Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, TechConnect, PowerFlex, Connected Components Workbench, DriveExplorer, DriveTools, DriveExecutive, RSLinx, RSLogix, Studio 5000, and ControlLogix are
trademarks of Roc kwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual contains new and updated information.
Summary of Changes
New and Updated
Information
This table contains the changes made to this revision.
Top icPag e
Added information about the Connected Components Workbench software configuration tool for drives
and connected peripherals.
In the Chapter 3 subsection ‘Enable Datalinks To Write Data’, revised step 3 for better understanding.27
In the Chapter 4 sub-subsection ‘Add the Drive/Option Module to the I/O Configuration’, included new
information for the Create Database, Web Update, and Match Drive buttons on the Module Definition
dialog box, which are described in the step 6 table.
In Chapter 6 Explicit Messaging, added Table 4. Also added footnotes about limitations when using DPI
Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F to tables below message
configuration dialog boxes.
Throughout
manual
41
74…84
Rockwell Automation Publication 750COM-UM003B-EN-P - November 20123
Summary of Changes
Notes:
4Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Rockwell Automation Publication 750COM-UM003B-EN-P - November 20127
Table of Contents
Notes:
8Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Preface
This manual provides information about the 20-750-CNETC ControlNet
option module for network communication and how to use the module with
PowerFlex® 750-Series drives.
Conventions Used in This
Manual
Rockwell Automation
Support
The following conventions are used throughout this manual:
• Parameter names are shown in the format Device Parameter xx - [*] or
Host Parameter xx - [*]. The xx represents the parameter number. The *
represents the parameter name—for example Device Parameter 01 - [DPI
Por t].
• The firmware revision number (FRN) is displayed as FRN X.xxx, where
‘X’ is the major revision number and ‘xxx’ is the minor revision number.
• The dialog box images in this manual resulted from using the following
software:
– RSLinx® Classic software, version 2.52
– RSNetWorx for ControlNet software, version 8.00
– RSLogix™ 5000 software, version 16.00
Different versions of the software may have dialog boxes that vary in
appearance, and differences in procedures.
Rockwell Automation offers support services worldwide, with over 75 sales and
support offices, over 500 authorized distributors, and over 250 authorized
systems integrators located through the United States alone. In addition,
Rockwell Automation representatives are in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for the following:
• Sales and order support
• Product technical training
• Wa r r a nt y s up po rt
• Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 7,
Troubleshooting, first. If you still have problems, then access the Allen-Bradley
Technical Support website at http://www.ab.com/support/abdrives
Rockwell Automation.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 20129
or contact
Preface
Additional Resources
ResourceDescription
Network Communication Option Module Installation Instructions, publication 750COM-IN002Information on the installation of PowerFlex 750-Series Network
ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002Information on the required components of a ControlNet coax media system,
Connected Components Wo rkbench we bsite http://www.ab.com/support/abdrives/webupdate/
PowerFlex 20-HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication 20HIM-UM001
Getting Results with RSLinx Guide, publication LINX-GR001, and online help
RSLogix 5000 PIDE Autotuner Getting Results Guide, publication PIDE-GR001, and online help
ControlNet Network Configuration User Manual, publication CNET-UM001
(1)
(1) The online help is installed with the software.
These documents contain additional information concerning related products
from Rockwell Automation.
Commun ication mo dules.
which is useful in determining your system and for installing the required
components.
Information on the Connected Components Workbench™ software tool—and
includes a link for free software download.
, and online help
(1)
(1)
(1)
Information on installing, programming, and technical data of PowerFlex®
(1)
Information on how to use ControlNet communication modules with a
Information on using the DriveExplorer™ software tool.
Information on using the DriveExecutive™ software tool.
Information on using RSNetWorx™ for ControlNet.
750-Series drives.
Information on the installation and use of PowerFlex 20-HIM-A6 or 20-HIM-
C6S HIMs.
Information on using RSLinx Classic software.
(1)
Information on using the RSLogix 5000 software tool.
ControlLogix controller.
You can view or download publications at http://
www.rockwellautomation.com/literature. To order paper copies of technical
documentation, contact your local Allen-Bradley® distributor or Rockwell
Automation sales representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related questions,
go to the Drives Service & Support website at http://www.ab.com/support/
abdrives and click on the Downloads or Knowledgebase link.
.
10Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 1
ItemPartDescription
➊
Status IndicatorsFour status indicators that indicate the
status of the option module and
network communication. See
Chapter 7, Troubleshooting.
➋
Node Address
Switche s
Sets the node address of the option
module. See Setting the Node Address
Switches on page 18.
➌
Channel A
Coax R eceptacle
BNC connector for the Channel A
network coaxial cable.
➍
Channel B
Coax R eceptacle
BNC connector for the Channel B
(redundant) network coaxial cable.
Getting Started
The 20-750-CNETC option module is intended for installation into a
PowerFlex 750-Series drive and is used for network communication.
Top icPa ge
Components
Featu res
Compatible Produ cts
Required Equipment
Safety Precautions15
Quick Start16
11
12
13
13
Components
➊
➋
➌
➍
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201211
Chapter 1Getting Started
Features
The features of the option module include the following:
• Captive screws to secure and ground the module to the drive.
• Switches to set a node address before applying power to the drive—or you
can disable the switches and use an option module parameter to configure
the node address.
• Compatibility with the following configuration tools to configure the
option module and host drive:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM (Human Interface
Module) on the drive, if available
– Connected Components Workbench software, version 1.02 or later
– DriveExplorer software, version 6.01 or later
– DriveExecutive software, version 5.01 or later
• Status indicators that report the status of the option module and network
communication. They are visible when the drive cover is removed.
• Parameter-configured 32-bit Datalinks in the I/O to meet application
requirements (16 Datalinks to write data from the network to the drive,
and 16 Datalinks to read data to the network from the drive).
• Explicit Messaging support.
• Master-Slave hierarchy that can be set up so that the option module and
PowerFlex 750-Series drive transmit data to and from a scanner on the
network.
• User-defined fault actions to determine how the option module and its
connected host drive respond to the following:
– I/O messaging communication disruptions (Comm Flt Action)
– Controllers in Idle mode (Idle Flt Action)
– Explicit messaging disruptions for drive control via PCCC, the CIP
Register Object, or the CIP Assembly object (Msg Flt Action)
• Access to any PowerFlex drive and its connected peripherals on the
network to which the option module is connected.
12Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Getting StartedChapter 1
Understanding Parameter
Types
The option module has two types of parameters:
• Device parameters are used to configure the option module to operate on
the network.
• Host parameters are used to configure the option module Datalink transfer
and various fault actions with the drive.
Yo u can vi ew op ti on m od u le Device parameters and Host parameters with any of
the following drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM—use the or
key to scroll to the drive port in which the module resides, press the
(Folders) key, and use the or key to scroll to the DEV
PARA M or H OST PAR AM fo lder.
• Connected Components Workbench software—click the tab for the
option module at the bottom of the window, click the Parameters icon in
the tool bar, and click the Device or Host Parameters tab.
• DriveExplorer software—find the option module in the treeview and open
its Parameters folder.
Compatible Products
Required Equipment
• DriveExecutive software—find the option module in the treeview, expand
the module in the tree, and open its Parameters folder.
At the time of publication, the option module is compatible with the following
products:
• PowerFlex 753 drives (all firmware revisions)
• PowerFlex 755 drives (all firmware revisions)
Some of the equipment that is required for use with the option module is shipped
with the module, but some you must supply yourself.
Equipment Shipped with the Option Module
When you unpack the option module, verify that the package includes the
following:
❑ One 20-750-CNETC Coaxial ControlNet Option Module
❑ One Network Communication Option Module Installation Instructions,
publication 750COM-IN002
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201213
Chapter 1Getting Started
User-Supplied Equipment
To install and configure the option module, you must supply the following:
❑ A small screwdriver
❑ ControlNet cable—for details, see the ControlNet Coax Media Planning
and Installation Guide, publication CNET-IN002
❑ Drive and option module configuration tool, such as the following:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
– Connected Components Workbench software, version 1.02 or later
Connected Components Workbench is the recommended stand-alone
software tool for use with PowerFlex drives. You can obtain a free copy
by:
• Internet download at http://www.ab.com/support/abdrives/
webupdate/software.html
• Requesting a DVD at http://www.ab.com/onecontact/
controllers/micro800/
Your local distributor may also have copies of the DVD available.
Connected Components Workbench software cannot be used to
configure SCANport-based drives or Bulletin 160 drives.
– DriveExplorer software, version 6.01 or later
This software tool has been discontinued and is now available as
freeware at http://www.ab.com/support/abdrives/webupdate/
software.html. There are no plans to provide future updates to this tool
and the download is being provided ‘as-is’ for users that lost their
DriveExplorer CD, or need to configure legacy products not supported
by Connected Components Workbench software.
– DriveExecutive software, version 5.01 or later
A Lite version of DriveExecutive software ships with RSLogix 5000,
RSNetworx MD, FactoryTalk AssetCentre, and IntelliCENTER
software. All other versions are purchasable items:
• 9303-4DTE01ENE Drive Executive software
• 9303-4DTS01ENE DriveTools SP Suite (includes
DriveExecutive and DriveObserver software)
• 9303-4DTE2S01ENE DriveExecutive software upgrade to
DriveTools SP Suite (adds DriveObserver software)
DriveExecutive software updates (patches, and so forth) can be obtained
at http://www.ab.com/support/abdrives/webupdate/software.html
is highly recommended that you periodically check for and install the
latest update.
❑ RSNetWorx for ControlNet network configuration software, version 8.00
or later
14Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
. It
Getting StartedChapter 1
❑ Controller configuration software, such as RSLogix 5000 software, version 20.00
or earlier, or Studio 5000™ Logix Designer application, version 21.00 or later
❑ A computer communication card, such as 1784-PCC, 1784-KTCX, or
1770-KFC, for connection to the ControlNet network
Safety Precautions
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high
voltages that can cause injury or death. Remove all power from the PowerFlex
drive, and then verify power has been discharged before installing or removing
the option module.
ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar
with drive and power products and the associated machinery should plan or
implement the installation, startup, configuration, and subsequent maintenance
of the drive using the option module. Failure to comply may result in injury and/
or equipment damage.
ATTENTION: Risk of equipment damage exists. The option module contains
electrostatic discharge (ESD) sensitive parts that can be damaged if you do not
follow ESD control procedures. Static control precautions are required when
handling the option module. If you are unfamiliar with static control procedures,
see Guarding Against Electrostatic Damage, publication 8000-4.5.2
ATTENTION: Risk of injury or equipment damage exists. If the option module is
transmitting control I/O to the drive, the drive may fault when you reset the
option module. Determine how your drive will respond before resetting the
module.
.
ATTENTION: Risk of injury or equipment damage exists. Host Parameters 33 [Comm Flt Action], 34 - [Idle Flt Action], and 36 - [Msg Flt Action] let you
determine the action of the option module and connected drive if I/O
communication is disrupted, the controller is idle, or explicit messaging for drive
control is disrupted. By default, these parameters fault the drive. You may
configure these parameters so that the drive continues to run, however,
precautions should be taken to verify that the settings of these parameters do
not create a risk of injury or equipment damage. When commissioning the drive,
verify that your system responds correctly to various situations (for example, a
disconnected cable or a controller in idle state).
ATTENTION: Risk of injury or equipment damage exists. When a system is
configured for the first time, there may be unintended or incorrect machine
motion. Disconnect the motor from the machine or process during initial system
testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in this
publication are intended solely for purposes of example. There are many
variables and requirements with any application. Rockwell Automation does not
assume responsibility or liability (to include intellectual property liability) for
actual use of the examples shown in this publication.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201215
Chapter 1Getting Started
Quick Start
This section is provided to help experienced users quickly start using the option
module. If you are unsure how to complete a step, refer to the referenced chapter.
StepActionSee
1Review the safety precautions for the option module.Throughout this manual
2Verify that the PowerFlex drive is properly installed.PowerFlex 750-Series AC Drive
3Install the option module.
a. Verify that the PowerFlex drive is not powered.
b. Insert the option module in drive Port 4, 5, or 6.
c. Use the captive crews to secure and ground the option module to
the drive.
d. Connect the option module to the network with a ControlNet
cable.
4Apply power to the option module.
a. Verify that the option module is installed correctly.
The option module receives power from the drive.
b. Apply power to the drive.
The status indicators should be green. If they flash red, there is a
problem. See Chapter 7
c. Configure and verify key drive parameters.
5Configure the option module for your application.
Set option module parameters for the following functions as required by
your application:
• Node address
• I/O configuration
• Master-Slave hierarchy
• Fault actions
6Configure the controller to communicate with the option module.
Use the network configuration tool RSNetWorx for ControlNet software,
and a controller configuration tool, such as RSLogix software, to configure
the master on the network to recognize the option module and drive.
7Create a ladder logic program.
Use a controller configuration tool, such as RSLogix software, to create a
ladder logic program that enables you to do the following:
• Control the connected drive, via the option module, by using I/O.
• Monitor or configure the drive by using explicit messages.
, Troubleshooting.
Installation Instructions,
publication 750-IN001
Network Communication Option
Module Installation Instructions,
publication 750COM-IN002
Chapter 2,
Installing the Option Module
Chapter 2,
Installing the Option Module
Chapter 3,
Configuring the Option Module
,
Chapter 4
Configuring the I/O
,
Chapter 5
Using the I/O
,
Chapter 6
Using Explicit Messaging
and
16Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 2
Installing the Option Module
This chapter provides instructions for installing the option module in a
PowerFlex 750-Series drive.
Top icPa ge
Preparing for an Installation
Setting the Node Address Switches
Connecting the Option Module to the Drive
Connecting the Option Module to the Network
Applying Power20
Commissioning the Option Module23
17
18
19
19
Preparing for an Installation
Before installing the option module, do the following:
• Read the ControlNet Coax Media Planning and Installation Guide,
publication CNET-IN002
selecting cables, setting up a network, and network basics.
• Verify that you have all required equipment. See Required Equipment
page 13.
ATTENTION: Risk of equipment damage exists. The option module contains
electrostatic discharge (ESD) sensitive parts that can be damaged if you do not
follow ESD control procedures. Static control precautions are required when
handling the option module. If you are unfamiliar with static control procedures,
see Guarding Against Electrostatic Damage, publication 8000-4.5.2
. This publication provides information on
.
on
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201217
Chapter 2Installing the Option Module
IMPORTANT
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
ONES
Posi tion
TENS
Posi tion
Setting the Node Address
Switches
Set the option module Node Address switches (Figure 1) by rotating the switches
to the desired value for each digit.
Each node on the ControlNet network must have a unique address. Set the
node address before power is applied because the option module uses the
node address it detects when it first receives power. To change a node address,
you must set the new value and then remove and reapply power to (or reset)
the option module.
Figure 1 - Setting Node Address Switches
SettingsDescription
00If the Node Address switches are set to ‘00’, the option module uses the value stored in Device Parameter
01…99Node address used by the option module. The default switch setting is 02.
05 - [Net Addr Cfg] for the node address. See Setting the Node Address
The switch settings can be verified by viewing Device Parameter 06 - [Net Addr
Act] or Diagnostic Device Item number 58 (page 93
drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 6.01 or later
• DriveExecutive software, version 5.01 or later
on page 26.
) with any of the following
18Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Installing the Option ModuleChapter 2
IMPORTANT
IMPORTANT
Control Logix Controller
(with 1756-CNBR Bridge)
PowerFlex 755 Drives
(with 20-750-CNETC Option Modules)
(optional redundancy)
Channel A
Channel B
Control Net
Network
Connecting the Option
Module to the Drive
Connecting the Option
Module to the Network
Remove power from the drive before installing the option module in the drive
control pod.
Install the option module in the PowerFlex 750-Series Drive control pod in Port
4, 5, or 6. For more installation details, see the Network Communication Option
Module Installation Instructions, publication 750COM-IN002
the option module.
After inserting the option module into Port 4, 5, or 6, make sure to tighten the
module screws to the drive control pod to properly ground the module to the
drive. Torque both screws to 0.45…0.67 N•m (4.0…6.0 lb•in).
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high
voltages that can cause injury or death. Remove power from the drive, and then
verify power has been discharged before connecting the option module to the
network.
1. Remove power from the drive.
, provided with
2. Remove the drive cover and lift up the drive HIM bezel to its open
3. Use static control precautions.
4. Connect one end of the ControlNet cable to the network.
5. Route the other end of the ControlNet cable through the bottom of the
position to access the drive control pod.
Figure 2 - Coax Network Wiring Example
drive, and insert its ControlNet cable plug into the mating option module
receptacle. We recommend using a 1786-TPS straight tap.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201219
Chapter 2Installing the Option Module
➊
See Tab le 1 for
possible start-up
status indications.
Drive Control Pod
(drive shown with cover removed)
Applying Power
ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable
operation may occur if you fail to verify that parameter settings are compatible
with your application. Verify that settings are compatible with your application
before applying power to the drive.
Apply power to the drive. The option module receives its power from the drive.
When you apply power to the option module for the first time, its topmost
‘PORT’ status indicator should be steady green or flashing green after an
initialization. If it is red, there is a problem. See Chapter 7
, Troubleshooting.
Start-Up Status Indications
After power has been applied, the drive STS (status) indicator can be viewed on
the front of the drive and the option module status indicators can be viewed with
the drive cover open or removed (Figure 3
are shown in Ta b l e 1
Figure 3 - Drive and Option Module Status Indicators
.
). Possible start-up status indications
➋
➌
➍
➎
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
20Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Table 1 - Drive and Option Module Start-Up Status Indications
ItemNameColorStateDescription
Drive STS Indicator
STS
➊
(Status)
PORTGreenFlashingNormal operation. The option module is establishing an I/O
➋
MODGreenFlashingNormal operation. The option module is operating but is not
➌
NET A
➍
NET B
➎
GreenFlashingDrive ready but not running, and no faults are present.
SteadyDrive running, no faults are present.
YellowFlashingWhen running, a type 2 (non-configurable) alarm condition exists
SteadyA type 1 (user configurable) alarm condition exists, but the drive
RedFlashingA major fault has occurred. Drive will stop. Drive cannot be started
SteadyA non-resettable fault has occurred.
Red/YellowFlashing AlternatelyA minor fault has occurred. Use drive parameter 950 - [Minor Flt
Yellow/GreenFlashing AlternatelyWhen running, a type 1 alarm exists.
Green/RedFlashing AlternatelyDrive is firmware updating.
Option Module Status Indicators
SteadyNormal operation. The option module is properly connected and
SteadyNormal operation. The option module is operating and transferring
GreenFlashingA temporary channel error has occurred or the channel is in ‘listen-
SteadyNormal operation for that channel. The option module is properly
RedFlashingThe channel is not receiving network activity.
Green/RedFlashing AlternatelyThere is an invalid link configuration for that channel.
Installing the Option ModuleChapter 2
– drive continues to run. When stopped, a start inhibit condition
exists and the drive cannot be started (see drive parameter 933 [Start Inhibits]).
continues to run.
until fault condition is cleared.
Config] to enable. If not enabled, acts like a major fault. When
running, the drive continues to run. System is brought to a stop
under system control. The fault must be cleared to continue.
connection to the drive. It will turn steady green or red.
communicating with the drive.
transferring I/O data to a controller.
I/O data to a controller.
only’ mode.
connected and communicating on the network.
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see page 90
and page 91.
Configuring and Verifying Key Drive Parameters
The PowerFlex 750-Series drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could set the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201221
Chapter 2Installing the Option Module
The following steps in this section assume that the drive will receive the Logic
Command and Reference from the network.
1. Verify that drive Parameter 301 - [Access Level] is set to ‘1’ (Advanced) or
‘2’ (Expert) to access the required parameters in this procedure.
2. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed
Reference.
a. Set the Port field to ‘0’ as shown below.
b. Set the Parameter field to point to the port (slot) in which the option
module is installed (for this example, Port 4 Reference).
The number ‘874’ in the Parameter field of the example dialog box
above is the parameter in the drive that points to the port.
3. Verify that drive Parameter 930 - [Speed Ref Source] is reporting that the
source of the Reference to the drive (Port 0) is the port in which the option
module is installed (for this example, Port 4 Reference).
This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded SpdRef]. If a
problem occurs, this verification step provides the diagnostic capability to
determine whether the drive/option module or the network is the cause.
4. If hard-wired discrete digital inputs are not used to control the drive, verify
that all unused digital input drive parameters are set to ‘0’ (Not Used).
22Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Installing the Option ModuleChapter 2
IMPORTANT
Commissioning the Option
Module
To commission the option module, you must set a unique network node address.
See the Glossary
switches, see Setting the Node Address Switches
for details about node addresses. When using the Node Address
on page 18 for details.
New settings are recognized only when power is applied to the option module
or it is reset. After you change parameter settings, cycle power or reset the
option module.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201223
Chapter 2Installing the Option Module
Notes:
24Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
IMPORTANT
Chapter 3
Configuring the Option Module
This chapter provides instructions and information for setting the parameters to
configure the option module.
Top icPa ge
Configuration Tools
Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM to Access Parameters
Setting the Node Address
Setting a Master-Slave Hierarchy (Optional)
Setting a Fault Action29
Resetting the Option Module31
Restoring Option Module Parameters to Factory Defaults
Viewing the Option Module Status Using Parameters33
Updating the Option Module Firmware33
25
26
26
26
32
Configuration Tools
For a list of parameters, see Appendix
definitions of terms in this chapter, see the Glossary
The option module stores parameters and other information in its own
nonvolatile storage (NVS) memory. You must, therefore, access the option
module to view and edit its parameters. The following tools can be used to access
the option module parameters.
Too lSe e
PowerFlex 20-HIM-A6 or 20-HIM-C6S HIMpage 26
Connected Components Workbench software,
version 1.02 or later
DriveExplorer software,
version 6.01 or later
DriveExecutive software,
version 5.01 or later
For the HIM screens shown throughout this chapter, the option module was
installed in drive Port 4. If your option module is installed in a different drive
port, that port would appear instead of Port 4.
B, Option Module Parameters. For
.
http://www.ab.com/support/abdrives/webupdate/
software.html, or online help (installed with the software)
http://www.ab.com/drives/driveexplorer, or online help
(installed with the software)
http://www.ab.com/drives/drivetools
(installed with the software)
, or online help
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201225
Chapter 3Configuring the Option Module
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Net Addr Cfg
2
1<<99
Using the PowerFlex 20-HIMA6 or 20-HIM-C6S HIM to
Access Parameters
Setting the Node Address
If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it
can be used to access parameters in the option module.
1. Display the Status screen, which is shown on HIM power up.
2. Use the or key to scroll to the Port in which the option
module is installed.
3. Press the PAR# soft key to display the Jump to Param # entry pop-up box.
4. Use the numeric keys to enter the desired parameter number, or use the
or soft key to scroll to the desired parameter number.
For details on viewing and editing parameters, see the PowerFlex 20-HIM-A6/C6S HIM (Human Interface Module) User Manual, publication 20HIM-
UM001.
When the option module Node Address switches (Figure 1) are set to ‘00’
(Program) the value of DeviceParameter 05 - [Net Addr Cfg] determines the
node address. When the Node Address switches are in any other combination of
positions, these switches determine the node address.
Setting a Master-Slave
Hierarchy (Optional)
1. Set the value of Device Parameter 05 - [Net Addr Cfg] to a unique node
address.
2. Reset the option module; see Resetting the Option Module
This procedure is only required if Datalinks are used to write or read data of the
drive or its connected peripherals. A hierarchy determines the type of device with
which the option module exchanges data. In a Master-Slave hierarchy, the option
module exchanges data with a master, such as a bridge or scanner (1756-CNB,
1756-CNBR, 1747-SCNR, and so forth).
Enable Datalinks To Write Data
on page 31.
The controller output image (controller outputs-to-drive) can have 0 to 16
additional 32-bit parameters (Datalinks). The Datalinks are configured using
Host Parameters 01 - [DL From Net 01] through Parameter 16 - [DL From
Net 16]. The number of Datalinks actively used is controlled by the connection
size in the controller. See the respective controller example sections in Chapter 4
for more information on setting the connection size.
26Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
IMPORTANT
TIP
Configuring the Option ModuleChapter 3
Always use the Datalink parameters in consecutive numerical order, starting
with the first parameter. For example, use Host Parameters 01, 02, and 03 to
configure three Datalinks to write data. Otherwise, the network I/O connection
will be larger than necessary, which needlessly increases controller response
time and memory usage.
When using a ControlLogix controller and an RSLogix 5000 drive Add-On
Profile (version 16 or later), there is no need to configure Datalink parameters
at this time. They will be assigned when configuring the RSLogix 5000 drive
Add-On Profile (see Add the Drive/Option Module to the I/O Configuration
page 39).
When using a ControlLogix controller and the Generic Profile—or a PLC-5 or
SLC 500 controller, configure the Datalink parameters now as described in this
section.
Host Parameters 01 - [DL From Net 01] through 16 - [DL From Net 16]
configure which parameters in the drive, option module, or any other connected
peripheral receive the values from the network. You can use the PowerFlex 20HIM-A6 or 20-HIM-C6S HIM, or another drive configuration tool such as
Connected Components Workbench, DriveExplorer, or DriveExecutive software
to select the drive or peripheral by port number and the parameter by name. As
an alternate method, the parameter value can be set manually by number using
this formula:
on
From Net Parameter Value = (10000 * port number) + (Destination Parameter Number)
For example, suppose you want to use Host Parameter 01 - [DL From Net 01] to
write to Parameter 03 of an optional encoder module plugged into drive Port 5.
Using the formula, the value for Host Parameter 01 - [DL From Net 01] would
be (10000 * 5) + (3) = 50003.
Follow these steps to enable Datalinks to write data.
1. Set the values of only the required number of contiguous controller-todrive Datalinks needed to write data to the drive and that are to be
included in the network I/O connection.
2. Reset the option module; see Resetting the Option Module
3. Since the Logic Command and Reference is always used in the option
module, configure the parameters in the drive to accept the Logic
Command and Reference from the option module.
When using the controller for speed reference via the option module, set
two fields in drive Parameter 545 - [Speed Ref A Sel].
a. Set the Port field for the drive (for example, 0 - PowerFlex 755).
b. Set the Parameter field to point to the port in which the option module
is installed (for this example, Port 4 Reference).
Also, verify that the mask parameters in the drive (for example,
Parameter 324 - [Logic Mask]) are configured to receive the desired
logic from the option module. See the drive documentation for details.
on page 31.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201227
Chapter 3Configuring the Option Module
IMPORTANT
TIP
After the above steps are complete, the option module is ready to receive input
data and transfer status data to the master (controller). Next, configure the
controller to recognize and transmit I/O to the option module. See Chapter 4
Configuring the I/O.
Enable Datalinks To Read Data
The controller input image (drive-to-controller inputs) can have 0 to 16
additional 32-bit parameters (Datalinks). The Datalinks are configured using
HostParameters 17 - [DL To Net 01] through 32 - [DL To Net 16]. The
number of Datalinks actively used is controlled by the connection size in the
controller. See the respective controller example sections in Chapter 4
information on setting the connection size.
Always use the Datalink parameters in consecutive numerical order, starting
with the first parameter. For example, use Host Parameters 17, 18, 19, 20, and
21 to configure five Datalinks to read data. Otherwise, the network I/O
connection will be larger than necessary, which needlessly increases controller
response time and memory usage.
for more
,
When using a ControlLogix controller and an RSLogix 5000 drive Add-On
Profile, version 16.00 or later, there is no need to configure Datalink
parameters at this time. They will be assigned when configuring the RSLogix
5000 drive Add-On Profile (see Add the Drive/Option Module to the I/O
Configuration on page 39).
When using a ControlLogix controller and the Generic Profile—or a PLC-5 or
SLC 500 controller, configure the Datalink parameters now as described in this
section.
Host Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16] configure
which parameters in the drive, option module, or any other connected peripheral
send the values to the network. You can use the PowerFlex 20-HIM-A6 or 20HIM-C6S HIM, or another drive configuration tool such as Connected
Components Workbench, DriveExplorer, or DriveExecutive software to select
the drive or peripheral by port number and the parameter by name. As an
alternate method, the parameter value can be set manually by number using this
formula:
To Net Parameter Value = (10000 * Port Number) + (Origination Parameter Number)
For example, suppose you want to use Host Parameter 17 - [DL To Net 01] to
read Parameter 2 of an optional I/O module plugged into drive Port 6. Using the
formula, the value for Host Parameter 17 - [DL To Net 01] would be (10000 * 6)
+ (2) = 60002.
Follow these steps to enable Datalinks to read data.
28Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the Option ModuleChapter 3
1. Set the values of only the required number of contiguous drive-tocontroller Datalinks needed to read data from the drive and that are to be
included in the network I/O connection.
Setting a Fault Action
2. Reset the option module; see Resetting the Option Module
The option module is configured to send output data to the master (controller).
You must now configure the controller to recognize and transmit I/O to the
option module. See Chapter 4
By default, when communication is disrupted (for example, the network cable is
disconnected), the controller is idle (in program mode or faulted) or explicit
messaging for drive control is disrupted, the drive responds by faulting if it is
using I/O from the network. You can configure a different response to these
faults:
• Disrupted I/O communication by using Host Parameter 33 - [Comm Flt
Action].
• An idle controller by using Host Parameter 34 - [Idle Flt Action].
• Disrupted explicit messaging for drive control via PCCC, the CIP Register Object, or the CIP Assembly object by using Host Parameter 36 -
[Msg Flt Action].
ATTENTION: Risk of injury or equipment damage exists. Host Parameters 33 [Comm Flt Action], 34 - [Idle Flt Action], and 36 - [Msg Flt Action] let you
determine the action of the option module and connected drive if
communication is disrupted, the controller is idle, or explicit messaging for drive
control is disrupted. By default, these parameters fault the drive. You may
configure these parameters so that the drive continues to run, however,
precautions should be taken to verify that the settings of these parameters do
not create a risk of injury or equipment damage. When commissioning the drive,
verify that your system responds correctly to various situations (for example, a
disconnected network cable, controller in idle state or explicit message control
disruption).
, Configuring the I/O.
on page 31.
Changing the Fault Action
Set the values of Host Parameters 33 - [Comm Flt Action], 34 - [Idle Flt
Action], and 36 - [Msg Flt Action] to an action that meets your application
requirements.
ValueActionDescription
0FaultThe drive is faulted and stopped. (Default)
1StopThe drive is stopped, but not faulted.
2Zero DataThe drive is sent ‘0’ values for data. This does not command a stop.
3Hold LastThe drive continues in its present state.
4Send Flt CfgThe drive is sent the data that you set in the fault configuration parameters (Host
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201229
Chapter 3Configuring the Option Module
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Comm Flt Action
Fault0
0<<4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Idle Flt Action
Fault0
0<<4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Msg Flt Action
Fault0
0<<4
Figure 4 - Edit Fault Action HIM Screens
Changes to these parameters take effect immediately. A reset is not required.
If communication is disrupted and then is re-established, the drive will
automatically receive commands over the network again.
Setting the Fault Configuration Parameters
When setting Host Parameter 33 - [Comm Flt Action], 34 - [Idle Flt Action]
or 36 - [Msg Flt Action] to ‘Send Flt Cfg’, the values in the following parameters
are sent to the drive after a communication fault, idle fault, and/or explicit
messaging for drive control fault occurs. You must set these parameters to values
required by your application.
Option Module Host ParameterDescription
Parameter 37 - [Flt Cfg Logic]A 32-bit value sent to the drive for Logic Command.
Parameter 38 - [Flt Cfg Ref]A 32-bit REAL (floating point) value sent to the drive for Reference.
Parameter 39 - [Flt Cfg DL 01]
through
Parameter 54 - [Flt Cfg DL 16]
A 32-bit integer value sent to the drive for a Datalink. If the destination of the
Datalink is a REAL (floating point) parameter, you must convert the desired
value to the binary representation of the REAL value. (An internet search of
‘hex to float’ provides a link to a tool to do this conversion.)
30Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Changes to these parameters take effect immediately. A reset is not required.
Configuring the Option ModuleChapter 3
IMPORTANT
TIP
ValueDescript ion
0Ready (Default)
1Reset Module
2Set Defaults
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Reset Module
Ready0
0<<2
Resetting the Option Module
Changes to switch settings and some option module parameters require you to
reset the option module before the new settings take effect. You can reset the
option module by power cycling the drive or by using Device Parameter 07 - [Reset Module].
ATTENTION: Risk of injury or equipment damage exists. If the option module is
transmitting control I/O to the drive, the drive may fault when you reset the
option module. Determine how your drive will respond before resetting the
option module.
Set DeviceParameter 07 - [Reset Module] to ‘1’ (Reset Module).
When you enter ‘1’ (Reset Module), the option module will be immediately reset.
An alternate method to reset the module is by power cycling the drive. When you
enter ‘2’ (Set Defaults), the option module will set all of its Device and Host
parameters to their factory default values. (This is the same as pressing the ALL
soft key when using the MEMORY folder method described in Restoring Option
Module Parameters to Factory Defaults on page 32.)
When performing a Set Defaults, the drive may detect a conflict and then not
allow this function to occur. If this happens, first resolve the conflict and then
repeat a Set Defaults action. Common reasons for a conflict include the drive
running or a controller in Run mode.
After performing a Set Defaults, you must enter ‘1’ (Reset Module) or power
cycle the drive so that the new values take effect. Thereafter, this parameter
will be restored to a value of ‘0’ (Ready).
If your application allows, you can also reset the option module by cycling
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201231
power to the drive (resetting the drive) or by using the HIM’s Reset Device
function located in the drive’s DIAGNOSTIC folder.
Chapter 3Configuring the Option Module
IMPORTANT
Stopped
0.00 Hz
AUTO
Host Drive
240V4.2A
Rev 3.002 Ser. A
ESCREFTEXT
F
PAR#
Restoring Option Module
Parameters to Factory
Defaults
As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using Device Parameter 07 - [Reset Module] described in Resetting the Option Module
MEMORY folder method provides two ways to restore the option module
Device and Host parameters:
• ALL—restores ALL option module Device and Host parameters to their
factory default values.
• MOST—restores MOST option module Device and Host parameters—
except DeviceParameter 05 - [Net Addr Cfg] which is used for network
setup.
Follow these steps to restore option module Device and Host parameters to their
factory default values.
1. Access the Status screen, which is displayed on HIM powerup.
00
on page 31. The
2. Use the or key to scroll to the Port in which the option
module is installed.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults pop-up box.
7. Press the (Enter) key again to display the warning pop-up box to
reset Device and Host parameters to their factory default values.
8. Press the MOST soft key to restore MOST Device and Host parameters to
factory defaults or press the ALL soft key to restore ALL parameters. Or
press the ESC soft key to cancel.
When performing a Set Defaults, the drive may detect a conflict and
then not allow this function to occur. If this happens, first resolve the
conflict and then repeat this Set Defaults procedure. Common reasons
for a conflict include the drive running or a controller in Run mode.
9. Reset the option module using Device Parameter 07 - [Reset Module] or
by cycling power to the drive so that the restored parameters take effect.
32Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the Option ModuleChapter 3
Viewing the Option Module
Status Using Parameters
Updating the Option Module
Firmware
The following parameters provide information about the status of the option
module. You can view these parameters at any time.
Module Device ParameterDescription
02 - [DLs From Net Act]The number of controller-to-drive Datalinks that are included in the network I/O
03 - [DLs To Net Act]The number of drive-to-controller Datalinks that are included in the network I/O
04 - [Net Addr Src]Displays the source from which the option module node address is taken, which can
06 - [Net Addr Act]The node address used by the option module, which can be one of the following:
The option module firmware can be updated over the network or serially through
a direct connection from a computer to the drive using a 1203-USB or 1203-SSS
serial converter.
connection (controller outputs).
connection (controller inputs).
be one of the following:
• ‘0’ (Switches)
• ‘1’ (Parameters)
• The address set with the node address switches (Figure 1
• The value of Device Parameter 05 - [Net Addr Cfg].
• An old address from the switches or parameter. (If either has been changed, but
the option module has not been reset, the new address will not be in effect.)
).
When updating firmware over the network, you can use the Allen-Bradley
ControlFLASH software tool, the built-in update capability of DriveExplorer
Lite or Full software, or the built-in update capability of DriveExecutive
software.
When updating firmware through a direct serial connection from a computer to a
drive, you can use the same Allen-Bradley software tools described above, or you
can use HyperTerminal software set to the X-modem protocol.
To obtain a firmware update for this option module, go to http://www.ab.com/
support/abdrives/webupdate. This site contains all firmware update files and
associated Release Notes that describe the following items:
• Firmware update enhancements and anomalies
• How to determine the existing firmware revision
• How to update the firmware using DriveExplorer, DriveExecutive,
ControlFLASH, or HyperTerminal software
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201233
Chapter 3Configuring the Option Module
Notes:
34Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 4
Configuring the I/O
This chapter provides instructions on how to configure a Rockwell Automation
ControlLogix controller to communicate with the option module and connected
PowerFlex drive.
Top icPag e
Using RSLinx Classic Software
ControlLogix Controller Example
35
36
Using RSLinx Classic Software
RSLinx Classic software, in all its variations (Lite, Gateway, OEM, and so forth),
is used to provide a communication link between the computer, network, and
controller. RSLinx Classic software requires its network-specific driver to be
configured before communication is established with network devices. To
configure the RSLinx driver, follow this procedure.
1. Start RSLinx Classic software.
2. From the Communications menu, choose Configure Drivers to display the
Configure Drivers dialog box.
3. From the Available Driver Types pull-down menu, choose ControlNet
Drivers.
4. Click Add New to display the ControlNet Driver Selection dialog box.
5. In the Available ControlNet Drivers list, choose the computer connection
adapter (1784-PCC, 1770-KFC, or 1784-KTCX) being used to connect
your computer to the network, and click Select to display the Driver
Configuration dialog box.
6. Configure the driver for your computer and network settings and click
OK.
The Configure Drivers dialog box reports the progress of the
configuration.
7. When the Add New RSLinx Driver dialog box appears, type a name (if
desired) and click OK.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201235
Chapter 4Configuring the I/O
Node 0
ControlLogix Controll er
with 1756-CNBR Bridge
Node 1
PowerFlex 750-Series Drive
with 20-750-CNETC
ControlNet Option Module
Node 62
Computer with
ControlNet Connection
(optional redundancy)
Channel A
Channel B
Control Net
Network
The Configure Drivers dialog box reappears with the new driver in the
Configured Drivers list.
8. Click Close to close the Configure Drivers dialog box.
9. Keep RSLinx software running and verify that your computer recognizes
the drive.
10. Verify that your computer recognizes the drive.
a. From the Communications menu, choose RSWho.
b. In the menu tree, click ‘+’ next to the ControlNet driver.
ControlLogix Controller
Example
After the option module is configured, the drive and option module will be a
single node on the network. This section provides the steps needed to configure a
simple ControlNet network (see Figure 5
ControlLogix controller with 1756-CNBR (Series D) bridge to communicate
with a drive using Logic Command/Status, Reference/Feedback, and 32
Datalinks (16 to read and 16 to write) over the network.
Figure 5 - Example ControlLogix Controller ControlNet Network
). In our example, we will configure a
36Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
Adding the Bridge to the I/O Configuration
To establish communications between the controller and option module over the
network, you must first add the ControlLogix controller and its bridge to the
I/O configuration.
1. Start RSLogix 5000 software.
2. From the File menu, choose New to display the New Controller dialog box
(RSLogix 5000 software, version 16.00 or later shown).
a. Choose the appropriate choices for the fields in the dialog box to match
your application.
b. Click OK.
The RSLogix 5000 dialog box reappears with the treeview in the left
pane.
3. In the treeview, right-click the I/O Configuration folder and choose New
Module.
The Select Module dialog box appears.
4. Expand the Communications group to display all of the available
communication modules.
5. In the list, select the ControlNet bridge used by your controller.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201237
Chapter 4Configuring the I/O
In this example, we use a 1756-CNBR ControlNet Bridge (Series D), so
the 1756-CNBR/D option is selected.
6. Click OK.
7. In the Select Major Revision pop-up dialog box, select the major revision
of its firmware.
8. Click OK.
The bridge’s New Module dialog box appears.
9. Edit the following:
BoxSetting
NameA name to identify the ControlNet bridge.
DescriptionOptional – description of the ControlNet bridge.
NodeThe node address of the ControlNet bridge.
SlotThe slot of the ControlNet bridge in the rack.
RevisionThe minor revision of the firmware in the ControlNet bridge. (You already set the major
Electro nic
Keying
Open Module
Properties
10. Click OK.
The bridge is now configured for the ControlNet network, added to the
RSLogix 5000 project, and appears in the I/O Configuration folder.
revision by selecting the scanner series in step 7.)
Compatible Keying. The ‘Compatible Keying’ setting for Electronic Keying verifies that
the physical module is consistent with the software configuration before the controller
and bridge make a connection. Therefore, be sure that you have set the correct revision in
this dialog box. See the online Help for additional information on this and other
Electronic Keying settings. If keying is not required, select ‘Disable Keying’. Disable Keying
is recommended.
When this box is checked, clicking OK opens additional module properties dialog boxes to
further configure the bridge. When unchecked, clicking OK closes the bridge’s New
Module dialog box. For this example, uncheck this box.
In our example, a 1756-CNBR/D bridge appears under the I/O
Configuration folder with its assigned name. For convenience, keep the
project open. Later in this chapter the project will need to be downloaded
to the controller.
38Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
There are two ways to add the option module into the I/O configuration:
• Drive Add-on Profiles (RSLogix 5000 software, version 16.00 or later)
• Drive Generic Profile (RSLogix 5000 software, all versions)
These are described in the following separate sections. If your version of RSLogix
5000 software supports drive Add-on Profiles, we recommend that you use this
method.
Using RSLogix 5000 Drive Add-On Profiles, Version 16.00 or Later
When compared to using the Generic Profile (all versions), the RSLogix 5000
drive Add-on Profiles provide the following advantages:
• Profiles for specific drives that provide descriptive controller tags for basic
control I/O words (Logic Command/Status and Reference/Feedback)
and Datalinks. Additionally, Datalinks automatically take the name of the
drive parameter to which they are assigned. These profiles virtually
eliminate I/O mismatch errors and substantially reduce drive
configuration time.
• New Drive tab eliminates the need for a separate drive software
configuration tool.
• Drive configuration settings are saved as part of the RSLogix 5000
software, version 16.00 or later, project file (.ACD) and also downloaded
to the controller.
• Drive Add-on Profiles, version 2.01 or later, enable I/O to be added online
while the controller is in Run mode.
• Drive Add-on Profiles can be updated anytime. When a new drive is used
or to benefit from new updates for Add-on Profiles, you will need the
newest Add-on Profile update. Go to http://www.ab.com/support/
abdrives/webupdate to download the latest RSLogix 5000 drive Add-on
Profile.
Add the Drive/Option Module to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as a
child device to the parent bridge. In this example, RSLogix 5000 software version
16.00 is used with drive Add-on Profile version 3.01. To determine your drive
Add-on Profile version, see Allen-Bradley Knowledgebase document #65882.
1. In the treeview, right-click on the bridge and choose New Module to
display the Select Module dialog box.
In our example, we right-click on the 1756-CNBR/D bridge. Expand the
Drives group to display all of the available drives with their
communication option modules.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201239
Chapter 4Configuring the I/O
TIP
2. From the list, select the drive and its connected option module.
For this example, we selected ‘PowerFlex 755-CNETC’.
3. Click OK.
The drive’s New Module dialog box appears.
If the PowerFlex drive is not shown, go to http://www.ab.com/support/
abdrives/webupdate and download the latest RSLogix 5000 drive Add-on
Profile.
4. On the General tab, edit the following data about the drive/option module.
BoxSetting
NameA name to identify the drive.
DescriptionOptional – description of the drive/option module.
NodeThe node address of the option module.
5. On the New Module dialog box in the Module Definition section, click
Change to launch the Module Definition dialog box and begin the drive/
option module configuration process.
40Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
TIP
6. In the Module Definition dialog box, edit the following information.
BoxSetting
RevisionThe major and minor revision of the firmware (database) in the drive. If the drive’s major
Electro nic
Keying
Drive RatingThe voltage and current rating of the drive. If the drive rating is not listed, the drive
Rating OptionsSelects the drive power output required for the application. This must match the drive’s
Special TypesReserved for future use.
Conne ctionParameters via Datalinks. When selecting ‘Parameters via Datalinks’ (default), the
To get the latest RSLogix 5000 drive Add-on Profile, go to
http://www.ab.comsupport/abdrives/webupdate
and minor revision is not available, the drive database is not installed on your computer.
To get the correct database revision, use one of the following buttons at the bottom left
of the Module Definition dialog box:
•Create Database: Creates a database from an online network drive. Clicking this
button displays an RSLinx software RSWho dialog box. Browse to the online drive (for
this example, PowerFlex 755), select it, and click OK. The database will be uploaded
and stored on the computer. Thereafter, close the Module Definition dialog box and
then re-open it to display the new revision.
• Web Update: When a drive is not available online, opens the Allen-Bradley Drives
Web Updates website to download a specific database file. After downloading the file,
close the Module Definition dialog box and then re-open it to display the new
revisio n.
• Match Drive: Use this button when the drive being added to the network matches
the drive profile (revision, rating, Datalinks, configuration settings, and so forth) of an
existing online network drive. Click this button to conveniently create a duplicate drive
profile from the online drive, and automatically load this identical information into
the Module Definition dialog box. This eliminates the need to manually enter the
information each time a new drive with a matching profile is added to the network.
Compatible Module. The ‘Compatible Module’ setting for Electronic Keying verifies that
the physical module is consistent with the software configuration before the controller
and bridge make a connection. Therefore, be sure that you have set the correct revision in
this dialog box. See the online Help for additional information on this and other
Electronic Keying settings. If keying is not required, select ‘Disable Keying’. Drives do not
require keying, and so ‘Disable Keying’ is recommended.
database is not installed on your computer. To get the drive rating, use the Create Database, Web Update, or Match Drive button described above.
actual rating.
controller tags for the Datalinks use the drive parameter names to which they are
assigned. When selecting ‘Datalinks’, the controller tags for the Datalinks have nondescriptive UserDefinedData[n] names like those used in RSLogix 5000 software, version
15.00.
.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201241
Chapter 4Configuring the I/O
IMPORTANT
BoxSetting
Data FormatParameters. When the Connection field is set to ‘Parameters via Datalinks’, ‘Parameters’
Input DataAssigns selected drive or connected peripheral parameters to be READ by the controller
Output DataAssigns selected drive or connected peripheral parameters to be WRITTEN by the
Use Network
Reference
On the Module Definition dialog box, notice that the automaticallyassigned controller tags DriveStatus, Feedback, LogicCommand, and
Reference are always used.
However, when using Datalinks you must still assign Host Parameters
01…16 - [DL From Net 01-16] and Host Parameters 17…32 - [DL To
Net 01-16] to point to the appropriate drive or connected peripheral
parameters. The procedure to configure the Datalinks on the Module
Definition dialog box for the Input Data and Output Data is the same.
is automatically selected. When the Connection field is set to ‘Datalinks’, you must select
the number of Datalinks required for your application in the ‘Data Format’ field.
using DL To Net Datalinks. See steps 6a through 6e below for details.
controller using DL From Net Datalinks. See steps 6a through 6e below for details.
Conveniently selects the speed reference for the drive to come from the network. This box
is checked by default.
a. Click the button in the topmost blank row to display the
Parameter Properties dialog box for the corresponding Datalink.
Always use the Datalink parameters in consecutive numerical order,
starting with the first parameter. (For example, use Parameters 01, 02,
and 03 to configure three Datalinks to write data and/or Parameters
17, 18, 19, 20, and 21 to configure five Datalinks to read data.)
Otherwise, the network I/O connection will be larger than necessary,
which needlessly increases controller response time and memory
usage.
42Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
b. From the Port field pull-down menu, choose the port of the device to
which this Datalink will be assigned (for this example, Port 0, the
PowerFlex 755 drive).
c. From the Parameter field pull-down menu for the selected device,
choose the parameter to which this Datalink will point (for this
example, drive parameter 370 - [Stop Mode A]).
d. Click OK to complete configuration of the Datalink.
The name of the parameter that this Datalink points to is now shown in
the row on the Module Definition dialog box.
e. Repeat Steps 6a through 6d for each Datalink being configured.
7. Click OK on the Module Definition dialog box to save the drive and
option module configuration, and close the dialog box.
The drive’s New Module dialog box reappears.
8. Click the Connection tab.
9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0
milliseconds or greater (default is 20.0 milliseconds).
This value determines the maximum interval that a controller should use
to move data to and from the option module. To conserve bandwidth, use
higher values for communicating with low priority devices.
The ‘Inhibit Module’ box, when checked, inhibits the module from
communicating with the RSLogix 5000 project. When the ‘Major Fault
On’ box is checked, a major controller fault will occur when the module’s
connection fails while the controller is in the Run Mode. For this example,
leave the ‘Inhibit Module’ and ‘Major Fault On’ boxes unchecked.
10. Click OK on the New Module dialog box.
The new node (‘My_PowerFlex_755_Drive’ in this example) now appears
under the bridge (‘My_ControlNet_Bridge’ in this example) in the I/O
Configuration folder. If you double-click the Controller Tags, you will see
that module-defined data types and tags have been automatically created
(Figure 6
include the assigned drive parameter name. After you save and download
and Figure 7). Note that all tag names are defined and Datalinks
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201243
Chapter 4Configuring the I/O
the configuration, these tags allow you to access the Input and Output data
of the drive via the controller’s ladder logic.
Figure 6 - Controller Input Tags
44Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Figure 7 - Controller Output Tags
Configuring the I/OChapter 4
Save the I/O Configuration to the Controller
After adding the bridge and drive/option module to the I/O configuration, you
must download the configuration to the controller. You should also save the
configuration to a file on your computer.
1. From the Communications menu in the RSLogix 5000 dialog box, choose
Download.
The Download dialog box appears.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201245
Chapter 4Configuring the I/O
TIP
2. Click Download to download the configuration to the controller.
When the download is successfully completed, RSLogix 5000 software
goes into the Online mode and the I/O Not Responding box in the upperleft of the dialog box should be flashing green. Also, a yellow warning
symbol should be displayed on the I/O Configuration folder in the
treeview and on the drive profile because the connections have not yet
been scheduled with the RSNetWorx for ControlNet software.
If the controller was in Run Mode before clicking Download, RSLogix
5000 software prompts you to change the controller mode back to Remote
Run. In this case, choose the appropriate mode for your application. If the
controller was in Program Mode before clicking Download, this prompt
will not appear.
3. From the File menu, choose Save.
If a message box reports that RSLogix 5000 software is unable to go
online, find your controller in the Who Active dialog box. From the
Communications menu, choose Who Active. After finding and
selecting the controller, click Set Project Path to establish the path. If
your controller does not appear, you need to add or configure the
ControlNet driver with RSLinx software. See Using RSLinx Classic
Software on page 35 and the RSLinx online help for details.
If this is the first time you saved the project, the Save As dialog box appears.
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.
To be sure that present project configuration values are saved, RSLogix
5000 software prompts you to upload them. Click Yes to upload and save
the values.
Correlate the Drive with the Controller
You must now correlate the drive settings to the RSLogix 5000 project I/O
settings so that they match. This requires loading the project I/O settings into
the drive.
1. In the treeview under I/O Configuration, right-click the drive profile (for
this example, ‘My_PowerFlex_755_Drive’) and choose Properties.
46Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
TIP
2. Click the Drive tab.
3. Click Connect to Drive to begin the correlation process.
After the drive configuration data has been verified, a pop-up dialog box
appears, which synchronizes ports from the online drive to the project to
be sure that the correct Datalinks are assigned.
4. Click OK.
If the Differences Found dialog box appears—which is typical, click
Download. This will download the project settings from the controller to
the drive and its connected option module. If Upload is clicked, the drive
and option module settings are uploaded to the controller.
On subsequent connections to the drive (after the initial download),
click Upload.
5. The I/O Configuration Differences dialog box appears.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201247
Chapter 4Configuring the I/O
6. To match the Datalinks in the drive to the project I/O configuration, click
Use Project.
After the datalinks have been matched, the Input Data and Output Data
columns are grayed out.
7. Click Continue.
A series of download dialog boxes appear, which may take a minute to
complete.
8. Click OK to close the Module Properties dialog box for the drive.
9. Use the procedure in the next subsection Use RSNetworx for ControlNet
Software to Configure and Save the I/O to the Bridge to do the following:
• Change the I/O Not Responding box in the upper-left of the RSLogix
5000 dialog box from flashing green to steady green.
• Remove the yellow warning symbols in the treeview under the I/O
Configuration folder and drive profile.
Use RSNetworx for ControlNet Software to Configure and Save the I/O to the Bridge
After configuring the I/O in the controller and drive, you must now download
and save these configurations to the bridge. This will also resolve the I/O Not
Responding box and the yellow warning symbols in the RSLogix 5000
project.
1. Start RSNetWorx for ControlNet software.
2. From the File menu, choose New to display the New File dialog box.
3. Select ControlNet Configuration as the network configuration type.
4. Click OK.
5. From the Network menu, choose Online to display the Browse for
Network dialog box.
48Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
6. Expand the communication path from your computer to the ControlNet
bridge.
The following dialog box shows our example navigating to devices on a
ControlNet network. Depending on the communication link you are
using, the navigation path may be different.
7. Click OK after selecting a valid path to the ControlNet network (for this
example, A, ControlNet).
As the selected ControlNet path is browsed, RSNetWorx for ControlNet
software creates a graph view window that shows a graphical
representation of the devices on the network.
If the icon for the drive (for this example, PowerFlex 755) on the network
appears as Unrecognized Device, you must download the EDS file for that
PowerFlex 750-Series drive from the Rockwell Automation website.
a. Go to the website http://www.rockwellautomation.com/resources/eds
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201249
.
Chapter 4Configuring the I/O
TIP
b. On the website search screen in the Network entry field, enter the type
of network (for this example, ControlNet), which enables the use of the
other search fields.
c. In the Keyword entry field, enter the type of PowerFlex 750-Series drive
(for this example, PowerFlex 755), noting that this field is space
sensitive.
d. Click Search.
Due to the large number of EDS files, this search may take seconds or
up to several minutes.
e. On the search results screen in the Details & Download Column, click
the ‘Download’ hyperlink for the EDS file.
f. Click Save on the File Download screen to save the EDS file to an
appropriate location on your computer.
g. Launch the EDS Hardware Installation Tool by clicking on the
Microsoft Windows Start button and choosing Programs > Rockwell
Software > RSLinx Tools > EDS Hardware Installation Tool.
Then follow the screen prompts to add the EDS file for use with your
project.
h. Reboot the computer and repeat steps 1 through 7 at the beginning of
this subsection.
The Unrecognized Device icon in the RSNetWorx for ControlNet
graph view window in step 7 should have been replaced by a drive icon
(for this example, the icon for a PowerFlex 755 drive).
8. From the Network menu, choose Enable Edits, or check the Edits Enabled
box in the RSNetWorx for ControlNet project window.
If the bridge has a different I/O configuration than the configuration now
being saved, the Online/Offline mismatch dialog box will appear.
a. When both Options choices are available, click ‘Use offline data
(download)’. When this choice is dimmed (grayed out), you must click
‘Use online data (upload)’.
b. Click OK.
If a message box reports that the download cannot be completed
because the controller is not in Program mode, click Change Mode to
place the controller in Remote Program mode and continue the
download.
9. From File menu, choose Save to save the I/O configuration file to the
computer.
If this is the first time you saved the project, the Save As dialog box appears.
50Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
TIP
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.
The Save Configuration dialog box appears.
d. Click OK to download the I/O configuration to the bridge.
When both Save Type choices are available, we recommend to click
‘Optimize and re-write schedule for all connections’.
Using the RSLogix 5000 Generic Profile, All Versions
We recommend that you only use the basic RSLogix 5000 software Generic
Profile for any of the following reasons:
• A specific drive profile in other versions of RSLogix 5000 software is
unavailable.
• Users are already familiar with a Generic Profile and do not want to
convert an existing project to a drive Add-on Profile (RSLogix 5000
software, version 16.00 or later).
• A project must maintain specific revision level control.
• The controller cannot be taken offline. RSLogix 5000 software, version
16.00 or later, enables the drive Generic Profile to be added while the
controller is online and in the Run mode.
Add the Drive/Option Module to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as a
child device to the parent bridge.
1. In the treeview, right-click the bridge and choose New Module to display
the Select Module dialog box.
In our example, we right-click the 1756-CNBR/D bridge.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201251
Chapter 4Configuring the I/O
2. Expand the Communications group to display all of the available
communication modules.
3. Select ‘CONTROLNET-MODULE’ from the list to configure the drive
and its connected ControlNet option module.
4. Click OK.
The drive’s New Module dialog box appears.
5. Edit the following information about the drive and option module.
BoxSetting
NameA name to identify the drive and option module.
DescriptionOptional – description of the drive/option module.
Comm FormatData - DINT (This setting formats the data in 32-bit words.)
Node AddressThe node address of the option module.
Open Module
Properties
When this box is checked, clicking OK opens additional module properties dialog boxes
to further configure the drive/option module. When unchecked, clicking OK closes the
drive’s New Module dialog box. For this example, check this box.
52Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
6. Under Connection Parameters, edit the following information.
BoxAssembly
Input1 (This value is
Output2 (This value is
Confi guration6 (This value is
Enter the number of 32-bit words that are required for your I/O in the
Input Size and Output Size boxes. Because the option module always uses
the 32-bit Logic Status, 32-bit Feedback, and a 32-bit word dedicated for
memory allocation of the Generic ControlNet module profile, at least
three 32-bit words must be set for the Input Size. The option module also
uses the 32-bit Logic Command and 32-bit Reference, requiring at least
two 32-bit words for the Output Size. If any or all of the drive’s sixteen 32bit Datalinks are used (see Setting a Master-Slave Hierarchy (Optional)
page 26), the Input and Output Size settings must be increased
accordingly.
•Input Size: Start with 3 words and add 1 word for each Datalink used
to read data. For example, if 3 Datalinks—Host [DL To Net xx]
parameters—will be used to read drive or peripheral parameters, add 3
words to the required 3 words for a total of 6 words. You can use option
module DeviceParameter 03 - [DLs To Net Act] to check the total
number of Datalinks being used. Word 0 is a pad word, Word 1 is Logic
Status, Word 2 is Speed Feedback, Word 3 is DL To Net 01, and so
forth (see Figure 8
•Output Size: Start with 2 words and add 1 word for each Datalink
used to write data. For example, if 7 Datalinks—Host [DL From Net xx] parameters—will be used to write to drive or peripheral parameters,
add 7 words to the required 2 words for a total of 9 words. You can use
option module Device Parameter 02 - [DLs From Net Act] to check
the total number of Datalinks being used. Word 0 is Logic Command,
Word 1 is Speed Reference, Word 2 is DL From Net 01, and so forth
(see Figure 9
Instance
required. )
required. )
required. )
).
Size
The value will vary based on the number of Host [DL From Net xx]
parameters used for your application (see details below).
The value will vary based on the number of Host [DL To Net xx]
parameters used for your application (see details below).
0 (This value is required.)
on
).
For the example in this manual, all 16 Host[DL From Net xx] and all 16 Host[DL To Net xx] are used, resulting in an Input Size of ‘19’ and an
Output Size of ‘18’.
7. After setting the information in the drive’s New Module dialog box, click
OK.
The Module Properties dialog box appears.
8. Click the Connection tab.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201253
Chapter 4Configuring the I/O
9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0
milliseconds or greater (default is 20.0 milliseconds).
This value determines the maximum interval that a controller should use
to move data to and from the option module. To conserve bandwidth, use
higher values for communicating with low priority devices.
The ‘Inhibit Module’ box, when checked, inhibits the module from
communicating with the RSLogix 5000 project. When the ‘Major Fault
On’ box is checked, a major controller fault will occur when the module’s
connection fails while the controller is in the Run Mode. For this example,
leave the ‘Inhibit Module’ and ‘Major Fault On’ boxes unchecked.
10. Click OK.
The new node (‘My_PowerFlex_755_Drive’ in this example) now appears
under the bridge (‘My_ControlNet_Bridge’ in this example) in the I/O
Configuration folder. If you double-click the Input and Output Controller
Ta g s (Figure 8
and tags have been automatically created. After you save and download the
configuration, these tags allow you to access the Input and Output data of
the drive via the controller’s ladder logic.
Figure 8 - Input Image Controller Tags
and Figure 9), you will see that module-defined data types
54Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
TIP
TIP
Figure 9 - Output Image Controller Tags
Save the I/O Configuration to the Controller
After adding the bridge and drive/option module to the I/O configuration, you
must download the configuration to the controller. You should also save the
configuration to a file on your computer.
When using RSLogix 5000 software, version 16.00 or later, you can add the I/O
configuration of a Generic Profile while the controller is online and in the Run
mode.
1. From the Communications menu in the RSLogix 5000 dialog box, choose
Download.
The Download dialog box appears.
If a message box reports that RSLogix 5000 software is unable to go
online, find your controller in the Who Active dialog box. From the
Communications menu, choose Who Active. After finding and
selecting the controller, click Set Project Path to establish the path. If
your controller does not appear, you need to add or configure the
ControlNet driver with RSLinx software. See Using RSLinx Classic
Software on page 35 and RSLinx online help for details.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201255
Chapter 4Configuring the I/O
2. Click Download to download the configuration to the controller.
When the download is successfully completed, RSLogix 5000 software
goes into the Online mode and the I/O Not Responding box in the upperleft of the screen should be flashing green.
3. From the File menu, choose Save.
If this is the first time you saved the project, the Save As dialog box appears.
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.
4. Configure any Datalinks in the drive that were enabled in the controller
and option module during I/O configuration.
Each Datalink being used must be assigned to a specific parameter in the
drive or connected peripheral (see Setting a Master-Slave Hierarchy
(Optional) on page 26). If this is not done, the controller will receive or
send placeholder data instead of actual drive or peripheral parameter
values.
5. Place the controller in Remote Run or Run Mode.
6. Use the procedure in the next subsection Use RSNetworx for ControlNet
Software to Configure and Save the I/O to the Bridge to do the following:
• Change the I/O Not Responding box in the upper-left of the RSLogix
5000 window from flashing green to steady green.
• Remove the yellow warning symbols in the treeview under the I/O
Configuration folder and drive profile.
Use RSNetworx for ControlNet Software to Configure and Save the I/O to the Bridge
After configuring the I/O in the controller and drive, you must now download
and save these configurations to the bridge. This will also resolve the I/O Not
Responding box and the yellow warning symbols in the RSLogix 5000
project.
1. Start RSNetWorx for ControlNet software.
2. From the File menu, choose New to display the New File dialog box.
3. Select ControlNet Configuration as the network configuration type.
4. Click OK.
5. From the Network menu, choose Online to display the Browse for
Network dialog box.
56Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
6. Expand the communications path from your computer to the ControlNet
bridge.
The following dialog box shows our example navigating to devices on a
ControlNet network. Depending on the communication link you are
using, the navigation path may be different.
7. Click OK after selecting a valid path to the ControlNet network (for this
example, A, ControlNet).
As the selected ControlNet path is browsed, RSNetWorx for ControlNet
software creates a graph view window that shows a graphical
representation of the devices on the network.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201257
Chapter 4Configuring the I/O
If the icon for the drive (for this example, PowerFlex 755) on the network
appears as Unrecognized Device, you must download the EDS file for that
PowerFlex 750-Series drive from the Rockwell AUtomation website.
a. Go to the website http://www.rockwellautomation.com/resources/eds
b. On the website search screen in the Network entry field, enter the type
of network (for this example, ControlNet), which enables the use of the
other search fields.
c. In the Keyword entry field, enter the type of PowerFlex 750-Series drive
(for this example, PowerFlex 755), noting that this field is space
sensitive.
d. Click Search.
Due to the large number of EDS files, this search may take seconds or
up to several minutes.
e. On the search results screen in the Details & Download Column, click
the ‘Download’ hyperlink for the EDS file.
f. Click Save on the File Download screen to save the EDS file to an
appropriate location on your computer.
g. Launch the EDS Hardware Installation Tool by clicking on the
Microsoft Windows Start button and choosing Programs > Rockwell
Software > RSLinx Tools > EDS Hardware Installation Tool.
Then follow the screen prompts to add the EDS file for use with your
project.
h. Reboot the computer and repeat steps 1 through 7 at the beginning of
this subsection.
The Unrecognized Device icon in the RSNetWorx for ControlNet
graph view window in step 7 should have been replaced by a drive icon
(for this example, the icon for a PowerFlex 755 drive).
.
8. From the Network menu, choose Enable Edits, or check the Edits Enabled
box in the RSNetWorx for ControlNet project window.
58Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Configuring the I/OChapter 4
TIP
TIP
If the bridge has a different I/O configuration than the configuration now
being saved, the Online/Offline mismatch dialog box will appear.
a. When both Options choices are available, click ‘Use offline data
(download)’. When this choice is dimmed (grayed out), you must click
‘Use online data (upload)’.
b. Click OK.
If a message box reports that the download cannot be completed
because the controller is not in Program mode, click Change Mode to
place the controller in Remote Program mode and continue the
download.
9. From the File menu, choose Save to save the I/O configuration file to the
computer.
If this is the first time you saved the project, the Save As dialog box appears.
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.
The Save Configuration dialog box appears.
d. Click OK to download the I/O configuration to the bridge.
When both Save Type choices are available, we recommend to click
‘Optimize and re-write schedule for all connections’.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201259
Chapter 4Configuring the I/O
Notes:
60Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 5
Using the I/O
This chapter provides information and examples that explain how to control,
configure, and monitor a PowerFlex 750-Series drive using the configured I/O.
Top icPa ge
About I/O Messaging
Understanding the ControlLogix Controller I/O Image62
Using Logic Command/Status63
Using Reference/Feedback63
Using Datalinks64
Example Ladder Logic Program Information65
ControlLogix Controller Example66
61
About I/O Messaging
ATTENTION: Risk of injury or equipment damage exists. The examples in this
publication are intended solely for purposes of example. There are many
variables and requirements with any application. Rockwell Automation does not
assume responsibility or liability (to include intellectual property liability) for
actual use of the examples shown in this publication.
On CIP-based networks, including ControlNet, I/O connections are used to
transfer the data which controls the PowerFlex drive and sets its Reference. I/O
can also be used to transfer data to and from Datalinks in PowerFlex 750-Series
drives.
The option module includes the Logic Command, Logic Status, Reference, and
Feedback (all as 32-bit words) in the controller’s I/O image. This basic I/O must
always be configured in the ControlNet bridge using RSLogix 5000 software.
Additional I/O, if needed, can be set using up to 16 Datalinks to write data and/
or up to 16 Datalinks to read data. When using any combination of these
Datalinks, add one 32-bit word for each Datalink to the basic I/O Input Size
and/or Output Size.
Chapter 3
Configuring the I/O, discuss how to configure the option module and controller
on the network for the required I/O. The Glossary defines the different options.
This chapter discusses how to use I/O after you have configured the option
module and controller.
, Configuring the Option Module, and Chapter 4,
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201261
Chapter 5Using the I/O
Understanding the
ControlLogix Controller I/O
Image
The terms ‘input’ and ‘output’ are defined from the controller’s point of view.
Therefore, output I/O is data that is produced by the controller and consumed by
the option module. Input I/O is status data that is produced by the option
module and consumed as input by the controller. The I/O image will vary based
on the following :
• How many of the drive’s 32-bit Datalinks (Host DL From Net 01-16 and
Host DL To Net 01-16) are used.
• ControlLogix/CompactLogix Controllers only—The drive profile used
in RSLogix 5000 software (drive Add-on Profile in version 16.00 or later,
or Generic Profile in all versions).
Since the drive Add-on Profile in RSLogix 5000 software, version 16.00 or later,
provides descriptive controller tags, the I/O image (tag size and location) is
automatically configured based on the drive being used. When using the RSLogix
5000 Generic Profile, however, controller tags are not descriptive or defined.
shows the I/O image when using all of the 32-bit Datalinks.
(32-bit Logic Command/Status, Reference/Feedback, and Datalinks)
DINTOutput I/O
DINTDrive Add-on ProfileDINTGeneric Profile
0Logic Command0Logic Status0Padword
1Reference1Feedback1Logic Status
2DL From Net 012DL To Net 012Feedback
3DL From Net 023DL To Net 023DL To Net 01
4DL From Net 034DL To Net 034DL To Net 02
5DL From Net 045DL To Net 045DL To Net 03
6DL From Net 056DL To Net 056DL To Net 04
7DL From Net 067DL To Net 067DL To Net 05
8DL From Net 078DL To Net 078DL To Net 06
9DL From Net 089DL To Net 089DL To Net 07
10DL From Net 0910DL To Net 0910DL To Net 08
11DL From Net 1011DL To Net 1011DL To Net 09
12DL From Net 1112DL To Net 1112DL To Net 10
13DL From Net 1213DL To Net 1213DL To Net 11
14DL From Net 1314DL To Net 1314DL To Net 12
15DL From Net 1415DL To Net 1415DL To Net 13
16DL From Net 1516DL To Net 1516DL To Net 14
17DL From Net 1617DL To Net 1617DL To Net 15
Input I/O Using…
18DL To Net 16
62Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using the I/OChapter 5
TIP
Using Logic Command/Status
Using Reference/Feedback
The Logic Command is a 32-bit word of control data produced by the controller
and consumed by the option module. The Logic Status is a 32-bit word of status
data produced by the option module and consumed by the controller.
When using a ControlLogix controller, the Logic Command word is always
DINT 0 in the output image and the Logic Status word is always:
• DINT 0 in the input image when using the drive Add-on Profile.
• DINT 1 in the input image when using the Generic Profile.
This manual contains the bit definitions for compatible products available at the
time of publication in Appendix
750-Series Drives.
The Reference is a 32-bit REAL (floating point) piece of control data produced
by the controller and consumed by the option module. The Feedback is a 32-bit
REAL (floating point) piece of status data produced by the option module and
consumed by the controller.
When using a ControlLogix controller, the 32-bit REAL Reference word is
always DINT 1 in the output image (see Ta b l e 2
word is always:
• DINT 1 in the input image when using the drive Add-on Profile.
• DINT 2 in the input image when using the Generic Profile.
D, Logic Command/Status Words: PowerFlex
) and the 32-bit REAL Feedback
When using a drive Add-on Profile, the Reference and Feedback are
automatically formatted properly and displayed as a controller tag. When using
the Generic Profile, the I/O image is integer-based and the Reference and
Feedback are floating point. Because of this, a COP (Copy) instruction or User
Defined Data Type (UDDT) is required to correctly write values to the
Reference and read values from the Feedback. See the ladder logic program
examples in Figure 15
The Reference and Feedback 32-bit REAL values represent drive speed. The
scaling for the speed Reference and Feedback is dependent on drive Parameter
300 - [Speed Units]. For example, if Parameter 300 is set to Hz, a 32-bit REAL
Reference value of ‘30.0’ would equal a Reference of 30.0 Hz. If Parameter 300 is
set to RPM, a 32-bit REAL Reference value of ‘1020.5’ would equal a Reference
of 1020.5 RPM. Note that the commanded maximum speed can never exceed the
value of drive Parameter 520 - [Max Fwd Speed]. Ta b l e 3
References and their results for a PowerFlex 750-Series drive that has its:
• Parameter 300 - [Speed Units] set to Hz.
• Parameter 37 - [Maximum Freq] set to 130 Hz.
• Parameter 520 - [Max Fwd Speed] set to 60 Hz.
and Figure 16.
When using the drive Add-on Profile, the controller tags for Reference and
Feedback are automatically and properly formatted. This eliminates the need
for data conversion using COP (copy) instructions or a UDDT to copy the DINT
data into a REAL word.
shows example
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201263
Chapter 5Using the I/O
IMPORTANT
When Parameter 300 - [Speed Units] is set to RPM, the other parameters are also
in RPM.
Table 3 - PowerFlex 750-Series Drive Example Speed Reference/Feedback Scaling
Network Reference ValueSpeed Command Value
130.0130 Hz60 Hz
65.065 Hz60 Hz
32.532.5 Hz32.5 Hz32.5
0.00 Hz0 Hz0.0
(1)
-32.5
(1) The effects of values less than 0.0 depend on whether the PowerFlex 750-Series drive uses a bipolar or unipolar direction mode. See
the drive documentation for details.
(2) For this example, drive parameter 300 - [Speed Units] is set to Hz.
(3) The drive runs at 60 Hz instead of 130 Hz or 65 Hz because drive Parameter 520 - [Max Fwd Speed] sets 60 Hz as the maximum
speed.
32.5 Hz32.5 Hz32.5
(2)
Output SpeedNetwork Feedback Value
(3)
(3)
60.0
60.0
Using Datalinks
A Datalink is a mechanism used by PowerFlex drives to transfer data to and from
the controller. Datalinks allow a drive parameter value to be read or written to
without using an Explicit Message. When enabled, each Datalink occupies one
32-bit word in a ControlLogix controller.
The following rules apply when using PowerFlex 750-Series drive Datalinks:
• The target of a Datalink can be any Host parameter, including those of a
peripheral. For example, drive parameter 535 - [Accel Time 1] can be the
target of any or all option modules installed in the drive.
• The data passed through the drive’s Datalink mechanism is determined by
the settings of Host Parameters 01…16 - [DL From Net 01-16] and Host Parameters 17…32 - [DL To Net 01-16].
A reset is always required after configuring Datalinks so that the
changes take effect.
• When an I/O connection that includes Datalinks is active, those Datalinks
being used are locked and cannot be changed until that I/O connection
becomes idle or inactive.
• When you use a Datalink to change a value, the value is not written to the
Nonvolatile Storage (NVS) memory. The value is stored in volatile
memory and lost when the drive loses power. Thus, use Datalinks when
you need to change a value of a parameter frequently.
Datalinks for PowerFlex 750-Series drive peripherals (the embedded EtherNet/
IP adapter on PowerFlex 755 drives only, and option modules such as an encoder
or a communication module) are locked when the peripheral has an I/O
connection with a controller. When a controller has an I/O connection to the
drive, the drive does not allow a reset to defaults, configuration download, or
64Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
TIP
Using the I/OChapter 5
anything else that could change the makeup of the I/O connection in a running
system. The I/O connection with the controller must first be disabled to allow
changes to the respective Datalinks.
Depending on the controller being used, the I/O connection can be disabled by
doing the following :
• Inhibiting the module in RSLogix 5000 software
• Putting the controller in Program mode
• Placing the scanner in idle mode
• Disconnecting the drive from the network
DeviceLogix Datalinks are also locked while the DeviceLogix program is
running. The DeviceLogix program must first be disabled to allow changes to the
Datalinks. Set DeviceLogix parameter 53 - [DLX Operation] to ‘DisableLogic’
to disable the logic (the parameter value will then change to ‘LogicDisabld’).
When using the drive Add-on Profile, the controller tags for Reference and
Feedback to Datalinks are automatically and properly formatted.
If a Generic Profile is used, a COP (copy) instruction or a UDDT is needed—for
REAL parameters, speed Reference, and speed Feedback only—to copy the
DINT data into a REAL word for input data conversion. For output data
conversion, a COP (Copy) instruction or UDDT is needed—for REAL parameters,
speed Reference, and speed Feedback only—to copy the REAL data into a
DINT word. To determine whether a parameter is a 32-bit integer (DINT) or a
REAL data type, see the Data Type column in the chapter containing
parameters in the PowerFlex 750-Series AC Drives Programming Manual,
publication 750-PM001
.
Example Ladder Logic
Program Information
The example ladder logic programs in the sections of this chapter are intended for
and operate PowerFlex 750-Series drives.
Functions of the Example Programs
The example programs enable you to do the following:
• Receive Logic Status information from the drive.
• Send a Logic Command to control the drive (for example, start, stop).
• Send a Reference to the drive and receive Feedback from the drive.
• Send/receive Datalink data to/from the drive.
Logic Command/Status Words
These examples use the Logic Command word and Logic Status word for
PowerFlex 750-Series drives. See Appendix
PowerFlex 750-Series Drivesto view details.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201265
D, Logic Command/Status Words:
Chapter 5Using the I/O
ControlLogix Controller
Example
This section include information when using a ControlLogix controller and an
RSLogix 5000 Drive Add-on Profile or a Generic Profile.
Creating Ladder Logic Using the RSLogix 5000 Drive Add-on Profiles,
Version 16.00 or Later
Because the drive Add-on Profile automatically created descriptive controller tags
(Figure 6
control and monitor the drive without creating any ladder logic program.
However, if you intend to use Human Machine Interface devices (for example, a
PanelView graphic terminal) to operate the drive and view its status, you will
need to create descriptive user-defined Program tags (Figure 10
logic program that will pass the Controller tag data to the Program tags.
Figure 10 - ControlLogix Program Tags for Drive Add-on Profile Ladder Logic Program Example
) for the entire I/O image in Chapter 4, you can use these tags to directly
) and a ladder
An example ladder logic program that uses the automatically-created descriptive
Controller tags and passes their data to the user-defined Program tags is shown in
Figure 11
determined by the name assigned when configuring the I/O (Chapter 4
and Figure 12. Note that the prefix for the drive Controller tags is
).
66Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using the I/OChapter 5
Figure 11 - ControlLogix Controller Example Ladder Logic Program Using a Drive Add-on Profile
for Logic Status/Feedback
Figure 12 - ControlLogix Controller Example Ladder Logic Program Using a Drive Add-on Profile
for Logic Command/Reference
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201267
Chapter 5Using the I/O
TIP
Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All
Versions
Option Module Parameter Settings for ControlLogix Controller Example
These option module settings were used for the example ladder logic program in
this section.
Option Module Host ParameterValueDescription
01 - [DL From Net 01]370Points to drive Par. 370 - [Stop Mode A]
02 - [DL From Net 02]371Points to drive Par. 371 - [Stop Mode B]
03 - [DL From Net 03]535Points to drive Par. 535 - [Accel Time 1]
04 - [DL From Net 04]536Points to drive Par. 536 - [Accel Time 2]
05 - [DL From Net 05]537Points to drive Par. 537 - [Decel Time 1]
06 - [DL From Net 06]538Points to drive Par. 538 - [Decel Time 2]
07 - [DL From Net 07]539Points to drive Par. 539 - [Jog Acc Dec Time]
08 - [DL From Net 08]556Points to drive Par. 556 - [Jog Speed 1]
09 - [DL From Net 09]557Points to drive Par. 557 - [Jog Speed 2]
10 - [DL From Net 10]571Points to drive Par. 571 - [Preset Speed 1]
11 - [DL From Net 11]572Points to drive Par. 572 - [Preset Speed 2]
12 - [DL From Net 12]573Points to drive Par. 573 - [Preset Speed 3]
13 - [DL From Net 13]574Points to drive Par. 574 - [Preset Speed 4]
14 - [DL From Net 14]575Points to drive Par. 575 - [Preset Speed 5]
15 - [DL From Net 15]576Points to drive Par. 576 - [Preset Speed 6]
16 - [DL From Net 16]577Points to drive Par. 577 - [Preset Speed 7]
17 - [DL To Net 01]370Points to drive Par. 370 - [Stop Mode A]
18 - [DL To Net 02]371Points to drive Par. 371 - [Stop Mode B]
19 - [DL To Net 03]535Points to drive Par. 535 - [Accel Time 1]
20 - [DL To Net 04]536Points to drive Par. 536 - [Accel Time 2]
21 - [DL To Net 05]537Points to drive Par. 537 - [Decel Time 1]
22 - [DL To Net 06]538Points to drive Par. 538 - [Decel Time 2]
23 - [DL To Net 07]539Points to drive Par. 539 - [Jog Acc Dec Time]
24 - [DL To Net 08]556Points to drive Par. 556 - [Jog Speed 1]
25 - [DL To Net 09]557Points to drive Par. 557 - [Jog Speed 2]
26 - [DL To Net 10]571Points to drive Par. 571 - [Preset Speed 1]
27 - [DL To Net 11]572Points to drive Par. 572 - [Preset Speed 2]
28 - [DL To Net 12]573Points to drive Par. 573 - [Preset Speed 3]
29 - [DL To Net 13]574Points to drive Par. 574 - [Preset Speed 4]
30 - [DL To Net 14]575Points to drive Par. 575 - [Preset Speed 5]
31 - [DL To Net 15]576Points to drive Par. 576 - [Preset Speed 6]
32 - [DL To Net 16]577Points to drive Par. 577 - [Preset Speed 7]
The Host[DL From Net xx] parameters are inputs into the drive that come
from controller outputs (for example, data to write to a drive parameter). The
Host[DL To Net xx] parameters are outputs from the drive that go to
controller inputs (for example, data to read a drive parameter).
68Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using the I/OChapter 5
Controller Tags
When you add the option module and drive to the I/O configuration
(Chapter 4
descriptive) controller tags. In this example program, the following controller
tags are used.
You can expand the Input and Output tags to reveal the input and output
configuration. The Input tag for this example program requires nineteen 32-bit
words of data (see Figure 13
eighteen 32-bit words of data (see Figure 14
Figure 13 - ControlLogix Controller Input Image for Drive Generic Profile Example Ladder Logic
). The Output tag for this example program requires
).
Program
Figure 14 - ControlLogix Controller Output Image for Drive Generic Profile Example Ladder Logic
Program
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201269
Chapter 5Using the I/O
Program Tags
To use the Controller tags that are automatically created, you need to create the
following Program tags for this example program.
Figure 15 - ControlLogix Controller Example Ladder Logic Program Using a Drive Generic Profile for
Logic Status/Feedback
70Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using the I/OChapter 5
Figure 16 - ControlLogix Controller Example Ladder Logic Program Using a Drive Generic Profile for
Logic Command/Reference
Example Datalink Data
The Datalink data used in the example program is shown in Figure 17. Note that
to describe the parameters to which the Datalinks are assigned, you may want to
add descriptions to the automatically-created generic controller tags or create a
UDDT. For this example, the DL_From_Net tags were created to describe the
drive parameters to which these Datalinks are assigned. For example,
DL_From_Net _01_Stop_Mode_A indicates that option module Host Parameter 01 - [DL From Net 01] is assigned to drive parameter 370 - [Stop
Mode A]. This same method applies to the DL_To_Net tags.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201271
Chapter 5Using the I/O
TIP
Figure 17 - ControlLogix Controller Example Datalinks for Ladder Logic Program Using a Drive
Generic Profile
To determine whether a parameter is a 32-bit integer (DINT) or a REAL data
type, see the Data Type column in the chapter containing parameters in the
PowerFlex 750-Series AC Drives Programming Manual, publication 750PM001. If a parameter is a REAL, a COP (Copy) instruction or UDDT is needed to
copy the DINT to a REAL (inputs) or copy the REAL to a DINT (outputs).
72Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 6
Using Explicit Messaging
This chapter provides information and examples that explain how to use Explicit
Messaging with a ControlLogix controller to configure and monitor the option
module and connected PowerFlex 750-Series drive.
Top icPa ge
About Explicit Messaging
Performing Explicit Messaging75
ControlLogix Controller Examples76
ATTENTION: Risk of injury or equipment damage exists. The examples in this
publication are intended solely for purposes of example. There are many
variables and requirements with any application. Rockwell Automation does not
assume responsibility or liability (to include intellectual property liability) for
actual use of the examples shown in this publication.
74
ATTENTION: Risk of equipment damage exists. If Explicit Messages are
programmed to write parameter data to Nonvolatile Storage (NVS) frequently,
the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do
not create a program that frequently uses Explicit Messages to write parameter
data to NVS. Datalinks do not write to NVS and should be used for frequently
changed parameters.
See Chapter 5 for information about the I/O Image, using Logic Command/
Status, Reference/Feedback, and Datalinks.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201273
Chapter 6Using Explicit Messaging
IMPORTANT
TIP
IMPORTANT
About Explicit Messaging
Explicit Messaging is used to transfer data that does not require continuous
updates. With Explicit Messaging, you can configure and monitor a slave device’s
parameters on the network.
When an explicit message is performed, by default no connection is made since it
is an ‘unconnected’ message. When timing of the message transaction is
important, you can create a dedicated message connection between the
controller and drive by checking the ‘Connected’ box on the Communications tab
message configuration screen during message setup. These message
connections are in addition to the I/O connection. However, the trade off for more
message connections is decreased network performance. If your application
cannot tolerate this, do not check the ‘Connected’ box, which is recommended.
To message to another device in a different drive port, see the Instance table in
Appendix C:
• DPI Parameter Object section on page 115
• Host DPI Parameter Object section on page 129
In the Message Configuration dialog box, set the Instance field to an
appropriate value within the range listed for the port in which the device
resides.
for Device parameters.
for Host parameters.
PowerFlex 750-Series drives have explicit messaging limitations. Tab le 4 shows
the ControlNet Object Class code compatibilities for these drives.
Table 4 - Explicit Messaging Class Code Compatibility with PowerFlex 750-Series Drive
ControlNet Objec t Class CodeCompatibilityExplicit Messaging Function
(1) Enables access to drive parameters (Por t 0), DPI device parameters (Ports 1…6 only), and Host parameters (Ports 7…14 o nly). For
example, DPI Parameter Object Class code 0x93 can access a Safe Speed Monitor option module in Port 6. However, Class code 0x93
cannot access, for example, the Host parameters in a 24V I/O option module in Port 5. See DPI Parameter Object
instance (parameter) numbering.
(2) Enables access to drive parameters (Por t 0) and Host parameters for all ports (1…14). Host DPI Parameter Object Class code 0x9F
cannot access DPI (device) parameters. For example, if a 20-750-CNET option module is in Port 4, its Host parameters can be
accessed, but not its DPI (device) parameters. See Host DPI Parameter Object
(1)
with limitations
(2)
with limitations
Single and scattered parameter reads/writes
Single and scattered parameter reads/writes
on page 115 for
on page 129 for instance (parameter) numbering.
74Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
IMPORTANT
Complete Explicit
Message
Retrieve Explicit
Message Response
Set up and send Explicit
Message Request
(optional redundancy)
Channel A
Channel B
Control Net
Network
Performing Explicit
Messaging
There are five basic events in the Explicit Messaging process. The details of each
step will vary depending on the type of controller being used. See the
documentation for your controller.
There must be a request message and a response message for all Explicit
Messages, whether you are reading or writing data.
Figure 18 - Explicit Message Process
➊
➎
➍
Event Description
You format the required data and set up the ladder logic program to send an Explicit Message request to the
➊
scanner module (download).
The scanner module transmits the Explicit Message Request to the slave device over the network.
➋
The slave device transmits the Explicit Message Response back to the scanner. The data is stored in the
➌
scanner buffer.
The controller retrieves the Explicit Message Response from the scanner’s buffer (upload).
➍
The Explicit Message is complete.
➎
➋➌
For information on the maximum number of Explicit Messages that can be
executed at a time, see the documentation for the bridge or scanner and/or
controller that is being used.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201275
Chapter 6Using Explicit Messaging
TIP
IMPORTANT
IMPORTANT
ControlLogix Controller
Examples
To display the Message Configuration dialog box in RSLogix 5000 software, add
a message instruction (MSG), create a new tag for the message (Properties:
Base tag type, MESSAGE data type, controller scope), and click the button
in the message instruction.
For supported classes, instances, and attributes, see Appendix C, ControlNet
Objects.
The explicit messaging examples in this sec tion can be performed with RSLogix
5000 software, any version—or Studio 5000™ Logix Designer application,
version 21.00 or later.
The read and write messaging examples in this section are for Device
parameters which use Class Code 0x93. For Host parameters, use Class Code
0x9F and format the rest of the message in the same way as these examples.
The Message Configuration has a Service Type of ‘Parameter Read’ which is
Class code 0x0F, Parameter Object. Parameter Object is not supported in
PowerFlex 750-series drives.
ControlLogix Controller Example Ladder Logic Program to Read a
Single Parameter
A Get Attribute Single message is used to read a single parameter. This read
message example reads the value of the 32-bit REAL (floating point) parameter
007 - [Output Current] in a PowerFlex 750-Series drive.
Table 5 - Example Controller Tags to Read a Single Parameter
OperandController Tags for Single Read MessageData Type
XICExecute_Single_Read_MessageBOOL
MSGSingle_Read_MessageMESSAGE
Figure 19 - Example Ladder Logic to Read a Single Parameter
76Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
ControlLogix – Formatting a Message to Read a Single Parameter
Figure 20 - Get Attribute Single Message Configuration Dialog Boxes
The following table identifies the data that is required in each box to configure a
message to read a single parameter.
Configuration TabExample ValueDescription
Message Type
Service Type
Service Code
Class
Instance
Attribute
Source Element
Source Length
Destination
Communication TabExample ValueDescription
Path
Tag Ta bExa mple V alueD escri ptio n
NameSingle_Read_MessageThe name for the message.
(1) The default setting for Service Type is ‘Custom’, enabling entry of a Serv ice Code not available from the Service Type pull-down menu. When choosing a
(2) The instance is the parameter number in the drive (Port 0). For example, to read parameter 4 of a peripheral in Port 5 of a PowerFlex 755 d rive, the
(3) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder (for this ex ample, My_PowerFlex_755 _Drive).
(4) See Table 4 on page 74
(5) In this example, Output Current is a 32-bit REAL (floating point) parameter requiring the Data Type field to be set to ‘REAL’ when creating the controller
(1)
(1)
(2)
(3)
Service Type other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically assigned to the Service Code box which is
dimmed (unavailable).
instance would be 21504 + 4 = 21508. See DPI Parameter Object
0x9F) to determine the instance number.
Class code 0x9F for explicit messaging.
tag. To read a 32-bit integer parameter, set the tag Data Type field to ‘DINT’. For a 16-bit parameter, set the Data Type field to ‘I NT’. See the drive
documentation to determine the size of the parameter and its data type.
CIP Generic
Get Attribute Single
e (Hex.)
93 or 9F (Hex.)
7 (Dec.)
9 (Hex.)
—
0 bytes
Output_Current
My_PowerFlex_755_DriveThe path is the route that the message will follow.
for limitations of PowerFlex 750-Series drives when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object
(4)
(5)
Used to access the DPI Parameter Object in the option module.
This service is used to read a parameter value.
Code for the requested service.
Class ID for the DPI Parameter Object.
Instance number is the same as parameter number.
Attribute number for the Parameter Value attribute.
Leave blank (not applicable).
Number of bytes of service data to be sent in the message.
The tag where the data that is read is stored.
on page 115 (Class code 0x93) or Host DPI Parameter Object on page 129 (Cla ss code
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201277
Chapter 6Using Explicit Messaging
ControlLogix Controller Example Ladder Logic Program to Write a
Single Parameter
A Set Attribute Single message is used to write to a single parameter. This write
message example writes a value to the 32-bit REAL (floating point) parameter
535 - [Accel Time 1] in a PowerFlex 750-Series drive.
Table 6 - Example Controller Tags to Write a Single Parameter
OperandController Tags for Single Write MessageData Type
XICExecute_Single_Write_MessageBOOL
MSGSingle_Write_MessageMESSAGE
Figure 21 - Example Ladder Logic to Write a Single Parameter
78Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
ControlLogix – Formatting a Message to Write a Single Parameter
Figure 22 - Set Attribute Single Message Configuration Dialog Boxes
The following table identifies the data that is required in each box to configure a
message to write a single parameter.
Configuration TabExample ValueDescription
Message Type
Service Type
Service Code
Class
Instance
Attribute
Source Element
Source Length
Destination
Communication TabExample ValueDescription
Path
Tag TabExa mple ValueD escr ipti on
NameSingle_Write_MessageThe name for the message.
(1) The default setting for Service Type is ‘Custom’, enabling entry of a Service Code not available from the Service Type pull-down menu. When choosing a Service Type other than ‘Custom’ from
(2) The instance is the parameter number in the drive (Port 0). For example, to write to parameter 4 of a peripheral in Port 5 of a PowerFlex 755 drive, the instance would be 21504 + 4 = 21508.
(3) Setting the Attribute value to ‘9’ will write the parameter value to the drive’s Nonvolatile Storage (EEPROM) memory, which retains the parameter value even after the drive is power cycled.
(4) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder (for this example, My_PowerFlex_755_Drive).
(5) See Table4 on page 74
(6) In this example, Accel Time 1 is a 32-bit REAL (floating point) parameter requiring the Data Type field to be set to ‘REAL’ when creating the controller tag. To write to a 32-bit integer parameter,
(1)
(1)
(2)
(3)
(4)
the pull-down menu, an appropriate Hex. value is automatically assigned to the Service Code box which is dimmed (unavailable).
See DPI Parameter Object
Important: When set to ‘9’, the EE PROM may quickly exceed its life cycle and cause the drive to malfunction. Setting the Attribute value to ‘A’ will wri te the parameter value to temporary
memory, which deletes the parameter value after the drive is power cycled. When frequent write messages are required, we recommend using the ‘A’ setting.
set the tag Data Type field to ‘DINT’. For a 16-bit parameter, set the Data Type field to ‘INT’. Also, the Source Length field on the Message Configuration dialog box must correspond to the selected
Data Type in bytes (for example, 4 bytes for a REAL or DINT, or 2 bytes for an INT). See the drive documentation to determine the size of the parameter and its data type.
CIP Generic
Set Attribute Single
10 (Hex.)
93 or 9F (Hex.)
535 (Dec.)
9 or A (Hex.)
Accel_Time_1
4 bytes
—
My_PowerFlex_755_DriveThe path is the route that the message will follow.
(5)
(6)
(6)
Used to access the DPI Parameter Object in the option module.
This service is used to write a parameter value.
Code for the requested service.
Class ID for the DPI Parameter Object.
Instance number is the same as parameter number.
Attribute number for the Parameter Value attribute.
Name of the tag for any service data to be sent from the scanner to the option module/drive.
Number of bytes of service data to be sent in the message.
Leave blank (not applicable).
on page 115 (Class code 0x93) or Host DPI Parameter Object on page 129 (Class code 0x9F) to determine the instance number.
for limitations of PowerFlex 750-Series drives when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201279
Chapter 6Using Explicit Messaging
ControlLogix Controller Example Ladder Logic Program to Read
Multiple Parameters
A Scattered Read message is used to read the values of multiple parameters. This
read message example reads the values of these five 32-bit REAL (floating point)
parameters in a PowerFlex 750-Series drive:
• Parameter 001 - [Output Frequency]
• Parameter 007 - [Output Current]
• Parameter 008 - [Output Voltage]
• Parameter 009 - [Output Power]
• Parameter 011 - [DC Bus Volts]
See DPI Parameter Object
Parameter Object on page 129 (Class code 0x9F) for parameter numbering.
Table 7 - Example Controller Tags to Read Multiple Parameters
OperandController Tags for Scattered Read MessageData Type
XICExecute_Scattered_Read_MessageBOOL
MSGScattered_Read_MessageMESSAGE
Figure 23 - Example Ladder Logic to Read Multiple Parameters
on page 115 (Class code 0x93) or Host DPI
80Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
ControlLogix – Formatting a Message to Read Multiple Parameters
The following table identifies the data that is required in each box to configure a
message to read multiple parameters.
Configuration TabExample ValueDescription
Message Type
Service Type
Service Code
Class
Instance
Attribute
Source Element
Source Length
Destination
Communication TabExample ValueDescription
Path
Tag TabExampl e Valu eDesc riptio n
NameScattered_Read_MessageThe name for the message.
(1) The default setting for Service Type is ‘Custom’, enabling entry of a Ser vice Code not available from the Service Type pull-down menu. When choosing a Service Type other than ‘Custom’ from the
(2) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder (for this example, My_PowerFlex_755_Drive).
(3) See Table4 on page 74
(4) In this example, we are reading five 32-bit REAL (floating point) parameters. Each parameter being read requires two contiguous DINT registers. Therefore, a controller tag was created with its
(5) The controller tag for ‘Scattered_Read_Response’ must be the same size as the controller tag for ‘Scattered_Read_Request’ (for th is example, 40 bytes), but ca n be a different data type (for this
(1)
(1)
(2)
pull-down menu, an appropriate Hex. value is automatical ly assigned to the Service Code box which is dimmed (unavailable). When reading 32-bit REAL (floating point) parameters, as in this
example, data conversion using COP (Copy) instructions or UDDTs is required to correctly show the parameter values.
Data Type field set to ‘DINT[10]’. Also, the Source Length field on the Message Configuration dialog box must correspond to the selected Data Type in bytes (for t his example, 40 bytes for a
DINT[10] array). Scattered read messages always assume that every parameter being read is a 32-bit parameter, regardless of its actual size. Maximum message length is 256 bytes which can
read up t o 32 paramet ers, regardle ss of their size. For parameter numbering, see DPI Parameter Object
example, a UDDT to handle conversions to parameter values that are a REAL data type).
My_PowerFlex_755_DriveThe path is the route that the message will follow.
(3)
(4)
(4)
(5)
Used to access the DPI Parameter Object in the option module.
Required for scattered messages.
Code for the requested service.
Class ID for the DPI Parameter Object.
Required for scattered messages.
Required for scattered messages.
Name of the tag for any service data to be sent from scanner to the option module/drive.
Number of bytes of service data to be sent in the message.
The tag where the data that is read is stored.
for limitations of PowerFlex 750-Series drives when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging.
on page 115 (Class code 0x93) or Host DPI Parameter Object on page 129 (Cl ass code 0x9F).
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201281
Chapter 6Using Explicit Messaging
ControlLogix Controller Example Scattered Read Request Data
In this message example, we use the data structure in Figure 25 in the source tag
named Scattered Read Request to read these five 32-bit REAL (floating point)
parameters in a PowerFlex 750-Series drive:
• Parameter 001 - [Output Frequency]
• Parameter 007 - [Output Current]
• Parameter 008 - [Output Voltage]
• Parameter 009 - [Output Power]
• Parameter 011 - [DC Bus Volts]
See DPI Parameter Object
Parameter Object on page 129 (Class code 0x9F) for parameter numbering.
Figure 25 - Example Scattered Read Request Data
ControlLogix Controller Example Scattered Read Response Data
The Scattered Read Request message reads the multiple parameters and returns
their values to the destination tag (Scattered_Read_Response). Figure 26
the parameter values which, in this example, have been converted using a UDDT
for correct presentation. COP (Copy) instructions could have been used for this
purpose instead of a UDDT. If parameters being read are 32-bit integers, do not
COP the data to a REAL tag.
Figure 26 - Example Scattered Read Response Converted Data
on page 115 (Class code 0x93) or Host DPI
shows
In this message example, the parameters have the following values:
PowerFlex 750-Series Drive ParameterRead Value
1 - [Output Frequency]60.205975 Hz
7 - [Output Current]12.570678 Amp
8 - [Output Voltage]418.34348V AC
9 - [Output Power]12.3584 kW
11 - [DC Bus Volts]566.5277V DC
82Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
IMPORTANT
ControlLogix Controller Example Ladder Logic Program to Write
Multiple Parameters
A Scattered Write message is used to write to multiple parameters. This write
message example writes the following values to these five 32-bit REAL (floating
point) parameters in a PowerFlex 750-Series drive:
PowerFlex 750-Series Drive ParameterWrite Value
536 - [Accel Time 2]11.1 Sec
538 - [Decel Time 2]22.2 Sec
575 - [Preset Speed 5]33.3 Hz
576 - [Preset Speed 6]44.4 Hz
577 - [Preset Speed 7]55.5 Hz
See DPI Parameter Object
Parameter Object on page 129 (Class code 0x9F) for parameter numbering.
Table 8 - Example Controller Tags to Write Multiple Parameters
OperandController Tags for Scattered Write MessageData Type
XICExecute_Scattered_Write_MessageBOOL
MSGScattered_Write_MessageMESSAGE
Figure 27 - Example Ladder Logic to Write Multiple Parameters
If the explicit message scattered write must be written continuously, then use
a separate explicit message single write for each parameter using DPI
Parameter Object Class code 0x93 and attribute A (see page 79
writes to RAM—not NVS (EEPROM) memory. This example scattered write
message using attribute 0 writes to NVS. Over time, continuous writes will
exceed the EEPROM life cycle and cause the drive to malfunction.
on page 115 (Class code 0x93) or Host DPI
). Attribute A
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201283
Chapter 6Using Explicit Messaging
ControlLogix – Formatting a Message to Write Multiple Parameters
The following table identifies the data that is required in each box to configure a
message to write multiple parameters.
Configuration TabExample ValueDescription
Message Type
Service Type
Service Code
Class
Instance
(2)
Attribute
Source Element
Source Length
Destination
Communication TabExample ValueDescription
(3)
Path
Tag TabExample ValueDescription
NameScattered_Write_MessageThe name for the message.
(1) The default setting for Service Type is ‘Custom’, enabling entry of a Service Code not available from the Service Type pull-down menu. When choosing a Service Type other than ‘Custom’ from
the pull-down menu, an appropriate Hex. value is automatically assigned to the Ser vice Code box which is dimmed (unavailable). When writing to 32-bit REAL (floating point) parameters, as
in this example, data conversion using COP (Copy) instructions or UDDTs is required to correctly write the parameter values.
(2) Scattered writes always write parameter values to the drive’s Nonvolatile Storage (EEPROM) memory, which retains these values even after the drive is power c ycled. Important: Be very
cautious as the EEPROM may quickly exceed its life cycle and cause the drive to malfunc tion.
(3) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder (for this example, My_PowerFlex_755_Drive).
(4) See Table 4 on page 74
(5) In this exampl e, we are writing to five 32-bi t REAL (floating point) parameters. Each parameter being written to requires two contiguous DINT registers. Therefore, a controller tag was created
with its Data Type field set to the name of the UDDT of five interleaved DINTs and REALs. Also, the Source Length field on the Message Configuration dialog box must correspond to the selected
Data Type in bytes (for this example, 40 bytes for an array of five scattered REAL structures). Scattered write messages always assume that every parameter being written to is a 32-bit
parameter, regardless of its actual size. Maximum message length is 256 bytes which can write up to 32 parameters, regardless of their size. For parameter numbering, see DPI Parameter
Object on page 115 (Class code 0x93) or Host DPI Parameter Object on page 129 (Class code 0x9F).
(6) The controller tag for ‘Scattered_Write_Response’ must be the same size as the controller tag for ‘Scattered_Write_Request’ (for this example, 40 bytes). An array of DINTs is suggested to be
able to read any error codes that are returned.
(1)
(1)
CIP Generic
Custom
4e (Hex.)
93 or 9F (Hex.)
0 (Dec.)
0 (Hex.)
Scattered_Write_Request
40 bytes
Scattered_Write_Response
My_PowerFlex_755_DriveThe path is the route that the message will follow.
(4)
(5)
(5)
(6)
Used to access the DPI Parameter Object in the option module.
Required for scattered messages.
Code for the requested service.
Class ID for the DPI Parameter Object.
Required for scattered messages.
Required for scattered messages.
Name of the tag for any service data to be sent from scanner to the option module/drive.
Number of bytes of service data to be sent in the message.
The tag where the data that is read is stored.
for limitations of PowerFlex 750-Series drives when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging.
84Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
ControlLogix Controller Example Scattered Write Request Data
In this message example, we use the data structure in Figure 29 in the source tag
(Scattered_Write_Request) to write new values to these 32-bit REAL (floating
point) parameters:
PowerFlex 750-Series Drive ParameterWrite Value
536 - [Accel Time 2]11.1 Sec
538 - [Decel Time 2]22.2 Sec
575 - [Preset Speed 5]33.3 Hz
576 - [Preset Speed 6]44.4 Hz
577 - [Preset Speed 7]55.5 Hz
See DPI Parameter Object
Parameter Object on page 129 (Class code 0x9F) for parameter numbering.
Figure 29
converted using a UDDT to correctly write their values. COP (Copy)
instructions could have been used for this purpose instead of a UDDT. If the
parameters being written to are 32-bit integers, do not COP the data to a REAL
tag.
Figure 29 - Example Scattered Write Request Converted Data
ControlLogix Controller Example Scattered Write Response Data
The results of the message appear in the destination tag named
Scattered_Write_Response (Figure 30
shows the parameter values which, in this example, have been
on page 115 (Class code 0x93) or Host DPI
). Values of ‘0’ indicate no errors occurred.
Figure 30 - Example Scattered Write Response Data
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201285
Chapter 6Using Explicit Messaging
ControlLogix Controller – Explanation of Request and Response Data
for Read/Write Multiple Messaging
The data structures in Ta b l e 9 and Ta b l e 1 0 use 32-bit words and can
accommodate up to 32 parameters in a single message. In the Response Message,
a parameter number with Bit 15 set indicates that the associated parameter value
field contains an error code (parameter number in response data will be negative).
The PowerFlex 750-Series AC Drives Programming Manual, publication
750-PM001
Read of REAL data type parameters, the DINT parameter value in the Response
(Destination Data) array will need to be COP to a REAL tag.
Table 9 - Data Structures for Scattered Read Messages
DINT 0 Parameter NumberDINT 0 Parameter Number
, lists the data type for each parameter. When performing a Scattered
Request (Source Data)Response (Destination Data)
1Pad1Parameter Value
2 Parameter Number2 Parameter Number
3Pad3Parameter Value
4 Parameter Number4 Parameter Number
5Pad5Parameter Value
6 Parameter Number6 Parameter Number
7Pad7Parameter Value
8 Parameter Number8 Parameter Number
9Pad9Parameter Value
10 Parameter Number10 Parameter Number
11 Pad11 Parameter Value
12 Parameter Number12 Parameter Number
13 Pad13 Parameter Value
14 Parameter Number14 Parameter Number
15 Pad15 Parameter Value
16 Parameter Number16 Parameter Number
17 Pad17 Parameter Value
18 Parameter Number18 Parameter Number
19 Pad19 Parameter Value
20 Parameter Number20 Parameter Number
21 Pad21 Parameter Value
22 Parameter Number22 Parameter Number
23 Pad23 Parameter Value
24 Parameter Number24 Parameter Number
25 Pad25 Parameter Value
26 Parameter Number26 Parameter Number
27 Pad27 Parameter Value
28 Parameter Number28 Parameter Number
29 Pad29 Parameter Value
30 Parameter Number30 Parameter Number
31 Pad31 Parameter Value
32 Parameter Number32 Parameter Number
33 Pad33 Parameter Value
34 Parameter Number34 Parameter Number
35 Pad35 Parameter Value
...
...
62 Parameter Number62 Parameter Number
63 Pad63 Parameter Value
86Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Using Explicit MessagingChapter 6
When performing a Scattered Write to REAL data type parameters, the REAL
parameter value will need to be COP to the DINT parameter value tag in the
Request (Source Data) array.
Table 10 - Data Structures for Scattered Write Messages
Request (Source Data)Response (Destination Data)
DINT 0 Parameter NumberDINT 0 Parameter Number
1Parameter Value1Pad
2 Parameter Number2 Parameter Number
3Parameter Value3Pad
4 Parameter Number4 Parameter Number
5Parameter Value5Pad
6 Parameter Number6 Parameter Number
7Parameter Value7Pad
8 Parameter Number8 Parameter Number
9Parameter Value9Pad
10 Parameter Number10 Parameter Number
11 Parameter Value11 Pad
12 Parameter Number12 Parameter Number
13 Parameter Value13 Pad
14 Parameter Number14 Parameter Number
15 Parameter Value15 Pad
16 Parameter Number16 Parameter Number
17 Parameter Value17 Pad
18 Parameter Number18 Parameter Number
19 Parameter Value19 Pad
20 Parameter Number20 Parameter Number
21 Parameter Value21 Pad
22 Parameter Number22 Parameter Number
23 Parameter Value23 Pad
24 Parameter Number24 Parameter Number
25 Parameter Value25 Pad
26 Parameter Number26 Parameter Number
27 Parameter Value27 Pad
28 Parameter Number28 Parameter Number
29 Parameter Value29 Pad
30 Parameter Number30 Parameter Number
31 Parameter Value31 Pad
32 Parameter Number32 Parameter Number
33 Parameter Value33 Pad
34 Parameter Number34 Parameter Number
35 Parameter Value35 Pad
...
...
62 Parameter Number62 Parameter Number
63 Parameter Value63 Pad
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201287
Chapter 6Using Explicit Messaging
Notes:
88Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 7
➊
➋
➌
➌
0
5
4
9
3
8
2
7
1
6
0
5
4
9
3
8
2
7
1
6
Troubleshooting
This chapter provides information for diagnosing and troubleshooting potential
problems with the option module and network.
Top icPag e
Understanding the Status Indicators
PORT Status Indicator90
MOD Status Indicator90
NET A and NET B Status Indicators91
Viewing Option Module Diagnostic Items92
Viewing and Clearing Events94
89
Understanding the Status
Indicators
The option module has four status indicators. They can be viewed with the drive
cover removed.
ItemStatus IndicatorDescriptionPage
➊
➋
➌
➍
PORTDPI Connection Status90
MODOption Module Status90
NET AControlNet Channel A Status91
NET BControlNet Channel B Status91
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201289
Chapter 7Troubleshooting
PORT Status Indicator
StatusCauseCorrective Action
OffThe option module is not powered or is not properly connected to
Flashing RedThe option module is not communicating with the drive via DPI.• Verify that the option module is properly inserted in the drive port.
Steady RedThe drive has refused an I/O connection from the option module.
Flashing OrangeThe option module is not compatible with the drive’s firmware.Update the drive with the latest firmware revision.
Steady OrangeThe option module is not compatible with the drive.Install the option module into a compatible product of the same brand
Flashing GreenThe option module is establishing an I/O connection to the drive. No action required. Normal behavior if no I/O is enabled.
Steady GreenThe option module is properly connected and is communicating
This red/green bicolor LED indicates the status of the option module’s
connection to the drive as shown in the table below.
the drive.
Another DPI peripheral is using the same DPI port as the option
module.
with the drive.
• Securely connect and ground the option module to the drive by
fully inserting it into the drive port and tightening its two captive
screws to the recommended torque.
• Apply power to the drive.
• Cycle power to the drive.
Important: Cycle power to the drive after making any of the following
corrections:
• Securely connect and ground the option module to the drive by
fully inserting it into the drive port and tightening its two captive
screws to the recommended torque.
• Verify that the drive supports the Comm Driver.
(an Allen-Bradley PowerFlex 750-Series drive).
No action required.
MOD Status Indicator
StatusCauseCorrective Action
OffThe option module is not powered or is not properly connected to
Flashing RedThe option module has failed the firmware test.
Steady RedThe option module has failed the hardware test.• Cycle power to the drive.
Flashing GreenThe option module is operating normally, but is not transferring
Steady GreenThe option module is operating normally and is transferring I/O
This red/green bicolor LED indicates the status of the option module as shown
in the table below.
the drive.
The option module firmware is being updated.
I/O data to a controller.
data to a controller.
• Securely connect and ground the option module to the drive by
fully inserting it into the drive port and tightening its two captive
screws to the recommended torque.
• Apply power to the drive.
• Clear faults in the option module.
• Cycle power to the drive.
• If cycling power does not correct the problem, the option module
parameter settings may have been corrupted. Reset defaults and
reconfigure the option module.
• If resetting defaults does not correct the problem, update the
option module with the latest firmware revision.
• Replace the option module.
• Place the scanner in RUN mode.
• Program the controller to recognize and transmit I/O to the option
module.
• Configure the option module for the program in the controller.
• Normal behavior if no I/O is being transferred.
No action required.
90Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
TroubleshootingChapter 7
NET A and NET B Status
Indicators
StatusCauseCorrective Actions
Both indicators OffA reset occurred or the option module is not powered.Apply power to the drive.
Both indicators Steady
Red
Indicators Alternately
Flashing Red/Green
Indicators Alternately
Flashing Red/Off
These red/green bicolor LEDs indicate the status for the ControlNet Channel A
and Channel B network connections. Depending on the state of these LEDs,
they should be interpreted together or independently.
Indicators Interpreted Together
When interpreted together, the NET A and NET B LEDs indicate the network
status as shown in the table below.
A link interface failed.• Check network coaxial media for broken cables, loose connectors,
missing terminators, and so forth.
• Cycle power to the drive, or reset the option module. If the problem
persists, contact Rockwell Technical Support.
The option module is in self-test mode.No action required. The option module will exit this mode after the
self-test is completed.
There is a bad node configuration.• Verify that all node addresses are unique.
• Check the option module’s configuration.
• Check network coaxial media for broken cables, loose connectors,
missing terminators, and so forth.
• Cycle power to the drive, or reset the option module.
Indicators Interpreted Independently
When interpreted independently, the NET A and NET B LEDs respectively
indicate the network status as shown in the table below.
StatusCauseCorrective Actions
One channel indicator is
Steady Off
One channel indicator is
Flashing Red/Green
One channel indicator is
Flashing Red/Off
One channel indicator is
Flashing Green/Off
One channel indicator is
Steady Green
That channel is disabled or not supported.Program the network for redundant media, if required.
There is an invalid link configuration for that channel.• Cycle power to the drive, or reset the option module.
• Reset the controller.
• If the problem persists, contact Rockwell Technical Support.
The channel is not receiving network activity.Check network coaxial media for broken cables, loose connectors,
A temporary channel error has occurred, or the
channel is in ‘listen-only’ mode.
Normal operation for that channel.No action required.
missing terminators, and so forth.
Verify that the controller is present on the network and working.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201291
Chapter 7Troubleshooting
Viewing Option Module
Diagnostic Items
Table 11 - Option Module Diagnostic Items
No.NameDescription
1Common Logic CmdThe present value of the Common Logic Command being transmitted to the drive by this option module.
2Prod Logic CmdThe present value of the Product Logic Command being transmitted to the drive by this option module.
3ReferenceThe present value of the Reference being transmitted to the drive by this option module.
4Common Logic StsThe present value of the Common Logic Status being received from the drive by this option module.
5Prod Logic StsThe present value of the Product Logic Status being received from the drive by this option module.
6FeedbackThe present value of the Feedback being received from the drive by this option module.
7Input SizeThe size of the input image in bytes transferred from the network to the drive.
8Output SizeThe size of the output image in bytes transferred from the drive to the network.
9DL Fr Net AvailThe number of Host DL From Net xx Datalinks currently available to the option module.
10DL To Net AvailThe number of Host DL To Net xx Datalinks currently available to the option module
11DL Fr Net 01 ValThe present value of respective Host DL From Net xx parameter being transmitted to the drive by this
12DL Fr Net 02 Val
13DL Fr Net 03 Val
14DL Fr Net 04 Val
15DL Fr Net 05 Val
16DL Fr Net 06 Val
17DL Fr Net 07 Val
18DL Fr Net 08 Val
19DL Fr Net 09 Val
20DL Fr Net 10 Val
21DL Fr Net 11 Val
22DL Fr Net 12 Val
23DL Fr Net 13 Val
24DL Fr Net 14 Val
25DL Fr Net 15 Val
26DL Fr Net 16 Val
If you encounter unexpected communication problems, the option module’s
diagnostic items may help you or Rockwell Automation personnel troubleshoot
the problem. Option module diagnostic items can be viewed with any of these
drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 6.01 or later
• DriveExecutive software, version 5.01 or later
For details on viewing diagnostic items using the HIM, see the PowerFlex 20HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication
20HIM-UM001
option module. (If not using a Datalink, its respective value should be zero.)
.
92Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
27DL To Net 01 ValThe present value of respective Host DL To Net xx parameter being received from the drive by this option
28DL To Net 02 Val
29DL To Net 03 Val
30DL To Net 04 Val
31DL To Net 05 Val
32DL To Net 06 Val
33DL To Net 07 Val
34DL To Net 08 Val
35DL To Net 09 Val
36DL To Net 10 Val
37DL To Net 11 Val
38DL To Net 12 Val
39DL To Net 13 Val
40DL To Net 14 Val
41DL To Net 15 Val
42DL To Net 16 Val
43DPI Rx ErrsThe present value of the DPI Receive error counter.
44DPI Rx Errs MaxThe maximum value (since reset) of the DPI Receive Error counter.
45DPI Tx ErrsThe present value of the DPI Transmit error counter.
46DPI Tx Errs MaxThe maximum value (since reset) of the DPI Transmit Error counter.
47CN Rx PacketsA count of the number of network packets received by the option module.
48CN Rx UnderflowsA count of the number of network receive underflow errors.
49CN Rx OverflowsA count of the number of network receive overflow errors.
50CN Rx Bad FramesA count of the number of network receive bad frame errors.
51CN Tx PacketsA count of the number of network packets transmitted by the option module.
52CN Tx UnderflowsA count of the number of network transmit underflow errors.
53CN Tx OverflowsA count of the number of network transmit overflow errors.
54CN Tx OutOfStepsA count of the number of network transmit out-of-step errors.
55CN Tx BlockagesA count of the number of network transmit blockage errors.
56Boot Flash CountNumber of times the boot firmware in the option module has been updated.
57App Flash CountNumber of times the application firmware in the option module has been updated.
58Net Addr SwThe present value of the node address switches.
module. (If not using a Datalink, its respective value should be zero.)
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201293
Chapter 7Troubleshooting
Viewing and Clearing Events
The option module has an event queue to record significant events that occur in
the operation of the module. When such an event occurs, an entry consisting of
the event’s numeric code and a timestamp is put into the event queue. You can
view the event queue with any of these drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 6.01 or later
• DriveExecutive software, version 5.01 or later
• Other clients using the DPI Fault object
For details on viewing and clearing events using the HIM, see the PowerFlex 20HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication
20HIM-UM001
The event queue can contain up to 32 entries, which are stored in an EEPROM
chip—making the event queue nonvolatile. Eventually the event queue will
become full, since its contents are retained through option module power cycles
and resets. At that point, a new entry replaces the oldest entry. Only an event
queue clear operation or the corruption of the EEPROM group containing the
event queue will clear the event queue contents. In the latter case, the option
module will not generate a fault to indicate that the event queue was corrupted.
.
Table 12 - Option Module Events
CodeEvent TextDescription
1No EventText displayed in an empty event queue entry.
2Device Power UpPower was applied to the option module.
3Device ResetThe option module was reset.
4EEPROM CRC ErrorThe EEPROM checksum/CRC is incorrect, which limits option module functionality. Default parameter values must be loaded to
5App UpdatedThe option module application firmware was updated.
6Boot UpdatedThe option module boot firmware was updated.
7Watchdog TimeoutThe software watchdog detected a failure and reset the option module.
8DPI Bus OffA bus-off condition was detected on DPI. This event may be caused by noise.
9DPI Ping TimeoutA ping message was not received on DPI within the specified time.
10DPI Port InvalidThe option module was not connected to a valid port on a DPI product.
11DPI Port ChangedThe DPI port changed after start up.
12DPI Host ResetThe drive sent a reset event message.
Resetting the option module to defaults has no effect on the event queue, other
than to log a Code 58 ‘Module Defaulted’ event.
Many events in the event queue occur under normal operation. If you encounter
unexpected communications problems, the events may help you or Allen-Bradley
personnel troubleshoot the problem. The following events may appear in the
event queue.
Option Module Events
clear this condition.
DPI Events
94Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
TroubleshootingChapter 7
Table 12 - Option Module Events (Continued)
CodeEvent TextDescription
13DPI Baud 125kbpsThe option module detected that the drive was communicating at 125 Kbps.
14DPI Baud 500kbpsThe option module detected that the drive was communicating at 500 Kbps.
15DPI Host InvalidThe option module was connected to an incompatible product.
16DPI Dup PortAnother peripheral with the same port number is already in use.
17DPI Type 0 LogonThe option module has logged in for Type 0 control.
18DPI Type 0 TimeThe option module has not received a Type 0 status message within the specified time.
19DPI DL LogonThe option module has logged into a Datalink.
20DPI DL ErrorThe drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.
21DPI DL TimeThe option module has not received a Datalink message within the specified time.
22DPI Ctrl DisableThe option module has sent a ‘Soft Control Disable’ command to the drive.
23DPI Ctrl EnableThe option module has sent a ‘Soft Control Enable’ command to the drive.
24DPI Msg TimeoutA Client-Server message sent by the option module was not completed within 1 second.
25DPI Manual ResetThe option module was reset by changing its Reset Module parameter.
SI Events
26SI OnlineThe option module has logged into the Serial Interface Communication.
27SI Logon ErrorThe option module failed to log into the Serial Interface.
28SI Comm FaultThe Serial Interface Communication has faulted.
29Net Link UpA network link was available for the option module.
30Net Link DownThe network link was removed from the option module.
31Net Dup AddressThe option module uses the same address as another device on the network.
32Net Comm FaultThe option module detected a communication fault on the network.
33Net Sent ResetThe option module received a reset from the network.
34Net IO CloseAn I/O connection from the network to the option module was closed.
35Net Idle FaultThe option module received ‘idle’ packets from the network.
36Net IO OpenAn I/O connection from the network to the option module has been opened.
37Net IO TimeoutAn I/O connection from the network to the option module has timed out.
38Net IO Size ErrThe option module received an incorrectly sized I/O packet.
39PCCC IO CloseThe device sending PCCC Control messa ges to the option modul e has set the PCCC Control Timeout to zero.
40PCCC IO OpenThe option module has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a non-zero value).
41PCCC IO TimeoutThe option module has not received a PCCC Control message for longer than the PCCC Control Timeout.
42Msg Ctrl OpenThe timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing control messages
43Msg Ctrl CloseThe timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing control messages to
44Msg Ctrl TimeoutThe timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.
45-57Reser ved—
58Module DefaultedThe option module has been set to defaults.
Network Events
to be sent to the option module.
be sent to the option module.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201295
Chapter 7Troubleshooting
Notes:
96Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Specifications
This appendix presents the specifications for the option module.
Top icPa ge
Communications97
Electrical97
Mechanical97
Environmental98
Regulatory Compliance98
Appendix A
Communications
Electrical
Network
Protocol
Data Rate
Media
Connectio n Limits
Requested Packet Interval (RPI)
Packe t Rate
Drive
Protocol
Data Rates
Consu mption
Drive
Network
Control Net
5 Mbps (fixed)
Coax with BNC connector
16 simultaneous CIP messaging connections
32 simultaneous unconnected messages
Unlimited input-only I/O connections
One of the following connection types:
• 1 exclusive-owner I/O connection
• Up to 3 redundant-owner I/O connections
• 1 listen-only I/O connection
5 ms minimum
Up to 400 total I/O packets per second (200 in and 200 out)
DPI
500 kbps
250 mA at 14 VDC supplied by the host drive
None
Mechanical
Dimensions
Height
Length
Widt h
Weight62 g (2.1 oz.)
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201297
68 mm (2.7 inches)
150 mm (5.9 inches)
26 mm (1.0 inches)
Appendix ASpecifications
Environmental
Regulatory Compliance
Temperature
Operating
Storage
Relative Humidity5…95% non-condensing
Atmosph ereImportant: The option module must not be installed in an area where the
CertificationSpecification
ULUL508C
cULCAN / CSA C22.2 No. 14-05
CEEN61800-3
CTickEN61800-3
NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in which case
supplementary mitigation measures may be required.
-10…50 °C (14…122 °F)
-40…85 °C (-40…185 °F)
ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the
option module is not going to be installed for a period of time, it must be
stored in an area where it will not be exposed to a corrosive atmosphere.
98Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Appendix B
Option Module Parameters
This appendix provides information about the option module parameters.
Top icPa ge
Parameter Types99
About Parameter Numbers100
How Parameters Are Organized100
Device Param eters100
Host Parameters101
Parameter Types
The Option Module has two types of parameters:
• Device parameters are used to configure the option module to operate on
the network.
• Host parameters are used to configure the option module Datalink transfer
and various fault actions with the drive.
Yo u can vi ew op ti on m od u le Device parameters and Host parameters with any of
the following drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM—use the or
key to scroll to the drive port in which the module resides, press the
(Folders) key, and use the or key to scroll to the DEV
PARA M or H OST PAR AM fo lder.
• Connected Components Workbench software—click the tab for the
option module at the bottom of the window, click the Parameters icon in
the tool bar, and click the Device or Host Parameters tab.
• DriveExplorer software—find the option module in the treeview and open
its Parameters folder.
• DriveExecutive software—find the option module in the treeview, expand
the module in the tree, and open its Parameters folder.
Rockwell Automation Publication 750COM-UM003B-EN-P - November 201299
Appendix BOption Module Parameters
About Parameter Numbers
How Parameters Are
Organized
Device Parameters
Each parameter set is independently and consecutively numbered.
Configuration ToolNumbering Scheme
• HIM
• Connected Components Workbench software
• DriveExplorer software
• DriveExecutive software
• Explicit MessagingSee Chapter 6
The Device Parameters and Host Parameters are separately displayed in a
Numbered List view order.
Parameter
No. Name and DescriptionDetails
01[Port Number]
Displays the drive port into which the option module is installed.
Typically, this will be Por t 4, 5, or 6.
02[DLs From Net Act]
Displays the number of controller-to-drive Datalinks that the
drive is using based on the I/O connection opened by the
controller.
03[DLs To Net Act]
Displays the number of drive-to-controller Datalinks that the
controller is using based on the I/O connection opened by the
controller.
04[Net Addr Src]
Displays the source from which the option module node address
is taken. This will be either the Node Address switches (see
Figure 1 on page 18), or the value of Device Parameter 05- [Net
Addr Cfg].
05[Net Addr Cfg]
Sets the network node address for the option module when
DeviceParameter 04 - [Net Addr Src] is set to ‘1’ (Parameters).
06[Net Addr Act]
Displays the actual network node address used by the option
module.
The Device parameters and Host parameters begin with parameter
01. For example, Device Parameter 01 - [Port Number] and Host Parameter 01 - [Net to Drv DL 01] are parameter 01 as
indicated by this manual.