Important User Information4
Additional Resources5
Overview6
Controller Description7
Hazardous Location Considerations8
Mounting the Controller10
Connecting 1762 I/O Expansion Modules16
Wiring the Controller17
Specifications23
Page 2
4
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
) describes some important differences between solid state
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion
in a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you identify a
hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert
people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert
people that surfaces may reach dangerous temperatures.
Publication 1763-IN001C-EN-P - June 2015
Page 3
Additional Resources
ResourceDescription
5
MicroLogix 1100 Programmable Controllers User
Manual 1763-UM001
MicroLogix 1100 Instruction Set Reference
Manual1763-RM001
Installation Instructions 1762-INxxxInformation on installing and using 1762 expansion I/O
Industrial Automation Wiring and Grounding
Guidelines 1770-4.1
A more detailed description of how to install and use your
MicroLogix 1100 programmable controller and expansion
I/O system.
A reference manual that contains data and function files,
instruction set, and troubleshooting information for
MicroLogix 1100.
modules.
More information on proper wiring and grounding
techniques.
If you would like a manual, you can:
• download a free electronic version from the internet:
http://literature.rockwellautomation.com
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
Publication 1763-IN001C-EN-P - June 2015
Page 4
6
ATTENTION
ATTENTION
debris strip
Overview
MicroLogix 1100 controllers are suitable for use in an industrial environment when installed
in accordance with these instructions. Specifically, this equipment is intended for use in clean,
dry environments (Pollution degree 2
Category II
(2)
(IEC 60664-1).
(3)
Install your controller using these installation instructions.
(1)
) and with circuits not exceeding Over Voltage
Do not remove the protective debris strip until after the controller and all other equipment
in the panel near the controller are mounted and wiring is complete. Once wiring is
complete, remove protective debris strip. Failure to remove strip before operating can
cause overheating.
Electrostatic discharge can damage semiconductor devices inside the controller. Do not
touch the connector pins or other sensitive areas.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
10DIN Rail Latches
11RS-232/485 Communication Port (Channel 0, isolated)
12Ethernet Port (Channel 1)
(1)
Shipped with controller.
(2)
Optional equipment.
Publication 1763-IN001C-EN-P - June 2015
Page 6
8
Catalog
Number
Description
Input
Power
Digital
Inputs
Analog
Inputs
1763-L16AWA120/240V ac(10) 120V ac(2) voltage input
0...10V dc
1763-L16BWA120/240V ac(6) 24V dc
(2) voltage input
(4) high-speed
(1)
24V dc
1763-L16BBB24V dc(6) 24V dc
0 ...10V dc
(2) voltage input
(4) high-speed
(1)
24V dc
1763-L16DWD12/24V dc(6) 12/24V dc
(4) high-speed
12/24V dc
(1)
0...10V dc
(2) voltage input
0...10V dc
Digital
Outputs
(6) relay
All individually
isolated
(6) relay
All individually
isolated
(2) relay (isolated)
(2) 24V dc FET
(2) high-speed
24V dc FET
(6) relay
All individually
isolated
Comm.
Ports
(1) RS-232/485
combo
(isolated)
(1) Ethernet
(1) RS-232/485
combo
(isolated)
(1) Ethernet
(1) RS-232/485
combo
(isolated)
(1) Ethernet
(1) RS-232/485
combo
(isolated)
(1) Ethernet
(1)
The 4 high-speed inputs (inputs 0 through 3) can be used for pulse latching or higher speed counting. Refer to Input
Specifications on page 25 and the MicroLogix 1100 Instruction Set Reference Manual, publication 1763-RM001, for more
information.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous
locations only. The following WARNING statement applies to use in hazardous locations.
Publication 1763-IN001C-EN-P - June 2015
Page 7
WARNING
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been
switched off.
• Do not connect or disconnect components unless power has been switched off.
• This product must be installed in an enclosure. All cables connected to the
product must remain in the enclosure or be protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-10(b).
• The interior of the enclosure must be accessible only by the use of a tool.
• For applicable equipment (for example, relay modules), exposure to some
chemicals may degrade the sealing properties of the materials used in these
devices:
– Relays, epoxy
9
It is recommended that you periodically inspect these devices for any degradation
of properties and replace the module if degradation is found.
Publication 1763-IN001C-EN-P - June 2015
Page 8
10
ATTENTION
Use only the following communication cables in Class I, Division 2 hazardous locations.
Environment ClassificationCommunication Cables
Class I, Division 2 Hazardous Environment1761-CBL-AC00 Series C or later
1761-CBL-AM00 Series C or later
1761-CBL-AP00 Series C or later
1761-CBL-PM02 Series C or later
1761-CBL-HM02 Series C or later
1761-CBL-PH02 Series A or later
1761-CBL-AH02 Series A or later
2707-NC9 Series C or later
1763-NC01 Series A or later
UNSUPPORTED CONNECTION
Do not connect a MicroLogix 1100 controller to another MicroLogix family controller
such as MicroLogix 1000, MicroLogix 1200, or MicroLogix 1500 using a 1761-CBL-AM00
(8-pin mini-DIN to 8-pin mini-DIN) cable or equivalent.
This type of connection will cause damage to the RS-232/485 communication port
(Channel 0) of the MicroLogix 1100 and/or the controller itself. Communication pins
used for RS-485 communications are alternately used for 24V power on the other
MicroLogix controllers.
Mounting the Controller
General Considerations
Most applications require installation in an industrial enclosure to reduce the effects of
electrical interference and environmental exposure. Locate your controller as far as possible
from power lines, load lines, and other sources of electrical noise such as hard-contact
switches, relays, and ac motor drives. For more information on proper grounding guidelines,
see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Vertical mounting is not supported due to thermal considerations.
Be careful of metal chips when drilling mounting holes for your controller or other
equipment within the enclosure or panel. Drilled fragments that fall into the controller
could cause damage. Do not drill holes above a mounted controller if the protective
debris strips have been removed.
Mounting Dimensions
Dimension1763-
L16AWAL16BWAL16BBBL16DWD
A90 mm (3.5 in.)
B110 mm (4.33 in.)
C87 mm (3.43 in.)
Publication 1763-IN001C-EN-P - June 2015
Page 10
12
ESCOK
Top
Side
Bottom
A
B
C
Controller Spacing
The controller mounts horizontally, with the expansion I/O extending to the right of the
controller. Allow 50 mm (2 in.) of space on all but the right side for adequate ventilation, as
shown below.
DIN Rail Mounting
The maximum extension of the latch is 14 mm (0.55 in.) in the open position. A flat-blade
screwdriver is required for removal of the controller. The controller can be mounted to
EN50022-35x7.5 or EN50022-35x15 DIN rails. DIN rail mounting dimensions are shown
below.
DimensionHeight
A90 mm (3.5 in.)
B27.5 mm (1.08 in.)
C27.5 mm (1.08 in.)
Publication 1763-IN001C-EN-P - June 2015
Page 11
Follow these steps to install your controller on the DIN rail.
ESCOK
open
closed
1. Mount your DIN rail. (Make sure that the placement of the controller on the DIN rail
meets the recommended spacing requirements. See Controller Spacing on page 12.
Refer to the mounting template inside the back cover of this document.)
2. If it is open, close the DIN latch.
3. Hook the top slot over the DIN rail.
4. While pressing the controller down against the top of the rail, snap the bottom of the
controller into position.
5. Leave the protective debris strip attached until you are finished wiring the controller
and any other devices.
Follow these steps to remove your controller from the DIN rail.
13
1. Place a flat-blade screwdriver in the DIN rail latch at the bottom of the controller.
2. Holding the controller, pry downward on the latch until the latch locks in the open
position.
3. Repeat steps 1 and 2 for the second DIN rail latch.
4. Unhook the top of the DIN rail slot from the rail.
Publication 1763-IN001C-EN-P - June 2015
Page 12
14
IMPORTANT
Mounting
Temp la te
Panel Mounting
Mount to panel using #8 or M4 screws. Follow these steps to install your controller using
mounting screws.
1. Remove the mounting template from inside the back cover of this document.
2. Secure the template to the mounting surface. (Make sure your controller is spaced
properly. See Controller Spacing on page 12.)
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the controller.
6. Leave the protective debris strip
in place until you are finished
wiring the controller and any
other devices
Using the Battery
The MicroLogix 1100 controller is equipped with a replaceable battery. The Battery Low
indicator on the LCD display of the controller shows the status of the replaceable battery.
When the battery is low, the indicator is set (displayed as a solid rectangle). This means that
either the battery wire connector is disconnected, or the battery may fail within 2 days if it is
connected.
The MicroLogix 1100 controller ships with the battery wire connector connected.
Ensure that the battery wire connector is inserted into the connector port if your
application needs battery power. For example, when using a real-time clock (RTC), or
to store the program in the controller’s memory for an extended period of time while
the power is removed.
Refer to the MicroLogix 1100 Programmable Controller User Manual, publication
1763-UM001, for more information on installation, handling, usage, storage, and
disposal of the battery.
Publication 1763-IN001C-EN-P - June 2015
Page 13
Follow these steps to connect the replaceable battery.
ESCOK
Wire Guide
Battery Connector Wires
Replaceable
Battery
Replaceable Battery Pocket
Battery Wire Connector
Battery Connector
1. Insert the replaceable battery wire connector into the battery connector.
2. Secure the battery connector wires along the wire guide as shown below.
15
Publication 1763-IN001C-EN-P - June 2015
Page 14
16
ATTENTION
Connec
Connect 1762 I/O after mounting the controller.
1. Remove the expansion port cover to install expansion I/O modules.
2. Plug the ribbon cable connector into the bus connector.
3. Replace the cover as shown below.
ting 1762 I/O Expansion Module
Remove power to the system before installing or removing expansion I/O or damage to the
controller may result.
s
The MicroLogix 1100 controller is designed to support up to any four 1762 expansion I/O
modules.
For detailed information on using expansion I/O, refer to the installation instructions for
your expansion module.
Publication 1763-IN001C-EN-P - June 2015
Page 15
Wiring the Controller
TIP
AC
COM
NOT
USED
VACO/0
VDC
VACO/1
VDC
VACO/2
VDC
VACO/3
VDC
VACO/4
VDC
VACO/5
VDC
NOT
USED
NOT
USED
L1L2/N
100-240 VAC
NOT
USED
I/1I/0I/2I/3
AC
COM
I/4I/5
IA
COM
IV1(+)IV2(+)I/6I/7I/8I/9
1763-L16AWAInput Terminal Block
Output Terminal Block
DC
COM-
VACO/0
VDC
VACO/1
VDC
VACO/2
VDC
VACO/3
VDC
VACO/4
VDC
VACO/5
VDC
NOT
USED
NOT
USED
L1L2/N
100-240 VAC
DC OUT
+ 24V
I/1I/0I/2I/3
DC
COM
I/4I/5
IA
COM
IV1(+)IV2(+)I/6I/7I/8I/9
1763-L16BWAInput Terminal Block
Output Terminal Block
DC
COM
NOT
USED
VACO/0
VDC
VACO/1
VDC
NOT
USED
NOT
USED
DCO/2O/3
24V+
DC
24V-
O/4O/5NOT
USED
NOT
USED
+ 24V -
DC IN
NOT
USED
I/1I/0I/2I/3
DC
COM
I/4I/5
IA
COM
IV1(+)IV2(+)I/6I/7I/8I/9
1763-L16BBBInput Terminal Block
Output Terminal Block
Terminal Block Layouts
The shading in the following terminal block illustrations indicates
which terminals are tied to which commons.
17
Publication 1763-IN001C-EN-P - June 2015
Page 16
18
ATTENTION
Input Terminal Block
Output Terminal Block
1763-L16DWD
NOT
USED
NOT
USED
DC
COM
I/1I/0I/2I/3
COM
DC
I/4I/5
IA
COM
IV1(+)IV2(+)I/6I/7I/8I/9
+ 12/24V -
DC IN
NOT
USED
VACO/0
VDC
VACO/1
VDC
VACO/2
VDC
VACO/3
VDC
VACO/4
VDC
Wire Requirements
Wire TypeWire Size (2 wire maximum per terminal)
1 wire per terminal2 wire per terminal
SolidCu-90 °C (194 °F)12...20 AWG16...20 AWG
StrandedCu-90 °C (194 °F)14...20 AWG18...20 AWG
Wiring torque = 0.56 Nm (5.0 in-lb) rated.
Be careful when stripping wires. Wire fragments that fall into the controller could
cause damage. Once wiring is complete, be sure the controller is free of all metal
fragments before removing the protective debris strip. Failure to remove the strip
before operating can cause overheating.
VACO/5
VDC
NOT
USED
Wiring Recommendation
The MicroLogix 1100 controllers have screw-cage clamps on the input and output terminal
blocks. With screw-cage clamp terminal blocks, there is no need to attach additional hardware
such as a spade lug to the wire, or use a finger-safe cover.
Follow these steps to wire the terminal block.
1. Strip the end of the wire.
The recommended length for the stripped end of the wire is 11.0 mm
(0.440 in.).
Publication 1763-IN001C-EN-P - June 2015
Page 17
19
ATTENTION
Screw-cage clamp terminal block
2. Insert it into an open clamp.
3. Using a small, flat-blade screwdriver, tighten the terminal screw. To ensure that the
wire conductor is secured inside the clamp, tighten it to the rated torque, 0.56 Nm (5.0
in-lb).
The diameter of the terminal screw head is 5.5 mm (0.220 in.).
Surge Suppression
Inductive load devices such as motor starters and solenoids require the use of some
type of surge suppression to protect the controller output. Switching inductive loads
without surge suppression can significantly reduce the life of relay contacts or
damage transistor outputs. By using suppression, you also reduce the effects of
voltage transients caused by interrupting the current to that inductive device, and
prevent electrical noise from radiating into system wiring. Refer to the MicroLogix
1100 Programmable Controller User Manual, publication 1763-UM001, for more
information on surge suppression.
Publication 1763-IN001C-EN-P - June 2015
Page 18
20
ATTENTION
Grounding the Controller
In solid-state control systems, grounding and wire routing helps limit the effects of noise due
to electromagnetic interference (EMI). Run the ground connection from the ground screw of
the controller to the ground bus prior to connecting any devices. Use AWG #14 wire. For
ac-powered controllers, this connection must be made for safety purposes.
All devices connected to the RS-232/485 communication port must be referenced to
controller ground, or be floating (not referenced to a potential other than ground).
Failure to follow this procedure may result in property damage or personal injury.
• For the 1763-L16BWA controller:
The COM of the sensor supply is also connected to chassis ground internally.
The 24V dc sensor power source should not be used to power output circuits. It
should only be used to power input devices.
• For 1763-L16BBB and 1763-L16DWD controllers:
The VDC NEUT or common terminal of the power supply is also connected to
chassis ground internally.
You must also provide an acceptable grounding path for each device in your application. For
more information on proper grounding guidelines, refer to the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
Publication 1763-IN001C-EN-P - June 2015
Page 19
Wiring Your Analog Channels
IA
COM
IV1(+)IV2(+)
Sensor 2
(V) Voltage
Sensor 1
(V) Voltage
IV1(+) or IV2(+)
IA COM
IV1(+) or IV2(+)
IA COM
+-
+
-
+
-
IV1(+) or IV2(+)
IA COM
+
-
+
-
GND
+
-
TransmitterTransmitter
Transmitter
Transmitter
SupplySignal
SupplySignal
Controller
Controller
Controller
Power
Supply
3-Wire Transmitter
4-Wire Transmitter
2-Wire Transmitter
Power
Supply
Power
Supply
Analog input circuits can monitor voltage signals and convert them to serial digital data.
The controller does not provide loop power for analog inputs. Use a power supply that
matches the transmitter specifications as shown below.
21
Minimizing Electrical Noise on Analog Channels
Inputs on analog channels employ digital high-frequency filters that significantly reduce the
effects of electrical noise on input signals. However, because of the variety of applications and
environments where analog controllers are installed and operated, it is impossible to ensure
that all environmental noise will be removed by the input filters.
Several specific steps can be taken to help reduce the effects of environmental noise on
analog signals:
Publication 1763-IN001C-EN-P - June 2015
Page 20
22
IMPORTANT
Foil Shield
Black Wire
Drain Wire
Clear Wire
Insulation
• install the MicroLogix 1100 system in a properly rated (NEMA) enclosure. Make sure
that the MicroLogix 1100 system is properly grounded.
• use Belden cable #8761 for wiring the analog channels, making sure that the drain
wire and foil shield are properly earth grounded.
• route the Belden cable separately from any ac wiring. Additional noise immunity can
be obtained by routing the cables in grounded conduit.
Grounding Your Analog Cable
Use shielded communication
cable (Belden #8761). The Belden
cable has two signal wires (black
and clear), one drain wire, and a
foil shield. The drain wire and foil
shield must be grounded at one
end of the cable.
Do not ground the drain wire and foil shield at both ends of the cable.
Publication 1763-IN001C-EN-P - June 2015
Page 21
Specifications
General Specifications
Description1763-
L16AWAL16BWAL16BBBL16DWD
DimensionsHeight: 90 mm (3.5 in.), 104 mm (4.09 in.) (with DIN latch open)
Width: 110 mm (4.33 in.), Depth: 87 mm (3.43 in.)
Shipping Weight0.9 kg (2.0 lbs)
Number of I/O12 inputs (10 digital and 2 analog) and 6 outputs
23
Power Supply
Voltage
Heat DissipationRefer to the MicroLogix 1100 Programmable Controllers User Manual, Publication
Power Supply
Inrush Current
Power
Consumption
24V dc Sensor
Power
Input Circuit TypeDigital: 120V ac
Output Circuit
Type
100...240V ac (-15%, +10%) at 47...63 Hz24V dc (-15%,
+10%) Class 2 SELV
1763-UM001.
120V ac: 25 A for 8 ms
240V ac: 40 A for 4 ms
46 VA52 VA35W
none250 mA at 24V DC
400 µF max.
Digital: 24V dc
sink/source
(standard and
high-speed)
Analog: 0...10V dc
RelayRelayRelay/FETRelay
Analog: 0...10V dc
24V dc:
15 A for 20 ms
none
Digital: 24V dc
sink/source
(standard and
high-speed)
Analog: 0...10V dc
12V to 24V dc
( -15%, +10%)
Class 2 SELV
Digital: 12/24V dc
sink/source
(standard and
high-speed)
Analog: 0...10V dc
Pilot Duty RatingOrdinary location – B300, R150
Hazardous location – C300, R150
Temperature,
Operating
Temperature,
Storage
Relative Humidity5...95% non-condensing
VibrationOperating: 10... 500 Hz, 5 g, 0.015 in. max. peak-to-peak, 2 hours each axis
Shock, Operating30 g; 3 pulses each direction, each axis
-20... +65 °C (-4 ...+149 °F)
-40...+85 °C (-40... +185 °F)
Relay Operation: 1.5 g
Relay Operation: 10 g
Publication 1763-IN001C-EN-P - June 2015
Page 22
24
General Specifications
Description1763-
L16AWAL16BWAL16BBBL16DWD
Shock,
Nonoperating
Terminal Screw
Torque
CertificationsUL Listed Industrial Control Equipment for use in Class 1, Division 2, Hazardous
ESD ImmunityEN 61000-4-2
Radiated RF
Immunity
Fast Transient
Immunity
50 g panel mounted (40 g DIN Rail mounted); 3 pulses each direction,
each axis
0.56 Nm (5.0 in-lb) rated
Locations, Groups A, B, C, D
C-UL Listed Industrial Control Equipment for use in Canada
CE marked for all applicable directives
RCM marked for all applicable acts
EAC certified for: Russian Customs Union TR CU 020/2011 EMC Technical Regulation,
Russian Customs Union TR CU 004/2011 LV Technical Regulation
10V/m, 26 to 1000 MHz (alternatively, 80 to 1000 MHz),
80% amplitude modulation, +900 MHz keyed carrier
EN 61000-4-4
2 kV, 5 kHz
communications cable such as EtherNet, RS-232, and RS-485: 1 kV, 5 kHz
Surge Transient
Immunity
Conducted RF
Immunity
EN 61000-4-5
Unshielded communications cable: 2 kV CM (common mode), 1 kV DM (differential
mode)
Shielded communications cable: 1 kV galvanic gun
I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
ac Power Supply Input: 4 kV CM (common mode), 2 kV DM (differential mode)
dc Power Supply Input: 500V CM (common mode), 500V DM (differential mode)
ac/dc Auxiliary Output: 500V CM (common mode), 500V DM (differential mode)
EN 61000-4-6
10V, 150 kHz...80 MHz
Publication 1763-IN001C-EN-P - June 2015
Page 23
General Specifications
Description1763-
L16AWAL16BWAL16BBBL16DWD
25
Conducted
Emissions
Radiated
Emissions
Line Related TestsEN 61000-4-11
EN 55011
ac Power Supply Input: 150 kHz...30 MHz
EN 55011
30...1000 MHz
ac Power Supply Input:
voltage drop: -30% for 10 ms, -60% for 100 ms
voltage interrupt: at voltage greater than -95% for 5 secs.
voltage fluctuation: +10% for 15 minutes, -10% for 15 minutes
dc Power Supply Input:
voltage fluctuation: +20% for 15 minutes, -20% for 15 minutes
Input Specifications
Digital Inputs
Description1763-L16AWA1763-L16BWA, -L16BBB
Inputs 0 through 3
(4 high-speed dc inputs)
Inputs 4 and higher
(6 standard dc inputs)
On-State Voltage
Range
Off-State Voltage
Range
Operating
Frequency
On-State Current:
• minimum
• nominal
• maximum
79 ...132V ac14...24V dc
(14...26.4V dc (+10%) at
65 °C/149 °F)
(14...30V dc (+25%) at
30 °C/86 °F)
0...20V ac0...5V dc
47...63 Hz0 Hz...20 kHz
0 Hz...40 kHz
• 5.0 mA at 79V
ac
• 12 mA at 120V
ac
• 16.0 mA at
132V ac
• 2.5 mA at 14V dc
• 8.8 mA at 24V dc
• 12.0 mA at 30V dc
10...24V dc
(10...26.4V dc (+10%) at
65 °C/149 °F)
(10...30V dc (+25%) at
30 °C/86 °F)
0 Hz...1 kHz
(1)
(scan time dependent)
• 2.0 mA at 10V dc
• 8.5 mA at 24V dc
• 12.0 mA at 30V dc
Publication 1763-IN001C-EN-P - June 2015
Page 24
26
Digital Inputs
Description1763-L16AWA1763-L16BWA, -L16BBB
Inputs 0 through 3
(4 high-speed dc inputs)
Off-State Leakage
2.5 mA max.1.5 mA max.
Current
Nominal
Impedance
Inrush Current
12 kΩ at 50 Hz
3.1 kΩ3.1 kΩ
10 kΩ at 60 Hz
250 mANot Applicable
(max.) at 120V ac
(1)
OS Series B FRN 4 or later
Digital Input Specifications for 1763-L16DWD
Description1763-L16DWD
Inputs 0 through 3
(4 high-speed dc inputs)
On-State Voltage Range10...24V dc at 65 °C/149 °F)
(10...30V dc at 30 °C/86 °F)
Inputs 4 and higher
(6 standard dc inputs)
Inputs 4 and higher
(6 standard dc inputs)
Off-State Voltage Range0...5V dc
Operating Frequency
0 Hz...40 kHz
(1)
0 Hz...1 kHz
On-State Current:
• minimum
• nominal
• maximum
• 2.0 mA at 10V dc
• 8.5 mA at 24V dc
• 12.0 mA at 30V dc
Off-State Leakage Current1.5 mA max.
Nominal Impedance2.61 kΩ3.1 kΩ
Maximum Inrush CurrentNot Applicable
(1)
OS Series B FRN 4 or later.
Publication 1763-IN001C-EN-P - June 2015
Page 25
Analog Inputs
Description1763-L16AWA, -L16BWA, -L16BBB, -L16DWD
Voltage Input Range0 ...10.0V dc - 1 LSB
Type of Data10-bit unsigned integer
Input Coding (0 to 10.0V dc - 1 LSB)0 ...+1,023
Voltage Input Impedance210 kΩ
Input Resolution10 bit
27
Non-linearity
Overall Accurarcy
-20...+65 °C (-4...+149 °F)
Voltage Input Overvoltage Protection10.5V dc
Field Wiring to Logic IsolationNon-isolated with logic
Out
put Specificat
ions For Hazardous Locations Applications
±0.5% of full scale
±0.5% of full scale
(Class I, Division 2, Groups A, B, C, D)
General
Description1763
-L16AWA, -L16BWA,
-L16DWD
Relay and FET Outputs
Maximum Controlled Load1080 VA360 VA
Maximum Continuous Current:
-L16BBB
Current per Group Common3A3A
Current per Controllerat 150V max18 A or total of per-point loads, whichever is less
at 240V max18 A or total of per-point loads, whichever is less
Relay Outputs
Turn On Time/Turn Off Time
Relay life - Electrical (Resistive Load)Refer to Relay Life Chart
Relay life - Mechanical10,000,000 cycles
Load Current10 mA (minimum)
For AC voltage applications lower than 240V AC but higher than 120V AC, the maximum make and break ratings are to be
obtained by dividing the volt-amperes rating by the application voltage.
For AC voltage applications lower than 120V AC, the maximum make current is to be the same as for 120V AC, and the
maximum break current is to be obtained by dividing the break volt-amperes rating by the application voltage, but the
currents are not to exceed the thermal continuous current.
For DC voltage applications lower than 125V DC, the make/break ampere rating for relay contacts can be determined by
dividing the volt-ampere rating by the applied DC voltage but the current values are not to exceed the thermal continuous
current.
7.5 A0.75 A2.5 A1800 VA180 VA
15.0 A1.5 A2.5 A1800 VA180 VA
0.22 A1.0 A28 VA
Continuous
Volt-Amperes
Do not exceed the “Current per group common” specification.
Out
put Specificat
ions For Ordinary (Non-Hazardous) Locations only
General
Description1763
Relay and FET Outputs
Maximum Controlled Load1440 VA720 VA
Maximum Continuous Current:
Current per Group Common
Current per Controllerat 150V max30 A or total of per-point loads, whichever is less
at 240V max20 A or total of per-point loads, whichever is less
Publication 1763-IN001C-EN-P - June 2015
-L16AWA, -L16BWA,
-L16DWD
(1)
5A
-L16BBB
5A
Page 27
ATTENTION
General
Description1763
29
-L16AWA, -L16BWA,
-L16DWD
Relay Outputs
Turn On Time/Turn Off Time
10 msec (maximum)
(2)
Relay life - Electrical (Resistive Load)Refer to Relay Life Chart
Relay life - Mechanical10,000,000 cycles
Load Current10 mA (minimum)
For AC voltage applications lower than 240V AC but higher than 120V AC, the maximum make and break ratings are to be
obtained by dividing the volt-amperes rating by the application voltage.
For AC voltage applications lower than 120V AC, the maximum make current is to be the same as for 120V AC, and the
maximum break current is to be obtained by dividing the break volt-amperes rating by the application voltage, but the
currents are not to exceed the thermal continuous current.
For DC voltage applications lower than 125V DC, the make/break ampere rating for relay contacts can be determined by
dividing the volt-ampere rating by the applied DC voltage but the current values are not to exceed the thermal continuous
current.
3.0 A above 40 °C.
0.22 A1.0 A28 VA
Do not exceed the “Current per group common” specification.
Publication 1763-IN001C-EN-P - June 2015
Page 28
30
Number of operations (x 10
3
)
Switching capacity(A)
1000
10
0
500
300
100
50
30
246810
30 VDC resistive
load
250 VAC resistive load
250 VAC induction
load (cosφ=0.4)
Relay Life Chart
BBB FET Output Specifications
DescriptionGeneral Operationl
Power Supply Voltage24V dc (-15%, +10%)
On-State Voltage Drop:
• at maximum load current
• at maximum surge current
Current Rating per Point
• maximum load
• minimum load
• maximum leakage
• 1V dc
• 2.5V dc
• See graphs below
• 1.0 mA
• 1.0 mA
High Speed Operation
(Output 2 and 3 Only)
• Not Applicable
• Not Applicable
• 100 mA
• 10 mA
• 1.0 mA
(1)
Publication 1763-IN001C-EN-P - June 2015
Page 29
BBB FET Output Specifications
0.25
10˚C
(50˚F)
30˚C
(86˚F)
50˚C
(122˚F)
0.75A, 65˚C (149˚F)
1.5A, 30˚C (86˚F)
70˚C
(158˚F)
80˚C
(176˚F)
0.5
0.75
1.0
1.25
1.5
1.75
2.0
1.0
10˚C
(50˚F)
30˚C
(86˚F)
50˚C
(122˚F)
1.5A, 65˚C (149˚F)
3.0A, 30˚C (86˚F)
70˚C
(158˚F)
80˚C
(176˚F)
2.0
3.0
4.0
5.0
6.0
7.0
8.0
FET Current per Point
(1763-L16BBB)
FET Total Current
(1763-L16BBB)
Current (Amps)
Current (Amps)
TemperatureTemperature
Valid
Range
Valid
Range
DescriptionGeneral Operationl
Maximum Output Current (temperature dependent):
High Speed Operation
(Output 2 and 3 Only)
(1)
Surge Current per Point:
• peak current
• maximum surge duration
• maximum rate of repetition at 30 °C (86 °F)
• maximum rate of repetition at 65 °C (149 °F)
Turn-On Time (maximum)0.1 ms6 µs
Turn-Off Time (maximum)1.0 ms18 µs
Repeatability (maximum)Not Applicable2 µs
Drift (maximum)Not Applicable1 µs per 5 °C (9 °F)
(1)
• 4.0 A
• 10 ms
• once every second
• once every 2
• Not Applicable
• Not Applicable
• Not Applicable
• Not Applicable
seconds
Output 2 and 3 are designed to provide increased functionality over the other FET outputs. Output 2 and 3 may be used like
the other FET transistor outputs, but in addition, within a limited current range, they may be operated at a higher speed.
Output 2 and 3 also provide a pulse train output (PTO) or pulse width modulation output (PWM) function.
Page 30
32
Working Voltage
Working Voltage (1763-L16AWA)
Description1763-L16AWA
Power Supply Input to
Backplane Isolation
Input Group to Backplane
Isolation
Input Group to Input Group
Isolation
Output Group to Backplane
Isolation
Output Group to Output
Group Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second
132V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second
132V ac Working Voltage (basic insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1second
265V ac Working Voltage (basic insulation), 150V ac Working Voltage (IEC
Class 2 reinforced insulation)
Working Voltage (1763-L16DWD)
Description1763-L16DWD
Input Group to Backplane
Isolation and Input Group to
Input Group Isolation
Output Group to Backplane
Isolation
Output Group to Output Group
Isolation
Publication 1763-IN001C-EN-P - June 2015
Verified by one of the following dielectric tests: 1200V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V
a
c Working Voltage (IEC Class 2 reinforced insulation).
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
ac
Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2
265V
reinforced insulation)
Page 31
Notes:
Page 32
1763-L16AWA
1763-L16BWA
1763-L16BBB
109.10 mm
(4.295 in.)
95.00 mm
(3.740 in.)
25.81 mm
(1.016 in.)
Expansion I/O
d'extension d'E/S
E/A Erweiterungsmodule
l'espansione dei
moduli I/O
de expansión de E/S
de expa nsão de E/S
DIN rail center line.
Ligne médiane du rail DIN.
Mittellinie der DIN-Schiene.
Línea central del riel DIN.
Linea centrale della guida DIN.
linha de centro do trilho DIN.
100.00 mm
(3.937 in.)
4.6 mm
(0.181 in.)
Page 33
IP:
S/MASK:
G/WAY:
IP:
S/MASK:
G/WAY:
OUTPUTS
01234567891011
OUTPUTS
01234567891011
INPUTS
01234567891011
INPUTS
01234567891011
Page 34
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its
products. At http://support.rockwellautomation.com
knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of these
tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect support programs. For more information, contact
your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation,
please review the information that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your module up and running:
United States1.440.646.3434
Monday – Friday, 8am – 5pm EST
, you can find technical manuals, a
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when
shipped from the manufacturing facility. However, if your product is not functioning and
needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
(see phone number above to obtain one) to your distributor in order to
complete the return process.
Outside United
States
Allen-Bradley, Rockwell Automation, MicroLogix and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Please contact your local Rockwell Automation representative for return
procedure.