 controller, configure the Datalink parameters now as described in this section.
Host Parameters 01 - [DL From Net 01] through 16 - [DL From Net 16] configure which parameters in the drive, option module, or any other connected peripheral receive the values from the network. You can use the PowerFlex 20­HIM-A6 or 20-HIM-C6S HIM, or another drive configuration tool such as Connected Components Workbench, DriveExplorer, or DriveExecutive software to select the drive or peripheral by port number and the parameter by name. As an alternate method, the parameter value can be set manually by number using this formula:
on
From Net Parameter Value = (10000 * port number) + (Destination Parameter Number)
For example, suppose you want to use Host Parameter 01 - [DL From Net 01] to write to Parameter 03 of an optional encoder module plugged into drive Port 5. Using the formula, the value for Host Parameter 01 - [DL From Net 01] would be (10000 * 5) + (3) = 50003.
Follow these steps to enable Datalinks to write data.
1. Set the values of only the required number of contiguous controller-to­drive Datalinks needed to write data to the drive and that are to be included in the network I/O connection.
2. Reset the option module; see Resetting the Option Module
3. Since the Logic Command and Reference is always used in the option
module, configure the parameters in the drive to accept the Logic Command and Reference from the option module.
When using the controller for speed reference via the option module, set two fields in drive Parameter 545 - [Speed Ref A Sel].
a. Set the Port field for the drive (for example, 0 - PowerFlex 755). b. Set the Parameter field to point to the port in which the option module
is installed (for this example, Port 4 Reference). Also, verify that the mask parameters in the drive (for example,
Parameter 324 - [Logic Mask]) are configured to receive the desired logic from the option module. See the drive documentation for details.
on page 31.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 27
Chapter 3 Configuring the Option Module
IMPORTANT
TIP
After the above steps are complete, the option module is ready to receive input data and transfer status data to the master (controller). Next, configure the controller to recognize and transmit I/O to the option module. See Chapter 4 Configuring the I/O.
Enable Datalinks To Read Data
The controller input image (drive-to-controller inputs) can have 0 to 16 additional 32-bit parameters (Datalinks). The Datalinks are configured using Host Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16]. The number of Datalinks actively used is controlled by the connection size in the controller. See the respective controller example sections in Chapter 4 information on setting the connection size.
Always use the Datalink parameters in consecutive numerical order, starting with the first parameter. For example, use Host Parameters 17, 18, 19, 20, and 21 to configure five Datalinks to read data. Otherwise, the network I/O connection will be larger than necessary, which needlessly increases controller response time and memory usage.
for more
,
When using a ControlLogix controller and an RSLogix 5000 drive Add-On Profile, version 16.00 or later, there is no need to configure Datalink parameters at this time. They will be assigned when configuring the RSLogix 5000 drive Add-On Profile (see Add the Drive/Option Module to the I/O
Configuration on page 39).
When using a ControlLogix controller and the Generic Profile—or a PLC-5 or SLC 500 controller, configure the Datalink parameters now as described in this section.
Host Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16] configure which parameters in the drive, option module, or any other connected peripheral send the values to the network. You can use the PowerFlex 20-HIM-A6 or 20­HIM-C6S HIM, or another drive configuration tool such as Connected Components Workbench, DriveExplorer, or DriveExecutive software to select the drive or peripheral by port number and the parameter by name. As an alternate method, the parameter value can be set manually by number using this formula:
To Net Parameter Value = (10000 * Port Number) + (Origination Parameter Number)
For example, suppose you want to use Host Parameter 17 - [DL To Net 01] to read Parameter 2 of an optional I/O module plugged into drive Port 6. Using the formula, the value for Host Parameter 17 - [DL To Net 01] would be (10000 * 6) + (2) = 60002.
Follow these steps to enable Datalinks to read data.
28 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the Option Module Chapter 3
1. Set the values of only the required number of contiguous drive-to­controller Datalinks needed to read data from the drive and that are to be included in the network I/O connection.

Setting a Fault Action

2. Reset the option module; see Resetting the Option Module
The option module is configured to send output data to the master (controller). You must now configure the controller to recognize and transmit I/O to the option module. See Chapter 4
By default, when communication is disrupted (for example, the network cable is disconnected), the controller is idle (in program mode or faulted) or explicit messaging for drive control is disrupted, the drive responds by faulting if it is using I/O from the network. You can configure a different response to these faults:
Disrupted I/O communication by using Host Parameter 33 - [Comm Flt Action].
An idle controller by using Host Parameter 34 - [Idle Flt Action].
Disrupted explicit messaging for drive control via PCCC, the CIP Register Object, or the CIP Assembly object by using Host Parameter 36 - [Msg Flt Action].
ATTENTION: Risk of injury or equipment damage exists. Host Parameters 33 ­[Comm Flt Action], 34 - [Idle Flt Action], and 36 - [Msg Flt Action] let you
determine the action of the option module and connected drive if communication is disrupted, the controller is idle, or explicit messaging for drive control is disrupted. By default, these parameters fault the drive. You may configure these parameters so that the drive continues to run, however, precautions should be taken to verify that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected network cable, controller in idle state or explicit message control disruption).
, Configuring the I/O.
on page 31.
Changing the Fault Action
Set the values of Host Parameters 33 - [Comm Flt Action], 34 - [Idle Flt Action], and 36 - [Msg Flt Action] to an action that meets your application
requirements.
Value Action Description
0 Fault The drive is faulted and stopped. (Default)
1 Stop The drive is stopped, but not faulted.
2 Zero Data The drive is sent ‘0’ values for data. This does not command a stop.
3 Hold Last The drive continues in its present state.
4 Send Flt Cfg The drive is sent the data that you set in the fault configuration parameters (Host
Parameters 37 - [Flt Cfg Logic], 38 - [Flt Cfg Ref], and 39 - [Flt Cfg DL 01] through 54 - [Flt Cfg DL 16]).
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 29
Chapter 3 Configuring the Option Module
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Comm Flt Action
Fault 0
0<<4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Idle Flt Action
Fault 0
0<<4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Msg Flt Action
Fault 0
0<<4
Figure 4 - Edit Fault Action HIM Screens
Changes to these parameters take effect immediately. A reset is not required.
If communication is disrupted and then is re-established, the drive will automatically receive commands over the network again.
Setting the Fault Configuration Parameters
When setting Host Parameter 33 - [Comm Flt Action], 34 - [Idle Flt Action] or 36 - [Msg Flt Action] to ‘Send Flt Cfg’, the values in the following parameters are sent to the drive after a communication fault, idle fault, and/or explicit messaging for drive control fault occurs. You must set these parameters to values required by your application.
Option Module Host Parameter Description
Parameter 37 - [Flt Cfg Logic] A 32-bit value sent to the drive for Logic Command.
Parameter 38 - [Flt Cfg Ref] A 32-bit REAL (floating point) value sent to the drive for Reference.
Parameter 39 - [Flt Cfg DL 01]
through
Parameter 54 - [Flt Cfg DL 16]
A 32-bit integer value sent to the drive for a Datalink. If the destination of the Datalink is a REAL (floating point) parameter, you must convert the desired value to the binary representation of the REAL value. (An internet search of ‘hex to float’ provides a link to a tool to do this conversion.)
30 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Changes to these parameters take effect immediately. A reset is not required.
Loading...
+ 120 hidden pages