Toshiba MMU-AP0091H, MMC-AP0151H, MMD-AP0961H, MMU-AP0121H, MMU-AP0151H DESIGN MANUAL

...
0 (0)

FILE NO. A04-017

DESIGN MANUAL

R410A

Heat Recovery Type

Indoor Unit

<4-way Air Discharge Cassette Type>

MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H

<2-way Air Discharge Cassette Type>

MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH, AP0481WH*

* CHINA market only

<1-way Air Discharge Cassette Type>

MMU-AP0071YH, AP0091YH, AP0121YH, MMU-AP0151SH, AP0181SH, AP0241SH

<Concealed Duct Standard Type>

MMD-AP0071BH, AP0091BH, AP0121BH, MMD-AP0151BH, AP0181BH, AP0241BH, MMD-AP0271BH, AP0301BH, AP0361BH, MMD-AP0481BH, AP0561BH

<Concealed Duct High Static Pressure Type>

MMD-AP0181H, AP0241H, AP0271H, MMD-AP0361H, AP0481H, AP0721H, MMD-AP0961H

<Under Ceiling Type>

MMC-AP0151H, AP0181H, AP0241H, MMC-AP0271H, AP0361H, AP0481H

<High Wall Type>

MMK-AP0071H, AP0091H, AP0121H, MMK-AP0151H, AP0181H, AP0241H, MMK-AP0072H*, AP0092H*, AP0122H*

* European market only

<Floor Standing Cabinet Type>

MML-AP0071H, AP0091H, AP0121H, MML-AP0151H, AP0181H, AP0241H

<Floor Standing Concealed Type>

MML-AP0071BH, AP0091BH, AP0121BH, MML-AP0151BH, AP0181BH, AP0241BH

<Floor Standing Type>

(2 Series)

Outdoor Unit

<Inverter Unit>

MMY-MAP0802FT8 MMY-MAP1002FT8 MMY-MAP1202FT8

FS unit

RBM-Y1122FE

RBM-Y1802FE

RBM-Y2802FE

MMF-AP0151H, AP0181H, AP0241H MMF-AP0271H, AP0361H, AP0481H MMF-AP0561H

PRINTED IN JAPAN, 2005

CONTENTS

DESIGN MANUAL ..................................................................

3

1.OUTLINE OF TOSHIBA SUPER HRM

 

(Super Heat Recovery Multi System) .................................................

3

2.

SUMMARY OF SYSTEM EQUIPMENTS ..............................................

6

3.

BASIC SYSTEM CONFIGURATION ...................................................

11

4.

EQUIPMENT SELECTION PROCEDURE ..........................................

16

5.

REFRIGERANT PIPING DESIGN .......................................................

25

6.

WIRING DESIGN .................................................................................

30

7.

CONTROLS .........................................................................................

35

8.

ACCESSORIES ...................................................................................

41

9.

TECHNICAL SPECIFICATIONS..........................................................

44

10.

FAN CHARACTERISTICS ..................................................................

59

11.

DIMENSIONAL DRAWINGS ...............................................................

62

DESIGN MANUAL

1.OUTLINE OF TOSHIBA SUPER HRM (Super Heat Recovery Multi System)

Shortest route design by free branching

Combination of line and header branching is highly flexible.

This follows for the shortest design route possible, thereby saving on installation time and cost. Line/header branching after header branching is only available with TOSHIBA Super HRM.

Line branching

Outdoor unit

Branching joint

8F

FS unit

Indoor unit

Header branching

Outdoor unit

Branching

7F

header

FS unit

Indoor unit

Line + Header branching

Outdoor unit

 

Header

2F

 

 

 

 

 

FS

 

 

 

unit

Branching joint

Indoor

 

 

unit

 

 

 

 

 

Line branching after header branching

1F

Outdoor unit

 

 

 

 

 

 

Header

Branching joint

 

Super HRM

 

 

 

MMS Only

 

 

 

Only

FS unit

 

Indoor unit

 

Header branching after header branching

Outdoor unit

Header

Super HRM

Only

Header

FS unit

Indoor unit

3

Toshiba MMU-AP0091H, MMC-AP0151H, MMD-AP0961H, MMU-AP0121H, MMU-AP0151H DESIGN MANUAL

8F

7F

2F

1F

• Non-polarized control wiring between outdoor and indoor units

Outdoor unit

U1 U2

 

 

Indoor unit

U1 U2

U1 U2

U1 U2

Sub heat exchanger

main heat exchanger

Outdoor unit

 

FS unit

 

 

 

 

Indoor

 

 

 

 

unit

 

 

 

Compressor

Heating

Cooling

Cooling

Cooling

 

• Simultaneous operation

Allowable pipe length :

150m equivalent length

Outdoor unit

differenceHeightbetween indoor outdoorandunitunit : 50m

differenceHeightbetween indoor unitindoorandunit: 35m

 

1st branching

 

section

From 1st branching to the farthest indoor unit : 50m

4

Energy saving

No. 1 COP in heat recovery VRF industry. Compared with the conventional chiller fan coil system, a large energy saving can be realized.

Advanced bus communication system

Wiring between indoor and outdoor unit is a simple 2 wire system.

Communication address is also automatically configured.

A default test mode operation is available.

Self diagnostics system

Comprehensive troubleshooting code allows for timely identification of problems arising.

High lift and flexible piping design

Equivalent pipe length of 150m and vertical lift of 50m is made possible with TOSHIBA Super HRM. Vertical lift between indoor units of 35m is the highest in the industry.

Also, maximum piping length from 1st branching is 50m. These allow for greater flexibility in the location of the system.

Simultaneous operation

By controling the FS unit, Super HRM enables freely simultaneous operation of cooling and heating. This operation meets the various needs of modern buildings that has highly airtight or an increasing heat load due to use of computers. Also, Super HRM improves energy efficiency by recycling exhaust heat.

Extended outdoor temperature operating range

By employing sophisticated system control with all inverter driven compressor, the operating range in cooling has been extended from -5ºC to -10ºC.

Compact FS unit design

The compact and light weight design of the FS unit (Flow selector unit) allows it to be easily installed in limited spaces.

Group control by one FS unit

Up to 8 indoor units of group control by one FS unit gives the design flexibility for various type and size of rooms.

Intelligent control

TOSHIBA Super HRM intelligent controls and modulating valves deliver the required capacity, according to the load variation from 50% to 100%.

The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so humidity and temperature are kept in the comfort zone.

Conforms to building control law

IAQ (Indoor Air Quality) is also achieved by combining various accessories required by the Building Control Law.

Wide control applications

Artificial Intelligence Network system

Central control and monitoring system available

Weekly schedule operation through weekly timer

Integration with Building Management System (BMS) is available.

5

2. SUMMARY OF SYSTEM EQUIPMENTS

Equipments

1. Outdoor units

Inverter unit

Corresponding HP

 

 

Appearance

 

 

8HP

10HP

12HP

Model name

MMY-

MAP0802FT8

MAP1002FT8

MAP1202FT8

Cooling capacity (kW)

 

22.4

28.0

33.5

Heating capacity (kW)

 

25.0

31.5

35.5

2. Outdoor units (Combination of outdoor units)

Corresponding HP

8HP

10HP

12HP

16HP

18HP

Combined model

MMY-

MAP0802FT8

MAP1002FT8

MAP1202FT8

AP1602FT8

AP1802FT8

 

 

 

 

 

 

 

Cooling capacity (kW)

 

22.4

28

33.5

45

50.4

Heating capacity (kW)

 

25

31.5

35.5

50

56.5

 

 

8HP

10HP

12HP

8HP

10HP

Combined outdoor units

 

 

 

 

8HP

8HP

 

 

 

 

 

 

 

No. of connectable indoor units

13

16

16

27

30

Corresponding HP

20HP

24HP

26HP

28HP

30HP

Combined model

MMY-

AP2002FT8

AP2402FT8

AP2602FT8

AP2802FT8

AP3002FT8

 

 

 

 

 

 

 

Cooling capacity (kW)

 

56

68

73

78.5

84

Heating capacity (kW)

 

63

76.5

81.5

88

95

 

 

10HP

8HP

10HP

10HP

10HP

Combined outdoor units

 

10HP

8HP

8HP

10HP

10HP

 

 

 

8HP

8HP

8HP

10HP

No. of connectable indoor units

33

40

43

47

48

3. FS units (Flow selector units)

Model name

Usage

 

Appearance

 

 

 

 

RBM-Y1122FE

Total capacity for indoor unit :

Below 11.2 kw

 

 

 

 

 

RBM-Y1802FE

Total capacity for indoor unit :

11.2 to below 18.0 kw

 

 

 

 

 

RBM-Y2802FE

Total capacity for indoor unit :

18.0 to 28.0 kw or less

 

 

 

 

 

* Accessory part (Sold separately): Connection cable kit (RBC-CBK15FE), up to 15m.

4. Branching joints and headers

 

Model name

 

 

Usage

 

 

 

 

Appearance

 

 

 

 

 

 

 

 

 

 

 

RBM-BY53FE

Indoor unit capacity code (*1) : Total below 6.4

 

 

 

 

 

 

RBM-BY103FE

Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2

 

 

For 3

 

Y-shape

RBM-BY203FE

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

 

piping

 

RBM-BY303FE

Indoor unit capacity code (*1) : Total 25.2 or more

 

 

 

 

 

branching

 

 

 

 

 

RBM-BY53E

Indoor unit capacity code (*1) : Total below 6.4

 

 

 

 

 

joint (*3)

 

 

 

 

 

RBM-BY103E

Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2

 

 

For 2

 

 

 

 

 

 

RBM-BY203E

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

piping (*6)

 

 

RBM-BY303E

Indoor unit capacity code (*1) : Total 25.2 or more

 

 

 

 

 

4-branching

RBM-HY1043FE

Indoor unit capacity code (*1) : Total below 14.2

 

 

 

For 3

 

RBM-HY2043FE

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

 

piping

 

header (*4) (*5)

RBM-HY1043E

Indoor unit capacity code (*1) : Total below 14.2

 

 

 

For 2

 

 

RBM-HY2043E

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

piping (*6)

 

8-branching

RBM-HY1083FE

Indoor unit capacity code (*1) : Total below 14.2

 

 

 

For 3

 

RBM-HY2083FE

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

 

piping

 

header (*4) (*5)

RBM-HY1083E

Indoor unit capacity code (*1) : Total below 14.2

 

 

 

For 2

 

 

RBM-HY2083E

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

piping (*6)

 

 

 

1 set 4 types T-shape joint pipes as described below:

 

 

 

 

 

T-shape

 

The required quantity is arranged and they are combined on site.

 

 

 

 

 

 

 

 

 

 

 

 

branching

 

 

Connection piping

Corresponded dia. (mm)

Q'ty

 

 

 

joint (For

 

 

 

 

 

 

 

 

 

RBM-BT13FE

 

Balance pipe

Ø 9.5

1

 

 

 

 

connection

 

 

 

 

 

 

 

Piping at liquid side

Ø12.7 to Ø22.2

1

 

 

 

 

of outdoor

 

 

 

 

 

 

 

 

Piping at discharge gas side

Ø19.1 to Ø28.6

1

 

 

 

 

units)

 

 

 

 

 

 

 

 

Piping at suction gas side

Ø22.2 to Ø38.1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1 Capacity codecan be obtained from page 8. (Capacity code is not actual capacity)

*2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit. *3 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit. *4 Max. 6.0 capacity code in total can be connected.

*5 If capacity code of outdoor unit is 26 or more, it is not used for 1st branching. *6 This is used for branching to cooling onlyindoor unit.

*7 Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.

6

50Hz

Super Heat Recovery Multi System Outdoor Unit

HP (Capacity

Model name

No. of

Inverter

Used

Inverter

Used

Inverter

Used

combined

8 HP

10 HP

12 HP

code)

MMY-

Q'ty

Q'ty

Q'ty

units

MMY-

MMY-

MMY-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8HP ( 8)

MAP0802HT8

1

MAP0802FT8

1

 

 

 

 

 

 

 

 

 

 

 

 

 

10HP (10)

MAP1002HT8

1

 

 

MAP1002FT8

1

 

 

 

 

 

 

 

 

 

 

 

12HP (12)

MAP1202HT8

1

 

 

 

 

MAP1202FT8*

1

 

 

 

 

 

 

 

 

 

16HP (16)

 

2

MAP0802FT8

2

 

 

 

 

 

 

 

 

 

 

 

 

 

18HP (18)

 

2

MAP0802FT8

1

MAP1002FT8

1

 

 

 

 

 

 

 

 

 

 

 

20HP (20)

 

2

 

 

MAP1002FT8

2

 

 

 

 

 

 

 

 

 

 

 

24HP (24)

 

 

MAP0802FT8

3

 

 

 

 

 

 

 

 

 

 

 

 

 

26HP (26)

 

 

MAP0802FT8

2

MAP1002FT8

1

 

 

 

 

 

 

 

 

 

 

 

28HP (28)

 

 

MAP0802FT8

1

MAP1002FT8

2

 

 

 

 

 

 

 

 

 

 

 

30HP (30)

 

 

 

 

MAP1002FT8

3

 

 

 

 

 

 

 

 

 

 

 

*12HP unit is for stand-alone usage only.

Outdoor unit combination with 12HP unit is not available.

1.Allocation standard of model name

MMY– M AP

F T 8

Power supply specifications, 3Ø 380–415 V, 50Hz .......

8

T : Capacity variable unit

 

F : Heat recovery

Development series No.

Capacity rank HP x 10

New refrigerant R410A

M : Single module unit, No mark : Combined Model name

Modular Multi

2. Rated conditions (Rated mode : Condition)

Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

3. Compatibility with 1 Series

Oudoor unit

MMY-

1 Series

2 Series*

-MAP**1FT8

-MAP**2FT8

1 Series

NG

OK

RBM-Y***1E

 

FS unit

2 Series

OK

OK

RBM-Y***2E

* 2 series outdoor units cannot be used with 1 series outdoor units.

7

4. Indoor unit

*1) China only

*2) European market only

Type

Appearance

Model name

Capacity rank

Capacity code

Cooling

Heating

capacity (kW)

capacity (kW)

 

 

MMU-AP0091H

009 type

1

2.8

3.2

 

 

MMU-AP0121H

012 type

1.25

3.6

4.0

 

 

MMU-AP0151H

015 type

1.7

4.5

 

 

 

5.0

4-way Air Discharge

 

MMU-AP0181H

018 type

2

5.6

6.3

 

MMU-AP0241H

024 type

2.5

7.1

8.0

Cassette Type

 

MMU-AP0271H

027 type

3

8.0

9.0

 

 

MMU-AP0301H

030 type

3.2

9.0

10.0

 

 

MMU-AP0361H

036 type

4

11.2

12.5

 

 

MMU-AP0481H

048 type

5

14.0

16.0

 

 

MMU-AP0561H

056 type

6

16.0

18.0

 

 

MMU-AP0071WH

007 type

0.8

2.2

2.5

 

 

MMU-AP0091WH

009 type

1

2.8

3.2

 

 

MMU-AP0121WH

012 type

1.25

3.6

4.0

2-way Air Discharge

 

MMU-AP0151WH

015 type

1.7

4.5

5.0

 

MMU-AP0181WH

018 type

2

5.6

6.3

Cassette Type

 

 

MMU-AP0241WH

024 type

2.5

7.1

8.0

 

 

 

 

MMU-AP0271WH

027 type

3

8.0

 

 

 

9.0

 

 

MMU-AP0301WH

030 type

3.2

9.0

10.0

 

 

MMU-AP0481WH*1)

048 type

5

14.0

16.0

 

 

MMU-AP0071YH

007 type

0.8

2.2

2.5

1-way Air Discharge

 

MMU-AP0091YH

009 type

1

2.8

3.2

 

MMU-AP0121YH

012 type

1.25

3.6

4.0

Cassette Type

 

MMU-AP0151SH

015 type

1.7

4.5

5.0

 

 

MMU-AP0181SH

018 type

2

5.6

6.3

 

 

MMU-AP0241SH

024 type

2.5

7.1

8.0

 

 

MMD-AP0071BH

007 type

0.8

2.2

2.5

 

 

MMD-AP0091BH

009 type

1

2.8

3.2

 

 

MMD-AP0121BH

012 type

1.25

3.6

 

 

 

4.0

 

 

MMD-AP0151BH

015 type

1.7

4.5

 

 

 

5.0

Concealed Duct

 

MMD-AP0181BH

018 type

2

5.6

6.3

 

MMD-AP0241BH

024 type

2.5

7.1

8.0

Standard Type

 

 

MMD-AP0271BH

027 type

3

8.0

9.0

 

 

 

 

MMD-AP0301BH

030 type

3.2

9.0

10.0

 

 

MMD-AP0361BH

036 type

4

11.2

12.5

 

 

MMD-AP0481BH

048 type

5

14.0

 

 

 

16.0

 

 

MMD-AP0561BH

056 type

6

16.0

 

 

 

18.0

 

 

MMD-AP0181H

018 type

2

5.6

6.3

 

 

MMD-AP0241H

024 type

2.5

7.1

8.0

Concealed Duct

 

MMD-AP0271H

027 type

3

8.0

9.0

High Static

 

MMD-AP0361H

036 type

4

11.2

12.5

Pressure Type

 

MMD-AP0481H

048 type

5

14.0

16.0

 

 

MMD-AP0721H

072 type

8

22.4

 

 

 

25.0

 

 

MMD-AP0961H

096 type

10

28.0

 

 

 

31.5

 

 

MMC-AP0151H

015 type

1.7

4.5

5.0

 

 

MMC-AP0181H

018 type

2

5.6

6.3

Under Ceiling Type

 

MMC-AP0241H

024 type

2.5

7.1

8.0

 

MMC-AP0271H

027 type

3

8.0

9.0

 

 

 

 

MMC-AP0361H

036 type

4

11.2

12.5

 

 

MMC-AP0481H

048 type

5

14.0

16.0

 

 

MMK-AP0071H

007 type

0.8

2.2

 

 

 

2.5

High Wall Type

 

MMK-AP0091H

009 type

1

2.8

3.2

 

MMK-AP0121H

012 type

1.25

3.6

4.0

(1 Series)

 

MMK-AP0151H

015 type

1.7

4.5

5.0

 

 

MMK-AP0181H

018 type

2

5.6

6.3

 

 

MMK-AP0241H

024 type

2.5

7.1

8.0

High Wall Type

 

MMK-AP0072H

007 type

0.8

2.2

2.5

 

MMK-AP0092H

009 type

1.0

2.8

3.2

(2 Series) *2)

 

 

MMK-AP0122H

012 type

1.25

3.6

4.0

 

 

 

 

MML-AP0071H

007 type

0.8

2.2

 

 

 

2.5

Floor Standing

 

MML-AP0091H

009 type

1

2.8

3.2

 

MML-AP0121H

012 type

1.25

3.6

4.0

Cabinet Type

 

MML-AP0151H

015 type

1.7

4.5

 

 

5.0

 

 

MML-AP0181H

018 type

2

5.6

 

 

 

6.3

 

 

MML-AP0241H

024 type

2.5

7.1

8.0

 

 

MML-AP0071BH

007 type

0.8

2.2

2.5

 

 

MML-AP0091BH

009 type

1

2.8

 

Floor Standing

 

3.2

 

MML-AP0121BH

012 type

1.25

3.6

4.0

Concealed Type

 

MML-AP0151BH

015 type

1.7

4.5

5.0

 

 

MML-AP0181BH

018 type

2

5.6

6.3

 

 

MML-AP0241BH

024 type

2.5

7.1

8.0

 

 

MMF-AP0151H

015 type

1.7

4.5

5.0

 

 

MMF-AP0181H

018 type

2

5.6

6.3

Floor Standing Type

 

MMF-AP0241H

024 type

2.5

7.1

8.0

 

MMF-AP0271H

027 type

3

8.0

9.0

 

 

MMF-AP0361H

036 type

4

11.2

12.5

 

 

MMF-AP0481H

048 type

5

14.0

 

 

 

16.0

 

 

MMF-AP0561H

056 type

6

16.0

18.0

8

5. Remote controller

Model Name name

Wired remote controller

RBC-AMT21E

Simple remote controller

RBC-AS21E

Wireless remote controller kit

TCB-AX21U (W)-E

RBC-AX22CE

AX21E

 

TCB-

Appearance

Application

 

Function

 

 

Connected to indoor unit

Start / Stop

 

 

Changing mode

 

 

 

Temperature setting

 

 

 

Air flow changing

 

 

 

Timer function

 

 

 

 

Either “ON” time or “OFF” time or “CY-

 

 

 

 

CLIC” can be set how many 30 min. later

 

CODE No.

 

 

ON or OFF is operated.

 

 

 

Combined with the weekly timer, weekly

SET DATA

UNIT No.

 

 

SETTINGTEST

R.C. No.

 

 

schedule operation can be operated.

 

 

 

Filter sign

 

 

 

 

Displays automatically maintenance time of

 

 

 

 

indoor filter.

 

UNIT

Wired remote Wired remote controller

 

Filter sign flashes.

 

 

Self-diagnosis function

SET CL

 

controller (In case of control by

 

 

2 remote controllers)

 

Pressing “CHECK” button displays cause of

 

 

 

 

trouble on the check code.

 

 

 

Control by 2 remote controllers is available.

 

 

 

 

Two remote controllers can be connected to

 

 

 

 

one indoor unit. The indoor unit can be

 

 

 

 

separately operated from the isolated places.

 

 

Connected to indoor unit

Start / Stop

 

 

Temperature setting

 

 

 

Air flow changing

 

 

 

Check code display

TEST

˚C

 

 

 

SETTING

˚F

 

 

 

Simple remote controller

• Start / Stop

• Changing mode

• Temperature setting

• Air flow changing

• Timer function

Either “ON” time or “OFF” time or “CYCLIC” Connected to indoor unit can be set how many 30 min. later ON or OFF

is operated.

• Control by 2 remote controllers is available.

Two wireless remote controllers can operate one indoor unit. The indoor unit can be separately operated from the isolated places.

• Check code display

TCB-AX21U (W)-E

(For 4-way air discharge cassette)

RBC-AX22CE

(For under ceiling)

TCB-AX21E

(For others except concealed duct high static pressure)

9

Model Name name

Weekly timer

RBC-EXW21E

Central remote controller

TCB-SC642TLE

 

Appearance

Application

 

 

Performance

 

 

 

 

 

 

 

Weekly schedule operation

 

 

 

 

 

Connected to central

 

Setting different start / stop time for

 

 

 

remote controller,

 

 

 

 

 

each day of the week

 

 

 

 

 

wired remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON / OFF can be easily set 3 times

 

 

 

 

 

 

 

a day.

 

 

 

 

 

 

 

 

 

 

ON

OFF ON

OFF ON

OFF

 

 

 

 

 

 

8:00

12:00

13:00

18:00

19:00

21:00

 

 

 

Wired

 

Weekly

 

“CHECK” “PROGRAM” “DAY”

 

 

 

 

 

button make setting copy easy.

 

 

 

remote controller

 

timer

 

 

 

SuMoTuWeTh Fr Sa

 

 

 

 

 

 

 

 

 

 

 

 

 

Two patterns of schedule for a

PROGRAM1

 

 

 

 

 

 

PROGRAM2

 

ERROR

 

 

 

 

week can be specified.

 

 

 

 

 

 

 

 

 

 

PROGRAM3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Summer schedule and winter

 

 

 

 

 

 

 

WEEKLY TIMER

 

 

 

 

 

schedule, etc.)

 

 

 

 

 

 

 

Outdoor unit

 

“CANCEL” “DAY” button make

 

 

 

 

 

 

 

 

 

 

 

 

 

 

holiday setting easy.

 

 

 

 

 

 

 

 

 

If power supply fails, the setting

 

 

 

 

 

 

 

contents are stored in memory, for

 

 

 

 

 

 

 

100 hours.

 

 

 

 

 

 

 

Central

 

Weekly

 

 

 

 

 

 

 

 

 

remote controller

 

timer

 

 

 

 

 

 

 

 

 

 

 

Individual control up to 64 indoor units.

 

 

 

Connected to outdoor unit,

 

 

 

 

 

 

 

 

 

indoor unit

Individual control for max. 64 indoor

 

 

 

 

 

 

units divided 1 to 4 zone.

 

 

 

 

 

Outdoor

 

 

Up to 16 indoor units for each

 

 

 

unit

 

 

zone

 

 

 

 

 

 

 

 

 

Up to 16 outdoor header units are

 

 

 

 

 

 

connectable.

 

 

 

 

 

 

 

 

 

4 type central control setting to inhibit

 

 

 

 

 

 

individual operation by remote

 

ALL ZONE

 

 

 

 

controller can be selected.

 

 

 

 

 

 

 

 

 

 

 

 

ZONE

 

 

 

 

 

 

 

 

 

 

 

GROUP

 

No.

 

 

Setting for one of 1 to 4 zone is

 

 

 

CODE

 

 

 

 

 

 

 

 

 

1234

UNIT No.

TEST

 

 

 

available.

 

 

 

 

SET DATA

 

 

 

 

 

 

 

 

 

 

 

SETTING R.C.

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Usable with other central control

 

 

 

 

 

 

 

devices (Up to 10 central control

 

 

 

GROUP

 

 

 

devices in one control circuit)

 

SELECT

ZONE

Central

 

 

 

 

 

 

 

 

 

 

 

 

Two control mode selectivity

 

 

 

 

remote controller

 

 

CL SET

 

 

 

Central controller mode

 

 

 

 

 

Remote controller mode

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting of simultaneous ON/OFF 3

 

 

 

 

 

 

times for each day of the week

 

 

 

 

 

 

 

combined with weekly timer.

 

 

 

 

Central

 

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

 

 

 

 

 

 

 

 

controller

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote controller

 

 

 

 

 

 

10

3. BASIC SYSTEM CONFIGURATION

8HP system

 

 

Capacity code

• Max. indoor unit : 13 units

 

 

 

 

 

Total 10.4

• Capacity code of indoor unit :

Min. : 5.6

 

 

No. of total units

 

 

Max. : 10.8

 

 

 

13

 

 

 

 

Outdoor unit

8HP

Capacity code over the branch (0.8 + 0.8 = 1.6)

Indoor unit designation

10.4

4.8

4.0

3.2

2.4

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

007

007

007

007

007

(0.8)

(0.8)

(0.8)

(0.8)

(0.8)

 

 

 

 

 

 

 

 

 

 

Capacity

code

007

(0.8)

 

5.6

4.8

4.0

FS unit

 

 

 

Indoor unit

007

007

007

Remote

(0.8)

(0.8)

(0.8)

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

3.22.4

007

007

(0.8) (0.8)

1.60.8

007

007

(0.8) (0.8)

11

10 HP system

 

 

Capacity code

• Max. indoor unit : 16 units

 

 

Total 12.8

• Capacity code of indoor unit :

Min. : 7

 

 

 

 

Max. : 13.5

No. of total units

 

 

 

 

 

16

 

 

 

 

Outdoor unit

10HP

12.8

6.4

5.6

4.8

4.0

3.2

2.4

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

007

007

(0.8)

(0.8)

007

007

(0.8)

(0.8)

007

007

(0.8)

(0.8)

007

007

(0.8)

(0.8)

 

6.4

5.6

4.8

FS unit

 

 

 

Indoor unit

007

007

007

Remote

(0.8)

(0.8)

(0.8)

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

4.0 3.2 2.4

007

007

007

(0.8) (0.8) (0.8)

1.6

 

007

007

(0.8)

(0.8)

12

12 HP system

 

 

Capacity code

• Max. indoor unit : 16 units

 

 

Total 14.0

• Capacity code of indoor unit :

Min. : 8.4

 

 

 

 

Max. : 14.4

No. of total units

 

 

 

 

 

16

 

 

 

 

Outdoor unit

12HP

14.0

6.4

5.6

4.8

4.0

3.2

2.4

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

007

007

(0.8) (0.8)

007

007

(0.8) (0.8)

007

007

(0.8) (0.8)

007

007

(0.8)

(0.8)

 

 

 

 

 

 

 

 

7.6

6.8

6.0

5.0

FS unit

 

 

 

 

Indoor unit

007

007

009

009

Remote

(0.8)

(0.8)

(1.0)

(1.0)

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.0

3.0

2.0

 

009

009

009

009

(1.0)

(1.0)

(1.0)

(1.0)

13

20 HP system

Max. indoor unit : 33 units

Capacity code of indoor unit : Min. : 14

Max. : 27

Outdoor unit

10HP 10HP

10

Capacity code

Total 26.75

No. of total units

19

26.75

10.25

8.25

6.25

5.0

3.75

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

018

(2.0)

(2.0)

012

012

012

012

012

(1.25)

(1.25)

(1.25)

(1.25)

(1.25)

16.5

8.25

6.25

5.0

3.75

2.5

018

012

(2.0)

(1.25)

012

012

(1.25)

(1.25)

012

012

(1.25)

(1.25)

8.25 6.25 5.0 3.75 2.5 FS unit

Indoor unit

018

Remote

(2.0)

controller

 

012

012

(1.25)

(1.25)

012

012

012

(1.25)

(1.25)

(1.25)

14

30 HP system

 

 

Capacity code

• Max. indoor unit : 48 units

 

 

Total 40

• Capacity code of indoor unit :

Min. : 21

 

 

No. of total units

 

Max. : 40.5

 

 

 

 

 

28

 

 

 

 

Outdoor unit

10HP 10HP 10HP

20 10

40

10

9.2

8.4

7.6

6.8

6

007

007

007

(0.8) (0.8) (0.8)

007

007

(0.8) (0.8)

018

036

(2)

(4)

30

10

9.2

8.4

7.6

6.8

6

007

007

007

(0.8) (0.8) (0.8)

007

007

(0.8) (0.8)

018

036

(2)

(4)

20

10

9.2

8.4

7.6

6.8

6

007

007

007

(0.8) (0.8) (0.8)

007

007

(0.8) (0.8)

018

036

(2)

(4)

 

10

9.2

FS unit

 

 

Indoor unit

007

007

Remote (0.8) (0.8) controller

8.4 7.6 6.8

007

007

007

(0.8) (0.8) (0.8)

6

 

018

036

(2)

(4)

15

4. EQUIPMENT SELECTION PROCEDURE

1.Selection flow chart

1.Determination of indoor air conditioning load

2. Preliminary selection of indoor units

3.Preliminary selection of outdoor unit with indoor units

4.Capacity correction for piping length/height between indoor and outdoor units

5.Capacity correction based on indoor and outdoor temperature

NO

6.Validate preliminary selection of indoor units

7.Confirmation of selection for indoor unit and outdoor units

End

2. Combination conditions for indoor unit and outdoor unit

1. For indoor unit, the capacity code is decided for each capacity rank.

Capacity rank type

007

009

012

015

018

024

027

030

036

048

056

072

096

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity code

0.8

1

1.25

1.7

2

2.5

3

3.2

4

5

6

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

Capacity rank : Correspondence to Btu/h. Capacity code : Correspondence to Horsepower.

2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.

Outdoor unit

Capacity code of

Max. No. of

Total capacity code

(Heat recovery)

outdoor unit

indoor units

of indoor units

MMY-MAP0802FT8

8

13

5.6

to

10.8

 

 

 

 

 

 

MMY-MAP1002FT8

10

16

7.0

to

13.5

 

 

 

 

 

 

MMY-MAP1202FT8

12

16

8.4

to

14.4

 

 

 

 

 

 

MMY-AP1602FT8

16

27

11.2

to

21.6

 

 

 

 

 

 

MMY-AP1802FT8

18

30

12.6

to

24.3

 

 

 

 

 

 

MMY-AP2002FT8

20

33

14.0

to

27.0

 

 

 

 

 

 

MMY-AP2402FT8

24

40

16.8

to

32.4

 

 

 

 

 

 

MMY-AP2602FT8

26

43

18.2

to

35.1

 

 

 

 

 

 

MMY-AP2802FT8

28

47

19.6

to

37.8

 

 

 

 

 

 

MMY-AP3002FT8

30

48

21.0

to

40.5

 

 

 

 

 

 

70 to 135% of outdoor unit capacity for all systems except 12HP 70 to 120% of outdoor unit capacity for 12HP

16

3. Cooling/heating capacity characteristics

1. Cooling capacity calculation method :

Required cooling capacity = Cooling capacity x Factor ( , , , , *1) kW

Indoor air wet bulb temperature vs. capacity correction value

Capacity correction value

1.2

1.1

1.0

0.9

0.8

15

20

24

Indoor air wet bulb temp. (˚C)

Outdoor air dry bulb temperature vs.capacity correction value

Capacity correction value

1.2

1.1

1.0

0.9

–5

0

5

10

15

20

25

30

35

40 43

Outdoor air dry bulb temp. (˚C)

Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)

Capacity correction value

1.1

1.0

0.9

80

90

100

110

120

Air flow variation ratio (%)

*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity.

17

Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value

Height of outdoor unit H (m)

50 Outdoor unit (8 to 30HP)

40

30

 

 

 

%100

 

20

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

0

98

96

94

92

90

88

86

84

82

80

78

76

 

 

 

 

 

 

 

 

 

 

 

 

–10

–20

–30 0

10

20

30

40

50

60

70

80

90 100 110 120 130 140 150

Pipe length (Equivalent length) L (m)

Outdoor unit

L’ is the longest one of

(l’o + l’a, l’o + l’b, l’o + l’c)

ho l’o

H = ho +

(Largest one of ha, hb, and hc)

 

 

 

 

 

ha

 

 

hc

hb

 

 

l’a A

 

 

 

 

 

 

 

 

 

l’b

B Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

l’c

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

Correction of outdoor unit diversity

Correction (%)

120

100

80

60

40

20

0

20

40

60

80

100

120

135

Standard capacity ratio

Indoor units total capacity ratio (%)

*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity.

18

2. Heating capacity calculation method :

Required heating capacity = Heating capacity x Factor ( , , , , *1, *2) kW

Indoor air dry bulb temperature vs. capacity correction value

Capacity correction value

1.2

1.1

1.0

0.9

0.8

15 20 24

Indoor air dry bulb temp. (˚C)

Outdoor air wet bulb temperature vs. capacity correction value

Capacity correction value

1.2

1.1

1.0

0.9

0.8

0.7

0.6

0.5 –15 –10 –5 0 5 10 15

Outdoor air wet bulb temp. (˚C)

Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)

Capacity correction value

1.1

1.0

0.9

90

100

110

120

80

Air flow variation ratio (%)

*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity.

*2 : Refer to item 3 in page 20.

19

Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value

Height of outdoor unit H (m)

50 Outdoor unit (8 to 30HP)

40

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

99

 

 

98

 

 

97

 

 

96

 

95

 

 

94

93

92

91

–10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

–20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

–30 0

10

 

 

 

30

40

 

 

 

60

 

70

 

 

 

 

 

 

 

 

20

50

 

80

90 100 110 120 130 140 150

Pipe length (Equivalent length) L (m)

Correction of outdoor unit diversity

Outdoor unit

L’ is the longest one of

(l’o + l’a, l’o + l’b, l’o + l’c)

ho l’o

H = ho +

(Largest one of ha, hb, and hc)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ha

 

 

 

 

 

 

 

 

 

 

hc

hb

 

 

 

l’a A

 

 

 

 

 

 

 

 

 

 

 

l’b

B Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

l’c

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correction (%)

120

100

80

60

40

20

0

20

40

60

80

100

120

135

Standard capacity ratio

Indoor units total capacity ratio (%)

*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity.

3. Capacity correction in case of frost on the outdoor heat exchanger in heating

Correct the heating capacity when frost was found on the outdoor heat exchanger.

Heating capacity = Capacity after correction of outdoor unit × Correction value of capacity resulted from frost (Capacity after correction of outdoor unit : Heating capacity calculated in the above item 2.)

6 Capacity correction in case of frost on the outdoor heat exchanger

Capacity correction value

1.0

0.9

0.8

–15

–10

–5

0

5

10

Outdoor air wet bulb temp. (˚C)

20

4. Capacity calculation for each indoor unit

Capacity for each indoor unit

Required standard capacity of indoor unit

= Capacity after correction of outdoor unit ×

 

 

Total value of standard indoor unit capacity

 

5. Operating temperature range

 

 

In cooling time

 

 

 

45

 

 

 

 

 

(˚C)

40

 

 

 

 

 

35

 

 

 

 

 

temp.

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

dryairbulb

25

 

 

Usablerange

pull(indown)

 

10

 

Continuously

 

 

20

 

 

 

 

 

 

 

operable

 

 

 

Outdoor

15

 

range

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

–5

 

 

 

 

 

 

–10

15

20

25

28

30

 

10

Indoor air wet bulb temp. (˚C)

In heating time

 

20

 

 

 

 

 

(˚C)

15

 

 

 

 

 

 

 

 

 

 

 

temp.

10

 

 

 

 

 

5

 

 

 

 

 

Outdoor air wet bulb

 

(in warming-up)

 

 

 

0

Usable range

Continuously

 

operable

 

 

range

 

 

–5

 

 

 

–10

 

 

 

–15

 

 

 

 

 

 

 

 

 

 

–20

10

15

20

25

30

 

5

Indoor air dry bulb temp. (˚C)

*The unit can be operated even if outdoor temperature gets down to -20°C, however note that the warranty covers only up to -15°C because operation beyond that temperature is out of specification.

*When outdoor air temperature falls to under -15°C, it may cause shortening the product lifetime.

*When outdoor temperature goes out of specified range “ or ” mark is indicated on the remote controller display and required operation will stop.

& ”: When heating operation “”: When cooling operation

[Notice]

This indication is not failure.

When outdoor temperature goes back to specified range, “ or ” disappear and start normal operation.

Operation stops because concurrent operation can not be kept in the condition of out of specification for Super HRM.

(Outdoor temp.(DB)

<-10°C: Cooling,

 

>21°C: Heating)

*Do not use “Super HRM” for other than personal usage where the ambient temperature may go down below -10°C. (For example, OA equipment/Electric device/Food/Animals and plants/Art object)

6.Rated conditions

Cooling :

Indoor air temperature 27°C DB/19.0°C WB, Outdoor air temperature 35°C DB

Heating :

Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

21

4. Example of equipment selection

The following shows an example of equipment selection based upon a building model

Fig. 1 Overview of building model

<Outside view>

<Stories configuration>

2F

1F

14.4m

8m

7.2m

2F

 

 

 

Office rooms

2 – 1 2 – 2 2 – 3

2 – 4

2 – 5

(2–1, 2–2 : Computer room)

 

1 – 1

1 – 4

Stores

1F

 

 

 

1 – 3

(1-4 : Kitchen)

1 – 2

 

 

 

 

 

 

 

 

 

 

 

Non-air conditioning zone

 

 

Steel frame, reinforced concrete building, four stories above ground. Total floor area : 207m²

Outdoor unit is installed on the roof.

Design indoor conditions

Cooling : 27.0/19.0°C DB/WB, Heating : 20°C DB

Design outdoor conditions

Cooling : 35°C DB (Standard condition), Heating : 3°C WB (Standard condition : 6°C WB)

Selection Criteria for Each Floor

2F : Outdoor capacity exactly matches the total indoor capacity.

Total indoor HP = Outdoor unit HP Indoor : 2.5 HP x 2 units + 1.25 HP + 2 HP x 2 = 10.25 HP Outdoor : 10 HP Same capacity

Heat load of room 2-1 and 2-2 is higher than other rooms.

1F : Consider the increasing heat load in the specific room.

Total indoor units HP > Outdoor unit HP

Select each indoor unit based on individual peak room load. Indoor : 2.5HP + 2.5HP + 3.2HP + 2.0HP =

10.2HP < > Outdoor : 10HP (Same capacity)

The room “1-4” is designed for “cooling only” because of its high heat load.

The outdoor module should have sufficient capacity to cover the peak demand of the indoor unit connected.

22

Procedure and result of equipment selection

1.Procedure of equipment selection

a.Calculate cooling for every rooms.

b.Select an indoor unit to match the cooling load for every room from the table in pages 8.

c.Choose a tentative outdoor module that will match with the indoor units. Perform capacity correction based on the pipe length, system lift, indoor set temperature, outdoor temperature.

Then, make sure the corrected system cooling capacity satisfies the cooling load.

2.Equipment selection and capacity check

 

Air conditioning load

 

 

 

Equipment selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor air conditioning load

Indoor unit

 

 

Outdoor unit

 

Floor

Room No.

(kW)

 

Model

Capacity (kW)

Model

Capacity (kW)

 

 

 

 

 

 

 

 

 

 

 

MMY-

 

 

 

 

Cooling

 

Heating

Cooling

 

Heating

Cooling

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-1

6.0

 

3.4

MMU-AP0241H

7.1

 

8.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-2

5.0

 

2.2

MMU-AP0181H

5.6

 

6.3

 

 

 

2F

 

 

 

 

 

 

 

 

 

 

 

2-3

5.0

 

4.2

MMU-AP0181H

5.6

 

6.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-4

3.2

 

2.7

MMU-AP0121H

3.6

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

MAP2002FT8

56.0

63.0

 

2-5

6.4

 

5.4

MMU-AP0241H

7.1

 

8.0

 

 

 

 

 

 

 

 

 

 

 

 

 

1-1

6.1

 

6.0

MMU-AP0241H

7.1

 

8.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-2

6.3

 

6.3

MMU-AP0241H

7.1

 

8.0

 

 

 

1F

 

 

 

 

 

 

 

 

 

 

 

1-3

7.2

 

7.0

MMU-AP0301H

9.0

 

10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-4

5.1

 

MMD-AP0181H

5.6

 

6.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping distance

 

Capacity correction

Capacity check after correction

 

 

 

 

 

 

 

 

 

 

 

 

Height

Pipe correction x temp.

 

Capacity

 

 

 

Equivalent

 

 

 

 

 

correction

 

 

 

Floor

Room No.

difference

Capacity (kW)

Judgment

length (m)

 

 

 

 

(m)

 

 

 

 

 

 

 

 

Cooling

Heating

Cooling

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-1

 

 

 

 

6.6

7.0

 

 

 

 

 

 

 

 

 

 

 

2-2

 

 

 

 

5.2

5.5

 

2F

 

 

 

 

 

 

 

 

2-3

 

 

 

1.0

5.2

5.5

 

 

 

 

 

 

 

 

 

 

2-4

 

 

1.0

×

3.3

3.5

 

 

 

 

×

0.95

 

 

 

 

 

 

 

 

1.0×

2-5

34

5

×

0.98

6.6

7.0

good

 

 

 

 

0.936

×

 

 

 

1-1

 

 

=

0.95

6.6

7.0

 

 

 

0.936

=

 

 

 

 

 

 

 

 

 

 

 

 

 

0.884

 

 

 

1-2

 

 

 

6.6

7.0

 

 

 

 

 

 

1F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-3

 

 

 

 

8.4

8.8

 

 

 

 

 

 

 

 

 

1-4

 

 

 

 

5.2

5.5

 

23

Schematic diagram

MMY-MAP2002FT8

10 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st branching joint

4th branching

5th branching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3rd branching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd branching joint

joint

joint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

joint

 

 

FS unit

 

FS unit

FS unit

FS unit

FS unit

RBM-Y1122FE

RBM-Y1122FE

RBM-Y1122FE

RBM-Y1122FE

RBM-Y1122FE

Indoor unit

 

Indoor unit

Indoor unit

Indoor unit

Indoor unit

MMU-AP0241H

 

MMU-AP0181H

MMU-AP0181H

MMU-AP0121H

MMU-AP0241H

R

R

R

R

R

Computer

Computer

Office

Office

Office

Room

 

Room

 

 

 

 

2 – 1

 

2 – 2

2 – 3

2 – 4

2 – 5

 

 

 

 

Branching header

 

FS unit

FS unit

FS unit

 

RBM-Y1122FE

 

RBM-Y1122FE

RBM-Y1122FE

 

 

 

 

 

Indoor unit

 

Indoor unit

Indoor unit

Indoor unit

MMU-AP0241H

 

MMU-AP0241H

MMU-AP0301H

MMD-AP0181H

R

 

R

 

R

R

 

 

 

 

 

<Cooling only>

Store

 

Store

 

Restaurant

Kitchen

1 – 1

 

 

1 – 2

1 – 3

1 – 4

24

5. REFRIGERANT PIPING DESIGN

1. Warnings on refrigerant leakage Important

Check of Concentration Limit

The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.

The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc.

Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).

In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device.

The concentration is as given below.

Total amount of refrigerant (kg)

Min. volume of the indoor unit installed room (m³)

Concentration limit (kg/m³)

The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m³.

(For details, refer and comply with local regulations.)

NOTE 1 :

If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.

Outdoor unit

e.g., charged

amount (10kg) e.g.,

charged amount (15kg)

Room A Room B Room C Room D Room E Room F

Indoor unit

For the amount of charge in this example:

The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg.

The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.

NOTE 2 :

The standards for minimum room volume are as follows.

(1) No partition (shaded portion)

(2)When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).

Outdoor unit

Refrigerant piping

Indoor unit

(3)If an indoor unit is installed in each partitioned room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.

 

 

Refrigerant piping

 

 

Outdoor unit

Very

 

 

small

 

Indoor unit

room

 

Small

Medium

Large room

room

room

 

Mechanical ventilation device - Gas leak detector

NOTE 3 :

The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)

 

40

 

 

 

 

35

Range below the

 

 

 

density limit

 

 

 

 

30

of 0.3 kg/m³

 

 

 

 

(countermeasures

 

 

 

 

 

 

 

 

 

25

not needed)

 

 

 

area

 

 

 

 

20

 

 

 

 

floor

15

 

Range above

 

 

the density limit

 

indoor

10

 

of 0.3 kg/m³

 

 

(countermeasures

 

 

 

needed)

 

 

Min.

5

 

 

 

 

 

 

 

0

 

 

 

 

 

10

20

30

 

 

 

 

 

 

Total amount of refrigerant

kg

25

2. Free branching system

Line branching system

Header branching system

Header branching system after line branching

Line branching system after header branching

Header branching system after header branching

The above five branching systems are available to dramatically increase the flexibility of refrigerant piping design.

 

 

Outdoor unit

 

 

Branching joint

Line

 

 

branching

 

 

system

 

FS unit

 

 

 

 

Indoor unit

 

 

Remote

 

 

controller

 

 

Outdoor unit

Header

 

Branching header

 

 

branching

 

 

system

 

FS unit

 

 

Indoor unit

 

 

Remote controller

 

 

Outdoor unit

Header

 

Branching joint

 

Branching header

branching

 

 

system

 

 

after line

 

FS unit

branching

 

Indoor unit

 

 

 

 

Remote

 

 

controller

Line

 

 

branching

 

Outdoor unit

system after

 

 

header

 

 

branching

 

Branching header

 

 

 

 

Branching

Header

FS unit

joint

 

branching

Indoor

 

system after

unit

 

header

 

Remote

branching

 

controller

 

 

26

3. Allowable length/height difference of refrigerant piping

Height difference between outdoor units

H35m

Height difference between outdoor and indoor units

H1 50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Follower Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header Unit Follower Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T-shape

 

La

 

 

 

 

 

 

 

 

 

Lb

 

 

 

 

 

 

 

 

 

 

Lc

branching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main piping

 

 

 

 

LA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

In case of connecting method <Ex.2>, a large amount of refrigerant and refrigerant oil may return to the head unit. Therefore, set the T-shape joint so that oil does not enter directly.

<Ex.1> Header Unit Follower Unit Follower Unit

A B C

 

Main connecting piping between outdoor units

<Ex.2> Header Unit Follower Unit Follower Unit

 

Length corresponded to farthest piping

 

 

 

 

 

 

A

 

 

 

 

 

 

B

 

 

 

 

 

 

C

 

between outdoor units LO 25m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Branching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Branching piping L2 header

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st branching section

L3

 

 

 

Connecting piping of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

L9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b

 

 

 

 

 

c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

g

 

 

 

 

 

h

 

 

 

i

 

 

 

 

 

 

 

 

j

 

 

 

 

k

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

< Cooling only > < Cooling only >

 

 

 

 

 

 

 

Equivalent length corresponded to farthest piping L 150m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equivalent length corresponded to farthest piping after 1st branching Li

 

 

50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lj

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height difference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between

 

 

 

 

 

 

 

 

L4

 

 

 

L5

 

 

L6

 

L7

 

L8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H2 35m

 

 

 

 

 

 

d

 

 

 

e

 

 

 

 

 

f

 

 

Lh

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Upper outdoor unit)

 

 

 

l

 

 

 

 

 

 

m

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Header)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

p

 

 

 

 

q

 

 

 

 

(q)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height difference between indoor units in group control by one FS unit

H40.5 m

* Allowable length and height difference of refrigerant piping

 

 

 

 

Allowable value

Piping section

 

 

 

 

 

 

 

Total extension of pipe (Liquid pipe, real length)

300 m

LA+La+Lb+Lc+L1+L2+L3+L4+L5+L6+L7+L8+9

 

+a+b+c+d+e+f+g+h+i+j+k+l+m+n+o+p+q

 

 

 

 

 

 

 

 

 

 

 

 

Farthest piping length L (*1)

 

Real length

125 m

LA+Lc+L1+L3+L4+L5+L6+L7+L8+q

 

 

 

 

 

 

Equivalent length

150 m

 

Max. equivalent length of main piping

85 m

L1

 

 

 

 

 

Pipe

Equivalent length of farthest piping from 1st branching Li (*1)

50 m

L3+L4+L5+L6+L7+L8+q

Length

Max. real length of indoor unit connecting piping

30 m

a+g, b+h, c+i, d+l, e+m, f+n, j, k

 

 

 

 

 

 

Max. real length between FS unit and indoor unit (*2)

15 m

g, h, i, l, m, n, L7+o, L7+L8+p, L7+L8+q

 

Max. Equivalent length of outdoor unit connecting piping LO (*1)

25 m

LA+Lc (LA+Lb)

 

Max. real length of outdoor unit connecting piping

10 m

La, Lb, Lc

 

 

 

 

 

 

Max. equivalent length between FS unit and indoor unit Lj

30 m

L7+L8+q, L7+L8+p

 

 

 

 

 

 

Max. real length between FS unit

and header indoor unit Lh (*2)

15 m

L7+o

 

Height between indoor

Upper outdoor unit

50 m

——

 

and outdoor units H1

Lower outdoor unit

30 m

——

 

 

 

 

 

 

 

 

 

Height

Height between indoor units H2

Upper outdoor unit

35 m

——

 

 

 

Lower outdoor unit

15 m

——

Difference

 

 

 

 

 

 

 

 

Height between outdoor units H3

 

5 m

——

 

 

 

 

 

Height difference between indoor units in group control by one FS

0.5 m

——

 

unit H4

 

 

 

 

 

 

 

 

 

 

 

*1 : The farthest outdoor unit from 1st branch to be named C, and farthest indoor unit from 1st branch to be named (q).

*2 : Attached connection cable can be used up to 5 m in pipe length between indoor and FS unit. When the pipe length between indoor and FS unit exceeds 5 m, be sure to use the connection cable kit (RBC-CBK15FE).

* System restrictions

Max. No. of combined outdoor units

 

 

3 units

 

 

 

 

 

Max. capacity of combined outdoor units

 

 

84.0 kW

 

 

 

 

 

Max. No. of connected indoor units

 

 

48 units

 

 

 

 

 

Max. capacity of combined indoor units

H2

 

15m

135% (*1)

 

 

 

 

H2

> 15m

105%

 

*1 : MMY-MAP1201HT8 : UP to 120 %

Note 1) Combination of outdoor units : Header unit (1 unit) + Follower unit (0 to 2 units). Header unit is outdoor unit nearest to the connected indoor units

Note 2) Install the outdoor units in order of capacity. (Header unit Follower unit 1 Follower unit 2)

Note 3) Refer to outdoor unit combination table in page.6.

Note 4) Piping to indoor units shall be perpendicular to piping to the head outdoor unit as <Ex.1>.

Do not connect piping to indoor units in the same direction of head outdoor unit as <Ex.2>.

27

4. Selection of refrigerant piping

Follower Unit Follower Unit Header Unit

Outdoor unit

1Outdoor unit connecting piping

C

B

A

 

 

 

 

 

 

Balance pipe

1st branching section

 

 

 

 

4

Liquid pipe

 

 

 

1

1

8

Y-Shape branching joint

 

 

Discharge gas pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction gas pipe

 

 

 

2

3 Main piping

 

 

 

4

9

T-shape

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main connecting piping

branching joint

 

 

 

 

 

 

 

8 Y-Shape branching joint

 

between outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

5

5

 

5

 

 

 

 

 

 

 

FS unit

 

 

 

 

 

 

 

 

 

4

 

 

6

6

 

6

 

7

7

 

 

 

 

 

 

 

 

 

 

< Cooling only >

< Cooling only >

 

 

Liquid pipe

8

4

8

4

8

4

4

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge gas pipe

 

 

 

 

 

 

 

 

 

 

 

 

Suction gas pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

5

5

 

5

 

 

 

 

 

 

 

FS unit

 

 

 

 

 

 

 

 

 

 

 

 

6

6

 

6

 

6

6

6

Indoor unit

Group control

* Selection of refrigerant piping

No.

Item

Suction

Discharge

Liquid side

 

Outdoor unit model name

 

 

gas side

gas side

 

 

 

 

 

Pipe size of outdoor

Ø 22.2

Ø 19.1

Ø 12.7

MMY-MAP0802FT8

 

Ø 22.2

Ø 19.1

Ø 12.7

MMY-MAP1002FT8

 

unit

 

Ø 28.6

Ø 19.1

Ø 12.7

MMY-MAP1202FT8

 

 

 

 

 

 

 

 

 

Total capacity code of indoor units at

No.

Item

Suction

Discharge

Liquid side

Balance

downstream side

gas side

gas side

pipe

Equivalent to

Equivalent to HP

 

 

 

 

 

 

 

 

 

capacity

 

 

 

 

 

 

 

 

Connecting pipe size

Ø 28.6

Ø 22.2

Ø 15.9

Ø 9.5

Below 61.5

Below 22

 

between outdoor units

 

 

 

 

 

 

 

 

 

Suction

Discharge

 

 

Total capacity code of all outdoor units

No.

Item

Liquid side

 

Equivalent to

 

 

 

gas side

gas side

 

 

Equivalent to HP

 

 

 

 

 

 

capacity

 

 

 

 

 

 

 

 

 

Ø 22.2

Ø 19.1

Ø 12.7

 

Below 33.5

Below 12

 

Size of main pipe

Ø 28.6

Ø 19.1

Ø 12.7

33.5

12

 

Ø 28.6

Ø 22.2

Ø 19.1

45.0 to below 61.5

16 to below 22

 

 

Ø 34.9

Ø 28.6

Ø 19.1

 

61.5 to below 73.0

22 to below 26

 

 

Ø 34.9

Ø 28.6

Ø 22.2

 

73.0 or more

26 or more

 

 

Suction

Discharge

 

 

Total capacity code of all indoor units

No.

Item

Liquid side

 

Equivalent to

 

 

 

gas side

gas side

 

 

Equivalent to HP

 

 

 

 

 

 

capacity

 

 

 

 

 

 

 

 

 

Ø 15.9

Ø 12.7

Ø 9.5

 

Below 18.0

Below 6.4

 

Pipe size between

Ø 22.2

Ø 19.1

Ø 12.7

18.0 to below 34.0

6.4 to below 12.2

 

branching sections

Ø 28.6

Ø 22.2

Ø 15.9

34.0 to below 56.5

12.2 to below 20.2

 

*1 *2 *3

Ø 34.9

Ø 28.6

Ø 15.9

 

56.5 to below 70.5

20.2 to below 25.2

 

 

Ø 34.9

Ø 28.6

Ø 19.1

 

70.5 or more

25.2 or more

 

Pipe size between the

Ø 15.9

Ø 12.7

Ø 9.5

Below 18.0

Below 6.4

 

end of branch and FS

 

 

 

 

 

 

Ø 22.2

Ø 19.1

Ø 12.7

18.0 or more

6.4 or more

 

unit

 

 

 

 

 

 

 

No.

Item

Suction

Discharge

Liquid side

 

Capacity rank of indoor unit

 

 

gas side

gas side

 

 

 

 

 

 

Ø 9.5

Ø 6.4

 

007 to 012 Type

 

Piping of indoor unit

Ø 12.7

Ø 6.4

015 to 018 Type

 

Ø 15.9

Ø 9.5

024 to 056 Type

 

 

 

 

Ø 22.2

Ø 12.7

 

072 to 096 Type

 

 

Ø 9.5

Ø 6.4

 

15m or less

007 to 012 Type

 

Piping of cooling only

Ø 12.7

 

Ø 9.5

15m above

 

 

 

 

indoor unit (Between

Ø 12.7

Ø 6.4

15m or less

015 to 018 Type

 

branching and indoor

Ø 15.9

 

Ø 9.5

15m above

 

 

 

 

 

unit) *2

Ø 15.9

Ø 9.5

024 to 056 Type

 

 

Ø 22.2

Ø 12.7

072 to 096 Type

* Selection for branching section

Selection of FS unit

 

Total capacity code of

Max.No. of

Model Name

indoor unit

connected

 

Equivalent to

Equivalent

indoor

 

capacity (kW)

to HP

units

RBM-Y1122FE

Below 11.2

Below 4.0

5

RBM-Y1802FE

11.2 to below

4.0 to below

8

18.0

6.4

 

 

 

 

RBM-Y2802FE

18.0 to 28.0

6.4 to 10.0

8

or less

or less

 

 

 

 

 

 

 

* Minimum wall thickness for R410A

application

 

Half

Outer

Outer

Minimum

Soft

Hard

Wall

dia.

dia.

 

or

(Inch)

(mm)

Thickness

 

Hard

(mm)

OK

OK

1/4”

6.35

0.80

 

 

 

 

 

OK

OK

3/8”

9.52

0.80

 

 

 

 

 

OK

OK

1/2”

12.70

0.80

 

 

 

 

 

OK

OK

5/8”

15.88

1.00

 

 

 

 

 

NG

OK

3/4”

19.05

1.00

NG

OK

7/8”

22.20

1.00

NG

OK

1.1/8”

28.58

1.00

 

 

 

 

 

NG

OK

1.3/8”

34.92

1.10

 

 

 

 

 

*1 In case the pipe exceeds main pipe size, it should be the same as main pipe size.

*2 2 pipes for cooling only indoor unit shall be used with liquid pipe and suction gas pipe.

*3 2 pipes from FS unit to branching section shall be used with liquid pipe and suction gas pipe.

*4 Branching pipe on the 1st branch should be selected according to the capacity code for outdoor unit.

*5 In case total capacity code for indoor units shall be exceeded to capacity code for outdoor unit, the pipe size should be selected with capacity code for outdoor unit.

*6 For 1 line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected.

No.

 

 

Total capacity code of indoor unit

Model Name

 

 

 

 

 

Equivalent to capacity

 

Equivalent to HP

For 3 piping

For 2 piping

 

Y-Shape branching joint

Below 18.0

 

Below 6.4

RBM-BY53FE

RBM-BY53E

 

18.0 to below 40.0

 

6.4 to below 14.2

RBM-BY103FE

RBM-BY103E

 

*4 *5

40.0 to below 70.5

 

14.2 to below 25.2

RBM-BY203FE

RBM-BY203E

 

 

 

70.5 or more

 

25.2 or more

RBM-BY303FE

RBM-BY303E

 

Branching

For

Below 40.0

 

Below 14.2

RBM-HY1043FE

RBM-HY1043E

 

4 Branching

40.0 to below 70.5

 

14.2 to below 25.2

RBM-HY2043FE

RBM-HY2043E

 

Header

For

Below 40.0

 

Below 14.2

RBM-HY1083FE

RBM-HY1083E

 

*4, *5, *6

 

 

 

8 Branching

40.0 to below 70.5

 

14.2 to below 25.2

RBM-HY2083FE

RBM-HY2083E

 

 

 

1 set of 4 types of T-shape joint pipes as described below : The rewired

 

 

 

T-Shape branching joint

quantity is arranged and combined at the site.

 

 

 

 

- Balance pipe (Ø 9.52) X 1

 

 

 

 

(For connecting outdoor

- Piping at liquid side (Ø 12.7 to Ø 22.2) X 1

 

RBM-BT13FE

 

unit)

- Piping at discharge gas side (Ø 19.1 to Ø 28.6) X 1

 

 

 

 

 

 

 

 

 

 

- Piping at suction gas side (Ø 22.2 to Ø 38.1) X 1

 

 

28

5. Charging requirement with additional refrigerant

After the system has been vacuumed, replace the vacuum pump with a refrigerant cylinder and charge the system with additional refrigerant.

Calculating the amount of additional refrigerant required

Refrigerant in the system when shipped from the factory

R410A

 

 

 

 

 

 

 

 

 

8HP

10HP

12HP

 

 

 

 

 

 

 

Refrigerant amount charged in factory

Heat recovery model

11.5kg

11.5kg

11.5kg

 

 

 

 

 

 

 

When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the site is not included. Calculate the additional amount needed, and add that amount to the system.

(Calculation)

Additional refrigerant charge amount is calculated from size of liquid pipe at site and its real length.

[Additional refrigerant charge amount at site] =

 

 

 

 

 

 

[Real length of liquid pipe] ×

 

Additional refrigerant charge amount

 

× 1.3 +

Compensation by

 

 

 

per liquid pipe 1m (Table 1)

 

 

system HP (Table 2)

 

 

 

 

 

 

 

 

 

 

Example : Additional charge amount R (kg) = {(L1 x 0.025kg/m) + (L2 x 0.055kg/m) + (L3 x 0.105kg/m) + (L4 x 0.160kg/m) + (L5 x 0.250kg/m)} x 1.3

 

 

 

 

 

 

 

L1

: Real total length of liquid pipe Ø6.4 (m)

 

 

 

 

 

 

 

 

L2

: Real total length of liquid pipe Ø9.5 (m)

 

 

 

 

 

 

 

 

L3

: Real total length of liquid pipe Ø12.7 (m)

 

 

 

 

 

 

 

 

L4

: Real total length of liquid pipe Ø15.9 (m)

 

 

 

 

 

 

 

 

L5

: Real total length of liquid pipe Ø19.1 (m)

 

 

 

 

 

 

 

 

System : 24HP

 

 

 

 

Table 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe dia. at liquid side

 

 

 

 

Ø6.4

 

Ø9.5

 

Ø12.7

Ø15.9

Ø19.1

Ø22.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional refrigerant amount/1m

 

0.025kg

 

0.055kg

 

0.105kg

0.160kg

0.250kg

0.350kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combined

 

Outdoor

 

 

 

Compensation

 

 

 

 

 

 

horse power

combination (HP)

 

by system HP

 

 

 

 

 

(HP)

 

 

 

 

 

 

(kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

8

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

10

 

 

 

 

 

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

12

 

 

 

 

 

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

8

8

 

 

 

 

-1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

10

8

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

10

10

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

8

8

 

8

 

 

-4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

10

8

 

8

 

 

-3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

10

10

 

8

 

 

-1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

10

10

 

10

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

6. WIRING DESIGN

1.General

(1)Perform wiring of the power supply in conformance with the regulations of the local electric company.

(2)For the control wires connecting indoor units, and between indoor and outdoor units, use of double-core shield wires is recommended to prevent noise trouble.

(3)Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor unit.

(4)Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each outdoor unit.

(5)Never connect the 220–240V power to the terminal block (U1, U2, U3, U4, U5, U6) for control cables. (Trouble is caused.)

(6)Store wiring system for control and refrigerant piping system in the same line.

(7)Arrange the cables so that the electric wires do not come to contact with high-temperature part of the pipe ; otherwise coating melts and an accident may be caused.

(8)Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.

2.For outdoor unit power supply

Select the power supply cabling and fuse of each outdoor unit from the following specifications: Cable 5-core, in conformance with Design 60245 IEC 66

Do not connect them via the incorporated terminal block (L1, L2, L3, N).

L1

L2 L3

N

Outdoor power supply 3-phase 380-415V, 50Hz

3. Electrical wiring design

L1 L2 L3

N

L1 L2 L3

N

3-phase

50Hz 380-415V

Earth leakage breaker hand switch

Outdoor power source

Earth

 

 

 

Pull box

 

 

Indoor

 

FS unit

FS unit

FS unit

FS unit

 

 

 

 

 

power source

 

 

 

 

 

 

Single phase

 

 

 

 

 

50Hz 220-240V

Indoor unit

Indoor unit

Indoor unit

Indoor unit

 

Earth leakage breaker

 

 

 

 

 

 

power switch

 

 

 

 

 

 

FS unit

FS unit

FS unit

FS unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

• Unit capacities and power supply wire sizes (Reference)

Model

Power supply wiring

 

MMY-

Wire size

 

Field fuse

MAP0802FT8

3.5 mm² (AWG #10) Max. 20 m

 

30 A

 

 

 

 

MAP1002FT8

5.5 mm² (AWG #10) Max. 28 m

 

30 A

MAP1202FT8

5.5 mm² (AWG #10) Max. 27 m

 

30 A

 

 

 

 

Determine the wire size for indoor unit according to the number of connected indoor units downstream.

Observe local regulation regarding wire size selection and installation.

30

Loading...
+ 72 hidden pages