Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com
Model #: SU2200XLCD
SmartOnline 2.2kVA On-Line Double-Conversion UPS, Tower, Interactive LCD display, 100/110/120/127V NEMA 5-15/20R & L5-20R outlets
Highlights
2200VA / 2.2kVA / 1800 watt on-line double-conversion tower UPS
100/110/120/127V 50/60Hz output, 97% efficiency economy mode option
Interactive LCD with 10 selectable screens of UPS and site power data
Expandable runtime, Hot-swappable batteries
USB, RS232 & EPO ports, SNMPWEBCARD option
2 independently switched load banks
NEMA 5-20P input; 6 5-15/20R & 1 L5-20R outlets
Description
Tripp Lite Smart Online UPS systems offer high performance power protection ideal for critical server and network equipment in a variety of application environments. Online, double-conversion Uninterruptible Power Supply / UPS maintains perfectly regulated output power by continuously converting raw AC input to DC, then re-converting output back to AC. Sine wave AC output with +/-2% voltage regulation powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains battery-derived AC output during power failures with zero transfer time. Extended runtime options available. Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Highly efficient operation in optional economy mode saves BTU heat output and energy costs. Network management interfaces support communications via USB, RS-232, contact-closure and optional SNMPWEBCARD network interface. Built-in DB9 port offers both enhanced RS-232 data and basic contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. LED display reports UPS operating mode, line power availability, battery mode operation, inverter operation, ECO mode status and output power availability. Audible alarm with push-button momentary alarm-cancel and silent-mode LCD configuration options. Programmable self-test. Fault-tolerant auto-bypass mode. Battery independent restart. Field-replaceable, hot-swappable internal batteries and external battery packs.
Package Includes
SU2200XLCD UPS System
PowerAlert Software CD and cabling
Owner's Manual with warranty information
EPO (Emergency Power Off) cabling
Features
Tripp Lite SU2200XLCD 2200VA / 2.2kVA / 1800W on-line, double-conversion tower UPS
Selectable 100/110/120/127V output (120V factory preset)
NEMA 5-20P input, 6 5-15/20R & 1 L5-20R outlets
Two switched output load banks support remote reboot and programmable load shedding options
Supports 2% output voltage regulation and zero transfer time in double conversion mode
Economy mode option offers high 97% efficiency, reduced power consumption and lower BTU emissions
13 minutes runtime at 50% load (900W) and 4.5 minutes at 100% load (1800W) with internal batteries
Extended runtime options available with BP48V24-2U (limit 1) or BP48V60RT3U (no limit) external battery packs (external battery configurations require Tripp Lite's External Battery Configuration Software)
LCD interface reports operating mode plus 10 selectable screens of UPS data (Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Load kVA, Load kW, Battery charge percentage, Battery voltage and Minutes runtime)
LCD interface also supports 9 screens of advanced UPS configuration, setup and information options (Output voltage, Output frequency, Frequency regulation, Bypass range, Economy mode, Audible alarm, Overload alarm, External battery, Display IP address)
Single line TEL / Network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement
Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60 to 50Hz
Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
Output kVA capacity (kVA)
Output Watt
Capacity (watts)
Output kW capacity
Output power factor
Output Capacity
Details
2200
2.2
1800
1.8
0.82
ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120V 1800 watts, 115V 1620 watts, 110V 1530 watts, 100V 1440 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120V 1260 watts, 115V 1134 watts, 110V 1071 watts, 100V 1008 watts).
Crest Factor
Nominal Output
Voltage(s)
Supported
3:1
100V; 110V; 120V; 127V
Nominal Voltage details
Frequency compatibility
Frequency compatibility details
120V default
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency when input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is regulated to +/-0.05Hz of selected nominal.
Output voltage |
+/- 2% |
|
regulation (line |
|
|
mode) |
|
|
|
|
|
|
|
|
Output voltage |
+/- 10% |
|
regulation |
|
|
(Economy line |
|
|
mode) |
|
|
|
|
|
|
|
|
Output voltage |
+/- 3% |
|
regulation (Battery |
|
|
mode) |
|
|
|
|
|
|
|
|
Built-in UPS |
|
6 5-15/20R outlet(s); 1 L5-20R outlet(s) |
output receptacles |
|
|
|
|
|
Built-in |
|
Two switchable three-outlet load banks |
controllable |
|
|
switched load |
|
|
banks |
|
|
|
|
|
|
|
|
Output AC |
|
Pure Sine wave |
waveform (AC |
|
|
mode) |
|
|
|
|
|
|
|
|
Output AC |
|
Pure Sine wave |
waveform (battery |
|
|
mode) |
|
|
|
|
|
INPUT |
|
|
|
|
|
Rated input |
|
16A |
current (at |
|
|
maximum load) |
|
|
|
|
|
|
|
|
Nominal Input |
|
100V AC; 110V AC; 120V AC; 127V AC |
Voltage(s) |
|
|
Supported |
|
|
|
|
|
Nominal input voltage description
UPS input connection type
Input circuit breaker
UPS Input cord length (ft.)
UPS Input cord length (m)
Recommended
Electrical Service
BATTERY
120V factory default
5-20P
30A
10
3
15A 120V
Full load runtime (minutes)
Half load runtime (minutes)
Expandable battery runtime
External battery pack compatibility
Expandable runtime description
DC system voltage (VDC)
Battery recharge rate (included batteries)
4.5 min. (1800w)
13 min. (900w)
Extended runtime supported via optional external battery packs
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible)
External battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual for details
48
Less than 3 hours from 10% to 90%
Replacement |
|
RBC48-SUTWR |
battery cartridge |
|
|
(internal UPS |
|
|
battery |
|
|
replacement) |
|
|
|
|
|
Battery Access |
|
Battery access door |
|
|
|