1311 Three Wire Zone Valve
TERMINALS 1, 2 = POWER TO VALVE 1= 24 VAC NEUTRAL
2 = 24 VAC HOT
TERMINALS 5,4,6 = SPDT THERMOSTAT 5 = POWER (SAME AS 2 INTERNALLY) 4 = OPENS VALVE
6 = CLOSES VALVE
TERMINALS 2, 3 = AUXILIARY SWITCH
2, 3 BECOME SAME POINT ON CALL FOR HEAT
|
|
|
|
TO AUXILIARY CIRCUIT |
|
THERMOSTAT |
|
|
|
FOR OPERATING BURNER |
|
5 |
|
2 |
AND/OR CIRCULATOR. |
||
|
|
||||
|
|
|
|
(NOTE: IF SAME TRANS- |
|
|
CONTACT |
|
|
FORMER POWERS BOTH |
|
6 |
|
|
THE AUXILIARY CIRCUIT |
||
|
|
|
AND THE WATER VALVE, |
||
|
|
SIDE "A" |
|
||
|
|
|
CONNECT AUXILIARY CIR- |
||
R |
6 |
OPEN |
3 |
||
CUITTOTERMINALS1AND |
|||||
|
|
POSITION |
|
||
|
|
|
3 INSTEAD OF 2 AND 3.) |
||
|
HOLDING |
|
|
||
W |
|
|
|
||
CONTACT |
|
|
|
||
|
|
|
|
||
|
4 |
|
|
|
|
|
|
|
|
SIDE "B" |
|
|
CLOSED |
|
|
OPEN |
|
|
POSITION |
|
|
POSITION |
|
INTERNAL |
SIDE "A" OF |
|
|
|
|
MOTOR SWITCH |
|
|
LINE |
||
WIRING |
|
|
|||
|
|
1 |
|
||
EXTERNAL |
SIDE "B" OF |
|
|
||
MOTOR |
|
|
|||
WIRING |
MOTOR SWITCH |
|
|
||
|
|
|
|||
|
|
|
|
TRANSFORMER |
|
|
SCHEMATIC OF VALVE |
|
|
TERMINALS 1, 3 = POWER OUT TO AUXILIARY CIRCUIT ON CALL FOR HEAT
TROUBLESHOOTING:
1)Attach a voltmeter to terminals 1 and 2. Power (24 volts) should always be present on 1 and 2. If power is interrupted check transformer or power source.
2)With a voltmeter attached as above, jumper terminals 5 and 4 to verify the valve opens. If power is present on 1 and 2 but the valve fails to open check connections. Replace motor assembly (replacement Motor # F19-0097) if condition persists. When the valve opens, break the connection between 5 and 4 and jumper between 5 and 6. The valve should close. If the valve fails to close replace motor assembly.
3)Terminals 2 and 3 (auxiliary circuit) become the same point electrically when the valve opens. Because terminal 2 is 24 volts hot, a voltmeter should read 24 volts between terminal 3 and terminal 1 (neutral) when the valve is open.
Note: If the auxiliary circuit terminals (2 and 3) are being attached to a control circuit with a separate transformer the transformers must be in phase or one transformer may be damaged. If phasing the transformers is not possible a 24 volt isolation relay can be installed with the coil attached to terminals 1 and 3 and the contacts can be used to operate the control circuit. The relay will energize when the valve opens.
For complete installation instructions visit our website.
|