PNOZpower
Expander Module
PNOZ po3.3p
Expander module for the PNOZpower
modular safety system in accordance
with EN 60204-1 VDE 0113-1, 11/98
and IEC 60204-1, 10/97
Features
● 3 safety contacts
● Dual channel connection capa-
bility with detection of shorts
across the inputs when using
the base unit.
● Suitable for safely switching
loads with utilisation category
AC3 (e.g. motor)
● External start/stop input for
non-safety-related load switching
Technical Details PNOZ po3.3p
Electrical Data
Supply Voltage via P-01-Bus
Power Consumption Approx. 5 W
Total Current Max. 36 A
Switching Capabiltiy in accordance with
EN 60947-4-1, 01/00 AC1: 240 V/16 A/4000 VA
400 V/10 A/4000 VA
(1 x 106 cycles)
500 V/8 A/4000 VA
AC3: 240 V/3 kW
400 V/5.5 kW
(7 x 105 cycles)
500 V/4000 W
DC1: 24 V/16 A/384 W
Output Contacts 3 safety contacts (N/O)
Contact fuse protection according to Blow-out fuse: 16 A gG quick/slow
EN 60947-5-1, 08/00
External start/stop input y39-Y40 24 V DC/15 mA
Times
Switch-on Delay Approx. 100 ms + Switch-on Delay
of the base unit
Delay-on De-energisation Approx. 50 ms + Delay-on De-
energisation of the base unit
Mechanical Data
Cross Section of 1 x 2.5 mm
External Conductors Single-core or multi-core with
crimp connectors
Torque setting for connection terminals 0.5 Nm (screws)
Mounting Position On a top hat rail installed horizontally.
Protection Housing IP 30
Dimensions (H x W x D) 94 x 90 x 144 mm
Weight 645 g
2
Approvals
PNOZ po3.3p
Pending
●
●
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
Description
● 90 mm, P-01 housing, DIN-Rail
mounting
● Relay outputs, positive-guided:
– 3 safety contacts (N/O)
● Connection between base unit,
control unit and between
expander moduls via P-01-Bus
through connector plug on the
rear of the unit.
● LEDs for channel 1/2, supply
voltage and fault
Function Description
PNOZ po3.3p supplies 3 safety
contacts for the modular safety
system PNOZpower. It must be used
in conjunction with a base unit or
PNOZ e1p control unit
The output contacts can be opened
via an external start/stop input. This
enables loads to be switched under
normal operating conditions, without
energising the E-STOP circuit.
NSG-D-2-312-02/03
6
PNOZpower
Expander Module
PNOZ po3.3p
Internal Wiring Diagram
Y39
External
start/stop input
Input circuits
PNOZpower-Bus
K1
Safety contacts
L11L23L3
5
Y40
External Wiring
● PNOZpower Bus: Base unit connected with 4 expansion moduls and
power supply (optional) via connector plugs.
Power supply
Feedback control loop
K2
PNOZpower-Bus
Base unit Expander module 1
PNOZ po3.3p
2T14T26
T3
Expander module 4
6
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-312-02/03