TECHNICAL HELP
1F82-261 / 1F89-211 |
|
CONFIGURATION AND |
|
TYPICAL WIRING DIAGRAMS |
|
|
||
|
|
|
|
|
|
|
|
|
CONFIGURATION
The following table allows you to customize the options on your Comfort-Set thermostat. Begin by pressing simultaneously the two buttons in step 1.
Step |
1F82-261 |
1F89-211 |
Displayed (Factory Default) |
Press |
or |
to select: |
COMMENTS |
||||
Press Button(s) |
Press Button(s) |
||||||||||
|
|
|
|
|
|
|
|||||
1 |
|
PRGM |
Set SYSTEM |
HOLD |
|
0 to 8 hrs (in |
|
Select temporary Hold time |
|||
|
and RUN |
switch to OFF |
(0:00) |
15 minute increments) |
|
||||||
2 |
|
HOLD* |
or |
|
|
|
|
FA |
|
Select FA or SL (Fast or Slow) pump cycle rate |
|
|
|
(SL) |
|
|
|||||||
|
|
|
|
|
|
|
|
|
|||
3 |
|
HOLD* |
or |
EMER |
|
SL |
|
Select FA or SL (Fast or Slow) Auxiliary and |
|||
|
|
|
|
|
(FA) |
|
|
|
Emergency Aux heating cycle rate |
||
4 |
|
HOLD* |
or |
|
d-L |
|
OFF |
|
Select display backlight OFF or ON |
||
|
|
|
|
|
(on) |
|
|
|
|
||
5 |
|
HOLD* |
or |
|
E |
|
OFF |
|
Select Energy Management Recovery OFF or ON |
||
|
|
|
|
|
(on) |
|
|
|
|
||
6 |
|
HOLD* |
or |
|
Filter |
0 to 1950 hours |
Select filter replacement run time |
||||
|
|
|
|
(000) |
(in 50 hour increments) |
|
|||||
7 |
|
HOLD* |
or |
|
LOC |
|
on |
|
Select Compressor lockout OFF or ON |
||
|
|
|
|
(OFF) |
|
|
|
|
|||
8 |
|
HOLD* |
or |
|
0 HI |
|
4 LO to |
|
Select temperature display adjustment higher or lower |
||
|
|
|
|
(0) |
|
4 HI |
|
|
|||
9 |
|
HOLD* |
or |
|
°(F) |
|
°C |
|
Select temperature display to °F or °C |
||
|
|
|
|
|
|
|
|
|
|
|
|
10 |
|
HOLD* |
or |
FA (ON) |
|
OFF |
|
Selects fast second stage ON or OFF |
|||
|
|
|
|
|
|
|
|
|
|
|
|
11 |
|
RUN |
|
|
|
|
|
|
|
Returns to normal operation |
|
|
|
|
|
|
|
|
|
|
|
|
* Press HOLD to advance to next item or TIME to move backwards to previous item
O/B switch
|
W904 |
Reset switch |
|
(below Fan switch) |
Electric/Gas |
|
jumper (W904) |
Electric / Gas Jumper (Fan Option)
If your emergency or auxiliary system will energize the blower, then jumper W904, on the thermostat base, must be cut (see figure at left). If your emergency or auxiliary heat system requires that the thermostat energize the fan circuit, do not cut jumper W904.
O/B Terminal Switch Selection
The O/B switch on this thermostat is factory set to the “O” position.
This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in COOL. If the thermostat you are replacing or the heat pump being installed with this thermostat requires a “B” terminal, to energize the changeover relay in HEAT, the O/B switch must be moved to the “B” position.
TYPICAL WIRING DIAGRAMS
O/B |
Y |
|
G |
|
W2 |
|
|
E |
C |
|
L |
R |
|||||||
|
|
|
|
|
|
|
See Note ** |
|
|
SYSTEM |
|
|
|
SYSTEM |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
Changeover |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
Fan |
|
|
|
|
|
|
|
MONITOR |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
Emergency |
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
Relay* |
|
Compressor |
|
|
Aux |
|
|
|
|
SWITCH |
|
|
|
|
|||||
|
|
Relay |
|
|
|
Relay |
|
|
|
|
|
|
|||||||
|
|
|
|
Relay |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
Contactor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Stage 2) |
|
|
|
|
24 VAC |
|
|
|
Hot |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
120 VAC |
||||
* Changeover Relay is energized in COOL when O/B switch is in the “O” position |
|
|
|
|
|
|
|
|
|
Neutral |
|||||||||
|
|
|
|
|
|
|
|
|
|||||||||||
Changeover Relay is energized in HEAT when O/B switch is in the “B” position |
|
|
|
|
|
TRANSFORMER |
|||||||||||||
** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency |
|
|
|
|
|
|
(Class II) |
Single transformer systems
NOTE
If safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits.
|
|
O/B |
Y |
G |
W2 |
E |
C |
L |
CUT AND |
|
|
|
|
|
|
|
|
TAPE OFF! |
Changeover |
|
Fan |
See Note ** |
|
SYSTEM |
||
|
|
|
|
Emergency |
|
MONITOR |
||
HOT |
|
Relay* |
|
Relay |
|
|
SWITCH |
|
|
|
|
|
|
Aux |
Relay |
|
|
120 VAC |
24 VAC |
Compressor |
|
|
|
|
||
|
|
|
Relay |
|
|
|
||
|
|
|
Contactor |
|
|
|
|
|
NEUTRAL |
|
|
|
(Stage 2) |
|
|
|
TWO COMMONS MUST
* Changeover Relay is energized in COOL when O/B switch is in the “O” position BE JUMPERED TOGETHER! Changeover Relay is energized in HEAT when O/B switch is in the “B” position
** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency
Two transformer systems with NO safety circuits
R
SYSTEM
Limit or
Safety
Switches
Hot
24 VAC 120 VAC
Neutral
TRANSFORMER
(Class II)
158 |