E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X5
Gertebild
][Bildunterschrift_NOT_Sch.tuer_Licht
Safety relay for monitoring E-STOP
pushbuttons, safety gates and light
beam devices
Approvals
PNOZ X5
SÜDDEUTSCHLAND
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 2 safety contacts (N/O), instanta-
neous
` Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Reset button
– Light barriers
` LED indicator for:
– Switch status channel 1/2
– Supply voltage
` See order reference for unit types
Unit description
Bestimmung/Gertebesc hreibung NOT-AUS , Schutzt, Lichtsc hr_PNOZ
The safety relay meets the requirements of EN 60947-5-1, EN 60204-1
and VDE 0113-1 and may be used in
applications with
` E-STOP pushbuttons
` Safety gates
` Light beam devices
Safety features
][Sicherheitseigenschaften Schaltgerät_allgemeiner Teil
The relay meets the following safety
requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component failure.
` The correct opening and closing of
the safety function relays is tested
automatically in each on-off cycle.
Sicherheitseigenschaften Zusatz - Sicherung DC_PNOZ
` The unit has an electronic fuse.
Zulassungen
Block diagram
Blockschaltbild
S11 S12A1 A2
~
Input
S22
Input
S33 S34
Reset/
Start
=
Power
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
13 23
K1
K2
14 24
NSG-D-2-035-2010-08
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X5
Function description
][Funktionen_einkanalig_Erd_Start
` Single-channel operation: no re-
dundancy in the input circuit, earth
faults in the reset circuit are detected.
][Funktionen_zweikanalig_ohne_quer
` Dual-channel operation without de-
tection of shorts across contacts:
redundant input circuit, detects
Timing diagram
POWER
Reset/Start
Input
Output safe
Key
` Power: Supply voltage
` Reset/Start: Reset circuit S33-S34
` Input: Input circuits S11, S12, S22
` Output safe: Safety contacts 13-14,
23-24
` c: Automatic reset
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in
the reset circuit too.
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_manuStart
][Zeitdiagramm_auto_manu
1 2
t1 t2
t1 t2
` d: Manual reset
` a: Input circuit closes before reset
circuit
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
` Manual reset: Unit is active once
the input circuit is closed and then
the reset circuit is closed.
][Funktionen_Kontaktvervielfachung
` Increase in the number of available
instantaneous safety contacts by
connecting contact expansion
modules or external contactors.
ab
t1
t1
t2
t3
` t
2
` t
3
t2
: Delay-on de-energisation
: Recovery time
Wiring
][Verdrahtung_Si_unverz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24 are safety
contacts.
` To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-035-2010-08Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X5
Preparing for operation
Betriebsbereitschaft her stellen
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
` Input circuit
Input circuit Single-channel Dual-channel
E-STOP
without detection of shorts across contacts
Safety gate
without detection of shorts across contacts
S11
S12
S22
S11
S12
S22
S1
S1
S11
S12
S22
A1
A2
S11
S12
S22
S1
L+
L-
S1
S2
Light barrier with detection of shorts
across contacts via ESPE
` Reset circuit
Reset circuit E-STOP wiring (single-channel)
Safety gate (single-channel)
Automatic reset
Manual reset
S33
S34
S33
S34
S3
S12
S12
S22
S22
E-STOP wiring (dual-channel)
Safety gate (dual-channel)
S33
S34
S33
S34
24 V DC
24 V DC
S3
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-035-2010-08