Contact expansion module for increasing the number of available contacts
Approvals
PNOZ s22
Zulassungen
Unit features
Gertemerkmale
Positive-guided relay outputs:
– 6 safety contacts (N/O), instanta-
neous
– 2 auxiliary contacts (N/C), in-
stantaneous
3 safety contacts and 1 auxiliary
contact each; these can be controlled separately
Safety contacts are safely separat-
ed from all other circuits; safety
contacts from Ext.1/O0 are safely
separated from the safety contacts
from Ext.2/O1
Basic insulation between contacts
LED indicator for:
– Input state of channel Ext.1/O0
– Input state of channel Ext.2/O1
Plug-in connection terminals (either
spring-loaded terminals or screw
terminals)
Unit description
Gertebeschreibung
The unit meets the requirements of
EN 60947-5-1, EN 60204-1 and
VDE 0113-1. The contact expansion
module is used to increase the number
of instantaneous safety contacts available on a base unit. Base units are
Speed monitor PNOZ s30
PNOZmulti Mini base units
PNOZ mm0.1p, PNOZ mm0.2p
The category that can be achieved in
accordance with EN 954-1 and
EN ISO 13849-1 depends on the category of the base unit. The contact expansion module may not exceed this.
The unit meets the following safety requirements:
The contact expansion module ex-
pands an existing circuit. As the
output relays are monitored via the
base unit's feedback loop, the safe-
ty functions on the existing circuit
are transferred to the contact ex-
pansion module.
The safety function remains effec-
tive in the case of a component fail-
ure.
Earth fault in the feedback loop:
Detected, depending on the base
unit that is used.
Earth fault in the input circuit:
The output relays de-energise and
the safety contacts open.
Block diagram
Blockschaltbild
][Blockschaltbild_nur sichere Trennung
*Safe separation in accordance with EN 60947-1, 6 kV
1002374-EN-01-2011-05
Contact expansion modules
Interface
PNOZsigma
PNOZ s30/
PNOZ mm0.1p
PNOZ mm0.2p
PNOZs22
Up to PL e of EN ISO 13849-1
PNOZ s22
Function description
Funktionsbeschreibung
Wiring
Verdrahtung
Please note:
Information given in the “Technical
details” must be followed.
The wiring guidelines in the base
units' operating instructions must
be taken into account.
Preparing for operation
Betriebsbereitschaft herstellen PNOZs_BA
Versorgungsspannung/Eingangskreis/
Rückführkreis
Supply voltage/input circuit/feedback
loop
Tension d'alimentation/circuit d'entrée/
boucle de retour
Dual-channel operation and supply
voltage via PNOZsigma connector
Outputs 13 -14, 23 -24, 33 - 34 are
safety contacts; outputs 41 - 42 are
auxiliary contacts (e.g. for display).
To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
ACDC
3 safety contacts and 1 auxiliary
contact each; these can be control-
led separately
Use copper wire that can withstand
60/75 °C.
Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
1002374-EN-01-2011-05
Contact expansion modules
14
24
34
42
13 23 33
41
X3
X1
Ext.1/O0
PNOZ s22
14
24
34
42
13 23 33
41
X2
X4
Ext.2/O1
120 (4.72")
* 100 (3,94")
98 (3.86")
22,5
(0.88")
Up to PL e of EN ISO 13849-1
PNOZ s22
Terminal configuration
Klemmenbelegung
Installation
Montage PNOZsigma_22
Connecting the contact expansion
block to the PNOZ s30 or base unit
PNOZmm0.1p/PNOZ mm0.2p
Connect the contact expansion
block using the connector supplied.
Control cabinet installation
The safety relay should be installed
in a control cabinet with a protection type of at least IP54.
Use the notch on the rear of the unit
to attach it to a DIN rail.
Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by using a fixing element (e.g. retaining
bracket or an end angle).
Push the unit upwards or downwards
before lifting it from the DIN rail.
Dimensions
Abmessungen
*with spring-loaded terminals
1002374-EN-01-2011-05
Contact expansion modules
Up to PL e of EN ISO 13849-1
PNOZ s22
NOTICE
][WICHTIG_PDB_alt
This data sheet is only intended for use
during configuration. For installation
and operation, please refer to the operating instructions supplied with the
unit.
Service life graph
Lebensdauerkurve_R elais_Text vor Kur ve
The service life graphs indicate the
number of cycles from which failures
due to wear must be expected. The
wear is mainly caused by the electrical
load; the mechanical load is negligible.
Lebensdauerkurve
Lebensdauerkurve_Rel ais_Text nach Kurve_SIS_SI R_SLR Bsp
Example
Inductive load: 0,2 A
Utilisation category: AC15
Contact service life: 1,000,000 cy-
cles
Provided the application requires fewer than 1,000,000 cycles, the PFH value (see technical details) can be used
in the calculation.
To increase the service life, sufficient
spark suppression must be provided
on all output contacts. With capacitive
loads, any power surges that occur
must be noted. With contactors, use
freewheel diodes for spark suppression.
1002374-EN-01-2011-05
Contact expansion modules
Up to PL e of EN ISO 13849-1
PNOZ s22
Technical details
Electrical data
Supply voltage
Supply voltage U
Voltage tolerance-15 %/+20 %
Power consumption at U
Number of output contacts
Safety contacts (S) instantaneous:6
Auxiliary contacts (N/C):2
Utilisation category in accordance with EN 60947-4-1
Safety contacts: AC1 at 240 VI
Safety contacts: DC1 at 24 VI
Auxiliary contacts: AC1 at 240 VI
Auxiliary contacts: DC1 at 24 VI
Utilisation category in accordance with EN 60947-5-1
Safety contacts: AC15 at 230 VI
Safety contacts: DC13 at 24 V (6 cycles/min)I
Auxiliary contacts: AC15 at 230 VI
Auxiliary contacts: DC13 at 24 V (6 cycles/min)I
Contact materialAgCuNi + 0.2 µm Au
External contact fuse protection (I
Blow-out fuse, quick
Safety contacts:6 A
Auxiliary contacts:6 A
Blow-out fuse, slow
Safety contacts:4 A
Auxiliary contacts:4 A
Circuit breaker 24 VAC/DC, characteristic B/C
Safety contacts:4 A
Auxiliary contacts:4 A
Safety-related characteristic data
PL in accordance with EN ISO 13849-1: 2006PL e (Cat. 4)
Category in accordance with EN 954-1Cat. 4
SIL CL in accordance with EN IEC 62061SIL CL 3
PFH in accordance with EN IEC 620612.50E-09
SIL in accordance with IEC 61511SIL 3
PFD in accordance with IEC 615112.13E-05
[year] in accordance with EN ISO 13849-1: 200620
T
M
Times
Switch-on delay
with automatic reset typ.11 ms
with automatic reset max.20 ms
Delay-on de-energisation
with E-STOP typ.12 ms
with E-STOP max.20 ms
Environmental data
EMCEN 60947-5-1, EN 61000-6-2, EN 61000-6-4
Vibration to EN 60068-2-6
Frequency10 - 55 Hz
Amplitude0.35 mm
Climatic suitabilityEN 60068-2-78
DC24 V
B
DC1.5 W
B
= 1 kA) to EN 60947-5-1
K
: 0.01 A , I
min
: 1500 VA
P
max
: 0.01 A , I
min
: 150 W
P
max
: 0.01 A , I
min
: 1500 VA
P
max
: 0.01 A , I
min
: 150 W
P
max
: 3.0 A
max
: 4.0 A
max
: 4.0 A
max
: 4.0 A
max
max
max
max
max
: 6.0 A
: 6.0 A
: 6.0 A
: 6.0 A
1002374-EN-01-2011-05
Contact expansion modules
Up to PL e of EN ISO 13849-1
PNOZ s22
Environmental data
Airgap creepage in accordance with EN 60947-1
Pollution degree2
Overvoltage categoryIII
Rated insulation voltage250 V
Rated impulse withstand voltage6.00 kV
Ambient temperature-10 - 55 °C
Storage temperature-40 - 80 °C
Protection type
Mounting (e.g. cabinet)IP54
HousingIP40
TerminalsIP20
Mechanical data
Housing material
HousingPC
FrontPC
Cross section of external conductors with screw terminals
1 core flexible0.25 - 2.50 mm² , 24 - 12 AWG No. 750132
2 core, same cross section, flexible:
with crimp connectors, without insulating sleeve0.25 - 1.00 mm² , 24 - 16 AWG No. 750132
without crimp connectors or with TWIN crimp connectors0.20 - 1.50 mm² , 24 - 16 AWG No. 750132
Torque setting with screw terminals0.50 Nm No. 750132
Cross section of external conductors with spring-loaded terminals: Flexible with/without crimp connectors
Spring-loaded terminals: Terminal points per connection2 No. 751132
Stripping length9 mm No. 751132
Dimensions
Height96.0 mm
Width22.5 mm
Depth120.0 mm
Weight265 g
Technische Daten_Satz No.
0.20 - 2.50 mm² , 24 - 12 AWG No. 751132
No. stands for order number.
Si-Kennzahlen_Zusatz_Re lais_Lebensdauer_PDB
It is essential to consider the relay's
service life graphs. The relay outputs'
safety-related characteristic data is
only valid if the values in the service life
graphs are met.
The PFH value depends on the switching frequency and the load on the relay
output.
If the service life graphs are not accessible, the stated PFH value can be
used irrespective of the switching fre-
The standards current on 2010-04 apply.
quency and the load, as the PFH value
already considers the relay's B10d value as well as the failure rates of the
other components.
Si_Kennzahlen_Er läuterung_PNOZ _s22
NOTICE
The safety-related characteristic data
applies per channel of the contact expansion block. The safety-related
characteristic data of the base unit and
all other devices that are used must be
taken into account when calculating
the safety function. We recommend
that you use the PAScal software tool
to calculate the safety function's SIL/
PL values.
Technische Daten_S atz Normen
1002374-EN-01-2011-05
Contact expansion modules
Up to PL e of EN ISO 13849-1
PNOZ s22
Conventional thermal current
Schaltleistung Ex t1 und Ext2
Conventional thermal current when
][Dauerstrom_DC_PNOZ_ s22_Ext.1 und Ext.2
the contacts from Ext.1/O0 and Ext.2/
O1 are under load simultaneously.
Number of contacts used at a timeIth [A] per contact
1 6.00 A
25.00 A
34.00 A
Schaltleistung Ex t1 oder ext2
Conventional thermal current when either the contacts from Ext.1/O0 or the
contacts from Ext.2/O1 are under
][Dauerstrom_DC_PNOZ_s22_Ext.1 oder Ext.2
load. They may not be under load simultaneously.
Number of contacts in totalIth [A] per contact
26.00 A
3 5.00 A
Order reference
TypeFeaturesTerminalsOrder no.
PNOZ s2224 V DCWith screw terminals750 132
PNOZ s22 C24 V DCWith spring-loaded terminals751 132
Bestelldaten
1002374-EN-01-2011-05