The tekmar 10K Temperature Simulator 002 can be used to test any tekmar control using 10K thermistor
sensors. With this simulator, checking control operation on a counter or in a boiler room is a simple process.
The simulator is also ideal for use at trade shows or product training schools to demonstrate the features and
operation of various tekmar controls. Up to three different sensors can be individually simulated using the
three separate rotary switches. The simulator is designed to provide sensor resistance values for a 10kΩ
@ 77°F (25°C ± 0.2°C), ß=3892,
NTC thermistor. Other controls
that use thermistor sensors with
a different resistance curve can-
not be tested correctly with this
simulator. (This includes all older
tekmar controls with 2K sensor
inputs.)
Sequence of Operation
After connecting up the simulator and applying power to
the control being tested, simulation can begin. Using the
data brochure for the control being tested, select temperatures from the simulator to verify the operation of the
control.
As an example, Figure 3 shows a One Stage Boiler
Control 250 being tested. The following are typical
features you can test with the simulator — WWSD, Boiler
Minimum, Boiler Differential and Heating Curve. Some
calculations may be required to determine if correct control operation is taking place.
Note: Understanding the operation of the control
being tested is required to ensure correct conclusions are made. Do not apply power to the simulator
as damage to the simulator may result.
Temperature #2
Selector (Yellow)
Wiring for Temperature
Dial #2 (Yellow)
Temperature #1
Selector (Red)
10K Temperature
Simulator 002
140
130
110
°F
80
95
230
Do not apply power to any terminals
40
35
32
27
45
55
65
70
75
85
°F
Wiring for Temperature
Dial #1 (Red)
09/94
Date
S/N
150
170
190
210
32
50
10
-10
-45
-40
60
70
80
90
Temperature #3
Selector (Blue)
Wiring for Temperature
Dial #3 (Blue)
Installation
Blue Dial (Wiring)
The blue dial temperature settings have been selected to be representative of outdoor air temperatures. The two blue wires running from
the simulator are typically connected to the input terminals of the
outdoor sensor of a tekmar control (see figure 3).
Red Dial (Wiring)
The red dial temperature settings have been selected to be representative of boiler supply temperatures. The two red wires running
from the simulator are typically connected to the input terminals of the
supply sensor of a tekmar control (see figure 3).
Yellow Dial (Wiring)
The yellow dial temperature settings have been selected to be
representative of indoor feedback readings. The two yellow wires
running from the simulator are typically connected to the 10K Sen
input terminals of a tekmar control.
In North America: tekmar Control Systems Ltd., Canada
tekmar Control Systems, Inc., U.S.A.
Head office: 4611 - 23rd Street
Vernon, B.C. Canada V1T 4K7
Tel. (604) 545-7749 Fax. (604) 545-0650
Product design and literature are Copyright © 1994 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
Using the tekmar 10K Temperature Simulator to test
the operation of a Boiler Reset control.
Date
10K Temperature
Simulator 002
110
°F
80
Do not apply power to any terminals
40
35
32
27
45
85
S/N
140
150
130
170
190
95
210
230
32
10
55
-10
65
-45
70
-40
75
90
°F
For Aux.
10K Input
(Not used in this example)
To 120 V ac
Power Source
50
60
70
80
Class II
Transformer
All specifications are subject to change without notice.
Printed in Canada on recycled paper.
H1097
Enclosed Energy
110
°F °F
50 170
Minimum
One Stage Boiler
Control 250
Power
R
LR 58223
Heating
Curve
2.0
0.4 3.6
CLASS 2 CIRCUITS ONLY; CC-CU 20 AWG or larger wire, 60°C, 30
1C2R3Ht4
Power 24V 2VA
Relay 24V 48VA
Ht
Management
Equipment
Test
R
E150539
242
Differential
UnOcc
WWSD
Minimum
Boiler On
Date
S/N
WWSD
Listed
5T62
55
UnO
Jumper
Sw
22
70
°F
85
5
6
7
Com
Sup
Out
Sen
Sen
Sen
Figure 3
8