Bryant 350MAV User Manual

0 (0)

 

 

 

 

 

installation, start-up,

350MAV

 

 

 

 

 

and operating instructions

Series D

 

 

 

 

 

DELUXE 4-WAY MULTIPOISE

 

 

 

 

 

FIXED-CAPACITY DIRECT-VENT

 

 

 

 

 

 

 

 

 

 

 

CONDENSING GAS FURNACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cancels: II 350M-40-7

II 350M-40-8

 

 

 

 

 

 

12-96

®

ama

CANADIAN GAS ASSOCIATION

A PP R O VED

R

A93040

NOTE: Read the entire instruction manual before starting the

installation.

 

This symbol → indicates a change since the last issue.

 

Index

Page

DIMENSIONAL DRAWING........................................................

2

SAFETY CONSIDERATIONS .....................................................

3

Clearances to Combustibles......................................................

3

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

....3-4

INTRODUCTION ..........................................................................

4

APPLICATIONS ......................................................................

4-11

General ......................................................................................

4

Upflow Applications..............................................................

4-7

Downflow Applications.........................................................

7-8

Horizontal Left (Supply-Air Discharge) Applications .........

8-9

Horizontal Right (Supply-Air Discharge) Applications .....

9-11

LOCATION ............................................................................

11-12

General...............................................................................

11-12

Furnace Location Relative to Cooling Equipment ................

12

Hazardous Locations...............................................................

12

INSTALLATION....................................................................

13-17

Leveling Legs (If Desired) .....................................................

13

Installation In Upflow and Downflow Applications ........

13-15

Installation In Horizontal Applications ..................................

15

Filter Arrangement..................................................................

16

Bottom Closure Panel.............................................................

16

Gas Piping...............................................................................

17

ELECTRICAL CONNECTIONS ...........................................

17-21

115-v Wiring......................................................................

17-18

24-v Wiring.............................................................................

18

Wiring Diagram ......................................................................

19

Accessories ........................................................................

20-21

DIRECT VENTING ...............................................................

21-29

Removal of Existing Furnaces from

 

Common Vent Systems.....................................................

21

Combustion-Air and Vent Piping .....................................

21-27

Concentric Vent and Combustion-Air Termination

 

Kit Installation..............................................................

27-29

Multiventing and Vent Termination.......................................

29

CONDENSATE DRAIN ........................................................

29-31

General ....................................................................................

29

Application ..............................................................................

29

Condensate Drain Protection.............................................

29-31

Ð1Ð

As an ENERGY STARSM Partner, Bryant/Day & Night has determined that this product meets the ENERGY STAR guidelines for energy efficiency.

CERTIFICATION OF MANUFACTURING SITE

AIRFLOW

UPFLOW

HORIZONTAL

HORIZONTAL

LEFT

RIGHT

DOWNFLOW

 

AIRFLOW

 

 

AIRFLOW

AIRFLOW

 

 

A93041

Fig. 1ÐMultipoise Orientations

SEQUENCE OF OPERATION..............................................

31-33

Heating Mode ....................................................................

31-32

Cooling Mode .........................................................................

32

Continuous Blower Mode.......................................................

32

Heat Pump Mode ....................................................................

32

Component Test.................................................................

32-33

START-UP PROCEDURES ..................................................

33-41

General ....................................................................................

33

Prime Condensate Trap With Water ......................................

33

Purge Gas Lines......................................................................

34

Adjustments .......................................................................

34-41

Set Gas Input Rate ............................................................

34-40

Set Temperature Rise ........................................................

40-41

Adjust Blower Off Delay (Heat Mode) .................................

41

Set Thermostat Heat Anticipator............................................

41

CHECK SAFETY CONTROLS..................................................

41

Check Primary Limit Control.................................................

41

Check Pressure Switch ...........................................................

41

CHECKLIST...........................................................................

41-42

 

 

26 1516"

 

 

 

 

 

 

26 14"

 

 

 

AIRFLOW

 

 

24 12"

 

 

 

 

 

 

 

 

 

 

 

22 516"

 

 

 

A

 

 

 

 

 

 

 

 

2-IN. COMBUSTION-

 

 

13/16"

D

 

 

CONDENSATE DRAIN

 

 

 

 

AIR CONN

 

OUTLET

 

 

 

TRAP LOCATION

 

 

 

 

 

 

 

 

 

 

 

(DOWNFLOW &

 

 

 

 

 

 

HORIZONTAL LEFT)

 

 

 

 

 

78-IN. DIA

 

 

 

 

 

12-IN. DIA

POWER CONN

 

 

 

 

 

GAS CONN

 

 

 

 

 

 

2-IN. VENT CONN

 

 

 

 

 

 

 

 

 

33 14"

 

 

 

 

 

 

TYP

 

 

 

1

 

 

32 58"

 

 

 

2-IN. DIA THERMOSTAT

 

 

TYP

 

 

 

ENTRY

 

 

 

 

 

78-IN. DIA

 

30 1316"

 

 

 

22 1116"

 

 

 

 

 

 

ACCESSORY

 

29 1116"

 

 

 

 

POWER ENTRY

 

27 58" TYP

 

 

 

 

CONDENSATE

 

 

 

 

 

 

 

 

 

 

 

DRAIN TRAP

 

27 916"

 

 

 

 

LOCATION

 

TYP

 

 

 

 

(ALTERNATE

24

12"

 

 

 

 

UPFLOW)

 

 

14 12"

SIDE INLET

 

 

 

 

17 516"

 

 

 

TYP

 

 

 

 

 

 

 

 

 

 

 

 

9 716"

 

 

 

 

 

 

TYP

 

 

 

Ð2Ð

114"

 

 

 

 

INLET

 

CONDENSATE

 

 

 

1"

23 14" TYP

 

11/16"

E

DRAIN LOCATION

 

SIDE INLET

 

 

 

(UPFLOW)

 

 

 

 

 

 

 

 

 

 

 

26 1516" TYP

 

 

 

 

 

 

28 12"

 

 

 

26 1516"

 

 

 

26 14"

 

 

 

22 516"

 

13/16"

916"

19"

1316"

 

TYP

 

58"

 

 

OUTLET

 

 

 

CONDENSATE DRAIN

2-IN. COMBUSTION-

 

 

TRAP LOCATION

 

 

AIR CONN

 

 

(DOWNFLOW &

516"

HORIZONTAL RIGHT)

12-IN. DIA

 

 

OR ALTERNATE

 

12-IN. DIA GAS CONN

GAS CONN

 

 

 

78-IN. DIA

 

 

 

POWER CONN

 

 

 

12-IN. DIA

 

 

 

THERMOSTAT ENTRY

 

 

30 12"

2-IN. VENT CONN

39 78"

 

 

 

 

 

22 1116"

 

 

18 14"

SIDE INLET

 

 

 

 

 

 

 

1"

 

CONDENSATE

22 14" TYP

716"

11/16"

DRAIN LOCATION

 

(UPFLOW)

24 316"

1116"

 

DIMPLE LOCATORS

 

BOTTOM INLET

 

 

FOR HORIZONTAL

 

 

 

HANGING

 

 

NOTES: Minimum return-air opening at furnace:

1. For 800 CFM--16-In. round or 14 1/2 x 12-In. rectangle.

2. For 1200 CFM--20-In. round or 14 1/2 x 19 1/2-In. rectangle. 3. For 1600 CFM--22-In. round or 14 1/2 x 23 1/4-In. rectangle.

4. For airflow requirements above 1800 CFM, use both side inlets, a combination of 1 side inlet and the bottom, or the bottom only.

A93023

DIMENSIONS (IN.)

UNIT SIZE

A

D

E

024040

17-1/2

15-7/8

16

036040

17-1/2

15-7/8

16

024060

17-1/2

15-7/8

16

036060

17-1/2

15-7/8

16

048060

17-1/2

15-7/8

16

036080

17-1/2

15-7/8

16

048080

17-1/2

15-7/8

16

060080

21

19-3/8

19-1/2

048100

21

19-3/8

19-1/2

060100

21

19-3/8

19-1/2

060120

24-1/2

22-7/8

23

060140

24-1/2

22-7/8

23

Fig. 2ÐDimensional Drawing

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.

Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1- and .2-M95 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.

Recognize safety information. This is the safety-alert symbol . When you see this symbol on unit or in instructions and manuals, be alert to potential for personal injury.

Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

CAUTION: Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.

1.Disconnect all power to the furnace. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY'S ELECTROSTATIC CHARGE TO GROUND.

2.Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person's hand during grounding will be satisfactorily discharged.

3.After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).

4.If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.

5.Use this procedure for installed and uninstalled (ungrounded) furnaces.

This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size Furnaces are only approved for altitudes 0 - 7,000 ft. (0 - 2,135m).

An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications.

This direct-vent, forced-air furnace is for indoor installation in a building constructed on site or in a manufactured (mobile) home when using factory authorized kit, see rating plate.

This furnace may be installed on combustible flooring in alcove or closet at minimum clearance from combustible material.

This appliance requires a special venting system. Refer to the installation instructions for parts list and method of installation. This furnace is for use with schedule-40 PVC, PVC-DWV, or ABS-DWV pipe, and must not be vented in common with other gas-fired appliances. Construction through which vent/air intake pipes may be installed is maximum 24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roofing materials).

MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION

TOP / PLENUM

BOTTOM

SIDES

BACK

 

FRONT

VENT

INSTALLATION

 

 

 

 

 

 

 

 

 

 

1

0

0

0 ††

 

3*

0

UPFLOW

 

 

 

 

1

0

0 ††

 

3*

0

DOWNFLOW

 

 

 

 

1

0 Ø

1§

0 ††

 

3*

0

HORIZONTAL

 

 

 

For Installation on combustible floors only when installed on special base No. KGASB0201ALL,

 

Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.

 

§

Clearance shown is for air inlet and air outlet end.

 

 

 

 

Horizontal position: Line contact is permissible only between lines formed by intersections

of top and two sides of furnace jacket, and building joists, studs, or framing.

Ø120 and 140 size Furnaces require 1 inch bottom clearance to combustible materials.

*Minimum front clearance for service 30 inches (762mm).

†† 140 size Furnaces require 1 inch back clearance to combustible materials.

323855-101 REV. A (LIT)

A96313

Fig. 3ÐClearances to Combustibles

Ð3Ð

6.Before removing a new control from its container, discharge your body's electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.

7.An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.

INTRODUCTION

The model 350MAV, Series D Furnaces are available in sizes 40,000 through 138,000 Btuh input capacities.

The 350MAV Multipoise Condensing Gas-Fired Furnaces are A.G.A./C.G.A. certified for natural and propane gases and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. An A.G.A./C.G.A. listed gas conversion kit is required to convert furnace for use with propane gas. The 350MAV 040 through 120 size units are A.G.A./C.G.A. approved for use in manufactured (mobile) homes when factory accessory conversion kit is used. The 140 size unit is NOT approved for use in manufactured (mobile) homes. These furnaces are suitable for installation in a residence built on site or a manufactured residence completed at final site. The design of this furnace line is NOT A.G.A./C.G.A. certified for installation in recreation vehicles or outdoors.

These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer's Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used.

These furnaces are shipped with the drain and pressure tubes connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT, or HORIZONTAL LEFT (supply-air discharge direction) applications as shown in Fig. 1. See details in Applications section.

These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.

Installer Packet includes:

 

Installation, Start-Up, and Operating Instructions

 

Service and Maintenance Instructions

 

User's Information Manual

 

Warranty Certificate

 

Loose Parts Bag includes:

Quantity

Pressure tube extension

1

Collector box or condensate trap extension tube

1

Inducer housing drain tube

1

1/2-in. CPVC street elbow

2

Drain tube coupling

1

Drain tube coupling grommet

1

Vent and combustion-air pipe support

2

Combustion-air pipe perforated disk assembly

1

Vent Pipe Extension

1*

* ONLY supplied with some furnaces.

Before installing the furnace in the United States, refer to the current edition of the NFGC and the NFPA 90B. For further information, the NFGC and the NFPA 90B are available from National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209; or from Literature Distribution. Before installing the furnace in Canada, refer to the current edition of the NSCNGPIC. Contact Standards Department of Canadian Gas Association, 55 Scarsdale Road, Don Mills, Ontario, Canada M3B 2R3.

Ð4Ð

Installations must comply with regulations of serving gas supplier and local building, heating, plumbing, or other codes in effect in area in which installation is made. In absence of local codes, installation must conform with NFGC.

Canadian installations must be made in accordance with NSCNGPIC and all authorities having jurisdiction.

These instructions cover minimum requirements for a safe installation and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these instructions as a minimum for a safe installation.

CAUTION: Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing. Improper installation or misapplication of furnace can require excessive servicing or cause premature component failure.

WARNING: Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.

For accessory installation details, refer to applicable installation literature.

APPLICATIONS

I.GENERAL

Some assembly and modifications are required for furnaces installed in any of the 4 applications shown in Fig. 1. All drain and pressure tubes are connected as shown in Fig. 5. See appropriate application instructions for these procedures.

II.UPFLOW APPLICATIONS

An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned air is discharged upwards.

A. Condensate Trap Location (Factory-Shipped

Orientation)

The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications. A factory-supplied tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate Trap Tubing (Factory-Shipped Orientation) section for drain tube extension details.

B. Condensate Trap Tubing (Factory-Shipped Orientation)

NOTE: See Fig. 5 or tube routing label on main furnace door to confirm location of these tubes.

1.Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes

These tubes should be factory attached to condensate trap and pressure switch ready for use in UPFLOW applications. These tubes can be identified by their connection location

BLOWER SHELF

FURNACE

CONDENSATE

 

DOOR

 

TRAP

CONDENSATE

 

 

 

TRAP (INSIDE)

 

FURNACE

 

 

 

 

SIDE

4 78

 

FIELD

26 1 4

11 2

 

DRAIN

 

 

ALTERNATE DRAIN

CONN

 

 

TUBE LOCATION

SIDE VIEW

FRONT VIEW

CONDENSATE TRAP

 

 

DRAIN TUBE LOCATION

DOWNFLOW AND ALTERNATE

UPFLOW APPLICATIONS

EXTERNAL UPFLOW APPLICATIONS

 

SLOT FOR SCREW

 

 

HORIZONTAL

 

 

APPLICATION

 

 

(OPTIONAL)

 

 

11 2

 

 

3 4

 

 

 

71 8

 

13 4

 

 

WIRE TIE

7 8

 

21 4

 

GUIDES

 

(WHEN USED)

 

 

FRONT VIEW

SIDE VIEW

Fig. 4ÐCondensate Trap

FURNACE

DOOR FURNACE

SIDE

4

 

 

5 3 4

 

5 3 4

 

4

 

26 1 4

3

4

FIELD

 

 

 

DRAIN

 

 

CONN

 

 

END VIEW

FRONT VIEW

HORIZONTAL

APPLICATIONS

14 OD

COLLECTOR BOX TO TRAP RELIEF PORT

12 OD

INDUCER HOUSING DRAIN CONNECTION

58 OD COLLECTOR BOX

DRAIN CONNECTION

SCREW HOLE FOR UPFLOW OR DOWNFLOW APPLICATIONS (OPTIONAL)

12-IN. PVC OR CPVC

A93026

and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).

2.Condensate Trap Drain Tube

The condensate trap drain connection must be extended for field attachment by doing the following:

a.Determine location of field drain connection. (See Fig. 2 or 5.)

NOTE: If internal filter is used, drain tube should be located to opposite side of casing of return duct attachment to assist in filter removal.

b.Remove and discard casing drain hole plug button from desired side.

c.Install drain tube coupling grommet (factory-supplied in loose parts bag) in selected casing hole.

d.Slide drain tube coupling (factory-supplied in loose parts bag) through grommet ensuring long end of coupling faces blower.

e.Cement 2 factory-supplied 1/2-in. street CPVC elbows to the rigid drain tube connection on the condensate trap. (See Fig. 5.) These elbows must be cemented together and cemented to condensate trap drain connection.

NOTE: Failure to use CPVC elbows may allow drain to kink and prevent draining.

Ð5Ð

f.Connect larger diameter drain tube and clamp (factorysupplied in loose parts bag) to condensate trap and clamp securely.

g.Route tube to coupling and cut to appropriate length.

h.Attach tube to coupling and clamp securely.

C. Condensate Trap Location (Alternate Upflow

Orientation)

An alternate location for the condensate trap is the left-hand side of casing. (See Fig. 2 and 6.)

NOTE: If the alternate left-hand side of casing location is used, the factory-connected drain and relief port tubes must be disconnected and modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment.

To relocate condensate trap to the left-hand side, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 6.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

PLUG

 

CAP

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE

 

& WHITE STRIPED)

 

COLLECTOR BOX

 

TUBE (PINK)

 

COLLECTOR BOX

 

TUBE (GREEN)

 

INDUCER HOUSING

 

(MOLDED) DRAIN

 

TUBE (BEHIND

 

COLLECTOR BOX

 

DRAIN TUBE)

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE)

CONDENSATE

 

 

TRAP

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

 

COUPLING (LEFT

 

DRAIN OPTION)

 

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE

FIELD-INSTALLED

FIELD-INSTALLED

FACTORY-SUPPLIED

FACTORY-SUPPLIED

12-IN. CPVC STREET

DRAIN TUBE

ELBOWS (2) FOR

COUPLING (RIGHT

LEFT DRAIN OPTION

DRAIN OPTION)

A96194

Fig. 5ÐFactory-Shipped Upflow Tube Configuration (Shown With Blower Access Panel Removed)

D. Condensate Trap Tubing (Alternate Upflow

Orientation)

NOTE: See Fig. 6 or tube routing label on main furnace door to confirm location of these tubes.

1. Collector Box Drain Tube

Connect collector box drain tube (blue label) to condensate trap.

NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks from occurring.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Connect relief port tube (green label) to condensate trap.

b. Extend this tube (if required) by splicing to small diameter tube (factory-supplied in loose parts bag).

c.Determine appropriate length, cut, and connect tube.

Ð6Ð

PLUG

CAP

COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

DRAIN TUBE (BLUE)

CONDENSATE

TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

A96195

Fig. 6ÐAlternate Upflow Tube Configuration and Trap Location

E.Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

F. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

G. Upper Collector Box and Inducer Housing (Unused)

Drain Connections

UPPER COLLECTOR BOX DRAIN CONNECTION

Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

UPPER INDUCER HOUSING DRAIN CONNECTION

Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

H. Condensate Trap Freeze Protection

 

c. Connect

LOWER collector box drain connection to

Refer to Condensate Drain Protection section for recommenda-

 

condensate trap.

 

 

 

 

tions and procedures.

 

 

(1.)

Condensate Trap Located on Left Side of Casing

 

 

 

 

III.

DOWNFLOW APPLICATIONS

 

 

 

(a.) Connect LOWER collector box

drain

tube

 

 

 

 

 

A downflow furnace application is where furnace blower is located

 

 

 

(blue and white striped label) to condensate

above combustion and controls section of furnace, and conditioned

 

 

 

trap. Tube does not need to be cut.

 

 

air is discharged downwards.

 

 

 

(b.)

Clamp tube to prevent any condensate leakage.

A.

Condensate Trap Location

 

 

 

 

 

(2.)

Condensate Trap Located on Right Side of Casing

The condensate trap must be removed from the factory-installed

 

 

 

(a.)

Install drain tube coupling (factory-supplied in

blower shelf location and relocated in selected application location

 

 

 

 

 

loose parts bag) into collector box drain tube

as shown in Fig. 2, 7, or 8.

 

 

 

 

 

 

 

 

(blue and white striped label) which was pre-

To

relocate condensate trap from the

blower shelf to desired

 

 

 

 

 

 

viously plugged.

 

 

 

location, perform the following:

 

 

 

 

 

 

 

 

 

 

(b.) Connect larger diameter drain tube (factory-

 

1. Remove 3 tubes connected to condensate trap.

 

 

 

 

 

 

supplied

in loose parts bag)

to

drain

tube

 

2. Remove trap from blower shelf

by gently pushing tabs

 

 

 

 

 

 

 

coupling,

extending collector

box

drain

tube

 

inward and rotating trap.

 

 

 

 

 

 

 

 

 

for connection to condensate trap.

 

 

 

3. Remove casing hole filler cap from casing hole. (See Fig. 2,

 

 

 

 

 

 

(c.)

Route extended collector box

drain tube di-

 

7, or 8.)

 

 

 

 

 

 

 

rectly from collector box drain to condensate

 

4. Install casing hole filler cap into blower shelf hole where

 

 

 

 

 

 

 

trap as shown in Fig. 8.

 

 

 

 

trap was removed.

 

 

 

 

 

 

 

 

 

 

 

(d.)

Determine appropriate length and cut.

 

 

5. Install condensate trap into desired casing hole by inserting

 

 

 

 

 

 

(e.)

Connect to condensate trap.

 

 

 

 

tube connection stubs through casing hole and rotating until

 

 

 

 

 

 

tabs snap into locking position.

 

 

 

(f.)

Clamp tube to prevent any condensate leakage.

 

 

 

 

 

B.Condensate Trap Tubing

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to condensate trap.

2.Inducer Housing Drain Tube

a.Remove factory-installed cap and clamp from LOWER inducer housing drain connection.

b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap.

c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.

COLLECTOR BOX

DRAIN TUBE (BLUE)

CAP

PLUG

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

INDUCER HOUSING

DRAIN TUBE (VIOLET)

A96196

Fig. 7ÐDownflow Tube Configuration (Left-Hand Trap Installation)

Ð7Ð

PLUG

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

INDUCER HOUSING

DRAIN TUBE

(VIOLET)

CONDENSATE

TRAP

COLLECTOR BOX

EXTENSION

DRAIN TUBE

DRAIN TUBE

COUPLING

A96197

Fig. 8ÐDownflow Tube Configuration (Right-Hand Trap Installation)

d.Use inducer housing drain tube (violet label and factorysupplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.

e.Connect inducer housing drain connection to condensate trap.

(1.)

Condensate Trap Located on Left Side of Casing

 

(a.)

Determine appropriate length and cut.

 

(b.)

Connect tube to condensate trap.

 

(c.)

Clamp tube to prevent any condensate leakage.

(2.)

Condensate Trap Located on Right Side of Casing

(a.)

Route inducer housing drain tube (violet label)

 

 

directly from inducer housing to condensate

 

 

trap as shown in Fig. 8.

 

(b.)

Determine appropriate length and cut.

 

(c.)

Connect tube to condensate trap.

 

(d.)

Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

Refer to Pressure Switch Tubing section for connection procedure.

C.Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D.Pressure Switch Tubing

One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

Relocate tubes as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory-supplied in loose parts bag).

3.Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.

4. Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to remaining small diameter tube (factory-supplied in loose parts bag).

5.Route this extended tube (pink label) to condensate trap relief port connection.

6.Determine appropriate length, cut, and connect tube.

7.Clamp tube to relief port connection.

E. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations and procedures.

IV. HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.

PLUG

 

 

 

CAP

COLLECTOR BOX EXTENSION TUBE

 

 

AUXILIARY "J" BOX

 

COLLECTOR BOX

RELOCATED HERE

 

DRAIN TUBE

 

 

(BLUE AND WHITE STRIPED)

CONDENSATE

COLLECTOR BOX

TRAP

TUBE (GREEN)

 

COLLECTOR

INDUCER HOUSING

DRAIN TUBE (VIOLET)

BOX EXTENSION

COLLECTOR BOX

DRAIN TUBE

 

DRAIN TUBE (BLUE)

COLLECTOR BOX

EXTENSION TUBE

DRAIN TUBE COUPLING

COLLECTOR BOX TUBE (PINK)

A96198

Fig. 9ÐHorizontal Left Tube Configuration

Ð8Ð

CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.

NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 9.) See Electrical Connection section for J-Box relocation.

A.Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 9.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 9.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

B.Condensate Trap Tubing

NOTE: See Fig. 9 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.

b.Connect large diameter drain tube and clamp (factorysupplied in loose parts bag) to drain tube coupling, extending collector box drain tube.

c.Route extended tube (blue label) to condensate trap and cut to appropriate length.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a. Extend collector box tube (green label) which was previously connected to the condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).

b.Route extended collector box pressure tube to relief port connection on the condensate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

Ð9Ð

C. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications.

NOTE: See Fig. 9 or tube routing label on main furnace door to check for proper connections.

Modify tube as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

2.Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.

3.Route extended tube:

a.Behind inducer housing.

b.Between blower shelf and inducer housing.

c.Behind inducer motor bracket.

d.Between inducer motor and pressure switch.

4.Determine appropriate length, cut, and reconnect tube to pressure switch connection labeled COLLECTOR BOX.

E.Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations and procedures.

F.Construct a Working Platform

Construct working platform where all required furnace clearances are met. (See Fig. 3 and 10.)

CAUTION: The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.

NOTE: Combustion-air and vent pipes are restricted to a minimum length of 5 ft. (See Table 6.)

NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 10 or 29.)

V. HORIZONTAL RIGHT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.

CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in attic application or over a finished ceiling.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes.

A.Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 11.

To relocate condensate trap from the blower shelf to desired location, perform the following:

COMBUSTION – AIR

INTAKE

VENT

5 34²

MANUAL

SHUTOFF

GAS VALVE

SEDIMENT

TRAP

CONDENSATE

TRAP

A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM

30² MIN EXITING THE VENT PIPE. WORK AREA

ACCESS OPENING

FOR TRAP

DRAIN

NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE

FURNACE AND CONDENSATE TRAP WHEN A CONDENSING

FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.

A93031

Fig. 10ÐAttic Location and Working Platform

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 11.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

B.Condensate Trap Tubing

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was previously connected to condensate trap.

c.Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

a.Remove factory-installed cap and clamp from LOWER inducer housing drain connection.

b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap.

Ð10Ð

c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.

d.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.

e.Determine appropriate length, cut, and connect tube to condensate trap.

f.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

Refer to Pressure Switch Tubing section for connection procedure.

C. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D. Pressure Switch Tubing

One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

Relocate tubes as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

CAP

COLLECTOR BOX DRAIN TUBE (BLUE)

COLLECTOR BOX TUBE (GREEN)

 

PLUG

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX TUBE (PINK)

CONDENSATE

TRAP

COLLECTOR BOX DRAIN TUBE

(BLUE AND WHITE STRIPED)

 

INDUCER HOUSING

 

 

DRAIN TUBE (VIOLET)

 

 

COLLECTOR BOX

 

 

EXTENSION TUBE

 

 

 

A96199

Fig. 11ÐHorizontal Right Tube Configuration

2. Extend collector box pressure tube (green label) which was

LOCATION

 

previously connected to condensate trap relief port connec-

 

 

tion by splicing to small diameter tube (factory-supplied in

I. GENERAL

 

loose parts bag).

 

When a furnace is installed so that supply ducts carry air to areas

 

3. Route extended collector box pressure tube behind inducer

 

outside the space containing the furnace, return air must also be

 

motor bracket then between inducer motor and pressure

 

handled by ducts sealed to furnace casing. The ducts terminate

 

switch.

 

outside the space containing the furnace to ensure there will not be

 

4. Connect collector box pressure tube (green label) to pres-

 

a negative pressure condition within equipment room or space.

 

sure switch connection labeled COLLECTOR BOX.

 

Furnace may be located in a confined space without special

 

 

 

5. Use remaining smaller diameter tube (factory-supplied in

provisions for dilution or ventilation air. This furnace must be

 

loose parts bag) to extend collector box pressure tube (pink

installed so electrical components are protected from water.

 

label) which was previously connected to pressure switch.

 

6.Route this extended tube (pink label) to condensate trap relief port connection.

7. Determine appropriate length, cut, and connect tube.

8. Clamp tube to relief port connection.

E. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda-

LEVEL

 

(0²)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tions and procedures.

 

 

 

 

FRONT

 

 

 

 

FRONT

 

 

 

 

 

 

 

TO

LEVEL (0²)

 

 

F. Construct a Working Platform

 

 

 

 

12² MAX

 

TO

 

 

 

 

 

 

 

 

 

 

 

 

 

Construct working platform where all required furnace clearances

 

 

 

 

12² MAX

 

 

 

are met. (See Fig. 3 and 10.)

 

 

 

UPFLOW OR DOWNFLOW

 

HORIZONTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: The condensate trap MUST be installed

 

 

 

 

 

 

 

 

 

 

A93025

 

 

below furnace. See Fig.

4 for

dimensions. The drain

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: For proper furnace operation, install furnace so that it is

 

 

connection to condensate

trap

must also be properly

 

 

 

 

level or pitched forward within 1/2 in. to ensure proper condensate

 

 

sloped to an open drain.

 

 

 

 

 

 

 

 

drainage from secondary heat exchangers.

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Combustion-air and vent pipes are restricted to a mini-

 

 

 

 

 

 

 

 

 

 

 

 

 

mum length of 5 ft. (See Table 6.)

 

 

Locate furnace as close to

center of air

 

distribution system as

NOTE: A 12-in. minimum offset pipe section is recommended

 

possible.

 

 

 

 

 

 

 

with short (5 to 8 ft) vent systems. This recommendation is to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reduce excessive condensate droplets from exiting the vent pipe.

Locate furnace so combustion-air pipe maximum lengths are not

(See Fig. 10 or 29.)

 

 

 

exceeded. Refer to Table 6.

 

 

 

 

 

 

 

 

 

 

 

 

Ð11Ð

 

 

 

 

 

 

 

 

 

Bryant 350MAV User Manual

FRONT

°F °F

RETURN

AIR

MAX 85°F MIN 55°F

A93042

NOTE: These furnaces are designed for a minimum continuous return-air temperature of 60°F or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls.

FRONT

B A C K

BACK

FRONT

A93043

WARNING: Do not install furnace on its back. Safety control operation will be adversely affected. Never connect return-air ducts to back of furnace. Failure to follow this warning could result in fire, personal injury, or death.

CAUTION: If these furnaces are used during construction when adhesives, sealers, and/or new carpets are being installed, make sure all combustion and circulating air requirements are followed. If operation of furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine, when burned with combustion air, form acids which will cause corrosion of heat exchangers. Some of these compounds are found in paneling, dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in construction process.

Excessive exposure to contaminated combustion air will result in safety and performance related problems.

32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED

A93058

CAUTION: If these furnaces are installed in an unconditioned space where ambient temperatures may be 32°F or lower, freeze protection measures must be taken.

Provide ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown on unit's clearance to combustibles label. (See Fig. 3.) Locate furnace where available electric power and gas supplies meet specifications on furnace rating plate.

II. FURNACE LOCATION RELATIVE TO COOLING EQUIPMENT

The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air must prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless damper is in full-heat or full-cool position.

III.HAZARDOUS LOCATIONS

18-IN. MINIMUM

TO BURNERS

A93044

WARNING: When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire Protection Association, Inc.

Ð12Ð

INSTALLATION

I.LEVELING LEGS (IF DESIRED)

When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 12.) Install field-supplied, corrosion-resistant 5/16-in. machine bolts and nuts.

516²

516²

1 34²

1 34²

516²

516²

1 34²

1 34²

A89014

Fig. 12ÐLeveling Legs

NOTE: The maximum length of bolt should not exceed 1-1/2 in.

1.Position furnace on its back. Locate and drill a 5/16-in. diameter hole in each bottom corner of furnace. (See Fig. 12.) Holes in bottom closure panel may be used as guide locations.

2.For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)

3.Install another nut on other side of furnace base. (Install flat washer if desired.)

4.Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.

NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.

II. INSTALLATION IN UPFLOW OR DOWNFLOW APPLICATIONS

NOTE: For downflow applications, this furnace is approved for use on combustible flooring when special base (available from manufacturer) Part No. KGASB0201ALL is used. Special base in not required when this furnace is installed on manufacturer's Coil Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is used.

1.Determine application being installed from Table 1.

2.Construct hole in floor per dimensions specified in Table 1 and Fig. 13.

3.Construct plenum to dimensions specified in Table 1 and Fig. 13.

4.If downflow subbase (KGASB) is used, install as shown in Fig. 14.

If Coil Assembly Part No. CD5 or CK5 or Coil Box Part No. KCAKC is used, install as shown in Fig. 15.

NOTE: Remove furnace perforated, discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated, discharge duct flange, use wide duct pliers or duct flange tool to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 16.)

WARNING: Do not bend duct flanges inward as shown in Fig. 16. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210° as shown in Fig. 16.

NOTE: For 140 size unit when installed in downflow orientation, cut the white jumper wire off between terminals PL1-6 and PL1-9. Refer to Fig. 24 for location of jumper. Cut jumper close to connector and remove wire to avoid a short circuit.

Ð13Ð

 

A

 

PLENUM

 

OPENING

B

D

 

FLOOR

 

OPENING

 

C

 

A96283

 

Fig. 13ÐFloor and Plenum Opening Dimensions

FURNACE

FURNACE

(OR COIL CASING

CD5 OR CK5

WHEN USED)

 

COIL ASSEMBLY

 

OR KCAKC

 

COIL BOX

 

COMBUSTIBLE

COMBUSTIBLE

FLOORING

FLOORING

 

DOWNFLOW

SHEET METAL

SUBBASE

PLENUM

SHEET METAL

FLOOR

PLENUM

FLOOR

OPENING

 

OPENING

 

 

A96284

A96285

Fig. 14ÐFurnace, Plenum, and Subbase

Installed on a Combustible Floor

TABLE 1ÐOPENING DIMENSIONS (IN.)

Fig. 15ÐFurnace, Plenum, and Coil Assembly or Coil Box Installed on a Combustible Floor

FURNACE

 

PLENUM OPENING

FLOOR OPENING

CASING

APPLICATION

 

 

 

 

A

B

C

D

WIDTH

 

 

Upflow Applications

16

24-1/8

16-5/8

24-3/4

 

 

 

 

 

 

 

Downflow Applications on Non-Combustible Flooring

15-7/8

19

16-1/2

19-5/8

 

 

 

 

 

 

17-1/2

Downflow Applications on Combustible Flooring Using KGASB Subbase

15-1/8

19

16-3/4

20-3/8

Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box

 

 

 

 

 

 

Downflow Applications on Combustible Flooring NOT Using KGASB Subbase

15-1/2

19

16-1/2

20

 

Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box

 

 

 

 

 

 

Upflow Applications

19-1/2

24-1/8

20-1/8

24-3/4

 

Downflow Applications on Non-Combustible Flooring

19-3/8

19

20

19-5/8

21

Downflow Applications on Combustible Flooring Using KGASB Subbase

18-5/8

19

20-1/4

20-3/8

Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box

 

 

 

 

 

 

Downflow Applications on Combustible Flooring NOT Using KGASB Subbase

19

19

20

20

 

Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box

 

 

 

 

 

 

Upflow Applications

23

24-1/8

23-5/8

24-3/4

 

Downflow Applications on Non-Combustible Flooring

22-7/8

19

23-1/2

19-5/8

24-1/2

Downflow Applications on Combustible Flooring Using KGASB Subbase

22-1/8

19

23-3/4

20-3/8

Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box

 

 

 

 

 

 

Downflow Applications on Combustible Flooring NOT Using KGASB Subbase

22-1/2

19

23-1/2

20

 

Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box

 

 

 

 

 

Ð14Ð

Loading...
+ 30 hidden pages