Operation Manual
Smart-UPS X
Uninterruptible Power Supply
Rack-Mount 2U
SMX750 VA
SMX1000 VA
SMX 1500 VA
120 Vac
230 Vac
The APC™ by Schneider Electric Smart-UPS™ is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are fully discharged.
This user manual is available on the enclosed CD and on the APC by Schneider Electric Web site, www.apc.com.
Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.
The following safety messages may appear throughout this manual to warn of potential hazards.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.
Read the Safety Guide supplied with this unit before installing the UPS.
•Adhere to all local and national electrical codes.
•This UPS is intended for indoor use only.
•Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
•Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
•The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.
•Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U |
1 |
1 Battery
2 Battery connector
3 Display interface
4 Bezel
su0443a
1 |
SmartSlot |
120 Vac |
||
2 |
External battery pack connector |
|
|
|
3 |
Outlets |
|
|
|
4 |
EPO connector |
|
|
|
5 |
USB port |
|
|
|
|
|
|
||
6 |
Serial port |
|
|
|
7 |
Chassis ground screw |
|
|
|
|
|
|
||
8 |
UPS input |
|
|
|
|
|
|
||
9 |
Circuit breaker |
|
|
|
230 Vac
su0340a
su0341a |
2 |
Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U |
Environmental Specifications
For additional specifications, refer to the APC by Schneider Electric Web site at www.apc.com.
Temperature |
Operating |
0° to 40° C (32° to 104° F) |
|
Storage |
-15° to 45° C (5° to 113° F) |
|
charge UPS battery every six months |
|
|
|
|
|
|
|
Maximum |
Operating |
3,000 m (10,000 ft) |
Elevation |
Storage |
15,000 m (50,000 ft) |
|
||
|
|
|
Humidity |
0% to 95% relative humidity, non-condensing |
UPS
For UPS installation information, refer to the Smart-UPS X Installation Guide that is included with the UPS. The guide is also available on the enclosed CD and the APC by Schneider Electric Web site at www.apc.com.
Network Management Card
For installation information, refer to the user manual provided with the Network Management Card (NMC). The user manual is also available on the APC by Schneider Electric Web site at www.apc.com.
External Battery Pack
For installation information, refer to the SMX48RMBP2U external battery pack Installation Guide that is included with the external battery pack (XLBP). The guide is also available on the enclosed CD and the APC by Schneider Electric Web site at www.apc.com.
Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U |
3 |
CAUTION
RISK OF EQUIPMENT DAMAGE
•Adhere to all local and national electrical codes.
•Wiring should be performed by qualified electrician.
•Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in equipment damage
Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.
1.Connect equipment to the outlets on the rear panel of the UPS.
2.Connect the UPS to the building utility power.
Always connect the UPS to a two pole, three wire, grounded source.
3.To use the UPS as a master ON/OFF switch, turn on all the equipment that is connected to the UPS.
4.Press the ON/OFF button on the front panel of the UPS to turn on the UPS and all connected equipment.
5.See “Controllable Outlet Groups” on page 8 for information on how to use the Controllable Outlet Groups.
su0439a
Basic Connectors
Serial port: Connect to a computer to use power management software.
USB port: Connect to a computer to use power management software.
Note: Serial and USB communication can not be used simultaneously.
External Battery Pack connector: Connect external battery packs to provide extended runtime during power outages. The UPS can support up to five external battery packs.
Ground Screw: The UPS features a ground screw for connecting the ground lead on surge suppression devices such as a telephone and network line protectors. When connecting a ground cable, disconnect the UPS from utility power.
4 |
Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U |
Overview
1 |
Online LED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
2 |
UPS Output On/Off button |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
3 |
On Battery LED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
4 |
Site Wiring Fault LED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
5 |
Replace Battery LED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
6 |
Display screen |
APC by Schneider |
|
|
||||||||||||||||||||
|
|
|||||||||||||||||||||||
|
|
|
|
|
|
|||||||||||||||||||
7 |
UP/DOWN arrow buttons |
|
|
|
|
Electric |
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
||||||||||||||||||
8 |
ENTER button |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
9 |
ESCAPE button |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
su0343a
Using the display interface
Use the UP/DOWN arrow buttons to scroll through the main menu options. Press ENTER to view the submenus under each main menu option. Press ESCAPE to exit a submenu and return to a main menu.
Standard menus
The Standard menus are the most commonly used menus for the UPS.
Menu |
General Functions |
|
|
|
|
|
View basic information about the UPS: |
|
|
• Operating mode |
|
|
• Switched Outlet status, On or Off |
|
|
• Efficiency of the UPS |
|
Status |
• Information about the load |
|
• Battery capacity |
||
|
• Estimated runtime |
|
|
• Input and output voltage and frequency |
|
|
• Information about the last transfer to battery power |
|
|
• Self-test results |
|
|
• SmartSlot Card information |
|
|
|
|
|
Configure the settings for the UPS: |
|
|
• Language |
|
Configuration |
• Local power quality: Good, Fair, Poor |
|
• Choose Standard or Advanced menus |
||
|
||
|
• UPS Test settings |
|
|
• Reset to Factory Defaults |
|
|
|
|
Test & Diags |
Use the Test & Diags menu to have the UPS perform a self-test. |
|
|
|
|
|
Display information about this unit: |
|
|
• Unit model number |
|
|
• Serial number |
|
About |
• Battery information |
|
•Model number |
||
|
||
|
•Installation date |
|
|
•Suggested battery replacement date |
|
|
•UPS firmware version |
Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U |