Rockwell Automation 1756-L6x, 1756-L7x User Manual

User Manual
ControlLogix System
Catalog Numbers 1756-L61, 1756-L62, 1756-L63, 1756-L63XT, 1756-L64, 1756-L65, 1756-L71, 1756-L72, 1756-L73, 1756-L73XT, 1756-L74, 1756-L75

Important User Information

IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, ArmorBlock, ArmorBlock MaXum, ArmorPOINT, Compact I/O, CompactLogix, ControlFLASH, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, DriveLogix, FactoryTalk, FLEX, FLEX Ex, FlexLogix, GuardLogix, Guard PLC, Integrated Architecture, Kinetix, Logix5000, Logix5550, Logix Designer, MessageView, MicroLogix, PanelView, PhaseManager, PLC-5, POINT I/O, PowerFlex, RediSTATION, Rockwell Automation, Rockwell Software, RSBizWare, RSFieldbus, RSL inx, RSLogix, R SNetWorx, RSView, RSWho, Series 9000, S LC, Studio 5000, Studio 5000 Automation & Engineering Design Environment, Studio 5000 Log ix Designer, and Stratix 8000 are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

This manual contains new and updated information. Changes throughout this revision are marked by change bars, as shown to the right of this paragraph.

New and Updated Information

This table contains the changes made to this revision.
Top ic Pag e
Added DLR segment to EtherNet/IP Network Example. 86
Added DH+ Modules and Capabilities table. 95
Added Access the Module Object section to Develop Applications chapter. 160
Updated screenshots and descriptions for the Studio 5000 environment version 24. Throughout publication
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 3
Summary of Changes
Notes:
4 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Table of Contents

Preface
Install the 1756-L7x Controller
Studio 5000 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ControlLogix Controllers Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Standard ControlLogix Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Redundant ControlLogix Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . 13
Extreme Environment ControlLogix Controllers . . . . . . . . . . . . . . . 13
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Required Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 1
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1756-L7x Controller Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Parts Included with the 1756-L7x Controller . . . . . . . . . . . . . . . . . . . 21
Parts Available for Use with the 1756-L7x Controller . . . . . . . . . . . 22
1756-L7x Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Insert the Controller into the Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Insert the Key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Install the SD Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Remove the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Install the ESM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Uninstall the ESM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Install the 1756-L6x Controller
Start Using the Controller
Chapter 2
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1756-L6x Controller Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Parts Not Included with the 1756-L6x Controller. . . . . . . . . . . . . . . 35
1756-L6x Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
CompactFlash Card Installation and Removal. . . . . . . . . . . . . . . . . . . . . . 36
Battery Connection and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Insert the Controller into the Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Remove the Controller from the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Chapter 3
Make Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
1756-L7x Connection Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
1756-L6x Connection Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Connect to the 1756-L7x Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Configure the USB Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Connect to the 1756-L6x Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Configure the Serial Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Upgrade Controller Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Determine Required Controller Firmware. . . . . . . . . . . . . . . . . . . . . . 52
Obtain Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Use ControlFLASH Software to Upgrade Firmware . . . . . . . . . . . . 53
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 5
Table of Contents
Use AutoFlash to Upgrade Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Set the Communication Path. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Go Online with the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Download to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Use the Who Active Dialog Box to Download . . . . . . . . . . . . . . . . . . 59
Use the Controller Status Menu to Download . . . . . . . . . . . . . . . . . . 60
Upload from the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Use the Who Active Dialog Box to Upload . . . . . . . . . . . . . . . . . . . . . 60
Use the Controller Status Menu to Upload . . . . . . . . . . . . . . . . . . . . . 61
Choose the Controller Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Use the Mode Switch to Change the Operation Mode . . . . . . . . . . . 62
Use Logix Designer to Change the Operation Mode . . . . . . . . . . . . . 64
Load or Store to the Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Store to the Memory Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Load from the Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Other Memory Card Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Use ControlLogix Energy Storage Modules (ESMs) . . . . . . . . . . . . . . . . . 70
Save the Program to On-board NVS Memory . . . . . . . . . . . . . . . . . . . 71
Clear the Program from On-board NVS Memory . . . . . . . . . . . . . . . 71
Estimate the ESM Support of the WallClockTime . . . . . . . . . . . . . . . . . . 72
Maintain the Battery (Only 1756-L6x Controllers) . . . . . . . . . . . . . . . . . 72
Check the Battery Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
1756-BA1 or 1756-BATA Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . 73
1756-BATM Battery Module and Battery Life . . . . . . . . . . . . . . . . . . 74
Estimate 1756-BA2 Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Estimate 1756-BA2 Battery Life After Warnings . . . . . . . . . . . . . . . . 76
Battery Storage and Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Chapter 4
ControlLogix System and Controllers
ControlLogix System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Configuration Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Design a ControlLogix System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
ControlLogix Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
System, Communication, and Programming Features. . . . . . . . . . . . 82
Memory Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Electronic Keying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Chapter 5
Communication Networks
6 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Networks Available. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
EtherNet/IP Network Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ControlLogix EtherNet/IP Module Features. . . . . . . . . . . . . . . . . . . . 86
ControlLogix EtherNet/IP Communication Modules . . . . . . . . . . . 87
Software for EtherNet/IP Networks. . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Connections Over an EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . 88
Double Data Rate (DDR) Backplane Communication. . . . . . . . . . . 88
ControlNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Table of Contents
ControlLogix ControlNet Module Features . . . . . . . . . . . . . . . . . . . . 90
ControlLogix ControlNet Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Software for ControlNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Connections Over a ControlNet Network . . . . . . . . . . . . . . . . . . . . . 92
DeviceNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
ControlLogix DeviceNet Module Features . . . . . . . . . . . . . . . . . . . . . 93
ControlLogix DeviceNet Bridge Module and Linking Devices . . . 94
Software for DeviceNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Connections Over DeviceNet Networks . . . . . . . . . . . . . . . . . . . . . . . 94
ControlLogix DeviceNet Module Memory . . . . . . . . . . . . . . . . . . . . . 94
Data Highway Plus (DH+) Network Communication . . . . . . . . . . . . . . 95
Communicate Over a DH+ Network . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Universal Remote I/O (RIO) Communication . . . . . . . . . . . . . . . . . . . . . 97
Communicate Over a Universal Remote I/O Network . . . . . . . . . . 97
Foundation Fieldbus Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
HART Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Chapter 6
Serial Communication on 1756-L6x Controllers
Manage Controller Communication
1756-L6x Controller Serial Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
ControlLogix Chassis Serial Communication Options . . . . . . . . . 102
Communication with Serial Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
DF1 Master Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
DF1 Point to Point Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
DF1 Radio Modem Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
DF1 Radio Modem Advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
DF1 Radio Modem Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
DF1 Radio Modem Protocol Parameters . . . . . . . . . . . . . . . . . . . . . . 108
DF1 Slave Protocol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
DH-485 Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
ASCII Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Configure the 1756-L6x Controller for Serial Communication . . . . . 113
Broadcast Messages Over a Serial Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Configure Controller Serial Port Properties . . . . . . . . . . . . . . . . . . . 115
Program the Message Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Modbus Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Chapter 7
Connection Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Produce and Consume (Interlock) Data . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Connection Requirements of a Produced or Consumed Tag . . . . 120
Send and Receive Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Determine Whether to Cache Message Connections . . . . . . . . . . . 122
Calculate Connection Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Local Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Remote Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Connections Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 7
Table of Contents
Chapter 8
I/O Modules
Develop Motion Applications
Selecting ControlLogix
I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Add Local I/O to the I/O Configuration . . . . . . . . . . . . . . . . . . . . . . 128
Remote I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Add Remote I/O to the I/O Configuration . . . . . . . . . . . . . . . . . . . . 130
Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Add Distributed I/O to the I/O Configuration . . . . . . . . . . . . . . . . 133
Reconfigure an I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Reconfigure an I/O Module Via the Module Properties . . . . . . . . . 135
Reconfigure an I/O Module Via a Message Instruction. . . . . . . . . . 137
Add to the I/O Configuration While Online . . . . . . . . . . . . . . . . . . . . . . 137
Modules and Devices that Can be Added While Online. . . . . . . . . 137
Online Additions - ControlNet Considerations . . . . . . . . . . . . . . . . 138
Online Additions—EtherNet/IP Considerations . . . . . . . . . . . . . . 141
Determine When Data is Updated. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Chapter 9
Motion Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Motion Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Obtain Axis Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Program Motion Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Develop Applications
Chapter 10
Elements of a Control Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Tasks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Task Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Scheduled and Unscheduled Programs . . . . . . . . . . . . . . . . . . . . . . . . 153
Routines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Parameters and Local Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Extended Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Access Extended Properties in Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Programming Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Add-On Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Access the Module Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Create the Add-On Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Monitoring Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Monitoring I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Determine if I/O Communication has Timed Out . . . . . . . . . . . . . 163
Determine if I/O Communication to a Specific I/O Module has
Timed Out. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Interrupt the Execution of Logic and Execute the Fault Handler. 164
System Overhead Time Slice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
8 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Table of Contents
Configure the System Overhead Time Slice. . . . . . . . . . . . . . . . . . . . 166
Sample Controller Projects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Chapter 11
Using the PhaseManager Tool
Redundant Systems
Troubleshoot the Module
PhaseManager Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Minimum System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
State Model Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
How Equipment Changes States. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Manually Change States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
PhaseManager Tool versus Other State Models . . . . . . . . . . . . . . . . . . . . 174
Equipment Phase Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Chapter 12
ControlLogix Redundancy Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
System Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
System Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Enhanced Versus Standard Redundancy. . . . . . . . . . . . . . . . . . . . . . . 179
Build a Redundant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
ControlNet Considerations in Redundant Systems . . . . . . . . . . . . . . . . 180
EtherNet/IP Considerations in Redundant Systems . . . . . . . . . . . . . . . 180
IP Address Swapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Redundancy and Scan Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Appendix A
Use Logix Designer Application for Troubleshooting . . . . . . . . . . . . . . 183
Fault Type Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
1756-L7x Controller Status Display and Indicators . . . . . . . . . . . . . . . . 186
1756-L7x Controller Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
General Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Major Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
I/O Fault Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
1756-L7x Controller Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
RUN Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
FORCE Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
SD Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
OK Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
1756-L6x Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
RUN Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
I/O Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
FORCE Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
RS232 Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
BAT Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
OK Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 9
Table of Contents
Appendix B
History of Changes
Index
1756-UM001N-EN-P, November, 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . 200
1756-UM001M-EN-P, February 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
1756-UM001L-EN-P, November 2011 . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
1756-UM001K-EN-P, May 2011. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
1756-UM001J-EN-P, July 2010 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
1756-UM001I-EN-P, January 2007. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
1756-UM001H-EN-P, July 2008 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
1756-UM001G-EN-P, January 2007. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
1756-UM001F-EN-P, May 2005 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
1756-UM001E-EN-P, August 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
1756-UM001D-EN-P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
1756-UM001C-EN-P, June 2001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
1756-UM001B-EN-P, November 2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
10 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Preface

Studio 5000 Environment

The Studio 5000 Automation Engineering & Design Environment™ combines engineering and design elements into a common environment. The first element in the Studio 5000® environment is the Studio 5000 Logix Designer™ application. The Logix Designer application is the rebranding of RSLogix™ 5000 software and continues to be the product to program Logix5000™ controllers for discrete, process, batch, motion, safety, and drive-based solutions.

ControlLogix Controllers Overview

The Studio 5000 environment is the foundation for the future of Rockwell Automation® engineering design tools and capabilities. This environment is the one place for design engineers to develop the elements of their control system.
There are three types of ControlLogix® controllers available. These types include the following:
Standard ControlLogix controllers
Extreme environment ControlLogix controllers
GuardLogix® controllers
This manual explains how to use standard and extreme environment ControlLogix controllers.
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 11
Preface
For detailed information about GuardLogix safety controllers, see the following publications.
Resource Description
GuardLogix 5570 Controllers User Manual, publication
1756-UM022
GuardLogix 5570 Controller System Safety Reference Manual, publication 1756-RM099
GuardLogix Controllers User Manual, publication
1756-UM020
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
GuardLogix Safety Application Instruction Set Safety Reference Manual, publication 1756-RM095
Provides information on how to install, configure, and operate GuardLogix 5570 controllers in Studio 5000, version 21 or later projects.
Provides information on how to meet safety application requirements for GuardLogix 5570 controllers in Studio 5000, version 21 or later projects.
Provides information on how to install, configure, and operate GuardLogix 5560 and GuardLogix 5570 controllers in RSLogix 5000, version 20 or earlier projects.
Provides information on how to meet safety application requirements for GuardLogix 5560 and GuardLogix 5570 controllers in RSLogix 5000, version 20 or earlier projects.
Provides programmers with details about the GuardLogix safety application instruction set.
Standard ControlLogix Controllers
Two lines of standard ControlLogix controllers are now available. These controllers are identified as 1756-L6x controllers and 1756-L7x controllers according to abbreviations of their full catalog numbers.
Table 1 - ControlLogix Catalog Numbers
Abbreviated Cat. No. Cat. No.
1756-L6x 1756-L61, 1756-L62,1756-L63, 1756-L64,1756-L65
1756-L7x 1756-L71, 1756-L72, 1756-L73,1756-L74, 1756-L75
The standard ControlLogix controllers share many similar features, but also have some differences. Table 2 provides a brief overview the differences between the controllers. For further details about these features and differences, see the appropriate chapters of this manual.
Table 2 - Differences between 1756-L7x and 1756-L6x Controllers
Feature 1756-L7x 1756-L6x
Clock support and backup used for memory retention at powerdown
Communication ports (built-in) USB Serial
Connections, controller 500 250
Memory, nonvolatile Secure Digital (SD) card CompactFlash card
Status display and status indicators Scrolling status display and four
Unconnected buffer defaults 20 (40, max) 10 (40, max)
Energy Storage Module (ESM) Battery
Six status indicators
status indicators
For information on using ControlLogix controllers in SIL 2 applications, see the Using ControlLogix in SIL 2 Applications Safety Reference Manual, publication
1756-RM001
12 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
.
Preface
Redundant ControlLogix Controllers
Certain ControlLogix controllers are also supported for use in redundant systems. For more information about controllers and redundant systems, see
Chapter 12
.
Extreme Environment ControlLogix Controllers
The extreme environment ControlLogix controllers, catalog numbers 1756-L73XT and 1756-L63XT, provide the same functionality as the 1756-L73 and 1756-L63 controllers, but are designed to withstand temperatures
-25…70 °C (-13…158 °F).
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 13
Preface

Before You Begin

Before you begin using your ControlLogix controller, verify that you have the applications that are required to configure and program the controller.
Required Software
Use Ta b l e 3 to identify the minimum software versions that are required to use your ControlLogix controller.
Table 3 - Required Software for Controller Use
Cat. No. Studio 5000 Environment RSLogix 5000 Software RSLinx® Classic
1756-L61/A Version 12.06.00 or later Any version
1756-L61/B Version 13.04.00 or later
1756-L62/A Version 12.06.00 or later
1756-L62/B Version 13.04.00 or later
1756-L63/A If not using a CompactFlash
card, version 10.07.00 or later
If using a CompactFlash card, version 11.16.00 or later
1756-L63/B Version 13.04.00 or later
1756-L63XT/B Version 13.04.00 or later Version 2.55.00 or later
1756-L64/B Version 16.03.00 or later Any version
1756-L65/B Version 17.01.02 or later
1756-L71 Version 21.00.00 or later Version 20.01.02 Version 2.59.00 or later
1756-L72 Version 21.00.00 or later Version 19.01.00 or later Version 2.57.00 or later
1756-L73 Version 21.00.00 or later Version 19.01.00 or later
1756-L73XT Version 21.00.00 or later Version 19.01.00 or later
1756-L74 Version 21.00.00 or later Version 19.01.00 or later
1756-L75 Version 21.00.00 or later Version 19.01.00 or later
14 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Preface

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
1756 ControlLogix Controllers Technical Data, publication
1756-TD001
1756 ControlLogix I/O Specifications Technical Data, publication 1756-TD002
ControlLogix Analog I/O Modules User Manual, publication 1756-UM009
ControlLogix Battery Module Installation Instructions, publication 1756-IN576
ControlLogix Chassis and Power Supply Installation Instructions, publication 1756-IN005
ControlLogix Configurable Flowmeter Module User Manual, publication 1756-UM010
ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual, publication 1756-UM514
ControlLogix DH-485 Communication Module User Manual, publication 1756-UM532
ControlLogix Digital I/O Modules User Manual, publication
1756-UM058
ControlLogix Enhanced Redundancy System User Manual, publication 1756-UM535
ControlLogix HART Analog I/O Modules User Manual, publication 1756-UM533
ControlLogix High-speed Analog I/O Module User Manual, publication 1756-UM005
ControlLogix High-speed Counter Module User Manual, publication 1756-UM007
ControlLogix Low-speed Counter Module User Manual, publication 1756-UM536
ControlLogix Pe er I/O Control Appl ication Technique, publication 1756-AT016
ControlLogix Programmable Limit Switch Module User Manual, publication 1756-UM002
ControlLogix Redundancy System User Manual, publication 1756-UM523
ControlLogix Remote I/O Communication Module User Manual, publication 1756-UM534
ControlLogix SIL2 System Configuration Using RSLogix 5000 Subroutines Application Technique, publication
1756-AT010
ControlLogix SIL2 System Configuration Using SIL2 Add­On Instructions Application Technique, publication
1756-AT012
ControlLogix System Selection Guide, publication
1756-SG001
ControlNet Network Configuration User Manual, publication CNET-UM001
Provides specifications for ControlLogix controllers.
Provides specifications for ControlLogix I/O modules.
Provides information about analog I/O module configuration properties.
Provides information for battery module installation.
Describes how to install and troubleshoot standard and ControlLogix-XT™ versions of the 1756 chassis and power supplies, including redundant power supplies.
Provides information about configurable flowmeter configuration properties.
Provides information about Data Highway Plus communication and remote I/O communication module configuration properties.
Provides information for connecting a 1756-DH485 module to a DH-485 network with multiple controllers.
Provides information about digital I/O module configuration properties.
Provides detailed information about ControlLogix redundancy systems.
Provides information for using HART analog I/O modules.
Provides information about high-speed analog I/O module configuration properties.
Provides information about high-speed counter module configuration properties.
Provides information about low-speed counter module configuration properties.
Describes typical peer control applications and provides details about how to configure I/O modules for peer control operation.
Provides information about programmable limit switch configuration properties.
Provides information ControlLogix standard redundancy systems.
Provides information for remote I/O network communication configuration.
Provides information about ControlLogix SIL2- certified fault-tolerant systems.
Provides information about ControlLogix SIL2- certified fault-tolerant systems.
Provides information about designing and selecting components for your ControlLogix system.
Provides information about using ControlNet modules.
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 15
Preface
Resource Description
DeviceNet Network Configuration User Manual, publication DNET-UM004
Ethernet Design Considerations Reference Manual, publication ENET-RM002
EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual, publication 1788-UM057
EtherNet/IP Network Configuration User Manual, publication ENET-UM001
FOUNDATION Fieldbus Design Considerations Reference Manual, publication PROCES-RM005
Guidelines for Handling Lithium Batteries Technical Data, publication AG-5.4
Integrated Architecture and CIP Sync Configuration Application Technique, publication IA-AT003
Integrated Motion on the EtherNet/IP Network Configuration and Startup User Manual, publication
MOTION-UM003
Logix5000 Controllers Add-On Instructions Programming Manual, publication 1756-PM010
Logix5000 Controllers General Instructions Reference Manual, publication 1756-RM003
Logix5000 Controllers I/O and Tag Data Programming Manual, publication 1756-PM004
Logix5000 Controllers Major, Minor and I/O Faults Programming Manual, publication 1756-PM014
Logix5000 Controllers Messages Programming Manual, publication 1756-PM012
Logix5000 Controllers Motion Instructions Reference Manual, publication MOTION-RM002
Logix5000 Controllers Nonvolatile Memory Card Programming Manual, publication 1756-PM017
Logix5000 Controllers Produced and Consumed Tags Programming Manual, publication 1756-PM011
Motion Coordinate System User Manual, publication
MOTION-UM002
PhaseManager User Manual, publication LOG IX- UM0 01
Runtime/On-line Addition of ControlLogix (1756) I/O over ControlNet and EtherNet/IP White Paper, publication
LOG IX- WP0 06
SERCOS and Analog Motion Configuration and Startup User Manual, publication MOTION-UM001
Using ControlLogix in SIL2 Applications Safety Reference Manual, publication 1756-RM001
Using Logix5000 Controllers as Masters or Slaves on Modbus Application Solution, publication CIG-AP129
Provides information about DeviceNet modules and devices.
Provides additional information about network design for your system.
Provides more information about using the available Foundation Fieldbus devices.
Provides information about EtherNet/IP communication modules.
Provides more information about using the available Foundation Fieldbus devices.
Provides information regarding storage, handling, transportation, and disposal of lithium batteries.
Describes how to configure CIP Sync with Integrated Architecture® products and applications.
Details how to design your ControlLogix system for Integrated Motion on the EtherNet/IP network applications.
Provides more information about using add-on instructions.
Provides more information about GSV instructions, SSV instructions, objects, and attributes.
Provides information for creating and configuring program tags for optimal task and program execution.
Provides more information for I/O faults.
Provides information for controller messages.
Provides programmers with details about the motion instructions that are available for a Logix5000 controller.
Provides information about changing the project that is available to load from nonvolatile memory,
Provides more information for produced and consumed tags.
Details how to create and configure a coordinated motion application system.
Provides more information about instructions for use with equipment phases.
Provides information for adding to the I/O Configuration while online.
Details how to configure a sercos motion application system.
Provides specific configuration and programming considerations.
For more information about using Modbus sample programs.
16 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Resource Description
Industrial Automation Wiring and Grounding Guidelines Application Data, publication 1770-4.1
Product Certifications website,
http://www.rockwellautomation.com/ rockwellautomation/certification/overview.page
Programmable Controllers Battery Reference,
http://www.ab.com/programmablecontrol/ batteries.html
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
Provides Material Safety Data Sheets (MSDS) for individual replacement batteries.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Preface
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 17
Preface
Notes:
18 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller
Top ic Pag e
Before You Begin 21
1756-L7x Controller Parts 21
1756-L7x Controller Installation 22
Insert the Controller into the Chassis 23
Insert the Key 24
Install the SD Card 25
Remove the SD Card 26
Install the ESM 28
Uninstall the ESM 29
Chapter 1
ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibilit y to live par ts. The enclosure must have suitable flame -retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1
, for additional
installation requirements
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosure
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 19
Chapter 1 Install the 1756-L7x Controller
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has
been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be
WARNING: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
nonhazardous.
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
20 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller Chapter 1
Logix 5575
RUN
FORCE
SD
OK
1756-L7x Controller
1756-ESMCAP (installed)
1747-KY Key
SD Card (installed)
WARNING:
This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54
(as defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure must utilize a tool removable cover or door.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
This equipment must be used only with ATEX certified Rockwell Automation backplanes.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other
means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

Before You Begin

1756-L7x Controller Parts

See 1756-IN005 to install a ControlLogix chassis and power supply before you install your controller and power supply.
These sections describe parts that are included with the L7x controllers and available accessory parts.
Parts Included with the 1756-L7x Controller
These parts are included with the controller:
1756-ESMCAP capacitor-based energy storage module (ESM)
1784-SD1 Secure Digital (SD) card, 1 GB
1747-KY controller key
Figure 1 - Parts with the 1756-L7x Controller
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 21
Chapter 1 Install the 1756-L7x Controller
IMPORTANT
The 1756-L7x controllers ship with an SD card installed. We recommend that you leave the SD card installed.
Parts Available for Use with the 1756-L7x Controller
You can choose to use the parts included with the controller and these parts specific to your application.
.
If your application requires Then use this part
USB connection from a computer to the controller USB c able
Nonvolatile memory 1784-SD1 (1 GB) or 1784-SD2 (2 GB)
ESM without WallClockTime back-up power 1756-ESMNSE
ESM that secures the controller by blocking the USB connection and SD card use
This ESM provides your application an enhanced degree of security.
(2)
(1)
This ESM does not have WallClockTime back-up power. Use this ESM if your application requires that the installed
ESM deplete its residual stored energy to 40 μJoule or less before transporting it into or out of your application. Additionally, you can use this ESM with only a 1756-L73 (8 MB) or smaller memory-sized controller.
1756-ESMNRM
(2)

1756-L7x Controller Installation

(1) The USB port is intended only for temporary loc al programming purposes and not intended for permanent connection. The USB
cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
(2) For information about the hold-up time of the ESMs, see Hold-up Time (in days) on page 72 and stored energy depletion rate on
page 29
.
WARNING: Do not use the USB port in hazardous locations.
ATT EN TI ON :
The USB port is intended only for temporary local programming purposes and
not intended for permanent connection.
The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
These sections explain how to install the 1756-L7x controller. To install the 1756-L7x controller, complete the tasks summarized in this table.
Tas k Pag e
Insert the Controller into the Chassis 23
Insert the Key 24
Remove the SD Card 26
Install the SD Card 25
Install the ESM 28
22 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller Chapter 1
IMPORTANT

Insert the Controller into the Chassis

When installing a ControlLogix controller, you can do the following:
Place the controller in any slot.
Use multiple controllers in the same chassis.
You can install or remove a ControlLogix controller while chassis power is on and the system is operating.
WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the controller and its mating connector on the chassis. Worn contacts may create electrical resistance that can affect controller operation.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
The ESM begins charging when one of these actions occurs:
The controller and ESM are installed into a powered chassis.
Power is applied to the chassis that contains a controller with the ESM
installed.
An ESM is installed into a powered controller.
After power is applied, the ESM charges for up to two minutes as indicated by CHRG or ESM Charging on the status display.
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 23
Chapter 1 Install the 1756-L7x Controller
Logix 55xx
RU
N
FO
RCE
S
D
OK
Top Circuit Board Aligned
Bottom Circuit Board Aligned
Logix 55xx
RUN
FORCE
SD
OK
1. Align the circuit board with the top and bottom guides in the chassis.
2. Slide the module into the chassis until it snaps into place.
3. Verify that the controller is flush with the power supply or other installed
modules.

Insert the Key

After you have inserted the controller into the chassis, reference the Troubleshoot
the Module on page 183 for information to interpret the status indicators.
After the controller is installed, insert the key.
24 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller Chapter 1
Unlocked
Locked
Log
ix 55
xx
RUN
FORCE
SD
OK

Install the SD Card

Complete these steps to install the SD card in the 1756-L7x controllers.
It is recommended that you leave the SD card in the controller, even when it is not used. If the controller experiences a Major nonrecoverable Fault, extended fault information is saved to the card.
WARNING: When you insert or remove the Secure Digital (SD) memory card while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Verify that the SD card is locked or unlocked according to your preference.
For more information about the lock/unlock memory settings, see the
Load or Store to the Memory Card
on page 65.
2. Open the door for the SD card.
3. Insert the SD card into the SD card slot.
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 25
Chapter 1 Install the 1756-L7x Controller
Log
ix 55
xx
RUN
FORCE
SD
OK
Log
ix 55
xx
RUN
FORCE
SD
OK
4. Gently press the card until it clicks into place.
5. Close the SD card door.

Remove the SD Card

The 1756-L7x controller ships with an SD card installed. Complete these steps to remove the SD card from the 1756-L7x controller.
WARNING: When you insert or remove the Secure Digital (SD) memory card while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
26 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller Chapter 1
IMPORTANT
TIP
Log
ix 55
xx
RUN
FORCE
SD
OK
Verify that the SD card status indicator is off and that the card is not in use before removing it.
We recommend that you do the following:
Leave an SD card installed. Use the SD cards available from Rockwell Automation (catalog number
1784-SD1 or 1784-SD2).
While other SD cards can be used with the controller, Rockwell Automation has not tested the use of those cards with the controller. If you use an SD card other than those cards that are available from Rockwell Automation, you can experience data corruption or loss.
Also, SD cards that are not provided by Rockwell Automation do not have the same industrial, environmental, and certification ratings as those cards that are available from Rockwell Automation.
1. Verify that the SD card is not in use by checking to be sure that the SD indicator is Off.
You can also put the controller into Hard Run mode to keep the controller from writing to the SD card while it is removed.
2. Open the door to access the SD card.
3. Press and release the SD card to eject it.
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 27
Chapter 1 Install the 1756-L7x Controller
Logix 55xx
RUN
FO
RCE
SD
O
K
Log
ix 55
xx
RUN
FO
RC
E
SD
OK
4. Remove the SD card and close the door.

Install the ESM

To install an ESM in the 1756-L7x controller, complete these steps.
ATT EN TI ON : To avoid potential damage to the product when inserting the ESM, align it in the track and slide forward with minimal force until the ESM snaps into place.
1. Align the tongue-and-groove slots of the ESM and controller.
2. Slide the ESM back until it snaps into place.
The ESM begins charging after installation. The following status messages indicate charging status:
ESM Charging
CHRG
After you install the ESM, it can take up to 15 seconds for the charging status messages to display.
28 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Install the 1756-L7x Controller Chapter 1
IMPORTANT
TIP
IMPORTANT
.
Allow the ESM to finish charging before removing power from the controller. Failure to do so can result in the loss of the application program. A type 1, code 40 major fault is logged on powerup.
To verify that the ESM is fully charged, check the status display to confirm that messages CHRG or ESM charging are no longer indicated.
We recommend that you check the WallClockTime object attributes after installing an ESM to verify that time of the controller is correct.
The ESM contains a real-time clock. If the ESM is new or came from another controller, the WallClockTime object attributes for your controller can change.

Uninstall the ESM

WARNING: If your application requires the ESM to deplete its residual stored
energy to 40 μJoule or less before you transport it into or out of the application, use only the 1756-(SP)ESMNSE(XT) module. In this case, complete these steps before you remove the ESM.
Turn power off to the chassis.
After you turn power off to the chassis, the controller’s OK status indicator transitions from green to solid red to OFF.
Wai t at least 20 minutes for the residual stored energy to decrease to 40 μJoule or less before you remove the ESM.
There is no visual indication of when the 20 minutes has expired. You must trac k
that time period.
WARNING: When you insert or remove the energy storage module while
backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector.
Before you remove an ESM, make necessary adjustments to your program to account for potential changes to the WallClockTime attribute.
Consider these points before removing the ESM:
The following ESM modules can be currently installed in your 1756-L7x or 1756-L7xXT controller:
1756-ESMCAP1756-ESMNSE1756-ESMCAPXT1756-ESMNSEXT
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 29
Chapter 1 Install the 1756-L7x Controller
IMPORTANT
The 1756-L7x controllers come with the 1756-ESMCAP module installed. The 1756-L7xXT extreme temperature controller ships with a 1756-ESMCAPXT module installed. For more information on how to use a 1756-ESMNSE, 1756-ESMNRM, 1756-ESMNSEXT, or 1756-ESMNRMXT module, see page 28
.
After the 1756-L7x or 1756-L7xXT controllers lose power, because the chassis power is turned off or the controller has been removed from a powered chassis, do not immediately remove the ESM.
Wait until the OK status indicator on the controller transitions from Green to Solid Red to OFF before you remove the ESM.
You can use the 1756-ESMNSE module with only a 1756-L73 (8 MB) or smaller memory-sized controller.
Use the 1756-ESMNSE module if your application requires that the installed ESM deplete its residual stored energy to 40 μJoule or less before transporting it into or out of your application.
Once it is installed, you cannot remove the 1756-ESMNRM or 1756-ESMNRMXT module from a 1756-L7x or 1756-L7xXT controller.
Complete these steps to remove an ESM module from the controller.
1. Remove the key from the mode switch.
The next step depends on which of the following conditions applies to your application.
If you are removing the ESM from a powered 1756-L7x controller, go to
step 2
.
If you are removing the ESM from a 1756-L7x controller that is not powered, because the chassis power is turned off or the controller has been removed from a powered chassis, do not immediately remove the ESM.
Wait until the OK status indicator on the controller transitions from Green to Solid Red to OFF before you remove the ESM.
After the OK status indicator transitions to Off, go to step 2
.
30 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Loading...
+ 182 hidden pages