The Snow Melting Control 654 is designed to operate electric or hydronic equipment to melt snow or ice from any surface
including driveways, walkways, patios, business entrances, parking ramps, loading docks, hospital entrances, helipads
or car wash bays. The surface temperature for snow melting is controlled automatically to reduce operating energy costs.
The 654 has an automatic start and stop function when used with the Snow/Ice Sensor 090 or 094. Automatic start with a
timed stop is available when used with the Snow Sensor 095. The 654 can operate a dedicated hydronic boiler or a mixing
device. Isolation relays are required to operate line voltage pumps. Electric systems require a separate GFCI and electrical
relay contactor.
Job Record .......................................................................42
Technical Data ................................................................. 44
Limited Warranty and Product Return Procedure ........... 44
Getting Started
Congratulations on the purchase of your new Snow Melting Control!
This manual covers the complete installation, programming and sequence of operation for this control. You will also find
instruction on testing, commissioning, and troubleshooting the control and system that it operates.
It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards.
tekmar is not responsible for damages resulting from improper installation and/or maintenance.
To avoid serious personal injury and damage to the equipment:
Read Manual and all product labels
•
BEFORE using the equipment. Do not
use unless you know the safe and proper
operation of this equipment.
•
Keep this Manual available for easy
access by all users.
•
Replacement Manuals are available at
tekmarControls.com
•
Disconnect all power before opening
the control.
Radio Frequency Interference
The installer must ensure that this control and its wiring are
isolated and/or shielded from strong sources of electromagnetic
noise. Conversely, this Class B digital apparatus complies
with Part 15 of the FCC Rules and meets all requirements of
the Canadian Interference-Causing Equipment Regulations.
However, if this control does cause harmful interference to
radio or television reception, which is determined by turning
It is the installers responsibility to ensure that this control
•
is safely installed according to all applicable codes and
standards.
Improper installation and operation of this control could result
•
in damage to the equipment and possibly even personal
injury or death.
This electronic control is not intended for use as a primary
•
limit control. Other controls that are intended and certified
as safety limits must be placed into the control circuit.
Do not attempt to service the control. There are no user
•
serviceable parts inside the control. Attempting to do so
voids warranty.
the control off and on, the user is encouraged to try to correct
the interference by re-orientating or relocating the receiving
antenna, relocating the receiver with respect to this control,
and/or connecting the control to a different circuit from that
to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
When choosing the location for the control, consider the
following:
Interior Wall.
•
Keep dry. Avoid potential leakage onto the control.
•
Relative Humidity less than 90%. Non-condensing
•
environment.
No exposure to extreme temperatures beyond -4 to
•
122°F (-20 to 50°C).
No draft, direct sun, or other cause for inaccurate
•
temperature readings.
Rough-In Wiring
Low Voltage Wiring
Each cable must be pulled from the equipment to the control’s
plastic enclosure. All low voltage wiring connections enter
the enclosure through the square knockout on the rear. It is
recommended to label each cable for easy identification. All
low voltage wires are to be stripped to a length of 3/8" (9 mm)
to ensure proper connection to the control.
Pull four conductor 18 AWG LVT cable, up to 500 feet
(150 m) for the following equipment:
•
Snow Sensor 095
Pull five conductor 18 AWG LVT cable, up to 500 feet
(150 m) for the following equipment:
The control requires an external transformer. A tekmar
Transformer 009 can supply up to 40 VA, and includes an
in-line fuse to protect the transformer and control.
The total power capacity of the power supply should be
larger than the total load of all the devices connected to the
control. This total load must not exceed 100 VA.
Control Wiring
See Application Brochure 654_A for specific application wiring diagrams.
Notice: The temperature sensor (thermistor) is built into the
sensor enclosure.
Remove the screw and pull the front cover off the sensor
•
enclosure.
•
The outdoor sensor can either be mounted directly onto a
wall or a 2" x 4" electrical box. When the outdoor sensor is
wall mounted, the wiring should enter through the back or
bottom of the enclosure. Do not mount the outdoor sensor
with the conduit knockout facing upwards as rain could
enter the enclosure and damage the sensor.
Sensor with rear
entry wiring
In order to prevent heat transmitted through the wall from
•
affecting the sensor reading, it may be necessary to install
an insulating barrier behind the enclosure.
The outdoor sensor should be mounted on a wall which best
•
represents the heat load on the building (a northern wall
for most buildings and a southern facing wall for buildings
with large south facing glass areas). The outdoor sensor
should not be exposed to heat sources such as ventilation
or window openings.
•
The outdoor sensor should be installed at an elevation above the
ground that will prevent accidental damage or tampering.
Sensor with bottom
entry wiring
Sensor mounted
onto 2" x 4"
electrical box
Wiring the Outdoor Sensor
Connect 18 AWG or similar wire to the two terminals provided in the enclo-
sure and run the wires from the outdoor sensor to the control. Do not run
the wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic interference (EMI),
shielded cable or twisted pair should be used or the wires can be run in
a grounded metal conduit. If using shielded cable, the shield wire should
be connected to the Com or Com Sen terminal on the control and not to
earth ground.
Follow the sensor testing instructions in this brochure and connect the
NOTICE: These sensors are designed to mount on a pipe or in a temperature
immersion well.
The Universal Sensor should be placed downstream of a pump or after an
elbow or similar fitting. This is especially important if large diameter pipes
are used as the thermal stratification within the pipe can result in erroneous
sensor readings. Proper sensor location requires that the fluid is thoroughly
mixed within the pipe before it reaches the sensor.
Strapped to Pipe
The Universal Sensor can be strapped directly to the pipe using the cable tie
provided. Insulation should be placed around the sensor to reduce the effect
of air currents on the sensor measurement.
Wires from outdoor
sensor to control’s
outdoor sensor and
sensor common
terminals
If a Universal Sensor is mounted onto 1" (25 mm) diameter L type copper pipe,
there is approximately an 8 second delay between a sudden change in water
temperature and the time the sensor measures the temperature change. This
delay increases considerably when mild steel (black iron) pipe is used. In general,
it is recommended that a temperature well be used for steel pipe of diameter
greater than 1-1/4" (32 mm). Temperature wells are also recommended when
large diameter pipes are used and fluid stratification is present.
Conduit Connection
The Universal Sensor and Universal Sensor Enclosure 080 (sold separately)
are specifically designed to mount onto a 3/8" (10 mm) ID temperature well that
is supplied with an end groove. To install the well, plumb a ‘T’ into the pipe and
fix the well into the ‘T’. The 080 enclosure has a 7/8" (22 mm) back knockout that
must be removed and fitted over the temperature well. The universal sensor is
then inserted into the well and the retaining clip supplied with the enclosure is
snapped onto the well end groove. If the well has a threaded end, the installer
must supply a standard threaded conduit retaining ring. The two wires from
the sensor are connected to the terminal block provided in the enclosure. The
other side of the terminal block is used to connect wires from the control.
Testing the Sensor Wiring
Retaining
Clip
Universal
Sensor
Sensor Well
Universal
Sensor
Bottom of
Enclosure 080
Cable Tie
A good quality test meter capable of measuring up to 5,000 kΩ
(1 kΩ = 1000 Ω) is required to measure the sensor resistance. In
addition to this, the actual temperature must be measured with
either a good quality digital thermometer, or if a thermometer
is not available, a second sensor can be placed alongside
the one to be tested and the readings compared.
First measure the temperature using the thermometer and
then measure the resistance of the sensor at the control. The
wires from the sensor must not be connected to the control
while the test is performed. Using the chart below, estimate
Temperatur eRe sistanceTemperatur eResistanceTemperatureResistanceTemper atureResistance
the temperature measured by the sensor. The sensor and
thermometer readings should be close. If the test meter reads
a very high resistance, there may be a broken wire, a poor
wiring connection or a defective sensor. If the resistance is
very low, the wiring may be shorted, there may be moisture
in the sensor or the sensor may be defective. To test for
a defective sensor, measure the resistance directly at the
sensor location.
Do not apply voltage to a sensor at any time as damage
to the sensor may result.
Testing the Control Wiring
Testing the Power
1. Remove the front cover from the control.
2. Use an electrical test meter to measure (ac) voltage between the R and C terminals. The reading should be 24 V (ac)
+/– 10%.
The control includes an Override menu to check if the control’s
relays are operating and that the control is wired correctly to
the snow melting equipment.
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Press and hold the Home button for 3 seconds.
Press NEXT to navigate to the Override menu.
Press ENTER to enter the Override menu.
Select Manual Override to Hand.
For hydronic systems, set System Pump to On. The
system pump should now be operating.
Manual Override - Maximum Heat
Step 6:
Step 7:
Step 8:
Step 9:
Step 10:
Set Heat Relay to On. The boiler or electric heating
cables should start heating.
For modulating boilers change the Boiler Percent from
0 to 100%. The boiler should be firing.
For a mixing valve or mixing injection pump, change
the Mix Percent from 0 to 100%. The mixing valve
should open or the mixing injection pump should
increase speed.
Select the Override Time after which the control
resumes normal operation.
Exit the Manual Override by selecting Auto.
In hydronic application modes, the control includes a
Maximum Heat operation where the control operates the
snow melting system to maintain the maximum allowed
heating setpoints. This allows testing of the snow melting
system during warm weather.
Manual Override - Test
When operating an electric snow melting system, the control
includes a Test operation where the electrical heating cables
can be energized for 10 minutes after which the control
resumes normal operation. This allows testing of the electric
snow melting system during warm weather.
Manual Override - Purge
When operating a hydronic snow melting system, it is necessary to purge and bleed all air out of the system. The control
includes a Purge operation where the System Pump as well
as pumps operated by the tekmarNet® system are all turned
on to assist in purging air from the system.
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Press and hold the Home button for 3 seconds.
Press NEXT to navigate to the Override menu.
Press ENTER to enter the Override menu.
Select Manual Override to Max.
Select the Maximum Heat Time after which the control
resumes normal operation.
Exit the Manual Override by selecting Auto.
Press and hold the Home button for 3 seconds.
Press NEXT to navigate to the Override menu.
Press ENTER to enter the Override menu.
Select Manual Override to Test.
Exit the Manual Override by selecting Auto.
Press and hold the Home button for 3 seconds.
Press NEXT to navigate to the Override menu.
Press ENTER to enter the Override menu.
Select Manual Override to Purge.
Select the Maximum Purge Time after which the control
resumes normal operation.
Exit the Manual Override by selecting Auto.
Manual Override - Off
The snow melting system can be manually turned off and the
control remains off until manually changed back to Auto. This
allows the installer or end user to permanently disable the snow
melting system without removing power from the control.
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Press and hold the Home button for 3 seconds.
Press NEXT to navigate to the Override menu.
Press ENTER to enter the Override menu.
Select Manual Override to Off.
Exit the Manual Override by selecting Auto.
Switch Settings
1058-01
Switch
H1220A
Lock
ON
Snow Melting Control 654
tekmarNet Electric or Hydronic Boiler/Mixing
www.tekmarControls.com
Settings
2
1
Power: 24 V (ac) ±10%, 60 Hz, Class 2,
16 VA standby, 100 VA fully loaded
Unlock
Relays: 24 V (ac) 2 A, 3.5 A combined
Unused
Designed and assembled in Canada
Meets Class B: ICES & FCC Part 15
The control is locally locked and the access level cannot be changed.
Set to Lock when installation has been completed.
UNLOCK ACCESS LEVEL
The control is unlocked and the access level may be changed. Go to
the Toolbox menu to change the access level. Set to Unlock during
the installation process.
Note: tekmarNet
®
system controls include a Global Lock that locks all
connected snow melt controls, and thermostats. Set the tekmarNet®
system control to unlock to allow access level adjustment on all
connected devices.
Not used
Not used
Page 10
User Interface
Display
Status Field
Operation Field
Touch to display
Run Time,
Outdoor & Slab
Temperature
Touch to quickly enter
the View menu
Touch to turn system
off while away
Touch to
Melt or Stop
Touch to adjust settings
Operation Field
MELTSystem is melting snow or ice.
IDLESystem is idling.
Status Field
WWSD
CWCOCold Weather Cut Out. Too cold to melt.
TIMED
Warm Weather Shut Down. The slab is naturally
warm enough to melt snow or ice.
Timed melting operation. System operates until
time has elapsed.
Touch to go to the next setting
Home Button
Return to the Home Screen
Press and hold for 3
seconds to access the
Home
Button
ENTER
programming menus.
STRMSystem is in storm operation.
OFFSystem is off.
PEND
WAIT
SENSOR
Pending. The system has detected water but it is too
cold to operate or the schedule is in Idle or Off.
Zone priority in effect. Zone must wait until higher
priority zone finishes melting.
Tandem 090 sensor.
WARMSlab is warming up to the melting temperature.
AWAY
Away scene. No melting until the away scene is
exited.
Press and hold the Home button for 3 seconds to enter the programming menus. The control returns to the last programming
menu previously used.
Press and
hold for 3
seconds to
access the
programming
menus.
Select a Programming Menu
Touch “NEXT” to advance (clockwise in above illustration)
•
to the next menu.
•
Touch “BACK” to go backwards (counterclockwise in above
illustration) through the menus.
•
Touch “ENTER” to enter a menu.
--------------------
Access Levels and Access Level Lock
The control is shipped pre-programmed with common settings.
The control has an “Installer” access level that allows full
access to all settings and a “User” access level that restricts
the number of settings available. The control defaults to the
“
User” access level after 12 hours of operation.
Notice: tekmarNet® system controls include a Global Lock that
locks all connected snow melting controls and thermostats. Set
the tekmarNet® system control to unlock to allow access level
adjustment on all connected devices.
Setting Items
Touch or arrow to adjust the setting if required.
•
•
Touch “NEXT ITEM” to advance to the next item within the
menu.
•
Touch “BACK ITEM” to go backwards to the previous item
within the menu.
•
To return to the parent menu after changing a setting, press
and release the Home button.
•
To return to the Home screen, press and release the Home
button twice or wait 30 seconds to automatically return to
the Home screen.
To change to the “Installer” access level:
•
In the Toolbox menu, locate Access
Adjust the access level to “Installer” by pressing the up or down
•
button. This will permit setting changes to the control.
The View menu items display the current operating temperatures and status information of the system.
Item FieldRangeAccessDescriptionSet to
1 to 12
– – –, -76 to
149°F
(-60 to 65°C)
– – –, -76 to
149°F
(-60 to 65°C)
-76 to 149°F
(-60 to 65°C)
DRY or WET
User
Installer
User
Installer
Installer
User
Installer
User
Installer
SNOW ZONE
The snow melt zone number on the tekmarNet®
system.
Conditions: tekmarNet
OUTDOOR
Current outdoor air temperature as measured by the local
or remote outdoor sensor. The outdoor air temperature is
shared to all devices in the tekmarNet® system. “– – –” is
displayed when no outdoor sensor is available.
Conditions: Application Mode is set to PWM, Boil, Mix or
Elec.
SLAB TARGET
The calculated slab target of the snow melting system.
“– – –” is displayed when the snow melt control is off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.
SLAB
Current slab temperature as measured by the control.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.
WATER SENSOR
Current status of the water detection sensor.
Conditions: A snow/ice sensor or snow sensor is installed.
®
communication available.
---, 70 to 200°F
(21.0 to 93.5°C)
---, 70 to 200°F
(21.0 to 93.5°C)
-58 to 212°F
(50.0 to 100.5°C)
-58 to 212°F
(50.0 to 100.5°C)
0 to 100%Installer
Installer
Installer
Installer
Installer
BOILER TARGET
The calculated boiler target of the snow melt system.
“– – –” is displayed when the snow melt control is not operating
the boiler.
Conditions: Application Mode is set to Boil.
MIX TARGET
The calculated mix target of the snow melt system. “– – –”
is displayed when the snow melt control is not operating the
mixing valve or mixing injection pump.
Conditions: Application Mode is set to Mix.
SUPPLY
Current system supply temperature as measured by the
control.
Conditions: Application Mode is set to PWM, Boil or Mix.
BOILER RETURN
Current boiler return temperature as measured by the
control.
Conditions: Application Mode is set to PWM, Boil or Mix and
Out/Bret Sensor is set to Bret (boiler return sensor).
MIX RATE
Current position of the mixing valve or mixing injection
pump speed.
Current firing rate of the modulating boiler.
Conditions: Application Mode is set to Boil and Boiler Type
is set to Mod (modulating boiler).
Page 13
View Menu (2 of 2)
Item FieldRangeAccessDescriptionSet to
HEAT RELAY
OFF or ON
User
Installer
0 to 100%Installer
Current status of the heat relay. The boiler, pump or
electric cable is on when ON is displayed. The boiler,
pump or electric cable is off when OFF is displayed.
Conditions: Application Mode is set to PWM, Boil, Mix, or
Elec.
PWM RATE
Current duty cycle rate of the zone or boiler for each 20
minute cycle.
Conditions: Application Mode is set to PWM or Elec. Not
visible when Manual Override is not Auto.
OFF or ON
OFF or ON
00:00 to 24:00
hours
00:00 to 6:00
hours
User
Installer
User
Installer
User
Installer
User
Installer
SYSTEM PUMP RELAY
Current status of the system pump relay.
Conditions: Application Mode is set to PWM, Boil or Mix and
Auxiliary Relay is set to SYS (system pump).
ALERT RELAY
Current status of the alert relay.
Conditions: Application Mode is set to PWM, Boil or Mix and
Auxiliary Relay is set to ALRT (alert) or Application Mode is
set to Elec.
MANUAL MELT TIME
When manually started, the display shows the remaining
run time before shutting off.
Conditions: Application Mode is set to PWM, Boil, Mix or
Elec.
ADDITIONAL MELT TIME
When automatically started by a Snow/Ice Sensor 090
or 094, the display shows the remaining run time before
shutting off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow / ice sensor 090 or 094 is installed.
The Set Temp menu items select the operating temperatures of the snow melt system.
Item FieldRangeAccessDescriptionSet to
32 to 95°F
(0.0 to 35.0°C)
Default = 36°F
(2.0°C)
OFF, 20 to 95°F
(-6.5 to 35.0°C)
Default = OFF
OFF, 20 to 95°F
(-6.5 to 35.0°C)
Default = 28°F
(-2.0°C)
User
Installer
Installer
Installer
MELTING
Select the desired surface temperature of the snow melt
surface when melting.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
IDLING
Select the desired surface temperature of the snow melt
surface when idling. Idling pre-heats the slab when the
slab is dry but cold and allows faster reaction time to reach
the melting temperature. Recommended for commercial
use only.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
STORM
Select the desired surface temperature of the snow melt
surface while operating in the storm operation. Storm
operation temporarily pre-heats the slab to allow faster
reaction time to reach the melting temperature.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
0:30 to 24:00
hours
Default = 4:00
hours
0:00 to 6:00
hours
Default = 0:00
hours
0:30 to 24:00
hours
Default = 8:00
hours
AUTO, MIN, -2,
-1, MID, +1, +2,
MAX
Default = AUTO
AUTO, 32 to
95°F
(0.0 to 35.0°C)
Default = AUTO
User
Installer
Installer
Installer
Installer
Installer
MANUAL MELT RUN TIME
Select the amount of running time when manually starting
the system.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
ADDITIONAL MELT TIME
Select the amount of additional melting time after the
Snow / Ice Sensor 090 or 094 is dry. This allows low
spots on the slab to fully dry before the snow melting
system is shut off.
Conditions: Conditions: Application Mode is set to PWM,
Boil, Mix or Elec and a Snow / Ice Sensor is installed or
Track Zone is set to On.
STORM RUN TIME
Select the amount of storm run time to pre-heat the slab
when advised of a winter storm warning.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and Storm is set to a temperature.
WATER SENSITIVITY
Select how sensitive the Snow / Ice Sensor 090 or 094,
or the Snow Sensor 095 is to water detection.
Conditions: Snow / Ice Sensor is set to 090 or 095.
WARM WEATHER SHUT DOWN
Select the temperature at which to shut down the snow
melting system during warm weather. This allows the
snow or ice to melt off the slab naturally.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
Select the temperature at which to shut down the snow
melting system during extremely cold weather. Below
this temperature, the heat loss of the slab exceeds the
capacity of the boiler or heating appliance.
Page 15
Time Menu
Time settings are only required when using a programmable schedule. The Time menu is not available when the Application
Mode is set to 090.
Item FieldRangeAccessDescriptionSet to
00 to 59
Default = 00
12 AM to 11 PM
00 to 23
Default = 12 AM
Sunday, Monday,
Tuesday,
Wednesday,
Thursday, Friday,
Saturday
JANUARY to
DECEMBER
1 to 31
Default = 1
2006 to 2038
Default = 2013
User
Installer
User
Installer
User
Installer
User
Installer
User
Installer
User
Installer
MINUTE
Select the current time minutes.
HOURS
Select the current time hours.
DAY OF WEEK
Select the current day of the week.
MONTH
Select the current month.
Conditions: Available when Daylight Savings Time is On.
DAY OF MONTH
Select the day of the current month.
Conditions: Available when Daylight Savings Time is On.
YEAR
Select the current year.
Conditions: Available when Daylight Savings Time is On.
OFF or ON
Default = ON
12 or 24 hour
Default = 12 hour
OFF or ON
Default = OFF
User
Installer
User
Installer
User
Installer
DAYLIGHT SAVINGS TIME
Select if daylight savings time is observed.
TIME MODE
Select either 12 or 24 hour time format.
CLOCK
Select whether or not to show the time clock on the
display.
The Schedule menu can operate on a 24 hour or 7 day repeating schedule. When a 24 hour schedule is selected,
“SuMoTuWeThFrSa” is shown on the top of the screen to show that the event time applies to all days of the week. When
a 7 day schedule is selected, each individual day of the week is shown with the event time.
The Schedule menu is not available when the Application Mode is set to 090.
Item FieldRangeAccessDescriptionSet to
12:00 AM to 11:50
SuMoTuWeThFrSa
SuMoTuWeThFrSa
PM, SKIP
or
00:00 to 23:50,
SKIP
Default = 6:00 AM
12:00 AM to 11:50
PM, SKIP
or
00:00 to 23:50,
SKIP
Default =
10:00 PM when
Event/Day is 2
8:00AM when
Event/Day is 4
User
Installer
User
Installer
EVENT 1
The first programmable schedule time period of the
day. During Event 1 the control operates in MELT
operation.
EVENT 2
The first programmable schedule time period of the
day. During Event 2 the control operates in OFF or
IDLE operation.
SuMoTuWeThFrSa
SuMoTuWeThFrSa
12:00 AM to 11:50
PM, SKIP
or
00:00 to 23:50,
SKIP
Default = 6:00 PM
12:00 AM to 11:50
PM, SKIP
or
00:00 to 23:50,
SKIP
Default = 10:00
PM
Always available
OFF, ZONE
Available with
tekmarNet
®
OFF, ZONE,
Master 1, 2, 3, 4,
Member 1, 2, 3, 4
Default = OFF
User
Installer
User
Installer
User
Installer
EVENT 3
The first programmable schedule time period of the
day. During Event 3 the control operates in MELT
operation.
EVENT 4
The first programmable schedule time period of the
day. During Event 4 the control operates in OFF or
IDLE operation.
SCHEDULE
Select if the control should change the temperature
automatically using a programmable schedule.
OFF = Programmable schedule is not used.
Zone = Applies to this control only.
Master 1, 2, 3, 4 = In charge of one of four available
Select between a 24 hour schedule or a 7 days per
week schedule.
Page 17
Display Menu
The Display menu items select the temperature units and backlight options.
Item FieldRangeAccessDescriptionSet to
°F or °C
Default = °F
User
Installer
UNITS
Select Fahrenheit or Celsius as the temperature
units.
BACKLIGHT
ON,
ON MELT,
OFF
Default =
ON MELT
User
Installer
Select how the display backlight operates.
ON = Always on.
ON MELT = On when melting, off when not melting.
This provides a visual indicator to occupants that the
snow melting system is currently melting.
OFF = Always off.
Scene Menu
The Scene menu items selects if the away scene and the away key are available. The Scenes menu is not available when the
Application Mode is set to 090.
Item FieldRangeAccessDescriptionSet to
NONE or AWAY
Default = NONE
User
Installer
SCENES
Enable or disable the use of scenes (building overrides)
on this control.
OFF or ON
Default = OFF
User
Installer
AWAY KEY
Enable or disable the away touch key on the home
screen.
The Toolbox Menu is a location for system information and Test functions. If any errors are present on the system, they will be
located at the beginning of this menu.
Item FieldRangeAccessDescription
ACCESS LEVEL
Installer (INST)
User (USER)
Default = INST
User
Installer
Select the access level of the control, which determines which menus
and items are available.
Conditions: Adjustable only when control switch setting set to UNLOCK
or tekmarNet® system control switch setting set to UNLOCK.
Software J1226A
Type 654
User
Installer
Not applicableInstaller
See Troubleshooting
Guide
Installer
SOFTWARE VERSION AND TYPE NUMBER
Select the access level of the control, which determines which menus
and items are available.
FACTORY DEFAULTS
Loads the factory default settings. Press ENTER to load defaults.
HISTORY - 1 THROUGH 5
Displays a history of any past errors that have occurred on the system.
Will clear after 30 days, or press Up and Down buttons for 1 second
to manually clear. The last 5 history items will display if present.
The Override Menu allows an operator to manually test each relay and manually start the system.
Item FieldRangeAccessDescription
Hydronic
AUTO, HAND,
MAX, PRGE, OFF
Electric
AUTO, HAND,
TEST, OFF
Default = AUTO
OFF or ON
Default = OFF
OFF or ON
Default = OFF
0 to 100%
Default = 0%
0 to 100%
Default = 0%
Installer
Installer
Installer
Installer
Installer
MANUAL OVERRIDE
Manually override the normal automatic operation of the control to test
the equipment or operate the system at the maximum temperature
limits.
AUTO = Normal operation
HAND = Manual override of each relay output
MAX = Operate hydronic system at maximum heat
TEST = Operate electric system for 10 minutes
PRGE = Hydronic system purge operates pumps to help bleed air
from the system
SYSTEM PUMP RELAY
Manually turn on the system pump during the HAND Manual
Override.
HEAT RELAY
Manually turn on the heat during the HAND Manual Override.
BOILER PERCENT
Manually set the modulating boiler firing rate during the HAND
Manual Override.
Conditions: Application Mode is set to Boil.
MIX PERCENT
Manually set the mixing valve or mixing injection pump output during
the HAND Manual Override.
Conditions: Application Mode is set to Mix.
OFF or ON
Default = OFF
0:10 to 72:00
hours
Default = 0:10
hours
0:10 to 72:00
hours
Default = 24:00
hours
0:10 to 72:00
hours
Default = 24:00
hours
Installer
Installer
Installer
Installer
ALERT RELAY
Manually turn on the alert relay during the HAND Manual
Override.
Conditions: Application Mode is set to PWM, Boil or Mix and Alert
Relay is set to ALRT (alert) or the Application Mode is set to Elec.
OVERRIDE TIME
Select the amount of time that the HAND
before returning to Automatic operation.
Manual Override
is in effect
MAXIMUM PURGE TIME
Select the amount of time that the PURGE Manual Override is in
effect before returning to Automatic operation.
Conditions: Application Mode is set to PWM, Boil or Mix.
MAXIMUM HEAT TIME
Select the amount of time that the MAX HEAT Manual Override is
in effect before returning to Automatic operation.
Conditions: Application Mode is set to PWM, Boil or Mix.
Select to limit the amount of melting run time after snow
is automatically detected by a Snow / Ice Sensor 090 or
094, or a Snow Sensor 095.
Conditions: Application Mode is set to PWM, Boil or
Mix or Elec.
Page 22
Boiler Menu
The Boiler Menu provides settings on how to configure and operate the boiler.
Item FieldRangeAccessDescriptionSet to
App Mode = Boil
MOD, 1STG,
EMS1, EMS2
Default = MOD
App Mode = Mix
OFF, ENBL,
CTRL
Default = OFF
App Mode = PWM
OFF, CTRL
Default = OFF
0-10 or 4-20
Default = 0-10
Installer
Installer
BOILER TYPE
The type of boiler connected to the control.
MOD = Modulating boiler.
1STG = Single one-stage on-off boiler.
EMS1 = tekmar boiler staging controls.
EMS2 = Viessmann modulating boilers with 0-10 V
OpenTherm Module.
CTRL = tekmarNet
ENBL = When operating a mixing valve or mixing
injection pump, the heat relay is closed to fire the
boiler.
®
System Control operates boiler.
BOILER MODULATION TYPE
Select if the modulating boiler accepts a 0-10 V (dc) or
4-20 mA input signal to control the boiler firing rate.
Conditions: Boiler Type is set to MOD (modulating
boiler).
0 to 50%
Default = 0%
OFF, 10 to 180
seconds
Default = OFF
30 to 230 seconds
Default = 30 seconds
AUTO, 2 to 42°F
(1.0 to 23.5°C)
Default = AUTO
OFF, 50 to 180°F
(10.0 to 82.0°C)
Default = OFF
Installer
Installer
Installer
Installer
Installer
BOILER MINIMUM MODULATION
The minimum percent modulation of the boiler burner.
Conditions: Boiler Type is set to MOD (modulating
boiler).
BOILER MODULATION DELAY
Delay time between the burner firing and the boiler
releasing to modulation.
Conditions: Boiler Type is set to MOD (modulating
boiler).
BOILER MOTOR SPEED
The time required for the modulating actuating motor to
fully open the gas valve or ramp the burner fan from off to
full speed on a modulating boiler. Set to 30 seconds unless
otherwise recommended by the boiler manufacturer.
Conditions: Boiler Type is set to MOD (modulating
boiler).
BOILER DIFFERENTIAL
The temperature differential that the control is to use to
cycle the boiler on and off (half above and half below
target).
Conditions: Boiler Type is set to MOD (modulating boiler)
or 1STG (one stage).
BOILER MINIMUM
The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommended supply water
temperatures.
Conditions: Application Mode is set to Boil or Application
Mode is set to Mix and the Boiler Type is set to CTRL (tN4
Control) and Out/Bret Sensor is set to RET (return).
The Mix Menu provides settings on how to configure and operate the mixing valve or mixing injection pump.
only available when the Application Mode is set to Mix.
Item FieldRangeAccessDescriptionSet to
MIX TYPE
0-10 or 4-20
Default = 0-10
30 to 230
seconds
Default = 105
seconds
Installer
Installer
Select the type of mixing analog signal.
0-10 = 0 to 10 V (dc)
4-20 = 4 to 20 mA
MIX MOTOR SPEED
The time that the mix actuating motor requires to operate
from fully closed to fully open.
Mixing Injection Pump = 30 seconds
tekmar Actuator Motor 741 = 105 seconds
Refer to actuating motor for correct setting.
The Mix menu is
80 to 180
°F
(26.5°C to 82.0°C),
OFF
Default = 140°F
(60
°C)
Installer
MIX MAXIMUM
Select the maximum operating temperature of the system
supply water.
The tekmarNet® menu includes settings of how the snow melting control communicates and operates together with other controls.
The tekmarNet® menu is only available when communication is detected.
Item FieldRangeAccessDescriptionSet to
Range: AUTO,
01 to 24,
b:01 to b:24,
1:01 to 1:24,
Installer
2:01 to 2:24,
3:01 to 3:24
1 to 24Installer
ADDRESS
The tekmarNet® address of this control. To manually set
the address, use the up or down arrow buttons.
DEVICE COUNT
Provides a count of all the tekmarNet® thermostats,
setpoint controls and snow melting controls on the
tekmarNet® system.
1 to 12
Default = 1
OFF or ON
Default = OFF
1 to 12
Default = 1
1 to 12
Default = 12
Installer
Installer
Installer
Installer
SNOW ZONE
Select the Snow Zone that this control operates. Snow
Zone 1 has the highest priority while Snow Zone 12 has
the lowest priority.
TRACK ZONE
Select to track and record the running hours of Snow Zone
1 and repeats this run time on this control. This allows
snow zones without a snow / ice sensor to automatically
start.
Conditions: Snow Zone must be set 2 through 12 (cannot
be Snow Zone 1) and Application Mode is set to PWM,
Boil, Mix or Elec.
MELT GROUP
A User Switch may be used to manually start melting
the snow zone. Set the Melt Group number to the
corresponding Setpoint Enable number on the User
Switch.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
STORM GROUP
A User Switch may be used to manually start storm
operation of the snow zone. Set the Melt Group number
to the corresponding Setpoint Enable number on the
User Switch.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
OFF, COND,
FULL
Default = OFF
Installer
PRIORITY
Select the priority operation of the snow melting system.
Conditions: Application Mode is PWM, Mix or Elec.
LOCAL NETWORK GROUP
Select if scenes and time clock are shared when
OFF or ON
Default = OFF
Installer
connected to a tekmarNet® system.
OFF = Send and receive messages.
ON = Receive messages only.
Conditions: Application Mode is set to PWM, Boil, Mix
or Elec.
A snow melting system can offer a safe, convenient, and cost
effective way of removing snow and ice from the snow melting
slab and similar surfaces. Safety is increased by activating
the snow melting system as soon as the snow falls rather
than waiting for mechanical snow removal after snow has
accumulated. This eliminates slip hazards and reduces the
risk of injury by mechanized snow melting equipment, thereby
reducing potential liability costs. The elimination of snow plow
equipment and corrosive salts also reduces damage to the
slab surface and to the environment. Snow melting systems
when controlled correctly can be cost competitive compared
to mechanical snow removal.
Slab Temperature Control
Controlling the slab temperature is critical to minimizing the
cost of snow melting. This requires that either a Snow / Ice
Sensor 090 or 094 or a Slab Sensor 072 or 073 is installed.
The Snow / Ice Sensor contains a built-in slab temperature
sensor. While the control will continue to operate without a
slab sensor installed, operating costs will be much higher.
The slab is operated using slab outdoor reset. As the outdoor
temperature gets colder, the heat loss of the slab increases.
In order to keep the slab surface at a constant temperature
while operating, the inner core of the slab must be heated
above the melt, idle or storm temperature setting. The amount
that the slab inner core temperature is above the melt, idle
or storm setting is proportional to the outdoor temperature.
Since the slab sensor is installed below the surface of the
slab, it is not measuring the true slab surface temperature but
rather the inner core temperature. The control automatically
compensates for this temperature difference. However, the
The snow melting control can operate in one of four
different ways:
Melt
Idle
Heats the slab to melt snow or ice
Pre-heats the slab just below freezing to shorten the
time required to melt snow
Storm
Temporarily pre-heats the slab just below freezing to
shorten the time required to melt snow
Off
Snow melting system is off
The control display shows the control operation in the home
screen.
Slab item in the View menu displays the actual measured
temperature, so it is normal to view slab temperatures that
exceed the melt, idle, or storm temperature settings.
Slab Outdoor ResetSlab Outdoor Reset
Surface temperature = 35F
Core (sensor)
is warmer
Decreasing Air Temperature
Slab Surface Temperature is Constant
Increasing Slab Core Temperature
Melt Operation
The snow melting system operates the heating equipment
to heat the slab from a cold start or from the idle or storm
temperature to reach the melt temperature setting to melt
snow or ice. Melt operation can be triggered automatically using a snow / ice sensor, by tracking the run time
of another zone, manually by pressing a button, or by a
programmable schedule. The melt temperature setting
affects calculated targets such as the slab target, boiler
target and mix target.
Page 26
Melt - Manual Start and Timed Stop
The snow melting system can be started manually in one of
three different methods:
Touch the Melt key on the control display.
•
Press the Setpoint Enable button on a User Switch.
•
Activate through a Gateway webpage or home automation
•
system.
Press
Melt
tN4 User Switch
480 or 481
Storm
Press
Melt
Melt
Away
Once manually started, the snow melting system continues to
operate until the time set by the Manual Melt Run Time setting
in the Set Temp menu elapses.
If a manual start has been provided and a Snow / Ice Sensor
detects water, the control changes from manual melt to
automatic operation. The snow melting system will continue
to operate until the sensor is dry and the Additional Melt
Time elapses.
095 detects water
Touch MELT key
095 detects water
Tracked zone melt
Idle
or
Off
User Switch / Gateway Enable
MANUAL MELT RUN TIME elapses
Tracked zone time elapses
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
CWCO
Timed
Melt
Melt - Automatic Start and Stop
Automatic start and stop operation requires the installation
of a Snow / Ice Sensor 090 (65' or 20 m cable) or 094 (210'
or 64 m cable). The control continually monitors the sensor
for the presence of moisture and slab temperature conditions in which snow or ice may be present. When moisture
is detected, the control will show “Sensor Water Wet” in the
View menu. When the sensor is dry the control will show
“Sensor Water Dry”. The control includes a Sensitivity
setting in the Set Temp menu that allows the installer to
adjust the amount of moisture required to start and stop the
melting operation. In areas with low amounts of dust and
/ or air pollution, the sensitivity may need to be increased.
The Sensitivity setting default is Auto, and the control will
automatically determine the best suitable sensitivity setting
for the installation.
Snow / Ice Sensor
090 or 094
When moisture is detected and the slab and outdoor temperatures
are at or below freezing, the control will automatically start the
snow melting system. As the snow or ice melts and the slab dries
off, the sensor also dries off at the same time. When the sensor
is dry, the snow melt system automatically shuts off. If there are
low spots on the slab surface that dry off slower than the sensor,
additional melting run time can be included by adjusting the
Additional Melt Time setting in the Set Temp menu.
If the snow melting system is manually stopped, the Snow / Ice
Sensor must fully dry before it is able to detect a new snow fall
and automatically start the snow melting system.
When a Snow / Ice Sensor 090 or 094 is installed, the installer
can choose to select to either automatically or manually
start the snow melting system. Selecting EconoMelt to On
provides the option to remove the snow using a snow plow
or shovel and then use the snow melting system to melt the
remaining thin layer of snow or ice that mechanical snow
removal methods are unable to remove. The snow melting
system stops when the sensor is dry. The factory default for
EconoMelt is Off.
Melt - Automatic Start and Timed Stop
Automatic start with a timed stop operation requires the installation of a Snow Sensor 095. It is also highly recommended to
install a Slab Sensor 072 (20’ or 6 m cable) or 073 (40’ or 12 m
cable) in order to regulate the slab temperature and operate
the snow melting system at the highest possible efficiency.
The control continually monitors the sensor for the presence
of moisture and slab temperature conditions in which snow or
ice may be present. When moisture is detected, the control will
show “Sensor Water Wet” in the View menu. When the sensor
is dry the control will show “Sensor Water Dry”. The control
includes a Sensitivity setting in the Set Temp menu that allows
the installer to adjust the amount of moisture required to start
Touch START key
090 and slab dry and
ADD MELT time elapses
Off
Touch STOP key
AWAY scene
WWSD
User Switch / Gateway Disable
Enters
CWCO
Melt
Melt
Suspended
Exits
CWCO
and stop the melting operation. In areas with low amounts
of dust and / or air pollution, the sensitivity may need to be
increased. The factory default is for the Sensitivity setting is
Auto. The control automatically determines the best suitable
sensitivity setting for the installation.
When moisture is detected and both the slab and outdoor
temperatures are below the Melting setting, the control automatically starts the snow melting system. The snow melting
system operates to heat the slab to the slab target temperature
and continues to operate until the time set by the Manual Melt
Run Time in the Set Temp menu elapses.
Snow
Sensor 095
Idle
or
Off
Touch MELT key
095 detects water
Tracked zone melt
The snow melting system can have multiple zones. Zones
have the option to track the melting run time of zone 1. This
is useful in cases where zone 1 has an automatic Snow / Ice
Sensor installed and the remaining zones do not. This allows
zones 2 to 12 to gain the functionality of automatic starting
and stopping with only one Snow / Ice sensor installed in the
system.
When zone 1 detects snow or ice, it starts melting. Zones
with tracking enabled can also start melting unless priority is
selected. When the sensor in zone 1 is dry or the Manual Melt
Run Time has fully elapsed, it sends a signal to the tracked
zones that zone 1 has stopped. Each zone can continue to
operate to complete their own Additional Melt Time after which
the zone stops heating and returns to the Off or Idle operation.
Zones with priority selected start after zone 1 has finished
melting and repeat the same run time as zone 1.
Track Melt Start and Stop
Zone 1
Snow / Ice
Sensor
Records
Run Time
Zone 2Zone 3
Slab
Sensor
Repeats
Zone 1 Run
Time + Add
Melt Time
Slab
Sensor
Repeats
Zone 1 Run
Time + Add
Melt Time
Melt - Scheduled Start and Stop
The snow melting system can be started based upon a
programmable schedule. The time clock must cross past the
scheduled event time in order to start or stop. In addition,
operation is dependent or whether or not a slab sensor, snow
/ ice, snow sensor or no slab sensor is installed.
The use of a programmable schedule is well suited for
commercial installations where operation is not required 24
hours a day.
Systems With Automatic Detection
This applies when a Snow / Ice Sensor 090, 094 or Snow
Sensor 095 is installed.
When the time clock reaches the schedule Event 1 (wake)
time, the system is allowed to melt if the sensor detects
snow or ice.
When the time clock reaches the schedule Event 2 (unoccupied)
time, the system is off or in idle operation.
When the time clock reaches the schedule Event 3 (occupied)
time, the system is allowed to melt if the sensor detects
snow or ice.
--------------
When the time clock reaches the schedule Event 4 (sleep)
time, the system is off or in idle operation.
Systems Without Automatic Detection
----------
This applies when a Slab Sensor 072, 073 or no slab sensor
is installed and there is no automatic detection.
When the time clock reaches the schedule Event 1 (wake)
time, the system is in melt operation.
When the time clock reaches the schedule Event 2 (unoccupied)
time, the system is off or in idle operation.
When the time clock reaches the schedule Event 3 (occupied)
time, the system is in melt operation.
When the time clock reaches the schedule Event 4 (sleep)
time, the system is off or in idle operation.
A Snow / Ice Sensor 090 or 094 automatically shuts off the
snow melting system when the water sensor is dry. Due to
the construction of the slab and the layout of the heating
pipe or electrical cable, there may be areas that do not melt
completely. The Additional Melt Time setting in the Set Temp
menu allows the installer to set addition melting time after the
sensor is dry.
Idle Operation
When the snow melting system starts from a cold temperature,
there may be a long time delay before the slab is warm enough
to melt snow. This time delay allows snow to accumulate on
the slab which is not acceptable in some commercial and
institutional applications. To decrease the start up time, the
slab can be pre-heated to maintain a minimum temperature.
This is known as the Idle temperature. Idling requires large
energy consumption is generally recommended for institutional
and / or commercial installations where safety concerns are
paramount. Idle is shown on the display when the control is
in idle operation.
When designing a snow melting system, an engineer may
specify the amount of allowed snow accumulation as the
Snow-Free Area Ratio. There are three different levels. A
Snow-Free Area Ratio of 1 is defined as a system that melts
all snow as it falls with no allowed accumulation. This requires
that the Idle temperature be set just below freezing. Examples
of these types of applications include:
Hospital emergency areas
•
Helicopter landing pads
•
Parking garage ramps
•
A Snow-Free Area Ratio of 0.5 is defined as a system with
partial snow accumulation on the slab but not in all areas.
These types of systems may also use Idling but usually set
Snow Ice Sensor
Dry
at a temperature several degrees below freezing to reduce
energy consumption. Applications may include:
Steep residential driveways
•
Commercial sidewalks
•
Loading docks
•
A Snow-Free Area Ratio of 0 is defined as a system that
allows snow accumulation. These systems operate the snow
melting system from a cold start resulting in the lowest energy
consumption costs and the longest times to start melting snow.
In this case set the Idle to off. This is recommended for most
residential applications:
Flat residential driveways
•
Patios
•
Residential sidewalks
•
Some systems are designed for keeping a slab surface free of
ice rather than free of snow. The most common applications
include:
Car wash bays and aprons
•
Aircraft hanger aprons
•
Turf conditioning on golf course greens
•
These systems require the use of Idling at or near freezing throughout the winter and may result in high energy consumption.
Storm Operation
For many residential applications it is too costly to Idle the snow
melt system all winter. Storm combines the benefits of a fast
response time together with lower operating costs. The Storm
operation does this by allowing the user to manually pre-heat
the slab temporarily in preparation of a snow fall warning. In the
event that snow falls and is detected by a Snow / Ice Sensor
or a Snow Sensor or the system is manually started, the snow
melt system heats the slab up to the melting temperature
and completes a melting cycle. Should no snow fall during
the storm time period, the control exits Storm operation and
returns to Off.
The Storm operation is setup by setting the Storm temperature
and the Storm Run Time in the Set Temp menu. The Storm
operation can only be activated by a User Switch or Gateway.
To respond to a User Switch or Gateway, select the Storm
Group number to be 1 through 12. Then program the User
Switch or Gateway setpoint enable to be the same as the
Storm Group. Pressing the programmed User Switch button will
now activate the Storm operation on the snow melting control.
Likewise, sending the setpoint enable command through the
Gateway 482 will enable the Storm operation. On the Gateway
483, activating the storm group on the Scenes page in turn
enables the Storm operation.
Press
Storm
Storm
Melt
Away
Page 30
Warm Weather Shut Down
---------------------------------------
--------------------------------------
--------------------------------
During warm weather, the slab is warm enough to naturally
melt snow or ice. The control has a Warm Weather Shut
Down (WWSD) setting in the Set Temp menu that prevents
the control from entering Melt, Idle or Storm operation in order
to conserve energy. The control shows WWSD on the display
when WWSD is in effect.
Automatic (Auto)
The control enters WWSD when both the slab temperature
of a zone and the outdoor temperature exceed the Melt
temperature setting by more than 2°F (1°C).
Cold Weather Cut Out
Maintaining the melting or idling temperature during extremely
cold temperatures is not only expensive but may be impossible if the heat loss of the slab exceeds the input capacity
of the heating plant or electric cable. The control turns the
snow melting system off when the outdoor air temperature
drops below the Cold Weather Cut Out (CWCO) temperature
and the slab is below freezing. This is a safety and energy
saving measure. The control shows CWCO on the display
Away Scene
Manual WWSD
The control enters WWSD when the outdoor air temperature
exceeds the WWSD setting by 1°F (0.5°C) and when the
slab temperature exceeds 34°F (1°C). The control exits
WWSD when the outdoor air temperature falls 1°F (0.5°C)
below the WWSD setting or if the slab temperature falls
below 34°F (1°C). This allows the Melt temperature setting
to be set higher than the WWSD. This is useful when high
slab temperatures are required to melt the snow or ice. An
example of this are installations using paving bricks on top
of sand and concrete layers.
when CWCO is in effect. When the temperature reaches the
CWCO setting in an actively melting system with an 090 or
094, melting is suspended until the outdoor temperature rises
above the CWCO setting. If an 090 or 094 is not installed,
melting is permanently stopped when CWCO is in effect.
Melting does not resume when the temperature rises above
the CWCO setting.
Scenes provide an easy way to save energy while away
on vacation, or override a programmable schedule when
plans change.
Away Key
---------------------------------------
This control includes an Away Key to quickly disable the
snow melting system, and when connected to a tekmarNet®
system, can also turn down the heating temperature on all
thermostats and suspend heating the domestic hot water
tank to maximize energy savings. To turn on the Away Key,
go to the Scene menu.
To activate the Away scene, touch “Going Away” on the
screen.
Select PERM (permanent) or a number of days using the
•
or arrow. Range is 1 to 180 days.
Press the home button to accept the setting or leave the
•
screen untouched for several seconds.
“Scene Away” is displayed on the home screen until the
•
number of days expires.
Touch “Cancel Away” to cancel at any time.
•
User Switch
A User Switch may be used to activate the Away scene.
Press
--------------------------------------
Storm
Melt
Away
Away
Additional Scenes
The snow melting control supports scenes 1 (normal) 2
(away) and 3 (unoccupied). Scene 3 disables the snow
melting system. When the tekmarNet® system is set to
scene 4 through 8, the snow melting control remains in
scene 1.
To provide greater energy savings, the control can operate on
a programmable schedule. The schedule is stored in memory
and is not affected by loss of power to the control. If tekmarNet®
communication is detected the control can become either a
schedule member or schedule master.
Zone Schedule
The schedule only applies to the control. The control follows
its own schedule and the events are not communicated to the
tekmarNet® system.
Master Schedule
If the control is connected to other tekmarNet® devices, then
the control can operate on a master schedule. A maximum of
four master schedules are available on the tekmarNet® system.
Using master schedules simplify installation since one master
schedule may be used by multiple devices.
----------------------------------
--------------------------------
To create a master schedule:
•
Assign the control to be a schedule master by setting
Schedule in the Schedule menu to Master (MST) 1 to 4.
Time Clock
The control has a built-in time clock to allow the control to
operate on a schedule. A battery-less backup allows the
control to keep time for up to 4 hours without power. The time
To follow a master schedule:
Assign the control to follow a master schedule by setting
•
Schedule in the Schedule menu to Member (MBR) 1 to 4.
Schedule Types
The schedule type determines when the schedule repeats
itself. This control includes two different schedule types:
• 24 Hour: Repeats every 24 hours.
• 7 Day: Repeats on a weekly basis and allows for separate
event times for each day.
---------------------------------
Events / Day
The events / day can be either 4 or 2. An event is a time at
which the control changes the target temperature. The event
time can be set to the nearest 10 minutes. To have the control
skip the event, enter “SKIP“ as the time. SKIP is found between
11:50 PM and 12:00 AM or 23:50 and 00:00 hours.
clock supports automatic adjustment for Daylight Saving Time
(DST) once the day, month and year are entered. Use the Time
menu to set the correct time, day, month and year.
Snow Melt Zones and Priority
Dividing a system into a number of snow melting zones and
prioritizing the zone operation reduces the size requirements
of the hydronic heating plant or the amperage of the electrical service panel. This results in lower initial capital cost of
the snow melting system. The trade off is that some snow
melt zones may not be able to melt as soon as the snow fall
begins and the user must tolerate snow accumulation on the
slab. The snow melt system may have up to 12 snow melt
zones. Zone 1 has the highest priority and zone 12 has the
lowest. The priority setting in the tekmarNet® menu allows
the installer to select the level of zone priority for entire snow
melt system. Changing the priority setting on one control
will update on all other snow melt controls at the same time.
The zone priority has 3 setting levels. There is some risk
that lower priority zones may ice up when they are shut off
by the higher priority zone. For example, if a high priority
zone should finish melting and allow a lower priority zone
to start melting, and then a new snow fall occurs, the high
priority zone will shut off the lower priority zones. This may
potentially allow the lower priority zones to ice over. The
limitations of zoning and using priority must be carefully
considered and discussed with the building owners and
occupants when designing the snow melting system.
Priority does not apply when the application mode is set to
Boiler. In this mode, the boiler is dedicated to a single snow
melting zone so priority is no longer applicable.
Electric snow melting offers three levels of priority: None,
Conditional and Full. The None and Full priority options function
the same as with the hydronic operation. The Conditional
priority is unique to electrical operation. The highest priority
zone operates first. Whenever the highest priority zone shuts
MELT
OFF
MELT
OFF
Zone 1
Zone 2
OFF
Zone 2
off its relay, the lower priority zone is allowed to start melting
and close its relay. Only one electrical relay is allowed to be
on at any time. This eliminates large instantaneous demands
and avoids surcharges from the electrical utility.
In a hydronic snow melting system, the boiler or heating
plant capacity may be much larger than the load of the snow
melting zones. This can result in large temperature differentials
between the supply water temperature and the slab creating
large tensile stresses on the slab. Concrete is weak to tensile
forces and when repeatedly exposed to tensile loads the
concrete may crack. This may be prevented by selecting the
Protect Slab setting in the System menu to On. The control
measures and limits the temperature differential between
the supply water and the slab.
Application Modes
tensile stresses
The snow melting control can operate either an electric or
a hydronic snow melting system. A hydronic system can be
further categorized as either boiler, mixing or pulse width
modulation zone operation, as well as, whether the boiler
plant is dedicated or non-dedicated for the snow melting
system. A dedicated boiler only provides heat from the snow
melting system. A non-dedicated boiler provides heat for
the snow melting system in addtion to the space heating
and / or domestic hot water system. The control requires
Electric Operation
The control operates the heat relay on a 20 minute pulse
width modulation cycle. The heat relay in turn activates a
line voltage electrical contactor to energize the electrical
cable heater installed in the slab. The heat relay on time is
determined by the calculated slab target and by the measured
slab temperature reading. As the slab temperature reaches
the slab target, the on time per cycle of the heat relay is
Pulse Width Modulation Operation
The Application Mode should be set to Pulse Width Modulation
(PWM) when the boiler or heat source is non-dedicated to
the snow melting system and there is no mixing system. The
snow melting system is considered to be a zone together with
space heating and the domestic hot water system.
The control operates the heat relay on a 20 minute pulse width
modulation cycle. The heat relay in turn activates the hydronic
heating system zone pump or zone valve. The heat relay on
time is determined by the calculated slab target and by the
measured slab temperature reading. As the slab temperature
reaches the slab target, the on time per cycle of the heat relay
that one of the following Application Modes is selected in
the System menu:
•
PWM Pulse Width Modulation
•
BOIL Boiler Operation
MIX Mixing Operation
•
ELEC Electrical Operation
•
090 Tandem Snow / Ice Detection using an
•
090 or 094
reduced to prevent the slab temperature from overshooting.
If no slab sensor is installed the heat relay remains on 100%
of the time until the Melt operation has completed. Idle and
Storm operation are not available when a slab sensor is not
installed. The electric operation requires the installation of
an outdoor sensor. A slab sensor is highly recommended in
order to reduce operating costs.
is reduced to prevent the slab temperature from overshooting.
If no slab sensor is installed the heat relay remains on 100%
of the time until the Melt operation has completed. Idle and
Storm operation are not available when a slab sensor is not
installed. The hydronic PWM operation requires the installation
of an outdoor sensor and a supply sensor. The supply sensor
is installed on the glycol antifreeze system supply pipe and
allows the control to provide Slab Protection and as well as
Supply Zone Priority. A slab sensor is highly recommended
in order to reduce operating costs.
Boiler Operation
The Application Mode should be set to Boil when the snow
melting system has a dedicated boiler or heat source. The
boiler is piped primary-secondary to the snow melting loop,
allowing the boiler to fire on and off while allowing continuous flow through the snow melting system loop. The control
calculates a Boiler Target based upon the Slab Target which
in turn is based upon the measured outdoor temperature and
the Melt, Idle or Storm temperature setting. The control can
operate a boiler in one of six different methods: modulating
boiler, 1 stage, EMS1, EMS2, control and enable. The Boiler
Target is shown in the View menu. Settings for the boiler
operation are located in the Boiler menu.
Important Note: The boiler operator, or aquastat, remains in
the burner circuit and acts as a secondary upper limit on the
boiler temperature. The boiler aquastat temperature setting
must be adjusted above 200°F (93.5°C) in order to prevent
short cycling of the burner.
Page 34
Single Stage On/Off Boiler (1STG)
---------------
------------------------
--------------------------------------------
--------------------------------------------
----------------------------------
-----------------------------------
The control turns on or off the heat relay to fire the boiler in order
to maintain the Boiler Target temperature. The boiler supply
temperature operates on a differential that is half above and
half below the boiler target. The status of the boiler is shown
by the Boil Relay item in the View menu.
Modulating Boiler (MOD)
The control can operate a single hot-water modulating boiler
using the Mod output and the Heat contact. The control
operates the boiler by first switching the heat contact to allow
the modulating boiler to go through the ignition sequence
(the heat contact may not be required on all modulating
boilers). A 0-10 V (dc) or 4-20 mA analog signal is then used
to modulate the boiler firing rate starting at 50% (5 V (dc) or
12 mA signal) for 30 seconds. After the 30 second delay has
elapsed, the control will then allow the boiler to modulate down
to the Minimum Modulation setting and hold it there for the
Modulation Delay time setting. After the modulation delay has
elapsed, the control uses PID logic to change the boiler firing
rate signal in order to satisfy the boiler target temperature.
When the firing rate signal is reduced down to the minimum
modulating setting and the boiler supply temperature exceeds
the boiler target by 1/2 of the differential, the control will shut
off the boiler burner. The modulating signal output is shown
by the Boil Rate item in the View menu.
The Modulation Delay setting is determined by the boiler
manufacturer. It is the amount of time that the burner must
operate before the internal boiler control allows an external
signal to operate the burner.
The Motor Speed sets the rate at which the modulating electrical
signal can change. For most modulating boilers with a ECM
fan, the motor speed can be set to 30 seconds. For commercial
boilers with a mod motor, set the motor speed according to
the time required by the mod motor to travel from the closed
to open position.
EMS1
--------------------------------------------
The EMS1 signal is a method for the snow melting control to
send the boiler target temperature to a tekmar Boiler Control
268. The control provides a 0-10 V (dc) signal proportional
to the boiler target and turns on the heat relay to operate the
boiler to maintain the Boiler Target temperature.
------------------------
---------------
EMS2
--------------------------------------------
The EMS2 signal is a method for the snow melting control to
send the boiler target to a Viessmann boiler that supports the
OpenTherm temperature targeting. Typical boilers include the
Viessmann Vitodens 100-W and 200-W. The boiler may require
an OpenTherm Input Module 0-10V. Contact Viessmann for
details. The control provides a 0-10 V (dc) signal proportional
to the boiler target and turns on the heat relay to operate the
boiler to maintain the Boiler Target temperature.
Control (CTRL)
When the Application Mode is set to Mix or to PWM, the
snow melting control can send a call for heat message using
tekmarNet® communication to the tN4 System Control. The
call for heat is received on the water temperature bus that
the snow melting control is communicating on. When wired
to a boiler bus, the snow melting control calls for heat on the
boiler bus. The same logic applies to the mixing and tank bus
available on the tN4 System Control. In most cases, the Boiler
Type is set to Control when the snow melting system has a
non-dedicated boiler plant.
A tN4 System Control is defined as a control that operates a
boiler or mixing system. At the time of this writing the available
controls are:
Boiler Control 274, 275, 284
•
House Control 400, 401, 402, 403, 406
•
Reset Modules 420, 421, 422, 423
•
Enable (ENBL)
When the Application Mode is set to Mix, the snow melting
system may have a non-dedicated boiler plant. When not using
tekmarNet® communication, the heat relay closes whenever
the mixing device is increasing and reaches a position or
speed of 10%. The heat relay opens when the mixing device
is decreasing and reaches a position or speed of 5%.
The Application Mode can be set to Mix when a mixing valve
or a mixing injection pump is installed to regulate the supply
water temperature to the snow melting system. The boiler or
heat plant can be either dedicated or non-dedicated to the
snow melting system. The mixing device position or speed is
controlled by an analog 0-10 V (dc) or a 4-20 mA signal so that
the supply temperature maintains the Mix Target temperature.
The control calculates a Mix Target based upon the Slab
Target which in turn is based upon the measured outdoor
temperature and the Melt, Idle or Storm temperature setting.
The Mix Maximum setting limits the upper temperature of the
Mix Target. The Mix Target is shown in the View menu.
Boiler protection is only available when the snow melting control
is connected to a tN4 System Control. The tN4 System Control
provides the outdoor temperature to the snow melting control
using tekmarNet(R) communication. See Boiler Operation
section regarding recommended tN4 System Controls. The
mixing device provides boiler return protection to the boiler
inlet by closing the valve when the boiler return temperature
falls below the Boiler Minimum setting. Boiler return protection
requires the installation of a boiler return sensor 082 on the
inlet to the boiler and the Outdoor/Boiler Return Sensor setting
must be set to Boiler Return.
The 654 provides a 0-10 V (dc) signal to operate an actuator
motor for mixing using a 3 or 4-way mixing valve.
Recommended Mixing Injection Pumps
The control provides a 0-10 V (dc) or 4-20 mA signal to operate
a mixing device. In large commercial applications, a Variable
Frequency Drive (VFD) that can accept a 0-10 V (dc) or 4-20
mA can be used to vary the speed of the mixing injection
pump. For residential and smaller commercial applications,
specialized wet rotor, split-capacitor pumps that accept a 0-10
V (dc) signal are available from Grundfos and Taco. See Essay
E021 for piping information. The recommended models are
listed in the table below.
TacoGrundfos
----------------
---------
UP 15-42
F/VS
UP 26-64
F/VS
Required Taco 00-VV control settings:
DIP SwitchDIP Switch Position Description
1ONOperates using a linear output characteristic
2OFFAutomatic operation
3OFFOperates using a 0-10 V (dc) signal
Required Grundfos VS control settings:
DIP SwitchDIP Switch PositionDescription
AOFFOperates using a V (dc) signal
BOFFOperates using 0-10 V (dc) range
CONMinimum speed is off
DONSpeed control external
In systems where reliability of the snow melting system is
critical, it is possible to install two Snow / Ice Sensors 090
or 094 into a single snow melt zone. Both sensors are used
to detect snow or ice and if either sensor is wet the snow
melting zone starts melting. The zone continues to operate
until both sensors are dry. This allows snow or ice detection
over a wider area. In the event of a sensor failure, the snow
melting zone continues to function normally, giving building
maintenance staff time to troubleshoot and replace the sensor
if necessary.
In order to setup a zone using tandem snow / ice detection:
Step 1:
Step 2:
Install two Snow Melting Controls 654 each having
their own Snow / Ice Sensor 090 or 094.
Connect the two 654 together using tekmarNet®
communication.
Snow Zone 1
Master
App Mode
tekmarNet
PWM, Boil,
Mix, Elec
Step 3:
Step 4:
Step 5:
®
In the tekmarNet® menu, select the Snow Zone that
the 654 is to operate. There can be up to 12 different
Snow Zones. Both 654 controls must be set to the
same Snow Zone number.
On one of the 654, select the Application Mode to
PWM, Boil, Mix or Elec. This control is the Snow
Zone Master and it will operate the snow melting
equipment.
On the other 654, select the Application Mode to 090.
This control is the Snow Zone Member. This control
must be wired to power, tekmarNet® communication,
and the Snow / Ice Sensor 090 or 094.
Communication
Snow Zone 1
Member
App
Mod
090
Operates
Snow Melting
Snow Zone 1
Equipment
Exercising
In a hydronic snow melting system, the control operates the system pump as well as the mixing valve or mixing injection pump
every 3 days to prevent pump and valve seizure.
Alert Relay
The control includes an auxiliary relay that can be configured to be either a system pump or an alert output. When the Auxiliary
Relay setting in the System menu is set to Alert, the relay closes whenever there is a local error code. A network error on the
tekmarNet® communication system is not considered a local error code and the Alert Relay does not close if only a network
error is present. The Alert Relay is connected to the input power R and provides a 24 V (ac) powered signal when closed. An
isolation relay may be installed if a dry contact switch is required on the 3rd party equipment.
Pump Post Purge
After a zone has finished heating, the boiler or heat source is shut off and the zone continues to operate for 20 seconds to post
purge heat from the boiler to the zone.
The snow melting control is able to respond to a setpoint enable
signal from a User Switch or Gateway to remotely activate
or deactivate the storm or melt operation. The tekmarNet®
communication system supports setpoint enable signals 1
through 12. When the snow melting control receives a setpoint
enable signal that is the same as the Melt Group number, the
control enters Melt operation. Likewise, if the snow melting
control receives a setpoint enable signal that is the same as
the Storm Group number, the control enters Storm operation.
Each snow melting control has its own Melt Group and Storm
®
Group setting located in the tekmarNet
menu.
User Switch Setup
A User Switch 480 or 481 can be programmed to allow a user
to remotely activate or deactivate the storm, melt, and away
operations of the snow melting control. The User Switch has
three buttons and it is recommended to have the top button
setup to start or stop the Storm operation, the middle button
start or stop the Melt operation and the bottom button selects
if the scene is Away or Normal.
Storm
Melt
Away
BUTTON
A
User
Button
User
Button
User
Button
1
2
3
BUTTON
B
Melt Group 1
Melt
Group
Melt
Group
1
2
Zone 1Zone 2
Melt Group 2
Zone 3Zone 4
Setup Instructions
------------------------------
The User Switch has a total of 5 buttons.
User Buttons 1, 2, and 3 allow for users to select the operation
of the tekmarNet® system.
Buttons A and B allow the installer to program the operation
of User Buttons 1, 2, and 3.
The User Switch trim bezal must be removed to program and
must be reinstalled after programming is complete.
Storm Button
Step 1:
Press button “A” once using a blunt object to begin
programming mode.
Step 2:
Press and hold the top button until is turns Green,
then let go.
Step 3:
The snow melting control Storm Group default is 12.
Press the User Switch top button 12 times to set the
setpoint enable to 12. The button should flash Green
12 times, pause, then repeat the flashing sequence.
Step 4:
Press button “B” to finalize the User Button setting
and exit the programming mode.
Melt Button
Step 1:
Press button “A” once using a blunt object to begin
programming mode.
Step 2:
Press and hold the middle button until is turns Green,
then let go.
Step 3:
The snow melting control Melt Group default is 1.
Press the User Switch middle button 1 time to set the
setpoint enable to 1. The button should flash Green
1 time, pause, then repeat the flashing sequence.
Step 4:
Press button “B” to finalize the User Button setting
and exit the programming mode.
Away Button
Step 1:
Press button “A” once using a blunt object to begin
programming mode.
Step 2:
Press and hold the top button until is turns Red, then
let go.
Step 3:
The away scene number is 2. Press the User Switch
bottom button 2 times to set the scene number to 2.
The button should flash Red 2 times, pause, then
repeat the flashing sequence.
Step 4:
Press button “B” to finalize the User Button setting
and exit the programming mode.
It is recommended to complete all wiring to ensure trouble free operation. Should an error occur, simply follow these steps:
1. Find: If the control flashes on the screen, it is indicating a problem on the system.
2. Identify: Hold the Home button for 3 seconds, touch the NEXT key to locate the Toolbox Menu, then touch the ENTER key.
The error code should appear as the first item.
3. Solve: Use the chart below to match the error code to the one on the control. Use the description to solve the problem.
Error Messages (1 of 4)
Error MessageDescription
SET TEMP MENU SAVE ERROR
The control failed to read the Set Temp menu settings from memory and has reloaded the factory default
settings. The control stops operation until all settings in the Set Temp menu are checked.
To clear the error, set the access level to Installer and check all settings in the Set Temp menu.
SYSTEM MENU SAVE ERROR
The control failed to read the System menu settings from memory and has reloaded the factory default
settings. The control stops operation until all settings in the System menu are checked.
To clear the error, set the access level to Installer and check all settings in the System menu.
BOILER MENU SAVE ERROR
The control failed to read the Boiler menu settings from memory and has reloaded the factory default
settings. The control stops operation until all settings in the Boiler menu are checked.
To clear the error, set the access level to Installer and check all settings in the Boiler menu.
MIXING MENU SAVE ERROR
The control failed to read the Mixing menu settings from memory and has reloaded the factory default
settings. The control stops operation until all settings in the Mixing menu are checked.
To clear the error, set the access level to Installer and check all settings in the Mixing menu.
tekmarNet® MENU SAVE ERROR
The control failed to read the tekmarNet® menu settings from memory and has reloaded the factory
default settings. The control continues to operate but does not provide any tekmarNet® features until all
settings in the tekmarNet® menu are checked.
To clear the error, set the access level to Installer and check all settings in the tekmarNet
®
menu.
SCHEDULE MENU SAVE ERROR
The control failed to read the Schedule menu settings from memory and has reloaded the factory
default settings. The control operates with the programmable schedule disabled until all settings in the
Schedule menu are checked.
To clear the error, set the access level to Installer and check all settings in the Schedule menu.
SCENES MENU SAVE ERROR
The control failed to read the Scenes menu settings from memory and has reloaded the factory default
settings. The control operates with the away scene disabled until all settings in the Scenes menu are
checked.
To clear the error, set the access level to Installer and check all settings in the Scenes menu.
MAXIMUM MELT TIME ERROR
The control has operated in melting for the time set by Maximum Melt Days setting located in the System
menu. This error is usually created when there is a mechanical system failure resulting in the snow melt
slab not heating correctly.
Clear the error message by touching the Cancel key while viewing the error message. Use the Manual
Override menu to manually check that each component of the mechanical system is operating correctly.
If necessary, change the Maximum Melt Days setting to a longer time period or to Off.
tekmarNet® COMMUNICATION ERROR
The tekmarNet® communication bus has either an open or a short circuit. The result is that there are no
communications. Check for loose wires between tN4 and C. Check for short circuits between the tN4
and C wires on the House Control, Wiring Center, or Zone Manager. Check for correct polarity between
the C and R wires. The error clears automatically once the wiring fault has been corrected. To force the
error to clear while allowing a short or open circuit to continue, touch the Cancel key.
Two devices (thermostats, setpoint controls, snow melting controls) have been manually set to the same
address. The device continues to operate with this error but does not communicate with the tekmarNet®
system.
To clear this error, select an unused tekmarNet
SNOW ZONE TAKEN ERROR
Two snow melting controls have been manually set to the same snow zone number and one of the
controls is NOT set to App Mode 090. The control continues to operate with this error.
To clear this error, select an unused snow zone number or set the App Mode to 090.
APP MODE 090 ERROR
Two snow melting controls have been manually set to the same snow zone number and both of the
controls are set to App Mode 090.
To clear this error, select an unused snow zone number or set the App Mode to anything other than
090.
TANDEM 090 ERROR
There are two Snow / Ice Sensors 090 or 094 installed in the zone and the other snow melting control’s
090 or 094 has a sensor problem. Locate the other snow melting control and navigate to the Toolbox
menu to determine and correct the problem. The control continues to operate with this error.
®
address or select automatic addressing.
DEVICE LIMIT
More than 24 devices (thermostats or setpoint controls) have been connected to the tekmarNet®
communication bus. To clear the error, remove and relocate devices to other available buses until the
device count is 24 or less.
OUTDOOR SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Outdoor Sensor 070. The control continues to
operate and assumes an outdoor temperature of 32°F (0°C). Energy saving features such as Warm
Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are disabled.
Check the outdoor sensor wire for short circuits according to the sensor installation manual. It may
be necessary to replace the outdoor sensor. Once the error has been corrected, the error message
automatically clears.
OUTDOOR SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Outdoor Sensor 070. The control continues to
operate and assumes an outdoor temperature of 32°F (0°C). Energy saving features such as Warm
Weather Shut Down (WWSD) and Cold Weather Cut Out (CWCO) are disabled.
Check the outdoor sensor wire for open circuits according to the sensor installation manual. It may
be necessary to replace the outdoor sensor. Once the error has been corrected, the error message
automatically clears.
SUPPLY SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Supply Sensor 082. When set to App Mode Boiler
or Mixing the control stops operation and does not provide any heat. When set to App Mode PWM the
control continues melting or idling but supply priority operation is not available.
Check the supply sensor wire for short circuits according to the sensor installation manual. It may
be necessary to replace the supply sensor. Once the error has been corrected, the error message
automatically clears.
SUPPLY SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Supply Sensor 082. When set to App Mode Boiler
or Mixing the control stops operation and does not provide any heat. When set to App Mode PWM the
control continues melting or idling but supply priority operation is not available.
Check the supply sensor wire for open circuits according to the sensor installation manual. It may
be necessary to replace the supply sensor. Once the error has been corrected, the error message
automatically clears.
Due to a short circuit, the control is unable to read the Boiler Return Sensor 082. The control continues
operation but does not provide any boiler return protection.
Check the boiler return sensor wire for short circuits according to the sensor installation manual. It may
be necessary to replace the boiler return sensor. Once the error has been corrected, the error message
automatically clears.
BOILER RETURN SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Boiler Return Sensor 082. The control continues
operation but does not provide any boiler return protection.
Check the boiler return sensor wire for open circuits according to the sensor installation manual. It may
be necessary to replace the boiler return sensor. Once the error has been corrected, the error message
automatically clears.
SLAB SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the Slab Sensor 072 or 073. Idling and Storm are
disabled and energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather
Cut Out (CWCO) are operate using the outdoor temperature only.
Check the slab sensor wire for short circuits according to the sensor installation manual. It may be
necessary to replace the slab sensor. Once the error has been corrected, the error message automatically
clears.
SLAB SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the Slab Sensor 072 or 073. Idling and Storm are
disabled and energy saving features such as Warm Weather Shut Down (WWSD) and Cold Weather
Cut Out (CWCO) are operate using the outdoor temperature only.
Check the slab sensor wire for open circuits according to the sensor installation manual. It may be
necessary to replace the slab sensor. Once the error has been corrected, the error message automatically
clears.
If the slab sensor has been intentionally removed, set the slab sensor setting in the System menu to
Off.
YELLOW WIRE OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the yellow wire connected to the Snow / Ice Sensor
090 or 094, or the Snow Sensor 095. The control can no longer automatically detect snow or ice but
manual start of the snow melting system is still available.
Check the Snow / Ice Sensor or Snow Sensor yellow and black wires and any wire splices for open
circuits according to the sensor installation manual. It may be necessary to replace the sensor. Once
the error has been corrected, the error message automatically clears.
BLUE WIRE SHORT CIRCUIT ERROR
Due to a short circuit, the control is unable to read the blue wire connected to the Snow / Ice Sensor
090 or 094, or the Snow Sensor 095. The control can no longer automatically detect snow or ice but
manual start of the snow melting system is still available.
First check the Snow / Ice Sensor or Snow Sensor for dirt or debris. The ring structure of the sensor
may need cleaning with hot soapy water and a nylon brush. Rinse with water. Secondly, check the Snow
/ Ice Sensor or Snow Sensor blue and black wires and any wire splices for short circuits according to
the sensor installation manual. It may be necessary to replace the sensor. Once the error has been
corrected, the error message automatically clears.
BLUE WIRE OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the blue wire connected to the Snow / Ice Sensor
090 or 094, or the Snow Sensor 095. The control can no longer automatically detect snow or ice but
manual start of the snow melting system is still available.
Check the Snow / Ice Sensor or Snow Sensor blue and black wires and any wire splices for open circuits
according to the sensor installation manual. It may be necessary to replace the sensor. Once the error
has been corrected, the error message automatically clears.
BROWN WIRE SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the control is unable to read the brown wire connected to the Snow / Ice Sensor
090 or 094. Idling and Storm is disabled and energy saving features such as Warm Weather Shut Down
(WWSD) and Cold Weather Cut Out (CWCO) are operate using the outdoor temperature only.
Check the Snow / Ice Sensor brown and black wires for open circuits according to the sensor installation
manual. It may be necessary to replace the sensor. Once the error has been corrected, the error message
automatically clears.
The control is unable to properly detect the Snow / Ice Sensor 090 or 094. The control can no longer
automatically detect snow or ice but manual start of the snow melting system is still available.
Check the Snow / Ice Sensor brown, yellow, red and black wires according to the sensor installation
manual. It is important to check any cable splices for loose wiring connections. It may be necessary to
replace the sensor. Once the error has been corrected, the error message automatically clears.
SNOW SENSOR ERROR
The control is unable to properly detect the Snow Sensor 095. The control can no longer automatically
detect snow but manual start of the snow melting system is still available.
Check the Snow Sensor yellow, red and black wires according to the sensor installation manual. It may
be necessary to replace the sensor. Once the error has been corrected, the error message automatically
clears.
SCHEDULE MASTER ERROR
Two devices on the tekmarNet® system have been set to the same Schedule Master number. The control
operates according to the local programmable schedule while this error is present.
To clear the error, select a different Schedule Master number, set a different Schedule Member number,
set the Schedule to Zone, or set the Schedule to None.
SCHEDULE MEMBER ERROR
The control can no longer detect its schedule master. The control operates as if the programmable
schedule is in idle or off operation while this error is present.
To clear the error, select a different Schedule Member number, set the Schedule to Zone, or set the
Schedule to None.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system
and not on this control.
01 to 24 = There is an error on a thermostat or setpoint control with this tekmarNet
®
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system
and not on this control.
b:01 to b:24 = There is an error on a thermostat or setpoint control wired to the boiler communication
®
bus with this tekmarNet
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system
and not on this control.
1:01 to 1:24 = There is an error on a thermostat or setpoint control wired to communication bus 1 with
®
this tekmarNet
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system
and not on this control.
2:01 to 2:24 = There is an error on a thermostat or setpoint control wired to communication bus 2 with
®
this tekmarNet
address.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system
and not on this control.
3:01 to 3:24 = There is an error on a thermostat or setpoint control wired to the mix 3 bus with this
tekmarNet® address.
ERROR AT SYSTEM CONTROL
There is an error on the tekmarNet® system control connected to the tekmarNet® system and not on
this control.
Use electrical meter to measure 24 V (ac) voltage on input power R and C
terminals.
Idle operation requires that the system pump operate continuously while below the
melting temperature setting.
The snow/ice sensor requires regular cleaning. Avoid using road salt on the snow
melting slab.
The slab is heated to the slab target.
Check wiring of the system pump. The system pump operates continously during
melt, idle or storm operation. The heat source must be wired to operate together
with the heat relay.
Idling heats the slab when the temperature falls below the Idle temperature.
During cold weather cut out (CWCO), the system is shut off. If shut off during a
melt cycle, the system resumes melting once the outdoor temperature is above
CWCO.
System manually started.
System started on a programmable schedule.
System has a programmable schedule and is in event 2 or 4 (unoccupied).
System has been manually Stopped and the automatic snow / ice sensor never
dried, thereby preventing the system to automatically start.
WARNING: This product contains chemicals known to the State of California to
cause cancer and birth defects or other reproductive harm. For more information:
www.watts.com/prop65
Snow Melting Control 654tekmarNet® Electric or Hydronic Boiler / Mixing
Literature654_A, 654_C, 654_D, 654_Q, 654_U
ControlMicroprocessor control. This is not a safety (limit) control
Packaged weight1.3 lb. (590 g)
Dimensions5" H x 3-1/4" W x 15/16" D (127 x 82 x 23 mm)
EnclosureWhite PVC plastic, NEMA type 1
Ambient conditions
Power supply24 V (ac) ±10%, 60 Hz, Class 2, 16 VA standby, 100 VA fully loaded
Relay capacity24 V (ac) 2 A, 3.6 A combined
Modulating output0-10 V (dc), 500 minimum load impedance, 4-20 mA 1 k max load impedance
SensorsNTC thermistor, 10k
- IncludedOutdoor Sensor 070 and Universal Sensor 082
-4 to 122°F (-20 to 50°C), < 90% RH non-condensing, outdoor use permitted when installed inside
a NEMA 3 enclosure
@ 77°F (25°C ± 0.2°C) ß=3892
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is lim-
ited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at
the time of such Product sale and acknowledges that it has read
and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold
hereunder is a manufacturer’s pass-through warranty which the
Purchaser is authorized to pass through to its customers. Under
the Limited Warranty, each tekmar Product is warranted against
defects in workmanship and materials if the Product is installed and
used in compliance with tekmar’s instructions, ordinary wear and
tear excepted. The pass-through warranty period is for a period of
twenty-four (24) months from the production date if the Product is
not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months
from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at
tekmar’s sole discretion: the cost of parts and labor provided by tekmar
to repair defects in materials and/or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the
defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any
way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages,
whether direct, indirect, special, secondary, incidental or consequential,
arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of
contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport
the defective Product, or to reinstall the repaired or replacement Product,
all such costs and expenses being subject to Purchaser’s agreement and
warranty with its customers.
Any representations or warranties about the Products made by Purchaser
to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any
and all claims, liabilities and damages of any kind or nature which arise
out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar,
accident, fire, Act of God, abuse or misuse; or has been damaged by
modifications, alterations or attachments made subsequent to purchase
which have not been authorized by tekmar; or if the Product was not
installed in compliance with tekmar’s instructions and/or the local codes
and ordinances; or if due to defective installation of the Product; or if the
Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS
OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO
CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE
PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS
OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY
LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT
EX TEND BEYON D TWE NTY-FO UR (24) MONT HS FROM THE PRODUC TION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY
THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to
have defects in workmanship or materials must be returned, together
with a written description of the defect, to the tekmar Representative
assigned to the territory in which such Product is located. If tekmar
receives an inquiry from someone other than a tekmar Representative,
including an inquiry from Purchaser (if not a tekmar Representative) or
Purchaser’s customers, regarding a potential warranty claim, tekmar’s
sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., A Watts Water Technologies Company.