Rockwell Automation 198E-C0C4R User Manual [en, fr, it, es]

Plastic Enclosure for DOL and Reversing Starters with Motor Protection Circuit Breaker Application Instruction
WARNING:
To prevent electrical shock, disconnect from power source before installing or servicing. To be commissioned and maintained only by qualied personnel; pay attention to the operating instructions!
The opening of the branch circuit protective device may be an indication that a fault current has been inter­rupted. To reduce the risk of re or electric shock, current-carrying parts and other components of the starter should be examined and replaced if damaged.
When wired for 2-wire control, a motor connected to the circuit may start when a person actuates the RESET push button.
Kunststogehäuse für DOL- und Wendestarter mit Motorschutz-Leistungsscalter Anwendungsanweisung
WARNUNG:
Vor Installations- oder Servicearbeiten Stromversorgung unterbrechen, um Unfälle zu vermeiden. Inbetriebsetzung und Wartung nur durch Fachpersonal; Betriebsanleitung beachten!
Das Ansprechen eines Schutzgeräts kann auf einen aufgetretenen Kurzschluss hinweisen. Um Risiken wie Feuer oder Stromschlag zu vermeiden sollten die Starterkomponenten überprüft und gegebenenfalls ersetzt werden.
Bei Startern mit Dauerkontaktsteuerung kann ein Motor automatisch starten, wenn das Motorschutzrelais auf automatische Rückstellung eingestellt ist.
Bei Startern mit Dauerkontaktsteuerung kann ein Motor automatisch starten, wenn nach einer Auslösung des Motorschutzrelais die Rückstelltaste betätigt wird.
Boîtier plastique pour démarreur direct et inverseur avec disjoncteur de protection de moteur Notice d´application
AVERTISSEMENT:
Avant le montage et la mise en service, couper l'alimentation secteur an d'éviter tout accident. Mise en service et entretien: seulement par du personnel spécialisé; respecter les instructions d'exploitation!
Le déclenchement d'un dispositif de protection peut indiquer qu'un court-circuit s'est produit. Pour éviter des risques tels qu'un incendie ou un choc électrique, les éléments du démarreur devraient être contrôlés et remplacés si nécessaire.
Si la commande de démarrage est réalisée avec un contact permanent, le moteur peut démarrer automa­tiquement lorsque le relais de surcharge est en mode de réarmement automatique.
Si la commande de démarrage est réalisée avec un contact permanent, le moteur peut démarrer lorsque, après déclenchement du relais de surcharge, le bouton de réinitialisation est actionné.
198E-C0C4R
IEC / EN 62208
IEC / EN 60947-4-1
UL 508
CSA 22.2, No. 14
Custodie plasitce per avviatore diretto e invertitore con interruttore automatico Istruzione d'applicazione
AVVERTENZA:
Per prevenire infortuni, togliere tensione prima dell'installazione o manutenzione. Messa in servizio e manutenzione devono essere eettuate solo da personale specializzato; attenersi alle istruzioni per l'esercizio!
L'intervento di un dispositivo di protezione può indicare che si è vericato un corto circuito. Per evitare rischi, quali incendi o scosse elettriche, i componenti dell'avviatore dovrebbero essere controllati e sostituiti se necessario.
Quando collegato con controllo a due li, il motore connesso al circuito può avviarsi automaticamente se il relè è impostato su reset automatico.
Quando collegato con controllo a due li, il motore connesso al circuito può avviarsi automaticamente se il pulsante di RESET del relè di sovraccarico viene premuto.
Cofre en plástico para arrancador directo e inversor con interruptor automático Instrucciones de montaje
ADVERTENCIA:
Desconectar la alimentación eléctrica antes de realizar el montaje, con el objeto de evitar accidentes. La puesta en servicio y el mantenimiento ha de realizarse exclusivamente por personal especializado; ¡prestar atención a las instrucciones de montaje y puesta en marcha!
El disparo de un dispositivo de protección puede indicar que se ha producido un cortocircuito. Para evitar riesgos como incendio o descargas eléctricas, los componentes del arrancador deben ser examinados y reemplazados si fuera necesario.
Cuando el sistema de control es por contacto permanente, el motor se puede conectar automáticamente si el relé de sobrecarga tiene ajustado el rearme en posición de automático.
Cuando el sistema de control es por contacto permanente, después del disparo del relé térmico, el motor se puede conectar cuando se presiona el pulsador de RESET (rearme).
Assembly of Reversing Starters
321
Assemble the reversing contactor:
• Turn the coil terminals to the load side according the contactors instruction sheet.
• Place the mechanical interlock between contactors
• Insert the dovetail connector from rear side
• Attach the reversing connection on load side
• Attach the parallel connection and the Eco connection module on line side
4
5
The enclosure ts for both, the 140M-C and the 140M-D MPCB.
For the 140M-D, shorten the support by breaking o the 2 tabs.
Snap the reversing contactor onto the metal hat rail
Snap the 800F contact blocks onto the device support:
• Pos. 2 (center): N.C. contact
• Pos. 3 (left): N.O. contact
Do the control wiring according the wiring diagram/wire table.
Prepare the MPCB by replacing the knob and adding the auxiliary:
• Remove original knob
• Remove front cover
• Add auxiliary and lockable twist knob
(2)
6
Attach the MPCB and complete the control wiring. Mount the 800F push button operator and the MPCB
rotary handle into the cover.
Component Selection for DOL and Reversing Starters
With Motor Protection Circuit Breaker 140M-C / -D
IEC60947-4-1 COMB. MTR. CNTRL., UL 508 (TYPE F)
480Y/
Setting
Range
[A]
0.1 - 0.16
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.63 - 1.0
1.0 - 1.6
1.6 - 2.5
2.5 - 4.0
2.5 - 4.0
4.0 - 6.3
4.0 - 6.3
6.3 - 10
6.3 - 10
6.3 - 10
6.3 - 10
6.3 - 10
6.3 - 10
10 - 16
10 - 16
10 - 16
10 - 16
To complete the cat. no., please replace with a coil voltage code.
400/415V AC 500V AC 690V AC
AC-3 Type 1 Type 1 Type 1Type 2 AC-3 AC-3
[kW] [kW]
-----
65 65 65 65 47500.06 0.06
0.06 - - -65 65 65 65 47500.06 0.12
0.09 - - -65 65 65 65 47500.12 0.18
0.18 - - -65 65 65 65 47500.18 0.37
0.25 - - -65 65 65 65 47500.37 0.55
0.55 - - 3/465 65 65 65 47500.75 1.1
0.75 1/2 1/2 165 50 50 65 3081.1 1.8
1.5 3/4 3/4 250 50 50 65 3082.2 3
1.5 3/4 3/4 265 65 50 65 30102.2 3
2.2 1 1 1/2 350 50 50 65 -434
2.2 1 1 1/2 365 65 50 65 305034
423565 50 50 65 --4-
423565 65 50 65 30
423565 50 50 65 -45.5 5.5
423565 65 65 65505.5 5.5
423565 50 50 6545.5 7.5
423565 65 65 65505.5 7.5
5.5 3 3 7 1/250 50 - 30---
5.5 3 3 7 1/265 65 - 65---
7.5 3 5 1050 - 10 30310 -
7.5 3 5 1065 - 50 65610 -
lq [kA]lq [kA]lq [kA]lq [kA][kW]
200V
230V 460V 575V
[HP] [HP] [HP] [HP] lq [kA]
-
-
-
1/2
3/4
1 1/2
3
3
-
5
-
-4-
7 1/2
-
7 1/2
-
7 1/2
-
10
-
10
lq [kA]
277V
600Y/ 347V
30
-
30
-
30
-
30
Additional components
Mechanical / Electrical Interlock 1 Power Wiring Kit for Reversing Starters 1 ECO Starter Connecting Module 1 Actuator type G, Black/Grey, 90° Lockable Twist Knob
UL 508 Type E Spacing Module Neutral Terminal
Control Components required for Impulse Control
Front-Mounted Auxiliary Contact for MPCB 1 Multi-Function Push Button Operator, 3 Functions, without Markings ‡§ Base Mounted Contact Block 1 N.C. 1 Base Mounted Contact Block 1 N.O. 2
Control Components required for Maintained Control
Front-Mounted Auxiliary Contact for MPCB 1 Selector Switch Operator, non-illuminated, 3-position § 1 Base Mounted Contact Block 1 N.O. 2
For button caps with text or symbols, order the operator without cap (cat. no. 800FP-U3X ). Caps are to be ordered separately.
§ For legend plates and frames, please see catalog A116. ¥ For UL applications.
(3)
¥ ¥
Components
MPCB Contactor
140M-C2E-A16
140M-C2E-A25
140M-C2E-A40
140M-C2E-A63
140M-C2E-B10
140M-C2E-B16
140M-C2E-B25
140M-C2E-B40
140M-D8E-B40
140M-C2E-B63
140M-D8E-B63
140M-C2E-C10
140M-D8E-C10
140M-C2E-C10
140M-D8E-C10
140M-C2E-C10
140M-D8E-C10
140M-C2E-C16
140M-D8E-C16
140M-C2E-C16
140M-D8E-C16
ytitnauQ deriuqeRnoitpircseD Cat. No.
140M-C-PEC23A 1 1 1
1
1
800FP-U3F3F34
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C09 10
100-C12 10
100-C12 10
100-C16 10
100-C16 10
100-C12 10
100-C12 10
100-C16 10
100-C16 10
100-MCA02
105-PW23
198-SHB
140M-C-KN1 140M-C-TE1 198E-PNT
140M-C-AFA10
800F-BX01 800F-BX10
140M-C-AFA10
800FP-SM32
800F-BX10
Impulse Control, Multi Function Push Button Maintained Control, Selector Switch < O >
Schematic Diagram
L1
WARNING: AVERTISSEMENT:
conduits métalliques.
Bonding between metallic conduits must be provided.
SUPPLY CONDUCTOR
SIZE (AWG)
GROUNDING ADAPTER KIT, CAT. NO. 198-GR1
1 1
1
L1 control voltage supplied from external source.
1
Une liaison électrique doit être assurée entre les
BONDING CONDUCTOR
14 12 10
FOR USE WITH ALLEN-BRADLEY
SEE APPLICABLE CODES AND LAW FOR GROUNDING REQUIREMENTS
QTY. SIZE
1 1 2
14 12 12
1
2
1
3
1- HAND
2- OFF
3- AUTO
Illuminated HOA Selector Switch
L1
I
1
1
A1
A2
I
2 WIRE CONTROL
Dimensions
250 [9.85]
14.1 [0.56] 14.1 [0.56]
159.3 [6.28]
Ø3.5
[Ø0.14]
Ø15
[Ø0.59]
14.1
[0.56]
38.7 [1.52]
[0.14]
[0.56]
95 [3.74]
125 [4.93]
50 [1.97]
3.5
Ø23
[Ø0.91]
14.1
13 [0.51]
150 [5.91]
24 [0.95]
50 [1.97]
50 [1.97]
125 [4.93] 32.5 [1.28]125 [4.93]
Pozidriv No. 2
(1.2 x 6.5)
2.0 Nm 18 lb-in
Rotary operator alternatively (for maintained control)
28.1 [1.11]
10
2 x 1...6 mm²
2 x 1...6 mm²
2 x No. 14...10 AWG
2 x No. 14...10 AWG
110 [4.33]
Pozidriv No. 2
2.3 Nm 20 lb-in
235 [9.26]
DIR 10000248718 (Version 03)
Printed in Estonia