ELECTRIC HEAT PRODUCTS
MODEL 24A34 ELECTRIC HEAT SEQUENCERS
Direct Replacement for Most Fan / Heat Sequencing Functions.
Terminal Markings are Equivalent to Competitive Types
FEATURES
|
• Replaces Honeywell, MARS, TOD, |
• Any contacts (except M1 & M2) can be |
||||||
|
GEMLINE, Klixon (Texas Instruments). |
used as auxiliary contacts. |
|
|||||
|
• 24V input control. |
|
• Double quick-connect terminals for |
|||||
|
• Multi-poise mounting. |
|
combination loads. |
|
||||
|
SPECIFICATIONS |
|
|
|
|
|
|
|
|
Ambient Temperature Rating . . . . . |
-50 to +165°F |
|
|
|
|||
|
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . |
U.L. component recognized |
|
|||||
|
ELECTRICAL RATINGS – SINGLE LOAD CONTACT RATINGS (ALL MODELS) |
|||||||
24A34-3 |
|
|
|
|
|
|
|
|
VAC |
Resistive (Non-Inductive) |
Motor Ratings (Inductive) |
|
Pilot Duty |
||||
|
Watts |
Amps |
Full Load |
|
Locked Rotor |
|
||
|
120 |
3000 |
25.0 |
14.0A |
|
72.0A |
|
125 VA |
|
240 |
6000 |
25.0 |
7.0A |
|
42.0A |
|
125 VA |
|
480 |
6000 |
12.5 |
– |
|
– |
|
480 VA |
COMBINED LOAD RATING TABLE (ALL MODELS)
30A @ 240 VAC – TOTAL,
23A Non-Inductive + 7 FLA / 42 LRA Inductive,
ON Time: Elapsed time to make contacts after heater is energized (min. to max.)
OFF Time: Elapsed time to break contacts after heater is de-energized (min. to max.)
TABLE NOTES:
M1-M2 and M3-M4 are always first switches to turn ON and last to turn OFF. All other switches are random ON and random OFF
24A34-14 Switch contacts designated F1 - F2 instead of M1 - M2
24A34-28 is 2 pole double throw
These contacts switch simultaneously
NOTE: Underwriters Laboratories requires a fan interlock circuit to insure the blower remains operating whenever more than one sequencer is used. The fan interlock should be the M1 / M2 contacts of the second or third sequencer.
All M1 / M2 contacts are wired to the blower motor so that any sequencer that is energized will keep the blower ON.
|
Model |
|
|
|
Timings – ON |
|
|
|
Timings – OFF |
|
|
||||
|
Number |
Timings |
Switches |
M1-M2 |
M3-M4 |
M5-M6 |
M7-M8 |
M9-M10 |
M1-M2 |
M3-M4 |
M5-M6 |
M7-M8 |
M9-M10 |
||
|
24A34-1 |
1 |
1 |
1-20 |
– |
– |
|
– |
– |
40-110 |
– |
– |
|
– |
– |
|
24A34-2 |
1 |
1 |
– |
– |
30-90 |
|
– |
– |
– |
– |
1-30 |
|
– |
– |
|
24A34-3 |
1 |
2 |
1-20 ♦ 1-20 |
– |
|
– |
– |
40-110 ♦40-110 |
– |
|
– |
– |
||
|
24A34-4 |
1 |
2 |
– |
– |
30-90 ♦30-90 |
– |
– |
– |
1-30 ♦ 1-30 |
– |
||||
|
24A34-5 |
2 |
3 |
1-110 ♦1-110 |
1-110 |
|
– |
– |
1-110 ♦1-110 |
1-110 |
|
– |
– |
||
|
24A34-6 |
2 |
4 |
1-110 ♦1-110 |
1-110 ♦1-110 |
– |
1-110 ♦1-110 |
1-110♦1-110 |
– |
||||||
|
24A34-14 |
4 |
5 |
1-160♦1-160 |
1-160 1-160 |
1-160 |
1-160 ♦1-160 |
1-160 1-160 |
1-160 |
||||||
24A34-21 |
1 |
1 |
1-20 |
– |
– |
– |
– |
1-50 |
– |
– |
– |
– |
|||
|
24A34-22 |
1 |
1 |
15-45 |
– |
– |
– |
– |
1-30 |
– |
– |
– |
– |
||
|
24A34-23 |
1 |
1 |
25-55 |
– |
– |
– |
– |
15-45 |
– |
– |
– |
– |
||
|
24A34-24 |
1 |
1 |
30-75 |
– |
– |
– |
– |
1-40 |
– |
– |
– |
– |
||
|
24A34-25 |
1 |
1 |
40-90 |
– |
– |
– |
– |
1-30 |
– |
– |
– |
– |
||
|
24A34-26 |
2 |
2 |
1-20 |
30-90 |
– |
– |
– |
40-90 |
1-30 |
– |
– |
– |
||
|
24A34-27 |
2 |
2 |
1-160 1-160 |
– |
– |
– |
1-160 1-160 |
– |
– |
– |
||||
|
24A34-28 |
2 |
2 |
1-160 1-160 |
– |
– |
– |
1-160 1-160 |
– |
– |
– |
||||
|
24A34-29 |
1 |
1 |
15-35 |
– |
– |
– |
– |
25-55 |
– |
– |
– |
– |
||
|
24A34-36 |
2 |
2 |
1-20 |
30-45 |
– |
– |
– |
45-110 1-30 |
– |
– |
– |
|||
|
24A34-37 |
1 |
1 |
1-110 |
– |
– |
– |
– |
1-110 |
– |
– |
– |
– |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
24A34-15 HEAT PUMP CONTROL
FEATURES
•Used in heat pump air handler applications.
•Provides a delay off to the blower motor in cooling mode.
•Single pole double throw.
|
Model |
|
|
|
|
|
|
|
|
|
|
Timings |
|
|
|
Number |
|
|
Timings |
|
|
Switches |
|
|
ON 1-3 |
|
OFF 1-3 |
||
|
24A34-15 |
|
1 |
|
|
1 |
|
|
1-60 |
|
75-95 |
|||
|
ELECTRICAL RATINGS – NORMALLY OPEN CONTACTS 1-3 |
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|||||
|
VAC |
|
Resistive (Non-Inductive) |
Motor Ratings (Inductive) |
Pilot Duty |
|||||||||
|
|
Watts |
|
Amps |
Full Load |
|
|
Locked Rotor |
||||||
|
120 |
|
|
3000 |
|
|
25.0 |
|
14.0A |
|
|
72.0A |
125 VA |
|
|
240 |
|
|
6000 |
|
|
25.0 |
|
7.0A |
|
|
42.0A |
125 VA |
|
|
ELECTRICAL RATINGS – NORMALLY CLOSED CONTACTS 1-2 |
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
VAC |
|
Resistive (Non-Inductive) |
Pilot Duty |
|
|
|
|
|
|||||
|
|
Watts |
|
Amps |
|
|
|
|
|
|||||
|
120 |
|
|
1200 |
|
|
10.0 |
125 VA |
|
|
|
|
|
|
|
240 |
|
|
1200 |
|
|
5.0 |
125 VA |
|
|
|
|
|
|
Indicates Canadian Model Number: call 1-800-305-6953 to order |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
www.white-rodgers.com |
|
|
|
|
|
|
|