Pilz PNOZ mc1p, PNOZ mi1p, PNOZ mi2p, PNOZ mo2p, PNOZ ml1p Configuration Manual

...
Configuration guide
Technical Catalogue 3.4 – August 2008 edition
PNOZmulti Modular Safety System
KURAL TEKNOLOJİ ELEKTRO MARKET
KURAL TECHNOLOGY ELECTRO MARKET
www.kuralteknoloji.com
bilgi@kuralteknoloji.com - info@kuralteknoloji.com
Exclusion of liability
We have taken great care in compiling our application manual. It contains information about our company and our products. All statements are made in accordance with the current status of technology and to the best of our know-ledge and belief. However, we cannot except liability for the accuracy and entirety of the information provided, except in the case of gross negligence. In particular it should be noted that statements do not have the legal quality of assurances or assured properties. We are grateful for any feedback on the contents.
August 2008
All rights to this publication are re­served by Pilz GmbH & Co. KG. We reserve the right to amend specifications without prior notice. Copies may be made for the user’s internal purposes. The names of products, goods and technologies used in this manual are trademarks of the respective companies.
Why does Pilz offer more?
Because the integrality of our business activities is what sets us apart.
Pilz is a solution supplier for all auto­mation functions. Including standard control functions. Developments from Pilz protect man, machine and the environment. That’s why all our experi­ence and knowledge goes into individual products as well as consistently sophisticated system solutions.
Sensor technology Control and communication Motion Control Operating and monitoring Software Consulting Engineering Training
Appropriate services relating to indi­vidual components and independent generic services guarantee that our customers obtain customised automation solutions, all from one source.
You can find more details about Pilz and your products and
services on the Internet:
www.pilz.com
Pilz is a family business that’s closer to its customers
Pilz has a tradition as a family-run company stretching back over 50 years. Real proximity to customers is visible in all areas, instilling confidence through individual consultation, flexibility and reliable service.
We are your contact, guide and competency leader en route to an optimum automation solution.
Support – Technical help round the clock!
Technical support is available from Pilz round the clock. This service is provided free of charge beyond standard business hours.
You can reach our international hotline on:
+49 711 3409-444
Contents
3
Contents1.02007-11
Basics
1.0
System description
1.1
Installation
1.2
Electrical installation
1.3
Configuration and Wiring
1.4
Products
2.0
Selection guide
2.1
Base units
2.2
Expansion modules
2.3
Adapter for PNOZ ms1p and PNOZ ms2p
2.4
Software
2.5
Applications
3.0
Accessories
4.0
Order reference
5.0
Order reference
5.1
Standards and directives
6.0
Standards and directives
6.1
Service
7.0
Service
7.1
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.0-0
1.0
Basics1.0
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
2007-11
1.0-1
1.0
Contents Page
System description from 1.1-1 Installation from 1.2-1 Electrical installation from 1.3-1 Configuration and Wiring from 1.4-1
Basics
System description
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.1-0
1.1
BasicsSystem description1.1
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
System description
2007-11
1.1-1
1.1
Contents Page
System description
Overview 1.1-2 Hardware 1.1-3 Software 1.1-4 Maximum system expansion 1.1-5 Diagnostics 1.1-7 Safety 1.1-8
Basics
System description
Overview
2007-11Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.1-2
1.1
Overview1.12007-11BasicsSystem descriptionOverview
Modular design
` The modular safety system consists
of a base unit and several expan­sion modules.
` The base unit has several inputs
and outputs and is fully functional even without an expansion module.
` The expansion modules supple-
ment the base unit with additional inputs or outputs.
Configuration in the PNOZmulti Configurator
` The function of the safety system is
established through the PNOZmulti Configurator.
` The PNOZmulti Configurator is a
graphic tool which is used to define the functions of the units. Using predefined symbols, a simple cir­cuit diagram shows how the units' inputs and outputs should be con­nected. This circuit diagram is then downloaded to the base unit.
` From this data, the base unit recog-
nises the safety functions it is to perform. For example, safety func­tions such as E-STOP, two-hand monitoring and safety gate monitor­ing are available. With the correct circuitry it is possible to achieve categories 2, 3 and 4 in accordance with EN 954-1.
` The fact that the system is modular
and configurable guarantees the highest level of flexibility. The safety system can be expanded or the safety functions modified at any time.
Inputs
` Units in the PNOZmulti modular
safety system have semiconductor inputs for safety-related and stand­ard applications.
` The inputs for standard applica-
tions can also be set via the serial interface or via fieldbus modules (e.g. PROFIBUS-DP, CANopen, ...).
` One expansion module in the
PNOZmulti modular safety system has safe, analogue inputs. The in­put signals are converted into digit­al signals.
` For standard applications, the ex-
act analogue values are made avail­able to the base unit to forward to a fieldbus.
Outputs
` Units in the PNOZmulti modular
safety system have both semicon­ductor and relay safety outputs.
` The outputs for standard functions
use semiconductor technology.
` The safety outputs use semicon-
ductor technology, require no main­tenance and are non-wearing; they are therefore suitable for applica­tions with frequent operations or cyclical functions. They can be used for 24 VDC applications.
` The relay safety outputs are suita-
ble for less frequent operations, but they have a higher breaking capac­ity and can be used for AC applica­tions.
` The outputs for standard applica-
tions can also be evaluated via the serial interface or via fieldbus mod­ules (e.g. PROFIBUS-DP, CAN­open, ...).
Base unit + expansion modules
Download
PNOZm Config
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
System description
Hardware
2007-11
1.1-3
1.1
Hardware1.12007-11BasicsSystem descriptionHardwarePNOZmulti zusammengestell te Texte
Design of the modular safety sys­tem
The modular safety system consists of the base unit and expansion modules. The base unit itself has
` 20 inputs ` 2 relay outputs ` 4 semiconductor outputs ` 1 auxiliary output, which is required
for deleting the configuration data in the base unit
` 1 cascading input ` 1 cascading output
The number of inputs and outputs can be increased at any time using the ex­pansion modules. The modules are linked via a jumper. The system is con­figured using the PNOZmulti Configu­rator. Special expansion modules enable data to be exchanged via a fieldbus (non-safety-related) or safe speed monitoring, for example.
Operation of the units
The PNOZmulti Configurator gener­ates a project file which is downloaded to the base unit; there it defines:
` Which safety functions the inputs
are to carry out, e.g. E-STOP moni­toring, safety gate monitoring
` How the inputs are connected to
the outputs via logic functions
` Which output is configured (semi-
conductor, relay) The units react the same, irrespective of these functions: If the start-up condition of the specific safety function is met, there will be a high signal at the output “Out1”. The output signal can be linked via a logic function and is then present as the “Out2” signal at the output on the PNOZmulti unit.
Fieldbus modules
The fieldbus modules are used to
` Read the diagnostic data ` Set virtual inputs for standard func-
tions
` Read virtual outputs for standard
functions
RS 232 interface
The base unit has an RS 232 interface to
` Download the project ` Read the diagnostic data ` Set virtual inputs for standard func-
tions
` Read virtual outputs for standard
functions
Safety functions
The safety system has inputs and out­puts, which can be used for safety functions. The PNOZmulti safety sys­tem can be configured to monitor
` E-STOP pushbuttons ` Operating mode selector switches ` Enable switches ` Two-hand buttons ` Safety gates ` Light curtains ` Light beam devices ` Speeds
` Analogue input signals ` Safety mats ` Muting `
Mechanical presses
` Standstill
Various switch types are available for the required safety-related applica­tions. With some switch types it is possible to monitor for simultaneity (see chapter on “Configuration and Wiring”).
Standard functions
Expansion modules are available with inputs and outputs for standard func­tions.
Press applications
The PNOZ m2p base unit is designed for applications on mechanical press­es.
Inputs
Safety
functions
e.g.
E-STOP
safety gate
Outputs
Out1
Logic
functions
e.g.
AND
OR
Delay
Out2
Semiconductor
Relay
Basics
System description
Software
2006-02Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.1-4
1.1
Software1.12006-02BasicsSystem descriptionSoftware
The functions of the PNOZmulti sys­tem are defined in the PNOZmulti Configurator software.
Procedure
` In the PNOZmulti Configurator, the
first step is to enter the units that
are to be used in the safety system.
Each unit must be given a resource
label.
` When all the units are selected, the
interface appears for entering the
circuit diagram. The circuit diagram
describes the application for which
the safety system is to be used. It is
here that you determine which in-
puts are assigned to which safety-
related or standard functions.
` The inputs and/or the results of the
safety-related or standard functions
can be linked through logic func-
tions. The results of the logic func-
tions or the results of the safety-
related or standard functions are
channelled to the outputs on the
PNOZmulti units.
` The circuit diagram is generated on
a graphical interface. Symbols are
provided for the safety-related or
standard functions, logic functions
and the various output types. These
are simply dragged on to a work-
space, configured and intercon-
nected.
` Once the circuit diagram is com-
plete, the data must be saved and
downloaded to the base unit. The
circuit diagram, unit configuration
and all the data that has been en-
tered are stored within a project.
` When the project is saved, various
passwords can be used to protect it
from unauthorised access.
` Once it is saved, the project has to
be downloaded to the base unit. To
do this, the project data is down-
loaded on to a chip card. The data
is either downloaded via the RS 232
interface or via a chip card reader.
` After downloading, a test must be
performed to check that the safety
devices function correctly.
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
System description
Maximum system expansion
2007-11
1.1-5
1.1
Maximum system expansion1.12007-11BasicsSystem descriptionMaximum system expansion
The PNOZmulti Configurator software provides support when assembling a PNOZmulti system. The maximum system expansion is limited only by the maximum permitted number of ex­pansion modules that can be connect­ed. The following modules are available:
` Base units ` Expansion modules ` Fieldbus modules
Positioning of units
` Only one base unit may be used. ` Expansion modules and a fieldbus
module may be connected to the left or right, depending on the base unit type. The maximum number per type is given in the tables be­low.
` The position of the expansion mod-
ules is defined in the PNOZmulti Configurator.
` Expansion modules for safety-relat-
ed and standard applications may be combined as required.
` However, if expansion modules of
the same function are combined into groups it makes things clearer and simplifies the wiring.
` The power supply for a fieldbus
module is not given a position number.
` If there is no fieldbus module, the
position numbers to the left of the base unit will be -1 ... -4.
Base units:
CHIP-Card
PNOZ mo3p
O1+
O0-
O0+
O1-
PROFIBUS-DP
PNOZ mc3p FAULT
OFF­LINE
x1
x10
X1
ON­LINE
ADDRESS
773700
Base unit
Fieldbus module
Max. 8 expansion
modules
8
Position
1
2
...
2
Shield
Power supply
Max. 4 expansion
modules
0-5 -1-2...
Unit type Max. number of expansion modules
installed on the left
Max. number of expansion modules installed on the right
PNOZ m0p 4 + 1 fieldbus module --­PNOZ m1p 4 + 1 fieldbus module 8 PNOZ m2p 4 + 1 fieldbus module 8
Basics
System description
Maximum system expansion
2007-11Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.1-6
1.1
Expansion modules:
Fieldbus modules:
Unit type Function Max. number of expansion
modules installed on the left
Max. number of expansion modules installed on the right
PNOZ ma1p 2 safe analogue inputs 4 --­PNOZ mc1p 16 outputs for standard func-
tions
--- 8
PNOZ mi1p 8 safe inputs --- 8 PNOZ mi2p 8 inputs for standard functions --- 8 PNOZ ml1p Connection module for 32 virtu-
al inputs and outputs
4 ---
PNOZ mo1p 4 safe 1-pole semiconductor
outputs
--- 6
PNOZ mo2p 2 safe relay outputs --- 6 PNOZ mo3p 2 safe 2-pole semiconductor
outputs
--- 6
PNOZ mo4p 4 safe relay outputs --- 6 PNOZ ms1p 2 incremental encoders or
proximity switches
--- 4
PNOZ ms1p 2 incremental encoders or
proximity switches
--- 4
Unit type Fieldbus Max. number of expansion
modules installed on the left
Max. number of expansion modules installed on the right
PNOZ mc3p PROFIBUS-DP 1 --­PNOZ mc4p DeviceNet 1 --­PNOZ mc5p Interbus 1 --­PNOZ mc5.1p Interbus fibre-optic cable 1 --­PNOZ mc6p CANopen 1 --­PNOZ mc7p CC-Link 1 --­PNOZ mc8p Ethernet IP/Modbus TCP 1 --­PNOZ mc9p PROFINET IO 1 ---
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
System description
Diagnostics
2006-02
1.1-7
1.1
Diagnostics1.12006-02BasicsSystem descriptionDiagnostics
The PNOZmulti has many options for diagnostics and fault detection:
` LEDs on the base unit and expan-
sion modules
` Diagnostic data via serial interface
and fieldbus
` Expanded diagnostic options using
a visualisation system, e.g. PMImi-
cro diag
` Error stack ` Diagnostic word in the PNOZmulti
Configurator
Note
Please refer to the chapters
` “Diagnostic interface” and ` “Diagnostic word”
in the configuration guide “PNOZmulti – Special applications”.
LEDs on the base unit and expan­sion modules
The LEDs signal
` Operating statuses (e.g. “RUN”) ` External and internal errors
The key to the LEDs can be found in the operating instructions supplied with the units.
Diagnostic Interface
The serial interface on the PNOZmulti modular safety system is used to transfer diagnostic data to a user pro­gram.
Diagnostic data
The diagnostic data can be called up via the serial interface or via a con­nected fieldbus. The diagnostic data may only be used for non-safety purposes, e.g. visuali­sation. Diagnostic data on the PNOZmulti modular safety system comprises:
` Version:
Product number, unit version, serial
number
` Status of inputs/outputs:
Indicates whether inputs and out-
puts are active or inactive (open/
closed)
` LED status:
Indicates the status of the LEDs on
the base unit and expansion mod-
ules (on/off/flashes), plus the oper­ating mode (start up, RUN, STOP)
` Simplified status scan:
Shows group messages relating to the safety system: Signal changes, LED status, operating statuses
` Virtual inputs and outputs:
Virtual inputs can be set. The status of the virtual inputs and outputs can be scanned.
` Diagnostic word:
The diagnostic word contains the status of elements from the user program within the PNOZmulti.
` Test data:
To check commmunication.
` Data in table form:
This is structured data (arranged in tables and segments) from the PNOZmulti, as it could also be read via a fieldbus module: – Configuration – Status of the inputs and outputs –LED status – Diagnostic word –Element types
Expanded diagnostic options using a diagnostic terminal, e.g. PMImicro diag
An expanded diagnsotic configuration can be created in the PNOZmulti Con­figurator. The diagnostic configuration enables appropriate event messages to be displayed in the case of:
` Errors in or on the PNOZmulti:
Contains the event messages that are triggered when there are errors in or on the PNOZmulti (error stack)
` Changes in the operating status of
the PNOZmulti
` which are triggered when safety de-
vices, inputs, outputs and connec-
tion points have a defined status PNOZmulti event messages can also be supplemented through additional information, which is helpful during di­agnostics. With expanded diagnostics, a display unit (e.g. PMImicro diag) is connected to a PNOZmulti. If an event occurs in or on the PNOZmulti, an event tele­gram is sent to the display unit. The event telegram is evaluated in the dis­play unit. In most cases, the event message that corresponds to the event is displayed and is entered in the
event list. The event message contains a description of the event. A remedy can be displayed for each event mes­sage. The remedy describes how to react to the event, in other words, what “actions” to take. The diagnostic configuration is project-related, i.e. a separate diag­nostic configuration is created for each PNOZmulti project (see Create a diagnostic configuration). Then the diagnostic configuration is downloaded to the PNOZmulti and to the display unit. The diagnostic configuration is de­scribed in detail in the PNOZmulti Configurator's online help.
Error stack
The error stack on the PNOZmulti con­tains important information for diag­nostics and troubleshooting. The error stack can be read out by the PNOZ­multi Configurator. It contains mes­sages and help texts such as
` Hardware errors ` Wiring errors ` Configuration errors ` Errors in the operation of the inter-
face or fieldbus
` Errors in the project's user program ` Messages relating to differences
between the programs stored on the PNOZmulti and chip card
Diagnostic word
A diagnostic word can be called up for those elements of the PNOZmulti Con­figurator interface that have the ability to store a status:
` Online in the PNOZmulti Configura-
tor
` Via the base unit's serial interface ` Via a connected fieldbus
The diagnostic word contains informa­tion about a certain element, e.g.:
` Operating statuses (e.g. switch op-
erated)
` Error messages (e.g. monitoring
time elapsed) An individual bit from a diagnostic word can be evaluated in the user pro­gram of the PNOZmulti Configurator.
Basics
System description
Safety
2006-02Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.1-8
1.1
Safety1.12006-02BasicsSystem descriptionSafetyPNOZmulti z usammengestellte Te xte
Safety assessments
Before using a unit it is necessary to perform a safety assessment in ac­cordance with the Machinery Direc­tive. The safety system guarantees functional safety, but not the safety of the entire application. You should therefore define the safety require­ments for the plant as a whole, and also define how these will be imple­mented from a technical and organisa­tional standpoint.
General safety requirements
Always ensure the following safety re­quirements are met:
` Only install and commission the
unit if you are familiar with the infor­mation in the operating instructions or this technical catalogue, as well as the relevant regulations concern­ing health and safety at work and accident prevention.
` Only use the unit for the purpose for
which it is intended and comply with both the general and specific technical details.
` Transport, storage and operating
conditions should all conform to EN 60068-2-6, 01/00 (see general technical details).
` Adequate protection must be pro-
vided for all inductive consumers.
` Do not open the housing or make
any unauthorised modifications.
` Failure to comply with the safety re-
quirements will render the guaran­tee invalid.
Intended use
` The PNOZmulti Configurator soft-
ware is designed to configure units from the PNOZmulti modular safety system for use on E-STOP equip­ment and safety circuits, in accord­ance with EN 60204-1 (VDE 0113-
1), 11/98 and IEC 60204-1, 12/97.
` The units' intended use depends on
the individual unit and is therefore explained in the chapter entitled “Units”.
` The PNOZ m2p base unit is de-
signed for applications on mechan­ical presses. Please refer to the
safety guidelines in the chapter on “Safety solutions for presses” in the configuration guide “PNOZmulti – Special applications”.
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
System description
Safety
2006-02
1.1-9
1.1
Basics
Installation
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.2-0
1.2
BasicsInstallation1.2
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Installation
2007-11
1.2-1
1.2
Contents Page
Installation
Installing within the control cabinet 1.2-2 Installing the units 1.2-3
Basics
Installation
Installing within the control cabinet
2006-02Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.2-2
1.2
Installing within the control cabinet1.22006-02BasicsInstallationInstalling within the control cabinetPNOZmulti zusammengestell te Texte
` The safety system should be in-
stalled in a control cabinet with a protection type of at least IP54. Fit the safety system to a horizontal DIN rail. The venting slots must face upward and downward. Other mounting positions could destroy the safety system.
` Use the notches on the back of the
unit to attach it to a DIN rail. Con­nect the safety system to the DIN rail in an upright position, so that the earthing springs on the safety system are pressed on to the DIN rail.
` The ambient temperature of the
PNOZmulti units in the control cab­inet must not exceed the figure stated in the technical details, oth­erwise air conditioning will be re­quired.
` To comply with EMC requirements,
the DIN rail must have a low imped­ance connection to the control cab­inet housing.
Positioning of units
` Expansion modules and a fieldbus
module may be connected, de­pending on the base unit type.
` Install the expansion modules in the
position defined in the PNOZmulti Configurator (see section entitled “Maximum system expansion” in Chapter 1.1 “System Description”).
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Installation
Installing the units
2006-02
1.2-3
1.2
Installing the units1.22006-02BasicsInstallationInstalling the units
Installing a base unit without expan­sion modules
` The terminator must be fitted to the
side of the base unit marked “Ter­mination/Link”.
` Do not fit a terminator to the left
side of the base unit.
Connecting the base unit and ex­pansion modules (PNOZ m1p, PNOZ m1p coated version, PNOZ m2p on­ly)
Jumpers are used to connect the modules.
There are 2 pin connectors on the rear of the base unit.
` Make sure that no terminator is fit-
ted.
` Connect the base unit, the expan-
sion modules and the fieldbus mod­ule using the jumpers supplied.
` The terminator must be fitted to the
last expansion module to the right
of the base unit.
` Do not fit a terminator to the last ex-
pansion module to the left of the
base unit.
Terminator
Termination/Link
Expansion module 1 ... 8
Jumpers
Terminator
Fieldbus module
Base unit
Expansion module 1 ... 4
Power supply
Basics
Electrical installation
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.3-0
1.3
BasicsElectrical installation1.3
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Electrical installation
2007-11
1.3-1
1.3
Contents Page
Electrical installation
General requirements 1.3-2
Basics
Electrical installation
General requirements
2006-02Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.3-2
1.3
General requirements1.32006-02BasicsElectrical installationGeneral requirementsPNOZmulti zusammengestellte T exte
EMC
` The PNOZmulti is designed for use
in an industrial environment. It is not suitable for use in a domestic envi­ronment, as this can lead to inter­ference.
` To comply with EMC requirements,
the DIN rail must have a low imped­ance connection to the control cab­inet housing.
Supply voltage
` Power for the safety system and in-
put circuits must always be provid­ed from a single power supply. The power supply must meet the regu­lations for extra low voltages with safe separation (SELV, PELV).
` Two connection terminals are avail-
able for each of the supply connec­tions 24 V and 0 V (semiconductor outputs), plus A1 and A2 (power supply). This means that the supply voltage can be looped through sev­eral connections. The current at each terminal may not exceed 9 A.
Cables
` Do not route the test pulse lines to-
gether with actuator cables within an unprotected multicore cable.
` Use copper wiring that can with-
stand temperatures of 60/75°C.
Terminals
` The plug-in terminals for the inputs
and outputs are not supplied with the system. You can select be­tween a cage clamp connection or a screw connection.
` The plug-in connection terminals
on the relay outputs carry mains voltage and should only be con­nected and disconnected when the voltage is switched off.
ESD
Electrostatic discharge can damage components. Ensure against dis­charge before touching the units, e.g. by touching an earthed, conductive surface or by wearing an earthed arm­band.
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Electrical installation
General requirements
2006-02
1.3-3
1.3
Basics
Configuration and Wiring
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.4-0
1.4
BasicsConfiguration and Wiring1.4
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Configuration and Wiring
2007-11
1.4-1
1.4
Contents Page
Configuration and Wiring
Inputs 1.4-2 Logic elements 1.4-7 Outputs 1.4-8 Inputs and outputs for standard functions 1.4-9 Cascading 1.4-10
Basics
Configuration and Wiring
Inputs
2007-11Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.4-2
1.4
Inputs1.42007-11BasicsConfiguration and WiringInputsPNOZmulti zusammengestell te Texte
Connection options
Depending on the unit type, the follow­ing may be connected to the inputs on the PNOZmulti:
` E-STOP pushbutton ` Safety gate limit switch ` Two-hand button ` Reset button ` Light beam device, light curtain ` Safety mats ` Enable switch ` Operating mode selector switch ` Proximity switch ` Incremental encoder ` Foot switch ` Key switch ` Limit switch ` Pushbutton ` Encoder or transducer to monitor
safe analogue input signals
The PNOZmulti has inputs for both safety-related and standard applica­tions.
` Only safety inputs should be used
for safety-related applications.
` Inputs for standard functions may
be used for a reset button, for ex­ample.
Application with safety mats
The application with safety mats is de­scribed in detail in the configuration guide under “Special applications”.
Configuration in the PNOZmulti Configurator
The inputs on the PNOZmulti units are configured in the PNOZmulti Configu­rator. For example, you can define the fol­lowing:
` Switch types for various safety
functions
` Connection assignment ` Detection of shorts between con-
tacts in the input circuit
` Reset types ` Start-up test ` Detection of shorts between con-
tacts in the reset circuit with test pulse assignment
` Input for standard function
Some configuration options can only be selected for particular safety func­tions (e.g. the start-up test can only be selected for the safety gate and light curtain safety functions).
Input signals
Due to the cyclical processing, chang­es in the input signal will only be de­tected safely if the off-time >15 ms.
Connection assignment
Inputs on the PNOZmulti units are as­signed to particular safety functions (e.g. E-STOP, safety gate) in the PNOZmulti Configurator. The safety contacts must be connected to the in­puts on the PNOZmulti units in ac­cordance with their configuration.
Select switch type
The PNOZmulti Configurator provides the user with various switch types for safety-related applications. The switch types that can be selected will depend on the type of input element (e.g. E­STOP, safety gate). The switches drawn below are shown in the state when not activated, such as with the safety gate closed or E-STOP not pressed. On switches that are monitored for si­multaneity, the maximum switch-on time and the maximum switch-off time are the same. These values can be found in the “Description” and “Timing diagram” columns.
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Configuration and Wiring
Inputs
2007-11
1.4-3
1.4
Application Description Switch symbol Timing diagram
E-STOP Safety gate Enable switch Foot switch
Safety contacts: 1 normally closed (N/C) without on and off-time
1
E-STOP Safety gate Foot switch
Safety contacts: 1 normally closed (N/C) 1 normally open (N/O) without on and off-time
E-STOP Safety gate Foot switch
Safety contacts: 1 normally closed (N/C) 1 normally open (N/O) with on and off-time 3 s
2
Safety contacts: 2
normally closed (N/C) without on and off­time
2 ­Simultaneity
E-STOP Safety gate Safety gate
with Interlock Light curtain Enable switch Foot switch
3
3 ­Simultaneity
E-STOP Safety gate Light curtain Enable switch Foot switch
Safety contacts: 2 normally closed (N/C) with on and off-time 3 s
4 Safety contacts:
2 normally closed (N/C) 1 normally open (N/O) without on and off-time
Safety gate
4 ­Simultaneity
Safety contacts: 2 normally closed (N/C) 1 Schließer (S) with on and off-time 3 s
Safety gate
5 Safety contacts:
3 normally closed (N/C) without on and off-time
Safety gate
Switch type
t
t
t
t
N/C
Output
N/O
Output
N/C
max. 3 s
max. 3 s
N/O
Output
N/C
N/C
Output
N/C
N/C
Output
N/C
max. 3 s
max. 3 s
N/C
Output
N/C
N/O
N/C
Output
N/C
max. 3 s
max. 3 s
N/O
N/C
Output
N/C
N/C
Basics
Configuration and Wiring
Inputs
2007-11Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.4-4
1.4
5 ­Simultaneity
Safety contacts: 3 normally closed (N/C) with on and off-time 3 s
Safety gate
Safety contacts: 2 changeover contacts (C/O) with simultaneity monitoring 0.5 s, off-time not monitored
Safety contacts: 2 normally open (N/O) (C/O) with simultaneity monitoring 0.5 s, off-time not monitored
Two-hand button Ohne Taktung nur bis Kategorie 1 nach EN 954-1 einsetzbar
7
9
Operating mode Safety contacts:
Switch 1 from 2
10 Operating mode Safety contacts:
Switch 1 from 3
11 Operating mode Safety contacts:
Switch 1 from 4
12 Operating mode Safety contacts:
Switch 1 from 5
13 Operating mode Safety contacts:
Switch 1 from 6
14 Operating mode Safety contacts:
Switch 1 from 7
15 Operating mode Safety contacts:
Switch 1 from 8
Button Key switch Limit switch
Safety contacts: 1 normally closed (N/C)
16
Safety contacts: 1 normally open (N/O)
17
Two-hand button
6
N/C
Output
N/C
max. 3 s
max. 3 s
N/C
N/C 1
Output
N/O 1
max. 0,5 s
N/C 2
N/O 2
Output
N/O 1
max. 0,5 s
N/O 2
t
t
Application Description Switch symbol Timing diagramSwitch type
Button Key switch Limit switch
Basics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Configuration and Wiring
Inputs
2007-11
1.4-5
1.4
Input devices
When selecting input devices, you must comply with the technical details of the input circuits on the PNOZmulti units. To help you in your selection, Pilz has performed application tests with a number of input devices. The following input devices have passed the application test:
` Light curtains:
–SICK FGS – SICK C4000 – Honeywell MEYLAN – CEDES Safe 4 –OMRON F3SN-A – Fiessler ULVT – STI Minisafe MS 4600 (from S/N:
AC283791 / BA022933)
– STI Optofence OF 4600
` Limit switches:
– Schmersal AZ 16-02 – Guardmaster ferrocode – Euchner NP1-628AS – Euchner CES-A-C5E-01 (only
when operating without detec­tion of shorts across contacts)
– Euchner CES-A-C5E-01 (only
with test pulse wiring) – Euchner ENG-071990 – Euchner NM11KB
The following may not be used:
` Limit switches:
– Euchner CES-A-C5E-01 with
pulse signals
The following is generally valid: Input devices with mechanical contacts (re­lays) can be used in operating modes with or without detection of shorts across contacts, provided you comply with the technical details. It is not al­ways possible to use input devices with semiconductor outputs when op­erating with detection of shorts across contacts.
Units with OSSD semiconductor outputs
Units with OSSD semiconductor out­puts (e.g. self-testing light barriers) may only be used if the PNOZmulti is operated without detection of shorts across contacts.
ESPE
If the function of an ESPE (e.g. light barrier) is switched off via an operating mode selector switch, the supply volt­age to the ESPE must be switched off at the same time.
Operating modes
The following operating modes are available, depending on the selected safety function:
` Single-channel operation: Input
wiring in accordance with EN 60204, no redundancy in the input circuit; earth faults in the input cir­cuit are detected.
` Dual-channel operation: Redun-
dant input circuit; earth faults in the input circuit are detected, with or without detection of shorts be­tween the input contacts.
` Triple-channel operation: Redun-
dant input circuit; earth faults in the input circuit are detected, with or without detection of shorts be­tween the input contacts.
` Automatic reset: Unit is active as
soon as the input circuit is closed.
` Manual reset: The unit is not active
until the reset button has been op­erated.
` Monitored reset: Unit is not active
until the reset button has been op­erated and then released. This elim­inates the possibility of the reset button being overridden, triggering automatic activation.
` Detection of shorts between con-
tacts in the input circuit: Enabled by pulsing the input circuits. This oper­ating mode is automatically detect­ed on start-up.
` Detection of shorts between con-
tacts in the reset circuit:
` Only on E-STOP, safety gate and
light curtain
` Start-up test: The unit checks
whether safety gates that are closed are opened and then closed again when supply voltage is ap­plied.
` Increase in the number of safety
contacts available by connecting a contact block (e.g. PZE 9P) or ex­ternal contactors.
Reset button
A reset button triggers an enable for a safety device when all the correspond­ing safety switches (e.g. E-STOP) are closed. This prevents a machine start­ing up automatically after the supply has been interrupted or after a safety device has closed, for example.
Reset modes
When configuring inputs for E-STOPs, safety gates or light guards in the PNOZmulti Configurator, it is possible to define the reset mode:
` Automatic reset ` Manual reset ` Monitored reset
For a manual and monitored reset, the reset button can also be configured as a standard input.
` Automatic reset
With an automatic reset, the output on the function element goes to “1” when the safety switches on the input circuit are closed.
` Manual reset
A N/O contact on the reset input gen­erates the reset signal. The reset but­ton must be operated after the safety switch has closed. The output on the input element is set to “1” when the re­set button is operated.
` Monitored reset
A N/O contact on the reset input gen­erates the reset signal. The reset but­ton must be operated after the safety switch has closed. The output on the input element is set to “1” when the re­set button is released.
Reset button
Output
Safety contact
Basics
Configuration and Wiring
Inputs
2007-11Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1.4-6
1.4
Test pulses and detection of shorts across contacts
` Under certain circumstances, sig-
nal inputs with infrequent operation (constant signals) supply an un­changing signal over a long period of time. During this time, the func­tion of the periphery devices can only be monitored to a limited ex­tent. Faults that arise may remain undetected. Signal inputs with in­frequent operation must therefore be checked via test pulses from category 2 onwards, in accordance with EN 954-1.
` Test pulses are assigned to inputs
in the PNOZm Configurator. If “De­tection of shorts between contacts in the input circuit” has been select­ed, the base unit provides 4 test pulses.
` Two-hand button: Switch type 6
contains a N/C / N/O combination per two-hand button.
` If switch type 7 is used, the two N/
O contacts should use different test pulses.
` Please refer to clause 4 of EN 574
during configuration.
` Detection of shorts between con-
tacts in the reset circuit: Monitored reset mode will detect a short across the contacts. For wiring rea­sons the reset circuit may also use test pulses.
` Test pulse outputs may only be
used to test the inputs. They must not be used to drive loads.
` Test pulse outputs are also used to
supply safety mats that trigger a short circuit. Where test pulses are used for the safety mat, they may not be reused for other purposes. Safety mats are supported from the following base unit versions:
– PNOZ m0p: From Version 1.2 – PNOZ m1p: From Version 4.3 – PNOZ m2p: From Version 1.3
Start-up test
` A start-up test is available for the
safety gate and light curtain safety functions.
` When supply voltage is removed
and then re-applied, the safety gate is enabled (output on the safety gate input element = “1”) only after the gate has been opened and then closed. In this way you are forced to check the correct function of the safety gate and safety gate switch.
` The PNOZmulti switches to a STOP
condition after an error. The PNOZ­multi switches back to a RUN con­dition when the supply voltage has been switched on and off. For this reason the start-up test must be carried out again after each STOP.
Reset button
Output
Safety contact