tekmar 557 Installation

Page 1
557_D
tekmarNet® Thermostat 557
Installation & Operation Manual
Introduction
The tekmarNet® Thermostat 557 is a communicating touchscreen thermostat designed to operate either: a hydronic radiant floor with a two stage heat pump (water-to-air or air-to-air) for heating & cooling and an emergency backup heating system; or two stages of heating and two stages of cooling. There are three auxiliary sensor inputs that can be used to measure room, floor, outdoor or duct temperature. The optional floor sensor allows precise heating of radiant floors. Relative humidity level can be measured and controlled using either the built-in or external humidity sensor. The large touchscreen display allows you to easily adjust 7-day programmable schedules and room temperatures to optimize comfort and energy savings. The 557 can connect to tekmarNet® controls using two or four wires or it can operate as a stand-alone device.
09/14
Replaces: 09/13
Energy Saving Features
Programmable Schedule
• Zone Synchronization
• Zone Post Purge
• Warm Weather Shut Down
• Cooling Interlock
• Auto Heating Cycle
• Temporary Hold
• Away Scene Key
Additional Features
3 Auxiliary Sensor Inputs
• Air Group Master
• Backlight
• Daylight Savings Time
• Exercising
• Freeze Protection
• Heat / Cool Priority
• Network Schedule Master or
• Member
Optimum Start
• Outdoor & Floor Temperature
• Display
Radiant Floor Heating & Cooling
• Relative Humidity Control
• Room Temperature Limiting
• Scenes
• Touchscreen Technology
• tekmarNet® Communication
• Compatible
A Watts Water Technologies Company
1 of 52
© 2014
557_D - 09/14
Page 2
Table of Contents
Installation ..............................................................................................................4
Preparation ........................................................................................................4
Removing The Wiring Cover ..............................................................................5
Mounting The Thermostat..................................................................................5
Thermostat Wiring .............................................................................................6
Compatible Sensors ..........................................................................................6
Testing the Thermostat Wiring ...........................................................................6
Switch Settings .......................................................................................................8
User Interface .........................................................................................................9
Home Screen .....................................................................................................9
Symbols Description ..........................................................................................9
Programmable Settings ........................................................................................10
Programming Menus .......................................................................................10
Set Temp Menu ................................................................................................ 11
Time Menu ....................................................................................................... 14
Schedule Menu ................................................................................................16
Display Menu ...................................................................................................17
Scenes Menu ...................................................................................................18
Monitor Menu ...................................................................................................19
Toolbox Menu ..................................................................................................23
Setup Menu......................................................................................................26
Sequence of Operation .........................................................................................33
Heating Operation ............................................................................................33
Cooling Operation ............................................................................................36
Room Min and Max Limits ...............................................................................37
Hydronic Pump / Valve Operation ...................................................................37
Fan Operation ..................................................................................................38
Relative Humidity Operation ............................................................................39
Air Group Operation.........................................................................................41
Time Clock ....................................................................................................... 41
Temperature Adjustment .................................................................................42
Programmable Schedules ...............................................................................43
Scenes (System Override) ...............................................................................44
Secondary Temperature Display .....................................................................45
Access Levels ..................................................................................................46
tekmarNet
Cleaning the Thermostat .................................................................................46
Troubleshooting ....................................................................................................43
Error Messages ...............................................................................................47
Technical Data ................................................................................................. 51
Limited Warranty and Product Return Procedure ...........................................52
®
Address ........................................................................................46
A Watts Water Technologies Company
2 of 52
© 2014 557_D - 09/14
Page 3
Important Safety Information
It is your responsibility to ensure that this thermostat is safely installed according to all applicable codes and standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.
This is a safety-alert symbol. The safety alert symbol is shown alone or used with a signal word (DANGER, WARNING, or CAUTION), a pictorial and/or a safety message to identify hazards.
When you see this symbol alone or with a signal word on your equipment or in this Manual, be alert to the potential for death or serious personal injury.
This pictorial alerts you to electricity, electrocution, and shock hazards.
This symbol identifies hazards which, if not avoided, could result in death or serious injury.
This symbol identifies hazards which, if not avoided, could result in minor or moderate injury.
This symbol identifies practices, actions, or failure to act which could result in property damage or damage to the equipment.
Read Manual and all product labels BEFORE using the equipment. Do not use unless you know the safe and proper operation of this equipment. Keep this Manual available for easy access by all users. Replacement Manuals are available at tekmarControls.com
It is the installers responsibility to ensure that this thermostat is safely installed according to all applicable codes and standards.
Improper installation and operation of this thermostat could result in damage to the equipment and possibly even personal injury or death.
This thermostat is not intended for use as a primary limit control. Other controls that
• are intended and certified as safety limits must be placed into the control circuit.
Do not attempt to service the thermostat. There are no user serviceable parts inside the thermostat. Attempting to do so voids warranty.
A Watts Water Technologies Company
3 of 52
© 2014 557_D - 09/14
Page 4
Getting Started
------------------------------------------------------
--------------------------------------------------
-------------------------------------------------
Congratulations on the purchase of your new tekmar® thermostat. This manual will step through the complete installation, programming and sequence
of operation for this control. At the back, there are tips for control and system troubleshooting.
Installation
Preparation
Tools Required
tekmar or jeweller screwdriver
• Phillips head screwdriver
Materials Required
18 AWG LVT Solid Wire
• (Low Voltage Connections)
Installation Location
Choose the placement of the thermostats early in the construction process to enable proper wiring during rough-in.
Consider the following:
Interior Wall.
• Keep dry. Avoid potential leakage onto the control.
• Relative Humidity less than 90%. Non-condensing environment.
• No exposure to extreme temperatures beyond 32-122°F (0-50°C).
• No draft, direct sun, or other cause for inaccurate temperature readings.
• Away from equipment, appliances, or other sources of electrical
• interference.
Easy access for wiring, viewing, and adjusting the display screen.
• Approximately 5 feet (1.5 m) off the finished floor.
• The maximum length of wire is 500 feet (150 m).
• Strip wire to 3/8" (10 mm) for all terminal connections.
• Use standard 8 conductor, 18 AWG wire.
------------------------------------------------------
Wire Stripper
--------------------------------------------------
-------------------------------------------------
Do not use in the presence of ammonia (barn animals), methanol, ethanol
• or acetone. Damage to the internal sensor may result.
A Watts Water Technologies Company
4 of 52
© 2014 557_D - 09/14
Page 5
To prevent the risk of personal injury and/or death, make sure power is not applied to the thermostat until it is fully installed and ready for final testing. All work must be done with power turned off to the circuit being worked on.
Please be aware local codes may require this thermostat to be installed or connected by an electrician.
Removing The Wiring Cover
To remove the thermostat’s wiring cover:
Locate the slotted hole on the right
• side of the thermostat.
Insert a screwdriver in the slotted hole
• to depress the latch.
Remove the wiring cover from the
• thermostat.
Mounting The Thermostat
If a single gang box is used:
Feed the wiring through the large
• holes of the thermostat.
Fasten the base of the thermostat to
• the gang box using two screws.
Terminate wiring to the wiring strip.
• Re-install the wiring cover.
Thermostat
1
/
3
4
(83 mm)
Wiring
Cover
Stud
Switch Box
If a gang box is not used:
Feed the wiring through the large
• holes in the thermostat.
Use screws in the screw holes to
• fasten the thermostat to the wall. At least one of the screws should enter a wall stud or similar rigid material.
Terminate wiring to the wiring strip.
• Re-install the wiring cover.
Thermostat
Wall
Wiring Cover
Stud
A Watts Water Technologies Company
5 of 52
© 2014 557_D - 09/14
Page 6
Thermostat Wiring
------------------------------------------
The thermostat operates a single heating system zone and can be wired in three different ways.
Stand Alone
- Similar to tekmarNet®4 wiring with tN4 wiring terminal not used. First
stage heating relay (Rh1 - W1) can be wired directly to switching relays. tekmarNet®4 - Allows the thermostat to be wired using 4 wires to a tN4 Wiring Center
or Zone Manager point-to-point. Alternatively, the thermostat can operate the heating and cooling equipment locally and the tN4 communication bus can be daisey-chained from one thermostat to another.
®
tekmarNet
2 - Allows the thermostat to be wired point-to-point using 2 wires to a tN2
Wiring Center, House Control, or Zone Manager. This allows easy wiring for retrofit applications.
Application specific wiring diagrams are provided in the 557_A brochure.
Compatible Sensors
The thermostat is compatible with Indoor Sensor type 076, 077, 084, Slab Sensor type 072, 073, 079, Outdoor Sensor type 070, Duct Sensor type 083 and Humidity & Temperature Sensor type 086.
Testing the Thermostat Wiring
Only qualified personnel should perform testing procedures. A licensed electrician is recommended.
Testing tekmarNet®2 Wiring
------------------------------------------
Testing the Power
If the thermostat display turns on, this indicates that the thermostat is operating correctly and there are no electrical issues. In the event that the display is off, or the display is cycling on and off:
1. Remove the thermostat wiring cover.
2. Check to ensure that the tN2 wires on the thermostat are connected to a zone on a House Control, Wiring Center, or Zone Manager.
3. Use an electrical meter to measure DC voltage between the tN2 terminals.
If the DC voltage is 0 V (dc) for at least 20 seconds, then there is an open or
short circuit in the tN2 wires. If the DC voltage is 0 V (dc) for 10 seconds and then is 23 to 24 V (dc) for 5
seconds, this indicates the wiring is correct.
A Watts Water Technologies Company
6 of 52
© 2014 557_D - 09/14
Page 7
4. If the thermostat display is off, or is cycling on and off, move the thermostat to the
--------------------------
--------------------------------------------
next available zone on the House Control, Wiring Center, or Zone Manager.
If the thermostat display remains permanently on, there may be a fault with the
• previously tried zone on the House Control, Wiring Center, or Zone Manager.
If the thermostat display continues to be off, or is cycling on and off, there may
• be a fault on the thermostat.
If a fault is suspected, contact your tekmar sales representative for assistance.
Testing tekmarNet®4 and Stand Alone Wiring
Testing the Power
1. Remove the front cover from the thermostat.
2. Use an electrical test meter to measure (ac) voltage between the R and C terminals.
The reading should be 24 V (ac) +/– 10%.
3. Install the front cover.
Testing the Relay Outputs
The thermostat includes a User Test to check if the thermostat’s relays are operating and that the thermostat is wired correctly to the HVAC equipment. The User Test setting can be located in the Toolbox menu. Either Heat or Cool test can be selected.
Cancel button - Exits the user test and returns the Toolbox menu. Hold button - Pauses the user test step for up to 5 minutes. Next Item button - Advances the user test to the next test step.
Heat Test Cool Test
Step Relay(s) Closed Step Relay(s) Closed
O Relay OFF Rc-O/B is opened O Relay ON Rc-O/B B Relay ON Rc-O/B B Relay OFF Rc-O/B is opened Fan Rc-G Fan Rc-G Y1 Heat Rc-Y1 and Rc-G Y1 Cool Rc-Y1 and Rc-G
--------------------------------------------
User Test Sequence
--------------------------
Y2 Heat Rc-Y1 and Rc-Y2 and
Rc-G W2 Heat Rh2-W2 W2 Cool Rh2-W2 W1 Heat Rh1-W1 Humidify* ACC-ACC Humidify* ACC-ACC Dehumidify* ACC-ACC or Rc-Y2 Dehumidify* ACC-ACC or Rc-Y2 HRV* Rc-Y2 HRV* Rc-Y2 Valve* ACC-ACC or Rc-Y2 Valve* ACC-ACC or Rc-Y2
*availability of test step and additional relay closures based upon Setup menu settings.
A Watts Water Technologies Company
Y2 Cool Rc-Y1 and Rc-Y2 and
Rc-G
7 of 52
© 2014 557_D - 09/14
Page 8
Switch Settings
Y2
Y1
Rc G1 O/
W1Rh1 Rh2 W2 ACC
R
C
tN4
S2 S1
Com S3
Vdc
0-10
Y2Y1Rc G1 O/B
Switch
1
2
Position
ON
OFF
ON
OFF
Action
LOCK ACCESS LEVEL
Thermostat is locally locked and the access level cannot be changed. Set to Lock when installation has been completed.
UNLOCK ACCESS LEVEL
Thermostat is unlocked and the access level may be changed. Go to the Toolbox menu to change the access level. Set to Unlock during the installation process.
tekmarNet® system controls include a Global Lock that locks all connected thermostats. Set the tekmarNet® system control to unlock to allow access level adjustment on all connected thermostats.
Not used Not used
A Watts Water Technologies Company
8 of 52
© 2014 557_D - 09/14
Page 9
User Interface
Home Screen
The touchscreen of the 557 provides one touch access to these settings.
Display Humidity, Heat &
Adjust
the Time
Adjust the
Schedule
Away Key
Cool settings, Floor or Outdoor temperature
Room Temperature
Turn the Fan on
Switch between
Auto, Heat,
Cool, Off &
Emergency Mode
Adjust the
Temperature
Symbols Description
HEAT ON
Heat is turned on.
COOL ON
Cooling is turned on.
FAN
The fan is turned on.
%RH
Humidifying
%RH
Dehumidifying
SUN
Operating at the occupied (day) temperature.
MOON
Operating at the unoccupied (night) temperature.
tekmarNet
Communication is present.
®
Home
Button
Home Button. Return to the ‘Home’ Screen from any menu. Press and hold for 3 seconds to access the programming menus.
WARNING SYMBOL
Indicates an error is present.
ARROWS
Adjust the displayed setting.
SCENE AWAY
Operating at Away temperature.
TEMPORARY HOLD
Holds temperature for 3, 6, 9 or 12 hours.
WWSD
Warm Weather Shut Down.
COOL
Cooling system is on.
MIN or MAX
Reached the room min or max.
MIN FL or MAX FL
Reached the floor min or max.
A Watts Water Technologies Company
9 of 52
© 2014 557_D - 09/14
Page 10
Programmable Settings
-----------------------------------------
--------------------------------------------------------
Programming Menus
Press and hold the Home button for 3 seconds to enter the programming menus. The thermostat returns to the last programming menu previously used.
Press and hold for 3 seconds to access the programming menus.
Select a Programming Menu
Touch “NEXT” to advance (clockwise in above illustration) to the next menu.
• Touch “BACK” to go backwards (counterclockwise in above illustration) through
-----------------------------------------
the menus. Touch “ENTER” to enter a menu.
Setting Items
Touc h or arrow to adjust the setting if required.
• Touch “NEXT ITEM” to advance to the next item within the menu.
• Touch “BACK ITEM” to go backwards to the previous item within the menu.
• To return to the parent menu after changing a setting, press and release the
--------------------------------------------------------
Home button. To return to the Home screen, press and release the Home button twice or wait
• 30 seconds to automatically return to the Home screen.
A Watts Water Technologies Company
10 of 52
© 2014 557_D - 09/14
Page 11
Set Temp Menu (1 of 4)
Setting Display
SET HEAT ROOM
Room
Set the room heating temperature for the event.
Access Level: Installer, User Range: 40 to 95°F (4.5 to 35.0°C) Conditions: Always available Default: 70°F (21.0°C)
SET HEAT ROOM
Room
Set the room heating temperature for the event.
Access Level: Installer, User Range: 40 to 95°F (4.5 to 35.0°C) Conditions: Schedules are in use or Scenes are
set to All or Guest.
SET HEAT ROOM AWAY
Set the room heating temperature for the Away
Default: 65°F (18.5°C)
Room
scene. Access Level: Installer, User Range: 40 to 95°F (4.5 to 35.0°C) Conditions: Scenes is set to Away, All or Guest. Default: 62°F (16.5°C)
HEAT MINIMUM ROOM LIMIT
Set the minimum room heating limit.
Access Level: Installer Range: 40 to 95°F (4.5 to 35.0°C) Conditions: Schedules are in use or Scenes are
set to All or Guest.
Default: 40°F (4.5°C)
HEAT MAXIMUM ROOM LIMIT
Set the maximum room heating limit for the event.
Access Level: Installer Range: 40 to 95°F (4.5 to 35.0°C) Conditions: Always available Default: 85°F (29.5°C)
HEAT MAXIMUM ROOM LIMIT
Set the maximum room heating limit for the event.
Access Level: Installer Conditions: Schedules are in use or Scenes are
set to All or Guest.
Range: 40 to 95°F (4.5 to 35.0°C)
Default: 85°F (29.5°C)
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is suspended during the event.
Access Level: Installer
Range: CTRL (control), 40 to 100°F (4.5 to 38.0°C), OFF
Conditions: An outdoor sensor must be available. Default: CTRL
A Watts Water Technologies Company
11 of 52
© 2014 557_D - 09/14
Page 12
Set Temp Menu (2 of 4)
Setting Display
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is suspended during the event.
Access Level: Installer
Conditions: An outdoor sensor must be available and Schedules are in use or Scenes is set to All or Guest.
SET COOL ROOM
Set the room cooling temperature for the event.
Range: CTRL (control), 40 to 100°F (4.5 to 38.0°C), OFF
Default: CTRL
Access Level: Installer, User
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always Default: 78°F (25.5°C)
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User
Conditions: Requires that Schedules are in use or Scenes is set to All or Guest.
Range: 50 to 100°F (10.0 to
38.0°C)
Default: 85°F (29.5°C)
SET COOL ROOM AWAY
Set the room cooling temperature during the Away scene.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Scenes is set to Away, All or Guest. Default: 85°F (29.5°C)
COOL MINIMUM ROOM LIMIT
Set the minimum room cooling limit while in the event.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always available. Default: 50°F (10.0°C)
COOL MINIMUM ROOM LIMIT
Set the minimum room cooling limit while in the event.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always available. Default: 50°F (10.0°C)
A Watts Water Technologies Company
12 of 52
© 2014 557_D - 09/14
Page 13
Set Temp Menu (3 of 4)
Setting Display
COOL MAXIMUM ROOM LIMIT
Set the maximum room cooling limit.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always available Default: 100°F (38.0°C)
FLOOR MINIMUM
Set the floor heating temperature while in the event.
Access Level: Installer, User
Conditions: Sensor 1, 2 or 3 is set to Floor, and W1 Terminal is set to HRF1, HRF2 or Othr.
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Default: 72°F (22.0°C)
FLOOR MINIMUM
Set the floor heating temperature while in the event.
Access Level: Installer, User
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Conditions: Sensor 1, 2 or 3 is set to Floor, and W1 Terminal is set to HRF1, HRF2 or Othr, & Schedules
Default: OFF
are in use or Scenes are set to All or Guest.
FLOOR MAXIMUM
Set the floor maximum temperature in order to protect the floor covering.
Suggested settings: Tile = 90°F (32°C) Hardwood Floor = 85°F (29°C)
Access Level: Installer
Conditions: Sensor 1, 2 or 3 is set to Floor, & W1 Terminal is set to HRF1, HRF2 or Othr.
Range: 40 to 122°F (4.5 to
50.0°C), OFF
Default: 85°F (29.5°C)
TEMPORARY HOLD
Temperature adjustment in the home menu can result in either permanent temperature setting change or temporary temperature setting change that lasts 3, 6, 9, 12 hours or until the next scheduled event.
Access Level: Installer Range: OFF or ON Conditions: None Default: OFF
A Watts Water Technologies Company
13 of 52
© 2014 557_D - 09/14
Page 14
Set Temp Menu (4 of 4)
Setting Display
FAN
Set the minimum percentage the fan should operate while in the event. This provides ventilation for the building. Each 10% is 6 minutes per hour.
Access Level: Installer, User Range: Auto, 10 to 90%, ON Conditions: Always available. 10 to 90% available
when Ventilation Mode is On.
FAN
Set the minimum percentage the fan should operate while in the event or Away scene. This provides ventilation for the building. Each 10% is 6 minutes per hour.
Access Level: Installer, User Range: Auto, 10 to 90%, ON Conditions: Schedules used or Scenes set to Guest or
10 to 90% available when Ventilation Mode is On.
All.
HUMIDITY MINIMUM
Set the minimum humidity level during the event. Access Level: Installer, User Range: OFF, 20 to 80%
Conditions: Humidify Mode set to HM1, 2, 3. Default: 40%
HUMIDITY MAXIMUM
Set the maximum humidity level during the event.
Default: Auto
Default: Auto
Access Level: Installer, User Range: 20 to 80%, OFF Conditions: Dehumidify Mode set to DHM1, 2, 3, 4, 5. Default: 60%
HUMIDITY MAXIMUM AWAY
Set the maximum humidity level during Away scene.
Access Level: Installer Range: 20 to 80%, OFF Conditions: Dehumidify Mode set to DHM1, 2, 3, 4, 5. Default: OFF
HUMIDITY
Select if the humidification or dehumidification system should operate during the event or away scene.
Access Level: Installer Range: OFF or On Conditions: Humidity Mode set to DHM1, 2, 3 or
Dehumidity Mode set to DHM1, 2, 3, 4, 5.
Default: OFF
Time Menu (1 of 2)
Setting Display
MINUTES
Select the current time minutes. Access Level: Installer, User Range: 00 to 59 Conditions: Always available. Default: 00
A Watts Water Technologies Company
14 of 52
© 2014 557_D - 09/14
Page 15
Time Menu (2 of 2)
Setting Display
HOURS
Select the current time hours. Access Level: Installer, User Range: 12 AM to 11 PM or 00 to 23
Conditions: Always available. Default: 12 AM
DAY OF WEEK
Select the current day of the week. Access Level: Installer, User Range: Sunday to Saturday
Conditions: Always available. Default: Sunday
MONTH
Select the current month.
Access Level: Installer, User Range: JANUARY to DECEMBER Conditions: Always available. Default: JANUARY
DAY OF MONTH
Select the day of the current month.
Access Level: Installer, User Range: 1 to 31 Conditions: Always available. Default: 1
YEAR
Select the current year. Access Level: Installer, User Range: 2012 to 2255
Conditions: Always available. Default: 2012
DAYLIGHT SAVINGS TIME
Select if daylight savings time is observed.
Access Level: Installer, User Range: OFF or ON Conditions: Always available. Default: ON
TIME MODE
Select either 12 or 24 hour time format. Access Level: Installer, User Range: 12 or 24 hour Conditions: Always available. Default: 12 hour
CLOCK
Select whether to show the time clock on the display. Access Level: Installer, User Range: OFF or ON Conditions: The time is always shown when a
schedule is used and the clock setting option is no
Default: OFF
longer available.
A Watts Water Technologies Company
15 of 52
© 2014 557_D - 09/14
Page 16
Schedule Menu (1 of 2)
The schedule menu can operate on a 24 hour or 7 day repeating schedule. When a 24 hour schedule is selected, “SuMoTuWeThFrSa” is shown on the top of the screen to show that the event time applies to all days of the week. When a 7 day schedule is selected, each individual day of the week is shown with the event time.
Setting Display
EVENT 1
The first programmable schedule time period of the day. The
temperature settings are used
during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or Master 1, 2, 3, 4 and Event/Day is set to 2 or 4.
EVENT 2
The second programmable schedule time period of the day. The temperature settings are used during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or Master 1, 2, 3, 4 and Event/Day is set to 2 or 4.
EVENT 3
The third programmable schedule time period of the day. The temperature settings are used during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or Master 1, 2, 3, 4 and Event/Day is set to 4.
EVENT 4
The fourth programmable schedule time period of the day. The temperature settings are used during this time period.
Access Level: Installer, User
Conditions: Schedule setting is set to Zone or Master 1, 2, 3, 4 and Event/Day is set to 4.
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP or 00:00 to 23:50, SKIP
Default: 6:00 AM
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP or 00:00 to 23:50, SKIP
Default: 10:00 PM when Event/Day is 2 8:00 AM when Event/Day is 4
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP or 00:00 to 23:50, SKIP
Default: 6:00 PM
SuMoTuWeThFrSa
Range: 12:00 AM to 11:50 PM, SKIP or 00:00 to 23:50, SKIP
Default: 10:00 PM
A Watts Water Technologies Company
16 of 52
© 2014 557_D - 09/14
Page 17
Schedule Menu (2 of 2)
Setting Display
SCHEDULE
Select if the thermostat should change the temperature automatically using a programmable schedule.
OFF = Programmable schedule is not used. Zone = Applies to this thermostat only. Master 1, 2, 3, 4 = In charge of one of four available
network schedules. Member 1, 2, 3, 4 = Follows selected network
schedule.
Access Level: Installer, User
Conditions: In a tekmarNet® system, settings adjustable in Installer access level only.
EVENT PER DAY
Select the number of temperatures per day. Access Level: Installer, User Range: 2 or 4 Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4.
24 HOUR / 7 DAY
Access Level: Installer, User Range: 24 hour or 7 day Conditions: Schedule setting is set to Zone or Master
1, 2, 3, 4.
OPTIMUM START
Select whether or not to use optimum start. The thermostat learns the heat up and cool down rates of the room and starts heating or cooling in advance of Event 1 or Event 3.
Access Level: Installer, User Range: OFF or ON Conditions: A schedule must be in use. Default: ON
Range: OFF, Zone, Master 1, 2, 3, 4, Member 1, 2, 3, 4
Default: OFF
Default: 2
Default: 24 hour
Display Menu (1 of 2)
Setting Display
UNITS
Select Fahrenheit or Celsius as the temperature units.
Access Level: Installer, User Range: °F or °C Conditions: Always available. Default: °F
A Watts Water Technologies Company
17 of 52
© 2014 557_D - 09/14
Page 18
Display Menu (2 of 2)
Setting Display
BACKLIGHT
Select how the display backlight operates. ON = Always full brightness. DIM = Dim when inactive, on when touched.
= Dim in , off in . On when touched.
DIM
= On in , off in . On when touched.
ON OFF = Off when inactive, on when touched.
Access Level: Installer, User Conditions: Always available.
Range: DIM, ON, DIM , ON , OFF Default: DIM
SECONDARY ITEM
Determine the default item in the upper right hand corner of the Home screen.
Range: NONE, OUT (outdoor),
Access Level: Installer, User
FLOR (floor), HUM (Humidity), TEMP (Heat and Cool Temperature)
Conditions: Always available. Default: OUT (outdoor)
Scenes Menu (1 of 1)
Setting Display
SCENES
Enable or disable the use of scenes (building overrides) on this thermostat.
Access Level: Installer, User Conditions: Settings ALL and GUEST only available
in Installer access level.
SCENE 4
Select how the thermostat should respond to scene 4. Access Level: Installer
Conditions: Scenes is set to All. Default: SCHD (Schedule)
AWAY KEY
Enable or disable the away touch key on the home screen.
Access Level: Installer, User Range: OFF or ON Conditions: Scenes is set to ALL, AWAY, or GUEST. Default: OFF
LOCAL NETWORK GROUP
Select if scenes and time clock are shared when connected to a tekmarNet
®
system. OFF = Send and receive messages. ON = Receive messages only.
Access Level: Installer Range: OFF or ON Conditions: Always available. Default: OFF
Range: NONE, AWAY, ALL, GUEST
Default: NONE
Range: SCHD,
, , Away
A Watts Water Technologies Company
18 of 52
© 2014 557_D - 09/14
Page 19
Monitor Menu (1 of 5)
Setting Display
ROOM AVERAGE
Current room temperature. Displays the average if there are multiple room sensors.
Access Level: Installer
Conditions: Sensor 1, 2 or 3 is set to ROOM. Default: Not applicable.
FLOOR AVERAGE
Current floor temperature. Displays the average if there are multiple floor sensors.
Access Level: Installer
Conditions: Sensor 1, 2 or 3 is set to FLOR. Default: Not applicable.
AIR GROUP AVERAGE
Average room temperature of the thermostat and all air group member thermostats.
Access Level: Installer
Conditions: Setup menu setting Air Group Master must be set to 1 through 16.
W1 SUPPLY
First stage heating supply water temperature.
Access Level: Installer
Conditions: Setup menu setting W1 TERM set to HRF1, HRF2.
Range: -58 to 212°F (-50.0 to 100.0°C)
Range: -58 to 212°F (-50.0 to 100.0°C)
Range: -58 to 212°F (-50.0 to 100.0°C)
Default: Not applicable.
Range: -22 to 266°F (-30.0 to 130.0°C)
Default: Not applicable.
ROOM LOCAL
The built-in room sensor temperature measurement.
Access Level: Installer
Conditions: Setup menu setting Room Sensor is set to ON.
SENSOR 1
The temperature measurement from the sensor 1 input wiring terminals.
Access Level: Installer
Conditions: Setup menu setting Sensor 1 is set to ROOM, FLOR, or DUCT.
A Watts Water Technologies Company
19 of 52
Range: -58 to 212°F (-50.0 to 100.0°C)
Default: Not applicable.
Range: -22 to 266°F (-30.0 to 130.0°C)
Default: Not applicable.
© 2014 557_D - 09/14
Page 20
Monitor Menu (2 of 5)
Setting Display
SENSOR 2
The temperature measurement from the sensor 2 input wiring terminals.
Access Level: Installer
Conditions: Setup menu setting Sensor 2 is set to ROOM, FLOR, or OUT.
SENSOR 3
The temperature measurement from the sensor 3 input wiring terminals.
Access Level: Installer
Conditions: Setup menu setting Sensor 3 is set to ROOM, FLOR, or HUM.
HUMIDITY LOCAL
The built-in relative humidity sensor measurement.
Access Level: Installer Range: 0 to 100% Conditions: Setup menu setting Humidity Sensor
is set to On.
Range: -22 to 266°F (-30.0 to 130.0°C)
Default: Not applicable.
Range: -22 to 266°F (-30.0 to 130.0°C)
Default: Not applicable.
Default: Not applicable.
HUMIDITY EXTERNAL
The relative humidity measurement from the external humidity sensor.
Access Level: Installer Range: 0 to 100% Conditions: Setup menu setting Sensor 3 is set to
HUM.
Default: Not applicable.
OUTDOOR HIGH
The highest recorded outdoor air temperature measurement. Touch the number and the ENTER key to reset.
Access Level: Installer, User
Range: -76 to 149°F (-60.0 to 65.0°C)
Conditions: An outdoor temperature is available. Default: Not applicable.
OUTDOOR LOW
The lowest recorded outdoor air temperature measurement. Touch the number and the ENTER key to reset.
Access Level: Installer, User
Range: -76 to 149°F (-60.0 to 65.0°C)
Conditions: An outdoor temperature is available. Default: Not applicable.
A Watts Water Technologies Company
20 of 52
© 2014 557_D - 09/14
Page 21
Monitor Menu (3 of 5)
Setting Display
ROOM HIGH
The highest recorded room temperature measurement. Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup setting Room Sensor is set to ON or Sensor 1, 2 or 3 is set to ROOM.
ROOM LOW
The lowest recorded room temperature measurement. Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup setting Room Sensor is set to ON or Sensor 1, 2 or 3 is set to ROOM.
FLOOR HIGH
The highest recorded floor temperature measurement. Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup menu setting Sensor 1, 2 or 3 is set to FLOR.
FLOOR LOW
The lowest recorded floor temperature measurement. Touch the number and the ENTER key to reset.
Access Level: Installer, User
Conditions: Setup menu setting Sensor 1, 2 or 3 is set to FLOR.
FILTER HOURS
The total number of hours the fan has been operating since the air filter was last replaced. Touch the number and the ENTER key to reset and clear the Change Filter warning message.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Always available. Default: 0000 hours
HEAT Y1 HOURS
The total number of hours the first stage of heat pump has been in heating operation. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting Y1 TYPE is set to
HP1.
Range: -76 to 149°F (-60.0 to 65.0°C)
Default: Not applicable.
Range: -76 to 149°F (-60.0 to 65.0°C)
Default: Not applicable.
Range: -76 to 149°F (-60.0 to 65.0°C)
Default: Not applicable.
Range: -76 to 149°F (-60.0 to 65.0°C)
Default: Not applicable.
Default: 0000 hours
A Watts Water Technologies Company
21 of 52
© 2014 557_D - 09/14
Page 22
Monitor Menu (4 of 5)
Setting Display
HEAT Y2 HOURS
The total number of hours the second stage of heat pump has been in heating operation. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting Y2 TYPE is set to
HP2.
HEAT W1 HOURS
The total number of hours the W1 relay has been operated for heating. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu W1 TERM is set to HRF1,
HRF2 or OTHR.
BACKUP W2 HOURS
The total number of hours the Backup W2 relay has been operated for heating. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting BACKUP W2 TERM
is set to CONV, COIL, FURN, or OTHR.
COOL Y1 HOURS
The total number of hours the first stage of heat pump has been in cooling operation. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Always available. Default: 0000 hours
COOL Y2 HOURS
The total number of hours the second stage of heat pump has been in cooling operation. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu Y2 TYPE is set to HP2. Default: 0000 hours
COOL W1 HOURS
The total number of hours the W1 relay has been operated for cooling. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting Floor Cool is set to
ON and W1 TERM is set to HRF1 or HRF2.
Default: 0000 hours
Default: 0000 hours
Default: 0000 hours
Default: 0000 hours
A Watts Water Technologies Company
22 of 52
© 2014 557_D - 09/14
Page 23
Monitor Menu (5 of 5)
Setting Display
COOL W2 HOURS
The total number of hours the W2 relay has been operated for cooling. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting BACKUP W2 SOURC
is set to TANK and BACKUP W2 TERM is set to COIL.
FAN HOURS
The total number of hours the fan has been operated. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Always available. Default: 0000 hours
HUMIDIFY HOURS
The total number of hours the humidifier has been operated. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting ACC RELAY is set
to HUM.
DEHUMIDIFY HOURS
The total number of hours the dehumidifier has been operated. Touch the number and the ENTER key to reset.
Access Level: Installer, User Range: 0000 to 9999 hours Conditions: Setup menu setting ACC RELAY is set
to DHUM or Y2 RELAY is set to DHUM.
Default: 0000 hours
Default: 0000 hours
Default: 0000 hours
Toolbox Menu (1 of 3)
Setting Display
ACCESS LEVEL
Selects the access level of the thermostat, which determines which menus and items are available.
Range: INST (installer),
Access Level: Installer, User, Limited, Secure
Conditions: Adjustable only when thermostat switch setting set to UNLOCK OR tekmarNet® system control switch setting
set to UNLOCK.
A Watts Water Technologies Company
23 of 52
USER, LTD (limited), SEC (secure)
Default: INST
© 2014 557_D - 09/14
Page 24
Toolbox Menu (2 of 3)
Setting Display
STATUS INFO
Displays the current status of the thermostat including any overrides from the tekmarNet
between “Status Info” and the current status.
System Normal = Thermostat operating normally.
Override W1 = The tekmarNet® system control is either
forcing the W1 relay on or off.
Cooling Floor = Floor cooling is in effect.
WWSD = Warm Weather Shut Down is in effect. CWSD = Cold Weather Shut Down is in effect.
Optimum Start Heat or Cool = The heating or cooling
system is started early in order to meet temperature setpoint at Event 1 or Event 3. Floor Max = The floor has reached its maximum tempera­ture. Some under heating could occur. Floor Min = The floor is operating at its minimum tempera­ture. Some over heating could occur. Baseload On = Baseload heating is on even though the room temperature is satisfied. Reduces heat up time when the sun sets in the evening.
Hydronic Heat Off = The air group master is in cooling mode and air group member thermostats’ heating is shut off.
Interlock Wait = The thermostat is switching between heating to cooling or from cooling to heating.
Priority Heat = Air group members are calling for heat. Cooling is suspended.
Access Level: Installer, User Range: See Description Conditions: Always available. Default: System Normal
ADDRESS
The tekmarNet® address of this thermostat. To manually set the address, use the up or down arrow buttons
while in the Installer access level.
Access Level: Installer
Conditions: tekmarNet®2 or 4 detected.
SOFTWARE AND TYPE VERSION
Displays the software version and the tekmar type number. Access Level: Installer, User, Limited, Secure Range: 557
Conditions: Always available. Default: 557
®
system control. Toggles
Range: AUTO, 01 to 24, b:01 to b:24, 1:01 to 1:24, 2:01 to 2:24, 3:01 to 3:24
Default: AUTO
A Watts Water Technologies Company
24 of 52
© 2014 557_D - 09/14
Page 25
Toolbox Menu (3 of 3)
Setting Display
DEVICE COUNT
Provides a count of all the tekmarNet® thermostats and setpoint controls on the tekmarNet® system.
Access Level: Installer
®
Conditions: Must be connected to a tekmarNet
system.
USER TEST
Use the up or down arrow keys to select either the heat or cool test sequence, then press the NEXT key to begin. Press HOLD to pause at step for 5 minutes. Press NEXT to advance to the next step.
Access Level: Installer
Conditions: Always available.
OFFSET ROOM
Manual offset correction of the room temperature measurement.
Access Level: Installer
Conditions: Always available.
OFFSET HUMIDITY
Manual offset correction of the room humidity measurement.
Access Level: Installer Conditions: Always available.
FILTER CHANGE HOURS
Select the amount of time the fan operates before the air filter requires maintenance.
Access Level: Installer
Conditions: Always available. Default: OFF
LOAD FACTORY DEFAULTS
Touch Enter to load the factory defaults settings.
Range: 1 to 24 Default: 1
Range: OFF, HEAT or COOL
Default: OFF
Range: -5 to +5°F (-3.0 to +3.0°C)
Default: 0°F (0.0°C)
Range: -10 to +10% Default: 0%
Range: OFF, 200 to 2000 hours
Access Level: Installer Range: None
Conditions: Always available.
Default: Keep existing settings
ERROR HISTORY 1 THROUGH 5
Displays a history of the last 5 errors that have occurred on the thermostat in the past 30 days. Touch Enter to manually clear the error code.
Access Level: Installer
Conditions: An error must have occurred.
A Watts Water Technologies Company
25 of 52
Range: See Troubleshooting section
Default: Not applicable
© 2014 557_D - 09/14
Page 26
Setup Menu (1 of 7)
Setting Display
SENSOR 1
Select to the type of sensor connected to auxiliary sensor input 1.
Access Level: Installer
Conditions: Always available. Default: OFF
SENSOR 2
Select to the type of sensor connected to auxiliary sensor input 2.
Access Level: Installer
Conditions: Always available. Default: OFF
SENSOR 3
Select to the type of sensor connected to auxiliary sensor input 3.
Access Level: Installer
Conditions: Always available. Default: OFF
ROOM SENSOR
Select whether the built-in room temperature sensor is on or off.
Access Level: Installer Range: OFF or ON Conditions: Only available when Sensor 1, 2 or 3 is
set to ROOM or FLOR.
HUMIDITY SENSOR
Select whether the built-in humidity sensor is on or off.
Access Level: Installer Range: OFF or On Conditions: Only available when Sensor 3 is set
to HUM.
W1 TERMINAL UNIT
Select the terminal unit type of the first stage of heat W1.
HRF1 = High mass hydronic radiant floor HRF2 = Low mass hydronic radiant floor OTHR = Other than hydronic heating
Access Level: Installer
Conditions: Always available. HRF1 and HRF2 only available when connected to a tekmarNet
®
System
Control.
Range: OFF, ROOM, FLOR (floor), DUCT
Range: OFF, ROOM, FLOR (floor), OUT (outdoor)
Range: OFF, ROOM, FLOR (floor), HUM (humidity)
Default: ON
Default: On
Range: NONE, HRF1, HRF2, OTHR
Default: NONE
A Watts Water Technologies Company
26 of 52
© 2014 557_D - 09/14
Page 27
Setup Menu (2 of 7)
Setting Display
W1 PUMP
Select whether the primary or mix system pump on a tekmarNet® system control should operate while
the first stage of heat W1 is operating. Access Level: Installer Range: OFF or ON Conditions: Only available when a tekmarNet® system
control is connected and the Setup menu setting W1 TERM is set to HRF1, HRF2.
W1 THERMAL MOTOR
Select whether the first stage of heat W1 operates a thermally actuated zone valve (wax actuator). When set to ON, there is a 3 minute delay before operating the pump and any heat sources.
Access Level: Installer Range: OFF or ON Conditions: Only available when a tekmarNet
system control is connected and the Setup menu setting W1 TERM is set to HRF1, HRF2.
BACKUP W2 TERMINAL
Select the type of backup heating. CONV = baseboard convectors COIL = hydronic fan coil FURN = forced air furnace OTHR = non-hydronic heating that does not require
the fan to operate
Access Level: Installer
Conditions: Always available. Default: NONE
BACKUP W2 SOURCE
Select the water temperature of the hydronic backup heating.
Access Level: Installer
Conditions: BACKUP W2 TERMINAL is set to CONV or COIL.
BACKUP W2 PUMP
Select whether the primary or mix system pump on a tekmarNet® system control should operate while
the backup stage of heat W2 is operating. Access Level: Installer Range: OFF or ON Conditions: BACKUP W2 TERMINAL is set to CONV
or COIL.
Default: ON
®
Default: OFF
Range: NONE, CONV, COIL, FURN, OTHR
Range: BOIL, TNK1, MIX1, MIX2, MIX3
Default: BOIL
Default: ON
A Watts Water Technologies Company
27 of 52
© 2014 557_D - 09/14
Page 28
Setup Menu (3 of 7)
Setting Display
BACKUP W2 THERMAL MOTOR
Select whether the backup stage of heat W2 operates a thermally actuated zone valve (wax actuator). When set to ON, there is a 3 minute delay before operating the pump and any heat sources.
Access Level: Installer Range: OFF or ON Conditions: BACKUP W2 TERMINAL is set to CONV
or COIL.
BACKUP W2 DELAY
The minimum amount of time that the first stage W1 and the heat pump must be operating before the backup second stage W2 can turn on.
AUTO = Automatic PID staging OVR = W2 only turns on when Mode is set to EMER.
Access Level: Installer Range: AUTO, 10 to 180 min, OVR Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, or OTHR.
BACKUP W2 DIFFERENTIAL
Select the backup W2 differential turn on point from the previous heat stages.
Access Level: Installer Range: 0.0 to 8.0°F (0.0 to 8.0°C) Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, OTHER.
LOCKOUT W2
The outdoor temperature above which the backup heat W2 is disabled. When Mode is set to EMER (emergency), the W2 is allowed to turn on.
Access Level: Installer
Conditions: BACKUP W2 TERMINAL is set to CONV, COIL, FURN, or OTHR.
Y1 RELAY
Select the cooling equipment the Y1 relay operates. HP1 = Heat pump AC1 = Air conditioner W2 = W2 turned on together with Y1. Used for 2-pipe
hot / chilled water fan coils. The backup W2 relay activates the pump or zone valve for the fan coil for both heating and cooling. Only available when Backup W2 Source is set to TNK1.
Access Level: Installer Range: HP1, AC1, W2 Conditions: Always available. Default: HP1
Default: OFF
Default: 60 minutes
Default: 1.0°F (0.6°C)
Range: 40 to 65°F, OFF (4.5 to
18.5°C)
Default: 60°F (15.5°C)
A Watts Water Technologies Company
28 of 52
© 2014 557_D - 09/14
Page 29
Setup Menu (4 of 7)
Setting Display
Y2 RELAY
Select the equipment the Y2 relay operates. HP2 = Second stage heat pump AC2 = Second stage air conditioner HRV = Heat recovery ventilator DHUM = Dehumidifier VALV = Hydronic valve for building loop
Access Level: Installer
Conditions: Always available. Default: OFF
ACCESSORY RELAY
Select the equipment the accessory relay operates. HUM = Humidifier DHUM = Dehumidifier VALV = Hydronic valve for building loop
Access Level: Installer Range: OFF, HUM, DHUM, VALV Conditions: Always available. Default: OFF
O/B VALVE
Select the heat pump operation of the O / B relay. O = Turn on during cooling, turn off during heating B = Turn off during cooling, turn on during heating
Access Level: Installer Range: O or B Conditions: Y1 RELAY is set to HP1. Default: O
HP SOURCE
Select the type of source for the heat pump. AIR = Air source heat pump GEO = Geothermal source heat pump LOOP = Building hydronic loop heat pump
Access Level: Installer Range: AIR, GEO, LOOP Conditions: Y1 RELAY is set to HP1. Default: AIR
Range: OFF, HP2, AC2, HRV, DHUM, VALV
Y MINIMUM OFF
Select the compressor minimum off time.
Access Level: Installer Range: 0:30 to 10:00 minutes Conditions: Always available. Default: 5:00 minutes
Y2 DIFFERENTIAL
Select the Y2 differential on point.
Access Level: Installer Range: 0.0 to 4.0°F (0.0 to 4.0°C) Conditions: Y2 RELAY is set to HP2 or AC2. Default: 0.5°F
A Watts Water Technologies Company
29 of 52
© 2014 557_D - 09/14
Page 30
Setup Menu (5 of 7)
Setting Display
Y2 DELAY
Select the amount of time that must elapse after the Y1 relay is turned on before the Y2 relay is allowed.
Access Level: Installer Range: AUTO, 5 to 180 minutes Conditions: Y2 RELAY is set to HP2 or AC2. Defaults: AUTO minutes
COOLING CWSD
Select the outdoor temperature below which the cooling system is disabled.
Access Level: Installer
Range: OFF, 35 to 75°F (OFF, 1.5 to 24.0°C)
Conditions: Always available. Default: 55°F (13.0°C)
INTERLOCK
Select the amount of time for the heat - cool interlock. Applies only when Mode is set to Auto. Reduces excessive heat-cool switchovers.
Access Level: Installer Range: 10 to 180 minutes Conditions: Always available. Default: 30 minutes
BALANCE POINT SCHEDULE
Select if the heat pump balance point should change based upon a programmable schedule.
Access Level: Installer
Conditions: Y1 RELAY is set to HP1 and outdoor temperature is available.
Range: OFF, ZONE, MEMBER 1 to 4
Default: OFF
BALANCE POINT
Heat pump balance point during the time period.
Access Level: Installer
Conditions: Y1 RELAY is set to HP1 and an outdoor temperature is available.
Range: OFF, 10 to 70°F (OFF, -12.0 to 21.0°C)
Default: OFF
BALANCE POINT
Heat pump balance point during the time period.
Access Level: Installer
Conditions: Y1 RELAY set to HP1, BALANCE POINT is set to schedule and outdoor temperature is available.
A Watts Water Technologies Company
30 of 52
Range: OFF, 10 to 70°F (OFF,
-12.0 to 21.0°C)
Default: OFF
© 2014 557_D - 09/14
Page 31
Setup Menu (6 of 7)
Setting Display
W1 HEAT WWSD
Select the outdoor temperature above which the radiant floor heating is shut off.
Access Level: Installer
Conditions: W1 TERMINAL is set HRF1, HRF2, or OTHR and outdoor temperature is available.
W CYCLES PER HOUR
Select the number of heating cycles per hour. SYNC = 20 minute zone synchronization. AUTO = Automatic cycles per hour to minimize
temperature swings. Access Level: Installer Range: SYNC, AUTO, 2 to 12 Conditions: Setup menu setting W1 TERMINAL is set
to OTHR (other) or the thermostat is not connected to a tekmarNet
®
system control.
Y DURING W2
Select whether the heat pump compressor can operate when backup heat or cool W2 is on. When Mode is set to EMER (emergency), the heat pump compressors Y1 and Y2 are always shut off.
Access Level: Installer Range: OFF or ON Conditions: BACKUP W2 TERMINAL is set to CONV,
COIL, FURN, or OTHR.
BASELOAD
Select the level of radiant floor baseload heating. This warms the floor so that solar gain and / or air heating systems do not cause cold floors.
Access Level: Installer Range: OFF, LOW, MED, HIGH Conditions: Only available when a tekmarNet® system
control is connected and the Setup menu setting W1 TERM is set to HRF1 or HRF2 and SENSOR 1, 2 or 3 is not set to FLOR (floor).
FLOOR COOL
Select whether or not the thermostat operates W1 for radiant floor cooling.
Access Level: Installer Range: OFF or ON Conditions: Setup menu setting W1 TERM is set to
HRF1 or HRF2 and the thermostat must be connected to a tekmarNet® heat pump or chiller system control.
Range: OFF, 32 to 80°F (0 to
26.5°C)
Default: 60°F (15.5°C)
Default: SYNC
Default: OFF
Default: OFF
Default: OFF
A Watts Water Technologies Company
31 of 52
© 2014 557_D - 09/14
Page 32
Setup Menu (7 of 7)
Setting Display
AIR GROUP MASTER
Select if the thermostat is a master of an air group. Access Level: Installer Range: NONE, 1 to 16
Conditions: The thermostat must be connected to other thermostats using tekmarNet®.
PRIORITY
Select either heating or cooling priority. Access Level: Installer Range: HEAT or COOL Conditions: Air Group Master is set to 1 to 16. Default: COOL
VENTILATION MODE
Select whether the fan provides ventilation. Access Level: Installer Range: OFF or ON Conditions: Always available. Default: OFF
HEAT PURGE
Select the fan coil heating purge based upon either time or on duct air temperature.
Access Level: Installer
Conditions: Always available. Default: 0:30 min or 100°F (38.0°C)
COOL PURGE
Select the fan coil cooling purge based upon either time or on duct air temperature.
Access Level: Installer
Conditions: Always available. Default: 0:00 min or 60°F (15.5°C)
Default: NONE
Range: 0:00 to 3:00 minutes (no duct sensor) or 70 to 160°F, OFF (21.0 to 71.0°C,
OFF) (with duct sensor)
Range: 0:00 to 3:00 minutes (no duct sensor) or OFF, 40 to 70°F (OFF, 4.5 to
21.0°C) (duct sensor required)
HUMIDIFY MODE
Select the humidifier operation mode.
Access Level: Installer Range: OFF, HM1, HM2, HM3 Conditions: ACC RELAY is set to HUM. Default: OFF
DEHUMIDIFY MODE
Select the dehumidifier mode.
Access Level: Installer Range: OFF, DHM1 to DHM5 Conditions: ACC RELAY is set to DHUM or Y2 RELAY
is set to DHUM or HRV.
A Watts Water Technologies Company
32 of 52
Default: OFF
© 2014 557_D - 09/14
Page 33
Sequence of Operation
-----------------------------------------------
---------------------------------------------
--------------------------------------------------------
Heating Operation
Set Heat Temperature
-----------------------------------------------
Section A
The 557 can operate radiant floor heating, heat pump stage 1 and stage 2, and a backup heat source to provide heating in different combinations depending on the outdoor air temperature. The illustration below shows when each of the available heating units are available. The “Heat On” symbol is shown on the display when the thermostat is heating. If not operating a heat pump, the first and second stage of heat (W1 and W2) are allowed to turn on below the Warm Weather Shut Down to maintain the Set Heat Room temperature.
Heat Pump - Heating Mode
Room
Warmer
Set Heat
Room
Room
Colder
Air Temperature Heating
When using only a room temperature sensor, the thermostat operates the heating system to maintain the Set Heat Room temperature.
Floor Heating
When using both a room and a floor temperature sensor, the thermostat always maintains the Floor Minimum temperature, even when the air temperature is satisfied. When the air temperature is below the Set Heat Room temperature, the thermostat operates the heating system to maintain the Set Heat Room temperature. The floor is never heated above the Floor Maximum setting in order to protect the floor covering.
No heating Air heating only All allowedNo backup heat
W1 off
Y1 off Y2 off
Y1 on Y2 on
Warm Weather
Shut Down
Default = 70°F
--------------------------------------------------------
Radiant Floor
Warm Weather
Shut Down
Default = 60°F
---------------------------------------------
W1 off
Y1 off Y2 off
W1 on
Y1 on Y2 on
Default = 60°F
Y1 off Y2 off
W2 off W1 on
Y1 on Y2 on
W2 on
Lockout
No heat pump
W1 off W2 off
W1 on W2 on
Temperature
Balance
Point
Default = Off
Colder
Outdoor
Suggested Floor Maximum settings are 90°F (32°C) for tile, stone, or concrete floors and 85°F (29°C) for wood floors.
A Watts Water Technologies Company
33 of 52
© 2014 557_D - 09/14
Page 34
Radiant Floor Baseload
----------------------------------------------
--------------------------------------------
-------------------------------------------------------
When the terminal unit is selected to be a Hydronic Radiant Floor (HRF1 or HRF2) and no floor temperature sensor is installed, the thermostat has option to provide baseload heating. This allows the radiant floor to be heated even though the room air temperature is satisfied. This is useful in areas where a radiant floor heating zone is overlapped by an air heating system. The radiant floor heating is overwhelmed by the quick heat up rate of the air heating system, resulting in a radiant floor heating zone that rarely turns on. The radiant baseload option allows the radiant floor to counteract the air heating system by heating the floor at a reduced output even when the room air temperature is satisfied. This is also useful in areas that experience large solar gains through windows. The radiant baseload is automatically shut off in the summer by the warm weather shut down feature.
----------------------------------------------
Warm Weather Shut Down
When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD) setting on the tekmarNet® main control, the heating system is shut off.
A W1 HEAT WWSD setting is available to allow the heat pump to heat the building while the radiant floor heat system is shut off during mild outdoor temperatures. This is advantageous in the spring and fall when heating is required at night and cooling is required during the day. As the outdoor temperature falls below the W1 HEAT WWSD setting, the radiant floor becomes the primary heat source and the heat pump provides supplemental heating.
Balance Point
An air source heat pump’s Coefficient Of Performance (COP) decreases with colder outdoor temperature. This affects the heating output capacity of the heat pump to heat the building. When the COP is equal to 1, the heat pump no longer provides an economic advantage over electric heating elements or other supplemental heating fuel. The outdoor temperature at which this occurs is known as the balance point. When the outdoor temperature falls below the balance point, the heat pump is shut off and the backup supplemental heat source is operated to heat the building. The 557 has the ability for the balance point setting change based upon a programmable schedule. This is useful in cases where the electrical utility offers lower different energy pricing throughout the day.
-------------------------------------------------------
--------------------------------------------
A Watts Water Technologies Company
34 of 52
© 2014 557_D - 09/14
Page 35
Backup W2 Differential
-----------------------------------------------
----------------------------------------------------
The backup heat source operated by W2 has an adjustable differential. The differential is relative to the previous heating stage.
No radiant floor heating, no heat pump (no W1, no Y1, no Y2)
The W2 relay’s differential is ±1
Radiant floor heating, no heat pump (W1, no Y1, no Y2)
The W2 relay turns on at Set Heat - Backup Differential.
Single Stage Heat Pump (W1, Y1, no Y2)
The W2 relay turns on at Set Heat - 1°F (0.5°C) - Backup Differential.
Two Stage Heat Pump (W1, Y1, Y2)
The W2 relay turns on at Set Heat - 1°F (0.5°C) - Y2 Differential - Backup Differential.
-----------------------------------------------
°F (0.5°C) centered around Set Heat.
Freeze Protection
The thermostat operates the heat whenever the room or floor temperature falls below 40°F (4.5°C) even when the mode is set to off.
----------------------------------------------------
A Watts Water Technologies Company
35 of 52
© 2014 557_D - 09/14
Page 36
Cooling Operation
-----------------------------------------------
-------------------------------------------------------
-------------------------------------
Section B
Set Cool Temperature
-----------------------------------------------
The 557 can operate a two-stage heat pump or air conditioner to provide cooling depending on the outdoor air temperature. In some cases, cooling is provided by a chilled water fan coil. The illustration below shows when each of the available cooling units are available. The “Cool On” symbol is shown on the display when the thermostat is cooling.
Floor Cooling
-------------------------------------------------------
Floor cooling is designed to cool a building together with an air cooling system. Floor cooling reduces part of the sensible cooling load, while the air cooling equipment must cool the latent load (dehumidification) and the remaining sensible load.
The thermostat has the option to support floor cooling when connected to a heat pump control using tekmarNet® communication. The terminal unit type must be set to be HRF1 or HRF2, the floor cooling setting must be set to On and the heating system must be in Warm Weather Shut Down (WWSD). When the thermostat is set to Mode Cool, the floor cooling turns on 1.0°F (0.5°C) below the Set Cool setpoint. This allows the floor cooling to operate for long periods of time while the air cooling system cycles on and off to maintain the cooling setpoint. Floor cooling does not operate below 64°F (18.0°C).
Cooling Cold Weather Shut Down
-------------------------------------
When the outdoor air temperature falls below the Cooling Cold Weather Shut Down (CWSD) setting on the thermostat, the cooling system is shut off.
No Cooling
Cooling Cold Weather Shutdown
A Watts Water Technologies Company
Warm Weather Shut Down
36 of 52
Floor Cooling
Warmer Outdoor Temperature
© 2014 557_D - 09/14
Page 37
Room Min and Max Limits
----------------------------------------------------------
------------------------------------------------------------
---------------------------------------
---------------------------------------------------
Heating and cooling minimum and maximum temperature settings are available in the Set Temp menu. These allow the installer to select start and stop limits for the temperature settings in both heating and cooling for the User and Limited access levels. This is useful in commercial installations and child / guest bedrooms where availability of the full temperature setting range may not be desirable.
Section C
Hydronic Pump and Valve Operation
Exercising
When connected to a tekmarNet® system control, the thermostat exercises the heat relay for 10 seconds every 3 days. Exercising helps prevent zone valves or zone pumps from failing due to precipitate buildup. During exercising, the thermostat shows “TEST” on the display.
Flushing
The flushing feature is for open-loop systems that use a domestic hot water tank as a heat source. Flushing ensures that fresh potable water is circulated through the system once each day. If the thermostat is connected to a tekmarNet® system control with the Flushing feature turned on, the thermostat display will display “FLUSHING” for the duration of the flushing operation.
Hydronic System Supply Pump
When connected to a tekmarNet® system control, the thermostat’s W1 Pump setting affects how the primary pump or mix pump on the system control operates. When connected to the boiler bus, the boiler system or primary pump is operated. When connected to the mix bus, the mix system pump is operated.
If the thermostat operates a motorized or thermal motor zone valve, the W1 Pump setting should be set to On.
If the thermostat operates a thermal motor (wax actuator) zone valve, set the W1 Thermal Motor setting to On. This provides a three minute delay to allow the zone valve to open before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the W1 Pump setting can be set to Off. This allows a Zone Group Pump located on the Zone Manager, or Wiring Center to operate the pump for the manifold.
DHW Tank Priority
When a tekmarNet® system control is heating an indirect Domestic Hot Water (DHW) tank, the thermostat may shut off the heating zones to allow the DHW tank to recover quickly. This is determined by the DHW priority of the tekmarNet
----------------------------------------------------------
------------------------------------------------------------
---------------------------------------
---------------------------------------------------
Section D
®
system control.
A Watts Water Technologies Company
37 of 52
© 2014 557_D - 09/14
Page 38
Fan Operation
------------------------------------------------------
------------------------------------------------------
The fan operates together with the air heating or cooling systems. The user can also select to operate the fan manually by pressing the Fan button. This allows the user to choose between Auto and On. “Auto” allows the fan to operate together with heating or cooling but normally the fan is off. “On” forces the fan to operate continuously.
Section E
Ventilation Fan
In order to provide ventilation to the building, the fan can also operate for additional time beyond what is required for the heating and cooling systems. Ventilation allows the user to select the fan to operate for a minimum percentage out of each hour. Options are 10 to 90%, in 10% (6 minutes per hour) increments, as well as Auto and On. This is available when the Vent Mode setting in the Setup menu is set to On.
Once Ventilation is set to On, the Fan minimum run time percentage during the and events can be set so that the fan can operate on a schedule and/or together with scenes.
Fan Post Purge
The fan relay includes a post purge feature that operates the fan after the heating or cooling system has shut off. When a duct temperature sensor is installed the length of post purge is based on the air duct temperature and the Heatpurge or Coolpurge temperature settings. When there is no duct temperature sensor installed, the length of post purge is based upon the Heatpurge and Coolpurge time settings.
------------------------------------------------------
------------------------------------------------------
A Watts Water Technologies Company
38 of 52
© 2014 557_D - 09/14
Page 39
Relative Humidity Operation
Section F
Relative Humidity (RH) is controlled by maintaining the Minimum Humidity using humidification and by maintaining Maximum Humidity using dehumidification. The RH is maintained within a 5% differential. The differential is applied above the minimum setpoint, and applied below the maximum setpoint. When the mode is set to off, the humidification and dehumidification systems do not operate.
To avoid condensation on windows, the minimum relative humidity setting can be changed according to the following outdoor temperatures.
Outdoor Temperature Suggested RH Min
-10°F (-23°C) 0°F (-18°C) 10°F (-12°C) 20°F (-7°C) 30°F (-1°C) 20% 25% 30% 35% 35%
The thermostat has three humidification modes.
Operation Mode Required
Relay(s)
Stand Alone Humidifier
Humidifier operates independently of the HVAC
HM1 ACC RELAY
= HUM system. Available in all modes except off.
Humidifier with Fan
Humidifier ducted together with HVAC system.
HM2 ACC RELAY
= HUM The system fan is operated whenever the humidi-
fier is operating. Available in all modes except off.
Humidifier with Air Heating
Humidifier ducted together with HVAC system.
HM3 ACC RELAY
= HUM The air system must be heating (heat pump,
furnace, electric or hydronic fan coil) in order to allow the humidifier to operate.
Available when heating.
Sensor Required
None
None
None
A Watts Water Technologies Company
39 of 52
© 2014 557_D - 09/14
Page 40
The thermostat has up to five dehumidification modes.
Operation Mode Required
Relay(s)
Stand Alone Dehumidifier
Dehumidifier operates independently or the HVAC system.
Available in all modes except off.
DHM1 ACC RELAY
= DHUM
or
Y2 RELAY = DHUM
Coil Dehumidification
A duct temperature sensor is required. A DX or chilled water coil is operated to maintain a dis­charge air temperature of 45°F (7°C). The room air temperature is allowed to fall up to 3°F (1.5°C)
DHM2 ACC RELAY
= DHUM
or
Y2 RELAY = DHUM
below the cooling setpoint while coil dehumidifi­cation is operating, at which point dehumidifica­tion is shut off. The fan relay (G) is not turned on, rather the ACC or Y2 relay provides a signal to the air handler unit to operate the fan at low speed.
Available only when cooling.
HRV Dehumidification (only available with single stage heat pumps
DHM3 Y2 RELAY =
HRV
or air conditioners)
The HRV is operated based upon indoor dew point and outdoor air temperature. The HRV op­erates when the indoor dew point is 5.5°F (3.0°C) above the outdoor temperature. The HRV is shut off when the indoor dew point falls to 2°F (1.0°C) above the outdoor temperature.
Available in all modes except off.
Stand Alone + HRV Dehumidification (only available with single stage heat pumps
or air conditioners)
During cooling mode, a stand alone dehumidifier is operated in the same manner as DHM1.
DHM4 ACC RELAY
= DHUM
and
Y2 RELAY =
HRV During heating mode, an HRV provides dehu­midification in the same manner as DHM3. Available in all modes except off.
Coil + HRV Dehumidification (only available with single stage heat pumps
or air conditioners)
During cooling mode, a coil dehumidifier is oper­ated in the same manner as DHM2.
DHM5 ACC RELAY
= DHUM
and
Y2 RELAY =
HRV During heating mode, an HRV provides dehu­midification in the same manner as DHM3. Available in all modes except off.
Sensor Required
None
Duct Sensor 083
Outdoor Sensor 070
Outdoor Sensor 070
Duct Sensor 083
and
Outdoor Sensor 070
A Watts Water Technologies Company
40 of 52
© 2014 557_D - 09/14
Page 41
Air Group Operation
Section G
In order to prevent heating and cooling at the same time, this thermostat can operate together with other thermostats on a tekmarNet
®
system to form an air group. On older model thermostats the air group functionality was previously described as a cool group. In an air group, one thermostat is assigned as the air group master. The air group master operates the cooling equipment for the group. When operating as a air group, the air temperature readings of all the air group member thermostats are communicated to the air group master thermostat and an average temperature is determined. When the air group master is in cooling operation, the air group member thermostats do not operate the heating system for air heating.
When operating a heat pump, the 557 also has the ability to prevent air group member thermostats from heating while the outdoor temperature is between the Warm Weather Shut Down (WWSD) and the Radiant Floor WWSD (W1 WWSD) setting. This allows the air system heat pump to heat the building during mild outdoor weather and avoids heating up the radiant floor slab.
If the Set Heat Room temperature is adjusted while the air group is cooling, COOL is flashed on the display to alert the user that the air group cooling system is presently on and heating is not available. Once the cooling system shuts off, heating is available if required.
Air Group
Master
tekmarNet® Communication
Time Clock
MemberMember
Section H
The thermostat includes a time clock that is automatically visible in the Home menu when a programmable schedule is used. If the schedule is not used, the user has the option to select whether the time is shown in the Home menu.
During a loss of power, the thermostat continues to keep the correct time and date for at least 4 hours. If the power is off for more than 4 hours, the user will
need to set the time. The thermostat supports automatic update for daylight savings time. Simply set
Daylight Save to On together with the correct day, month, and year and the time is automatically updated each spring and fall.
When connected to a tekmarNet
®
system, adjustment of the time on one thermostat updates all connected thermostats. This option can be disabled by selecting the Local Network Group setting to be On.
A Watts Water Technologies Company
41 of 52
© 2014 557_D - 09/14
Page 42
Temperature Adjustment
--------------------------------
-------------------------------
-----------------------------------------------------
Section I
Permanent Adjustment - No Schedule
When no programmable schedule is used, touch the up or down arrows to permanently set the “Set Heat Room” or “Set Cool Room” temperature. This thermostat is capable of controlling both air and floor temperature.
Permanent Adjustment - With Schedule
--------------------------------
-------------------------------
When a programmable schedule is used, there are two room heating temperatures available, one for the
time period and another for the time period. When touching the up or down arrows to change the temperature, only the temperature for the current time period is changed.
1. To adjust the temperature for both time periods, press and hold the Home button
for 3 seconds to enter the programming menus.
2. Enter the “SET TEMP” menu to adjust the following settings:
Set Heat Room (air heating or air heating with floor sensor)
• Set Heat Room (air heating or air heating with floor sensor)
• Set Heat Room AWAY (air heating or air heating with floor sensor)
• Floor Min (air heating with floor sensor)
• Floor Min (air heating with floor sensor)
• Set Cool Room (air cooling)
• Set Cool Room (air cooling)
• Set Cool Room AWAY (air cooling)
Temporary Hold
Temporary hold allows a user to change the temperature for a period of time and then automatically return to the permanent temperature setting. This is especially useful in commercial buildings that are in use for short amounts of time. When selected, touching the up or down arrows changes the temperature for either 3, 6, 9 or 12 hours. If the thermostat is using a schedule, ‘Schd’ provides a temporary hold until the next schedule event time. After the temporary hold time expires, the thermostat returns to normal operation. By default, the temporary hold feature is off.
-----------------------------------------------------
When the temporary hold feature is enabled, the up or displays ‘TEMPORARY HOLD’.
A Watts Water Technologies Company
touching
down arrow
Use the Up or Down
arrow to select a
temperature.
42 of 52
Tap the hour setting until the preferred length of time is displayed.
Cancel the
temporary
hold.
‘HOLD’ is displayed while the thermostat is operating at the
temporary hold temperature.
© 2014 557_D - 09/14
Page 43
Programmable Schedules
Section J
Energy savings can be achieved by lowering the heating temperature and increasing the cooling temperature when the building is unoccupied or during the night.
When operating on a programmable schedule, a or a symbol is shown in the home menu. The or indicates the current operating temperature.
All schedules are stored in permanent memory and are not affected by a loss of power.
Display Action
Day temperature
Night temperature
This thermostat can operate on a programmable schedule in order to automatically lower the room temperature setting. Options include:
Turning off the schedule (OFF)
• Operate a schedule that applies only to this thermostat zone (ZONE)
• The ability to operate one of the four system-wide schedules as a master
• (Schedule Master 1 through 4*)
Join one of the four system-wide schedules as a member (Schedule Member
• 1 though 4*)
*Requires the thermostat to be connected to a tekmarNet® system. Once the type of schedule has been selected, the thermostat can support schedules
that have either:
2 events per day
• 4 events per day
Schedules with four events per day are common for residential use while two events per day are common for commercial installations.
The schedules can be repeated every:
24 hours
• 7 days (week)
A 7 day schedule allows a unique time to be set to change the temperature for each day of the week.
The schedule also includes a “SKIP” option that allows the programmable schedule to skip a temperature change and remain at the previous temperature setting. The “SKIP” setting can be found between 11:50 PM (23:50 hours) and 12:00 AM (0:00 hours).
When a programmable schedule is selected, there is a time delay for the room to warm up or cool down from the temperature to the temperature. The thermostat has the option to use Optimum Start to predict the heat up or cool down rate of the room. When Optimum Start is set to On, the heating or cooling is started in advance to allow the room to reach the Set Room temperature at the time set in the programmable schedule.
A Watts Water Technologies Company
43 of 52
© 2014 557_D - 09/14
Page 44
Scenes (System Override)
-----------------------------------------------------------
---------------------------------------------------
Section K
Scenes provide an easy way to save energy while away on vacation, or override a programmable schedule when plans change.
Away Key
-----------------------------------------------------------
This thermostat includes an Away Key to quickly turn down the heating temperatures and increasing the cooling temperatures on all thermostats and suspend heating the domestic hot water tank to maximize energy savings. To enable, go the Scene menu and set Away Key to on.
To activate the Away scene, touch “Going Away” on the screen.
Select PERM (permanent) or a number of days using
• the or arrow. Range is 1 to 180 days.
Press the home button to accept the setting or leave
• the screen untouched for several seconds.
“Scene Away” is displayed on the home screen until
• the number of days expires.
Touch “Cancel Away” to cancel at any time.
The temperature is not adjustable while the thermostat is in Away.
Additional Scenes
---------------------------------------------------
Additional energy saving scenes are available when a User Switch or Gateway is installed. A complete listing of each scene is shown below.
Scene
Number
1
2 3 4
5
6
7
8
Scenes = None Operation
Permanent or Schedule
Scene 1 Away Away Away Scene 1 Scene 1 Scene 1Scene 1Configurable
Scene 1 Scene 1
Scene 1 Scene 1
Scene 1 Scene 1
Scene 1 Scene 1
Scenes = Away Operation
Permanent or Schedule
Scenes = All Operation
Permanent or Schedule
Permanent Permanent
Permanent or Schedule
Temporary 3 Hours
Temporary 4 Hours
Temporary 8 Hours
Scenes = Guest Operation
Permanent
Permanent Permanent
or Schedule
Permanent
Permanent
Permanent
A Watts Water Technologies Company
44 of 52
© 2014 557_D - 09/14
Page 45
Recommendation on How to Use Scenes
-----------------------------
Choosing how to use scenes depends on the needs and lifestyle of the customer using the building.
-----------------------------
Multi-Tenant Apartments
Scenes should be disabled (None) in multi-tenant buildings where each occupant has differing heating requirements.
Residential Homes
Some residential customers may not require scenes, in which case, scenes can be disabled (None). Home owners that wish to save on energy costs should consider using the Away scene to save energy while away from the property (example: vacation or holidays).
The use of the Guest scene is useful in residential applications where there are a number of spare bedrooms that are occupied on an infrequent basis. Each spare bedroom would be setup to operate on the Guest scene. The remaining thermostats can be setup to operate on the None, Away or All scene configuration. Normally, the spare bedrooms would operate at the moon temperature settings. When guests arrive, scene 5 can be activated through the use a User Switch or Gateway. The spare bedroom then operates at the temperature settings or operates on a programmable schedule if a schedule has been setup. When guests depart, the scene can be changed back to scene 1 and the spare bedrooms resume operation at the temperature settings.
Commercial Buildings
Commercial buildings are typically in use on a predictable schedule and normally the building can operate in scene 1. In order to accommodate staff working overtime or cleaning staff, a 3 or 8 hour temporary override is available when installed in conjunction with a User Switch or Gateway. In these cases, the thermostats should be setup to use the All scene configuration. At the touch of a button, the whole building changes from operating on a programmable schedule (typically at the temperature setting when not occupied) to operating at the temperature settings for 3 hours (scene 6) or 8 hours (scene 8). After the timer counts down and expires, the scene changes back to the previous scene.
Secondary Temperature Display
Section L
This thermostat can display the outdoor, floor, relative humidity, or the room heating and cooling temperature settings in the smaller number area at the top right of the screen. To toggle the item currently displayed, touch the secondary temperature.
Display of the floor or outdoor temperature requires a connection to an outdoor or floor temperature sensor, or the thermostat is connected to a tekmarNet® system that includes an outdoor sensor. The reading of the outdoor sensor connected directly to the thermostat takes precedence over any outdoor sensor reading available on the tekmarNet® system.
or or or
A Watts Water Technologies Company
45 of 52
© 2014 557_D - 09/14
Page 46
Access Levels
The thermostat Toolbox menu supports four access levels: Installer (INST), User (USER), Limited (LTD), and Secure (SEC). The access level can be adjusted when the thermostat is unlocked. There are two locations to lock the thermostat:
1. Locally on the thermostat using the Lock switch located in the wiring area.
®
2. Globally on the tekmarNet
installed)
Both the local and global lock settings must be set to unlock before the thermostat access level is adjustable.
The selection of the access level is dependent on the use of the building and the type of occupants.
Installer - Suitable for HVAC installers only. Times out to User access level after 24 hours.
User - Suitable for most residential homeowners. Limited - Suitable for rental properties or commercial buildings where some level of
temperature adjustment is required. Secure - Suitable for schools, churches, and other public buildings where temperature
adjustment is not desired.
system control using the Lock switch or Access level (if
Section M
tekmarNet® Address
When connected to a tekmarNet® system, each thermostat will be automatically given an address. The address is useful as a troubleshooting tool to locate thermostats with errors and also allows room naming on a Gateway.
The address consists of the bus water temperature followed by the thermostat device number. Available buses are b (boiler), 1, 2 and 3. Device numbers range from 01 to
24. If the thermostat is used without a tekmarNet® system control, the bus number is
not shown. When using the thermostat together with a Gateway, it is important that each address
be changed to be manually set. This allows each thermostat to be named on the Gateway.
If two thermostats are manually set to the same address, an error message will appear. The error remains until one of the addresses is manually changed to a vacant address or to Auto.
It is highly recommended to keep a documented list of thermostat addresses. This is extremely helpful when troubleshooting errors. The tekmarNet® system control will display the addresses of thermostats that have errors. By referring to the address documentation, it simplifies the process to locate and correct error messages.
Cleaning the Thermostat
Entering the Screen Clean menu allows 30 seconds to clean the thermostat and display with a moist cloth. Do not use solvents to clean the thermostat.
Section N
Section O
A Watts Water Technologies Company
46 of 52
© 2014 557_D - 09/14
Page 47
Troubleshooting
Error Messages (1 of 5)
Error Message Description
SETUP MENU SAVE ERROR
The thermostat failed to read the Setup menu settings from memory and has reloaded the factory default settings. The thermostat stops normal operation until all settings in the Setup menu are checked except to provide freeze protection. To clear the error, set the access level to Installer and check all settings in the Setup menu.
SET TEMP MENU SAVE ERROR
The thermostat failed to read the Set Temp menu settings from memory and has reloaded the factory default settings. The thermostat stops normal operation until all settings in the Set Temp menu are checked except to provide freeze protection. To clear the error, set the access level to Installer and check all settings in the Set Temp menu.
MONITOR MENU SAVE ERROR
The thermostat failed to read the Monitor menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error. To clear the error, set the access level to Installer and check all settings in the Monitor menu.
SCHEDULE MENU SAVE ERROR
The thermostat failed to read the Schedule menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error. To clear the error, set the access level to Installer and check all settings in the Schedule menu.
TOOLBOX MENU SAVE ERROR
The thermostat failed to read the Toolbox menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error. To clear the error, set the access level to Installer and check all settings in the Toolbox menu.
TIME MENU SAVE ERROR
The thermostat failed to read the Time menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error. To clear the error, set the access level to Installer and check all settings in the Time menu.
SCENES MENU SAVE ERROR
The thermostat failed to read the Scenes menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error. To clear the error, set the access level to Installer and check all settings in the Scenes menu.
A Watts Water Technologies Company
47 of 52
© 2014 557_D - 09/14
Page 48
Error Messages (2 of 5)
Error Message Description
DISPLAY MENU SAVE ERROR
The thermostat failed to read the Display menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error.
To clear the error, set the access level to Installer and check all settings in the Display menu.
tN2 PORT ERROR
The thermostat has been connected to a tN2 zone already in use by a 2-stage zoning control. A 2-stage device requires two tN2 ports to operate. This device may be connected to one such port.
To clear the error, move the thermostat’s tN2 wires to an unused tN2 port on the zoning control.
NO SENSOR ON ERROR
All of the temperature sensors have been set to Off including the built-in room sensor.
To clear the error, the Room Sensor, Sensor 1, 2 or 3 must be set to measure an air or floor temperature.
W2 SOURCE BUS CONFIGURATION ERROR
The backup W2 heat source has been changed on the tekmarNet® System Control. To clear the error, check the Backup W2 Source setting in the Setup menu.
tekmarNet® COMMUNICATION ERROR
The tekmarNet® communication bus has either an open or a short circuit. The result is that there are no communications. Check for loose wires between tN4 and C. Check for short circuits between the tN4 and C wires on the House Control, Wiring Center, or Zone Manager. Check for correct polarity between the C and R wires.
The error clears automatically once the wiring fault has been corrected.
To force the error to clear while allowing a short or open circuit to continue, touch the Cancel key.
ADDRESS ERROR
Two thermostats have been manually set to the same address. The thermostat continues to operate with this error but does not communicate
with the tekmarNet® system. To clear this error, select an unused tekmarNet® address or select
automatic addressing.
DEVICE LIMIT
More than 24 devices (thermostats or setpoint controls) have been connected to the tekmarNet® communication bus. To clear the error,
remove and relocate devices to other available buses until the device count is 24 or less.
A Watts Water Technologies Company
48 of 52
© 2014 557_D - 09/14
Page 49
Error Messages (3 of 5)
Error Message Description
ROOM SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the thermostat is unable to read the built-in room temperature sensor. If Sensor 1, 2 or 3 is set to Room, or the thermostat
is connected to a tekmarNet® system control, the thermostat continues to operate, otherwise operation stops.
The error cannot be field repaired. Contact your tekmar® sales representative for repair procedures.
ROOM SENSOR OPEN CIRCUIT ERROR
Due to an open circuit, the thermostat is unable to read the built-in room temperature sensor. If Sensor 1, 2 or 3 is set to Room, or the
thermostat is connected to a tekmarNet® system control, the thermostat continues to operate, otherwise operation stops.
The error cannot be field repaired. Contact your tekmar® sales representative for repair procedures.
LOCAL HUMIDITY SENSOR ERROR
The built-in humidity sensor is faulty. The error cannot be field repaired. Contact your tekmar® sales representative for repair procedures.
EXTERNAL HUMIDITY SENSOR ERROR
The external humidity sensor is faulty. Check the external sensor wiring terminations and troubleshoot using the data brochure 086_D. The error will self clear when the humidity sensor is reading correctly. If the external humidity sensor has been intentionally removed, set the Sensor 3 setting in the Setup menu to Off.
SENSOR 1, 2 OR 3 SHORT CIRCUIT ERROR
Due to a short circuit, the thermostat is unable to read auxiliary Sensor 1, 2 or 3. The thermostat stops normal operation if the Sensor is the only active Room or Floor sensor or if a Floor Maximum temperature has been set.
Check the auxiliary sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the auxiliary sensor. Once the error has been corrected, the error message automatically clears.
SENSOR 1, 2 OR 3 OPEN CIRCUIT ERROR
Due to an open circuit, the thermostat is unable to read auxiliary Sensor 1, 2 or 3. The thermostat stops normal operation if the Sensor is the only active Room or Floor sensor or if a Floor Maximum temperature has been set.
Check the auxiliary sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the auxiliary sensor. Once the error has been corrected, the error message automatically clears.
If the auxiliary sensor has been intentionally removed, set the applicable Sensor 1, 2 or 3 setting in the Setup menu to Off.
A Watts Water Technologies Company
49 of 52
© 2014 557_D - 09/14
Page 50
Error Messages (4 of 5)
Error Message Description
SYSTEM CONTROL LOST ERROR
The thermostat can no longer communicate to the tekmarNet® system control. Check for open or short circuits in the tekmarNet® communication wiring. The error automatically clears once the tekmarNet® system
control has been detected. If the tekmarNet
system, remove and then re-apply power to the thermostat to clear the error.
NEED DUCT SENSOR ERROR
The dehumidifier mode has be configured to be DHUM2 or DHUM3. These modes require a duct sensor in order to function and no duct sensor has been detected. To clear the error message, either change the dehumidification mode or install a duct sensor to Sensor 1.
AIR GROUP MASTER ERROR
Two thermostats have been assigned to be the master of the same air group (cool group) number.
To clear the error, go to the Setup menu and either select a different air group master number or set the air group master to None.
SCHEDULE MASTER ERROR
Two thermostats on the tekmarNet® system have been set to the same Schedule Master number. The thermostat operates at the
temperature settings while this error is present.
To clear the error, select a different Schedule Master number, set a different Schedule Member number, set the Schedule to Zone, or set the Schedule to None.
SCHEDULE MEMBER ERROR
The thermostat can not longer detect its schedule master. The thermostat operates at the
error is present. To clear the error,
the Schedule to Zone, or set the Schedule to None.
CHANGE FILTER
The air filter requires cleaning or replacement. Once this has been completed touch the Cancel key in the Toolbox menu. Alternatively, go to the Monitor menu and clear the Filter Hours by touching the number and then touch the ENTER key.
®
system control was intentionally removed from the
temperature settings while this
select a different Schedule Member number, set
FREEZE PROTECTION WARNING
The duct temperature has dropped below 45°F (7.0°C). The second stage cooling will be forced off at 40°F (4.5°C) and the first stage cooling will be forced off at 35°F (1.5°C). The warning message self clears once the duct temperature exceeds 45°F (7.0°C).
A Watts Water Technologies Company
50 of 52
© 2014 557_D - 09/14
Page 51
Error Messages (5 of 5)
Error Message Description
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this thermostat. 01 to 24 = Thermostat only network Go to the thermostat with the listed address to correct the error.
ERROR AT THERMOSTAT
There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this thermostat. b:01 to b:24 = boiler bus 1:01 to 1:24 = bus 1 or mix1 bus 2:01 to 2:24 = bus 2 or mix2 bus 3:01 to 3:24 = bus 3 or mix 3 bus Go to the thermostat with the listed address to correct the error.
ERROR AT SYSTEM CONTROL
There is an error on the tekmarNet® system control connected to the tekmarNet® system and not on this thermostat.
Technical Data
tekmarNet® Thermostat 557; Radiant Floor, 2 Heat Pump/Cool, Backup, Humidity
Literature 557_A, 557_C, 557_D, 557_Q, 557_U Control Microprocessor control. This is not a safety (limit) control Packaged weight 0.9 lb. (400 g) Dimensions 4-1/2" H x 4-3/4" W x 7/8" D (114 x 120 x 22 mm) Enclosure White PVC plastic, NEMA Type 1 Approvals Meets Class B: ICES & FCC Part 15 Ambient conditions
Environmental
Power supply 24 V ±10%, 60 Hz, 2.0 VA standby, NEC / CEC Class 2 Relays 24 V (ac) 2 A 0-10 V (dc) Output 3.3 V (dc) humidity sensor power, 3.0 mA maximum Humidity sensor 0 to 90% ± 3% RH Temperature sensor – Included None – Optional tekmar type # 070, 072, 073, 076, 077, 079, 083, 084, 086
Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing Compatible with chlorinated swimming pool environments. Do not use
in presence of ammonia (animal barns), methanol, ethanol, acetone.
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
A Watts Water Technologies Company
51 of 52
© 2014 557_D - 09/14
Page 52
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt
of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass­through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass­through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the war­ranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defec­tive Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Pur­chaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or att achment s made subsequen t to purchase which have not been au thorized by tekmar; or if t he Prod ­uct was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOV­ERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABIL­ITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMEN­TAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CON­TRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materi­als must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: www.watts.com/prop65
Product design, software and literature are Copyright ©2014 by tekmar Control Systems Ltd., A Watts Water Technologies Company. Head Offi ce: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650
All specifications are subject to change without notice
52 of 52 557_D - 09/14.
Web Site
: www.tekmarControls.com
Loading...