tekmar 654 Installation

Page 1
Installation & Operation Manual
Snow Melting Control 654
Snow Melting
654_D
06/13
Replaces: New
Introduction
The Snow Melting Control 654 is designed to operate electric or hydronic equipment to melt snow or ice from any surface including driveways, walkways, patios, business entrances, parking ramps, loading docks, hospital entrances, helipads or car wash bays. The surface temperature for snow melting is controlled automatically to reduce operating energy costs. The 654 has an automatic start and stop function when used with the Snow/Ice Sensor 090 or 094. Automatic start with a timed stop is available when used with the Snow Sensor 095. The 654 can operate a dedicated hydronic boiler or a mixing device. Isolation relays are required to operate line voltage pumps. Electric systems require a separate GFCI and electrical relay contactor.
Features
• Supports Both Inslab & Retrofit Aerial Sensors
• Manual Start With Timer
• Programmable Schedule
• tekmarNet
• Warm Weather Shut Down
• Cold Weather Cut Out
• Idling
• Snow Melt Zoning With Priority
• Tandem Snow / Ice Detection
• Slab Protection
• Storm
• EconoMelt
• Manual Override
• Snow Melt Zone Tracking
• Scenes
• Away Key
• Exercising
• Alert Output
®
Communication Compatible
1 of 44 © 2013 654_D - 06/13
Page 2
Table of Contents
Important Safety Information .............................................3
Installation .........................................................................4
Preparation .................................................................... 4
Physical Dimensions ..................................................... 4
Installation Location ....................................................... 4
Rough-In Wiring ............................................................. 4
Sizing the Transformer ..................................................5
Control Wiring ................................................................5
Sensor Wiring ................................................................ 7
Testing the Sensor Wiring ............................................. 8
Testing the Control Wiring .............................................8
Manual Override - Maximum Heat ................................ 9
Manual Override - Test .................................................. 9
Manual Override - Purge ............................................... 9
Manual Override - Off .................................................... 9
Switch Settings ..................................................................9
User Interface ...................................................................10
Display .......................................................................... 10
Operation Field ............................................................. 10
Status Field ................................................................... 10
Symbols ........................................................................ 10
Programmable Settings....................................................11
Programming Menus .................................................... 11
Access Levels and Access Level Lock ........................ 11
View Menu .................................................................... 12
Set Temp Menu ............................................................ 14
Time Menu .................................................................... 15
Schedule Menu ............................................................ 16
Display Menu ................................................................ 17
Scene Menu ................................................................. 17
Monitor Menu ................................................................ 18
Toolbox Menu ............................................................... 19
Override Menu .............................................................. 20
System Menu ................................................................21
Boiler Menu .................................................................. 22
Mix Menu ...................................................................... 23
tekmarNet
®
Menu .........................................................24
Sequence of Operation ....................................................25
Snow Melting Overview ................................................25
Slab Temperature Control ............................................ 25
Melt Operation .............................................................. 25
Melt - Manual Start and Timed Stop ............................26
Melt - Automatic Start and Stop ................................... 26
Melt - EconoMelt........................................................... 27
Melt - Automatic Start and Timed Stop ........................ 27
Melt - Tracked Start and Stop ......................................28
Melt - Scheduled Start and Stop .................................. 28
Additional Melting Time ................................................ 29
Idle Operation ............................................................... 29
Storm Operation ........................................................... 29
Warm Weather Shut Down ...........................................30
Cold Weather Cut Out ..................................................30
Away Scene ..................................................................30
Programmable Schedules ............................................ 31
Time Clock .................................................................... 31
Snow Melt Zones and Priority ......................................31
Slab Protection .............................................................33
Application Modes ........................................................ 33
Electric Operation ......................................................... 33
Pulse Width Modulation Operation ..............................33
Boiler Operation ........................................................... 33
Mixing Operation ..........................................................35
Tandem Snow / Ice Detection ......................................36
Exercising ..................................................................... 36
Alert Relay ....................................................................36
Pump Post Purge.......................................................... 36
Melt and Storm Groups ................................................ 37
User Switch Setup ........................................................ 37
Troubleshootin g ............................................................... 38
Error Messages ............................................................38
Frequently Asked Questions ........................................42
Job Record .......................................................................42
Technical Data ................................................................. 44
Limited Warranty and Product Return Procedure ........... 44
Getting Started
Congratulations on the purchase of your new Snow Melting Control! This manual covers the complete installation, programming and sequence of operation for this control. You will also find
instruction on testing, commissioning, and troubleshooting the control and system that it operates.
© 2013 654_D - 06/13 2 of 44
Page 3
Important Safety Information
It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.
To avoid serious personal injury and damage to the equipment:
Read Manual and all product labels
• BEFORE using the equipment. Do not use unless you know the safe and proper operation of this equipment.
Keep this Manual available for easy access by all users.
Replacement Manuals are available at tekmarControls.com
Disconnect all power before opening the control.
Radio Frequency Interference
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning
It is the installers responsibility to ensure that this control
• is safely installed according to all applicable codes and standards.
Improper installation and operation of this control could result
• in damage to the equipment and possibly even personal injury or death.
This electronic control is not intended for use as a primary
• limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
Do not attempt to service the control. There are no user
• serviceable parts inside the control. Attempting to do so voids warranty.
the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exi­gences du Règlement sur le matériel brouilleur du Canada.
3 of 44 © 2013 654_D - 06/13
Page 4
-----------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------
Installation
Preparation
Tools Required
tekmar or jeweller screwdriver
• Phillips head screwdriver
Materials Required
-----------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------
18 AWG LVT Solid Wire (Low Voltage Connections)
Physical Dimensions
Front View
5"
(127 mm)
3-1/4"
(82 mm)
Side View
Needle-nose Pliers
• Wire Stripper
tekmar 24 V (ac) Transformer 009
Mounting Base
9/16"
(14 mm)
1-7/8"
(47 mm)
4"
(102 mm)
15/16"
(23 mm)
CL
3/4"
(19 mm)
tN4Aux Ht R C
(23 mm)
2-1/2"
(64 mm)
654
Brn
Mod
Slab
+
CL
29/32"
CL
No Power
(38 mm)
BlkYel Blu Red Sup
ComCom
1-1/2"
13/16 "
(20 mm)
3-1/4"
(83 mm)
Out/ Bret
Installation Location
When choosing the location for the control, consider the following:
Interior Wall.
• Keep dry. Avoid potential leakage onto the control.
• Relative Humidity less than 90%. Non-condensing
• environment.
No exposure to extreme temperatures beyond -4 to
• 122°F (-20 to 50°C).
No draft, direct sun, or other cause for inaccurate
• temperature readings.
Rough-In Wiring
Low Voltage Wiring
Each cable must be pulled from the equipment to the control’s plastic enclosure. All low voltage wiring connections enter the enclosure through the square knockout on the rear. It is recommended to label each cable for easy identification. All low voltage wires are to be stripped to a length of 3/8" (9 mm) to ensure proper connection to the control.
Pull four conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
Snow Sensor 095
Pull five conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
Snow / Ice Sensor 090 or 094
-------------------------------------------------------------------------------------
Away from equipment, appliances, or other sources of
• electrical interference.
Easy access for wiring, viewing, and adjusting the display
• screen.
Approximately 5 feet (1.5 m) off the finished floor.
• The maximum length of wire is 500 feet (150 m).
• Strip wire to 3/8" (10 mm) for all terminal connections.
• Use standard 8 conductor, 18 AWG wire.
Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
24 V (ac) power from transformer
Outdoor temperature sensor
Supply sensor (if applicable)
On/off boiler (if applicable)
Modulating boiler 0-10 V (dc) or 4-20 mA (if applicable)
Mixing valve or mixing injection pump 0-10 V (dc) or 4-20 mA (if applicable)
Boiler return temperature sensor (if applicable)
Alert output (if applicable)
tekmarNet
®
4 communication to other devices
© 2013 654_D - 06/13 4 of 44
Page 5
Sizing the Transformer
-------------------------------
--------------------------
------
-----
The control requires an external transformer. A tekmar Transformer 009 can supply up to 40 VA, and includes an in-line fuse to protect the transformer and control.
The total power capacity of the power supply should be larger than the total load of all the devices connected to the control. This total load must not exceed 100 VA.
Control Wiring
See Application Brochure 654_A for specific application wiring diagrams.
Snow / Ice Sensor
Mod
tN4Aux Ht R C
+
-------------------------------
Snow / Ice Sensor
090 or 094
No Power
Brn
Slab
Out/
BlkYel Blu Red Sup
Com
Bret
Snow and Slab Sensor
--------------------------
Snow Sensor
095
Slab Sensor 072 or 073
No Power
Brn
Mod
tN4Aux Ht R C
Slab
+
Out/
BlkYel Blu Red Sup
Com
Bret
Snow
Sensor
095
Outdoor, Supply and Boiler Return Sensor
------
Modulating Output and tN4 Communication
-----
Modulating Boiler
Mixing Valve or
Mixing Injection Pump
0-10 V (dc) Signal
– +
tN4Aux Ht R C
Slab
+
Out/
BlkYel Blu Red Sup
Com
Bret
Supply Sensor
082
Outdoor
Sensor
070
No Power
Brn
Mod
tN4 C
®
tekmarNet
4
Communication
Mod
tN4Aux Ht R C
No Power
Brn
Slab
+
Out/
BlkYel Blu Red Sup
Com
Bret
or
Boiler
Return
Sensor
082
5 of 44 © 2013 654_D - 06/13
Page 6
tN4 Wiring Center or Zone Manager
-------------
--------------------------------------------------------------------------------
------------------------------
-------------
Alert Relay Output
------------------------------
tN4 C R W tN4 C R W
Zone 1
Zone 2
tN4 Wiring Center or Zone Manager
Transformer and Relays
Transformer 009
L N
tN4Aux Ht R C
Slab
+
Out/
BlkYel Blu Red Sup
Com
Bret
Mod
tN4Aux Ht R C
No Power
Brn
Mod
No Power
Brn
Slab
+
Out/
BlkYel Blu Red Sup
Com
Bret
Alert
Equipment
--------------------------------------------------------------------------------
R C
Relay 003
3 4 5 6
TT
2 1 8 7
Relay 003
2
3
1
4
8
5 6
7
System
Pump
LNG
On/Off Boiler
115 V (ac)
© 2013 654_D - 06/13 6 of 44
tN4Aux Ht R C
Slab
+
Out/
BlkYel Blu Red Sup
Com
Bret
No Power
Brn
Mod
Page 7
Sensor Wiring
--------------------------------------------------------------------------
-----------------------------------------------------------------------------
-------------------------------------------------------------------------
Mounting the Outdoor Sensor
--------------------------------------------------------------------------
Notice: The temperature sensor (thermistor) is built into the sensor enclosure.
Remove the screw and pull the front cover off the sensor
• enclosure.
The outdoor sensor can either be mounted directly onto a wall or a 2" x 4" electrical box. When the outdoor sensor is wall mounted, the wiring should enter through the back or bottom of the enclosure. Do not mount the outdoor sensor with the conduit knockout facing upwards as rain could enter the enclosure and damage the sensor.
Sensor with rear entry wiring
In order to prevent heat transmitted through the wall from
• affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure.
The outdoor sensor should be mounted on a wall which best
• represents the heat load on the building (a northern wall for most buildings and a southern facing wall for buildings with large south facing glass areas). The outdoor sensor should not be exposed to heat sources such as ventilation or window openings.
The outdoor sensor should be installed at an elevation above the ground that will prevent accidental damage or tampering.
Sensor with bottom entry wiring
Sensor mounted onto 2" x 4" electrical box
Wiring the Outdoor Sensor
Connect 18 AWG or similar wire to the two terminals provided in the enclo-
-----------------------------------------------------------------------------
sure and run the wires from the outdoor sensor to the control. Do not run the wires parallel to telephone or power cables. If the sensor wires are lo­cated in an area with strong sources of electromagnetic interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com or Com Sen terminal on the control and not to earth ground.
Follow the sensor testing instructions in this brochure and connect the
• wires to the control.
Replace the front cover of the sensor enclosure.
Mounting the Universal Sensor
-------------------------------------------------------------------------
NOTICE: These sensors are designed to mount on a pipe or in a temperature immersion well.
The Universal Sensor should be placed downstream of a pump or after an elbow or similar fitting. This is especially important if large diameter pipes are used as the thermal stratification within the pipe can result in erroneous sensor readings. Proper sensor location requires that the fluid is thoroughly mixed within the pipe before it reaches the sensor.
Strapped to Pipe
The Universal Sensor can be strapped directly to the pipe using the cable tie provided. Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement.
Wires from outdoor sensor to control’s outdoor sensor and sensor common terminals
Sensor is built into the enclosure
7 of 44 © 2013 654_D - 06/13
Page 8
Immersion Well
--------------------------------------------------------------------------------------
If a Universal Sensor is mounted onto 1" (25 mm) diameter L type copper pipe, there is approximately an 8 second delay between a sudden change in water temperature and the time the sensor measures the temperature change. This delay increases considerably when mild steel (black iron) pipe is used. In general, it is recommended that a temperature well be used for steel pipe of diameter greater than 1-1/4" (32 mm). Temperature wells are also recommended when large diameter pipes are used and fluid stratification is present.
Conduit Connection
The Universal Sensor and Universal Sensor Enclosure 080 (sold separately) are specifically designed to mount onto a 3/8" (10 mm) ID temperature well that is supplied with an end groove. To install the well, plumb a ‘T’ into the pipe and fix the well into the ‘T’. The 080 enclosure has a 7/8" (22 mm) back knockout that must be removed and fitted over the temperature well. The universal sensor is then inserted into the well and the retaining clip supplied with the enclosure is snapped onto the well end groove. If the well has a threaded end, the installer must supply a standard threaded conduit retaining ring. The two wires from the sensor are connected to the terminal block provided in the enclosure. The other side of the terminal block is used to connect wires from the control.
Testing the Sensor Wiring
Retaining
Clip
Universal
Sensor
Sensor Well
Universal
Sensor
Bottom of
Enclosure 080
Cable Tie
A good quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000 Ω) is required to measure the sensor resistance. In addition to this, the actual temperature must be measured with either a good quality digital thermometer, or if a thermometer is not available, a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires from the sensor must not be connected to the control while the test is performed. Using the chart below, estimate
Temperatur e Re sistance Temperatur e Resistance Temperature Resistance Temper ature Resistance
°F °C
-50 -46 490,813 20 -7 46,218 90 32 7,334 160 71 1,689
-45 -43 405,710 25 -4 39,913 95 35 6,532 165 74 1,538
-40 -40 336,606 30 -1 34,558 100 38 5,828 170 77 1,403
-35 -37 280,279 35 2 29,996 105 41 5,210 175 79 1,281
-30 -34 234,196 40 4 26,099 110 43 4,665 180 82 1,172
-25 -32 196,358 45 7 22,763 115 46 4,184 185 85 1,073
-20 -29 165,180 50 10 19,900 120 49 3,760 190 88 983
-15 -26 139,403 55 13 17,436 125 52 3,383 195 91 903
-10 -23 118,018 60 16 15,311 130 54 3,050 200 93 829
-5 -21 100,221 65 18 13,474 135 57 2,754 205 96 763 0 -18 85,362 70 21 11,883 140 60 2,490 210 99 703 5-15 72,918 7524 10,501 14563 2,255 215102 648
10 -12 62,465 80 27 9,299 150 66 2,045 220 104 598 15 -9 53,658 85 29 8,250 155 68 1,857 225 107 553
°F °C °F °C °F °C
the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
Testing the Control Wiring
Testing the Power
1. Remove the front cover from the control.
2. Use an electrical test meter to measure (ac) voltage between the R and C terminals. The reading should be 24 V (ac) +/– 10%.
3. Install the front cover.
© 2013 654_D - 06/13 8 of 44
--------------------------------------------------------------------------------------
Page 9
Testing the Relay Outputs
-----------------------
-----------------------
The control includes an Override menu to check if the control’s relays are operating and that the control is wired correctly to the snow melting equipment.
Step 1: Step 2: Step 3: Step 4: Step 5:
Press and hold the Home button for 3 seconds. Press NEXT to navigate to the Override menu. Press ENTER to enter the Override menu. Select Manual Override to Hand. For hydronic systems, set System Pump to On. The
system pump should now be operating.
Manual Override - Maximum Heat
Step 6:
Step 7:
Step 8:
Step 9:
Step 10:
Set Heat Relay to On. The boiler or electric heating cables should start heating.
For modulating boilers change the Boiler Percent from 0 to 100%. The boiler should be firing.
For a mixing valve or mixing injection pump, change the Mix Percent from 0 to 100%. The mixing valve should open or the mixing injection pump should increase speed.
Select the Override Time after which the control resumes normal operation.
Exit the Manual Override by selecting Auto.
In hydronic application modes, the control includes a Maximum Heat operation where the control operates the snow melting system to maintain the maximum allowed heating setpoints. This allows testing of the snow melting system during warm weather.
Manual Override - Test
When operating an electric snow melting system, the control includes a Test operation where the electrical heating cables can be energized for 10 minutes after which the control resumes normal operation. This allows testing of the electric snow melting system during warm weather.
Manual Override - Purge
When operating a hydronic snow melting system, it is neces­sary to purge and bleed all air out of the system. The control includes a Purge operation where the System Pump as well as pumps operated by the tekmarNet® system are all turned on to assist in purging air from the system.
Step 1: Step 2: Step 3: Step 4: Step 5:
Step 6:
Step 1: Step 2: Step 3: Step 4: Step 5:
Step 1: Step 2: Step 3: Step 4: Step 5:
Step 6:
Press and hold the Home button for 3 seconds. Press NEXT to navigate to the Override menu. Press ENTER to enter the Override menu. Select Manual Override to Max. Select the Maximum Heat Time after which the control
resumes normal operation. Exit the Manual Override by selecting Auto.
Press and hold the Home button for 3 seconds. Press NEXT to navigate to the Override menu. Press ENTER to enter the Override menu. Select Manual Override to Test. Exit the Manual Override by selecting Auto.
Press and hold the Home button for 3 seconds. Press NEXT to navigate to the Override menu. Press ENTER to enter the Override menu. Select Manual Override to Purge. Select the Maximum Purge Time after which the control
resumes normal operation. Exit the Manual Override by selecting Auto.
Manual Override - Off
The snow melting system can be manually turned off and the control remains off until manually changed back to Auto. This allows the installer or end user to permanently disable the snow melting system without removing power from the control.
Step 1: Step 2: Step 3: Step 4: Step 5:
Press and hold the Home button for 3 seconds. Press NEXT to navigate to the Override menu. Press ENTER to enter the Override menu. Select Manual Override to Off. Exit the Manual Override by selecting Auto.
Switch Settings
1058-01
Switch
H1220A
Lock
ON
Snow Melting Control 654
tekmarNet Electric or Hydronic Boiler/Mixing
www.tekmarControls.com
Settings
2
1
Power: 24 V (ac) ±10%, 60 Hz, Class 2, 16 VA standby, 100 VA fully loaded
Unlock
Relays: 24 V (ac) 2 A, 3.5 A combined
Unused
Designed and assembled in Canada Meets Class B: ICES & FCC Part 15
Switch
Back of Control
9 of 44 © 2013 654_D - 06/13
1
2
Position
ON
OFF
ON
OFF
Action
LOCK ACCESS LEVEL
The control is locally locked and the access level cannot be changed. Set to Lock when installation has been completed.
UNLOCK ACCESS LEVEL
The control is unlocked and the access level may be changed. Go to the Toolbox menu to change the access level. Set to Unlock during the installation process.
Note: tekmarNet
®
system controls include a Global Lock that locks all connected snow melt controls, and thermostats. Set the tekmarNet® system control to unlock to allow access level adjustment on all connected devices.
Not used Not used
Page 10
User Interface
Display
Status Field
Operation Field
Touch to display Run Time, Outdoor & Slab Temperature
Touch to quickly enter the View menu
Touch to turn system
off while away
Touch to
Melt or Stop
Touch to adjust settings
Operation Field
MELT System is melting snow or ice.
IDLE System is idling.
Status Field
WWSD
CWCO Cold Weather Cut Out. Too cold to melt.
TIMED
Warm Weather Shut Down. The slab is naturally warm enough to melt snow or ice.
Timed melting operation. System operates until time has elapsed.
Touch to go to the next setting
Home Button Return to the Home Screen
Press and hold for 3 seconds to access the
Home
Button
ENTER
programming menus.
STRM System is in storm operation.
OFF System is off.
PEND
WAIT
SENSOR
Pending. The system has detected water but it is too cold to operate or the schedule is in Idle or Off.
Zone priority in effect. Zone must wait until higher priority zone finishes melting.
Tandem 090 sensor.
WARM Slab is warming up to the melting temperature.
AWAY
Away scene. No melting until the away scene is exited.
Symbols
HEAT ON
Heat is turned on.
tekmarNet
Communication is present.
© 2013 654_D - 06/13 10 of 44
®
TRACK
This zone tracks the melting operation of zone 1.
WARNING SYMBOL
Indicates an error is present.
ARROWS
Adjust the displayed setting.
Page 11
Programmable Settings
--------------------
------------------------------------
Programming Menus
Press and hold the Home button for 3 seconds to enter the programming menus. The control returns to the last programming menu previously used.
Press and hold for 3 seconds to access the programming menus.
Select a Programming Menu
Touch “NEXT” to advance (clockwise in above illustration)
• to the next menu.
Touch “BACK” to go backwards (counterclockwise in above illustration) through the menus.
Touch “ENTER” to enter a menu.
--------------------
Access Levels and Access Level Lock
The control is shipped pre-programmed with common settings. The control has an “Installer” access level that allows full access to all settings and a “User” access level that restricts the number of settings available. The control defaults to the “
User” access level after 12 hours of operation.
Notice: tekmarNet® system controls include a Global Lock that locks all connected snow melting controls and thermostats. Set the tekmarNet® system control to unlock to allow access level adjustment on all connected devices.
Setting Items
Touch or arrow to adjust the setting if required.
Touch “NEXT ITEM” to advance to the next item within the menu.
Touch “BACK ITEM” to go backwards to the previous item within the menu.
To return to the parent menu after changing a setting, press and release the Home button.
To return to the Home screen, press and release the Home button twice or wait 30 seconds to automatically return to the Home screen.
To change to the “Installer” access level:
In the Toolbox menu, locate Access Adjust the access level to “Installer” by pressing the up or down
• button. This will permit setting changes to the control.
------------------------------------
11 of 44 © 2013 654_D - 06/13
Page 12
View Menu (1 of 2)
The View menu items display the current operating temperatures and status information of the system.
Item Field Range Access Description Set to
1 to 12
– – –, -76 to
149°F
(-60 to 65°C)
– – –, -76 to
149°F
(-60 to 65°C)
-76 to 149°F
(-60 to 65°C)
DRY or WET
User
Installer
User
Installer
Installer
User
Installer
User
Installer
SNOW ZONE
The snow melt zone number on the tekmarNet® system.
Conditions: tekmarNet
OUTDOOR
Current outdoor air temperature as measured by the local or remote outdoor sensor. The outdoor air temperature is shared to all devices in the tekmarNet® system. “– – –” is displayed when no outdoor sensor is available.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
SLAB TARGET
The calculated slab target of the snow melting system. “– – –” is displayed when the snow melt control is off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec and a snow/ice sensor or slab sensor is installed.
SLAB
Current slab temperature as measured by the control. Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.
WATER SENSOR
Current status of the water detection sensor. Conditions: A snow/ice sensor or snow sensor is installed.
®
communication available.
---, 70 to 200°F
(21.0 to 93.5°C)
---, 70 to 200°F
(21.0 to 93.5°C)
-58 to 212°F
(50.0 to 100.5°C)
-58 to 212°F
(50.0 to 100.5°C)
0 to 100% Installer
Installer
Installer
Installer
Installer
BOILER TARGET
The calculated boiler target of the snow melt system. “– – –” is displayed when the snow melt control is not operating the boiler.
Conditions: Application Mode is set to Boil.
MIX TARGET
The calculated mix target of the snow melt system. “– – –” is displayed when the snow melt control is not operating the mixing valve or mixing injection pump.
Conditions: Application Mode is set to Mix.
SUPPLY
Current system supply temperature as measured by the control.
Conditions: Application Mode is set to PWM, Boil or Mix.
BOILER RETURN
Current boiler return temperature as measured by the control.
Conditions: Application Mode is set to PWM, Boil or Mix and Out/Bret Sensor is set to Bret (boiler return sensor).
MIX RATE
Current position of the mixing valve or mixing injection pump speed.
Conditions: Application Mode is set to Mix.
BOILER RATE
0 to 100% Installer
© 2013 654_D - 06/13 12 of 44
Current firing rate of the modulating boiler. Conditions: Application Mode is set to Boil and Boiler Type
is set to Mod (modulating boiler).
Page 13
View Menu (2 of 2)
Item Field Range Access Description Set to
HEAT RELAY
OFF or ON
User
Installer
0 to 100% Installer
Current status of the heat relay. The boiler, pump or electric cable is on when ON is displayed. The boiler, pump or electric cable is off when OFF is displayed.
Conditions: Application Mode is set to PWM, Boil, Mix, or Elec.
PWM RATE
Current duty cycle rate of the zone or boiler for each 20 minute cycle.
Conditions: Application Mode is set to PWM or Elec. Not visible when Manual Override is not Auto.
OFF or ON
OFF or ON
00:00 to 24:00
hours
00:00 to 6:00
hours
User
Installer
User
Installer
User
Installer
User
Installer
SYSTEM PUMP RELAY
Current status of the system pump relay. Conditions: Application Mode is set to PWM, Boil or Mix and
Auxiliary Relay is set to SYS (system pump).
ALERT RELAY
Current status of the alert relay. Conditions: Application Mode is set to PWM, Boil or Mix and
Auxiliary Relay is set to ALRT (alert) or Application Mode is set to Elec.
MANUAL MELT TIME
When manually started, the display shows the remaining run time before shutting off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
ADDITIONAL MELT TIME
When automatically started by a Snow/Ice Sensor 090 or 094, the display shows the remaining run time before shutting off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec and a snow / ice sensor 090 or 094 is installed.
13 of 44 © 2013 654_D - 06/13
Page 14
Set Temp Menu
The Set Temp menu items select the operating temperatures of the snow melt system.
Item Field Range Access Description Set to
32 to 95°F
(0.0 to 35.0°C)
Default = 36°F
(2.0°C)
OFF, 20 to 95°F
(-6.5 to 35.0°C)
Default = OFF
OFF, 20 to 95°F
(-6.5 to 35.0°C)
Default = 28°F
(-2.0°C)
User
Installer
Installer
Installer
MELTING
Select the desired surface temperature of the snow melt surface when melting.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
IDLING
Select the desired surface temperature of the snow melt surface when idling. Idling pre-heats the slab when the slab is dry but cold and allows faster reaction time to reach the melting temperature. Recommended for commercial use only.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
STORM
Select the desired surface temperature of the snow melt surface while operating in the storm operation. Storm operation temporarily pre-heats the slab to allow faster reaction time to reach the melting temperature.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
0:30 to 24:00
hours
Default = 4:00
hours
0:00 to 6:00
hours
Default = 0:00
hours
0:30 to 24:00
hours
Default = 8:00
hours
AUTO, MIN, -2,
-1, MID, +1, +2, MAX
Default = AUTO
AUTO, 32 to
95°F
(0.0 to 35.0°C)
Default = AUTO
User
Installer
Installer
Installer
Installer
Installer
MANUAL MELT RUN TIME
Select the amount of running time when manually starting the system.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
ADDITIONAL MELT TIME
Select the amount of additional melting time after the Snow / Ice Sensor 090 or 094 is dry. This allows low spots on the slab to fully dry before the snow melting system is shut off.
Conditions: Conditions: Application Mode is set to PWM, Boil, Mix or Elec and a Snow / Ice Sensor is installed or Track Zone is set to On.
STORM RUN TIME
Select the amount of storm run time to pre-heat the slab when advised of a winter storm warning.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec and Storm is set to a temperature.
WATER SENSITIVITY
Select how sensitive the Snow / Ice Sensor 090 or 094, or the Snow Sensor 095 is to water detection.
Conditions: Snow / Ice Sensor is set to 090 or 095.
WARM WEATHER SHUT DOWN
Select the temperature at which to shut down the snow melting system during warm weather. This allows the snow or ice to melt off the slab naturally.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
OFF, -30 to 50°F (-34.5 to 10.0°C)
Default = 10°F
Installer
(-12.0°C)
© 2013 654_D - 06/13 14 of 44
COLD WEATHER CUT OUT
Select the temperature at which to shut down the snow melting system during extremely cold weather. Below this temperature, the heat loss of the slab exceeds the capacity of the boiler or heating appliance.
Page 15
Time Menu
Time settings are only required when using a programmable schedule. The Time menu is not available when the Application Mode is set to 090.
Item Field Range Access Description Set to
00 to 59
Default = 00
12 AM to 11 PM
00 to 23
Default = 12 AM
Sunday, Monday,
Tuesday,
Wednesday,
Thursday, Friday,
Saturday
JANUARY to
DECEMBER
1 to 31
Default = 1
2006 to 2038
Default = 2013
User
Installer
User
Installer
User
Installer
User
Installer
User
Installer
User
Installer
MINUTE
Select the current time minutes.
HOURS
Select the current time hours.
DAY OF WEEK
Select the current day of the week.
MONTH
Select the current month. Conditions: Available when Daylight Savings Time is On.
DAY OF MONTH
Select the day of the current month. Conditions: Available when Daylight Savings Time is On.
YEAR
Select the current year. Conditions: Available when Daylight Savings Time is On.
OFF or ON
Default = ON
12 or 24 hour
Default = 12 hour
OFF or ON
Default = OFF
User
Installer
User
Installer
User
Installer
DAYLIGHT SAVINGS TIME
Select if daylight savings time is observed.
TIME MODE
Select either 12 or 24 hour time format.
CLOCK
Select whether or not to show the time clock on the display.
15 of 44 © 2013 654_D - 06/13
Page 16
Schedule Menu
The Schedule menu can operate on a 24 hour or 7 day repeating schedule. When a 24 hour schedule is selected, “SuMoTuWeThFrSa” is shown on the top of the screen to show that the event time applies to all days of the week. When a 7 day schedule is selected, each individual day of the week is shown with the event time.
The Schedule menu is not available when the Application Mode is set to 090.
Item Field Range Access Description Set to
12:00 AM to 11:50
SuMoTuWeThFrSa
SuMoTuWeThFrSa
PM, SKIP
or
00:00 to 23:50,
SKIP
Default = 6:00 AM 12:00 AM to 11:50
PM, SKIP
or
00:00 to 23:50,
SKIP
Default =
10:00 PM when
Event/Day is 2
8:00AM when
Event/Day is 4
User
Installer
User
Installer
EVENT 1
The first programmable schedule time period of the day. During Event 1 the control operates in MELT operation.
EVENT 2
The first programmable schedule time period of the day. During Event 2 the control operates in OFF or IDLE operation.
SuMoTuWeThFrSa
SuMoTuWeThFrSa
12:00 AM to 11:50
PM, SKIP
or
00:00 to 23:50,
SKIP
Default = 6:00 PM 12:00 AM to 11:50
PM, SKIP
or
00:00 to 23:50,
SKIP
Default = 10:00
PM
Always available
OFF, ZONE
Available with
tekmarNet
®
OFF, ZONE,
Master 1, 2, 3, 4,
Member 1, 2, 3, 4
Default = OFF
User
Installer
User
Installer
User
Installer
EVENT 3
The first programmable schedule time period of the day. During Event 3 the control operates in MELT operation.
EVENT 4
The first programmable schedule time period of the day. During Event 4 the control operates in OFF or IDLE operation.
SCHEDULE
Select if the control should change the temperature automatically using a programmable schedule.
OFF = Programmable schedule is not used. Zone = Applies to this control only. Master 1, 2, 3, 4 = In charge of one of four available
network schedules. Member 1, 2, 3, 4 = Follows selected network
schedule.
2 or 4
Default = 2
24 hour or 7 day
Default = 24 hour
© 2013 654_D - 06/13 16 of 44
User
Installer
User
Installer
EVENT PER DAY
Select the number of temperatures per day.
24 HOUR / 7 DAY
Select between a 24 hour schedule or a 7 days per week schedule.
Page 17
Display Menu
The Display menu items select the temperature units and backlight options.
Item Field Range Access Description Set to
°F or °C
Default = °F
User
Installer
UNITS
Select Fahrenheit or Celsius as the temperature units.
BACKLIGHT
ON,
ON MELT,
OFF
Default =
ON MELT
User
Installer
Select how the display backlight operates. ON = Always on. ON MELT = On when melting, off when not melting.
This provides a visual indicator to occupants that the snow melting system is currently melting.
OFF = Always off.
Scene Menu
The Scene menu items selects if the away scene and the away key are available. The Scenes menu is not available when the Application Mode is set to 090.
Item Field Range Access Description Set to
NONE or AWAY
Default = NONE
User
Installer
SCENES
Enable or disable the use of scenes (building overrides) on this control.
OFF or ON
Default = OFF
User
Installer
AWAY KEY
Enable or disable the away touch key on the home screen.
Condition: Scenes must be set to Away.
17 of 44 © 2013 654_D - 06/13
Page 18
Monitor Menu
The Monitor menu items provide information about the system’s operation and performance.
when the Application Mode is set to 090.
Item Field Range Access Description
HEAT HOURS
Records the number of running hours since the item was last reset. Touch the number and then the ENTER key to reset to zero.
0 to 9999 hours
User
Installer
HEAT CYCLES
0 to 9999 hours Installer
Records the numbers of cycles of the heat relay since the item was last reset. Touch the number and then the ENTER key to reset to zero.
SYSTEM PUMP HOURS
0 to 9999 hours
User
Installer
Records the system pump running hours since the item was last reset. Touch the number and then the ENTER key to reset to zero.
Conditions: Auxiliary Relay is set to SYS (system pump).
SLAB HIGH
-58 to 167°F
(-50.0 to 75.0°C)
Installer
Records the highest slab temperature since the item was last reset. Touch the number and then the ENTER key to reset.
Conditions: Snow / Ice Sensor is set to 090 or Slab Sensor is set to On.
SLAB LOW
-58 to 167°F
(-50.0 to 75.0°C)
Installer
Records the lowest slab temperature since the item was last reset. Touch the number and then the ENTER key to reset.
Conditions: Snow / Ice Sensor is set to 090 or Slab Sensor is set to On.
The Monitor menu is not available
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
Installer
Installer
Installer
Installer
Installer
Installer
OUTDOOR HIGH
Records the highest outdoor temperature since the item was last reset. Touch the number and then the ENTER key to reset.
OUTDOOR LOW
Records the lowest outdoor temperature since the item was last reset. Touch the number and then the ENTER key to reset.
SUPPLY HIGH
Records the highest supply temperature since the item was last reset. Touch the number and then the ENTER key to reset.
Conditions: Application Mode is set to PWM, Boil or Mix.
SUPPLY LOW
Records the lowest supply temperature since the item was last reset. Touch the number and then the ENTER key to reset.
Conditions: Application Mode is set to PWM, Boil or Mix.
BOILER RETURN HIGH
Records the highest boiler return temperature since the item was last reset. Touch the number and then the ENTER key to reset.
Conditions: Application Mode is set to PWM, Boil or Mix and Out/Bret Sensor is set to RET (return).
BOILER RETURN LOW
Records the lowest boiler return temperature since the item was last reset. Touch the number and then the ENTER key to reset.
Conditions: Application Mode is set to PWM, Boil or Mix and Out/Bret Sensor is set to RET (return).
© 2013 654_D - 06/13 18 of 44
Page 19
Toolbox Menu
The Toolbox Menu is a location for system information and Test functions. If any errors are present on the system, they will be located at the beginning of this menu.
Item Field Range Access Description
ACCESS LEVEL
Installer (INST)
User (USER)
Default = INST
User
Installer
Select the access level of the control, which determines which menus and items are available.
Conditions: Adjustable only when control switch setting set to UNLOCK or tekmarNet® system control switch setting set to UNLOCK.
Software J1226A
Type 654
User
Installer
Not applicable Installer
See Troubleshooting
Guide
Installer
SOFTWARE VERSION AND TYPE NUMBER
Select the access level of the control, which determines which menus and items are available.
FACTORY DEFAULTS
Loads the factory default settings. Press ENTER to load defaults.
HISTORY - 1 THROUGH 5
Displays a history of any past errors that have occurred on the system. Will clear after 30 days, or press Up and Down buttons for 1 second to manually clear. The last 5 history items will display if present.
19 of 44 © 2013 654_D - 06/13
Page 20
Override Menu
The Override Menu allows an operator to manually test each relay and manually start the system.
Item Field Range Access Description
Hydronic
AUTO, HAND,
MAX, PRGE, OFF
Electric
AUTO, HAND,
TEST, OFF
Default = AUTO
OFF or ON
Default = OFF
OFF or ON
Default = OFF
0 to 100%
Default = 0%
0 to 100%
Default = 0%
Installer
Installer
Installer
Installer
Installer
MANUAL OVERRIDE
Manually override the normal automatic operation of the control to test the equipment or operate the system at the maximum temperature limits.
AUTO = Normal operation HAND = Manual override of each relay output MAX = Operate hydronic system at maximum heat TEST = Operate electric system for 10 minutes PRGE = Hydronic system purge operates pumps to help bleed air
from the system
SYSTEM PUMP RELAY
Manually turn on the system pump during the HAND Manual Override.
HEAT RELAY
Manually turn on the heat during the HAND Manual Override.
BOILER PERCENT
Manually set the modulating boiler firing rate during the HAND
Manual Override.
Conditions: Application Mode is set to Boil.
MIX PERCENT
Manually set the mixing valve or mixing injection pump output during the HAND Manual Override.
Conditions: Application Mode is set to Mix.
OFF or ON
Default = OFF
0:10 to 72:00
hours
Default = 0:10
hours
0:10 to 72:00
hours
Default = 24:00
hours
0:10 to 72:00
hours
Default = 24:00
hours
Installer
Installer
Installer
Installer
ALERT RELAY
Manually turn on the alert relay during the HAND Manual
Override.
Conditions: Application Mode is set to PWM, Boil or Mix and Alert Relay is set to ALRT (alert) or the Application Mode is set to Elec.
OVERRIDE TIME
Select the amount of time that the HAND before returning to Automatic operation.
Manual Override
is in effect
MAXIMUM PURGE TIME
Select the amount of time that the PURGE Manual Override is in effect before returning to Automatic operation.
Conditions: Application Mode is set to PWM, Boil or Mix.
MAXIMUM HEAT TIME
Select the amount of time that the MAX HEAT Manual Override is in effect before returning to Automatic operation.
Conditions: Application Mode is set to PWM, Boil or Mix.
© 2013 654_D - 06/13 20 of 44
Page 21
System Menu
The System Menu provides settings on how to configure and operate the mechanical equipment.
Item Field Range Access Description Set to
APPLICATION MODE
Select the control application mode.
PWM, BOIL, MIX,
ELEC, 090
Default = PWM
Installer
PWM = Hydronic Pulse Width Modulation. BOIL = Hydronic boiler heats snow melting system. MIX = Hydronic mixing valve or injection pump heats
snow melting system. ELEC = Electric snow melt. 090 = Tandem Snow/ Ice Detection using 090 or 094
NONE,
090 (or 094),
095
Default = 090
OFF or ON
Default = ON
OFF or ON
Default = ON
OFF,
OUT
(Outdoor) or
BRET (Boiler Return)
Default = OUT
OFF or ON
Default = OFF
Installer
Installer
Installer
Installer
Installer
SNOW / ICE SENSOR
Select if a Snow / Ice Sensor 090 or 094, or Snow Sensor 095 is installed.
SLAB SENSOR
Select if a Slab Sensor 072 or 073 is installed to measure the slab temperature.
Conditions: Application Mode is set to PWM, Boil or Mix and Snow / Ice Sensor is set to None or 095.
SLAB PROTECTION
Select if the slab should be protected from large temperature differentials to avoid cracking the concrete due to high tensile stress.
Conditions: Application Mode is set to Boil or Mix and Snow / Ice Sensor is set to 090 or Slab Sensor is set to On.
OUTDOOR OR BOILER RETURN SENSOR
Select if the Out/Bret wiring terminal is connected to an outdoor sensor or a boiler return sensor.
Conditions: Application Mode is set to PWM, Boil or Mix or Elec.
ECONOMELT
EconoMelt allows the user to mechancially remove snow then manually start the system to melt the thin snow layer or ice.
Conditions: Application Mode is set to PWM, Boil or Mix or Elec.
tekmarNet® SYSTEM PUMP
OFF or ON
Default = ON
SYS (System Pump)
or
ALRT (Alert)
Default = SYS
Installer
Installer
Select if the system pump located on the tekmarNet® System Control should operate when the snow melt zone is heating.
Conditions: Application Mode is set to PWM, Boil or Mix and Boiler Type is set to CTRL (tN4 control).
AUXILIARY RELAY
Select if the auxiliary relay should function as system pump or as an alert.
Conditions: Application Mode is set to PWM, Boil or Mix.
MAXIMUM MELT TIME
0.5 to 7.0 days, OFF Default = 3.0 days
21 of 44 © 2013 654_D - 06/13
Installer
Select to limit the amount of melting run time after snow is automatically detected by a Snow / Ice Sensor 090 or 094, or a Snow Sensor 095.
Conditions: Application Mode is set to PWM, Boil or Mix or Elec.
Page 22
Boiler Menu
The Boiler Menu provides settings on how to configure and operate the boiler.
Item Field Range Access Description Set to
App Mode = Boil
MOD, 1STG, EMS1, EMS2
Default = MOD
App Mode = Mix
OFF, ENBL,
CTRL
Default = OFF
App Mode = PWM
OFF, CTRL
Default = OFF
0-10 or 4-20
Default = 0-10
Installer
Installer
BOILER TYPE
The type of boiler connected to the control. MOD = Modulating boiler. 1STG = Single one-stage on-off boiler. EMS1 = tekmar boiler staging controls. EMS2 = Viessmann modulating boilers with 0-10 V
OpenTherm Module. CTRL = tekmarNet ENBL = When operating a mixing valve or mixing
injection pump, the heat relay is closed to fire the boiler.
®
System Control operates boiler.
BOILER MODULATION TYPE
Select if the modulating boiler accepts a 0-10 V (dc) or 4-20 mA input signal to control the boiler firing rate.
Conditions: Boiler Type is set to MOD (modulating boiler).
0 to 50%
Default = 0%
OFF, 10 to 180
seconds
Default = OFF
30 to 230 seconds
Default = 30 seconds
AUTO, 2 to 42°F
(1.0 to 23.5°C)
Default = AUTO
OFF, 50 to 180°F
(10.0 to 82.0°C)
Default = OFF
Installer
Installer
Installer
Installer
Installer
BOILER MINIMUM MODULATION
The minimum percent modulation of the boiler burner. Conditions: Boiler Type is set to MOD (modulating
boiler).
BOILER MODULATION DELAY
Delay time between the burner firing and the boiler releasing to modulation.
Conditions: Boiler Type is set to MOD (modulating boiler).
BOILER MOTOR SPEED
The time required for the modulating actuating motor to fully open the gas valve or ramp the burner fan from off to full speed on a modulating boiler. Set to 30 seconds unless otherwise recommended by the boiler manufacturer.
Conditions: Boiler Type is set to MOD (modulating boiler).
BOILER DIFFERENTIAL
The temperature differential that the control is to use to cycle the boiler on and off (half above and half below target).
Conditions: Boiler Type is set to MOD (modulating boiler) or 1STG (one stage).
BOILER MINIMUM
The minimum allowed boiler target temperature and boiler return protection temperature. Check the boiler manufacturer’s manual for recommended supply water temperatures.
Conditions: Application Mode is set to Boil or Application Mode is set to Mix and the Boiler Type is set to CTRL (tN4 Control) and Out/Bret Sensor is set to RET (return).
© 2013 654_D - 06/13 22 of 44
Page 23
Mix Menu
The Mix Menu provides settings on how to configure and operate the mixing valve or mixing injection pump. only available when the Application Mode is set to Mix.
Item Field Range Access Description Set to
MIX TYPE
0-10 or 4-20
Default = 0-10
30 to 230
seconds
Default = 105
seconds
Installer
Installer
Select the type of mixing analog signal. 0-10 = 0 to 10 V (dc) 4-20 = 4 to 20 mA
MIX MOTOR SPEED
The time that the mix actuating motor requires to operate from fully closed to fully open.
Mixing Injection Pump = 30 seconds tekmar Actuator Motor 741 = 105 seconds Refer to actuating motor for correct setting.
The Mix menu is
80 to 180
°F
(26.5°C to 82.0°C),
OFF
Default = 140°F
(60
°C)
Installer
MIX MAXIMUM
Select the maximum operating temperature of the system supply water.
23 of 44 © 2013 654_D - 06/13
Page 24
tekmarNet® Menu
The tekmarNet® menu includes settings of how the snow melting control communicates and operates together with other controls. The tekmarNet® menu is only available when communication is detected.
Item Field Range Access Description Set to
Range: AUTO,
01 to 24, b:01 to b:24, 1:01 to 1:24,
Installer
2:01 to 2:24,
3:01 to 3:24
1 to 24 Installer
ADDRESS
The tekmarNet® address of this control. To manually set the address, use the up or down arrow buttons.
DEVICE COUNT
Provides a count of all the tekmarNet® thermostats, setpoint controls and snow melting controls on the tekmarNet® system.
1 to 12
Default = 1
OFF or ON
Default = OFF
1 to 12
Default = 1
1 to 12
Default = 12
Installer
Installer
Installer
Installer
SNOW ZONE
Select the Snow Zone that this control operates. Snow Zone 1 has the highest priority while Snow Zone 12 has the lowest priority.
TRACK ZONE
Select to track and record the running hours of Snow Zone 1 and repeats this run time on this control. This allows snow zones without a snow / ice sensor to automatically start.
Conditions: Snow Zone must be set 2 through 12 (cannot be Snow Zone 1) and Application Mode is set to PWM, Boil, Mix or Elec.
MELT GROUP
A User Switch may be used to manually start melting the snow zone. Set the Melt Group number to the corresponding Setpoint Enable number on the User Switch.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
STORM GROUP
A User Switch may be used to manually start storm operation of the snow zone. Set the Melt Group number to the corresponding Setpoint Enable number on the User Switch.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
OFF, COND,
FULL
Default = OFF
Installer
PRIORITY
Select the priority operation of the snow melting system. Conditions: Application Mode is PWM, Mix or Elec.
LOCAL NETWORK GROUP
Select if scenes and time clock are shared when
OFF or ON
Default = OFF
Installer
connected to a tekmarNet® system. OFF = Send and receive messages. ON = Receive messages only.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec.
© 2013 654_D - 06/13 24 of 44
Page 25
Sequence of Operation
Snow Melting Overview
A snow melting system can offer a safe, convenient, and cost effective way of removing snow and ice from the snow melting slab and similar surfaces. Safety is increased by activating the snow melting system as soon as the snow falls rather than waiting for mechanical snow removal after snow has accumulated. This eliminates slip hazards and reduces the risk of injury by mechanized snow melting equipment, thereby reducing potential liability costs. The elimination of snow plow equipment and corrosive salts also reduces damage to the slab surface and to the environment. Snow melting systems when controlled correctly can be cost competitive compared to mechanical snow removal.
Slab Temperature Control
Controlling the slab temperature is critical to minimizing the cost of snow melting. This requires that either a Snow / Ice Sensor 090 or 094 or a Slab Sensor 072 or 073 is installed. The Snow / Ice Sensor contains a built-in slab temperature sensor. While the control will continue to operate without a slab sensor installed, operating costs will be much higher.
The slab is operated using slab outdoor reset. As the outdoor temperature gets colder, the heat loss of the slab increases. In order to keep the slab surface at a constant temperature while operating, the inner core of the slab must be heated above the melt, idle or storm temperature setting. The amount that the slab inner core temperature is above the melt, idle or storm setting is proportional to the outdoor temperature. Since the slab sensor is installed below the surface of the slab, it is not measuring the true slab surface temperature but rather the inner core temperature. The control automatically compensates for this temperature difference. However, the
The snow melting control can operate in one of four different ways:
Melt Idle
Heats the slab to melt snow or ice Pre-heats the slab just below freezing to shorten the
time required to melt snow
Storm
Temporarily pre-heats the slab just below freezing to shorten the time required to melt snow
Off
Snow melting system is off
The control display shows the control operation in the home screen.
Slab item in the View menu displays the actual measured temperature, so it is normal to view slab temperatures that exceed the melt, idle, or storm temperature settings.
Slab Outdoor ResetSlab Outdoor Reset
Surface temperature = 35F
Core (sensor)
is warmer
Decreasing Air Temperature
Slab Surface Temperature is Constant
Increasing Slab Core Temperature
Melt Operation
The snow melting system operates the heating equipment to heat the slab from a cold start or from the idle or storm temperature to reach the melt temperature setting to melt snow or ice. Melt operation can be triggered automati­cally using a snow / ice sensor, by tracking the run time of another zone, manually by pressing a button, or by a
25 of 44 © 2013 654_D - 06/13
programmable schedule. The melt temperature setting affects calculated targets such as the slab target, boiler target and mix target.
Page 26
Melt - Manual Start and Timed Stop
The snow melting system can be started manually in one of three different methods:
Touch the Melt key on the control display.
• Press the Setpoint Enable button on a User Switch.
• Activate through a Gateway webpage or home automation
• system.
Press
Melt
tN4 User Switch
480 or 481
Storm
Press
Melt
Melt
Away
Once manually started, the snow melting system continues to operate until the time set by the Manual Melt Run Time setting in the Set Temp menu elapses.
If a manual start has been provided and a Snow / Ice Sensor detects water, the control changes from manual melt to automatic operation. The snow melting system will continue to operate until the sensor is dry and the Additional Melt Time elapses.
095 detects water
Touch MELT key
095 detects water
Tracked zone melt
Idle
or
Off
User Switch / Gateway Enable
MANUAL MELT RUN TIME elapses
Tracked zone time elapses
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
CWCO
Timed
Melt
Melt - Automatic Start and Stop
Automatic start and stop operation requires the installation of a Snow / Ice Sensor 090 (65' or 20 m cable) or 094 (210' or 64 m cable). The control continually monitors the sensor for the presence of moisture and slab temperature condi­tions in which snow or ice may be present. When moisture is detected, the control will show “Sensor Water Wet” in the View menu. When the sensor is dry the control will show “Sensor Water Dry”. The control includes a Sensitivity setting in the Set Temp menu that allows the installer to adjust the amount of moisture required to start and stop the melting operation. In areas with low amounts of dust and / or air pollution, the sensitivity may need to be increased. The Sensitivity setting default is Auto, and the control will automatically determine the best suitable sensitivity setting for the installation.
Snow / Ice Sensor
090 or 094
When moisture is detected and the slab and outdoor temperatures are at or below freezing, the control will automatically start the snow melting system. As the snow or ice melts and the slab dries off, the sensor also dries off at the same time. When the sensor is dry, the snow melt system automatically shuts off. If there are low spots on the slab surface that dry off slower than the sensor, additional melting run time can be included by adjusting the Additional Melt Time setting in the Set Temp menu.
If the snow melting system is manually stopped, the Snow / Ice Sensor must fully dry before it is able to detect a new snow fall and automatically start the snow melting system.
090 or 094 detects water
090 or 094 and slab dry and
Idle
or
Off
ADD MELT time elapses
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
Auto
Melt
© 2013 654_D - 06/13 26 of 44
Enters
CWCO
Melt
Suspended
Exits
CWCO
Page 27
Melt - EconoMelt
When a Snow / Ice Sensor 090 or 094 is installed, the installer can choose to select to either automatically or manually start the snow melting system. Selecting EconoMelt to On provides the option to remove the snow using a snow plow or shovel and then use the snow melting system to melt the remaining thin layer of snow or ice that mechanical snow removal methods are unable to remove. The snow melting system stops when the sensor is dry. The factory default for EconoMelt is Off.
Melt - Automatic Start and Timed Stop
Automatic start with a timed stop operation requires the instal­lation of a Snow Sensor 095. It is also highly recommended to install a Slab Sensor 072 (20’ or 6 m cable) or 073 (40’ or 12 m cable) in order to regulate the slab temperature and operate the snow melting system at the highest possible efficiency. The control continually monitors the sensor for the presence of moisture and slab temperature conditions in which snow or ice may be present. When moisture is detected, the control will show “Sensor Water Wet” in the View menu. When the sensor is dry the control will show “Sensor Water Dry”. The control includes a Sensitivity setting in the Set Temp menu that allows the installer to adjust the amount of moisture required to start
Touch START key
090 and slab dry and
ADD MELT time elapses
Off
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
Enters
CWCO
Melt
Melt
Suspended
Exits
CWCO
and stop the melting operation. In areas with low amounts of dust and / or air pollution, the sensitivity may need to be increased. The factory default is for the Sensitivity setting is Auto. The control automatically determines the best suitable sensitivity setting for the installation.
When moisture is detected and both the slab and outdoor temperatures are below the Melting setting, the control auto­matically starts the snow melting system. The snow melting system operates to heat the slab to the slab target temperature and continues to operate until the time set by the Manual Melt Run Time in the Set Temp menu elapses.
Snow
Sensor 095
Idle
or
Off
Touch MELT key 095 detects water Tracked zone melt
User Switch / Gateway Enable
MANUAL MELT RUN TIME elapses
Tracked zone time elapses
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
CWCO
095 detects water
Timed
Melt
27 of 44 © 2013 654_D - 06/13
Page 28
Melt - Tracked Start and Stop
--------------
----------
The snow melting system can have multiple zones. Zones have the option to track the melting run time of zone 1. This is useful in cases where zone 1 has an automatic Snow / Ice Sensor installed and the remaining zones do not. This allows zones 2 to 12 to gain the functionality of automatic starting and stopping with only one Snow / Ice sensor installed in the system.
When zone 1 detects snow or ice, it starts melting. Zones with tracking enabled can also start melting unless priority is selected. When the sensor in zone 1 is dry or the Manual Melt Run Time has fully elapsed, it sends a signal to the tracked zones that zone 1 has stopped. Each zone can continue to operate to complete their own Additional Melt Time after which the zone stops heating and returns to the Off or Idle operation. Zones with priority selected start after zone 1 has finished melting and repeat the same run time as zone 1.
Track Melt Start and Stop
Zone 1
Snow / Ice
Sensor
Records
Run Time
Zone 2 Zone 3
Slab
Sensor
Repeats
Zone 1 Run
Time + Add
Melt Time
Slab
Sensor
Repeats Zone 1 Run Time + Add
Melt Time
Melt - Scheduled Start and Stop
The snow melting system can be started based upon a programmable schedule. The time clock must cross past the scheduled event time in order to start or stop. In addition, operation is dependent or whether or not a slab sensor, snow / ice, snow sensor or no slab sensor is installed.
The use of a programmable schedule is well suited for commercial installations where operation is not required 24 hours a day.
Systems With Automatic Detection
This applies when a Snow / Ice Sensor 090, 094 or Snow Sensor 095 is installed.
When the time clock reaches the schedule Event 1 (wake) time, the system is allowed to melt if the sensor detects snow or ice.
When the time clock reaches the schedule Event 2 (unoccupied) time, the system is off or in idle operation.
When the time clock reaches the schedule Event 3 (occupied) time, the system is allowed to melt if the sensor detects snow or ice.
--------------
When the time clock reaches the schedule Event 4 (sleep) time, the system is off or in idle operation.
Systems Without Automatic Detection
----------
This applies when a Slab Sensor 072, 073 or no slab sensor is installed and there is no automatic detection.
When the time clock reaches the schedule Event 1 (wake) time, the system is in melt operation.
When the time clock reaches the schedule Event 2 (unoccupied) time, the system is off or in idle operation.
When the time clock reaches the schedule Event 3 (occupied) time, the system is in melt operation.
When the time clock reaches the schedule Event 4 (sleep) time, the system is off or in idle operation.
Schedule event 1 Schedule event 2
Schedule event 3
Idle
or
Off
Schedule event 4
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
CWCO
Scheduled
Melt
© 2013 654_D - 06/13 28 of 44
Page 29
Additional Melting Time
A Snow / Ice Sensor 090 or 094 automatically shuts off the snow melting system when the water sensor is dry. Due to the construction of the slab and the layout of the heating pipe or electrical cable, there may be areas that do not melt completely. The Additional Melt Time setting in the Set Temp menu allows the installer to set addition melting time after the sensor is dry.
Idle Operation
When the snow melting system starts from a cold temperature, there may be a long time delay before the slab is warm enough to melt snow. This time delay allows snow to accumulate on the slab which is not acceptable in some commercial and institutional applications. To decrease the start up time, the slab can be pre-heated to maintain a minimum temperature. This is known as the Idle temperature. Idling requires large energy consumption is generally recommended for institutional and / or commercial installations where safety concerns are paramount. Idle is shown on the display when the control is in idle operation.
When designing a snow melting system, an engineer may specify the amount of allowed snow accumulation as the Snow-Free Area Ratio. There are three different levels. A Snow-Free Area Ratio of 1 is defined as a system that melts all snow as it falls with no allowed accumulation. This requires that the Idle temperature be set just below freezing. Examples of these types of applications include:
Hospital emergency areas
• Helicopter landing pads
• Parking garage ramps
A Snow-Free Area Ratio of 0.5 is defined as a system with partial snow accumulation on the slab but not in all areas. These types of systems may also use Idling but usually set
Snow Ice Sensor
Dry
at a temperature several degrees below freezing to reduce energy consumption. Applications may include:
Steep residential driveways
• Commercial sidewalks
• Loading docks
A Snow-Free Area Ratio of 0 is defined as a system that allows snow accumulation. These systems operate the snow melting system from a cold start resulting in the lowest energy consumption costs and the longest times to start melting snow. In this case set the Idle to off. This is recommended for most residential applications:
Flat residential driveways
• Patios
• Residential sidewalks
Some systems are designed for keeping a slab surface free of ice rather than free of snow. The most common applications include:
Car wash bays and aprons
• Aircraft hanger aprons
• Turf conditioning on golf course greens
These systems require the use of Idling at or near freezing through­out the winter and may result in high energy consumption.
Storm Operation
For many residential applications it is too costly to Idle the snow melt system all winter. Storm combines the benefits of a fast response time together with lower operating costs. The Storm operation does this by allowing the user to manually pre-heat the slab temporarily in preparation of a snow fall warning. In the event that snow falls and is detected by a Snow / Ice Sensor or a Snow Sensor or the system is manually started, the snow melt system heats the slab up to the melting temperature and completes a melting cycle. Should no snow fall during the storm time period, the control exits Storm operation and returns to Off.
The Storm operation is setup by setting the Storm temperature and the Storm Run Time in the Set Temp menu. The Storm operation can only be activated by a User Switch or Gateway. To respond to a User Switch or Gateway, select the Storm Group number to be 1 through 12. Then program the User Switch or Gateway setpoint enable to be the same as the Storm Group. Pressing the programmed User Switch button will now activate the Storm operation on the snow melting control.
29 of 44 © 2013 654_D - 06/13
Likewise, sending the setpoint enable command through the Gateway 482 will enable the Storm operation. On the Gateway 483, activating the storm group on the Scenes page in turn enables the Storm operation.
Press
Storm
Storm
Melt
Away
Page 30
Warm Weather Shut Down
---------------------------------------
--------------------------------------
--------------------------------
During warm weather, the slab is warm enough to naturally melt snow or ice. The control has a Warm Weather Shut Down (WWSD) setting in the Set Temp menu that prevents the control from entering Melt, Idle or Storm operation in order to conserve energy. The control shows WWSD on the display when WWSD is in effect.
Automatic (Auto)
The control enters WWSD when both the slab temperature of a zone and the outdoor temperature exceed the Melt temperature setting by more than 2°F (1°C).
Cold Weather Cut Out
Maintaining the melting or idling temperature during extremely cold temperatures is not only expensive but may be impos­sible if the heat loss of the slab exceeds the input capacity of the heating plant or electric cable. The control turns the snow melting system off when the outdoor air temperature drops below the Cold Weather Cut Out (CWCO) temperature and the slab is below freezing. This is a safety and energy saving measure. The control shows CWCO on the display
Away Scene
Manual WWSD
The control enters WWSD when the outdoor air temperature exceeds the WWSD setting by 1°F (0.5°C) and when the slab temperature exceeds 34°F (1°C). The control exits WWSD when the outdoor air temperature falls 1°F (0.5°C) below the WWSD setting or if the slab temperature falls below 34°F (1°C). This allows the Melt temperature setting to be set higher than the WWSD. This is useful when high slab temperatures are required to melt the snow or ice. An example of this are installations using paving bricks on top of sand and concrete layers.
when CWCO is in effect. When the temperature reaches the CWCO setting in an actively melting system with an 090 or 094, melting is suspended until the outdoor temperature rises above the CWCO setting. If an 090 or 094 is not installed, melting is permanently stopped when CWCO is in effect. Melting does not resume when the temperature rises above the CWCO setting.
Scenes provide an easy way to save energy while away on vacation, or override a programmable schedule when plans change.
Away Key
---------------------------------------
This control includes an Away Key to quickly disable the snow melting system, and when connected to a tekmarNet® system, can also turn down the heating temperature on all thermostats and suspend heating the domestic hot water tank to maximize energy savings. To turn on the Away Key, go to the Scene menu.
To activate the Away scene, touch “Going Away” on the screen.
Select PERM (permanent) or a number of days using the
• or arrow. Range is 1 to 180 days.
Press the home button to accept the setting or leave the
screen untouched for several seconds. “Scene Away” is displayed on the home screen until the
number of days expires. Touch “Cancel Away” to cancel at any time.
User Switch
A User Switch may be used to activate the Away scene.
Press
--------------------------------------
Storm
Melt
Away
Away
Additional Scenes
The snow melting control supports scenes 1 (normal) 2 (away) and 3 (unoccupied). Scene 3 disables the snow melting system. When the tekmarNet® system is set to scene 4 through 8, the snow melting control remains in scene 1.
--------------------------------
© 2013 654_D - 06/13 30 of 44
Page 31
Programmable Schedules
----------------------------------
--------------------------------
---------------------------------
To provide greater energy savings, the control can operate on a programmable schedule. The schedule is stored in memory and is not affected by loss of power to the control. If tekmarNet® communication is detected the control can become either a schedule member or schedule master.
Zone Schedule
The schedule only applies to the control. The control follows its own schedule and the events are not communicated to the tekmarNet® system.
Master Schedule
If the control is connected to other tekmarNet® devices, then the control can operate on a master schedule. A maximum of four master schedules are available on the tekmarNet® system. Using master schedules simplify installation since one master schedule may be used by multiple devices.
----------------------------------
--------------------------------
To create a master schedule:
Assign the control to be a schedule master by setting Schedule in the Schedule menu to Master (MST) 1 to 4.
Time Clock
The control has a built-in time clock to allow the control to operate on a schedule. A battery-less backup allows the control to keep time for up to 4 hours without power. The time
To follow a master schedule:
Assign the control to follow a master schedule by setting
• Schedule in the Schedule menu to Member (MBR) 1 to 4.
Schedule Types
The schedule type determines when the schedule repeats itself. This control includes two different schedule types:
• 24 Hour: Repeats every 24 hours.
• 7 Day: Repeats on a weekly basis and allows for separate
event times for each day.
---------------------------------
Events / Day
The events / day can be either 4 or 2. An event is a time at which the control changes the target temperature. The event time can be set to the nearest 10 minutes. To have the control skip the event, enter “SKIP“ as the time. SKIP is found between 11:50 PM and 12:00 AM or 23:50 and 00:00 hours.
clock supports automatic adjustment for Daylight Saving Time (DST) once the day, month and year are entered. Use the Time menu to set the correct time, day, month and year.
Snow Melt Zones and Priority
Dividing a system into a number of snow melting zones and prioritizing the zone operation reduces the size requirements of the hydronic heating plant or the amperage of the electri­cal service panel. This results in lower initial capital cost of the snow melting system. The trade off is that some snow melt zones may not be able to melt as soon as the snow fall begins and the user must tolerate snow accumulation on the slab. The snow melt system may have up to 12 snow melt zones. Zone 1 has the highest priority and zone 12 has the lowest. The priority setting in the tekmarNet® menu allows the installer to select the level of zone priority for entire snow melt system. Changing the priority setting on one control will update on all other snow melt controls at the same time.
The zone priority has 3 setting levels. There is some risk that lower priority zones may ice up when they are shut off by the higher priority zone. For example, if a high priority zone should finish melting and allow a lower priority zone to start melting, and then a new snow fall occurs, the high priority zone will shut off the lower priority zones. This may potentially allow the lower priority zones to ice over. The limitations of zoning and using priority must be carefully considered and discussed with the building owners and occupants when designing the snow melting system.
Priority does not apply when the application mode is set to Boiler. In this mode, the boiler is dedicated to a single snow melting zone so priority is no longer applicable.
31 of 44 © 2013 654_D - 06/13
Page 32
Hydronic Priority Levels
--------------------------------------------------------------------------------
---------------------------------------------------------------------------------
--------------------------------------------------------------------------------
Priority = None
All zones have the same priority and can operate at the same time.
This setting is recommended when the boiler plant capacity is sized larger than the heat loss of all zones at design conditions.
Priority = Conditional
The zone with the lower priority starts melting when the zone with higher priority is warm enough to melt snow or ice.
This setting is recommended when the boiler plant capacity is sized to be larger than the heat loss of each zone with some extra capacity.
Priority = Full
The zone with the lower priority starts melting once the zone with higher priority has finished melting all snow or ice from the slab.
This setting is recommended when the boiler plant capacity is sized to be the same as the heat loss of each zone at design conditions.
MELT
OFF
MELT
OFF
MELT
OFF
MELT
OFF
MELT
OFF
MELT
Zone 1
Zone 2
Zone 1
Zone 2
Zone 1
Electric Priority Levels
---------------------------------------------------------------------------------
Electric snow melting offers three levels of priority: None, Conditional and Full. The None and Full priority options function the same as with the hydronic operation. The Conditional priority is unique to electrical operation. The highest priority zone operates first. Whenever the highest priority zone shuts
MELT
OFF
MELT
OFF
Zone 1
Zone 2
OFF
Zone 2
off its relay, the lower priority zone is allowed to start melting and close its relay. Only one electrical relay is allowed to be on at any time. This eliminates large instantaneous demands and avoids surcharges from the electrical utility.
Zone 1 Relay
ON
OFF
Zone 2 Relay
ON
OFF
© 2013 654_D - 06/13 32 of 44
Page 33
Slab Protection
In a hydronic snow melting system, the boiler or heating plant capacity may be much larger than the load of the snow melting zones. This can result in large temperature differentials between the supply water temperature and the slab creating large tensile stresses on the slab. Concrete is weak to tensile forces and when repeatedly exposed to tensile loads the concrete may crack. This may be prevented by selecting the Protect Slab setting in the System menu to On. The control measures and limits the temperature differential between the supply water and the slab.
Application Modes
tensile stresses
The snow melting control can operate either an electric or a hydronic snow melting system. A hydronic system can be further categorized as either boiler, mixing or pulse width modulation zone operation, as well as, whether the boiler plant is dedicated or non-dedicated for the snow melting system. A dedicated boiler only provides heat from the snow melting system. A non-dedicated boiler provides heat for the snow melting system in addtion to the space heating and / or domestic hot water system. The control requires
Electric Operation
The control operates the heat relay on a 20 minute pulse width modulation cycle. The heat relay in turn activates a line voltage electrical contactor to energize the electrical cable heater installed in the slab. The heat relay on time is determined by the calculated slab target and by the measured slab temperature reading. As the slab temperature reaches the slab target, the on time per cycle of the heat relay is
Pulse Width Modulation Operation
The Application Mode should be set to Pulse Width Modulation (PWM) when the boiler or heat source is non-dedicated to the snow melting system and there is no mixing system. The snow melting system is considered to be a zone together with space heating and the domestic hot water system.
The control operates the heat relay on a 20 minute pulse width modulation cycle. The heat relay in turn activates the hydronic heating system zone pump or zone valve. The heat relay on time is determined by the calculated slab target and by the measured slab temperature reading. As the slab temperature reaches the slab target, the on time per cycle of the heat relay
that one of the following Application Modes is selected in the System menu:
PWM Pulse Width Modulation
BOIL Boiler Operation MIX Mixing Operation
• ELEC Electrical Operation
• 090 Tandem Snow / Ice Detection using an
090 or 094
reduced to prevent the slab temperature from overshooting. If no slab sensor is installed the heat relay remains on 100% of the time until the Melt operation has completed. Idle and Storm operation are not available when a slab sensor is not installed. The electric operation requires the installation of an outdoor sensor. A slab sensor is highly recommended in order to reduce operating costs.
is reduced to prevent the slab temperature from overshooting. If no slab sensor is installed the heat relay remains on 100% of the time until the Melt operation has completed. Idle and Storm operation are not available when a slab sensor is not installed. The hydronic PWM operation requires the installation of an outdoor sensor and a supply sensor. The supply sensor is installed on the glycol antifreeze system supply pipe and allows the control to provide Slab Protection and as well as Supply Zone Priority. A slab sensor is highly recommended in order to reduce operating costs.
Boiler Operation
The Application Mode should be set to Boil when the snow melting system has a dedicated boiler or heat source. The boiler is piped primary-secondary to the snow melting loop, allowing the boiler to fire on and off while allowing continu­ous flow through the snow melting system loop. The control calculates a Boiler Target based upon the Slab Target which in turn is based upon the measured outdoor temperature and the Melt, Idle or Storm temperature setting. The control can operate a boiler in one of six different methods: modulating boiler, 1 stage, EMS1, EMS2, control and enable. The Boiler
33 of 44 © 2013 654_D - 06/13
Target is shown in the View menu. Settings for the boiler operation are located in the Boiler menu.
Important Note: The boiler operator, or aquastat, remains in the burner circuit and acts as a secondary upper limit on the boiler temperature. The boiler aquastat temperature setting must be adjusted above 200°F (93.5°C) in order to prevent short cycling of the burner.
Page 34
Single Stage On/Off Boiler (1STG)
---------------
------------------------
--------------------------------------------
--------------------------------------------
----------------------------------
-----------------------------------
The control turns on or off the heat relay to fire the boiler in order to maintain the Boiler Target temperature. The boiler supply temperature operates on a differential that is half above and half below the boiler target. The status of the boiler is shown by the Boil Relay item in the View menu.
Modulating Boiler (MOD)
The control can operate a single hot-water modulating boiler using the Mod output and the Heat contact. The control operates the boiler by first switching the heat contact to allow the modulating boiler to go through the ignition sequence (the heat contact may not be required on all modulating boilers). A 0-10 V (dc) or 4-20 mA analog signal is then used to modulate the boiler firing rate starting at 50% (5 V (dc) or 12 mA signal) for 30 seconds. After the 30 second delay has elapsed, the control will then allow the boiler to modulate down to the Minimum Modulation setting and hold it there for the Modulation Delay time setting. After the modulation delay has elapsed, the control uses PID logic to change the boiler firing rate signal in order to satisfy the boiler target temperature. When the firing rate signal is reduced down to the minimum modulating setting and the boiler supply temperature exceeds the boiler target by 1/2 of the differential, the control will shut off the boiler burner. The modulating signal output is shown by the Boil Rate item in the View menu.
The Modulation Delay setting is determined by the boiler manufacturer. It is the amount of time that the burner must operate before the internal boiler control allows an external signal to operate the burner.
The Motor Speed sets the rate at which the modulating electrical signal can change. For most modulating boilers with a ECM fan, the motor speed can be set to 30 seconds. For commercial boilers with a mod motor, set the motor speed according to the time required by the mod motor to travel from the closed to open position.
EMS1
--------------------------------------------
The EMS1 signal is a method for the snow melting control to send the boiler target temperature to a tekmar Boiler Control
268. The control provides a 0-10 V (dc) signal proportional to the boiler target and turns on the heat relay to operate the boiler to maintain the Boiler Target temperature.
------------------------
---------------
EMS2
--------------------------------------------
The EMS2 signal is a method for the snow melting control to send the boiler target to a Viessmann boiler that supports the OpenTherm temperature targeting. Typical boilers include the Viessmann Vitodens 100-W and 200-W. The boiler may require an OpenTherm Input Module 0-10V. Contact Viessmann for details. The control provides a 0-10 V (dc) signal proportional to the boiler target and turns on the heat relay to operate the boiler to maintain the Boiler Target temperature.
Control (CTRL)
When the Application Mode is set to Mix or to PWM, the snow melting control can send a call for heat message using tekmarNet® communication to the tN4 System Control. The call for heat is received on the water temperature bus that the snow melting control is communicating on. When wired to a boiler bus, the snow melting control calls for heat on the boiler bus. The same logic applies to the mixing and tank bus available on the tN4 System Control. In most cases, the Boiler Type is set to Control when the snow melting system has a non-dedicated boiler plant.
A tN4 System Control is defined as a control that operates a boiler or mixing system. At the time of this writing the available controls are:
Boiler Control 274, 275, 284
• House Control 400, 401, 402, 403, 406
• Reset Modules 420, 421, 422, 423
Enable (ENBL)
When the Application Mode is set to Mix, the snow melting system may have a non-dedicated boiler plant. When not using tekmarNet® communication, the heat relay closes whenever the mixing device is increasing and reaches a position or speed of 10%. The heat relay opens when the mixing device is decreasing and reaches a position or speed of 5%.
----------------------------------
-----------------------------------
EMS1 Conversion Table
0-10 V (dc)
0 – – – (OFF) 1 50°F (10°C) 2 68°F (20°C) 3 86°F (30°C) 4 103°F (39°C) 5 121°F (49°C) 6 139°F (59°C) 7 157°F (69°C) 8 174°F (79°C) 9 192°F (89°C)
10 210°F (99°C)
© 2013 654_D - 06/13 34 of 44
Boiler Target
Page 35
Mixing Operation
----------------
---------
The Application Mode can be set to Mix when a mixing valve or a mixing injection pump is installed to regulate the supply water temperature to the snow melting system. The boiler or heat plant can be either dedicated or non-dedicated to the snow melting system. The mixing device position or speed is controlled by an analog 0-10 V (dc) or a 4-20 mA signal so that the supply temperature maintains the Mix Target temperature. The control calculates a Mix Target based upon the Slab Target which in turn is based upon the measured outdoor temperature and the Melt, Idle or Storm temperature setting. The Mix Maximum setting limits the upper temperature of the Mix Target. The Mix Target is shown in the View menu.
Boiler protection is only available when the snow melting control is connected to a tN4 System Control. The tN4 System Control provides the outdoor temperature to the snow melting control using tekmarNet(R) communication. See Boiler Operation section regarding recommended tN4 System Controls. The mixing device provides boiler return protection to the boiler inlet by closing the valve when the boiler return temperature falls below the Boiler Minimum setting. Boiler return protection requires the installation of a boiler return sensor 082 on the inlet to the boiler and the Outdoor/Boiler Return Sensor setting must be set to Boiler Return.
Flow Rate
GPM
1.5 - 2.0 20 1/2" X X 21001/2"X
3.0 - 4.5 100 1/2" X X
4 - 5.5 100 3/4" X
7.5 - 8.5 100 3/4" X X
12 - 13 100 1" X X 19 - 21 100 1-1/4" X X 31 - 32 100 1-1/2" X
39 - 42 100 2" X
Turns open of the Globe
Valve
Nominal Pipe
Diameter
003-VV 007-VV 0010-VV 0012-VV
Mixing Valve and Actuator Motor
The 654 provides a 0-10 V (dc) signal to operate an actuator motor for mixing using a 3 or 4-way mixing valve.
Recommended Mixing Injection Pumps
The control provides a 0-10 V (dc) or 4-20 mA signal to operate a mixing device. In large commercial applications, a Variable Frequency Drive (VFD) that can accept a 0-10 V (dc) or 4-20 mA can be used to vary the speed of the mixing injection pump. For residential and smaller commercial applications, specialized wet rotor, split-capacitor pumps that accept a 0-10 V (dc) signal are available from Grundfos and Taco. See Essay E021 for piping information. The recommended models are listed in the table below.
Taco Grundfos
----------------
---------
UP 15-42
F/VS
UP 26-64
F/VS
Required Taco 00-VV control settings:
DIP Switch DIP Switch Position Description
1 ON Operates using a linear output characteristic 2OFFAutomatic operation 3 OFF Operates using a 0-10 V (dc) signal
Required Grundfos VS control settings:
DIP Switch DIP Switch Position Description
A OFF Operates using a V (dc) signal B OFF Operates using 0-10 V (dc) range C ON Minimum speed is off D ON Speed control external
35 of 44 © 2013 654_D - 06/13
Page 36
Tandem Snow / Ice Detection
e
In systems where reliability of the snow melting system is critical, it is possible to install two Snow / Ice Sensors 090 or 094 into a single snow melt zone. Both sensors are used to detect snow or ice and if either sensor is wet the snow melting zone starts melting. The zone continues to operate until both sensors are dry. This allows snow or ice detection over a wider area. In the event of a sensor failure, the snow melting zone continues to function normally, giving building maintenance staff time to troubleshoot and replace the sensor if necessary.
In order to setup a zone using tandem snow / ice detection: Step 1:
Step 2:
Install two Snow Melting Controls 654 each having their own Snow / Ice Sensor 090 or 094.
Connect the two 654 together using tekmarNet® communication.
Snow Zone 1
Master
App Mode
tekmarNet
PWM, Boil,
Mix, Elec
Step 3:
Step 4:
Step 5:
®
In the tekmarNet® menu, select the Snow Zone that the 654 is to operate. There can be up to 12 different Snow Zones. Both 654 controls must be set to the same Snow Zone number.
On one of the 654, select the Application Mode to PWM, Boil, Mix or Elec. This control is the Snow Zone Master and it will operate the snow melting equipment.
On the other 654, select the Application Mode to 090. This control is the Snow Zone Member. This control must be wired to power, tekmarNet® communication, and the Snow / Ice Sensor 090 or 094.
Communication
Snow Zone 1
Member
App
Mod
090
Operates
Snow Melting
Snow Zone 1
Equipment
Exercising
In a hydronic snow melting system, the control operates the system pump as well as the mixing valve or mixing injection pump every 3 days to prevent pump and valve seizure.
Alert Relay
The control includes an auxiliary relay that can be configured to be either a system pump or an alert output. When the Auxiliary Relay setting in the System menu is set to Alert, the relay closes whenever there is a local error code. A network error on the tekmarNet® communication system is not considered a local error code and the Alert Relay does not close if only a network error is present. The Alert Relay is connected to the input power R and provides a 24 V (ac) powered signal when closed. An isolation relay may be installed if a dry contact switch is required on the 3rd party equipment.
Pump Post Purge
After a zone has finished heating, the boiler or heat source is shut off and the zone continues to operate for 20 seconds to post purge heat from the boiler to the zone.
© 2013 654_D - 06/13 36 of 44
Page 37
Melt and Storm Groups
------------------------------
The snow melting control is able to respond to a setpoint enable signal from a User Switch or Gateway to remotely activate or deactivate the storm or melt operation. The tekmarNet® communication system supports setpoint enable signals 1 through 12. When the snow melting control receives a setpoint enable signal that is the same as the Melt Group number, the control enters Melt operation. Likewise, if the snow melting control receives a setpoint enable signal that is the same as the Storm Group number, the control enters Storm operation. Each snow melting control has its own Melt Group and Storm
®
Group setting located in the tekmarNet
menu.
User Switch Setup
A User Switch 480 or 481 can be programmed to allow a user to remotely activate or deactivate the storm, melt, and away operations of the snow melting control. The User Switch has three buttons and it is recommended to have the top button setup to start or stop the Storm operation, the middle button start or stop the Melt operation and the bottom button selects if the scene is Away or Normal.
Storm
Melt
Away
BUTTON
A
User
Button
User
Button
User
Button
1
2
3
BUTTON
B
Melt Group 1
Melt
Group
Melt
Group
1
2
Zone 1 Zone 2
Melt Group 2
Zone 3 Zone 4
Setup Instructions
------------------------------
The User Switch has a total of 5 buttons.
User Buttons 1, 2, and 3 allow for users to select the operation of the tekmarNet® system.
Buttons A and B allow the installer to program the operation of User Buttons 1, 2, and 3.
The User Switch trim bezal must be removed to program and must be reinstalled after programming is complete.
Storm Button
Step 1:
Press button “A” once using a blunt object to begin programming mode.
Step 2:
Press and hold the top button until is turns Green, then let go.
Step 3:
The snow melting control Storm Group default is 12. Press the User Switch top button 12 times to set the setpoint enable to 12. The button should flash Green 12 times, pause, then repeat the flashing sequence.
Step 4:
Press button “B” to finalize the User Button setting and exit the programming mode.
Melt Button
Step 1:
Press button “A” once using a blunt object to begin programming mode.
Step 2:
Press and hold the middle button until is turns Green, then let go.
Step 3:
The snow melting control Melt Group default is 1. Press the User Switch middle button 1 time to set the setpoint enable to 1. The button should flash Green 1 time, pause, then repeat the flashing sequence.
Step 4:
Press button “B” to finalize the User Button setting and exit the programming mode.
Away Button
Step 1:
Press button “A” once using a blunt object to begin programming mode.
Step 2:
Press and hold the top button until is turns Red, then let go.
Step 3:
The away scene number is 2. Press the User Switch bottom button 2 times to set the scene number to 2. The button should flash Red 2 times, pause, then repeat the flashing sequence.
Step 4:
Press button “B” to finalize the User Button setting and exit the programming mode.
37 of 44 © 2013 654_D - 06/13
Page 38
Troubleshooting
It is recommended to complete all wiring to ensure trouble free operation. Should an error occur, simply follow these steps:
1. Find: If the control flashes on the screen, it is indicating a problem on the system.
2. Identify: Hold the Home button for 3 seconds, touch the NEXT key to locate the Toolbox Menu, then touch the ENTER key. The error code should appear as the first item.
3. Solve: Use the chart below to match the error code to the one on the control. Use the description to solve the problem.
Error Messages (1 of 4)
Error Message Description
SET TEMP MENU SAVE ERROR
The control failed to read the Set Temp menu settings from memory and has reloaded the factory default settings. The control stops operation until all settings in the Set Temp menu are checked.
To clear the error, set the access level to Installer and check all settings in the Set Temp menu.
SYSTEM MENU SAVE ERROR
The control failed to read the System menu settings from memory and has reloaded the factory default settings. The control stops operation until all settings in the System menu are checked.
To clear the error, set the access level to Installer and check all settings in the System menu.
BOILER MENU SAVE ERROR
The control failed to read the Boiler menu settings from memory and has reloaded the factory default settings. The control stops operation until all settings in the Boiler menu are checked.
To clear the error, set the access level to Installer and check all settings in the Boiler menu.
MIXING MENU SAVE ERROR
The control failed to read the Mixing menu settings from memory and has reloaded the factory default settings. The control stops operation until all settings in the Mixing menu are checked.
To clear the error, set the access level to Installer and check all settings in the Mixing menu.
tekmarNet® MENU SAVE ERROR
The control failed to read the tekmarNet® menu settings from memory and has reloaded the factory default settings. The control continues to operate but does not provide any tekmarNet® features until all settings in the tekmarNet® menu are checked.
To clear the error, set the access level to Installer and check all settings in the tekmarNet
®
menu.
SCHEDULE MENU SAVE ERROR
The control failed to read the Schedule menu settings from memory and has reloaded the factory default settings. The control operates with the programmable schedule disabled until all settings in the Schedule menu are checked.
To clear the error, set the access level to Installer and check all settings in the Schedule menu.
SCENES MENU SAVE ERROR
The control failed to read the Scenes menu settings from memory and has reloaded the factory default settings. The control operates with the away scene disabled until all settings in the Scenes menu are checked.
To clear the error, set the access level to Installer and check all settings in the Scenes menu.
MAXIMUM MELT TIME ERROR
The control has operated in melting for the time set by Maximum Melt Days setting located in the System menu. This error is usually created when there is a mechanical system failure resulting in the snow melt slab not heating correctly.
Clear the error message by touching the Cancel key while viewing the error message. Use the Manual Override menu to manually check that each component of the mechanical system is operating correctly. If necessary, change the Maximum Melt Days setting to a longer time period or to Off.
tekmarNet® COMMUNICATION ERROR
The tekmarNet® communication bus has either an open or a short circuit. The result is that there are no communications. Check for loose wires between tN4 and C. Check for short circuits between the tN4 and C wires on the House Control, Wiring Center, or Zone Manager. Check for correct polarity between the C and R wires. The error clears automatically once the wiring fault has been corrected. To force the error to clear while allowing a short or open circuit to continue, touch the Cancel key.
© 2013 654_D - 06/13 38 of 44
Page 39
Error Messages (2 of 4)
Error Message Description
ADDRESS TAKEN ERROR
Two devices (thermostats, setpoint controls, snow melting controls) have been manually set to the same address. The device continues to operate with this error but does not communicate with the tekmarNet®
system. To clear this error, select an unused tekmarNet
SNOW ZONE TAKEN ERROR
Two snow melting controls have been manually set to the same snow zone number and one of the controls is NOT set to App Mode 090. The control continues to operate with this error.
To clear this error, select an unused snow zone number or set the App Mode to 090.
APP MODE 090 ERROR
Two snow melting controls have been manually set to the same snow zone number and both of the controls are set to App Mode 090.
To clear this error, select an unused snow zone number or set the App Mode to anything other than
090.
TANDEM 090 ERROR
There are two Snow / Ice Sensors 090 or 094 installed in the zone and the other snow melting control’s 090 or 094 has a sensor problem. Locate the other snow melting control and navigate to the Toolbox menu to determine and correct the problem. The control continues to operate with this error.
®
address or select automatic addressing.
DEVICE LIMIT
More than 24 devices (thermostats or setpoint controls) have been connected to the tekmarNet® communication bus. To clear the error, remove and relocate devices to other available buses until the device count is 24 or less.
OUTDOOR SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Outdoor Sensor 070. The control continues to operate and assumes an outdoor temperature of 32°F (0°C). Energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are disabled.
Check the outdoor sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the outdoor sensor. Once the error has been corrected, the error message automatically clears.
OUTDOOR SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Outdoor Sensor 070. The control continues to operate and assumes an outdoor temperature of 32°F (0°C). Energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are disabled.
Check the outdoor sensor wire for open circuits according to the sensor installation manual. It may be necessary to replace the outdoor sensor. Once the error has been corrected, the error message automatically clears.
SUPPLY SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Supply Sensor 082. When set to App Mode Boiler or Mixing the control stops operation and does not provide any heat. When set to App Mode PWM the control continues melting or idling but supply priority operation is not available.
Check the supply sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the supply sensor. Once the error has been corrected, the error message automatically clears.
SUPPLY SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Supply Sensor 082. When set to App Mode Boiler or Mixing the control stops operation and does not provide any heat. When set to App Mode PWM the control continues melting or idling but supply priority operation is not available.
Check the supply sensor wire for open circuits according to the sensor installation manual. It may be necessary to replace the supply sensor. Once the error has been corrected, the error message automatically clears.
39 of 44 © 2013 654_D - 06/13
Page 40
Error Messages (3 of 4)
Error Message Description
BOILER RETURN SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Boiler Return Sensor 082. The control continues operation but does not provide any boiler return protection.
Check the boiler return sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the boiler return sensor. Once the error has been corrected, the error message automatically clears.
BOILER RETURN SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Boiler Return Sensor 082. The control continues operation but does not provide any boiler return protection.
Check the boiler return sensor wire for open circuits according to the sensor installation manual. It may be necessary to replace the boiler return sensor. Once the error has been corrected, the error message automatically clears.
SLAB SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Slab Sensor 072 or 073. Idling and Storm are disabled and energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are operate using the outdoor temperature only.
Check the slab sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the slab sensor. Once the error has been corrected, the error message automatically clears.
SLAB SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Slab Sensor 072 or 073. Idling and Storm are disabled and energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are operate using the outdoor temperature only.
Check the slab sensor wire for open circuits according to the sensor installation manual. It may be necessary to replace the slab sensor. Once the error has been corrected, the error message automatically clears.
If the slab sensor has been intentionally removed, set the slab sensor setting in the System menu to Off.
YELLOW WIRE OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the yellow wire connected to the Snow / Ice Sensor 090 or 094, or the Snow Sensor 095. The control can no longer automatically detect snow or ice but manual start of the snow melting system is still available.
Check the Snow / Ice Sensor or Snow Sensor yellow and black wires and any wire splices for open circuits according to the sensor installation manual. It may be necessary to replace the sensor. Once the error has been corrected, the error message automatically clears.
BLUE WIRE SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the blue wire connected to the Snow / Ice Sensor 090 or 094, or the Snow Sensor 095. The control can no longer automatically detect snow or ice but manual start of the snow melting system is still available.
First check the Snow / Ice Sensor or Snow Sensor for dirt or debris. The ring structure of the sensor may need cleaning with hot soapy water and a nylon brush. Rinse with water. Secondly, check the Snow / Ice Sensor or Snow Sensor blue and black wires and any wire splices for short circuits according to the sensor installation manual. It may be necessary to replace the sensor. Once the error has been corrected, the error message automatically clears.
BLUE WIRE OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the blue wire connected to the Snow / Ice Sensor 090 or 094, or the Snow Sensor 095. The control can no longer automatically detect snow or ice but manual start of the snow melting system is still available.
Check the Snow / Ice Sensor or Snow Sensor blue and black wires and any wire splices for open circuits according to the sensor installation manual. It may be necessary to replace the sensor. Once the error has been corrected, the error message automatically clears.
BROWN WIRE SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the brown wire connected to the Snow / Ice Sensor 090 or 094. Idling and Storm is disabled and energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are operate using the outdoor temperature only.
Check the Snow / Ice Sensor brown and black wires for open circuits according to the sensor installation manual. It may be necessary to replace the sensor. Once the error has been corrected, the error message automatically clears.
© 2013 654_D - 06/13 40 of 44
Page 41
Error Messages (4 of 4)
Error Message Description
SNOW / ICE SENSOR ERROR
The control is unable to properly detect the Snow / Ice Sensor 090 or 094. The control can no longer automatically detect snow or ice but manual start of the snow melting system is still available.
Check the Snow / Ice Sensor brown, yellow, red and black wires according to the sensor installation manual. It is important to check any cable splices for loose wiring connections. It may be necessary to replace the sensor. Once the error has been corrected, the error message automatically clears.
SNOW SENSOR ERROR
The control is unable to properly detect the Snow Sensor 095. The control can no longer automatically detect snow but manual start of the snow melting system is still available.
Check the Snow Sensor yellow, red and black wires according to the sensor installation manual. It may be necessary to replace the sensor. Once the error has been corrected, the error message automatically clears.
SCHEDULE MASTER ERROR
Two devices on the tekmarNet® system have been set to the same Schedule Master number. The control operates according to the local programmable schedule while this error is present.
To clear the error, select a different Schedule Master number, set a different Schedule Member number, set the Schedule to Zone, or set the Schedule to None.
SCHEDULE MEMBER ERROR
The control can no longer detect its schedule master. The control operates as if the programmable schedule is in idle or off operation while this error is present.
To clear the error, select a different Schedule Member number, set the Schedule to Zone, or set the Schedule to None.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this control.
01 to 24 = There is an error on a thermostat or setpoint control with this tekmarNet
®
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this control.
b:01 to b:24 = There is an error on a thermostat or setpoint control wired to the boiler communication
®
bus with this tekmarNet
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this control.
1:01 to 1:24 = There is an error on a thermostat or setpoint control wired to communication bus 1 with
®
this tekmarNet
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this control.
2:01 to 2:24 = There is an error on a thermostat or setpoint control wired to communication bus 2 with
®
this tekmarNet
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this control.
3:01 to 3:24 = There is an error on a thermostat or setpoint control wired to the mix 3 bus with this tekmarNet® address.
ERROR AT SYSTEM CONTROL
There is an error on the tekmarNet® system control connected to the tekmarNet® system and not on this control.
41 of 44 © 2013 654_D - 06/13
Page 42
Frequently Asked Questions
Symptom Look For... Corrective Action
LCD display is off
System pump always on
Blue short
Slab is above melt temperature
System running with no snow
Snow on slab but system did not start
Power to control
Display shows Idle
Dirt or salt on snow/ ice sensor
Slab Target
Heat On not shown
Idle
Melt
Timed Melt
Sched Melt
Off
Off
Use electrical meter to measure 24 V (ac) voltage on input power R and C terminals.
Idle operation requires that the system pump operate continuously while below the melting temperature setting.
The snow/ice sensor requires regular cleaning. Avoid using road salt on the snow melting slab.
The slab is heated to the slab target.
Check wiring of the system pump. The system pump operates continously during melt, idle or storm operation. The heat source must be wired to operate together with the heat relay.
Idling heats the slab when the temperature falls below the Idle temperature.
During cold weather cut out (CWCO), the system is shut off. If shut off during a melt cycle, the system resumes melting once the outdoor temperature is above CWCO.
System manually started.
System started on a programmable schedule.
System has a programmable schedule and is in event 2 or 4 (unoccupied).
System has been manually Stopped and the automatic snow / ice sensor never dried, thereby preventing the system to automatically start.
Job Record
Schedule Menu Settings
Item Setting
EVENT 1
EVENT 2
EVENT 3
EVENT 4
Display Menu Settings
Item Setting
UNITS
Scene Menu Settings
Item Setting
SCENES
Item Setting
SCHEDULE
EVENT PER DAY
24 HOUR / 7 DAY
Item Setting
BACKLIGHT
Item Setting
AWAY KEY
© 2013 654_D - 06/13 42 of 44
Page 43
Set Temp Menu Settings
Item Setting
MELTING
IDLING
STORM
MANUAL MELT RUN TIME
ADDITIONAL MELT TIME
System Menu Settings
Item Setting
APPLICATION MODE
SNOW / ICE SENSOR
SLAB SENSOR
SLAB PROTECTION OUTDOOR OR BOILER
RETURN SENSOR
Item Setting
STORM RUN TIME
WATER SENSITIVITY
WARM WEATHER SHUT DOWN
COLD WEATHER CUT OUT
Item Setting
ECONOMELT
tekmarNet® SYSTEM PUMP
AUXILIARY RELAY
MAXIMUM MELT TIME
Boiler Menu Settings
Item Setting
BOILER TYPE
BOILER MODULATION TYPE
BOILER MINIMUM MODULATION
BOILER MODULATION DELAY
Mixing Menu Settings
Item Setting
MIX TYPE
MIX MOTOR SPEED
tekmarNet® Menu Settings
Item Setting
ADDRESS
SNOW ZONE
Item Setting
BOILER MOTOR SPEED
BOILER DIFFERENTIAL
BOILER MINIMUM
Item Setting
MIX MAXIMUM
Item Setting
STORM GROUP
PRIORITY
TRACK ZONE
MELT GROUP
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: www.watts.com/prop65
43 of 44 © 2013 654_D - 06/13
LOCAL NETWORK GROUP
Page 44
Technical Data
Snow Melting Control 654 tekmarNet® Electric or Hydronic Boiler / Mixing
Literature 654_A, 654_C, 654_D, 654_Q, 654_U Control Microprocessor control. This is not a safety (limit) control Packaged weight 1.3 lb. (590 g) Dimensions 5" H x 3-1/4" W x 15/16" D (127 x 82 x 23 mm) Enclosure White PVC plastic, NEMA type 1
Ambient conditions
Power supply 24 V (ac) ±10%, 60 Hz, Class 2, 16 VA standby, 100 VA fully loaded Relay capacity 24 V (ac) 2 A, 3.6 A combined Modulating output 0-10 V (dc), 500  minimum load impedance, 4-20 mA 1 k max load impedance Sensors NTC thermistor, 10k
- Included Outdoor Sensor 070 and Universal Sensor 082
- Optional tekmar type: 071, 072, 073, 082, 090, 091, 094, 095
Warranty Limited 3 Year
-4 to 122°F (-20 to 50°C), < 90% RH non-condensing, outdoor use permitted when installed inside a NEMA 3 enclosure
@ 77°F (25°C ± 0.2°C) ß=3892
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is lim-
ited. The Purchaser, by taking receipt of any tekmar product (“Prod­uct”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the docu­mented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective prod­uct; or to the exchange of the defective product for a warranty replace­ment product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liabil­ity, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in work­manship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Prod­ucts returned to tekmar during the warranty period. This Limited War­ranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Lim­ited Warranty are the Purchaser’s sole responsibility and obligation. Pur­chaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Pur­chaser to its customers.
The pass-through Limited Warranty does not apply if the returned Prod­uct has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA­TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EX TEND BEYON D TWE NTY-FO UR (24) MONT HS FROM THE PRODUC ­TION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa­tion regarding the appropriate Representative.
tekmar Control Systems Ltd., A Watts Water Technologies Company.
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com
Product design, software and literature are Copyright ©2013 by tekmar Control Systems Ltd.,
A Watts Water Technologies Company
44 of 44
Head Offi ce: 5100 Silver Star Road,
All specifications are subject to change without notice.
Printed in Canada. 654_D - 06/13.
Loading...