Wait 30 minutes for the controller to stabilized thermally. Operations such as
measurements should be taken after the equipment has been on for 30 minutes
or more.
- 3 -
3. Installation and Mounting
3-1. External/Panel Cut Dimensions
1-12
13-2425-36
25-36
1-12
13-24
Installing multiple controllers
50 or more
(48 × n - 3)
92
+0.8
0
+0.8
0
Close mounting in horizontal direction (n units)
45
+0.6
0
92
0
116 or more
116 or more
+0.8
Installing multiple controllers
92
+0.8
0
92
+0.8
0
100 or more
Terminal block is not attached to unused terminals
(from terminal 13 to 24) depending on model.
Terminal screw
Rear view
6.2
Terminal block is not attached to unused terminals
(from terminal 13 to 24) depending on model.
Rear view
6.2
Terminal screw
Panel
Terminal cover
(Option)
Terminal cover
(Option)
48
96
Water proof
packing
8.757
2
MTG. FixtureMTG. Fixture
91.4
110.4
If with terminal cover
72.2
If with terminal cover
72.2
8.757
2
93.7
110.4
96
96
Water proof
packing
Terminal cover
93.7
Terminal cover
Panel
91.4
Horizontally close mounting does not meet
NEMA4X/IP66 (front waterproof specification),
because packing cannot be used in this mounting.
PXF5PXF9
t (panel thickness) 1 ≤ t ≤ 8
*
* When using the parameter loader with PXF being mounted
on a panel: t (panel thickness) 1 ≤ t ≤ 4
t (panel thickness) 1 ≤ t ≤ 8
*
* When using the parameter loader with PXF being mounted
on a panel: t (panel thickness) 1 ≤ t ≤ 4
Caution
Panel cut dimensions should also meet the above dimensions after the panel is coated.
Cautions when Close Fit Mounting:
● When the power supply is AC 200V, keep the maximum ambient temperature at 45°C.
● If any equipment or walls which have a depth of 70 mm exist around this instrument,
keep a clearance of at least: 30 mm on the both sides, 50 mm below, 30 mm above.
Cautions when wiring:
● Start by wiring from the left-hand terminals (terminals 1 to 12).
● Use a screw that is the right size on terminals and tighten them with a torque of about 0.8
N/m.
● Do not attach anything to unused terminals. (Do not use relay terminals.)
- 4 -
- 5 -
4. Wiring
4-1. Terminal Connection Diagram (Syandard type)
Alarm output
1 or 2 points3 points
2 points
(independent common)
9
8
7
6
9
8
7
6
9
8
7
6
AL1
AL2
AL2 COM
AL1 COM
AL1
AL3
COM
AL2
AL1
AL2
COM
Non-C
(Note 1)
Note 1: Power supplies for AL1 and AL2 must be of the same type,
either AC or DC.
Option
Digital input
DI2
DI1
DI-COM
RS-485
Remote SV input
CT input
CT1
RS485
+
–
Digital output
Digital input
Option
Standard type
-
+
-
+
–
+
–
+
–
+
–
+
–
+
–
+
-
+
Power supply
24VAC/24VDC
+
–
A
B
B
+
–
+
–
35
34
36
35
34
36
35
36
35
36
5
4
6
7
8
9
10
11
12
2
3
1
17
16
18
19
20
21
22
23
24
14
15
13
29
28
30
31
32
33
34
35
36
26
27
25
100-240VAC
50/60Hz50/60Hz
12
11
12
11
26
25
28
29
27
32
33
31
DI4
DI5
DI3
DI-COM
AL5
AL4
COM
14
15
13
Relay output
(SPST)
2
1
5
4
5
4
5
4
5
4
5
4
5
4
Relay output
(SPDT)
Control
output 1
Control
output 2
SSR
Current
Voltage
2
1
2
1
2
1
2
3
1
COM
OUT1
COM
OUT1
COM
OUT1
COM
NC
NO
OUT1
OUT1
COM
OUT2
COM
OUT2
COM
OUT2
COM
OUT2
COM
OUT2
OUT2
Relay output
(SPST)
SSR
VoltageCurrent
Re-transmission
output (current)
Re-transmission
output (voltage)
RSV1
17
18
19
20
23
24
Process value input
Universal input
RTDCurrent
input
Voltage
input
Thermocouple
Control output 1
● Relay output (SPST)
250 V AC, 3 A (resistive load)
● Relay output (SPDT)
250 V AC, 5 A (resistive load)
● SSR output
12 V DC, 20 mA
● Current output
4 to 20 mA/0 to 20 mA (up to 500 Ω)
● Voltage output
0 to 5 V/1 to 5 V/0 to 10 V/2 to 10 V (MIN. 10 kΩ)
Control output 2
● Relay output
250 V AC, 3 A (resistive load)
● SSR output
12 V DC, 20 mA
● Current output
4 to 20 mA/0 to 20 mA (up to 500 Ω)
● Voltage output
0 to 5 V/1 to 5 V/0 to 10 V/2 to 10 V (MIN. 10 kΩ)
Alarm output 1 to 5
● Relay output
250 V DC, 1 A (resistive load)
Note) If you use PXF as a substitute for PXR or PXG which was used with
SSR output, be careful about the contlol voltage of SSR, for it is different
among PXR, PXG, and PXF.
Model
Output voltage range [V]
minmax
PXF10.713.2
PXR17.025.0
PXG18.024.0
Note) It is not necessary to make a mistake in the wiring for themeasurements
input terminal. There is a possibility that theinput circuit breaks when it
makes a mistake in wiring.
- 5 -
4-2. Terminal Connection Diagram (Motorized valve control type)
Alarm output
1 or 2 points3 points
2 points
(independent common)
9
8
7
6
9
8
7
6
9
8
7
6
AL1
AL2
AL2 COM
AL1 COM
AL1
AL3
COM
AL2
AL1
AL2
COM
Non-C
(Note 1)
Note 1: Power supplies for AL1 and AL2 must be of the same type,
either AC or DC.
I–
I+
Option
Digital input
Valve
control
output 1
Close
COM
Open
Valve Control
Valve Control
Motorized valve control type
COM
2
1
5
4
Power supply
24VAC/24VDC
100-240VAC
50/60Hz50/60Hz
12
11
12
11
Digital input
DI2
DI1
DI-COM
RS-485
PFB input
PFB
RS485
Option
–
+
+
–
A
B
B
+
–
+
–
35
34
36
35
34
36
35
36
35
36
5
4
6
7
8
9
10
11
12
2
3
1
17
16
18
19
20
21
22
23
24
14
15
13
29
28
30
31
32
33
34
35
36
26
27
25
26
25
28
29
27
30
31
32
33
DI3
DI-COM
17
18
RTDCurrent
input
Voltage
input
Thermocouple
Universal input
Process value input
Valve control output 1
● Relay output
250 V AC, 3 A (resistive load)
Alarm output 1 to 3
● Relay output
250 V DC, 1 A (resistive load)
- 6 -
- 7 -
5. Display and Operations
5-1. Part names and functions
Operation parts
USER key
SEL key
USER + key
USER + key
key
key
USER Key
Press this key once in PV/SV display to switch between SV display and MV display.
Press and hold this key in PV/SV display to start the assigned function.
Press this key once in operation control mode, channel-selection mode, or setup mode to return to
PV/SV display.
SEL key
Press this key once in operation mode to move to operation control mode.
Press and hold this key in operation mode to move to channel selection mode.
Press this key once in channel selection mode to move to setup mode.
Press and hold this key in setup mode to move to channel selection mode.
Press this key once in parameter selection submode of setup mode to enter parameter editing
submode.
Press this key once in parameter editing submode to save the change and return to parameter
selection submode.
key
Use this key to select the digit when changing values.
keys
Use this key to change SV value when in PV/SV screen.
Press this key in operation control mode, channel selection mode, or setup mode, to change
parameters to be displayed.
Use this key to edit parameter when in parameter setting submode.
USER+
key
Press and hold this key in PV/SV display to start the assigned function.
(The factory set function for this key is switching between RUN and standby.)
USER+ key
Press and hold this key in PV/SV display to start the assigned function.
(The factory set function for this key is switching between start/stop of auto-tuning.)
Display
(3)
(1)
(16)
(2)
(9)(18)
(6)
(7)
(8)
(12)
(11)
(5)
(4)
PXF5
(2)
(1)
(17)
(3)(18)(9)(12)
(11)
(15)
(14)
(13)
(10)
(4)(5)(6)(7)(8)
PXF9
(17)
(13)
(14)
(15)
(10)
(16)
(1) Process value (PV)
Indicates process value. Shows parameter name when in parameter setting.
(2) Set point (SV)
Shows set point. Shows parameter set value when in parameter setting.
(3) Screen No.
Shows screen No. when in parameter setting.
(4) OUT 1 indicator
Lights during control output 1 is ON.
(5) OUT 2 indicator
Lights during control output 2 is ON.
(6) EV 1, EV 2, EV 3 indicators
Lights during digital output 1 to 3 are ON.
(7) STBY indicator
Lights during standby.
(8) MANU indicator
Lights during manual mode.
(9) Lock indicator
Lights during key lock.
(10) No. indicator
Lights during indicating screen No.
(11) RUN/HOLD/END indicators
Lights during ramp/soak operation.
(12) AT indicator
Lights during auto tuning.
(13) MV indicator
Lights during MV is indicated on SV display.
(14) TM indicator
Lights during the time is indicated on SV display.
(15) RMN indicator
Lights during remaining time is indicated on SV display.
(16) °C/°F indicator
Shows the temperature unit under use.
(17) A/%/kW/h indicator
Shows the unit under use for the values indicated on SV display.
(18) Bar graph display
Displays a bar graph of control output (MV) during operation.
- 7 -
5-2. Basic Operations
The below gure illustrates the mode transition and the key operations.
Operation mode
Operation control mode
Channel selection mode
Setup mode
In this mode the normal operation is performed. The process value (PV) and the set value (SV) are displayed. The device starts in this mode when you turn on the
power. You can change the set value (SV) in this mode. You can check the output value (MV) and the amount of electric ower by switchin the screen.
In this mode you can put the device to standby or change the alarm set value.
In this mode you can select the parameter channel to be displayed.
In this mode you can setup each parameter. This mode includes the parameter selection submode and the parameter editing submode, which can be switched by
SEL key. In the parameter selection submode, you can switch between parameters by using ΛV keys. In theparameterediting submode, you can changeparameter
values by using ΛV keys.
Power ON
Operation
mode
(Operation
screen)
PV/SVdisplay
PV/power
PV/MVdisplay
AUTO/MANUAL
Press
andhold
P
Press
andhold
in the selected channel
Parameter
ex) ch1 PID
Parameter
Operation
control mode
Setup mode
Channel
selection mode
Ch1Ch2Ch3Ch4Ch5Ch6
PIDPLTPRGMONALMSET
Ch7Ch8Ch9Ch11Ch12Ch13
SYSMATHCOMDSPCFGPASS
i
d
Channel
5-3. Changing values on operation screen
● Changing SV (set values)
Change the display to PV/SV display (shown when you turn on the power and the SV lamp is
lit).
Change the SV with the
keys.
Press the
key to save the values.
(The value will be automatically saved after 3 seconds even if a key is not pressed.)
1
2
3
● Changing MV (control output values)
Switch to manual mode.
Change the display to PV/MV display (MAN/AT/SELF lamp is lit).
(Pressing the
key in manual mode toggles between PV/SV display and PV/MV display.)
Change the MV with the
keys.
(Changes are reected to the MV as it is changed.)
See “7-8 Manual Output” (page 15) for more about changing to manual mode.
1
2
3
- 8 -
- 9 -
6. Parameter List
The following explains each channel parameter.
● The list also shows the operational range of set values for parameters that are limited.
● When the PV input lower limit (Pvb), PV input upper limit (PvF), or decimal place position (Pvd) is
changed, recongure all the initial parameter setting values.
● When the parameter that has [RESET] on its Remarks column is changed, turn off the power once,
and then re-start the controller.
Operation control parameter
Parameter
FunctionSetting rangeInitial valueRemarks
№DisplayName
1
Switchover between auto and manual
mode
Switchover between auto and manual modesoFF (auto) / on(manual)oFFThis parameter is not displayed in default setting. If you
need to change this parameter, change the setting of
"Ch11 dSP" so that it appears.
2Switchover between RUN and standbySwitchover the operation mode between RUN and standbyoFF(RUN) / on(standby)oFF
3
Local/remote switchoverSwitches the operation between local/remote SV.LoCL (local)/ REM (remote)LoCL
4
Ramp soak control commandChanges ramp soak run statesoFF (stop)rUn (run)hLd (hold)oFFDisplays End (when ending) or GS (during guaranty
soak).
5Auto-tuning run commandRuns auto-tuning.oFF (stop/nish) on (normal type)
BetaSets 2-degrees-of-freedom coefcient β0.0 to 999.9%100.0%
Note 1: “SvL” and “Svh” must be set so that SvL < Svh. When you change the values for “SvL” and “Svh”, check SV 1 (“Sv1 Ch2”) through SV 7 (“Sv7 Ch2”).
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.