PNOZpower
Base unit
PNOZ p1vp
Base unit for the PNOZpower
modular safety system in accordance
with EN 60204-1 (VDE 0113-1),
11/98 and IEC 60204-1, 10/97
Features
● Dual-channel operation, with or
without detection of shorts
across contacts
● Monitored or automatic reset
can be selected
● Instantaneous and delayed
control of expander modules
● Delay time can be selected via
rotary switch and potentiometer
● Designed to be driven via
semiconductor outputs
● 2 semiconductor outputs:
Fault (group fault signal),
K1/K2
● Plug-in connection terminals
Approvals
PNOZ p1vp
●
●
●
Technical details PNOZ p1vp
Application range In accordance with EN 954-1, 12/96,
up to Category 4; E-STOP, safety gate
Electrical data
Supply voltage DC: 24 V
Tolerance -15/+10 % %
Power consumption 4 W + load from expander modules
Voltage and current at
S11-S12, S11-S52, S21-S22 24 VDC, max. 50 mA
S33-S34 24 VDC, max. 340 mA
Semiconductor outputs 24 VDC/20 mA, short-circuit protected
External supply voltage 24 VDC ±20 %
Times
Selectable delay time PNOZp1vp 30s: 0, 5, 10, 15, 20, 25 s
+ 0.3 ... 5 s
PNOZ p1vp 300s:
0, 50, 100, 150, 200, 250 s
+ 1.5 ... 50 s
Switch-on delay Monitored reset: max. 190 ms
Auto./manual reset: max. 250 ms
Delay-on de-energisation With E-STOP: max. 30 ms
With power failure: max. 70 ms
Recovery time 0.3 s
Simultaneity channel 1/2 Max. 150 ms
Supply interruption before de-energisation ca. 25 ms
Mechanical data
Cross section of external conductors
1 core Flexible: 0.2 ... 2.5 mm
2 core with the same cross section Flexible with crimp connectors, no
plastic sleeve: 0.25 ... 2.5 mm
Flexible, without crimp connectors or with
TWIN crimp connectors: 0.5 ... 1.5 mm
Torque setting for connection terminals 0.5 Nm (screws)
Mounting position On a top hat rail installed horizontally
Dimensions (H x W x D) 94 x 45 x 135 mm
Weight 360 g
Description
● 45 mm P-01 housing,
DIN rail mounting
● Connection options for
– E-STOP button
– Safety gate limit switch
– Reset button
● Output connected to PNOZpowerBus
● Max. 8 expander modules can be
connected
- max. 4 expander modules that
are controlled instantaneously
- max. 4 expander modules that
are controlled with a delay time
● Connection between PNOZ p1p
and expander modules via
PNOZpower bus, via jumpers on
the back of the unit
● LEDs for status of input and
output circuits, reset circuit,
supply voltage and fault
Operating modes
● Single-channel operation
● Dual-channel operation
● Automatic reset
● Manual reset
● Monitored manual reset
2
2
1
2
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-333-08/04
PNOZpower
S22
S34
S33
S21
S11
S12
S52
S1
S2
S11
Y2
Y1
S52
S34
S12
S11
S21
S12
S22
S11
Y2
Y1
S3
S1
S2
Base unit
PNOZ p1vp
Internal wiring diagram
A2 (0V)
S11A1 (+)
Input circuits
PNOZpower-Bus
Output
Y32 Y35
Y31Y30
● Example 1
Single-channel E-STOP wiring with
manual reset
S21
Y1
S33
S3
S11 S12
S1
S21 Y1S34
Reset/feedback circuit
S37
Y2S33S22S12 S52
Output
● Example 3
Dual-channel E-STOP wiring with
manual reset and detection of shorts
across contacts
S11
S11
S21
S1
S3
S12
● Example 5
Dual-channel safety gate control with
manual reset and detection of shorts
across contacts
PNOZpower-Bus
● Example 6
Dual-channel safety gate control with
automatic reset and detection of
shorts across contacts
Y1
S52
S12
S22
● Example 2
Single-channel E-STOP wiring with
monitored reset
S11 S12
S21
S1
S12
S52
S3
S22
– Key
S1/S2: E-STOP or safety gate switch
S3: Reset button
Switch operated
Gate open
Gate closed
S34
S33
S34
Y2
Y1
S37Y1Y2
S52
S34
Y2
S22
S12
● Example 4
Single-channel safety gate control
with manual reset
S11
S12
S21
S12
S1
S52
S22
Y1
S33
S3
Y2
S34
● Output contacts for switching
higher capacities
1L1
K5
K4
Y1 Y2
PNOZ p1vp
1L2
13
Expander
unit
14
K4 K5
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-333-08/04