Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual contains new and updated information.
Summary of Changes
New and Updated
Information
This table contains the changes made to this revision.
TopicPage
In Chapter 4, Table 3 in the first row AI0, corrected the drive parameter number from ‘60’ to
‘260’.
In Appendix D in the Segmentation Capability section, added a new checked box for
‘Segmented response accepted’. This new functionality is provided with firmware revision
1.003.
40
74
Rockwell Automation Publication 750COM-UM005B-EN-P - June 20143
Summary of Changes
Notes:
4Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Rockwell Automation Publication 750COM-UM005B-EN-P - June 20147
Table of Contents
8Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Preface
This manual provides information about the 20-750-BNETIP BACnet/IP
option module for network communication and how to use the module with
PowerFlex® 750-Series drives.
Conventions Used in This
Manual
Rockwell Automation
Support
The following conventions are used throughout this manual:
• Parameter names are shown in the format Device
Parameter xx - [*]. The xx represents the parameter number. The *
represents the parameter name—for example Device
Number]
• The firmware revision number (FRN) is displayed as FRN X.xxx, where
‘X’ is the major revision number and ‘xxx’ is the minor revision number.
• The dialog box images in this manual resulted from using DriveExplorer
Full software, version 6.02.99. Different versions of the software may have
dialog boxes that vary in appearance, and differences in procedures.
Rockwell Automation offers support services worldwide, with over 75 sales and
support offices, over 500 authorized distributors, and over 250 authorized
systems integrators located through the United States alone. In addition,
Rockwell Automation representatives are in every major country in the world.
Local Product Support
.
Parameter xx - [*] or Host
Parameter 01 - [Port
Contact your local Rockwell Automation representative for the following:
• Sales and order support
• Product technical training
• Wa rr an ty su pp or t
• Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 5,
Troubleshooting, first. If you still have problems, then access the Allen-Bradley
Technical Support website at http://www.ab.com/support/abdrives
Rockwell Automation.
Rockwell Automation Publication 750COM-UM005B-EN-P - June 20149
or contact
Preface
Additional Resources
ResourceDescription
Network Communication Option Module Installation Instructions, publication
750COM-IN002
TIA/EIA Standard PDF for CAT5e Ethernet cable at http://www.nag.ru/goodies/tia/TIA-
EIA-568-B.1.pdf and Allen-Bradley product website for Robotic cable at http://
ab.rockwellautomation.com/
DriveExecutive website http://www.ab.com/drives/drivetools, and online help
PowerFlex 750-Series AC Drives Installation Instructions, publication 750-IN001Information on installing, programming, and technical data of
PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001
PowerFlex 750-Series AC Drives Technical Data, publication 750-TD001
PowerFlex 20-HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication
20HIM-UM001
(1) The online help is installed with the software.
(1)
, and online help
(1)
Information on the installation of PowerFlex 750-Series Network
Communication modules.
Information about CAT5e Ethernet cable and Robotic cable.
Information on the Connected Components Workbench™
software tool—and includes a link for free software download.
(1)
Information on using the DriveExplorer™ software tool.
Information on using the DriveExecutive™ software tool.
®
PowerFlex
Information on the installation and use of PowerFlex 20-HIM-A6
or 20-HIM-C6S HIMs.
750-Series drives.
You can view or download publications at http://
www.rockwellautomation.com/literature. To order paper copies of technical
documentation, contact your local Rockwell Automation distributor or sales
representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations
For information, such as firmware updates or answers to drive-related questions,
go to the Drives Service & Support website at http://www.ab.com/support/
abdrives and click the Downloads or Knowledgebase link.
.
10Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter
Item PartDescription
➊Status IndicatorsThree status indicators that
indicate the status of the option
module and network
communication. See Chapter 5
,
Troubleshooting.
➋IP Address Selection
Jumper
Sets the source used for the
network address. See Setting
the IP Address Selection
Jumper on page 18.
➌Ethernet ConnectorRJ45 connector for the Ethernet
network cable.
Getting Started
The 20-750-BNETIP option module is intended for installation into a
PowerFlex 750-Series drive and is used for network communication.
TopicPage
Components
Features12
Understanding Parameter Types12
Compatible Products
Required Equipment13
Safety Precautions15
Quick Start
11
13
16
1
Components
➊
➋
➌
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201411
Chapter 1 Getting Started
Features
The features of the option module include the following:
• Captive screws to secure and ground the option module to the drive.
• An IP Address Selection Jumper to set the source of the network address
for the option module before applying power to the drive. The network
address can come from the default network address of the option module,
a DHCP server, or the option module parameter values.
• Compatibility with the following configuration tools to configure the
option module and host drive:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM (Human Interface
Module) on the drive, if available
– Connected Components Workbench software, version 1.02 or later
– DriveExplorer software, version 6.01 or later
– DriveExecutive software, version 5.01or later
– Third party BACnet controlling and monitoring tools
• Status indicators that report the status of the option module and network
communication. They are visible when the drive cover is removed.
• Read/write access for parameters, where parameter values can be
configured and monitored over the network.
Understanding Parameter
Types
• User-defined fault actions to determine how the option module and its
connected host drive respond to the following:
– I/O messaging communication disruptions (Comm Flt Action)
– Controllers in Idle mode (Idle Flt Action)
• Web pages, viewed by using a web browser, that show information about
the option module, its host drive, and DPI devices connected to the drive.
• Configurable e-mail messaging to desired addresses when selected drive
faults occur and/or are cleared, and/or when the option module takes a
communication or idle fault action.
The option module has two types of parameters:
• Device parameters are used to configure the option module to operate on
the network.
• Host parameters are used to configure the option module’s fault actions
with the drive.
12Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Getting Started Chapter 1
You ca n v ie w o pti on mo du le Device parameters and Host parameters with any of
the following drive configuration tools:
• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM—use the or
key to scroll to the drive port in which the module resides, press the
(Folders) key, and use the or key to scroll to the DEV PARAM
or HOST PARAM folder.
• Connected Components Workbench software—click the tab for the
option module at the bottom of the window, click the Parameters icon in
the tool bar, and click the Device or Host Parameters tab.
• DriveExplorer software—find the option module in the treeview and open
its Parameters folder.
• DriveExecutive software—find the option module in the treeview, expand
the module in the tree, and open its Parameters folder.
Compatible Products
Required Equipment
At the time of publication, the option module is compatible with the following
products:
• PowerFlex 753 drives (all firmware revisions)
• PowerFlex 755 drives (all firmware revisions)
Some of the equipment that is required for use with the option module is shipped
with the module, but some you must supply yourself.
Equipment Shipped with the Option Module
When you unpack the option module, verify that the package includes the
following:
❑ One 20-750-BNETIP BACnet/IP Option Module
❑ One Network Communication Option Module Installation Instructions,
publication 750COM-IN002
User-Supplied Equipment
To install and configure the option module, you must supply the following:
❑ A small screwdriver
Ethernet Cable
❑
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201413
Chapter 1 Getting Started
❑ Drive and option module configuration tool, such as the following:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
– Connected Components Workbench software, version 1.02 or later
Connected Components Workbench is the recommended stand-alone
software tool for use with PowerFlex drives. You can obtain a free copy
by:
• Internet download at http://www.ab.com/support/abdrives/
webupdate/software.html
• Requesting a DVD at http://www.ab.com/onecontact/
controllers/micro800/
Your local distributor may also have copies of the DVD available.
Connected Components Workbench software cannot be used to
configure SCANport-based drives or Bulletin 160 drives.
– DriveExplorer software, version 6.01 or later
This software tool has been discontinued and is now available as
freeware at http://www.ab.com/support/abdrives/webupdate/
software.html. There are no plans to provide future updates to this tool
and the download is being provided ‘as-is’ for users that lost their
DriveExplorer CD, or need to configure legacy products not supported
by Connected Components Workbench software.
– DriveExecutive software, version 5.01 or later
A Lite version of DriveExecutive software ships with RSLogix 5000,
RSNetworx MD, FactoryTalk AssetCentre, and IntelliCENTER
software. All other versions are purchasable items:
• 9303-4DTE01ENE Drive Executive software
• 9303-4DTS01ENE DriveTools SP Suite (includes
DriveExecutive and DriveObserver software)
• 9303-4DTE2S01ENE DriveExecutive software upgrade to
DriveTools SP Suite (adds DriveObserver software)
DriveExecutive software updates (patches, and so forth) can be obtained
at http://www.ab.com/support/abdrives/webupdate/software.html
is highly recommended that you periodically check for and install the
latest update.
– Third party network configuration software such as ORCAview
❑ A computer connection to the BACnet network
. It
14Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Getting Started Chapter 1
Safety Precautions
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may
contain high voltages that can cause injury or death. Remove all power
from the PowerFlex drive, and then verify power has been discharged
before installing or removing an option module.
ATTENTION: Risk of injury or equipment damage exists. Only personnel
familiar with drive and power products and the associated machinery
should plan or implement the installation, startup, configuration, and
subsequent maintenance of the drive using the option module. Failure to
comply can result in injury and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The option module
contains electrostatic discharge (ESD) sensitive parts that can be damaged
if you do not follow ESD control procedures. Static control precautions are
required when handling the option module. If you are unfamiliar with static
control procedures, see Guarding Against Electrostatic Damage,
publication 8000-4.5.2
ATTENTION: Risk of injury or equipment damage exists. If the option
module is transmitting control I/O to the drive, the drive can fault when you
reset the option module. Determine how your drive will respond before
resetting the module.
ATTENTION: Risk of injury or equipment damage exists. Host
Parameters 33 - [Comm Flt Action] and 34 - [Idle Flt Action] let you
determine the action of the option module and connected drive if I/O
communication is disrupted, the controller is idle, or messaging for drive
control is disrupted. By default, these parameters fault the drive. You can
configure these parameters so that the drive continues to run, however,
precautions must be taken to verify that the settings of these parameters
do not create a risk of injury or equipment damage. When commissioning
the drive, verify that your system responds correctly to various situations
(for example, a disconnected cable or a controller in idle state).
.
ATTENTION: Risk of injury or equipment damage exists. When a system is
configured for the first time, there can be unintended or incorrect machine
motion. Disconnect the motor from the machine or process during initial
system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in
this publication are intended solely for purposes of example. There are
many variables and requirements with any application. Rockwell
Automation does not assume responsibility or liability (to include
intellectual property liability) for actual use of the examples shown in this
publication.
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201415
Chapter 1 Getting Started
Quick Start
This section is provided to help experienced users quickly start using the option
module. If you are unsure how to complete a step, see the referenced chapter.
Step ActionSee
1Review the safety precautions for the option module.Throughout this manual
2Verify that the PowerFlex drive is properly installed.PowerFlex 750-Series AC Drive
Installation Instructions,
publication 750-IN001
3Install the option module.
a. Verify that the PowerFlex drive is not powered.
b. Set the source for the option module network
address with the IP Address Selection Jumper
(Figure 1 on page 18
c. Insert the option module in drive Port 4, 5, or 6.
d. Use the captive screws to secure and ground the
option module to the drive.
e. Connect the option module to the network with an
Ethernet cable (and RJ45 connector).
4Apply power to the option module.
a. Verify that the option module is installed correctly.
The option module receives power from the drive.
b. Apply power to the drive.
The status indicators should be green. If they flash
red, there is a problem. See Chapter 5
Troubleshooting.
c. Configure and verify key drive parameters.
5Configure the option module for your application.
Set option module parameters for the following functions
as required by your application:
• Network Address
• Fault actions
6Configure BACnet Objects.
Use a controller configuration tool, such as ORCAview,
that enables you to control the option module and
connected drive using BACnet Objects.
).
,
Network Communication Option
Card Installation Instructions,
publication 750COM-IN002
Chapter 2
Installing the Option Module
Chapter 2
Installing the Option Module
Chapter 3
Configuring the Option Module
Chapter 4
Using BACnet Services and
Objects
,
,
,
,
, and
16Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter
Installing the Option Module
This chapter provides instructions for installing the option module in a
PowerFlex 750-Series drive.
TopicPage
Preparing for an Installation
Setting the IP Address Selection Jumper18
Connecting the Option Module to the Drive19
Connecting the Option Module to the Network
Applying Power20
Commissioning the Option Module23
17
19
2
Preparing for an
Installation
Before installing the option module, verify that you have all required equipment.
See Required Equipment
ATTENTION: Risk of equipment damage exists. The option module
contains electrostatic discharge (ESD) sensitive parts that can be damaged
if you do not follow ESD control procedures. Static control precautions are
required when handling the option module. If you are unfamiliar with static
control procedures, see Guarding Against Electrostatic Damage,
publication 8000-4.5.2
on page 13.
.
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201417
Chapter 2 Installing the Option Module
Pin 2 and 3 (DEFAULT setting)
Pin 1 and 2 (CONFIG setting) to
use option module parameters or
DHCP server for network address
Setting the IP Address
Selection Jumper
The IP Address Selection Jumper (Figure 1) determines the source of the
network address for the option module.
Figure 1 - Setting the IP Address Selection Jumper
3
2
1
Using Default Network Address
When the jumper is on Pins 2 and 3 and Device Parameter 16 - [DHCP] is set to
‘0’ (Disabled), the following default network address is used:
• IP Address 192.168.0.1
• Subnet Mask 255.255.255.0
• Gateway 192.168.0.1
Using DHCP Server
When the jumper is on Pins 1 and 2 and Device Parameter 16 - [DHCP] is set to
‘1’ (Enabled), the network address is configured from a DHCP server. To set an
IP address using a DHCP server, do the following.
1. Set Device Parameter 16 - [DHCP] to ‘1’ (Enabled) to select the DHCP
server as the source for the IP address.
2. Reset the option module; see Resetting the Option Module
it can get the new IP address from the DHCP server.
Using Option Module Parameters
on page 33, so
18Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
When the jumper is on Pins 1 and 2—or there is no jumper—and Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled), the network address is
configured with option module parameters.
Installing the Option Module Chapter 2
IMPORTANT
IMPORTANT
Connecting the Option
Module to the Drive
Connecting the Option
Module to the Network
Remove power from the drive before installing the option module in the
drive control pod.
Install the option module in the PowerFlex 750-Series drive control pod in Port
4, 5, or 6. For more installation details, see the Network Communication Option
Module Installation Instructions, publication 750COM-IN002, provided with
the option module. See Figure 1
the drive.
After inserting the option module into drive Port 4, 5, or 6, make sure to
tighten the module screws to the pod mounting bracket to properly
ground the module to the drive. Torque both screws to 0.45…0.67 N•m
(4.0…6.0 lb•in).
ATTENTION: Risk of injury or death exists. The PowerFlex drive may
contain high voltages that can cause injury or death. Remove power from
the drive, and then verify power has been discharged before connecting the
option module to the network.
1. Remove power from the drive.
for an example of the option module installed in
2. Remove the drive cover and lift up the drive HIM bezel to its open
position to access the drive control pod.
3. Use static control precautions.
4. Connect one end of the Ethernet cable to the network.
5. Route the other end of the Ethernet cable through the bottom of the drive,
and insert its RJ45 male connector into the mating Ethernet connector of
the option module.
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201419
Chapter 2 Installing the Option Module
See Ta bl e 1 for
possible start-up
status indications.
Drive Control Pod
(drive shown with
cover removed)
Applying Power
ATTENTION: Risk of equipment damage, injury, or death exists.
Unpredictable operation can occur if you fail to verify that parameter
settings are compatible with your application. Verify that settings are
compatible with your application before applying power to the drive.
Apply power to the drive. The option module receives its power from the drive.
When you apply power to the option module for the first time, its topmost
‘PORT’ status indicator should be steady green or flashing green after an
initialization. If it is red, there is a problem. See Chapter 5
Start-Up Status Indications
After power has been applied, the drive STS (status) indicator can be viewed on
front of the drive and the option module status indicators can be viewed with the
drive cover open or removed (Figure 2
shown in Ta b l e 1
Figure 2 - Drive and Option Module Status Indicators
.
). Possible start-up status indications are
, Troubleshooting.
➊
➋
➌
➍
20Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Installing the Option Module Chapter 2
Table 1 - Drive and Option Module Start-Up Status Indications
ItemNameColorStatusDescription
Drive STS Indicator
STS
➊
(Status)
➋PORT—OffThe option module is not powered or connected properly to the drive.
➌MOD—OffThe option module is not powered or connected properly to the drive.
➍NET A—OffThe option module is not powered or connected properly to the network. The link is
GreenFlashingDrive ready but not running, and no faults are present.
SteadyDrive running, no faults are present.
YellowFlashingWhen running, a type 2 (non-configurable alarm condition exists – drive continues to run.
When stopped, a start inhibit condition exists and the drive cannot be started (see drive
parameter 933 - [Start Inhibits]).
SteadyA type 1 (user configurable) alarm condition exists, but the drive continues to run.
RedFlashingA major fault has occurred. Drive will stop. Drive cannot be started until fault condition is
cleared.
SteadyA non-resettable fault has occurred.
Red/YellowFlashing AlternatelyA minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not
enabled, acts like a major fault. When running, the drive continues to run. System is
brought to a stop under system control. The fault must be cleared to continue.
Yellow/GreenFlashing AlternatelyWhen running, a type 1 alarm exists.
Green/RedFlashing AlternatelyDrive firmware is updating.
Option Module Status Indicators
RedFlashingThe option module is not receiving any communication from the drive.
GreenFlashingNormal operation. The option module is establishing communication with drive. It will
OrangeSteadyThe brand of the option module and drive do not match.
RedFlashingThe option module has failed the firmware test or a firmware update is in progress.
GreenFlashingNormal operation. The option module is operating but is not transferring I/O data to a
RedFlashingAny error in packet validation and/or execution is considered a network configuration
GreenSteadyNormal operation. The option module is properly connected and communicating on the
SteadyThe option module detected a duplicate or invalid port ID.
turn steady green or red.
SteadyNormal operation. The option module is properly connected and communicating with the
drive.
SteadyThe option module has failed the hardware test.
controller.
SteadyNormal operation. The option module is operating and transferring I/O data to a
SteadyAny failure in self-test on the external Ethernet controller is considered a network
controller.
inactive.
error.
controller error.
network.
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see page 44
and page 45.
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201421
Chapter 2 Installing the Option Module
Configuring and Verifying Key Drive Parameters
The PowerFlex 750-Series drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could configure the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.
The following steps in this section assume that the drive will receive the Logic
Command and Reference from the network.
1. Verify that drive Parameter 301 - [Access Level] is set to ‘1’ (Advanced) or
‘2’ (Expert) to access the required parameters in this procedure.
2. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed
Reference.
a. Set the Port field to ‘0’ as shown below.
b. Set the Parameter field to point to the port (slot) in which the option
module is installed (for example, Port 4 Reference).
The number ‘874’ in the Parameter field of the example dialog box
above is the parameter in the drive that points to the port.
3. Verify that drive Parameter 930 - [Speed Ref Source] is reporting that the
source of the Reference to the drive (Port 0) is the port in which the option
module is installed (for example, Port 4 Reference).
22Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Installing the Option Module Chapter 2
IMPORTANT
This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded SpdRef ]. If a
problem occurs, this verification step provides the diagnostic capability to
determine whether the drive/option module or the network is the cause.
4. If hard-wired discrete digital inputs are not used to control the drive, verify
that all unused digital input drive parameters are set to ‘0’ (Not Used).
Commissioning the Option
Module
To commission the option module, you must set a unique network node address.
See the Glossary
Selection Jumper on page 18 for details on selecting the source (default address,
from a DHCP server, or from option module parameters) for the network
address.
for details about IP addresses. Also, see Setting the IP Address
New settings for some option module parameters (for example Device Parameters 04 - [IP Addr Cfg 1] through 07 - [IP Addr Cfg 4]) are
recognized only when power is applied to the option module or it is reset.
After you change parameter settings, cycle power or reset the option
module.
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201423
Chapter 2 Installing the Option Module
Notes:
24Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
IMPORTANT
Chapter
3
Configuring the Option Module
This chapter provides instructions and information for setting the parameters to
configure the option module.
TopicPage
Configuration Tools25
Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM to Access Parameters26
Setting the Option Module Address Using Parameters
Setting the Device Instance28
Setting the Device Port29
Setting a Fault Action
Setting the Comm Loss Time31
Setting Web Page Access32
Resetting the Option Module
Restoring Option Module Parameters to Factory Defaults34
Viewing the Option Module Status Using Parameters35
Updating the Option Module Firmware
26
29
33
35
Configuration Tools
For a list of parameters, see Appendix
definitions of terms in this chapter, see the Glossary
The option module stores parameters and other information in its own
nonvolatile storage (NVS) memory. You must, therefore, access the option
module to view and edit its parameters. The following tools can be used to access
the option module parameters.
ToolSee
PowerFlex 20-HIM-A6 or
20-HIM-C6S HIM
Connected Components Workbench
software, version 1.02 or later
DriveExplorer software,
version 6.01 or later
DriveExecutive software,
version 5.01 or later
For the HIM screens shown throughout this chapter, the option module
was installed in drive Port 4. If your option module is installed in a
different drive port, that port would appear instead of Port 4.
B, Option Module Parameters. For
.
page 26
http://www.ab.com/support/abdrives/webupdate/
software.html, or online help (installed with the software)
http://www.ab.com/drives/driveexplorer
(installed with the software)
http://www.ab.com/drives/drivetools
(installed with the software)
, or online help
, or online help
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201425
Chapter 3 Configuring the Option Module
AUTO
ESC
ENTER
Stopped
0.00 Hz
F
▲
▼
Edit DHCP
Disabled0
0<<1
ValueSetting
0Disabled
1Enabled (Default)
Using the PowerFlex 20HIM-A6 or 20-HIM-C6S HIM
to Access Parameters
Setting the Option Module
Address Using Parameters
If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it
can be used to access parameters in the option module.
1. Display the Status screen, which is shown on HIM powerup.
2. Use the or key to scroll to the Port in which the option
module is installed.
3. Press the PAR# soft key to display the Jump to Param # entry pop-up box.
4. Use the numeric keys to enter the desired parameter number, or use the
or soft key to scroll to the desired parameter number.
For details on viewing and editing parameters, see the PowerFlex 20-HIM-A6/C6S HIM (Human Interface Module) User Manual, publication 20HIM-
UM001.
By default, the option module is provided with the IP address 192.168.0.1,
subnet mask 255.255.255.0, and gateway address 192.168.0.1. If you want to set
these attributes using the option module parameters, you must first disable
DHCP and then set the associated option module parameters as described in the
following subsections.
Disable the DHCP Feature
1. Set the value of Device Parameter 16 - [DHCP] to ‘0’ (Disabled).
2. Reset the option module; see Resetting the Option Module
After disabling the DHCP feature, you can then configure the IP address, subnet
mask, and gateway address using option module parameters.
Set the IP Address
1. Verif y th at Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).
26Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
on page 33.
Configuring the Option Module Chapter 3
ESC
ENTER
Stopped
0.00 Hz
AUTO
Edit IP Addr Cfg 1
0
0 << 255
F
Default = 0.0.0.0255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Stopped
0.00 HzF
Edit Subnet Cfg 1
0
0 << 255
ENTER
ESC
AUTO
Default = 0.0.0.0255.255.255.255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
ESC
ENTER
AUTO
F
Edit Gateway Cfg 1
0
0 << 255
Stopped
0.00 Hz
Default = 0.0.0.0255.255.255.255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
2. Set the value of Device Parameters 04 - [IP Addr Cfg 1] through 07 - [IP
Addr Cfg 4] to a unique IP address.
3. Reset the option module; see Resetting the Option Module
on page 33.
Set the Subnet Mask
1. Verif y th at Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).
2. Set the value of Device Parameters 08 - [Subnet Cfg 1] through 11 [Subnet Cfg 4] to the desired value for the subnet mask.
3. Reset the option module; see Resetting the Option Module
on page 33.
Set the Gateway Address
1. Verif y th at Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).
2. Set the value of Device Parameters 12 - [Gateway Cfg 1] through 15 -
Rockwell Automation Publication 750COM-UM005B-EN-P - June 201427
[Gateway Cfg 4] to the IP address of the gateway device.
3. Reset the option module; see Resetting the Option Module
on page 33.
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.