Contact expansion modules
Input
A1 A2
=
Power
=
K1
K2
13
23 33 51
24 34 52
14
43
44
*
Interface
base
unit
63
73 83
74 84
64
93
94
Up to PL e of EN ISO 13849-1
PNOZ s11
Gertebild
][Bildunterschrift Kontakterweiterungen
Contact expansion module for increasing the number of available contacts
Approvals
PNOZ s11
Unit features
Gertemerkmale
Positive-guided relay outputs:
– 8 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
Safe separation of safety contacts
from all other circuits
LED indicator for:
– Input status, channel 1
– Input status, channel 2
– Switch status, safety contacts
– Error
Plug-in connection terminals (either
spring-loaded terminal or screw
terminal)
Unit description
Bestimmung/Gertebesch reibung Kontakter weiterungen Schalt _PNOZ
The unit meets the requirements of
EN 60947-5-1, EN 60204-1 and
VDE 0113-1. The contact expansion
module is used to increase the number
of instantaneous safety contacts available on a base unit. Base units are all
safety relays with feedback loop monitoring.
The category that can be achieved in
accordance with EN 954-1 and
EN ISO 13849-1 depends on the cate-
gory of the base unit. The contact expansion module may not exceed this.
Safety features
Sicherheitseigenschaften Kontakterweiterungen allg_PNOZ
The unit meets the following safety requirements:
The contact expansion module ex-
pands an existing circuit. As the
output relays are monitored via the
base unit's feedback loop, the safety functions on the existing circuit
are transferred to the contact expansion module.
The safety function remains effec-
tive in the case of a component failure.
Earth fault in the feedback loop:
Detected, depending on the base
unit that is used.
Earth fault in the input circuit:
The output relays de-energise and
the safety contacts open.
Zulassungen
Block diagram
Blockschaltbild
*Safe separation in accordance with EN 60947-1, 6 kV
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001967-EN-04-2011-09
Contact expansion modules
POWER
Input
Feedback
Output safe
t1 t1t2 t2
Up to PL e of EN ISO 13849-1
PNOZ s11
Function description
][Funktionsbeschreibung_Erweiterungsgert
with PNOZsigma base unit:
Dual-channel operation via
PNOZsigma connector
Timing diagram
Key
Power: Supply voltage
Input: Input circuits A1
Wiring
without PNOZsigma base unit:
Single-channel operation: one input
circuit affects the output relays
][Zeitdiagramm_PNOZs_Kontakterw_in_out_aux-rfk
Output safe: Safety contacts 13-14,
23-24, 33-34, 43-44, 63-64, 73-74,
83-84, 93-94
Feedback: Feedback loop 51-52
: Switch-on delay
t
1
: Delay-on de-energisation
t
2
][Verdrahtung_Si_unverz_1Hi_unverz
Please note:
Information given in the “Technical
details” must be followed.
Outputs 13-14, 23-24, 33-34, 43-
44, 63-64, 73-74, 83-84, 93-94 are
safety contacts, output 51-52 is an
auxiliary contact (e.g. for display).
To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
Calculation of the max. cable runs
in the input circuit:
l
max
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
Use copper wire that can withstand
60/75 °C.
Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001967-EN-04-2011-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Contact expansion modules
A1
A2
24 V DC
0 V
PNOZsigma
expansion
module
A1
A2
24 V DC
0 V
PNOZsigma
expansion
module
A1
A20 V
O1
L-
PNOZsigma
expansion
module
52
51
feedback
loop
PNOZsigma
expansion
module
51
52
24 V DC
feedback
loop
PNOZsigma
expansion
module
Interface
PNOZsigma
PNOZsigma
base unit
PNOZsigma
expansion module
Up to PL e of EN ISO 13849-1
PNOZ s11
Preparing for operation
Betriebsbereitschaft herstellen PNOZs
Supply voltage
Supply voltage AC DC
Input circuit
Input circuit Single-channel Dual-channel
Base unit:
Safety relay PNOZ X
Base unit:
Safety relay PNOZelog
Driven via semiconductor outputs
(24 VDC)
Feedback circuit
Feedback circuit Base unit: Safety relay
PNOZ X
The inputs that evaluate the feedback loop
will depend on the base unit and application
Connection to PNOZsigma base unit
Base unit: Safety relay PNOZsigma
The feedback loop is connected and evaluated via the connector
][Betriebsbereitschaft_herstellen_Info_Erweiterungsgert_DB
INFORMATION
If a base unit and a contact expander
Do not connect A1 to the contact ex-
pander module!
module from the PNOZsigma range
are connected via the connector, no
additional wiring is necessary.
Base unit: Safety relay PNOZelog
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de