96-TD |
|
LIQUID LINE |
SERIES |
|
FILTER-DRIERS |
|
||
|
|
|
|
|
|
|
|
|
96-TD
96-TD Series
Dimensional Drawing
All ratings in accordance with ARI standard 710-86:
86°F Liquid Refrigerant Temperature,
5°F Saturated Temperature, 4.0 lbs./min./ton for R-134a,
2.9 lbs./min./ton for R-22,
4.4 lbs./min./ton for R-404A/R-507
96-TD LIQUID LINE FILTER-DRIERS
Filter-Driers Designed to Offer Complete Protection to Your Refrigerant System. The 96-TD Series Removes Moisture, Acid and Foreign Materials to Protect the Compressor, Solenoid Valves, Expansion Valves, Capillary Tubes and Other Close Tolerance Parts of Your Refrigeration System
FEATURES
•Solid block desiccant core: a composite of molecular sieve and activated alumina.
•Provides high moisture, organic and inorganic acid removal.
•For use with HCFCs, CFCs and the lubricants that go with them.
•Nickel plated SAE flare and solid copper ODF fittings.
•Corrosion resistant paint.
SPECIFICATIONS
Maximum Working Pressure . . . . . . . 500 psig Minimum Burst Pressure . . . . . . . . . 2500 psig
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL / CUL file number SA11002
INSTALLATION NOTE: The 96-TD liquid line filter-drier may be installed in any position. Best results are achieved when located as close as possible to the inlet of the expansion device. If using a liquid line solenoid or moisture indicator, locate the filter-drier upstream. This will provide protection to the solenoid valve and allow the moisture indicator to measure the drier effectiveness. Install the drier in as cold a location as possible in the direction of the flow arrow on the unit.
SELECTION NOTE: Given the proper liquid line size and connection type, the correct drier may be selected using the charts below. Choosing a unit size with sufficient water capacity to reduce moisture content of the system to a safe level should be considered.
SELECTION
|
|
Flow Capacity in Tons Refrigerant1 @ psi (For kW, Multiply Tons By 3.5)2 |
|||
Model Number |
Connection |
R-134a |
R-22 |
R-410A |
R-404A/R507 |
96-TD032 |
1/4 SAE |
1.7 |
1.9 |
1.9 |
1.2 |
96-TD032S |
1/4 ODF |
2.1 |
2.2 |
2.2 |
1.5 |
96-TD052 |
1/4 SAE |
1.8 |
2.0 |
2.0 |
1.3 |
96-TD052S |
1/4 ODF |
2.6 |
2.8 |
2.9 |
1.9 |
96-TD053S |
3/8 ODF |
4.1 |
4.4 |
4.5 |
2.9 |
96-TD082S |
1/4 ODF |
2.8 |
3.0 |
3.1 |
2.0 |
96-TD083S |
3/8 ODF |
3.8 |
4.1 |
4.2 |
2.7 |
96-TD163 |
3/8 SAE |
4.0 |
4.3 |
4.4 |
2.9 |
96-TD163S |
3/8 ODF |
4.4 |
4.8 |
4.9 |
3.2 |
96-TD164S |
1/2 ODF |
7.7 |
8.4 |
8.6 |
5.6 |
96-TD165S |
5/8 ODF |
11.8 |
12.8 |
13.1 |
8.5 |
96-TD303S |
3/8 ODF |
5.7 |
6.1 |
6.2 |
4.1 |
96-TD304S |
1/2 ODF |
7.9 |
8.6 |
8.8 |
5.7 |
96-TD305S |
5/8 ODF |
13.1 |
14.1 |
14.4 |
9.5 |
1 All Ratings in accordance with ARI standard 710-04 liquid refrigerant Temperature
5°F Saturated vapor temperature |
4.4 lbs/min/ton R502 |
3.1 lbs/min/ton R134a |
2.7 lbs/min/ton R410A |
2.9 lbs/min/ton R22 and R407C |
2 Example: 1.0 tons x 3.5 = 3.5 KW |
4.0 lbs/min/ton R404A/507 and R-12 |
|
Connections, Dimensions, Flow Capacitors
|
|
|
|
|
Refrigeration Low Temperature |
Air Conditioning Field Replacement |
|
|
|||
|
|
|
Dimension |
& -Commercial Installations |
& Field Installations |
Air Conditioning OEM Self Contained |
|||||
Model Number |
Connection |
|
A |
B |
R-134a |
R-22 |
R-404A/R507 |
R-134a |
R-22/R-407C/R-410A |
R-134a |
R-22/R-407C/R-410A |
96-TD032 |
1/4 SAE |
|
4.32 |
1.63 |
1/2 |
1/2 |
|
|
|
3/4 |
1 |
96-TD032S |
1/4 ODF |
|
3.76 |
1.63 |
1/2 |
1 |
1 1/2 |
|
|||
|
|
|
|
|
|||||||
96-TD052 |
1/4 SAE |
|
4.88 |
2.50 |
3/4 |
3/4 |
1 |
1 1/2 |
|||
|
|
|
|
||||||||
96-TD052S |
1/4 ODF |
|
4.33 |
2.50 |
|
|
|
||||
|
|
|
|
|
|
|
|
||||
96-TD053S |
3/8 ODF |
|
4.53 |
2.50 |
1 1/2 |
2 |
1 1/2 |
3 |
4 |
2 |
3 |
96-TD082S |
1/4 ODF |
|
5.24 |
2.50 |
1 |
1 |
3/4 |
1 1/2 |
2 |
2 |
4 |
96-TD083S |
3/8 ODF |
|
5.43 |
2.50 |
2 |
3 |
2 |
4 |
5 |
3 |
4 |
96-TD163 |
3/8 SAE |
|
6.89 |
2.50 |
|
|
|
4 |
5 |
4 |
7 1/2 |
96-TD163S |
3/8 ODF |
|
6.22 |
2.50 |
3 |
5 |
|
|
|
||
|
|
|
|
|
|
||||||
96-TD164S |
1/2 ODF |
|
6.27 |
2.50 |
|
3 |
5 |
10 |
5 |
7 1/2 |
|
|
|
|
|||||||||
96-TD165S |
5/8 ODF |
|
6.54 |
2.50 |
|
7 1/2 |
|
7 1/2 |
12 |
7 1/2 |
10 |
96-TD303S |
3/8 ODF |
|
8.90 |
3.00 |
4 |
5 |
|
4 |
6 |
4 |
5 |
96-TD304S |
1/2 ODF |
|
8.94 |
3.00 |
7 1/2 |
4 |
7 1/2 |
10 |
7 1/2 |
9 |
|
|
|
||||||||||
96-TD305S |
5/8 ODF |
|
9.21 |
3.00 |
7 1/2 |
10 |
5 |
10 |
15 |
10 |
14 |
1 All Ratings in accordance with ARI standard 710-04 liquid refrigerant Temperature |
2.9 lbs/min/ton R22 and R407C |
4.4 lbs/min/ton R502 |
|||||||||
5°F Saturated vapor temperature |
|
|
|
|
|
4.0 lbs/min/ton R404A/507 and R-12 |
2.7 lbs/min/ton R410A |
||||
2 Example: 1.0 tons x 3.5 = 3.5 KW |
|
|
|
|
|