Bryant R-410A User Manual

0 (0)
Bryant R-410A User Manual

 

 

 

DELUXE 11 SEER

591B (60 Hz)

 

 

 

 

 

 

AIR CONDITIONER

 

 

 

 

WITH PURON® (R-410A)

Sizes 018 thru 060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bryant’s Quantum Plus 591B with Puron® provides features which cannot be matched by any other family of equipment. The 591B is a Quantum Plus air conditioning system utilizing Bryant’s unique Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer. Bryant’s Quantum Plus systems meet the Energy Star® guidelines for energy efficiency.

AVAILABLE OPTIONS

Puron® Environmentally Sound Refrigerant —Is Bryant’s unique refrigerant designed to help protect the environment. Puron is an HFC refrigerant which does not contain chlorine that can harm the ozone layer. The most important advantage of Puron refrigerant is that it has not been banned in future air conditioning systems as the traditional refrigerant R-22 has been. Puron refrigerant is in service in thousands of systems proving highly reliable, environmentally sound performance.

Heavy Duty Inlet Grille—The DuraGuard™ coil protector, made of a coated steel wire grid with vertical 3/8 in. spacing, is designed to help protect the coil from inclement weather, vandalism, and incidental damage. It provides protection while not restricting airflow and maintaining ease of coil inspection and cleaning.

High Efficiency Performance—Is delivered through a combination of features including Bryant’s Puron refrigerant, unique scroll compressor, and advanced heat transfer surfaces. Efficiency ratings are 11 to 12.5 SEER (Seasonal Energy Efficiency Ratio). Sophisticated heat transfer surfaces utilized in Bryant’s 591B design allow heat to easily be transferred to the outdoor air and require less energy. The unique scroll compressor found in the 591B design performs quietly and adds to the overall efficiency of the system. Finally, Bryant’s unique Puron refrigerant operates more efficiently than ordinary R-22 refrigerant found in other systems. The efficiency levels provided by the 591B provide end users with lower costs of operation than traditional air conditioning systems.

Assured Future Service—By utilizing the environmentally sound refrigerant, Puron®, 591B models will remain serviceable

well into the future. The Clean Air Act of 1990 has placed a cap on production of most other refrigerants which has scheduled reductions beginning in 2004. The resulting cap in production ultimately results in a complete ban on many other refrigerants in new equipment by the year 2010. These changes, required by federal law, mean the supply of other refrigerants may be limited in the near future making Puron the correct choice when considering long term serviceability.

Highly Reliable Performance—Is delivered through the superior design of the system and componentry. The reliability of the existing Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past few years of service. Long term reliability is assured through the use of both high and low pressure switches which will not allow the system to operate in the event of a significant change in operating pressure. In doing this, the system is protected from damage if an unusual condition arises. Finally, Bryant includes a special liquid line filter drier designed to trap moisture and contaminants which could otherwise shorten the life of the system.

Application Versatility—Bryant’s systems utilizing Puron refrigerant have the same application guidelines as other systems. Applications which include long line sets (50 to 175 ft) or applications which require the system to operate at low outdoor temperatures (below 55°F) are approved under Bryant’s standard guidelines.

Bryant Coils and Fan Coils to Complete the System—Bryant specially designs both the outdoor product and indoor coil products to operate with assured reliability and performance. A wide range of indoor coil options are listed in the ratings section of this publication.

Special Protective Devices—High and low pressure switches and internal protection in the compressor including temperature and current sensing overloads prevent operation under potentially damaging circumstances. A special liquid line filter drier designed to trap nearly 4 times the volume of contaminants of standard driers provides superior protection from moisture trapped in the system.

Electrical Range—208/230v, single phase.

Wide Range of Sizes—Available in seven sizes; 1-1/2, 2, 2-1/2, 3, 3-1/2, 4, and 5 tons.

Reliant Cabinet—Galvanized steel is coated with powder paint to provide a superior, long lasting appearance.

Totally Enclosed Fan Motor—Protected from adverse weather conditions.

Unit Design—Enhanced copper and aluminum heat transfer surfaces with vertical air discharge to direct air up and away from the area.

External Service Valves—Both service valves are back seating type valves which are externally located. These unique valves allow service technicians to evacuate or charge the system in less time than standard service valves.

Easy Serviceability—One panel provides access to electrical controls and compressor. Removal of wire dome gives access to fan motor and removal of the top gives access to the coil.

Agency Approvals—591B models are listed with UL, c-UL, ARI, CEC, and CSA-EEV. Special endorsements have also been awarded these products by Energy Star® which recognizes energy efficient products.

Limited Warranty—A standard five year warranty on parts with a 10 year limited warranty on the compressor. Optional warranties are available through your Bryant distributor.

Form No. PDS 591B.18.1

—2—

 

 

3/8" DIA. TIEDOWN KNOCKOUTS

 

 

 

 

 

(2) PLACES

 

 

 

 

L

C

FIELD POWER SUPPLY CONN. 7/8" DIA.

 

 

2 1/2"

HOLE WITH 1 1/8" DIA. KNOCKOUT

 

 

AND 1 3/8" DIA. KNOCKOUT

B

 

AIR IN

AIR DISCHARGE

AIR DISCHARGE

 

1 9/16"

 

 

 

 

 

 

 

 

 

 

K

FIELD CONTROL

 

ACCESS

 

 

SUPPLY CONN

 

 

 

D

7/8" DIA. HOLE

 

PANEL

 

 

H DIA. VAPOR

A

 

AIR IN

 

C

 

 

L

LINE CONN.

G

 

 

 

 

 

 

 

 

E

3/8" DIA. LIQUID

F

 

 

 

 

LINE CONN.

 

 

 

 

 

10 1/2"

M

 

 

 

 

 

 

 

 

 

4 3/16"

 

 

AIR DISCHARGE

AIR IN

J

 

1 1/4"

 

 

 

N

 

DIMENSIONS

 

 

 

1 3/4"

 

 

 

 

 

 

NOTES:

1.

ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE

 

SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.

2.

MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F,

 

(UNLESS LOW AMBIENT CONTROL IS USED) MAX. 125°F.

3.

SERIES DESIGNATION IS THE 14TH POSITION OF THE UNIT MODEL NUMBER.

4.

CENTER OF GRAVITY .

A99067

DIMENSIONS (IN.)

 

 

 

 

 

 

 

UNIT DIMENSIONS

 

 

 

 

 

 

MINIMUM

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOUNTING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

SERIES

A

B

C

D

E

F

G

 

H

J

K

L

M

N

PAD DIMENSIONS

018

A

23-13/16

22-1/2

27-1/2

2-13/16

6-15/16

13-15/16

18-3/8

 

5/8

8-3/16

12-1/2

14

16-1/2

2-3/8

20 x 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

A

27-13/16

22-1/2

27-1/2

2-13/16

6-15/16

15-15/16

22-3/8

 

5/8

8-3/16

12-1/2

14

16-1/2

2-15/16

20 x 32

030

A

27-13/16

22-1/2

27-1/2

2-13/16

6-15/16

15-15/16

22-3/8

 

3/4

8-3/16

12-1/2

14

16-1/2

2-15/16

20 x 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

A

33-13/16

22-1/2

27-1/2

2-13/16

6-15/16

21-15/16

28-3/8

 

3/4

8-3/16

12-1/2

14

17-1/2

2-15/16

20 x 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

A

27-13/16

30

33

5-1/16

9-11/16

15-15/16

22-3/8

 

7/8

8-3/16

18-1/2

19-3/4

13

2-15/16

26 x 32

048

A

27-13/16

30

33

5-1/16

9-11/16

15-15/16

22-3/8

 

7/8

8-3/16

18-1/2

19-3/4

13

2-15/16

26 x 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

A

39-13/16

30

33

5-1/16

9-11/16

27-15/16

34-3/8

 

7/8

8-3/16

17-3/4

19

17-3/4

2-15/16

26 x 32

RECOMMENDED TUBE DIAMETERS

 

Liquid Tube Diameter (In.)

Vapor Tube Diameter (In.)

UNIT

0 to 50 Ft

 

0 to 50 Ft

Long-Line Applications*

SIZE

Tube Length

Long-Line Applications*

Tube Length

(Maximum Diameter)

018

 

 

5/8

3/4

024

 

 

5/8

3/4

 

 

 

 

 

030, 036

3/8

3/8

3/4

7/8

 

 

 

 

 

042, 048

 

 

7/8

1-1/8

060

 

 

1-1/8

1-1/8

* For tube sets greater than 50 ft, consult Application Guideline and Service Manual— Air Conditioners and Heat Pumps Using Puron® Refrigerant.

CHECK-FLO-RATER® PISTON

 

PISTON*

UNIT SIZE–SERIES

IDENTIFICATION NO.

018-A

49

 

 

024-A

59

030-A

63

 

 

036-A

67

 

 

042-A

73

048-A

78

 

 

060-A

90

*Piston listed is for any approved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an approved indoor coil.

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE*)

UNIT SIZE–SERIES

REQUIRED SUBCOOLING (°F)

018-A

15

024-A

15

 

 

030-A

16

 

 

036-A

18

042-A

18

 

 

048-A

16

 

 

060-A

14

* Must be a Puron® approved hard shutoff TXV.

As an ENERGY STAR® partner, Bryant Heating & Cooling Systems has determined that this product meets the ENERGY

STAR® guidelines for energy efficiency.

T

U

C

 

A

 

F

 

U

 

N

 

A

 

M

R

E

R

 

 

 

D

 

 

FIE

 

 

TI

 

 

R

 

E

 

 

C

 

 

 

 

 

Y

 

IT

A

R

 

 

 

 

N

 

 

 

U

 

 

 

T

 

 

 

 

 

 

O A

 

 

 

 

 

 

RI

 

 

 

 

 

 

AS

 

 

 

 

 

 

C

 

AIR

O

 

C

M

 

 

P

 

 

O

L

 

 

N

 

 

D

Y

 

 

 

 

 

I

I

 

 

 

 

 

T

 

 

 

 

O

N

 

 

 

 

I

 

 

 

 

 

 

N

G

 

 

 

 

I

W

 

 

 

 

 

N

 

 

 

 

G

I

 

 

 

 

 

 

T

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

A RI

S

E

T

 

 

QUIPMEN

0

 

 

 

1

 

2

 

 

D

 

TANDAR

 

CERTIFICATION APPLIES ONLY

REGISTERED QUALITY SYSTEM

WHEN THE COMPLETE SYSTEM

 

IS LISTED WITH ARI.

 

— 3—

SPECIFICATIONS

UNIT SIZE-SERIES

018-A

024-A

 

030-A

036-A

 

 

 

 

 

 

 

 

 

 

 

Operating Weight (Lb)

168

178

 

188

198

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

 

Unit Volts— Hertz— Phase

 

208/230-60-1

 

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range*

 

 

187-253

 

 

 

 

 

 

 

 

 

 

 

Compressor— Rated Load Amps

10.3

13.5

 

15.4

17.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

51.0

61.0

 

73.0

100.0

 

 

 

 

 

 

 

 

 

 

 

Condenser Fan Motor— Full Load Amps

0.50

0.75

 

0.75

1.40

 

 

 

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

13.4

17.4

 

19.2

20.1

 

 

 

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

14

14

 

14

12

 

 

 

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

14

14

 

14

12

 

 

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

56

44

 

39

52

 

 

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

54

42

 

37

50

 

 

 

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

 

 

Circuit Breaker Size (Amps)

20

30

 

30

40

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

 

 

Compressor— Type

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manufacturer

 

 

Copeland

 

 

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

Internal Line Break

 

 

 

 

 

 

 

 

 

 

Refrigerant— Type

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

 

 

 

 

 

Amount (Lb)

4.15

4.66

 

5.28

6.13

 

 

 

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

 

 

Coil Face Area (Sq Ft)

7.27

8.72

 

8.72

10.9

 

 

 

 

 

 

 

 

 

 

 

Fins per In.— Rows— Circuits

20— 1— 1

25— 1— 2

 

25— 1— 2

25— 1— 2

 

 

 

 

 

 

 

 

 

 

Fan Motor— HP (PSC) & RPM

1/12 & 1100

1/10 & 1100

 

1/10 & 1100

1/10 & 1100

 

 

 

 

 

 

 

 

 

 

Volts— Hertz— Phase

 

208/230-60-1

 

 

 

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

1700

2000

 

2000

2500

 

 

 

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

 

Support Feet

 

KSASF0101AAA

 

 

 

 

 

 

 

 

 

 

Coastal Filter

 

KAACF0701SML

 

 

Time Delay Relay

 

KAATD0101TDR

 

 

 

 

 

 

 

 

 

 

Cycle Protector

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

KAACH1201AAA

 

 

 

 

 

 

 

 

 

 

 

 

Start Assist— Capacitor/Relay Type

KSAHS1701AAA

 

 

KSAHS1501AAA

 

 

 

 

 

 

 

 

 

 

Start Assist— PTC Type

 

KAACS0201PTC

 

 

 

 

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

 

KSATX0201HSZ

 

 

KSATX0301HSZ

 

 

 

 

 

 

 

 

Piston Body

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

 

 

 

Filter Drier (Suction Line)

 

 

KH45LG140

 

 

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat†† (RCD)

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

KAALS0201LLS

 

 

 

 

 

 

 

 

 

 

Winter Start Control††

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

KSALA0301410

 

 

 

 

 

 

 

 

 

 

 

MotorMaster® Control** (RCD)

 

 

32LT660004

 

 

 

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor (RCD)

 

 

HC34GE232

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat— Auto Changeover,

 

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

TSTATBBNAC01-B

 

 

Thermostat— Auto Changeover,

 

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

TSTATBBPAC01-B

 

 

Thermidistat™ Control—

 

 

 

 

 

 

Programmable Thermostat with Humidity Control

 

TSTATBBPRH01-B

 

 

Builder’s Thermostat— Manual Changeover,

 

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

TSTATBBBAC01-B

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Sensor

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

 

 

Thermostat Conversion Kit (4 to 5 wire)— 10 Pack

 

TSTATXXCNV10

 

 

 

 

 

 

 

 

 

 

 

 

See notes on page 5.

— 4—

SPECIFICATIONS Continued

UNIT SIZE-SERIES

042-A

 

048-A

 

060-A

Operating Weight (Lb)

215

 

217

 

278

 

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

Unit Volts— Hertz— Phase

 

208/230-60-1

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range*

 

187-253

 

 

 

 

 

 

 

 

 

 

Compressor— Rated Load Amps

19.9

 

24.4

 

30.1

 

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

127.0

 

131.0

 

172.0

 

 

 

 

 

 

 

 

 

Condenser Fan Motor— Full Load Amps

1.10

 

1.40

 

1.40

 

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

24.4

 

26.7

 

35.9

 

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

10

 

8

 

8

 

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

10

 

10

 

8

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

77

 

97

 

80

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

73

 

59

 

76

 

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

 

Circuit Breaker Size (Amps)

40

 

50

 

60

 

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

 

Compressor— Type

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manufacturer

 

 

Copeland

 

 

 

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

 

Internal Line Break

 

 

 

 

 

 

 

 

 

 

 

Refrigerant— Type

 

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

 

 

 

Amount (Lb)

6.33

 

6.83

 

7.93

 

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

 

Coil Face Area (Sq Ft)

12.16

 

12.16

 

18.3

 

 

 

 

 

 

 

 

 

Fins per In.— Rows— Circuits

25— 1— 2

 

25— 1— 2

 

25— 1— 3

 

 

 

 

 

 

 

 

 

Fan Motor— HP (PSC) & RPM

1/5 & 825

 

1/4 & 1100

 

1/4 & 1100

 

 

 

 

 

 

 

 

 

Volts— Hertz— Phase

 

208/230-60-1

 

 

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

2800

 

3400

 

3400

 

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

Support Feet

 

 

KSASF0101AAA

 

 

 

 

 

 

 

 

 

 

 

Coastal Filter

 

 

KAACF0801MED

 

 

 

 

 

 

 

 

 

 

 

Time Delay Relay

 

 

KAATD0101TDR

 

 

 

 

 

 

 

 

 

 

 

Cycle Protector

 

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

KAACH1201AAA

 

 

 

 

 

 

 

 

 

 

Start Assist— Capacitor/Relay Type

 

KSAHS1501AAA

 

KSAHS1601AAA

 

 

 

 

 

 

 

 

 

Start Assist— PTC Type

 

 

KAACS0201PTC

 

 

 

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

KSATX0301HSZ

 

KSATX0401HSZ

 

KSATX0501HSZ

 

 

 

 

 

 

 

 

 

Piston Body

 

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

 

 

 

Filter Drier (Suction Line) (RCD)

 

 

KH45LG141

 

 

 

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat††

 

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

 

KAALS0201LLS

 

 

 

 

 

 

 

 

 

 

 

Winter Start Control††

 

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

 

KSALA0301410

 

 

 

 

 

 

 

 

 

 

 

MotorMaster® Control**

 

 

32LT660004

 

 

 

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor (RCD)

HC38GE231

 

 

HC40GE232

 

 

 

 

 

 

 

 

 

Thermostat— Auto Changeover,

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-B

 

 

 

 

 

 

 

 

 

 

 

Thermostat— Auto Changeover,

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

 

 

 

 

 

 

 

 

 

 

Thermidistat™ Control—

 

 

 

 

 

Programmable Thermostat with Humidity Control

 

 

TSTATBBPRH01-B

 

 

 

 

 

 

 

 

 

 

 

Builder’s Thermostat— Manual Changeover,

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

 

 

 

Thermostat Conversion Kit (4 to 5 wire)— 10 Pack

 

 

TSTATXXCNV10

 

 

 

 

 

 

 

 

 

 

 

*Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

**Fan motor with ball bearings required.

††See low-ambient controller Installation Instructions for application. N/A — Not Applicable.

NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

5—

ACCESSORY USAGE GUIDELINE

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

 

LOW-AMBIENT

LONG-LINE

SEA COAST

 

APPLICATIONS

APPLICATIONS*

APPLICATIONS

ACCESSORY

(Below 55°F)

(Over 50 Ft)

(Within 2 Miles)

 

 

 

 

Crankcase Heater

Yes

Yes

No

 

 

 

 

Evaporator Freeze Thermostat

Yes

No

No

 

 

 

 

Winter Start Control

Yes†

No

No

 

 

 

 

Accumulator

No

No

No

 

 

 

 

Compressor Start Assist

Yes

Yes

No

Capacitor and Relay

 

 

 

 

 

 

 

MotorMaster® Control,

 

 

 

or

Yes

No

No

Low-Ambient Pressure Switch

 

 

 

 

 

 

 

Wind Baffle

See Low-Ambient Instructions

No

No

 

 

 

 

Coastal Filter

No

No

Yes

 

 

 

 

Support Feet

Recommended

No

Recommended

 

 

 

 

Liquid-Line Solenoid Valve

 

See Long-Line

 

or

No

Application

No

Hard Shutoff TXV

 

Guideline

 

 

 

 

 

Ball Bearing Fan Motor

Yes‡

No

No

 

 

 

 

*For tubing line sets greater than 50 ft, refer to Application Guideline and Service Manual— Air Conditioning and Heat Pumps Using Puron® Refrigerant.

Only when low-pressure switch is used.

‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

1.Ball Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

2.Coastal Filter

A mesh screen inserted under the top cover and inside base pan to protect the condenser coil from corrosive atmosphere without restricting airflow.

SUGGESTED USE: In geographic areas where salt damage could occur.

In areas with high pollution levels.

3.Compressor Start Assist—Capacitor/Relay Type

Start capacitor and start relay which gives a “hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).

Installations where Liquid-Line Solenoid Valve or hard shutoff TXV has been added.

4.Compressor Start Assist—PTC Type

Solid-state electrical device which gives a “soft” boost to compressor motor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

5.Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication

on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller. All commercial installations.

6.Cycle Protector

Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including normal room thermostat cycling.

SUGGESTED USE: Installations in areas where power interruptions are frequent.

Where user is likely to “play” with the room thermostat.

All commercial installations.

Installations where interconnecting tube length exceeds 50 ft.

High-rise applications.

7.Evaporator Freeze Thermostat

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE: All units where Winter Start Control has been added.

8.Filter Drier (Suction Line)

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow. See Application Guideline and Service Manual for proper application.

SUGGESTED USE: All split-system air conditioners.

9.Liquid-Line Solenoid Valve (LSV)

An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant

liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. NOTE: Compressor Start Assist— Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.

SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline and Service Manual.

— 6—

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued

10.Low-Ambient Pressure Switch

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

11.MotorMaster® Control

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at

100°F ± 10°F (37.8°C ± 5.6°C).

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

All commercial installations.

12.Outdoor Air Temperature Sensor

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.

SUGGESTED USE: All Bryant programmable thermostats.

13.Piston Body

This piston body is to be used as a replacement for the FK4C Fan Coil R-22 thermostatic expansion valve when used with Puron® (R-410A) air conditioner

units. Use piston and piston ring shipped with outdoor unit for installations under 50 ft. SUGGESTED USE: All Puron® air conditioner installations matched with FK4C Fan Coils.

14.Support Feet

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.

SUGGESTED USE: For improved sound ratings.

Coastal installations.

Windy areas or where debris is normally circulating.

Rooftop installations.

15.Thermostatic Expansion Valve (TXV)

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Hard shutoff valves are available. Do not use with Liquid-Line Solenoid Valve. NOTE: Compressor Start Assist— Capacitor/Relay Type must also be used. Do not use with Liquid Line Solenoid.

SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.

16.Time-Delay Relay

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.

SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.

17.Winter Start Control

An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load

conditions.

SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.

SOUND POWER (dBA) (A-WTD, WITHOUT PURE TONE PENALTY)

 

SOUND

 

 

OCTAVE BAND CENTER FREQUENCY (Hz)

 

 

UNIT

LEVEL

 

 

 

 

 

 

 

 

 

 

 

SIZE

(dBA)

125

250

500

1000

2000

4000

8000

018

74

52.0

63.5

65.5

69.0

64.5

58.0

51.0

 

 

 

 

 

 

 

 

 

024

74

57.5

64.0

67.5

68.5

66.0

60.5

53.0

 

 

 

 

 

 

 

 

 

030

75

58.5

66.0

69.0

69.0

66.0

61.0

53.5

036

77

61.0

67.5

71.0

71.5

70.0

67.0

58.0

 

 

 

 

 

 

 

 

 

042

77

61.0

67.0

68.5

66.5

63.5

56.5

51.5

 

 

 

 

 

 

 

 

 

048

78

61.5

68.0

71.5

72.0

68.5

65.5

60.0

060

78

61.5

65.5

69.0

69.5

65.0

64.0

56.0

— 7—

COMBINATION RATINGS

 

 

 

 

 

 

SEER

 

 

 

 

 

TOT.

FACTORY-

 

Bryant Gas

 

 

UNIT

INDOOR

 

SUPPLIED

 

Furnace or

 

 

 

CAP.

ENHANCE-

Standard

Accessory

Accessory

 

SIZE-SERIES

MODEL

 

BTUH

MENT

Rating

TDR†

Puron TXV

EER

 

CC5A/CD5AA024*

 

17,400

NONE

10.5

11.0

11.0

9.95

 

CC5A/CD5AA018

 

17,000

NONE

10.5

11.0

11.0

9.75

 

CC5A/CD5AW024

 

17,400

NONE

10.5

11.0

11.0

9.95

 

CE3AA024

 

17,400

NONE

10.5

11.0

11.0

10.00

 

CF5AA024

 

17,400

NONE

10.5

11.0

11.0

10.00

 

CK3BA024

 

17,400

NONE

10.5

11.0

11.0

10.05

 

CK5A/CK5BA018

 

17,000

NONE

10.5

11.0

11.0

9.85

 

CK5A/CK5BA024

 

17,400

NONE

10.5

11.0

11.0

10.05

 

CK5A/CK5BW024

 

17,400

NONE

10.5

11.0

11.0

10.05

 

F(A,B)4AN(F,C)018

 

17,000

TDR

11.0

11.0

9.85

 

F(A,B)4AN(F,C)024

 

17,400

TDR

11.0

11.0

10.15

 

FC4BNF024

 

17,400

TDR&TXV

11.0

10.15

 

FF1DNA018

 

17,000

TDR

11.0

11.0

10.10

 

FF1DNA024

 

17,400

TDR

11.0

11.0

10.00

 

FG3AAA024

 

17,300

NONE

11.0

11.0

9.85

 

FK4CNF001

 

17,400

TDR&TXV

12.5

11.25

018-A

FK4CNF002

 

17,800

TDR&TXV

12.5

11.30

FV4ANF002

 

17,800

TDR&TXV

12.5

11.30

 

 

 

FX4ANF018

 

17,400

TDR&TXV

11.0

10.15

 

 

COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AA018

 

16,800

TDR

11.5

11.5

10.55

 

CC5A/CD5AA024

 

17,400

TDR

11.5

11.5

10.85

 

CE3AA024

 

17,400

TDR

11.5

11.5

10.85

 

CK3BA024

 

17,400

TDR

11.5

11.5

11.15

 

CK5A/CK5BA018

 

17,000

TDR

11.5

11.5

10.85

 

CK5A/CK5BA024

 

17,400

TDR

11.5

11.5

11.15

 

 

COILS + 355MAV042060 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW024

 

17,400

TDR

11.5

11.5

10.85

 

CE3AA024

 

17,400

TDR

11.5

11.5

10.90

 

CK5A/CK5BW024

 

17,400

TDR

11.5

11.5

10.95

 

 

COILS + 355MAV042080 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW024

 

17,400

TDR

11.5

11.5

10.90

 

CC5A/CD5AA030*

 

23,800

NONE

10.5

11.0

11.0

9.70

 

CC5A/CD5AA024

 

23,400

NONE

10.5

11.0

11.0

9.60

 

CC5A/CD5AW024

 

23,400

NONE

10.5

11.0

11.0

9.60

 

CC5A/CD5AW030

 

23,800

NONE

10.5

11.0

11.0

9.70

 

CE3AA024

 

23,400

NONE

10.5

11.0

11.0

9.70

 

CE3AA030

 

23,800

NONE

10.5

11.0

11.0

9.75

 

CF5AA024

 

23,400

NONE

10.5

11.0

11.0

9.65

 

CK3BA024

 

23,400

NONE

10.5

11.0

11.0

9.75

 

CK3BA030

 

23,800

NONE

10.5

11.0

11.0

9.80

 

CK5A/CK5BA024

 

23,400

NONE

10.5

11.0

11.0

9.75

 

CK5A/CK5BA030

 

23,800

NONE

10.5

11.0

11.0

9.80

 

CK5A/CK5BW024

 

23,400

NONE

10.5

11.0

11.0

9.75

 

CK5A/CK5BW030

 

23,800

NONE

10.5

11.0

11.0

9.80

 

F(A,B)4AN(F,C)024

 

23,400

TDR

11.0

11.0

9.80

 

F(A,B)4AN(F,C)030

 

23,800

TDR

11.0

11.0

9.70

 

FC4BNF024

 

23,400

TDR&TXV

11.0

9.80

 

FC4BNF030

 

23,800

TDR&TXV

11.0

10.00

 

FF1(B,C,D)NA024

 

23,400

TDR

11.0

11.0

9.65

 

FF1(B,C,D)NA030

 

23,800

TDR

11.0

11.0

9.80

 

FG3AAA024

 

23,400

NONE

10.5

10.5

9.50

 

FK4CNF001

 

24,000

TDR&TXV

12.0

10.75

 

FK4CNF002

 

24,000

TDR&TXV

12.0

10.80

 

FK4CNF003

 

24,200

TDR&TXV

12.5

11.05

 

FV4ANF002

 

24,000

TDR&TXV

12.0

10.80

024-A

FV4ANF003

 

24,200

TDR&TXV

12.5

11.05

FX4ANF030

 

23,800

TDR&TXV

11.0

10.00

 

 

COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AA024

 

23,400

TDR

11.5

11.5

10.30

 

CC5A/CD5AA030

 

23,800

TDR

11.5

11.5

10.50

 

CC5A/CD5AW030

 

23,800

TDR

11.5

11.5

10.50

 

CE3AA024

 

23,400

TDR

11.5

11.5

10.35

 

CE3AA030

 

23,800

TDR

11.5

11.5

10.55

 

CK3BA024

 

23,400

TDR

11.5

11.5

10.50

 

CK3BA030

 

23,800

TDR

11.5

11.5

10.60

 

CK5A/CK5BA024

 

23,400

TDR

11.5

11.5

10.50

 

CK5A/CK5BA030

 

23,800

TDR

11.5

11.5

10.60

 

CK5A/CK5BW030

 

23,800

TDR

11.5

11.5

10.60

 

 

COILS + 355MAV042060 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW024

 

23,400

TDR

11.5

11.5

10.25

 

CC5A/CD5AW030

 

23,800

TDR

11.5

11.5

10.50

 

CE3AA024

 

23,400

TDR

11.5

11.5

10.30

 

CE3AA030

 

23,800

TDR

11.5

11.5

10.50

 

CK3BA024

 

23,400

TDR

11.5

11.5

10.40

 

CK3BA030

 

23,800

TDR

11.5

11.5

10.50

 

CK5A/CK5BW024

 

23,400

TDR

11.5

11.5

10.40

 

CK5A/CK5BW030

 

23,800

TDR

11.5

11.5

10.50

 

 

COILS + 355MAV042080 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW024

 

23,400

TDR

11.5

11.5

10.35

 

CC5A/CD5AW030

 

23,800

TDR

11.5

11.5

10.60

See notes on page 14.

— 8—

COMBINATION RATINGS Continued

 

 

 

 

 

 

SEER

 

 

 

 

 

TOT.

FACTORY-

 

Bryant Gas

 

 

UNIT

INDOOR

 

SUPPLIED

 

Furnace or

 

 

 

CAP.

ENHANCE-

Standard

Accessory

Accessory

 

SIZE-SERIES

MODEL

 

BTUH

MENT

Rating

TDR†

Puron TXV

EER

 

CE3AA024

 

23,400

TDR

11.5

11.5

10.40

024-A

CE3AA030

 

23,800

TDR

11.5

11.5

10.60

CK5A/CK5BW024

 

23,400

TDR

11.5

11.5

10.60

 

 

 

CK5A/CK5BW030

 

23,800

TDR

11.5

11.5

10.70

 

CC5A/CD5AA036*

 

29,000

NONE

10.5

11.0

11.0

9.75

 

CC5A/CD5AA030

 

28,000

NONE

10.4

10.8

10.8

9.50

 

CC5A/CD5AW030

 

28,000

NONE

10.4

10.8

10.8

9.50

 

CC5A/CD5AW036

 

29,000

NONE

10.5

11.0

11.0

9.75

 

CE3AA030

 

28,000

NONE

10.5

11.0

11.0

9.60

 

CE3AA036

 

28,200

NONE

10.5

11.0

11.0

9.65

 

CF5AA036

 

28,200

NONE

10.5

11.0

11.0

9.70

 

CK3BA030

 

28,000

NONE

10.5

11.0

11.0

9.55

 

CK3BA036

 

29,000

NONE

10.5

11.0

11.0

9.80

 

CK5A/CK5BA030

 

28,000

NONE

10.5

11.0

11.0

9.55

 

CK5A/CK5BA036

 

29,000

NONE

10.5

11.0

11.0

9.80

 

CK5A/CK5BT036

 

29,000

NONE

10.5

11.0

11.0

9.80

 

CK5A/CK5BW030

 

28,000

NONE

10.5

11.0

11.0

9.55

 

CK5A/CK5BW036

 

29,000

NONE

10.5

11.0

11.0

9.80

 

F(A,B)4AN(F,C)030

 

28,400

TDR

11.0

11.0

9.90

 

F(A,B)4AN(F,C)036

 

28,600

TDR

11.0

11.0

9.55

 

FC4BNF030

 

28,400

TDR&TXV

11.0

9.75

 

FC4BNF036

 

28,600

TDR&TXV

10.8

9.50

 

FF1(B,C,D)NA030

 

28,400

TDR

11.0

11.0

9.60

 

FG3AAA036

 

28,000

NONE

11.0

11.0

9.60

 

FK4CNF001

 

28,600

TDR&TXV

12.0

10.40

 

FK4CNF002

 

28,600

TDR&TXV

12.0

10.45

 

FK4CNF003

 

28,800

TDR&TXV

12.0

10.75

 

FK4CNF005

 

29,000

TDR&TXV

12.0

11.00

 

FV4ANF002

 

28,600

TDR&TXV

12.0

10.45

 

FV4ANF003

 

28,800

TDR&TXV

12.0

10.75

 

FV4ANF005

 

29,000

TDR&TXV

12.0

11.00

 

FX4ANF030

 

28,400

TDR&TXV

11.0

9.75

 

FX4ANF036

 

28,600

TDR&TXV

11.0

9.60

 

 

COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AA030

 

28,000

TDR

11.5

11.5

10.10

 

CC5A/CD5AA036

 

28,600

TDR

11.5

11.5

10.40

 

CC5A/CD5AW030

 

28,000

TDR

11.5

11.5

10.10

 

CE3AA030

 

28,000

TDR

11.5

11.5

10.15

 

CE3AA036

 

28,600

TDR

11.5

11.5

10.25

 

CK3BA030

 

28,000

TDR

11.5

11.5

10.15

 

CK3BA036

 

28,600

TDR

11.5

11.5

10.50

030-A

CK5A/CK5BA030

 

28,000

TDR

11.5

11.5

10.15

CK5A/CK5BA036

 

28,600

TDR

11.5

11.5

10.50

 

CK5A/CK5BT036

 

28,600

TDR

11.5

11.5

10.50

 

CK5A/CK5BW030

 

28,000

TDR

11.5

11.5

10.15

 

 

COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW030

 

28,000

TDR

11.5

11.5

10.25

 

CC5A/CD5AW036

 

28,600

TDR

11.5

11.5

10.55

 

CE3AA030

 

28,000

TDR

11.5

11.5

10.35

 

CE3AA036

 

28,600

TDR

11.5

11.5

10.40

 

CK5A/CK5BW030

 

28,000

TDR

11.5

11.5

10.30

 

CK5A/CK5BW036

 

28,600

TDR

11.5

11.5

10.65

 

 

COILS + 355MAV042060 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AA036

 

28,600

TDR

11.5

11.5

10.30

 

CC5A/CD5AW030

 

28,000

TDR

11.5

11.5

10.00

 

CE3AA030

 

28,000

TDR

11.5

11.5

10.10

 

CE3AA036

 

28,600

TDR

11.5

11.5

10.15

 

CK3BA036

 

28,600

TDR

11.5

11.5

10.30

 

CK5A/CK5BA036

 

28,600

TDR

11.5

11.5

10.30

 

CK5A/CK5BT036

 

28,600

TDR

11.5

11.5

10.30

 

CK5A/CK5BW030

 

28,000

TDR

11.5

11.5

10.00

 

 

COILS + 355MAV042080 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW030

 

28,000

TDR

11.5

11.5

10.15

 

CC5A/CD5AW036

 

28,600

TDR

11.5

11.5

10.45

 

CE3AA030

 

28,000

TDR

11.5

11.5

10.20

 

CE3AA036

 

28,600

TDR

11.5

11.5

10.30

 

CK5A/CK5BW036

 

28,600

TDR

11.5

11.5

10.40

 

 

COILS + 355MAV060100 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW036

 

28,600

TDR

11.5

11.5

10.45

 

CE3AA030

 

28,000

TDR

11.5

11.5

10.25

 

CE3AA036

 

28,600

TDR

11.5

11.5

10.30

 

CK5A/CK5BW030

 

28,000

TDR

11.5

11.5

10.25

 

CK5A/CK5BW036

 

28,600

TDR

11.5

11.5

10.60

 

 

COILS + 355MAV060120 VARIABLE SPEED FURNACE

 

 

 

CC5A/CD5AW036

 

28,600

TDR

11.5

11.5

10.45

 

CE3AA030

 

28,000

TDR

11.5

11.5

10.25

 

CE3AA036

 

28,600

TDR

11.5

11.5

10.30

 

CK5A/CK5BW036

 

28,600

TDR

11.5

11.5

10.55

See notes on page 14.

— 9—

Loading...
+ 19 hidden pages