Fault finding list for troubleshooting ............................................................................... 16
Declaration of conformity .............................................................................................. 17
2
Dimensions
207
7 9 10 11 12 13 14 15
NRS 2-3
OFF
ON
16654321
67.7
80
∅ 6
MAX
88
180
MIN
17
Fig. 1
169
NRS 2-3
MAX
OFF
ON
MIN
45.3 (9TE)
(TE = division units)
(1 TE = 5.08 mm)
128.5
3
Parts Drawings
7 9 10 11 12 13 14 15
NRS 2-3
D
C
C
MAX
OFF
E
F
KJ
ON
B
A
MIN
16654321
17
H
I
NRS 2-3
MAX
L
MAX 70 °C
OFF
4
ON
MAX 95 %
MIN
IP 10
Fig. 2
Key
A
LED “Low Level”
B
LED “Pump
C
LED “Pump
D
LED “High Level”
E
Adjustor for high level
F
Adjustor for pump
H
Adjustor for pump ON
I
Adjustor for low level
J
Fixing screws
K
Screw-type terminal strip
L
32way Euro card connector
ON”
OFF“
OFF
5
Important Notes
Usage for the intended purpose
Use level switch NRS 2-3 only in conjunction with GESTRA level transmitter
NRGT 26-1 as pump control.
Safety Note
The equipment must only be installed by qualified staff.
Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with
regulations concerning electrical safety systems, and first aid & accident
prevention – have achieved a recognised level of competence appropriate to
the installation and commissioning of this device.
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents
the danger of electric shock.
Cut off power supply before inserting or removing the 19" slide-in unit and
before carrying out any installation or maintenance work.
6
Explanatory Notes
Scope of supply
NRS 2-3, design “b”
1 Level switch NRS 2-3
1 Mounting panel for installation in control cabinets
1 Installation manual
The level switch type NRS 2-3 is an analogue electronic control instrument (pump
control) for the capacitance level transmitter type NRGT 26-1.
In combination with this transmitter the switch can signal the following levels:
High level, low level, level control unit
and can be used as level controller for steam boilers and pressurized hot-water plants.
Function
ON/OFF
The standardized input current signal is transformed by the resistor into a levelproportional voltage and then preamplified. This voltage is fed to three voltage
comparators V1, V2, V3 and compared with adjustable reference voltages. Depending
on the comparison result the relays will be (de)energized as follows:
■
If the level voltage across V1 is higher than the reference voltage, relay 1 is
de-energized and the red LED illuminated.
■
If the level voltage across V3 is lower than the reference voltage, relay 3 is
de-energized and the red LED illuminated.
■
If the level voltage across V3 is higher than the reference voltage, relay 3 is
energized and the red LED extinguishes.
D
A
A
V2 works as switching controller, e. g. for the boiler feed pump.
■ If the level voltage across V2 is lower than the reference voltage, relay 2 will switch
on the pump. The yellow LED is illuminated.
B
The pump switches off in accordance with the adjusted hysteresis, which is adjustable
over 1 % to 50 % of the level transmitter measuring range. Once the adjusted value is
reached the relay 2 switches off the pump and the green LED is illuminated.
C
7
Explanatory Notes– continued –
Designs
Design “b”
19" slide-in unit to DIN 41494 part 5, installed on a mounting panel for installation
in control cabinets with screw-type terminals at the top and bottom.
Design “c”
19" slide-in unit with guide rails and 32 pole screw-type connector for the installation in
19" mounting panels acc. to DIN 41494 part 5.
Design “d”
19" spare slide-in unit
Technical Data
Type approval no.
GL 99249-96HH
Mains voltage
230 V ± 10%, 50/60 Hz
115 V ± 10%, 50/60 Hz (option)
24 V ± 10%, 50/60 Hz (option)
Power consumption
5 VA
Input
4 – 20 mA (coming from level transmitter)
Output
3 volt-free relay contacts
Max. contact rating with switching voltages of 24V, 115 V and 230 V AC: 4A resistive,
0.75 A inductive at cos ϕ = 0.5.
Max. contact rating with a switching voltage of 24V DC: 4A
Service life of relay: 30 x 10
Limit value
HIGHLEVEL/LOWLEVEL
6
switching cycles.
Continuously adjustable within measuring range of level transmitter
Switchpoints
PUMPON /OFF
Continuously adjustable within 1– 50 % of the measuring range of level transmitter
Indicators and adjustors
1 red LED “
1 green LED “
4 adjustors for
HIGHLEVEL”, 1 red LED “LOWLEVEL”, 1 yellow LED “PUMPON”,
PUMPOFF”.
HIGHLEVEL/LOWLEVEL and PUMPON/ OFF.
Protection
IP 10 to DIN EN 60529
8
Explanatory Notes– continued –
Technical Data – continued –
Max. admissible ambient temperature
0°C to +70 °C
Case
19" slide-in unit with front panel to DIN 41494 part 5 and rear 32 way Euro card
connector to DIN 41612 installed in a mounting panel or for installation in
19" mounting panel.
Front panel, mounting panel: aluminium
Wiring
Design “b”: screw-type terminal strips at the back of the mounting panel, max.
conductor size 1.5 mm²
Design “c”: 32 pole screw-type connector at the back of the 19" mounting panel, max.
conductor size 1.5 mm²
Supply line to level transmitter: screened two-core cable, conductor size 0.5 mm²,
max. cable length 150 m
Internal fuse
Glass cartridge fine-wire fuse M 0.05 A, 5 x20, replaceable
Weight
approx. 0.8 kg
9
Installation
Design “b”
1. Drill four holes into the mounting panel of the control cabinet.
2. Put level switch onto the mounting panel and align.
3. Insert matching screws and fasten.
Design “c”/“d”
1. Install guide rails and screw-type connector into 19" mounting panel.
2. Insert 19" slide-in unit into the guide rails until it hits the stop.
3. Fasten the fixing screws .
Tools
■
Screwdriver for slotted screws, size 2mm, 5 mm, completely insulated to VDE 0680
J
10
Wiring
Design “b”
Wiring is effected via the two screw-type terminal strips. Use screened two-core cable,
conductor size 0.5 mm², max. cable length 150 m for the supply of the level
transmitter.
Wiring diagram for design “b”
G 2.5 A
2
3
4
1
5
Fig. 3Example of fill control with second level indicator
Key to wiring diagram
1
Level transmitter, output 4 –20 mA
2
High level
3
Water level controller (fill control)
4
Low level (LED red/green)
5
Connection for another device, e. g. NRR 2-3
11
Wiring– continued –
Design “c”/“d”
Wiring is effected via the 32 pole screw-type connector.
Use screened two-core cable, conductor size 0.5 mm², max. cable length 150 m for
the supply of the level transmitter.
Wiring diagram for design “c”/ “d”
2
3
4
1
12
5
Fig. 4
Attention
■
Protect the control circuit with a 2.5 A (slow blow) fuse.
■
Connect screen only to the assigned terminal of the NRS 2-3.
■
The screen must not make any other electrical contact.
■
When switching off inductive loads, voltage spikes are produced that
may impair the operation of control and measuring systems. Inductive
loads should therefore be provided with commercial arc suppressor
RC combinations, e. g. 0.1 µF/ 100 Ω.
Commissioning
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the
danger of electric shock.
Cut off power supply before removing or inserting the 19" slide-in unit or
undertaking any kind of installation or maintenance work.
Note
The level switch NRS 2-3 can only be operated and checked in
combination with the level transmitter NRGT 26-1s.
Check wiring
1. Check whether the 19" slide-in unit has been properly installed in the mounting
panel.
2. Check whether the mains supply corresponds to the wiring carried out on the
equipment.
Apply mains voltage
1. Switch on the mains supply and verify that the NRS 2-3 is receiving power. The
BC
LED or will illuminate to verify this.
Adjust the switchpoint “Low Level”
1. Fill the tank and observe the level indicator until the water has reached the desired
level.
2. Turn the adjustor from the left stop slowly to the right just until the red LED
IA
lights up.
Adjust the switchpoint “Pump ON”
1. Raise the water level in the tank until the desired switchpoint for the feedpump is
reached.
2. Turn the adjustors and to the left stop.
3. Turn the adjustor from the left stop to the right until the yellow LED lights up.
4. Turn the adjustor to the right stop. The green LED is not illuminated.
FH
HB
FC
13
Commissioning– continued –
Adjust the switchpoint “Pump OFF”
1. Raise the water level in the tank until the desired switchpoint for the pump is
reached.
2. Turn the adjustor to the left until the green LED
3. Carry out a final adjustment during operation: Adjust such that the exact
switchpoint is achieved. Turning to the right increases the separation between the
pump on and pump off positions.
Adjust the switchpoint „High level“
1. Fill the tank until the max. admissible water level is reached.
2. Turn the adjustor from the right stop slowly to the left until the red LED
lights up.
Note
FC
ED
PUMPOFF lights up.
F
You can directly change the switchpoints over the whole measuring range
of the level transmitter by using the adjustors for LOWLEVEL, for PUMP
ON
E
and for HIGHLEVEL. To avoid confusion of the switchpoints during
IH
commissioning, we recommend that the above-mentioned sequence is
carefully followed.
The adjustor for
PUMPON only.
F
PUMPOFF is for changing the distance to the switchpoint
Table 1 Switchpoints
Mark the adjusted switchpoints either on the water level indicator and/or enter the data
into the following table:
Switchpoint(above the lowest water level)
OW level...................... mm
L
Pump
ON...................... mm
OFF...................... mm
Pump
H
IGH level...................... mm
14
Operation
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the
danger of electric shock.
Cut off power supply before removing or inserting the 19" slide-in unit or
undertaking any kind of installation or maintenance work.
Note
The level switch NRS 2-3 can only be operated and checked in combination
with the level transmitter NRGT 26-1s.
Correct switchpoints
During operation you have to correct the switchpoints if the following
malfunctions occur:
■
Pump is switched on and off too frequently
Increase the distance between the switchpoints
adjustor to the right.
■
Signal LOWLEVEL too frequently
Raise the switchpoint
Turn the adjustor to the right or the adjustor for
■
Signal HIGHLEVEL too frequently
Raise the switchpoint
Turn the adjustor to the right or the adjustor to the left.
F
PUMPON or lower the switchpoint LOWLEVEL.
HI
HIGHLEVEL or lower the switchpoint PUMPOFF.
EF
If it is not possible to make this rectification install a time relay to delay the signal
LOWLEVEL by 2 to 20 sec.
PUMPON and PUMPOFF. Turn the
LOWLEVEL to the left.
Check power
1. Check the measuring current coming from the level transmitter across the
terminals 5(+) and 6(–) in the case of design “b” and A22/C24 in the case of
design “c” and “d”.
Measuring current: 4 to 20 mA
15
Annex
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the
danger of electric shock.
Cut off power supply before inserting or removing the 19" slide-in unit and
before carrying out any installation or maintenance work.
Fault finding list for troubleshooting
After applying mains voltage LEDs and do not light up
Fault:The mains voltage is not applied across the equipment.
Remedy: Apply mains voltage. Check installation of the 19" slide-in unit.
Fault:The internal fuse is defective.
Remedy: Remove the 19" slide-in unit and replace the internal fuse.
Incorrect measuring current between electrode terminal 2 and NRS terminal
5 or A22 defective
Fault:The level transmitter NRGT 26-1s is defective.
Remedy: Check level transmitter (see installation instructions NRGT 26-1s).
Level switch does not work properly despite correct measuring current
Vertretungen weltweit · Agencies all over the world · Représentations dans le monde entier · Representaciones en todo el mundo · Agenzie in tutto il mondo
España
GESTRA ESPAÑOLA S.A.
Luis Cabrera, 86-88
E-28002 Madrid
Tel. 00 3491 /5 152032
Fax 003491/4136747; 5152036
E-mail: gestra@gestra.es
Polska
GESTRA POLONIA Spolka zo. o.
Ul. Schuberta 104, P. O. Box 71
PL-80-172 Gdansk
Tel. 00 4858/ 30610 02 oder 30610 10
Fax 00 48 58/306 10 03 oder 306 3300
E-mail: gestra@gestra.pl