■ General

With frequency converters installed, high disturbance levels are caused by fast-acting switching transients of IGBTs on the high voltages used in the dc link and by parasitic capacitance. This can result in conducted disturbances on lines.

Electronic devices connected to the same mains line may be impaired by radio frequency interference (RFI). The RFI filter is designed to reduce these effects.

■ RFI Filter Environmental Conditions

Environment

Value

 

 

Maximum Ambient Temperature

-10°C to 40°C

Humidity

5% to 95%

 

 

CE Conformity

All units are CE marked.

■ Electrical Connections

To insure personal safety, power must be removed from mains during installation. Adhere to all local and national electrical safety standards for high voltage installations.

See VLT instruction manual for important details.

Additional Safety Protection

See the VLT instruction manual for use of Type B residual current device (RCD) relays for additional earth fault protection.

RFI Filter Conducted Emissions

The RFI filter meets the conducted emission requirements of EN55011, Class 1B.

Current Ratings

The external Class 1B RFI filters are rated at 180A and 400A.

Input Fuses

All RFI filter and frequency converter combinations must have input fuses installed in the mains power supply. Input fuses must be supplied by the installer of the equipment at the time of installation. See the VLT instruction manual for the required fuse rating for each converter size.

Mains Voltage/Frequency Ratings

Three phase AC, Vline = 550 Vrms maximum, 50/60 Hz.

■ Leakage Current

Typical Electrical Connection

 

The external RFI filter, motor, and frequency converter experience a high leakage current. The RFI filter and converter must have reinforced earthing in accordance with EN50178. The 180A

filter is specified at <6mA. The 400A filter is specified at <12mA.

MI.56.F1.83 - VLT is a registered Danfoss trademark

3

 

Danfoss VLT5075, VLT5100, VLT6100, VLT6125, VLT5032 Installation guide

VLT® Series 5000/6000 HVAC

English

Mechanical Installation

The following must be observed.

1)The filter and frequency converter must have a large ground-contact surface. Mount on a common, earthed metal plate or switch gear cabinet panel.

2)The contact surface for mounting the RFI filter must be clean, unpainted, bright metal. Paint or other insulating coatings must be removed prior to mounting the filter.

3)It is important to ensure good electrical contact from the installation back plate through the installation screws to the metal cabinet of the VLT frequency converter.

4)Use of star washers to assure HF connection is recommended.

See the connection diagrams on the following pages.

Wiring

1)Position the toroid between the filter output and the converter. Install tie wraps to secure the wiring (In IP54 auxiliary enclosures, tie-down holes are provided.)

2)Only the 3-phase wiring passes through the toroid. The physical earth (PE) cable must not pass through the toroid.

3)Cable connections between the RFI filter and the frequency converter should be as short as possible.

4)The mains maximum wire size is 95mm2 for 180A filters and 120mm2 X 2 for 400A filters.

5)The PE wire must have a cross-section greater than 50% of the cross-section of the mains wire.

6)Do not install mains and motor cables parallel and near to one another.

7)Maximum cable length of shielded motor wire for Class 1B RFI filter performance is 50m.

Dimension Diagram: 180A RFI Filter

4

MI.56.F1.83 - VLT is a registered Danfoss trademark

VLT® Series 5000/6000 HVAC

Deutsch

Allgemeine Informationen

Bei installierten Frequenzumrichtern kann es in der Hochspannung führenden DC-Verbindung durch schnelle transiente IGBT-Schaltströme und die Eigenkapazität zu einem erheblichen Störniveau kommen. Dies kann leitungsgebunden ausgestrahlte Störungen verursachen. Elektronische Geräte, die an die gleiche Netzleitung angeschlossen sind, können durch Hochfrequenzstörungen (RFI) in ihrer Funktion beeinträchtigt werden. Der Funkentstörfilter (RFI-Filter) besitzt die konstruktionstechnische Aufgabe, diese Störwirkung zu reduzieren.

Betriebsbedingungen für RFI-Filter

Umgebung

Wert

 

 

Max. Umgebungstemperatur

-10°C bis 40°C

 

 

Feuchtigkeit

5% bis 95%

 

 

CE-Konformität

Alle Geräte sind mit einem CE-Kennzeichen versehen.

■ Elektrische Anschlüsse

verstärkte Erdung nach EN50178 aufweisen. Der 180AFilter ist für <6mA ausgelegt. Der 400A-Filter ist für <12mA ausgelegt.

Zusätzlicher Sicherheitsschutz

Informationen über den zusätzlichen Schutz gegen Erdschlußfehler durch Verwendung von Fehlerstromrelais (RCD-Relais Typ B) finden Sie im VLTBedienungshandbuch.

RFI-Filter-Störspannungen

Alle RFI-Filter erfüllen die Störspannungsanforderungen der EN55011, Klasse 1B.

Nennstromstärken

Die Nennstromstärken bei RFI-Filtern der Klasse 1 betragen 180A und 400A.

Zur eigenen Sicherheit muß die Netzversorgung bei der Installation unterbrochen werden.

Alle örtlichen und im Installationsland geltenden Sicherheitsvorschriften für Hochspannungsanlagen sind einzuhalten. Wichtige Hinweise hierzu finden Sie im VLT-Bedienungshandbuch.

Eingangsicherungen

Bei allen RFI-Filter- und

Frequenzumrichterkombinationen müssen Eingangssicherungen in der Netzstromversorgung installiert werden. Die Eingangssicherungen müssen bei der Installation vom Geräteinstallateur geliefert werden. Die für die jeweilige Frequenzumrichtergröße erforderlichen Sicherungsleistungsdaten finden Sie im VLTBedienungshandbuch.

Netzspannung/Frequenz

Drehstrom AC, Vline = 550 Vrms max., 50/60 Hz.

Typische elektrische Verdrahtung

Kriechstrom

Der externe RFI-Filter, der Motor und der Frequenzumrichter weisen hohe Ableitströme auf. RFI-Filter und Frequenzumrichter müssen über eine

MI.56.F1.83 - VLT is a registered Danfoss trademark

5

 

Loading...
+ 9 hidden pages