The tekmarNet® Thermostat 557 is a
communicating touchscreen thermostat
designed to operate either: a hydronic
radiant floor with a two stage heat pump
(water-to-air or air-to-air) for heating
& cooling and an emergency backup
heating system; or two stages of heating
and two stages of cooling. There are
three auxiliary sensor inputs that can
be used to measure room, floor, outdoor
or duct temperature. The optional floor
sensor allows precise heating of radiant
floors. Relative humidity level can be
measured and controlled using either
the built-in or external humidity sensor.
The large touchscreen display allows
you to easily adjust 7-day programmable
schedules and room temperatures to
optimize comfort and energy savings.
The 557 can connect to tekmarNet®
controls using two or four wires or it can
operate as a stand-alone device.
It is your responsibility to ensure that this thermostat is safely installed according to all
applicable codes and standards. tekmar is not responsible for damages resulting from
improper installation and/or maintenance.
This is a safety-alert symbol. The safety alert symbol is shown alone
or used with a signal word (DANGER, WARNING, or CAUTION), a
pictorial and/or a safety message to identify hazards.
When you see this symbol alone or with a signal word on your
equipment or in this Manual, be alert to the potential for death or
serious personal injury.
This pictorial alerts you to electricity, electrocution, and shock hazards.
This symbol identifies hazards which, if not avoided, could result in
death or serious injury.
This symbol identifies hazards which, if not avoided, could result in
minor or moderate injury.
This symbol identifies practices, actions, or failure to act which could
result in property damage or damage to the equipment.
Read Manual and all product labels BEFORE using the
equipment. Do not use unless you know the safe and proper
operation of this equipment. Keep this Manual available
for easy access by all users. Replacement Manuals are
available at tekmarControls.com
•
It is the installers responsibility to ensure that this thermostat is safely installed
according to all applicable codes and standards.
•
Improper installation and operation of this thermostat could result in damage to the
equipment and possibly even personal injury or death.
This thermostat is not intended for use as a primary limit control. Other controls that
•
are intended and certified as safety limits must be placed into the control circuit.
Do not attempt to service the thermostat. There are no user serviceable parts inside
the thermostat. Attempting to do so voids warranty.
To prevent the risk of personal injury and/or death, make sure power is
not applied to the thermostat until it is fully installed and ready for final
testing. All work must be done with power turned off to the circuit being
worked on.
Please be aware local codes may require this thermostat to be installed
or connected by an electrician.
Removing The Wiring Cover
To remove the thermostat’s wiring cover:
Locate the slotted hole on the right
•
side of the thermostat.
Insert a screwdriver in the slotted hole
•
to depress the latch.
Remove the wiring cover from the
•
thermostat.
Mounting The Thermostat
If a single gang box is used:
Feed the wiring through the large
•
holes of the thermostat.
Fasten the base of the thermostat to
•
the gang box using two screws.
Terminate wiring to the wiring strip.
•
Re-install the wiring cover.
•
Thermostat
1
/
3
”
4
(83 mm)
Wiring
Cover
Stud
Switch Box
If a gang box is not used:
Feed the wiring through the large
•
holes in the thermostat.
Use screws in the screw holes to
•
fasten the thermostat to the wall.
At least one of the screws should
enter a wall stud or similar rigid
material.
The thermostat operates a single heating system zone and can be wired in three
different ways.
Stand Alone
- Similar to tekmarNet®4 wiring with tN4 wiring terminal not used. First
stage heating relay (Rh1 - W1) can be wired directly to switching relays.
tekmarNet®4 - Allows the thermostat to be wired using 4 wires to a tN4 Wiring Center
or Zone Manager point-to-point. Alternatively, the thermostat can operate the heating
and cooling equipment locally and the tN4 communication bus can be daisey-chained
from one thermostat to another.
®
tekmarNet
2 - Allows the thermostat to be wired point-to-point using 2 wires to a tN2
Wiring Center, House Control, or Zone Manager. This allows easy wiring for retrofit
applications.
Application specific wiring diagrams are provided in the 557_A brochure.
Compatible Sensors
The thermostat is compatible with Indoor Sensor type 076, 077, 084, Slab Sensor
type 072, 073, 079, Outdoor Sensor type 070, Duct Sensor type 083 and Humidity &
Temperature Sensor type 086.
Testing the Thermostat Wiring
Only qualified personnel should perform testing procedures. A licensed electrician
is recommended.
Testing tekmarNet®2 Wiring
------------------------------------------
Testing the Power
If the thermostat display turns on, this indicates that the thermostat is operating correctly
and there are no electrical issues. In the event that the display is off, or the display is
cycling on and off:
1. Remove the thermostat wiring cover.
2. Check to ensure that the tN2 wires on the thermostat are connected to a zone on a
House Control, Wiring Center, or Zone Manager.
3. Use an electrical meter to measure DC voltage between the tN2 terminals.
If the DC voltage is 0 V (dc) for at least 20 seconds, then there is an open or
•
short circuit in the tN2 wires.
If the DC voltage is 0 V (dc) for 10 seconds and then is 23 to 24 V (dc) for 5
4. If the thermostat display is off, or is cycling on and off, move the thermostat to the
--------------------------
--------------------------------------------
next available zone on the House Control, Wiring Center, or Zone Manager.
If the thermostat display remains permanently on, there may be a fault with the
•
previously tried zone on the House Control, Wiring Center, or Zone Manager.
If the thermostat display continues to be off, or is cycling on and off, there may
•
be a fault on the thermostat.
If a fault is suspected, contact your tekmar sales representative for assistance.
Testing tekmarNet®4 and Stand Alone Wiring
Testing the Power
1. Remove the front cover from the thermostat.
2. Use an electrical test meter to measure (ac) voltage between the R and C terminals.
The reading should be 24 V (ac) +/– 10%.
3. Install the front cover.
Testing the Relay Outputs
The thermostat includes a User Test to check if the thermostat’s relays are operating
and that the thermostat is wired correctly to the HVAC equipment. The User Test setting
can be located in the Toolbox menu. Either Heat or Cool test can be selected.
Cancel button - Exits the user test and returns the Toolbox menu.
Hold button - Pauses the user test step for up to 5 minutes.
Next Item button - Advances the user test to the next test step.
Heat TestCool Test
StepRelay(s) ClosedStepRelay(s) Closed
O Relay OFFRc-O/B is openedO Relay ONRc-O/B
B Relay ONRc-O/BB Relay OFFRc-O/B is opened
FanRc-GFanRc-G
Y1 HeatRc-Y1 and Rc-GY1 CoolRc-Y1 and Rc-G
--------------------------------------------
User Test Sequence
--------------------------
Y2 HeatRc-Y1 and Rc-Y2 and
Rc-G
W2 HeatRh2-W2W2 CoolRh2-W2
W1 HeatRh1-W1Humidify*ACC-ACC
Humidify*ACC-ACCDehumidify*ACC-ACC or Rc-Y2
Dehumidify*ACC-ACC or Rc-Y2HRV*Rc-Y2
HRV*Rc-Y2Valve*ACC-ACC or Rc-Y2
Valve*ACC-ACC or Rc-Y2
*availability of test step and additional relay closures based upon Setup menu settings.
Thermostat is locally locked and the access level cannot be changed.
Set to Lock when installation has been completed.
UNLOCK ACCESS LEVEL
Thermostat is unlocked and the access level may be changed. Go to
the Toolbox menu to change the access level. Set to Unlock during
the installation process.
tekmarNet® system controls include a Global Lock that locks all
connected thermostats. Set the tekmarNet® system control to unlock
to allow access level adjustment on all connected thermostats.
Conditions: Sensor 1, 2 or 3 is set to Floor, & W1
Terminal is set to HRF1, HRF2 or Othr.
Range: 40 to 122°F (4.5 to
50.0°C), OFF
Default: 85°F (29.5°C)
TEMPORARY HOLD
Temperature adjustment in the home menu
can result in either permanent temperature
setting change or temporary temperature setting
change that lasts 3, 6, 9, 12 hours or until the
next scheduled event.
Access Level: InstallerRange: OFF or ON
Conditions: NoneDefault: OFF
Set the minimum percentage the fan should operate
while in the event. This provides ventilation for the
building. Each 10% is 6 minutes per hour.
Access Level: Installer, UserRange: Auto, 10 to 90%, ON
Conditions: Always available. 10 to 90% available
when Ventilation Mode is On.
FAN
Set the minimum percentage the fan should operate while
in the event or Away scene. This provides ventilation
for the building. Each 10% is 6 minutes per hour.
Access Level: Installer, UserRange: Auto, 10 to 90%, ON
Conditions: Schedules used or Scenes set to Guest or
10 to 90% available when Ventilation Mode is On.
All.
HUMIDITY MINIMUM
Set the minimum humidity level during the event.
Access Level: Installer, UserRange: OFF, 20 to 80%
Conditions: Humidify Mode set to HM1, 2, 3.Default: 40%
HUMIDITY MAXIMUM
Set the maximum humidity level during the event.
Default: Auto
Default: Auto
Access Level: Installer, UserRange: 20 to 80%, OFF
Conditions: Dehumidify Mode set to DHM1, 2, 3, 4, 5. Default: 60%
HUMIDITY MAXIMUM AWAY
Set the maximum humidity level during Away scene.
Access Level: InstallerRange: 20 to 80%, OFF
Conditions: Dehumidify Mode set to DHM1, 2, 3, 4, 5. Default: OFF
HUMIDITY
Select if the humidification or dehumidification system
should operate during the event or away scene.
Access Level: InstallerRange: OFF or On
Conditions: Humidity Mode set to DHM1, 2, 3 or
Dehumidity Mode set to DHM1, 2, 3, 4, 5.
Default: OFF
Time Menu (1 of 2)
SettingDisplay
MINUTES
Select the current time minutes.
Access Level: Installer, UserRange: 00 to 59
Conditions: Always available.Default: 00
The schedule menu can operate on a 24 hour or 7 day repeating schedule. When a
24 hour schedule is selected, “SuMoTuWeThFrSa” is shown on the top of the screen
to show that the event time applies to all days of the week. When a 7 day schedule
is selected, each individual day of the week is shown with the event time.
SettingDisplay
EVENT 1
The first programmable schedule time period of
the day. The
temperature settings are used
during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4 and Event/Day is set to 2 or 4.
EVENT 2
The second programmable schedule time period
of the day. The temperature settings are used
during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4 and Event/Day is set to 2 or 4.
EVENT 3
The third programmable schedule time period
of the day. The temperature settings are used
during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4 and Event/Day is set to 4.
EVENT 4
The fourth programmable schedule time period
of the day. The temperature settings are used
during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4 and Event/Day is set to 4.
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP
or 00:00 to 23:50, SKIP
Default: 6:00 AM
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP
or 00:00 to 23:50, SKIP
Default:
10:00 PM when Event/Day is 2
8:00 AM when Event/Day is 4
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP
or 00:00 to 23:50, SKIP
Default: 6:00 PM
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP
or 00:00 to 23:50, SKIP
Conditions: In a tekmarNet® system, settings adjustable
in Installer access level only.
EVENT PER DAY
Select the number of temperatures per day.
Access Level: Installer, UserRange: 2 or 4
Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4.
24 HOUR / 7 DAY
Access Level: Installer, UserRange: 24 hour or 7 day
Conditions: Schedule setting is set to Zone or Master
1, 2, 3, 4.
OPTIMUM START
Select whether or not to use optimum start. The
thermostat learns the heat up and cool down rates
of the room and starts heating or cooling in advance
of Event 1 or Event 3.
Access Level: Installer, UserRange: OFF or ON
Conditions: A schedule must be in use.Default: ON
The highest recorded room temperature measurement.
Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup setting Room Sensor is set to ON
or Sensor 1, 2 or 3 is set to ROOM.
ROOM LOW
The lowest recorded room temperature measurement.
Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup setting Room Sensor is set to ON
or Sensor 1, 2 or 3 is set to ROOM.
FLOOR HIGH
The highest recorded floor temperature measurement.
Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup menu setting Sensor 1, 2 or 3 is
set to FLOR.
FLOOR LOW
The lowest recorded floor temperature measurement.
Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup menu setting Sensor 1, 2 or 3 is
set to FLOR.
FILTER HOURS
The total number of hours the fan has been operating
since the air filter was last replaced. Touch the number
and the ENTER key to reset and clear the Change
Filter warning message.
Displays the current status of the thermostat including any
overrides from the tekmarNet
between “Status Info” and the current status.
System Normal = Thermostat operating normally.
Override W1 = The tekmarNet® system control is either
forcing the W1 relay on or off.
Cooling Floor = Floor cooling is in effect.
WWSD = Warm Weather Shut Down is in effect.
CWSD = Cold Weather Shut Down is in effect.
Optimum Start Heat or Cool = The heating or cooling
system is started early in order to meet temperature
setpoint at Event 1 or Event 3.
Floor Max = The floor has reached its maximum temperature. Some under heating could occur.
Floor Min = The floor is operating at its minimum temperature. Some over heating could occur.
Baseload On = Baseload heating is on even though the
room temperature is satisfied. Reduces heat up time when
the sun sets in the evening.
Hydronic Heat Off = The air group master is in cooling
mode and air group member thermostats’ heating is shut off.
Interlock Wait = The thermostat is switching between heating
to cooling or from cooling to heating.
Priority Heat = Air group members are calling for heat. Cooling
is suspended.
Access Level: Installer, UserRange: See Description
Conditions: Always available.Default: System Normal
ADDRESS
The tekmarNet® address of this thermostat.
To manually set the address, use the up or down arrow buttons
while in the Installer access level.
Access Level: Installer
Conditions: tekmarNet®2 or 4 detected.
SOFTWARE AND TYPE VERSION
Displays the software version and the tekmar type number.
Access Level: Installer, User, Limited, SecureRange: 557
Conditions: Always available.Default: 557
®
system control. Toggles
Range: AUTO, 01 to 24,
b:01 to b:24, 1:01 to 1:24,
2:01 to 2:24, 3:01 to 3:24
Provides a count of all the tekmarNet® thermostats and
setpoint controls on the tekmarNet® system.
Access Level: Installer
®
Conditions: Must be connected to a tekmarNet
system.
USER TEST
Use the up or down arrow keys to select either the heat or
cool test sequence, then press the NEXT key to begin. Press
HOLD to pause at step for 5 minutes. Press NEXT to advance
to the next step.
Access Level: Installer
Conditions: Always available.
OFFSET ROOM
Manual offset correction of the room temperature
measurement.
Access Level: Installer
Conditions: Always available.
OFFSET HUMIDITY
Manual offset correction of the room humidity
measurement.
Select whether the primary or mix system pump on
a tekmarNet® system control should operate while
the first stage of heat W1 is operating.
Access Level: InstallerRange: OFF or ON
Conditions: Only available when a tekmarNet® system
control is connected and the Setup menu setting W1
TERM is set to HRF1, HRF2.
W1 THERMAL MOTOR
Select whether the first stage of heat W1 operates a
thermally actuated zone valve (wax actuator). When
set to ON, there is a 3 minute delay before operating
the pump and any heat sources.
Access Level: InstallerRange: OFF or ON
Conditions: Only available when a tekmarNet
system control is connected and the Setup menu
setting W1 TERM is set to HRF1, HRF2.
BACKUP W2 TERMINAL
Select the type of backup heating.
CONV = baseboard convectors
COIL = hydronic fan coil
FURN = forced air furnace
OTHR = non-hydronic heating that does not require
the fan to operate
Access Level: Installer
Conditions: Always available.Default: NONE
BACKUP W2 SOURCE
Select the water temperature of the hydronic backup
heating.
Access Level: Installer
Conditions: BACKUP W2 TERMINAL is set to CONV
or COIL.
BACKUP W2 PUMP
Select whether the primary or mix system pump on
a tekmarNet® system control should operate while
the backup stage of heat W2 is operating.
Access Level: InstallerRange: OFF or ON
Conditions: BACKUP W2 TERMINAL is set to CONV
Select whether the backup stage of heat W2 operates
a thermally actuated zone valve (wax actuator). When
set to ON, there is a 3 minute delay before operating
the pump and any heat sources.
Access Level: InstallerRange: OFF or ON
Conditions: BACKUP W2 TERMINAL is set to CONV
or COIL.
BACKUP W2 DELAY
The minimum amount of time that the first stage W1
and the heat pump must be operating before the
backup second stage W2 can turn on.
AUTO = Automatic PID staging
OVR = W2 only turns on when Mode is set to EMER.
Access Level: InstallerRange: AUTO, 10 to 180 min, OVR
Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, or OTHR.
BACKUP W2 DIFFERENTIAL
Select the backup W2 differential turn on point from
the previous heat stages.
Access Level: InstallerRange: 0.0 to 8.0°F (0.0 to 8.0°C)
Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, OTHER.
LOCKOUT W2
The outdoor temperature above which the backup
heat W2 is disabled. When Mode is set to EMER
(emergency), the W2 is allowed to turn on.
Access Level: Installer
Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, or OTHR.
Y1 RELAY
Select the cooling equipment the Y1 relay operates.
HP1 = Heat pump
AC1 = Air conditioner
W2 = W2 turned on together with Y1. Used for 2-pipe
hot / chilled water fan coils. The backup W2 relay
activates the pump or zone valve for the fan coil
for both heating and cooling. Only available when
Backup W2 Source is set to TNK1.
Select the equipment the Y2 relay operates.
HP2 = Second stage heat pump
AC2 = Second stage air conditioner
HRV = Heat recovery ventilator
DHUM = Dehumidifier
VALV = Hydronic valve for building loop
Access Level: Installer
Conditions: Always available.Default: OFF
ACCESSORY RELAY
Select the equipment the accessory relay operates.
HUM = Humidifier
DHUM = Dehumidifier
VALV = Hydronic valve for building loop
Select the heat pump operation of the O / B relay.
O = Turn on during cooling, turn off during heating
B = Turn off during cooling, turn on during heating
Access Level: InstallerRange: O or B
Conditions: Y1 RELAY is set to HP1.Default: O
HP SOURCE
Select the type of source for the heat pump.
AIR = Air source heat pump
GEO = Geothermal source heat pump
LOOP = Building hydronic loop heat pump
Access Level: InstallerRange: AIR, GEO, LOOP
Conditions: Y1 RELAY is set to HP1.Default: AIR
Select the outdoor temperature above which the
radiant floor heating is shut off.
Access Level: Installer
Conditions: W1 TERMINAL is set HRF1, HRF2, or
OTHR and outdoor temperature is available.
W CYCLES PER HOUR
Select the number of heating cycles per hour.
SYNC = 20 minute zone synchronization.
AUTO = Automatic cycles per hour to minimize
temperature swings.
Access Level: InstallerRange: SYNC, AUTO, 2 to 12
Conditions: Setup menu setting W1 TERMINAL is set
to OTHR (other) or the thermostat is not connected
to a tekmarNet
®
system control.
Y DURING W2
Select whether the heat pump compressor can
operate when backup heat or cool W2 is on. When
Mode is set to EMER (emergency), the heat pump
compressors Y1 and Y2 are always shut off.
Access Level: InstallerRange: OFF or ON
Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, or OTHR.
BASELOAD
Select the level of radiant floor baseload heating.
This warms the floor so that solar gain and / or air
heating systems do not cause cold floors.
Access Level: InstallerRange: OFF, LOW, MED, HIGH
Conditions: Only available when a tekmarNet® system
control is connected and the Setup menu setting W1
TERM is set to HRF1 or HRF2 and SENSOR 1, 2
or 3 is not set to FLOR (floor).
FLOOR COOL
Select whether or not the thermostat operates W1
for radiant floor cooling.
Access Level: InstallerRange: OFF or ON
Conditions: Setup menu setting W1 TERM is set to
HRF1 or HRF2 and the thermostat must be connected to
a tekmarNet® heat pump or chiller system control.
The 557 can operate radiant floor heating, heat pump stage 1 and stage 2, and a backup
heat source to provide heating in different combinations depending on the outdoor air
temperature. The illustration below shows when each of the available heating units are
available. The “Heat On” symbol is shown on the display when the thermostat is heating. If not
operating a heat pump, the first and second stage of heat (W1 and W2) are allowed to turn
on below the Warm Weather Shut Down to maintain the Set Heat Room temperature.
Heat Pump - Heating Mode
Room
Warmer
Set Heat
Room
Room
Colder
Air Temperature Heating
When using only a room temperature sensor, the thermostat operates the heating
system to maintain the Set Heat Room temperature.
Floor Heating
When using both a room and a floor temperature sensor, the thermostat always maintains
the Floor Minimum temperature, even when the air temperature is satisfied. When the
air temperature is below the Set Heat Room temperature, the thermostat operates the
heating system to maintain the Set Heat Room temperature. The floor is never heated
above the Floor Maximum setting in order to protect the floor covering.
No heatingAir heating onlyAll allowedNo backup heat
When the terminal unit is selected to be a Hydronic Radiant Floor (HRF1 or HRF2)
and no floor temperature sensor is installed, the thermostat has option to provide
baseload heating. This allows the radiant floor to be heated even though the room air
temperature is satisfied. This is useful in areas where a radiant floor heating zone is
overlapped by an air heating system. The radiant floor heating is overwhelmed by the
quick heat up rate of the air heating system, resulting in a radiant floor heating zone
that rarely turns on. The radiant baseload option allows the radiant floor to counteract
the air heating system by heating the floor at a reduced output even when the room air
temperature is satisfied. This is also useful in areas that experience large solar gains
through windows. The radiant baseload is automatically shut off in the summer by the
warm weather shut down feature.
----------------------------------------------
Warm Weather Shut Down
When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD)
setting on the tekmarNet® main control, the heating system is shut off.
A W1 HEAT WWSD setting is available to allow the heat pump to heat the building
while the radiant floor heat system is shut off during mild outdoor temperatures. This
is advantageous in the spring and fall when heating is required at night and cooling is
required during the day. As the outdoor temperature falls below the W1 HEAT WWSD
setting, the radiant floor becomes the primary heat source and the heat pump provides
supplemental heating.
Balance Point
An air source heat pump’s Coefficient Of Performance (COP) decreases with colder
outdoor temperature. This affects the heating output capacity of the heat pump to
heat the building. When the COP is equal to 1, the heat pump no longer provides an
economic advantage over electric heating elements or other supplemental heating fuel.
The outdoor temperature at which this occurs is known as the balance point. When
the outdoor temperature falls below the balance point, the heat pump is shut off and
the backup supplemental heat source is operated to heat the building. The 557 has
the ability for the balance point setting change based upon a programmable schedule.
This is useful in cases where the electrical utility offers lower different energy pricing
throughout the day.
The 557 can operate a two-stage heat pump or air conditioner to provide cooling
depending on the outdoor air temperature. In some cases, cooling is provided by a
chilled water fan coil. The illustration below shows when each of the available cooling
units are available. The “Cool On” symbol is shown on the display when the thermostat
is cooling.
Floor cooling is designed to cool a building together with an air cooling system. Floor
cooling reduces part of the sensible cooling load, while the air cooling equipment
must cool the latent load (dehumidification) and the remaining sensible load.
The thermostat has the option to support floor cooling when connected to a heat
pump control using tekmarNet® communication. The terminal unit type must be set
to be HRF1 or HRF2, the floor cooling setting must be set to On and the heating
system must be in Warm Weather Shut Down (WWSD). When the thermostat is set
to Mode Cool, the floor cooling turns on 1.0°F (0.5°C) below the Set Cool setpoint.
This allows the floor cooling to operate for long periods of time while the air cooling
system cycles on and off to maintain the cooling setpoint. Floor cooling does not
operate below 64°F (18.0°C).
Cooling Cold Weather Shut Down
-------------------------------------
When the outdoor air temperature falls below the Cooling Cold Weather Shut Down
(CWSD) setting on the thermostat, the cooling system is shut off.
Heating and cooling minimum and maximum temperature settings are available in the Set
Temp menu. These allow the installer to select start and stop limits for the temperature
settings in both heating and cooling for the User and Limited access levels. This is
useful in commercial installations and child / guest bedrooms where availability of the
full temperature setting range may not be desirable.
Section C
Hydronic Pump and Valve Operation
Exercising
When connected to a tekmarNet® system control, the thermostat exercises the heat relay for
10 seconds every 3 days. Exercising helps prevent zone valves or zone pumps from failing
due to precipitate buildup. During exercising, the thermostat shows “TEST” on the display.
Flushing
The flushing feature is for open-loop systems that use a domestic hot water tank as a
heat source. Flushing ensures that fresh potable water is circulated through the system
once each day. If the thermostat is connected to a tekmarNet® system control with the
Flushing feature turned on, the thermostat display will display “FLUSHING” for the
duration of the flushing operation.
Hydronic System Supply Pump
When connected to a tekmarNet® system control, the thermostat’s W1 Pump setting
affects how the primary pump or mix pump on the system control operates. When
connected to the boiler bus, the boiler system or primary pump is operated. When
connected to the mix bus, the mix system pump is operated.
If the thermostat operates a motorized or thermal motor zone valve, the W1 Pump
setting should be set to On.
If the thermostat operates a thermal motor (wax actuator) zone valve, set the W1 Thermal
Motor setting to On. This provides a three minute delay to allow the zone valve to open
before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the W1 Pump setting can be set
to Off. This allows a Zone Group Pump located on the Zone Manager, or Wiring Center
to operate the pump for the manifold.
DHW Tank Priority
When a tekmarNet® system control is heating an indirect Domestic Hot Water (DHW)
tank, the thermostat may shut off the heating zones to allow the DHW tank to recover
quickly. This is determined by the DHW priority of the tekmarNet
The fan operates together with the air heating or cooling systems. The user can also
select to operate the fan manually by pressing the Fan button. This allows the user to
choose between Auto and On. “Auto” allows the fan to operate together with heating or
cooling but normally the fan is off. “On” forces the fan to operate continuously.
Section E
Ventilation Fan
In order to provide ventilation to the building, the fan can also operate for additional
time beyond what is required for the heating and cooling systems. Ventilation allows the
user to select the fan to operate for a minimum percentage out of each hour. Options
are 10 to 90%, in 10% (6 minutes per hour) increments, as well as Auto and On. This
is available when the Vent Mode setting in the Setup menu is set to On.
Once Ventilation is set to On, the Fan minimum run time percentage during the and
events can be set so that the fan can operate on a schedule and/or together with scenes.
Fan Post Purge
The fan relay includes a post purge feature that operates the fan after the heating or
cooling system has shut off. When a duct temperature sensor is installed the length
of post purge is based on the air duct temperature and the Heatpurge or Coolpurge
temperature settings. When there is no duct temperature sensor installed, the length
of post purge is based upon the Heatpurge and Coolpurge time settings.
Relative Humidity (RH) is controlled by maintaining the Minimum Humidity using
humidification and by maintaining Maximum Humidity using dehumidification. The RH
is maintained within a 5% differential. The differential is applied above the minimum
setpoint, and applied below the maximum setpoint. When the mode is set to off, the
humidification and dehumidification systems do not operate.
To avoid condensation on windows, the minimum relative humidity setting can be
changed according to the following outdoor temperatures.
The thermostat has up to five dehumidification modes.
OperationModeRequired
Relay(s)
Stand Alone Dehumidifier
Dehumidifier operates independently or the
HVAC system.
Available in all modes except off.
DHM1ACC RELAY
= DHUM
or
Y2 RELAY
= DHUM
Coil Dehumidification
A duct temperature sensor is required. A DX or
chilled water coil is operated to maintain a discharge air temperature of 45°F (7°C). The room
air temperature is allowed to fall up to 3°F (1.5°C)
DHM2ACC RELAY
= DHUM
or
Y2 RELAY =
DHUM
below the cooling setpoint while coil dehumidification is operating, at which point dehumidification is shut off. The fan relay (G) is not turned
on, rather the ACC or Y2 relay provides a signal
to the air handler unit to operate the fan at low
speed.
Available only when cooling.
HRV Dehumidification
(only available with single stage heat pumps
DHM3Y2 RELAY =
HRV
or air conditioners)
The HRV is operated based upon indoor dew
point and outdoor air temperature. The HRV operates when the indoor dew point is 5.5°F (3.0°C)
above the outdoor temperature. The HRV is shut
off when the indoor dew point falls to 2°F (1.0°C)
above the outdoor temperature.
Available in all modes except off.
Stand Alone + HRV Dehumidification
(only available with single stage heat pumps
or air conditioners)
During cooling mode, a stand alone dehumidifier
is operated in the same manner as DHM1.
DHM4ACC RELAY
= DHUM
and
Y2 RELAY =
HRV
During heating mode, an HRV provides dehumidification in the same manner as DHM3.
Available in all modes except off.
Coil + HRV Dehumidification
(only available with single stage heat pumps
or air conditioners)
During cooling mode, a coil dehumidifier is operated in the same manner as DHM2.
DHM5ACC RELAY
= DHUM
and
Y2 RELAY =
HRV
During heating mode, an HRV provides dehumidification in the same manner as DHM3.
Available in all modes except off.
In order to prevent heating and cooling at the same time, this thermostat can operate
together with other thermostats on a tekmarNet
®
system to form an air group. On older
model thermostats the air group functionality was previously described as a cool group.
In an air group, one thermostat is assigned as the air group master. The air group master
operates the cooling equipment for the group. When operating as a air group, the air
temperature readings of all the air group member thermostats are communicated to the
air group master thermostat and an average temperature is determined. When the air
group master is in cooling operation, the air group member thermostats do not operate
the heating system for air heating.
When operating a heat pump, the 557 also has the ability to prevent air group member
thermostats from heating while the outdoor temperature is between the Warm Weather
Shut Down (WWSD) and the Radiant Floor WWSD (W1 WWSD) setting. This allows
the air system heat pump to heat the building during mild outdoor weather and avoids
heating up the radiant floor slab.
If the Set Heat Room temperature is adjusted while the air group is cooling, COOL is
flashed on the display to alert the user that the air group cooling system is presently
on and heating is not available. Once the cooling system shuts off, heating is available
if required.
Air Group
Master
tekmarNet® Communication
Time Clock
MemberMember
Section H
The thermostat includes a time clock that is automatically visible in the Home
menu when a programmable schedule is used. If the schedule is not used, the
user has the option to select whether the time is shown in the Home menu.
During a loss of power, the thermostat continues to keep the correct time and
date for at least 4 hours. If the power is off for more than 4 hours, the user will
need to set the time.
The thermostat supports automatic update for daylight savings time. Simply set
Daylight Save to On together with the correct day, month, and year and the time
is automatically updated each spring and fall.
When connected to a tekmarNet
®
system, adjustment of the time on one thermostat
updates all connected thermostats. This option can be disabled by selecting the
Local Network Group setting to be On.
When no programmable schedule is used, touch the up or down arrows to permanently
set the “Set Heat Room” or “Set Cool Room” temperature. This thermostat is capable
of controlling both air and floor temperature.
Permanent Adjustment - With Schedule
--------------------------------
-------------------------------
When a programmable schedule is used, there are two room heating temperatures
available, one for the
time period and another for the time period. When
touching the up or down arrows to change the temperature, only the temperature
for the current time period is changed.
1. To adjust the temperature for both time periods, press and hold the Home button
for 3 seconds to enter the programming menus.
2. Enter the “SET TEMP” menu to adjust the following settings:
Set Heat Room (air heating or air heating with floor sensor)
•
Set Heat Room (air heating or air heating with floor sensor)
•
Set Heat Room AWAY (air heating or air heating with floor sensor)
•
Floor Min (air heating with floor sensor)
•
Floor Min (air heating with floor sensor)
•
Set Cool Room (air cooling)
•
Set Cool Room (air cooling)
•
Set Cool Room AWAY (air cooling)
•
Temporary Hold
Temporary hold allows a user to change the temperature for a period of time and then
automatically return to the permanent temperature setting. This is especially useful
in commercial buildings that are in use for short amounts of time. When selected,
touching the up or down arrows changes the temperature for either 3, 6, 9 or 12 hours.
If the thermostat is using a schedule, ‘Schd’ provides a temporary hold until the next
schedule event time. After the temporary hold time expires, the thermostat returns to
normal operation. By default, the temporary hold feature is off.
Energy savings can be achieved by lowering the heating temperature and increasing
the cooling temperature when the building is unoccupied or during the night.
When operating on a programmable schedule, a or a symbol is shown in the
home menu. The or indicates the current operating temperature.
All schedules are stored in permanent memory and are not affected by a loss
of power.
DisplayAction
Day temperature
Night temperature
This thermostat can operate on a programmable schedule in order to automatically
lower the room temperature setting. Options include:
Turning off the schedule (OFF)
•
Operate a schedule that applies only to this thermostat zone (ZONE)
•
The ability to operate one of the four system-wide schedules as a master
•
(Schedule Master 1 through 4*)
Join one of the four system-wide schedules as a member (Schedule Member
•
1 though 4*)
*Requires the thermostat to be connected to a tekmarNet® system.
Once the type of schedule has been selected, the thermostat can support schedules
that have either:
2 events per day
•
4 events per day
•
Schedules with four events per day are common for residential use while two events
per day are common for commercial installations.
The schedules can be repeated every:
24 hours
•
7 days (week)
•
A 7 day schedule allows a unique time to be set to change the temperature for each
day of the week.
The schedule also includes a “SKIP” option that allows the programmable schedule to
skip a temperature change and remain at the previous temperature setting. The “SKIP”
setting can be found between 11:50 PM (23:50 hours) and 12:00 AM (0:00 hours).
When a programmable schedule is selected, there is a time delay for the room to warm
up or cool down from the temperature to the temperature. The thermostat has
the option to use Optimum Start to predict the heat up or cool down rate of the room.
When Optimum Start is set to On, the heating or cooling is started in advance to allow
the room to reach the Set Room temperature at the time set in the programmable
schedule.
This thermostat includes an Away Key to quickly turn down the heating temperatures
and increasing the cooling temperatures on all thermostats and suspend heating
the domestic hot water tank to maximize energy savings. To enable, go the Scene
menu and set Away Key to on.
To activate the Away scene, touch “Going Away” on the
screen.
Select PERM (permanent) or a number of days using
•
the or arrow. Range is 1 to 180 days.
Press the home button to accept the setting or leave
•
the screen untouched for several seconds.
“Scene Away” is displayed on the home screen until
•
the number of days expires.
Touch “Cancel Away” to cancel at any time.
•
The temperature is not adjustable while the thermostat
is in Away.
Choosing how to use scenes depends on the needs and lifestyle of the customer using
the building.
-----------------------------
Multi-Tenant Apartments
Scenes should be disabled (None) in multi-tenant buildings where each occupant has
differing heating requirements.
Residential Homes
Some residential customers may not require scenes, in which case, scenes can be
disabled (None). Home owners that wish to save on energy costs should consider
using the Away scene to save energy while away from the property (example: vacation
or holidays).
The use of the Guest scene is useful in residential applications where there are a number
of spare bedrooms that are occupied on an infrequent basis. Each spare bedroom would
be setup to operate on the Guest scene. The remaining thermostats can be setup to
operate on the None, Away or All scene configuration. Normally, the spare bedrooms
would operate at the moon temperature settings. When guests arrive, scene 5 can be
activated through the use a User Switch or Gateway. The spare bedroom then operates
at the temperature settings or operates on a programmable schedule if a schedule
has been setup. When guests depart, the scene can be changed back to scene 1 and
the spare bedrooms resume operation at the temperature settings.
Commercial Buildings
Commercial buildings are typically in use on a predictable schedule and normally the
building can operate in scene 1. In order to accommodate staff working overtime or
cleaning staff, a 3 or 8 hour temporary override is available when installed in conjunction
with a User Switch or Gateway. In these cases, the thermostats should be setup to use
the All scene configuration. At the touch of a button, the whole building changes from
operating on a programmable schedule (typically at the temperature setting when
not occupied) to operating at the temperature settings for 3 hours (scene 6) or 8
hours (scene 8). After the timer counts down and expires, the scene changes back to
the previous scene.
Secondary Temperature Display
Section L
This thermostat can display the outdoor, floor, relative humidity, or the room heating
and cooling temperature settings in the smaller number area at the top right of the
screen. To toggle the item currently displayed, touch the secondary temperature.
Display of the floor or outdoor temperature requires a connection to an outdoor or
floor temperature sensor, or the thermostat is connected to a tekmarNet® system that
includes an outdoor sensor. The reading of the outdoor sensor connected directly to
the thermostat takes precedence over any outdoor sensor reading available on the
tekmarNet® system.
The thermostat Toolbox menu supports four access levels: Installer (INST), User
(USER), Limited (LTD), and Secure (SEC). The access level can be adjusted when the
thermostat is unlocked. There are two locations to lock the thermostat:
1. Locally on the thermostat using the Lock switch located in the wiring area.
®
2. Globally on the tekmarNet
installed)
Both the local and global lock settings must be set to unlock before the thermostat
access level is adjustable.
The selection of the access level is dependent on the use of the building and the type
of occupants.
Installer - Suitable for HVAC installers only. Times out to User access level after 24
hours.
User - Suitable for most residential homeowners.
Limited - Suitable for rental properties or commercial buildings where some level of
temperature adjustment is required.
Secure - Suitable for schools, churches, and other public buildings where temperature
adjustment is not desired.
system control using the Lock switch or Access level (if
Section M
tekmarNet® Address
When connected to a tekmarNet® system, each thermostat will be automatically given
an address. The address is useful as a troubleshooting tool to locate thermostats with
errors and also allows room naming on a Gateway.
The address consists of the bus water temperature followed by the thermostat device
number. Available buses are b (boiler), 1, 2 and 3. Device numbers range from 01 to
24. If the thermostat is used without a tekmarNet® system control, the bus number is
not shown.
When using the thermostat together with a Gateway, it is important that each address
be changed to be manually set. This allows each thermostat to be named on the
Gateway.
If two thermostats are manually set to the same address, an error message will appear.
The error remains until one of the addresses is manually changed to a vacant address
or to Auto.
It is highly recommended to keep a documented list of thermostat addresses. This is
extremely helpful when troubleshooting errors. The tekmarNet® system control will
display the addresses of thermostats that have errors. By referring to the address
documentation, it simplifies the process to locate and correct error messages.
Cleaning the Thermostat
Entering the Screen Clean menu allows 30 seconds to clean the thermostat and display
with a moist cloth. Do not use solvents to clean the thermostat.
The thermostat failed to read the Setup menu settings from memory
and has reloaded the factory default settings. The thermostat stops
normal operation until all settings in the Setup menu are checked
except to provide freeze protection. To clear the error, set the access
level to Installer and check all settings in the Setup menu.
SET TEMP MENU SAVE ERROR
The thermostat failed to read the Set Temp menu settings from memory
and has reloaded the factory default settings. The thermostat stops
normal operation until all settings in the Set Temp menu are checked
except to provide freeze protection. To clear the error, set the access
level to Installer and check all settings in the Set Temp menu.
MONITOR MENU SAVE ERROR
The thermostat failed to read the Monitor menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Monitor menu.
SCHEDULE MENU SAVE ERROR
The thermostat failed to read the Schedule menu settings from
memory and has reloaded the factory default settings. The thermostat
continues to operate normally while displaying this error. To clear the
error, set the access level to Installer and check all settings in the
Schedule menu.
TOOLBOX MENU SAVE ERROR
The thermostat failed to read the Toolbox menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Toolbox menu.
TIME MENU SAVE ERROR
The thermostat failed to read the Time menu settings from memory and
has reloaded the factory default settings. The thermostat continues to
operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Time menu.
SCENES MENU SAVE ERROR
The thermostat failed to read the Scenes menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Scenes menu.
The thermostat failed to read the Display menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error.
To clear the error, set the access level to Installer and check all settings
in the Display menu.
tN2 PORT ERROR
The thermostat has been connected to a tN2 zone already in use by
a 2-stage zoning control. A 2-stage device requires two tN2 ports to
operate. This device may be connected to one such port.
To clear the error, move the thermostat’s tN2 wires to an unused tN2
port on the zoning control.
NO SENSOR ON ERROR
All of the temperature sensors have been set to Off including the
built-in room sensor.
To clear the error, the Room Sensor, Sensor 1, 2 or 3 must be set to
measure an air or floor temperature.
W2 SOURCE BUS CONFIGURATION ERROR
The backup W2 heat source has been changed on the tekmarNet®
System Control. To clear the error, check the Backup W2 Source
setting in the Setup menu.
tekmarNet® COMMUNICATION ERROR
The tekmarNet® communication bus has either an open or a short
circuit. The result is that there are no communications. Check for loose
wires between tN4 and C. Check for short circuits between the tN4
and C wires on the House Control, Wiring Center, or Zone Manager.
Check for correct polarity between the C and R wires.
The error clears automatically once the wiring fault has been
corrected.
To force the error to clear while allowing a short or open circuit to
continue, touch the Cancel key.
ADDRESS ERROR
Two thermostats have been manually set to the same address. The
thermostat continues to operate with this error but does not communicate
with the tekmarNet® system.
To clear this error, select an unused tekmarNet® address or select
automatic addressing.
DEVICE LIMIT
More than 24 devices (thermostats or setpoint controls) have been
connected to the tekmarNet® communication bus. To clear the error,
remove and relocate devices to other available buses until the device
count is 24 or less.
Due to a short circuit, the thermostat is unable to read the built-in room
temperature sensor. If Sensor 1, 2 or 3 is set to Room, or the thermostat
is connected to a tekmarNet® system control, the thermostat continues
to operate, otherwise operation stops.
The error cannot be field repaired. Contact your tekmar® sales
representative for repair procedures.
ROOM SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the thermostat is unable to read the built-in
room temperature sensor. If Sensor 1, 2 or 3 is set to Room, or the
thermostat is connected to a tekmarNet® system control, the thermostat
continues to operate, otherwise operation stops.
The error cannot be field repaired. Contact your tekmar® sales
representative for repair procedures.
LOCAL HUMIDITY SENSOR ERROR
The built-in humidity sensor is faulty. The error cannot be field repaired.
Contact your tekmar® sales representative for repair procedures.
EXTERNAL HUMIDITY SENSOR ERROR
The external humidity sensor is faulty. Check the external sensor wiring
terminations and troubleshoot using the data brochure 086_D. The
error will self clear when the humidity sensor is reading correctly. If
the external humidity sensor has been intentionally removed, set the
Sensor 3 setting in the Setup menu to Off.
SENSOR 1, 2 OR 3 SHORT CIRCUIT ERROR
Due to a short circuit, the thermostat is unable to read auxiliary Sensor
1, 2 or 3. The thermostat stops normal operation if the Sensor is the
only active Room or Floor sensor or if a Floor Maximum temperature
has been set.
Check the auxiliary sensor wire for short circuits according to the sensor
installation manual. It may be necessary to replace the auxiliary sensor.
Once the error has been corrected, the error message automatically
clears.
SENSOR 1, 2 OR 3 OPEN CIRCUIT ERROR
Due to an open circuit, the thermostat is unable to read auxiliary Sensor
1, 2 or 3. The thermostat stops normal operation if the Sensor is the
only active Room or Floor sensor or if a Floor Maximum temperature
has been set.
Check the auxiliary sensor wire for short circuits according to the sensor
installation manual. It may be necessary to replace the auxiliary sensor.
Once the error has been corrected, the error message automatically
clears.
If the auxiliary sensor has been intentionally removed, set the applicable
Sensor 1, 2 or 3 setting in the Setup menu to Off.
The thermostat can no longer communicate to the tekmarNet® system
control. Check for open or short circuits in the tekmarNet® communication
wiring. The error automatically clears once the tekmarNet® system
control has been detected.
If the tekmarNet
system, remove and then re-apply power to the thermostat to clear
the error.
NEED DUCT SENSOR ERROR
The dehumidifier mode has be configured to be DHUM2 or DHUM3.
These modes require a duct sensor in order to function and no duct
sensor has been detected. To clear the error message, either change
the dehumidification mode or install a duct sensor to Sensor 1.
AIR GROUP MASTER ERROR
Two thermostats have been assigned to be the master of the same
air group (cool group) number.
To clear the error, go to the Setup menu and either select a different
air group master number or set the air group master to None.
SCHEDULE MASTER ERROR
Two thermostats on the tekmarNet® system have been set to the
same Schedule Master number. The thermostat operates at the
temperature settings while this error is present.
To clear the error, select a different Schedule Master number, set
a different Schedule Member number, set the Schedule to Zone,
or set the Schedule to None.
SCHEDULE MEMBER ERROR
The thermostat can not longer detect its schedule master. The
thermostat operates at the
error is present.
To clear the error,
the Schedule to Zone, or set the Schedule to None.
CHANGE FILTER
The air filter requires cleaning or replacement. Once this has been
completed touch the Cancel key in the Toolbox menu. Alternatively, go
to the Monitor menu and clear the Filter Hours by touching the number
and then touch the ENTER key.
®
system control was intentionally removed from the
temperature settings while this
select a different Schedule Member number, set
FREEZE PROTECTION WARNING
The duct temperature has dropped below 45°F (7.0°C). The second
stage cooling will be forced off at 40°F (4.5°C) and the first stage
cooling will be forced off at 35°F (1.5°C). The warning message self
clears once the duct temperature exceeds 45°F (7.0°C).
There is an error on a different thermostat or setpoint control connected
to the tekmarNet® system and not on this thermostat.
01 to 24 = Thermostat only network
Go to the thermostat with the listed address to correct the error.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected
to the tekmarNet® system and not on this thermostat.
b:01 to b:24 = boiler bus
1:01 to 1:24 = bus 1 or mix1 bus
2:01 to 2:24 = bus 2 or mix2 bus
3:01 to 3:24 = bus 3 or mix 3 bus
Go to the thermostat with the listed address to correct the error.
ERROR AT SYSTEM CONTROL
There is an error on the tekmarNet® system control connected to
the tekmarNet® system and not on this thermostat.
Literature557_A, 557_C, 557_D, 557_Q, 557_U
ControlMicroprocessor control. This is not a safety (limit) control
Packaged weight0.9 lb. (400 g)
Dimensions4-1/2" H x 4-3/4" W x 7/8" D (114 x 120 x 22 mm)
EnclosureWhite PVC plastic, NEMA Type 1
ApprovalsMeets Class B: ICES & FCC Part 15
Ambient conditions
Environmental
Power supply24 V ±10%, 60 Hz, 2.0 VA standby, NEC / CEC Class 2
Relays24 V (ac) 2 A
0-10 V (dc) Output3.3 V (dc) humidity sensor power, 3.0 mA maximum
Humidity sensor0 to 90% ± 3% RH
Temperature sensor
– IncludedNone
– Optionaltekmar type # 070, 072, 073, 076, 077, 079, 083, 084, 086
Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing
Compatible with chlorinated swimming pool environments. Do not use
in presence of ammonia (animal barns), methanol, ethanol, acetone.
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt
of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time
of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s passthrough warranty which the Purchaser is authorized to pass through to its customers. Under the Limited
Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product
is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The passthrough warranty period is for a period of twenty-four (24) months from the production date if the Product is
not installed during that period, or twelve (12) months from the documented date of installation if installed
within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts
and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to
the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to
the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available
from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict
product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect,
special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in
workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to
Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different
from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages
of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to
its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by
persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications,
alterations or att achment s made subsequen t to purchase which have not been au thorized by tekmar; or if t he Prod uct was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to
defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR
TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24)
MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE
GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to
the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar
Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers,
regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact
information regarding the appropriate Representative.
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects
or other reproductive harm. For more information: www.watts.com/prop65