Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, ArmorBlock, ArmorBlock MaXum, ArmorPOINT, Compact I/O, CompactLogix, ControlFLASH, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, DriveLogix, FactoryTalk, FLEX, FLEX Ex,
FlexLogix, GuardLogix, Guard PLC, Integrated Architecture, Kinetix, Logix5000, Logix5550, Logix Designer, MessageView, MicroLogix, PanelView, PhaseManager, PLC-5, POINT I/O, PowerFlex, RediSTATION,
Rockwell Automation, Rockwell Software, RSBizWare, RSFieldbus, RSL inx, RSLogix, R SNetWorx, RSView, RSWho, Series 9000, S LC, Studio 5000, Studio 5000 Automation & Engineering Design Environment, Studio
5000 Log ix Designer, and Stratix 8000 are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Top icPag e
Added DLR segment to EtherNet/IP Network Example.86
Added DH+ Modules and Capabilities table.95
Added Access the Module Object section to Develop Applications chapter.160
Updated screenshots and descriptions for the Studio 5000 environment version 24.Throughout publication
Rockwell Automation Publication 1756-UM001O-EN-P - October 20143
Summary of Changes
Notes:
4Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
10Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Preface
Studio 5000 Environment
The Studio 5000 Automation Engineering & Design Environment™ combines
engineering and design elements into a common environment. The first element
in the Studio 5000® environment is the Studio 5000 Logix Designer™ application.
The Logix Designer application is the rebranding of RSLogix™ 5000 software
and continues to be the product to program Logix5000™ controllers for discrete,
process, batch, motion, safety, and drive-based solutions.
ControlLogix Controllers
Overview
The Studio 5000 environment is the foundation for the future of
Rockwell Automation® engineering design tools and capabilities. This
environment is the one place for design engineers to develop the elements of their
control system.
There are three types of ControlLogix® controllers available. These types include
the following:
• Standard ControlLogix controllers
• Extreme environment ControlLogix controllers
• GuardLogix® controllers
This manual explains how to use standard and extreme environment
ControlLogix controllers.
Rockwell Automation Publication 1756-UM001O-EN-P - October 201411
Preface
For detailed information about GuardLogix safety controllers, see the following
publications.
ResourceDescription
GuardLogix 5570 Controllers User Manual, publication
1756-UM022
GuardLogix 5570 Controller System Safety Reference
Manual, publication 1756-RM099
GuardLogix Controllers User Manual, publication
1756-UM020
GuardLogix Controller Systems Safety Reference Manual,
publication 1756-RM093
GuardLogix Safety Application Instruction Set Safety
Reference Manual, publication 1756-RM095
Provides information on how to install, configure, and
operate GuardLogix 5570 controllers in Studio 5000,
version 21 or later projects.
Provides information on how to meet safety application
requirements for GuardLogix 5570 controllers in Studio
5000, version 21 or later projects.
Provides information on how to install, configure, and
operate GuardLogix 5560 and GuardLogix 5570 controllers
in RSLogix 5000, version 20 or earlier projects.
Provides information on how to meet safety application
requirements for GuardLogix 5560 and GuardLogix 5570
controllers in RSLogix 5000, version 20 or earlier projects.
Provides programmers with details about the GuardLogix
safety application instruction set.
Standard ControlLogix Controllers
Two lines of standard ControlLogix controllers are now available. These
controllers are identified as 1756-L6x controllers and 1756-L7x controllers
according to abbreviations of their full catalog numbers.
The standard ControlLogix controllers share many similar features, but also have
some differences. Table 2 provides a brief overview the differences between the
controllers. For further details about these features and differences, see the
appropriate chapters of this manual.
Table 2 - Differences between 1756-L7x and 1756-L6x Controllers
Feature 1756-L7x1756-L6x
Clock support and backup used for
memory retention at powerdown
Communication ports (built-in)USBSerial
Connections, controller500250
Memory, nonvolatileSecure Digital (SD) cardCompactFlash card
Status display and status indicatorsScrolling status display and four
For information on using ControlLogix controllers in SIL 2 applications, see the
Using ControlLogix in SIL 2 Applications Safety Reference Manual, publication
1756-RM001
12Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
.
Preface
Redundant ControlLogix Controllers
Certain ControlLogix controllers are also supported for use in redundant
systems. For more information about controllers and redundant systems, see
Chapter 12
.
Extreme Environment ControlLogix Controllers
The extreme environment ControlLogix controllers, catalog numbers
1756-L73XT and 1756-L63XT, provide the same functionality as the 1756-L73
and 1756-L63 controllers, but are designed to withstand temperatures
-25…70 °C (-13…158 °F).
Rockwell Automation Publication 1756-UM001O-EN-P - October 201413
Preface
Before You Begin
Before you begin using your ControlLogix controller, verify that you have the
applications that are required to configure and program the controller.
Required Software
Use Ta b l e 3 to identify the minimum software versions that are required to use
your ControlLogix controller.
ControlLogix Chassis and Power Supply Installation
Instructions, publication 1756-IN005
ControlLogix Configurable Flowmeter Module User
Manual, publication 1756-UM010
ControlLogix Data Highway Plus-Remote I/O
Communication Interface Module User Manual,
publication 1756-UM514
ControlLogix DH-485 Communication Module User
Manual, publication 1756-UM532
ControlLogix Digital I/O Modules User Manual, publication
1756-UM058
ControlLogix Enhanced Redundancy System User Manual,
publication 1756-UM535
ControlLogix HART Analog I/O Modules User Manual,
publication 1756-UM533
ControlLogix High-speed Analog I/O Module User Manual,
publication 1756-UM005
ControlLogix High-speed Counter Module User Manual,
publication 1756-UM007
ControlLogix Low-speed Counter Module User Manual,
publication 1756-UM536
ControlLogix Pe er I/O Control Appl ication Technique,
publication 1756-AT016
ControlLogix Programmable Limit Switch Module User
Manual, publication 1756-UM002
ControlLogix Redundancy System User Manual,
publication 1756-UM523
ControlLogix Remote I/O Communication Module User
Manual, publication 1756-UM534
ControlLogix SIL2 System Configuration Using RSLogix
5000 Subroutines Application Technique, publication
1756-AT010
ControlLogix SIL2 System Configuration Using SIL2 AddOn Instructions Application Technique, publication
1756-AT012
ControlLogix System Selection Guide, publication
1756-SG001
ControlNet Network Configuration User Manual,
publication CNET-UM001
Provides specifications for ControlLogix controllers.
Provides specifications for ControlLogix I/O modules.
Provides information about analog I/O module
configuration properties.
Provides information for battery module installation.
Describes how to install and troubleshoot standard and
ControlLogix-XT™ versions of the 1756 chassis and power
supplies, including redundant power supplies.
Provides information about configurable flowmeter
configuration properties.
Provides information about Data Highway Plus
communication and remote I/O communication module
configuration properties.
Provides information for connecting a 1756-DH485
module to a DH-485 network with multiple controllers.
Provides information about digital I/O module
configuration properties.
Provides detailed information about ControlLogix
redundancy systems.
Provides information for using HART analog I/O modules.
Provides information about high-speed analog I/O
module configuration properties.
Provides information about high-speed counter module
configuration properties.
Provides information about low-speed counter module
configuration properties.
Describes typical peer control applications and provides
details about how to configure I/O modules for peer
control operation.
Provides information about programmable limit switch
configuration properties.
Provides information ControlLogix standard redundancy
systems.
Provides information for remote I/O network
communication configuration.
Provides information about ControlLogix SIL2- certified
fault-tolerant systems.
Provides information about ControlLogix SIL2- certified
fault-tolerant systems.
Provides information about designing and selecting
components for your ControlLogix system.
Provides information about using ControlNet modules.
Rockwell Automation Publication 1756-UM001O-EN-P - October 201415
Preface
ResourceDescription
DeviceNet Network Configuration User Manual,
publication DNET-UM004
Provides general guidelines for installing a Rockwell
Automation industrial system.
Provides declarations of conformity, certificates, and other
certification details.
Provides Material Safety Data Sheets (MSDS) for
individual replacement batteries.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Preface
Rockwell Automation Publication 1756-UM001O-EN-P - October 201417
Preface
Notes:
18Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller
Top icPag e
Before You Begin21
1756-L7x Controller Parts21
1756-L7x Controller Installation22
Insert the Controller into the Chassis23
Insert the Key24
Install the SD Card25
Remove the SD Card26
Install the ESM28
Uninstall the ESM29
Chapter 1
ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be
aware of the safety requirements in the application of the system and shall be trained in using the system.
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio
communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibilit y to live par ts. The enclosure must have suitable flame -retardant properties to prevent or minimize the spread
of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosure
Rockwell Automation Publication 1756-UM001O-EN-P - October 201419
Chapter 1Install the 1756-L7x Controller
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups
A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied
with markings on the rating nameplate indicating the hazardous location temperature
code. When combining products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.
Informations sur l’utilisation de cet équipement en environnements
dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
• Do not disconnect connections to this
equipment unless power has been removed or
the area is known to be nonhazardous. Secure
any external connections that mate to this
equipment by using screws, sliding latches,
threaded connectors, or other means provided
with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they must only
be changed in an area known to be
WARNING: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à
l'aide de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non
dangereux avant de changer les piles.
nonhazardous.
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
20Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x ControllerChapter 1
Logix 5575
RUN
FORCE
SD
OK
1756-L7x Controller
1756-ESMCAP
(installed)
1747-KY Key
SD Card (installed)
WARNING:
• This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54
(as defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when
applied in Zone 2 environments. The enclosure must utilize a tool removable cover or door.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• This equipment must be used only with ATEX certified Rockwell Automation backplanes.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other
means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Before You Begin
1756-L7x Controller Parts
See 1756-IN005 to install a ControlLogix chassis and power supply before you
install your controller and power supply.
These sections describe parts that are included with the L7x controllers and
available accessory parts.
Parts Included with the 1756-L7x Controller
These parts are included with the controller:
• 1756-ESMCAP capacitor-based energy storage module (ESM)
• 1784-SD1 Secure Digital (SD) card, 1 GB
• 1747-KY controller key
Figure 1 - Parts with the 1756-L7x Controller
Rockwell Automation Publication 1756-UM001O-EN-P - October 201421
Chapter 1Install the 1756-L7x Controller
IMPORTANT
The 1756-L7x controllers ship with an SD card installed. We recommend that
you leave the SD card installed.
Parts Available for Use with the 1756-L7x Controller
You can choose to use the parts included with the controller and these parts
specific to your application.
.
If your application requiresThen use this part
USB connection from a computer to the controllerUSB c able
Nonvolatile memory1784-SD1 (1 GB) or 1784-SD2 (2 GB)
ESM without WallClockTime back-up power1756-ESMNSE
ESM that secures the controller by blocking the USB
connection and SD card use
This ESM provides your application an enhanced degree of
security.
(2)
(1)
This ESM does not have WallClockTime back-up power.
Use this ESM if your application requires that the installed
ESM deplete its residual stored energy to 40 μJoule or less
before transporting it into or out of your application.
Additionally, you can use this ESM with only a 1756-L73
(8 MB) or smaller memory-sized controller.
1756-ESMNRM
(2)
1756-L7x Controller
Installation
(1) The USB port is intended only for temporary loc al programming purposes and not intended for permanent connection. The USB
cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
(2) For information about the hold-up time of the ESMs, see Hold-up Time (in days) on page 72 and stored energy depletion rate on
page 29
.
WARNING: Do not use the USB port in hazardous locations.
ATT EN TI ON :
• The USB port is intended only for temporary local programming purposes and
not intended for permanent connection.
• The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
These sections explain how to install the 1756-L7x controller. To install the
1756-L7x controller, complete the tasks summarized in this table.
Tas kPag e
Insert the Controller into the Chassis23
Insert the Key24
Remove the SD Card26
Install the SD Card25
Install the ESM28
22Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x ControllerChapter 1
IMPORTANT
Insert the Controller
into the Chassis
When installing a ControlLogix controller, you can do the following:
• Place the controller in any slot.
• Use multiple controllers in the same chassis.
You can install or remove a ControlLogix controller while chassis power is on and
the system is operating.
WARNING: When you insert or remove the module while backplane power
is on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
controller and its mating connector on the chassis. Worn contacts may create
electrical resistance that can affect controller operation.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
The ESM begins charging when one of these actions occurs:
• The controller and ESM are installed into a powered chassis.
• Power is applied to the chassis that contains a controller with the ESM
installed.
• An ESM is installed into a powered controller.
After power is applied, the ESM charges for up to two minutes as indicated by
CHRG or ESM Charging on the status display.
Rockwell Automation Publication 1756-UM001O-EN-P - October 201423
Chapter 1Install the 1756-L7x Controller
Logix 55xx
RU
N
FO
RCE
S
D
OK
Top Circuit Board
Aligned
Bottom Circuit Board
Aligned
Logix 55xx
RUN
FORCE
SD
OK
1. Align the circuit board with the top and bottom guides in the chassis.
2. Slide the module into the chassis until it snaps into place.
3. Verify that the controller is flush with the power supply or other installed
modules.
Insert the Key
After you have inserted the controller into the chassis, reference the Troubleshoot
the Module on page 183 for information to interpret the status indicators.
After the controller is installed, insert the key.
24Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x ControllerChapter 1
Unlocked
Locked
Log
ix 55
xx
RUN
FORCE
SD
OK
Install the SD Card
Complete these steps to install the SD card in the 1756-L7x controllers.
It is recommended that you leave the SD card in the controller, even when it is
not used. If the controller experiences a Major nonrecoverable Fault, extended
fault information is saved to the card.
WARNING: When you insert or remove the Secure Digital (SD) memory
card while power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Verify that the SD card is locked or unlocked according to your preference.
For more information about the lock/unlock memory settings, see the
Load or Store to the Memory Card
on page 65.
2. Open the door for the SD card.
3. Insert the SD card into the SD card slot.
Rockwell Automation Publication 1756-UM001O-EN-P - October 201425
Chapter 1Install the 1756-L7x Controller
Log
ix 55
xx
RUN
FORCE
SD
OK
Log
ix 55
xx
RUN
FORCE
SD
OK
4. Gently press the card until it clicks into place.
5. Close the SD card door.
Remove the SD Card
The 1756-L7x controller ships with an SD card installed. Complete these steps to
remove the SD card from the 1756-L7x controller.
WARNING: When you insert or remove the Secure Digital (SD) memory
card while power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
26Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x ControllerChapter 1
IMPORTANT
TIP
Log
ix 55
xx
RUN
FORCE
SD
OK
• Verify that the SD card status indicator is off and that the card is not in use
before removing it.
• We recommend that you do the following:
–Leave an SD card installed.
– Use the SD cards available from Rockwell Automation (catalog number
1784-SD1 or 1784-SD2).
• While other SD cards can be used with the controller, Rockwell Automation
has not tested the use of those cards with the controller. If you use an SD
card other than those cards that are available from Rockwell Automation,
you can experience data corruption or loss.
• Also, SD cards that are not provided by Rockwell Automation do not have
the same industrial, environmental, and certification ratings as those cards
that are available from Rockwell Automation.
1. Verify that the SD card is not in use by checking to be sure that the
SD indicator is Off.
You can also put the controller into Hard Run mode to keep the
controller from writing to the SD card while it is removed.
2. Open the door to access the SD card.
3. Press and release the SD card to eject it.
Rockwell Automation Publication 1756-UM001O-EN-P - October 201427
Chapter 1Install the 1756-L7x Controller
Logix 55xx
RUN
FO
RCE
SD
O
K
Log
ix 55
xx
RUN
FO
RC
E
SD
OK
4. Remove the SD card and close the door.
Install the ESM
To install an ESM in the 1756-L7x controller, complete these steps.
ATT EN TI ON : To avoid potential damage to the product when inserting the
ESM, align it in the track and slide forward with minimal force until the ESM
snaps into place.
1. Align the tongue-and-groove slots of the ESM and controller.
2. Slide the ESM back until it snaps into place.
The ESM begins charging after installation. The following status messages
indicate charging status:
• ESM Charging
• CHRG
After you install the ESM, it can take up to 15 seconds for the charging
status messages to display.
28Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x ControllerChapter 1
IMPORTANT
TIP
IMPORTANT
.
Allow the ESM to finish charging before removing power from the controller.
Failure to do so can result in the loss of the application program. A type 1,
code 40 major fault is logged on powerup.
To verify that the ESM is fully charged, check the status display to confirm that
messages CHRG or ESM charging are no longer indicated.
We recommend that you check the WallClockTime object attributes after
installing an ESM to verify that time of the controller is correct.
The ESM contains a real-time clock. If the ESM is new or came from another
controller, the WallClockTime object attributes for your controller can change.
Uninstall the ESM
WARNING: If your application requires the ESM to deplete its residual stored
energy to 40 μJoule or less before you transport it into or out of the application,
use only the 1756-(SP)ESMNSE(XT) module. In this case, complete these steps
before you remove the ESM.
• Turn power off to the chassis.
After you turn power off to the chassis, the controller’s OK status indicator
transitions from green to solid red to OFF.
• Wai t at least 20 minutes for the residual stored energy to decrease to
40 μJoule or less before you remove the ESM.
There is no visual indication of when the 20 minutes has expired. You must trac k
that time period.
WARNING: When you insert or remove the energy storage module while
backplane power is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector.
Before you remove an ESM, make necessary adjustments to your program
to account for potential changes to the WallClockTime attribute.
Consider these points before removing the ESM:
• The following ESM modules can be currently installed in your 1756-L7x
or 1756-L7xXT controller:
Rockwell Automation Publication 1756-UM001O-EN-P - October 201429
Chapter 1Install the 1756-L7x Controller
IMPORTANT
• The 1756-L7x controllers come with the 1756-ESMCAP module
installed. The 1756-L7xXT extreme temperature controller ships with a
1756-ESMCAPXT module installed. For more information on how to
use a 1756-ESMNSE, 1756-ESMNRM, 1756-ESMNSEXT, or
1756-ESMNRMXT module, see page 28
.
• After the 1756-L7x or 1756-L7xXT controllers lose power, because the
chassis power is turned off or the controller has been removed from a
powered chassis, do not immediately remove the ESM.
Wait until the OK status indicator on the controller transitions from
Green to Solid Red to OFF before you remove the ESM.
• You can use the 1756-ESMNSE module with only a 1756-L73 (8 MB) or
smaller memory-sized controller.
• Use the 1756-ESMNSE module if your application requires that the
installed ESM deplete its residual stored energy to 40 μJoule or less before
transporting it into or out of your application.
• Once it is installed, you cannot remove the 1756-ESMNRM or
1756-ESMNRMXT module from a 1756-L7x or 1756-L7xXT controller.
Complete these steps to remove an ESM module from the controller.
1. Remove the key from the mode switch.
The next step depends on which of the following conditions applies to your
application.
• If you are removing the ESM from a powered 1756-L7x controller, go to
step 2
.
• If you are removing the ESM from a 1756-L7x controller that is not
powered, because the chassis power is turned off or the controller has
been removed from a powered chassis, do not immediately remove
the ESM.
Wait until the OK status indicator on the controller transitions from Green to
Solid Red to OFF before you remove the ESM.
After the OK status indicator transitions to Off, go to step 2
.
30Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Loading...
+ 182 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.