White Rodgers 1311-102, 1311-103, 1311-104 Troubleshooting

5 (1)
White Rodgers 1311-102, 1311-103, 1311-104 Troubleshooting

RESIDENTIAL

WIRING

ZONE VALVES

1311 Three Wire Zone Valve

TERMINALS 1, 2 = POWER TO VALVE 1= 24 VAC NEUTRAL

2 = 24 VAC HOT

TERMINALS 5,4,6 = SPDT THERMOSTAT 5 = POWER (SAME AS 2 INTERNALLY) 4 = OPENS VALVE

6 = CLOSES VALVE

TERMINALS 2, 3 = AUXILIARY SWITCH

2, 3 BECOME SAME POINT ON CALL FOR HEAT

 

 

 

 

TO AUXILIARY CIRCUIT

THERMOSTAT

 

 

 

FOR OPERATING BURNER

5

 

2

AND/OR CIRCULATOR.

 

 

 

 

 

 

(NOTE: IF SAME TRANS-

 

CONTACT

 

 

FORMER POWERS BOTH

6

 

 

THE AUXILIARY CIRCUIT

 

 

 

AND THE WATER VALVE,

 

 

SIDE "A"

 

 

 

 

CONNECT AUXILIARY CIR-

R

6

OPEN

3

CUITTOTERMINALS1AND

 

 

POSITION

 

 

 

 

3 INSTEAD OF 2 AND 3.)

 

HOLDING

 

 

W

 

 

 

CONTACT

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

SIDE "B"

 

CLOSED

 

 

OPEN

 

POSITION

 

 

POSITION

INTERNAL

SIDE "A" OF

 

 

 

MOTOR SWITCH

 

 

LINE

WIRING

 

 

 

 

1

 

EXTERNAL

SIDE "B" OF

 

 

MOTOR

 

 

WIRING

MOTOR SWITCH

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

SCHEMATIC OF VALVE

 

 

TERMINALS 1, 3 = POWER OUT TO AUXILIARY CIRCUIT ON CALL FOR HEAT

TROUBLESHOOTING:

1)Attach a voltmeter to terminals 1 and 2. Power (24 volts) should always be present on 1 and 2. If power is interrupted check transformer or power source.

2)With a voltmeter attached as above, jumper terminals 5 and 4 to verify the valve opens. If power is present on 1 and 2 but the valve fails to open check connections. Replace motor assembly (replacement Motor # F19-0097) if condition persists. When the valve opens, break the connection between 5 and 4 and jumper between 5 and 6. The valve should close. If the valve fails to close replace motor assembly.

3)Terminals 2 and 3 (auxiliary circuit) become the same point electrically when the valve opens. Because terminal 2 is 24 volts hot, a voltmeter should read 24 volts between terminal 3 and terminal 1 (neutral) when the valve is open.

Note: If the auxiliary circuit terminals (2 and 3) are being attached to a control circuit with a separate transformer the transformers must be in phase or one transformer may be damaged. If phasing the transformers is not possible a 24 volt isolation relay can be installed with the coil attached to terminals 1 and 3 and the contacts can be used to operate the control circuit. The relay will energize when the valve opens.

For complete installation instructions visit our website.

 

TECHNICAL HELP

next

1361 Troubleshooting . . . . . . . . see next page