Toshiba VF-A7 User Manual 2

0 (0)

Instruction Manual

The new generation high-performance inverter

TOSVERTTMVF-A7

200V class 0.4 90kW

400V class 0.75 280kW

NOTICE

1.Make sure that this instruction manual is delivered to the end user of the inverter unit.

2.Read this manual before installing or operating the inverter unit, and store it in a safe place for reference.

© TOSHIBA Schneider Inverter Corporation 2001

All Rights Reserved.

Safety

I

precautions

Preface

II

Contents

 

Read this

1

section first

Connection

2

Operating

3

the inverter

Basic

4

Operation

Basic

5

parameters

Extended

6

parameters

Operation

7

with external

signal

 

Monitoring

8

operation

status

 

Peripheral

9

units

Table of

10

parameters

Specification

11

Prior to

12

service call

Regular

13

inspection and

maintenance

 

Warranty

14

Precautions

15

of disposal

Safety precautions

The labels on the inverter and this instruction manual contain important instructions for the prevention of possible injury to the user and other persons and damage to property, as well as for the safe use of the inverter. Please gain a good understanding of the following pictorial symbols before reading this manual and strictly observe the instructions that follow each symbols.

Marking

Symbols

Meaning

Danger

injuryMeans that improper use or handling could cause the risk of death or serious

 

 

Warning

Means that improper use or handling could cause injury to persons(*1) or

damage to property(*2).

 

 

(*1)”injury to persons” refer to injuries, burns, electric shocks, and so on, that do not oblige the injured person to be hospitalized or go to a hospital for a long period of time for medical treatment.

(*2)”damage to property” includes all kinds of losses resulting from it.

Symbols

Meaning

 

Represents prohibition(what you must not do)

 

What you must not do is described in or near this symbol by a picture or words

 

 

 

Represents mandatory items(what you must do)

 

What you must do is described in or near this symbol by a picture or word

 

Represents danger

 

What is dangerous is described in or near this symbol by a picture or word

 

Represents warning

 

What the warning should be applied is described in or near this symbol by a picture or word

 

 

Limited applications

This inverter is designed to control the speed of three-phase induction motors for general industry.

Precautions

When using our inverters for equipment such as nuclear power control equipment, aviation and space flight control equipment, traffic equipment, and safety equipment, and there is a risk that any failure or malfunction of the inverter could directly endanger human life or cause injury, please contact our headquarters, branch, or office printed on the front and back covers of this catalogue. Such applications must be studied carefully.

When using inverters for critical equipment, even though the inverters are manufactured under strict quality control always fit your equipment with safety devices to prevent serious accident or loss should the inverter fail(such as failure to issue an inverter trouble signal)

Do not use our inverters for any load other than three phase induction motors.

1

Handling in general

 

 

 

Danger

Reference

 

 

 

 

 

 

 

 

Never disassemble, modify or repair the inverter. Its disassembly could

2.

 

 

 

cause an electric shock, afire or an injury. Request your TOSHIBA dealer

 

Never

for repair.

 

Disassemble

 

 

 

 

 

-Never open the front cover of the inverter(or the door of the cabinet in

2.

 

 

 

which the inverter is installed) when the inverter is energized, or you

 

 

 

 

could get a shock since a high voltage is applied to certain portions of it.

 

Prohibited

-Do not put your fingers into the panel through a wiring opening or an

2.

opening in the cooling fan cover, or you could get a shock or an injury.

 

 

 

 

 

 

 

 

-Do not put or insert anything(e.g., electric cable, bar or steel wire) into the

2.

 

 

 

inverter, or the inverter could cause a shock or fire.

 

 

 

 

-Do not splash water over the inverter, or the inverter could cause a shock

2.

 

 

 

or a fire.

 

 

 

 

-Do not turn on the power before attaching the front cover (or closing the

2.

 

 

 

door of the cabinet in which the inverter is installed), or you could get a

3.

 

 

 

shock.

3.

Mandatory

-Turn off the power immediately in case the inverter smokes, smells of

smoke, or produce abnormal noise. Failure to do so could lead to a fire.

 

 

 

 

 

 

 

 

In such a case, request your TOSHIBA dealer for repair.

3.

 

 

 

-Due to the possibility of contaminants entering the drive, disconnect the

 

 

 

input power if the drive will be unused for extended periods.

 

 

 

 

The leakage current caused by the contamination may result in fire.

 

 

 

 

 

 

 

 

 

Warning

Reference

 

 

 

 

 

 

 

 

Do not touch any heat sink or braking resistor, or you could get a burn

3.

 

 

 

 

Never touch

since they become very hot.

 

 

 

2

Transportation Installation

 

Danger

Reference

 

 

 

 

-Do not install or operate the inverter if it is damaged or any part is missing

2.

 

from it. Operating the inverter in a defective condition could lead to a

 

 

shock or a fire. Request your Toshiba dealer for repair.

1.4.4

Prohibited

-Do not put any inflammable material near the inverter, or it could catch a

fire if the inverter sparks because of a breakdown, etc.

 

 

 

 

-Do not install the inverter where it can be splashed with water, etc., or it

2.

 

could cause a shock or a fire.

 

 

-Use the inverter under environmental conditions specified by this

1.4.4

 

instruction manual, or it could break down.

1.4.4

 

-Install the inverter on a non-combustible board, for example, a steel plate.

Mandatory

Installing it on a inflammable board or wall could lead to a fire because its

 

back is heated up during operation.

 

 

1.4.4

 

-Do not use the inverter with the front cover detached, or it could cause a

 

shock.

1.4.4

 

-Install an emergency shutdown device which matches the system (for

 

example, a switch interlocked with the brake of the machine). Failure to

 

 

do so could lead to injury to persons since it has no emergency stop

 

 

function.

 

 

-Do not use any optional devices other than those designated by our

1.4.4

 

company.

 

 

The use of improper devices could lead to accidents.

 

 

 

 

 

Warning

Reference

 

 

 

 

-Do not hold the front cover to carry the inverter, or the cover could come

2.

 

off and cause the main unit to fall, thus causing you to get an injury.

1.4.4

 

-Do not install the inverter in any place subject to vibration, or it could fall,

Prohibited

causing injury to persons.

 

 

-For a model (20 kg or more in weight) designed for 30kW motors or larger,

2.

 

carry it at least in a twosome, or it could fall and cause you to get an

 

 

injury.

 

Mandatory

-Handle large capacity model using a crane. Lifting heavy inverter causes

 

injury to persons. Taking care of safety for users, carefully handle in order

 

 

not to damage to the inverter.

 

 

Carefully lift up the inverter, hanging wires on the hanging bolts or halls

 

 

on the top or bottom of the inverter.

 

 

-Four points and perpendicular lifting is recommended. Even if

 

 

perpendicular lifting is impossible, respect the condition described in the

 

 

following figure. A crack may be attached to the product body when not

 

 

performing perpendicular lifting. Please be careful.

 

 

60° Max.

 

60° Max.

-Install the main unit on a wall, or the like, which is strong enough to

1.4.4

withstand its weight, or it could fall and cause injury to persons.

 

-Install a mechanical brake whenever the motor requires a brake (device

1.4.4

which retains the motor shaft). Failure to do so could lead to injury to

 

persons because the inverter itself has no function of mechanically

 

retaining the brake shaft.

 

3

Wiring

 

Danger

Reference

 

 

 

 

-Do not connect the power cable to any output terminal (U/T1, V/T2 or W/T3

2.2

 

on the motor side), or the inverter could break down and cause a fire.

2.2

 

-Do not connect a resistor to any D.C. terminal (between PA and PC or PO

Prohibited

and PC), or the inverter could cause a fire.

6.13.4

To install external braking resistor, refer to 6.13.4.

 

 

 

 

-Don’t touch the connector terminals and cables of the devices(MCCB) on

 

 

he input side of the inverter within 10 minutes after shutting down the

2.2

 

power source

 

 

-Entrust all electrical work to an experienced specialist. Wiring by an

2.

 

inexperienced person could result in a fire or an electric shock.

2.

 

-Connect the output terminals (on the motor side) correctly. Incorrect

Mandatory

connection of the terminals causes the motor to rotate in a wrong

 

direction, and thus could result in injury to persons.

 

 

2.

 

-Perform wiring always after installing the inverter, or you could get a

 

shock or an injury.

2.

 

-Be sure to perform the following preparatory work before proceeding to

 

wiring.

 

 

(1) Turn off the power.

 

 

(2) 10 minutes or more after turning off the power, make sure that charge

 

 

lamp is extinct.

 

 

(3) Using a circuit tester with a D.C. voltage measuring capacity of more

 

 

than 800V, check to be sure that the voltage remaining in the D.C.

 

 

main circuit (between PA and PC) is below 45V.

 

 

Failure to do so could lead to an electric shock.

 

 

-Tighten the terminal board fixing screws at the specified torque. Failure to

2.

 

do so could lead to a fire.

 

 

-Make sure that the supply voltage is within +10%/-15% (during continuous

1.4.4

 

operation or within ±10% under full load) of the inverter's rated voltage

 

 

specified on its rating label. Supplying a voltage exceeding the above

 

 

range could lead to a breakdown, an electric shock or a fire.

 

 

-Connect grounding wires correctly and securely. Otherwise, a breakdown

2.

 

or electric leakage could lead to an electric shock or a fire.

2.2

Be Grounded

 

9.

 

 

Warning

Charged capacitors can present a shock hazard even after source power is removed

Drives with EMI filters will retain a charge on the input terminals for up to 10 min. after the power has been removed. To avoid electrical shock, don’t touch the connector terminals and uninsulated source cables at either the main circuit disconnect or the drive until the capacitive charge has dissipated.

4

About operation

 

Danger

Reference

 

 

 

 

-Do not touch any inverter's terminal when it is energized even if the motor

3.

 

is standstill, or you could get a shock.

3.

 

-Do not operate switches with a wet hand or not put a wet cloth on the

Prohibited

inverter, or you could get a shock.

3.

-Do not get near the alarm-stopped motor when the system is in retry

 

 

mode, or you could get an injury.

 

 

Take safety measures, for example, attaching a cover to the motor, to

 

 

protect persons against accidents when the motor unexpectedly restarts.

6.21

 

-Don't set the motor constant 3 (exciting inductance: ) as 1/2 or less

 

value of default setting value. If the motor constant 3 (exciting

 

 

inductance : ) is set as extremely small value, the stole prevention

 

 

function

6.25.2

 

will incorrect-operate and will raise output frequency.

 

-Don't set the stole prevention level( ) as extremely small value.

 

 

When the stole prevention level( ) is set as motor no-load current

 

 

or value lower than it, the stole prevention function always operates. And

 

 

if it is judged as regeneration mode, frequency will be raised.

 

 

Please do not set the stole prevention level( ) to 30% or less in

 

 

the usual usage.

 

 

-Do not turn on the power before attaching the front cover. When the

3.

 

inverter is installed in a cabinet with the inverter's front panel detached,

9.

 

always close the door of the cabinet before turning on the power.

 

Mandatory

Turning on the power with the cover or the door left opened could lead to

 

an electric shock.

 

 

 

 

-Turn off the operation signal before resetting the inverter after trouble, or

3.

 

the motor unexpectedly restarts, causing injury to persons.

 

 

 

 

 

Warning

Reference

 

 

 

 

-Operate the motor always within the allowable operation range. (Refer to

 

 

the motor’s instruction manual for the allowable operation range.)

3.

Mandatory

Failure to do so could cause injury to persons.

 

 

 

When selecting the sequence that automatically restarts the motor after

recovery from a momentary power failure (Applicable to inverters)

 

Warning

Reference

 

 

 

 

-Do not get near the motor or the machine.

6.13.1

 

The motor and the machine unexpectedly restart after recovery from a

 

 

momentary power failure.

 

Mandatory

-Stick caution labels to the inverter, the motor and the machine, to prevent

 

accidents due to an unexpected restart of them after recovery from a

 

 

 

 

momentary power failure.

 

5

When selecting the retry mode (Applicable to inverters)

 

Warning

Reference

 

 

 

 

-Do not get near the motor.

6.13.3

 

When the retry mode is selected, the motor and machine that stopped

 

 

after an alarm restart unexpectedly after the selected time has passed,

 

Mandatory

thus causing injury to persons.

 

-Stick caution labels to the inverter, the motor and the machine, to prevent

 

 

 

 

accidents due to an unexpected restart of them in retry mode.

 

About inspection and maintenance

 

 

 

 

 

Danger

Reference

 

 

 

 

-Do not replace any part yourself, or you could get a shock or an injury, or

13.2

 

cause a fire. Request your Toshiba dealer for replacement of parts.

 

Prohibited

 

 

 

-Carry out inspection and maintenance on a daily basis. Failure to do so to

13.

 

find defects in the inverter could lead to accidents.

 

 

-Be sure to perform the following preparatory work before proceeding to

13.

Mandatory

inspection.

13.2

(1) Turn off the power.

 

 

 

 

(2) 10 minutes or more after turning off the power, make sure that charge

 

 

lamp is extinct.

 

 

(3) Using a circuit tester with a D.C. voltage measuring capacity of more

 

 

than 800V, check to be sure that the voltage remaining in the D.C.

 

 

main circuit (between PA and PC) is below 45V.

 

 

Failure to do so could lead to an electric shock.

 

About disposal of inverters

 

 

 

 

 

Warning

Reference

 

-When you throw away the inverter, have it done by a specialist in

15.

 

industrial waste disposal*.

 

 

If the collection, transport and disposal of industrial waste is dune by

 

Mandatory

someone who is not licensed, it is punishable as a violation of the law.

 

(Laws in regard to disposal and cleaning of waste.)

 

 

 

 

(*)People who specialize in the processing of waste and are known

 

 

as "industrial waste collectors and transporters" or "industrial

 

 

waste disposal specialists".

 

Sticking warning labels

Here are examples of caution labels designed to prevent accidents caused by an inverter, a motor or a machine. When selecting the automatic restart function or the retry function, stick the applicable

label to a conspicuous position.

Please stick this label to a conspicuous position when selecting the sequence that automatically restarts the machine after recovery from a mini power failure.(An example of the restart caution label)

Warning (automatic restart function enabled)

Do not get near the motor or the machine. The motor and the machine which stopped.

Because of a mini power failure, unexpectedly restart after the preset time has passed.

Please stick this label to a conspicuous position when selecting the retry function.

(An example of the retry caution label)

Warning (Retry function enabled)

Do not get near the motor or the machine. The motor and the machine which stopped after an alarm, unexpectedly restart after the preset time has passed.

6

Preface

Thank you for purchasing the industrial inverter "TOSVERT VF-A7".

This inverter has a "Ver. 315"CPU or later.

Please refer to "10. Table of parameters" for the functions available for the inverter with a CPU in this version.

The CPU version will be frequently upgraded.

Features

1. Noise filter incorporated

1)Every 200V or 400V model (200V 0.4 7.5KW and 400V 0.75 15kW models) has a built-in noise filter.

2)" VF-A7" complies with the European CE marking requirements. 3)" VF-A7" complies with the UL/cUL standard.

4)" VF-A7" saves space and does not require troublesome wiring.2. Excellent torque control performance

1)200% torque even at a frequency of 0.5 Hz(with vector control) The speed control ratio is 1 :150.

2)Torque limit function

3. A wide range of applications from simple speed control to system control

1)Auto-tuning function

All you have to do make the " VF-A7" ready for start is to connect it to the motor and the power supply unit; the " VF-A7" does not require cumbersome parameter setting to start it.

2)High flexibility and system expendability

" VF-A7" has a number of functions, including torque control, sensor (or sensorless) vector control, drooping function, commercial power/inverter switching function and various communication functions, which allow the inverter to be used as part of a system.

3)Torque control

In addition to speed control by the frequency command, " VF-A7" is capable of speed control by the torque command, which is best suited to winding control.

4. Options that widen the range of application

Extended terminal board

Communication devices

(RS485, RS232C, TOSLINE-F10M/S20)

Add-on cassettes compatible with sensor vector control(Speed feedback, torque control and positioning control, etc... )

Sensor vector control-compatible board(Speed feedback, torque control)

Extension panel Parameter writer

Other optional devices common to all models

Control power supply unit

Heat-sink attachment

7

Read this section first

1.1 Checking the purchase

Make sure that the inverter delivered is exactly what you ordered.

Warning

Use an inverter which matches the input power rating of your three-phase induction motor. The use of an inverter unsuitable for your motor can cause it to rotate in a wrong

Mandatory direction, and thus lead to grave accidents, including its burning due to overheating.

Applicable motor label Inverter main unit

Pet name

 

200V-3.7kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

 

Motor capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Warning label

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Package

Name plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter type

TRANSISTOR INVERTER

 

 

 

 

 

 

 

 

 

TYPE-FORM

 

VFA7-2037PL

 

 

 

 

 

 

 

 

 

Power supply

SOURCE

3PH 200-230V-50/60Hz

 

 

 

 

 

 

 

 

 

Rated output current

OUTPUT

3PH 200-230V

 

 

 

 

 

 

 

 

 

and capacity

LOT No.

0.01 80(400MAX)Hz 16.6A 6.5kVA

 

 

 

 

 

 

 

 

Type indication

 

 

75 Cu wire

 

 

 

 

 

 

 

 

SERIAL No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M6587144P005

 

 

MADE IN JAPAN

1.2 Contents of the product code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Special

 

 

 

 

 

Type

 

 

 

 

 

 

 

Form

 

 

 

specification code

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model name

 

Input voltage

 

Applicable motor capacity

 

Operating panel

 

 

 

Additional

 

 

 

Special

 

 

 

 

 

 

functions

 

 

specification code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

. 4kW :004

 

75kW :750

 

P :Provided

 

 

F :External

 

 

A□□ :Special

TOSVERT

 

2:200V 230V

 

0. 75kW :007

 

90kW :900

 

P1 :Provided

 

 

heat sink

 

 

 

spec. code

VF-A7 series

 

4:380V 460V

 

1. 5kW :015

110kW :110K

 

(37kW and more)

 

 

N :with dynamic

 

 

(□□ is a

 

 

 

 

 

 

 

 

2

. 2kW :022

132kW :132K

 

PL :Provided

 

 

braking circuit

 

 

number)

 

 

 

 

 

 

 

 

3

. 7kW :037

160kW :160K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with noise filter

 

 

NF :External

 

 

 

 

 

 

 

 

 

 

 

 

 

5

. 5kW :055

220kW :220K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat sink

 

 

 

 

 

 

 

 

 

 

 

 

 

7

. 5kW :075

280kW :280K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with dynamic

 

 

 

 

 

 

 

 

 

 

 

 

 

11kW :110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

braking circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

15kW :150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

. 5kW :185

 

 

 

 

 

 

 

 

 

 

Y :Others

 

 

 

 

 

 

 

 

 

 

 

 

 

22kW :220

 

 

 

 

 

 

 

 

 

 

(non-standard)

 

 

 

 

 

 

 

 

 

 

 

 

 

30kW :300

 

 

 

 

 

 

 

 

 

 

Z :Explosion proof

 

 

 

 

 

 

 

 

 

 

 

 

 

37kW :370

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45kW :450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55kW :550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note) Turn off the power in advance when checking the rating of the inverter installed in a cabinet.

A-1

Toshiba VF-A7 User Manual 2

1.3 Names and functions

1.3.1 Panel description

VEC lamp

RUN lamp

MON lamp

Lit when the Inverter

Lit when the inverter is in

Lit when the

operation or blinks when It

is in vector control

inverter is in

is in auto acceleration/

mode.

monitor mode.

deceleration mode.

ECN lamp

Lit when the inverter is in energy-saving mode.

RUN key lamp

Lit when the RUN key is enabled.

RUN key

Pressing this key while the RUN key is lit starts the motor.

UP/DOWN key lam

With these keys, you can set the operation frequency while the UP/DOWN lamp is lit.

[ Front view ]

Connector for options

PRG lamp

Lit when the inverter is in parameter setting mode.

STOP key

Pressing this key while the RUN key lump is lit causes the motor to make a slowdown stop.

MONITOR key

Used to display the operation frequency, parameter setting error messages, etc.

ENTER key

DOWN key

UP key

CHARGE lamp

Indicates that a high voltage remains in the inverter. Do not open the terminal board cover for safety while this lamp is lit.

Cover for common serial option connectors

To use connectors reserved for options, detach this cover by sliding it to the right.

Parameter writer

Extension panel, etc.

Cover for serial RS485 connectors

To use an RS485 connector, detach this cover by sliding it to the right.(Refer to 2.3.3)

Used to install the following options:

Expansion TB option unit

Vector option unit

F10M option unit

S20 option unit

PG feed back board, etc.

Terminal board cover fixing screws

Optional board

Used to install the following options:

PG feedback options

Pushing mark, make this cover slide to the right.

Sink/source

switching

Terminal board cover

Be sure to attach the cover before starting the operation to prevent persons from touching the terminal board in error.

A-2

Warning label on the top (*1)

 

Connectors for optional

 

Cooling fin

 

 

 

 

add-on module/board

 

 

Wiring hole (*2)

 

Ventilation slits

 

 

 

 

 

 

Rating label

 

 

 

[Bottom view]

[Side view]

(*1) Peel off this label when the inverter is installed in a rather hot place. (Models for 15kW motor or smaller) (*2) Using scissors or a cutter, cut the rubber bush in the wiring hole as shown below.(Models for 22kW

motor or smaller)

Cut

Rubber bush

Panel indication

LED display is using the following signs to indicate the operation parameter and so on.

LED indication (number)

 

 

 

 

 

 

 

 

 

 

 

 

LED indication (alphabet)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A-3

1.3.2 Main circuit, control power supply and control circuit terminal boards

Main circuit terminal board

VFA7-2004PL 2037PL

VFA7-4007PL 4037PL

VFA7-2055PL, 2075PL

VFA7-4055PL, 4075PL

VFA7-2110P 2150P

VFA7-4110PL 4150PL

A-4

VFA7-2185P, 2220P

VFA7-4185P, 4220P

Grounding terminal

VFA7-2300P, 4300P

VFA7-4370P1 4550P1

A-5

VFA7-2370P1 2550P1 VFA7-4750P1

VFA7-2750P1 VFA7-4110KP1, 4132KP1

VFA7-2900P1 VFA7-4160KP1 4280KP1

A-6

Control power supply terminal board

Note)To use R0,S0 terminal on 22kW model or smaller, you need a Control power supply

unit option.(Refer to 9.4)

VFA7-2055PL 2220P VFA7-4055PL 4220P

VFA7-2300P VFA7-4300P

VFA7-2370P1 2900P1

 

VFA7-4370P1 4280KP1

 

 

 

Control power

 

 

supply inputs

Control power

Power supply

 

supply inputs(*1)

for control circuit

(*1)Refer to 2.2 for the connection of control power cables by voltage(R46,R41 and S0 terminals).

A-7

Control circuit terminal

The control circuit terminal board is common to all models.

 

RES

 

S1

 

S2

 

S3

 

S4

 

RX

 

AM

 

FP

OUT2

 

F

 

R

 

ST

 

CC

 

CC

 

RR

 

PP

FM

 

OUT1

P24

FLA FLB FLC

ST-CC shorting bar

Screw size M3

Refer to section 2.3.2 for the functions of terminals.

1.3.3 Detaching the terminal board front cover

Detach the front lower cover for wiring, following the steps below.

■Less than 22kW

 

 

Remove the two screws at the lower part of the front cover.

Hooked

To detach the cover, draw the terminal board cover toward you while swinging it up a little.

* For a 30kW model or larger, detach the whole front cover for wiring.

A-8

1.4 Notes on the application of inverters

1.4.1 Notes on motors combined with inverters

Keep in mind the following notes when using the VF-A7 in combination with a motor.

Warning

Use an inverter which matches the input power rating of your three-phase induction motor. The use of an inverter unsuitable for your motor can cause it to rotate in a wrong direction,

Mandatory and thus lead to serious accidents, including its burning due to overheating.

Comparison with commercial power operation

The VF-A7 inverter uses a sinusoidal PWM control system. However, the waveforms of electric currents passing through the main and control circuits are not perfectly sinusoidal but slightly distorted though they are very close to perfect sine waves. For this reason, a motor produces more heat, larger noise and larger vibration when operated by means of the inverter than when operated directly by commercial power.

Operation in low speed ranges

Operating a general-purpose motor by means of the inverter causes a decrease in the cooling efficiency of the motor. So, reduce the motor's output below the rated load when operating it in a low speed range.

If you wish to operate a motor continuously at the rated torque, then use a Toshiba VF motor designed specially for use in conjunction with an inverter. When the inverter is combined with a VF motor, its overload protection level needs to be changed to "VF motor" ( setting).

Adjustment of overload protection level

The VF-A7 inverter has an overload detection circuit (electronic thermal detection) to protect the motor from overload. The reference current for the electronic thermal detection is set to the rated current of the inverter at the factory, and it needs to be adjusted to the rated current of the general-purpose motor combined with it.

High-speed operation at a frequency of 60 Hz or over

When a motor is operated at a frequency of 60 Hz or over, it produces larger noise and larger vibration, which can exceed a limit that the motor or its bearings can withstand. Contact the motor maker if you wish to operate the motor at such a high frequency.

Load of an oil lubrication type

When a speed reducer or a gear motor of an oil lubrication type is operated by the inverter, its oil lubrication efficiency decreases in low speed ranges. Inquire of the speed reducer maker about the allowable speed reduction range.

Extremely light load or load producing a very small moment of inertia

When a motor is operated under an extremely light load (e.g., at a load factor of less than 50%) or it drives a load which produces a very small moment of inertia, it sometimes becomes unstable, for example, it produces abnormal vibration or trips because of an over-current. In such a case, lower the carrier frequency to cope with this problem.

Unstable operation

When the inverter is used in combination with one of the following motors or loads, it sometimes makes the operation of the motor or load unstable.

A motor with a rated capacity that exceeds the motor capacity recommended for the inverter

A special type of motor, for example, an explosion-proof motor

When using the inverter for such motors, lower the inverter's carrier frequency to stabilize the operation. (In vector control mode, do not lower it below 2.2 kHz.)

A motor with a large backlash, which is coupled with a load

In this case, use the S-pattern acceleration/deceleration function, or in vector control mode, adjust the response time (setting of moment of inertia) or switch to V/f control mode to stabilize the operation.

A-9

A load, e.g., a reciprocating load, which requires a frequent change in the rotating speed

In this case, if the inverter is in vector control mode, adjust the response time (setting of moment of inertia) or switch to V/f control mode to stabilize the operation.

If it is operated in vector control mode, only a motor whose capacity is same as inverter standard or 1 rank lower is applied.

If it is operated in V/F (other than vector control), the rotating of motor can be unstable in combination with 3 or more ranks smaller motor.

<Stabilizing operation>

Lower the setting value of F300(PWM carrier frequency). (It causes much magnetic noise of motor, but it is not abnormal.)

In the case that it is still unstable even if the carrier frequency is lowered to 2.2kHz at ( ), set the setting value of F489(Dead time compensation) to 1 (Disabled) .

Braking of a motor after power shutoff

If the power is shut off while the motor is still rotating, the motor keeps rotating (or coasting) for a while before it comes to a complete stop. If you wish to stop it soon after turning off the power, equip the motor with an auxiliary braking system. There are several types of braking systems available, for example, mechanical and electrical types. Select a braking system which matches your system.

Load producing negative torque

When the inverter is combined with a load producing negative torque, the over-voltage or over-current protective function of the inverter sometimes works and causes the motor to trip. In this case, it is necessary to install a dynamic braking resistor, etc., suitable for the load.

Motor with a braking system

When a brake-equipped motor is connected directly with the inverter, the brake cannot be released at start-up because of an insufficient voltage. To avoid this, connect the brake cables separately from the motor main cables.

 

(Non-exciting brake)

(Non-exciting brake)

 

MC2

 

MC2

 

 

B

 

B

MC1

 

 

MC1

IM

 

FLB FLC ST

IM

Three-phase OUT1

Three-phase

CC

P24

 

 

power supply

 

power supply

 

MC3

 

 

 

 

 

 

 

 

LOW

 

MC1

MC3

LOW

MC3

 

 

 

 

MC3

MC2

MC3

MC2

 

 

 

 

 

Circuit configuration 1 Circuit configuration 2

In circuit configuration 1, the brake is turned on and off by means of MC2 and MC3. If the circuit is configured differently, the motor can trip because of a locked rotor current produced during braking.

In circuit configuration 2, the brake is turned on and off by means of a low-speed signal OUT1. However, for certain applications, e.g., elevator applications, it is recommended to use a low-speed detection signal (function of terminal OUT1) to turn on and off the motor. Contact your Toshiba dealer before designing a system.

A-10

1.4.2 Notes on inverters

Over-current protective function

The inverter has an over-current protective function. The current for this protection is adjusted to the maximum current rating of the applicable motors by default. Therefore, when the inverter is used to control a motor with a relatively small capacity, it is necessary to readjust the over-current protection level and the electronic thermal protective function. In such a case, follow the procedure specified in 5.13 to readjust them.

Inverter capacity

An inverter with a small capacity (kVA) must not be used for a motor with a relatively large capacity even if the motor is operated under a small load. If an inverter is used this way, the output peak current rises high because of a current ripple, thus causing the motor to trip easily.

Power factor improving capacitor

No power factor improving capacitor should be connected on the output side of the inverter. When the inverter is used for a motor equipped with a capacitor for power factor improvement, remove the capacitor from the motor. Connecting such a capacitor causes the inverter to break down and the motor to trip, or breaks the capacitor itself.

U

Inverter

V

W

IM

Remove the power factor improving capacitor and the surge absorber, if any.

Power factor improving capacitor

Use of an inverter at a voltage other than the rated one

There is a need to connect it to a power unit supplying a voltage different from the rated voltage, increase or reduce the supply voltage to the inverter's rated voltage, using a transformer, etc.

Use of a set of inverters, which requires circuit-breaking devices

MCCB1

MCCB2 Breaking fuse)

 

INV1

 

MCCB3

 

INV2

 

MCCBn

INVn

Circuit-breaking of defective inverter

When two or more inverters are connected to the same power line as shown above, it is necessary to select a circuit-breaking characteristic ensuring that, for example, if a short circuit occurs in INV 1, only MCCB2 trips but not MCCB1. If it is difficult to select a proper characteristic, then insert a breaking fuse between MCCB2 and INV 1 in this case.

Note on the disposal of inverters

Be sure to dispose of inverters as industrial wastes, when they become unnecessary.

A-11

1.4.3 Influences of leakage currents and measures against it

Warning

An electric current can leak through an input or output cable of the inverter because of its insufficient capacitance and, sometimes, affects the peripheral systems. The amount of a leakage current depends on the carrier frequency, the length of the input/output cable, etc. It is advisable to take the following measures to prevent leakage currents.

(1) Influences of a current leaking into other systems via the ground

An electric current can leak not only into other circuits of an inverter but also into other inverters through grounding wires. Such a leakage current can exerts influences on various electronic devices, for example, malfunction of ground leakage breakers or relays, ground relays, fire alarms, sensors, etc., noise on CRTs and display of incorrect current values on a

CRT screen.

Power

Inverter

IM

supply

 

 

Inverter IM

Measures to be taken:

1.Lower the PWM carrier frequency.

Use parameter to lower the PWM carrier frequency.

2.Use high frequency-ready ground leakage breakers (e.g., Esper Mighty series(manufactured by Toshiba Schneider Electric Ltd.)). When these ground leakage breakers are installed, there is no need to lower the PWM carrier frequency.

3.If sensors and CRTs are affected, they can be restored by lowering the PWM carrier frequency as described in 1 above. However, if lowering the PWM carrier frequency results in an increase in magnetic noise, contact your Toshiba dealer.

Cautions for applying models with a built-in noise filter.

For the models with a built-in noise filer, the leakage current value at power supply of (delta) connecting wire (1 phase earth) can be larger than normal inverter, so be

careful.

<Standard leakage current value> VFA7-2004PL 2037PL : about 4mA VFA7-2055PL, 2075PL : about 13mA

(2)Influences of a current leaking from a cable into other cables

Thermal relay

If a current leaks from an output cable of an inverter to other cables because of its insufficient capacitance, the high-frequency elements of the leakage current sometimes increase the effective current value, and thus cause external relays to malfunction. For a model with relatively long cables (longer than 50 m) or a model designed for motors with small current ratings (several amperes), especially 400V model with a small capacity (3.7kW or less), the external thermal relays can malfunction more easily because a leakage current can be too large as compared with the current rating of the motor.

A-12

Power

Inverter

IM

supply

 

 

A

Measures to be taken:

1.Use the electronic thermal function provided for the inverter.

Use parameter , to set the electronic thermal function.

2.Lower the PWM carrier frequency, though this results in an increase in motor magnetic noise. Use parameter to lower the PWM carrier frequency.

3.For improvement, connect film capacitors with capacitance of 0.1 to 0.5μF-1000V to the input and output terminals in each phase of the each thermal relay.

U/T1

 

V/T2

IM

W/T3

 

CT and ammeter

When a CT and an ammeter are installed externally to monitor the output current of the inverter, the ammeter could be burned by the high-frequency elements of a leakage current. For a model with relatively long cables (longer than 50 m) or a model for motors with small current ratings (several amperes), especially 400V model with a small capacity (3.7kW or less), the ammeter can be burned more easily by the high-frequency elements of a leakage current which flows into it through the external CT because a leakage current can be too large as compared with the current rating of the motor.

Measures to be taken:

1. For external meters, use the meter output terminals in the inverter's control circuit.

Output currents can also be output to the meter output terminals (AM). Use a 1 mAdc fullscale ammeter or a 7.5 Vdc-1 mA full-scale voltmeter.

2. Use the monitor function provided for the inverter.

Use the monitor function provided for the inverter to check the output current.

A-13

1.4.4 Notes on installation

Installation environment

The VF-A7 inverter is an electronic control device. Therefore, due consideration should be given to its installation environment.

Danger

-Do not put any inflammable material near the inverter, or it could catch a fire if the inverter sparks because of trouble.

Prohibited

-Use the inverter under environmental conditions specified by this instruction manual, or it could break down.

Mandatory

Warning

-Do not install the inverter in any place subject to vibration, or it could fall and cause injury to persons.

Prohibited

Make sure that the supply voltage is within +10%/-15% (within ±10% during continuous operation under full load) of the inverter's rated voltage specified on its

rating label.

Mandatory Supplying a voltage exceeding the above range could lead to a breakdown, an electric shock or a fire.

A-14

Avoid installing the inverter in a hot, damp, or dusty place, a place subject to freezing or water splash, or a place full of metal chips.

Do not install the inverter where there are gases that corrode metal or solvents that adversely affect plastic.

Use the inverter at ambient temperatures of -10 to 40 (-10 to 50 for models designed for 18.5kW motors or larger).

Measuring position

Measuring position

Note) The inverter produces heat. When installing it in a cabinet, consider its ventilating condition and internal space. When an inverter for 15kW motors or smaller is installed in a cabinet, it is advisable to peel off the label on the top of the inverter. Models for 18.5kW motors or larger can be used at ambient temperatures of up to 50 . (These models have no label on their top.)

Do not install the inverter in any place subject to vibration.

Note) If you intend to install it in a place subject to vibration, you should take measures to protect it from vibration. In such a case, contact your Toshiba dealer in advance.

If installing the inverter close to any of the following appliances or devices, take necessary measures to prevent them from malfunctioning.

Solenoid ... Connect a surge suppressor to the coil. Brake ... Connect a surge suppressor to the coil.

Magnetic contactor ... Connect a surge suppressor to the coil.

Fluorescent lamp ... Connect a surge suppressor to the coil. Resistor ... Move it away from the inverter.

Resistor

A-15

Installation

Danger

 

- Do not install or operate the inverter if it is damaged or any part is missing from it.

 

Operating the inverter in a defective condition could lead to a shock or a fire.

Prohibited

Request your Toshiba dealer for repair.

 

 

- Install the inverter on a non-combustible board, such as a steel plate. Installing it

 

on an inflammable wall or board could lead to a fire because its back is heated up

 

during operation.

Mandatory

- Do not use the inverter with the front cover detached, or it could cause a shock.

- Install an emergency shutdown device which matches the system (for example, a

 

 

switch interlocked with the brake of the machine). Failure to do so could lead to

 

injury to persons since it has no emergency stop function.

 

- Do not use any optional devices other than those designated by Toshiba. The use

 

of improper devices could lead to accidents.

Warning

-Install the main unit on a wall, or the like, which is strong enough to withstand its weight, or it could fall and cause injury to persons.

-Install a mechanical brake whenever the motor requires a brake (device which

Prohibited

retains the motor shaft). Failure to do so could lead to injury to persons because

the inverter itself has no function of mechanically retaining the brake shaft.

 

Installation place

Install the inverter vertically on a flat steel wall in a well-ventilated place. When installing two or more inverters, leave a clearance of at least 10 cm between inverters placed side by side.

above 10cm

above 5cm

above 5cm

above 10cm

The clearances indicated above are minimum clearances to be secured. Every air-cooling type model is equipped with a cooling fan. For this type of inverter, therefore, leave as large clearances as possible above and under the inverter.

For a model designed for 37kW motors or larger, leave a clearance of at least 20 cm above and under it for easy installation of wires and possible replacement of the fan.

Note) Do not install the inverter in a hot, damp, or dusty place, or a place full of metal chips. When you intend to install in a critical environment, consult your Toshiba dealer in advance.

A-16

Calorific values of inverters and amount of air to be ventilated

The VF-A7 series of inverter loses about 5% of energy when switching electric currents from AC, DC, then to AC. To limit a temperature rise due to this energy loss, it is necessary to forcefully ventilate and cool down the cabinet in which the inverter is installed.

The table below lists the amounts of air to be ventilated forcefully and the heat radiation areas required for closed-type cabinets containing an inverter.

Voltage

Applicable

Calorific value

Amount of air to be

Heat radiation area

required

motor

of inverter

ventilated forcefully

for closed-type

cabinet

class

(kW)

(W)

(m3/min.)

(m2)

 

 

 

 

0.4

50

0.29

1.0

 

 

0.75

70

0.40

1.4

 

 

1.5

110

0.63

2.2

 

 

2.2

140

0.80

2.8

 

 

3.7

220

1.3

4.4

 

 

5.5

310

1.8

6.2

 

 

7.5

420

2.4

8.4

 

200V

11

580

3.3

11.6

 

15

770

4.4

15.4

 

 

18.5

940

5.4

18.8

 

 

22

1110

6.3

22.2

 

 

30

1490

8.5

29.8

 

 

37

1530

8.7

30.6

 

 

45

1850

10.5

37.0

 

 

55

2250

12.8

45.0

 

 

75

3050

17.4

61.0

 

 

90

3650

20.8

73.0

 

 

0.75

70

0.40

1.4

 

 

1.5

110

0.63

2.2

 

 

2.2

140

0.80

2.8

 

 

3.7

220

1.3

4.4

 

 

5.5

280

1.6

5.6

 

 

7.5

370

2.1

7.4

 

 

11

530

3.0

10.6

 

 

15

710

4.0

14.2

 

 

18.5

800

4.6

16.0

 

400V

22

940

5.4

18.8

 

30

1270

7.2

25.4

 

 

37

1270

7.2

25.4

 

 

45

1490

8.5

29.8

 

 

55

1810

10.3

36.2

 

 

75

2300

13.1

46.0

 

 

90

2750

15.7

55.0

 

 

110

3350

19.1

67.0

 

 

132

4010

22.9

80.2

 

 

160

4850

27.6

97.0

 

 

220

6650

37.9

133.0

 

 

280

8450

48.2

169.0

 

Note)The calorific values in the above table do not include those of optional external devices (such as input reactors, DC reactors and radio noise filters).

A-17

Control panel designed in consideration of possible influences of noise

Inverters produce high-frequency noise. To avoid influences of noise, measures must be taken in designing a control panel. Here are some examples of measures against noise.

Separately install the wires of the main circuit and those of the control circuit. Do not install their wires in the same duct or in parallel with each other, and do not bind them together.

Use shielded wires or twisted wires for the control circuit.

Separate the input wires (on power supply side) of the main circuit from the output wires (on motor side). Do not install them in the same duct or in parallel with each other, and do not bind them together.

Be sure to ground the grounding terminal (G/E) of the inverter.

Be sure to connect a surge suppressor to every electromagnetic contactor and every relay installed near the inverter.

Install noise filters, as required.

Notes on the installation of two or more inverters in a single cabinet

When installing two or more inverters in a single cabinet, take the following precautions:

Leave a clearance of at least 10 cm between inverters placed side by side.

Leave a clearance of at least 20 cm between inverters placed one above another.

Install a deflector, etc., to prevent the upper inverter from being affected by heat produced and being exhausted by the lower one.

Inverter

Cooling fun

Deflector

Inverter

Installation of Cooling fun

A-18

Heat-sink going out attachment(simple type)

To install a standard VF-A7 designed for 37kW motor or larger, you can choose a one from next two forms.

(1)Normal attachment (Whole the inverter is in the cabinet)

(2)Heat-sink going out (the cabinet) attachment(simple type)

Heat-sink going out attachment reduces the generation of heat inside the cabinet. When you carry out heat-sink going out attachment, please change the position of the attachment ornaments (hanging hole) of the inverter according to the following figure.

(1) Normal attachment

(2) Heat-sink going out attachment

 

(simple type)

Take this ornament

Take this ornament

off (*1)

off (*1)

Change the position

Change the position

Change the position

Change the position

(*1) Metallic ornaments with the hanging hole are attached only in the following models.

200V class: Applicable motor capacity is 75kW or larger

400V class: Applicable motor capacity is 110kW or larger

A-19

2. Connection

Danger

Never disassemble, modify or repair the inverter. Its disassembly could cause an

electric shock, a fire or an injury. Request your Toshiba dealer for repair.

Disassemble

Do not put or insert anything (e.g., an electric cable, a bar or a steel wire) into the inverter, or the inverter could cause a shock or a fire.

Prohibited Do not splash water over the inverter, or the inverter could cause a shock or a fire.

Warning

Do not hold the front cover to carry the inverter, or the cover could come off and

cause the main unit to fall, thus causing you to get an injury.

Prohibited

For models designed for 30kW motor or larger, carry it at least in a twosome, or it

could fall and cause you to get an injury.

Mandatory

2.1 Cautions as to wiring

Danger

 

Never open the front cover of the inverter (or the door of the cabinet in which the

 

inverter is installed) when the inverter is energized, or you could get a shock since a

Prohibited

high voltage is applied to certain portions of it.

 

Do not turn on the power before attaching the front cover (or closing the door of the cabinet if the inverter is installed in it). Turning on the power with the cover or the

door left opened could lead to an electric shock.

Mandatory Entrust all electrical work to an experienced specialist. Wiring by an inexperienced person could result in a fire or an electric shock.

Connect the output terminals (on the motor side) correctly. connection of the terminals causes the motor to rotate in a wrong direction, and thus could result in injury to persons.

Perform wiring always after installing the inverter, or you could get a shock or an injury.

Be sure to perform the following preparatory work before proceeding to wiring.

(1)Turn off the power.

(2)Wait more than 10 minutes, and make sure that the charge lamp is extinct.

(3)Using a circuit tester with a D.C. voltage measuring capacity of more than 800 V, check to be sure that the voltage remaining in the D.C. main circuit (between PA and PC) is below 45 V to do so could lead to an electric shock.

Tighten the terminal board fixing screws at the specified torque. Failure to do so could lead to a fire.

Connect grounding wires correctly and securely. Failure to do so could cause an electric shock or a fire if current leakage occurs or the inverter breaks down.

Be Grounded

B-1

 

 

 

Warning

 

 

Do not connect any device or unit with a built-in capacitor (noise filter, surge

 

 

suppressor, etc.) to output terminals (on the motor side), or it could cause the risk of

 

Prohibited

a fire.

 

Prevention of radio noise

Prevent interference, such as radio noise, separately install and bind cables connected to the power supply-side terminals (R/L1, S/L2 and T/L3) of the main circuit and those connected to the motor-side terminals (U/T1, V/T2 andW/T3).

Power supply to the control and main circuits (for the 22kW and smaller models)

You want to keep the control circuit alive when the main circuit shuts off because of trouble or tripping, you can use an optional power supply unit to supply power to the control circuit separately from the main circuit.

Notes on wiring

When connecting wires to the main circuit terminals, use crimp contacts because there is no large space between terminals, and attach them in order so that they do not come into contact with each other.

Be sure to ground the inverter by connecting wires of the following size or larger to the grounding terminal G/E.(UL standard)

 

 

Voltage

 

Applicable motor

 

Grounding wire size

 

 

 

class

 

 

AWG(cross-section[mm2])

 

 

 

 

 

 

 

 

 

 

 

0.4 5.5kW

 

12(3.5)

 

 

 

 

 

7.5kW

 

10(5.5)

 

 

 

 

 

11 15kW

 

6(14)

 

 

 

200V

 

18.5 22kW

 

4(22)

 

 

 

 

 

30 37kW

 

2(38)

 

 

 

 

 

45 55kW

 

2/0(60)

 

 

 

 

 

75 90kW

 

4/0(100)

 

 

 

 

 

0.75 11kW

 

12(3.5)

 

 

 

 

 

15kW

 

10(5.5)

 

 

 

 

 

18.5kW

 

8(8)

 

 

 

 

 

22 30kW

 

6(14)

 

 

 

400V

 

37 55kW

 

4(22)

 

 

 

 

 

75kW

 

2(38)

 

 

 

 

 

110 132kW

 

2/0(60)

 

 

 

 

 

160 220kW

 

4/0(100)

 

 

 

 

 

280kW

 

300(150)

 

 

 

 

 

Refer to the

table in 9.1 for wire

sizes.

For the 200V 0.4~7.5kW models and the 400V 0.75~7.5kW models, a grounding screw (M5) is provided in the wiring hole cover, in addition to a grounding terminal.

Wire sizes listed in 9.1 is for the case the wire length is below 30m. To use wires longer than 30m, you need larger cables than listed in 9.1.

Tighten a terminal stand screw with specified bolting torque.

Recommended bolting torque for terminal stand

 

 

N m

lb ins

 

 

M3

0.5

4.4

 

 

M4

1.2

11

 

 

M5

2.4

21

 

 

M6

4.0

35

 

 

M8

8.0

71

 

 

M10

16

142

 

 

M12

32

283

 

 

 

 

 

 

 

 

B-2

 

 

2.2 Standard connection

 

 

Danger

 

 

-Do not connect the power cables to any output terminal (U/T1, V/T2 or W/T3 on the

 

 

motor side), or the inverter could break down and cause a fire.

 

Prohibited

-Do not connect a resistor to any D.C. terminal (between PA and PC or PO and PC), or

 

the inverter could cause a fire.

 

 

 

To install external braking resistor, refer to 6.13.4.

 

 

-Connect grounding wires correctly and securely. Failure to do so could cause an

 

 

electric shock or a fire if current leakage occurs or the inverter breaks down.

 

Be Grounded

 

 

 

[Standard connection diagram for sink logic(minus common)]

200V class: 0.4 22kW

 

 

400V class: 0.75 22kW

* External braking resistor Refer to 6.13.4 for details

 

DC reactor (DCL)

When using an external braking resistor in 3.7kW

 

model or less, change the connection of the internal

 

*2 (Optional)

 

resistor from terminal PB1 to terminal PR1.

Main circuit power supply

200V

class 0.4 7.5kW

 

 

 

 

 

 

This circuit is provided

3-phase 200 230V-50/60Hz

 

 

 

 

 

 

200V

class 11 22kW

PO

PA

PB

PC

(PA1)(PB1)

 

only for the 3.7kW and

3-phase 200 220V-50Hz

(PR1)

smaller models.

3-phase 200 230V-60Hz

 

 

 

 

 

 

 

400V

class 0.75 22kW

 

 

 

 

 

 

 

3-phase 380 460V-50/60Hz

 

 

 

 

 

 

 

 

MCCB

R/L1

 

 

Built-in dynamic

braking resistor

Motor

 

 

 

 

 

U/T1

 

 

 

 

 

 

 

 

 

 

 

S/L2

 

Main circuit

V/T2

IM

 

 

 

T/L3

 

W/T3

 

 

 

 

 

 

 

 

*When using a separate power source

 

R0

Control

 

 

F

Forward

 

for the control

circuit

 

CN21

 

 

 

For the 22kW and smaller models,

 

circuit

 

 

 

 

 

 

S0

 

 

R

Reverse

 

power is supplied to the control circuit

 

 

 

 

 

from the main circuit. An optional device

FLA

 

 

 

 

 

 

is required to

CN21

 

 

 

 

ST

Standby

 

supply from

 

FLB

 

 

 

 

 

 

 

 

 

 

another source.

 

 

 

 

RES

Reset

 

(though

Control circuit

 

 

FL

 

Factory

terminals only

Option

 

FLC

 

 

 

are provided.)

 

 

 

 

S1

Preset

default

 

 

 

 

 

*1: The control

power supply terminals

 

 

 

Control panel

 

speed 1

settings

 

 

 

 

Preset

 

P24

 

S2

 

RO and SO are optionally

 

 

 

 

speed 2

 

 

 

 

 

 

 

 

available for the 22kW and

Ry

OUT1

 

Connector for

 

S3

Preset

 

smaller models. Though terminals

 

common serial

 

 

RO and SO are fitted as

 

 

 

communication

SINK

 

speed 3

 

 

 

 

 

Preset

 

 

OUT2

 

RS485 connector

S4

 

standard for the 22kW and

Ry

 

 

 

smaller models as well, they

 

 

 

for serial

SOURCE

speed 4

 

 

G/E

 

communication

 

 

are not connected internally.

 

 

 

CC

Common

 

 

 

 

 

 

 

*2: The inverter is shipped with

 

 

 

 

 

 

 

 

the terminals PO and PA

FP FM AM CC

RX

VI

RR

PP

 

Current signal

shorted with a bar. Remove

4 to 20mA

this shorting bar when installing

 

 

 

 

 

 

 

a DC reactor (DCL).

 

 

 

 

Voltage signal -10 +10V

Digital

Frequency

Ammeter

 

 

voltmeter

meter

 

 

Voltage signal 0 10V

 

 

 

 

 

 

 

 

 

External potentiometer

 

 

Voltmeter or ammeter

 

 

(or voltage signal between RR and CC: 0 10V)

B-3

Loading...
+ 220 hidden pages