Flowserve NRS 2-3 User Manual

NRS 2-3
Installation Instructions 810414-01
Level Switch Type NRS 2-3
1
Contents
Page
Important Notes
Usage for the intended purpose ......................................................................................6
Safety Note .....................................................................................................................6
Explanatory Notes
System description ..........................................................................................................7
Technical data ........................................................................................................... 8 – 9
Installation
Design “b” ......................................................................................................................10
Design “c”/“d” ................................................................................................................10
Tools ..............................................................................................................................10
Wiring
Design “b” ......................................................................................................................11
Wiring diagram for design “b” ........................................................................................11
Key to wiring diagram.................................................................................................... 11
Design “c”/“d” ................................................................................................................12
Wiring diagram for design “c”/“d”................................................................................... 12
Attention ........................................................................................................................12
Commissioning
Warning .........................................................................................................................13
Check wiring.................................................................................................................. 13
Apply mains voltage ......................................................................................................13
Adjust switchpoint “Low Level” ......................................................................................13
Adjust switchpoint “Pump Adjust switchpoint “Pump
ON” ........................................................................................13
OFF” ......................................................................................14
Adjust switchpoint “High Level” ..................................................................................... 14
Table “Switchpoints” ......................................................................................................14
Operation
Warning .........................................................................................................................15
Correct switchpoints ......................................................................................................15
Check power .................................................................................................................15
Annex
Warning .........................................................................................................................16
Fault finding list for troubleshooting ............................................................................... 16
Declaration of conformity .............................................................................................. 17
2
Dimensions
207
7 9 10 11 12 13 14 15
NRS 2-3
OFF
ON
16654321
67.7 80
6
MAX
88
180
MIN
17
Fig. 1
169
NRS 2-3
MAX
OFF
ON
MIN
45.3 (9TE)
(TE = division units) (1 TE = 5.08 mm)
128.5
3
Parts Drawings
7 9 10 11 12 13 14 15
NRS 2-3
D
C
C
MAX
OFF
E
F
KJ
ON
B
A
MIN
16654321
17
H
I
NRS 2-3
MAX
L
MAX 70 °C
OFF
4
ON
MAX 95 %
MIN
IP 10
Fig. 2
Key
A
LED “Low Level”
B
LED “Pump
C
LED “Pump
D
LED “High Level”
E
Adjustor for high level
F
Adjustor for pump
H
Adjustor for pump ON
I
Adjustor for low level
J
Fixing screws
K
Screw-type terminal strip
L
32way Euro card connector
ON
OFF
OFF
5
Important Notes
Usage for the intended purpose
Use level switch NRS 2-3 only in conjunction with GESTRA level transmitter NRGT 26-1 as pump control.
Safety Note
The equipment must only be installed by qualified staff. Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with regulations concerning electrical safety systems, and first aid & accident prevention – have achieved a recognised level of competence appropriate to the installation and commissioning of this device.
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the danger of electric shock. Cut off power supply before inserting or removing the 19" slide-in unit and before carrying out any installation or maintenance work.
6
Explanatory Notes
Scope of supply
NRS 2-3, design “b”
1 Level switch NRS 2-3 1 Mounting panel for installation in control cabinets 1 Installation manual
NRS 2-3, design “c”
1 Level switch NRS 2-3 2 Guide rails 1 32 pole screw-type connector 1 Installation manual
NRS 2-3, design “d”
1 Level switch NRS 2-3 1 Installation manual
System description
The level switch type NRS 2-3 is an analogue electronic control instrument (pump control) for the capacitance level transmitter type NRGT 26-1.
In combination with this transmitter the switch can signal the following levels: High level, low level, level control unit and can be used as level controller for steam boilers and pressurized hot-water plants.
Function
ON/OFF
The standardized input current signal is transformed by the resistor into a level­proportional voltage and then preamplified. This voltage is fed to three voltage comparators V1, V2, V3 and compared with adjustable reference voltages. Depending on the comparison result the relays will be (de)energized as follows:
If the level voltage across V1 is higher than the reference voltage, relay 1 is de-energized and the red LED illuminated.
If the level voltage across V3 is lower than the reference voltage, relay 3 is de-energized and the red LED illuminated.
If the level voltage across V3 is higher than the reference voltage, relay 3 is energized and the red LED extinguishes.
D
A
A
V2 works as switching controller, e. g. for the boiler feed pump.
If the level voltage across V2 is lower than the reference voltage, relay 2 will switch
on the pump. The yellow LED is illuminated.
B
The pump switches off in accordance with the adjusted hysteresis, which is adjustable over 1 % to 50 % of the level transmitter measuring range. Once the adjusted value is reached the relay 2 switches off the pump and the green LED is illuminated.
C
7
Explanatory Notes – continued –
Designs
Design “b”
19" slide-in unit to DIN 41494 part 5, installed on a mounting panel for installation in control cabinets with screw-type terminals at the top and bottom.
Design “c”
19" slide-in unit with guide rails and 32 pole screw-type connector for the installation in 19" mounting panels acc. to DIN 41494 part 5.
Design “d”
19" spare slide-in unit
Technical Data
Type approval no.
GL 99249-96HH
Mains voltage
230 V ± 10%, 50/60 Hz 115 V ± 10%, 50/60 Hz (option) 24 V ± 10%, 50/60 Hz (option)
Power consumption
5 VA
Input
4 – 20 mA (coming from level transmitter)
Output
3 volt-free relay contacts Max. contact rating with switching voltages of 24V, 115 V and 230 V AC: 4A resistive,
0.75 A inductive at cos ϕ = 0.5. Max. contact rating with a switching voltage of 24V DC: 4A Service life of relay: 30 x 10
Limit value
HIGH LEVEL/LOW LEVEL
6
switching cycles.
Continuously adjustable within measuring range of level transmitter
Switchpoints
PUMP ON /OFF
Continuously adjustable within 1– 50 % of the measuring range of level transmitter
Indicators and adjustors
1 red LED “ 1 green LED “ 4 adjustors for
HIGH LEVEL”, 1 red LED “LOW LEVEL”, 1 yellow LED “PUMP ON”,
PUMP OFF”.
HIGH LEVEL/LOW LEVEL and PUMP ON/ OFF.
Protection
IP 10 to DIN EN 60529
8
Explanatory Notes – continued –
Technical Data – continued –
Max. admissible ambient temperature
0°C to +70 °C
Case
19" slide-in unit with front panel to DIN 41494 part 5 and rear 32 way Euro card connector to DIN 41612 installed in a mounting panel or for installation in 19" mounting panel. Front panel, mounting panel: aluminium
Wiring Design “b”: screw-type terminal strips at the back of the mounting panel, max.
conductor size 1.5 mm² Design “c”: 32 pole screw-type connector at the back of the 19" mounting panel, max. conductor size 1.5 mm² Supply line to level transmitter: screened two-core cable, conductor size 0.5 mm², max. cable length 150 m
Internal fuse
Glass cartridge fine-wire fuse M 0.05 A, 5 x20, replaceable
Weight
approx. 0.8 kg
9
Installation
Design “b”
1. Drill four holes into the mounting panel of the control cabinet.
2. Put level switch onto the mounting panel and align.
3. Insert matching screws and fasten.
Design “c”/“d”
1. Install guide rails and screw-type connector into 19" mounting panel.
2. Insert 19" slide-in unit into the guide rails until it hits the stop.
3. Fasten the fixing screws .
Tools
Screwdriver for slotted screws, size 2mm, 5 mm, completely insulated to VDE 0680
J
10
Wiring
Design “b”
Wiring is effected via the two screw-type terminal strips. Use screened two-core cable, conductor size 0.5 mm², max. cable length 150 m for the supply of the level transmitter.
Wiring diagram for design “b”
G 2.5 A
2
3
4
1
5
Fig. 3 Example of fill control with second level indicator
Key to wiring diagram
1
Level transmitter, output 4 –20 mA
2
High level
3
Water level controller (fill control)
4
Low level (LED red/green)
5
Connection for another device, e. g. NRR 2-3
11
Wiring – continued –
Design “c”/“d”
Wiring is effected via the 32 pole screw-type connector. Use screened two-core cable, conductor size 0.5 mm², max. cable length 150 m for the supply of the level transmitter.
Wiring diagram for design “c”/ “d”
2
3
4
1
12
5
Fig. 4
Attention
Protect the control circuit with a 2.5 A (slow blow) fuse.
Connect screen only to the assigned terminal of the NRS 2-3.
The screen must not make any other electrical contact.
When switching off inductive loads, voltage spikes are produced that may impair the operation of control and measuring systems. Inductive loads should therefore be provided with commercial arc suppressor RC combinations, e. g. 0.1 µF/ 100 Ω.
Commissioning
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the danger of electric shock. Cut off power supply before removing or inserting the 19" slide-in unit or undertaking any kind of installation or maintenance work.
Note
The level switch NRS 2-3 can only be operated and checked in combination with the level transmitter NRGT 26-1s.
Check wiring
1. Check whether the 19" slide-in unit has been properly installed in the mounting panel.
2. Check whether the mains supply corresponds to the wiring carried out on the equipment.
Apply mains voltage
1. Switch on the mains supply and verify that the NRS 2-3 is receiving power. The
B C
LED or will illuminate to verify this.
Adjust the switchpoint “Low Level”
1. Fill the tank and observe the level indicator until the water has reached the desired level.
2. Turn the adjustor from the left stop slowly to the right just until the red LED
I A
lights up.
Adjust the switchpoint “Pump ON”
1. Raise the water level in the tank until the desired switchpoint for the feedpump is reached.
2. Turn the adjustors and to the left stop.
3. Turn the adjustor from the left stop to the right until the yellow LED lights up.
4. Turn the adjustor to the right stop. The green LED is not illuminated.
F H
H B
F C
13
Commissioning – continued –
Adjust the switchpoint “Pump OFF”
1. Raise the water level in the tank until the desired switchpoint for the pump is reached.
2. Turn the adjustor to the left until the green LED
3. Carry out a final adjustment during operation: Adjust such that the exact switchpoint is achieved. Turning to the right increases the separation between the pump on and pump off positions.
Adjust the switchpoint „High level“
1. Fill the tank until the max. admissible water level is reached.
2. Turn the adjustor from the right stop slowly to the left until the red LED lights up.
Note
F C
E D
PUMP OFF lights up.
F
You can directly change the switchpoints over the whole measuring range of the level transmitter by using the adjustors for LOW LEVEL, for PUMP
ON
E
and for HIGH LEVEL. To avoid confusion of the switchpoints during
I H
commissioning, we recommend that the above-mentioned sequence is carefully followed. The adjustor for
PUMP ON only.
F
PUMP OFF is for changing the distance to the switchpoint
Table 1 Switchpoints
Mark the adjusted switchpoints either on the water level indicator and/or enter the data into the following table:
Switchpoint (above the lowest water level)
OW level ...................... mm
L Pump
ON ...................... mm
OFF ...................... mm
Pump H
IGH level ...................... mm
14
Operation
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the danger of electric shock. Cut off power supply before removing or inserting the 19" slide-in unit or undertaking any kind of installation or maintenance work.
Note
The level switch NRS 2-3 can only be operated and checked in combination with the level transmitter NRGT 26-1s.
Correct switchpoints
During operation you have to correct the switchpoints if the following malfunctions occur:
Pump is switched on and off too frequently Increase the distance between the switchpoints adjustor to the right.
Signal LOW LEVEL too frequently Raise the switchpoint Turn the adjustor to the right or the adjustor for
Signal HIGH LEVEL too frequently Raise the switchpoint Turn the adjustor to the right or the adjustor to the left.
F
PUMP ON or lower the switchpoint LOW LEVEL.
H I
HIGH LEVEL or lower the switchpoint PUMP OFF.
E F
If it is not possible to make this rectification install a time relay to delay the signal
LOW LEVEL by 2 to 20 sec.
PUMP ON and PUMP OFF. Turn the
LOW LEVEL to the left.
Check power
1. Check the measuring current coming from the level transmitter across the terminals 5(+) and 6(–) in the case of design “b” and A22/C24 in the case of design “c” and “d”. Measuring current: 4 to 20 mA
15
Annex
Warning
The terminal strip of the NRS 2-3 is live during operation. This presents the danger of electric shock. Cut off power supply before inserting or removing the 19" slide-in unit and before carrying out any installation or maintenance work.
Fault finding list for troubleshooting
After applying mains voltage LEDs and do not light up
Fault: The mains voltage is not applied across the equipment. Remedy: Apply mains voltage. Check installation of the 19" slide-in unit.
Fault: The internal fuse is defective. Remedy: Remove the 19" slide-in unit and replace the internal fuse.
Incorrect measuring current between electrode terminal 2 and NRS terminal 5 or A22 defective
Fault: The level transmitter NRGT 26-1s is defective. Remedy: Check level transmitter (see installation instructions NRGT 26-1s).
Level switch does not work properly despite correct measuring current
Fault: The level switch NRS 2-3 is defective. Remedy: Replace level switch.
B C
16
Annex – continued –
Declaration of conformity
We hereby declare that the equipment NRS 2-3 conforms to the following European guidelines:
LV guideline 73/23/eec version 93/68/eec
EMC guideline 89/336/eec version 93/68/eec
which are based on the following harmonised standards:
LV standard EN 60947-5-1: 1991 73/23/eec version 93/68/eec
EMC standard EN 50 081-2, EN 50 082-2
This declaration is no longer valid if modifications are made to the equipment without consultation with us.
Bremen, 28th April 1997
GESTRA GmbH
Head of the Design Dept.
Uwe Bledschun
Academically qualified engineer
Quality Assurance Representative
Walter Meyer
17
181920
GESTRA Gesellschaften · GESTRA Companies · Sociétés GESTRA · Sociedades Gestra · Società GESTRA
Vertretungen weltweit · Agencies all over the world · Représentations dans le monde entier · Representaciones en todo el mundo · Agenzie in tutto il mondo
España GESTRA ESPAÑOLA S.A.
Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 3491 /5 152032 Fax 003491/4136747; 5152036 E-mail: gestra@gestra.es
Polska GESTRA POLONIA Spolka zo. o.
Ul. Schuberta 104, P. O. Box 71 PL-80-172 Gdansk Tel. 00 4858/ 30610 02 oder 30610 10 Fax 00 48 58/306 10 03 oder 306 3300 E-mail: gestra@gestra.pl
France Portugal Flowserve Flow Control S.A. S.
10 Avenue du Centaure, BP 8263 F-95801 CERGY PONTOISE CEDEX Tél. 0 03 31 / 3443 2660 Fax 00331/34432687 E-mail: gnation@flowserve.com
Flowserve Portuguesa, Lda.
Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0035122/6198770 Fax 003 51 22 / 6 1075 75 E-mail: gestra@gestra.pt
Italia
Italgestra S.r.l.
Via Carducci 125 l-20099 Sesto San Giovanni (MI) Tel. 00 3902 /2410 12.1 Fax 00 39 02/ 241012.460 E-mail: info@italgestra.it
®
GESTRA GmbH
Postfach 1054 60 D-28054 Bremen
Münchener Str. 77 D-28215 Bremen
Tel. + 49 (0) 421 35 03-0 Fax + 49 (0) 421 35 03-393
E-mail
gestra.gmbh@flowserve.com
Internet www.gestra.de
A Unit of Flowserve Corporation
810414-01/1102c · © 1997 GESTRA GmbH · Bremen · Printed in Germany
Loading...