ABB standard drives
ACS550, 1 to 550 hp (0.75 to 355 kW)
ABB standard drives are simple to
buy, install, configure and use, saving
considerable time. They are widely
available through ABB channel partners,
hence the use of the term standard. The
drives have common user and process
interfaces with fieldbuses, common
software tools for sizing, commissioning,
maintenance and common spare parts.
ABB standard drives can be used in a wide
range of industries. These drives are ideal
in those situations where there is a need
for simplicity to install, commission and use
and where customizing or special product engineering is not required. The drives
include several features as standard, such
as swinging choke, EMC filter and control
panel.
Energy efficiency achieved with ABB standard drives can be easily monitored using
the built-in counters, which display energy
savings in kilowatt hours, carbon dioxide
emissions or local currencies.
Highlights
− Advanced control panel permitting
intuitive operation
− Patented swinging choke for superior
harmonic reduction (R1-R4) and AC line
reactor (R5-R8)
− Sensorless vector control
− Integral EMC filter as standard
− Built-in Modbus RTU and numerous
internally mountable fieldbus adapters
− FlashDrop
− Coated boards for harsh environments
− UL, cUL, C-Tick and Gost-R approved
− Built-in brake chopper (10Hp, 230V /
15Hp, 480V and 600 V)
− Many assistants including Start-up, Drive
Optimizer,
− Real-time Clock, Diagnostics, Maint
nance, Serial and PID
− Seismic Certification to ICC AC-156
Criteria
Voltage and power range
− 3-phase, 208 to 240 V, 0.75 - 100Hp
− 3-phase, 380 to 480 V, 1 - 550Hp
− 3-phase, 500 to 600V, 1.5 - 150Hp
Applications
− Pumps and Fans
− Conveyors
Options
− Fieldbus adapters
− Panel mounting kits
− DriveWindow Light 2 software
− Brake units and resistors
− Encoder feedback module
− Relay output extension module
− Flange mountin kits
− FlashDrop tool
ACS550 standard drives
ACS550-U1, wall mount
− NEMA 1 & 12 enclosures
− 1.0 to 100 HP @ 240Vac
− 1.5 to 200 HP @ 480Vac
− 2.0 to 150 HP @ 600Vac
ACS550-PC/PD, wall-mount packaged
− NEMA 1, 12 & 3R enclosures
− 0.75 to 100 HP @ 240Vac
− 1 to 200 HP @ 480Vac
− 1.5 to 150 HP @ 600Vac
− Circuit Breaker (PC)
− Fused disconnect (PD)
ACS550-PC, free standing packaged
− NEMA 1 & 12 enclosures (NEMA 12 std.
450-550 HP)
− 250 to 550 HP @ 480Vac
− Circuit Breaker (PC)
ACS550-CC, wall mount & free standing
− Three contactor Bypass
− Wall mount
− NEMA 1, 12 & 3R
− 1 to 100 HP @ 240Vac
− 1 to 400 HP @ 480Vac
− 1.5 to 150 HP @ 600Vac
− Free standing
− NEMA 1 & 12
− 250 - 400 HP @ 480Vac
Input power connection
Voltage and power range 3-phase, 208 to 240 V, +10/-15%, 0.75 - 100Hp
Frequency
Power factor
Motor connection
Frequency 0 to 500 Hz
Acceleration time 0.1 to 1800 s
Deceleration time 0.1 to 1800 s
Programmable control connections
Two analog inputs
Voltage signal
Current signal
Potentiometer reference value
Maximum delay
Resolution
Accuracy
Two analog outputs
Accuracy
Auxiliary voltage 24 V DC ±10%, max. 250 mA
Six digital inputs
Input impedance
Maximum delay
Three relay outputs
Maximum switching voltage
Maximum switching current
Maximum continuous current
Serial communication
RS 485 Built-in Modbus RTU protocol
Product compliance
240V products: UL, cUL, CSA, CE, C-TICK, and GOST-R approvals
480V products: UL, cUL, CSA, CE, C-TICK, and GOST-R approvals
600V products: UL, cUL, CSA, C-TICK, and GOST-R approvals
Low Voltage Directive 73/23/EEC with supplements
Machin ery Directive 98/37/EC
EMC Di rective 89/336/EEC with supplements
Qualit y assur ance system ISO 9001 and Environmental system ISO 14001
Seismi c Certi fication to ICC AC-156
Environmental Limits
Protection class
Ambient temperature 15 to 40oC (5 to 104oF)
Relative humidity
3-phase, 380 to 480 V, +10/-15%, 1 - 550Hp
3-phase, 500 to 600V, +10/-15%, 1.5 - 150Hp
48 to 63 Hz
0.98
0 (2) to 10 V, Rin > 312 kΩ single-ended
0 (4) to 20 mA, Rin = 100 Ω single-ended
10 V ±2% max. 10 mA, R < 10 kΩ
12...32 ms
0.1%
±1%
0 (4) to 20 mA, load < 500 Ω
±3%
12 V... 24 V DC with internal or external
supply, PNP and NPN
2.4 kΩ
5 ms ± 1ms
250 V AC/30 V DC
6 A/30 V DC; 1500 V A/230 V AC
2 A rm
UL Type 1 or 12 (NEMA 1 or NEMA 12)
40 to 50oC (104 to 122oF)
No frost allowed
fswitch 4 kHz, PN and I2 derated to 90%
lower than 95% (without condensation)
ACS550 -PHPB01 U-EN REVA Efefctive: 1/15/2010 Subject to change w ithout notice.
For more information see c atalog ABB st andard dr ives
ACS5 50-PHTC01U-EN
For more information please contact:
www.abb.us/drives
Copyright 2010 ABB. All rights reserved.
Specifications subject to change without notice.