SilentKnight SK-Control User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
J1
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118
SK-Control Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 6.5 mA (LED on) Average Operating Current: 375μA (LED flashing - in group poll mode) 350μA (LED flashing - in direct poll mode) 485μA Max. (LED flashing, NAC shorted) Maximum NAC Line Loss: 4 VDC Reg. Ext. Supply Voltage: (between Terminals T3 and T4) Maximum (NAC): Regulated 24VDC Drain on External Supply: 1.7 mA Maximum (using 24 VDC supply) Max. NAC Current Ratings: For class B wiring system, 3A; For class A wiring system, 2A Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10% to 93% Non-condensing Dimensions: 41/2˝ H x 4” W x 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.) Accessories: SMB500 Electrical Box
www.silentknight.com
I56-3436-001
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Dis­connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
SK-Control Supervised Control Modules are intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. This module is used to switch an external power supply to notification appliances. It also supervises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The SK-Control has two pairs of output termination points available for fault-tolerant wiring and a panel-controlled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible Silent Knight system control panels only (list available from Silent Knight).
MOUNTING
The SK-Control mounts directly to 4-inch square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited applications, UL requirements for the separation of power-limited and nonpower-limited terminals and wiring must be met. The barrier must be inserted into a 4˝ × 4˝ × 21/8˝ junction box, and the control module must be placed into the barrier and attached to the junction box (Figure 2A). The power-limited wiring must be placed into the isolated quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri­ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.
IMPORTANT: When using the SK-Control for fire fighter telephone applica­tions, remove Jumper (J1) and discard. The Jumper is located on the back as shown in Figure 1B.
FIGURE 1A. CONTROLS AND FIGURE 1B. JUMPER LOCATION: INDICATORS:
C1059-00 C0910-00
FIGURE 2A. MODULE MOUNTING FIGURE 2B: WITH BARRIER:
C1047-00
SK-460-005 1 I56-3436-001
FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:
(+)
(+)
(+)
(+)
(+)
(+)
47K EOL RESISTOR ELR-47K
UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT CONTROL MODULE OR END-OF-LINE RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL.
24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO
LISTED COMPATIBLE CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
CONTROL
MODULE
FROM PANEL
OR PREVIOUS
DEVICE
TO NEXT
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
(–) (–)
(–)
(–)
(–)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
MODULE POLARITIES ARE
SHOWN IN ALARM
EOL RESISTOR IS INTERNAL AT TERMINALS 8 AND 9
UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1
TO NEXT CONTROL MODULE OR END-OF-LINE RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL.
CONTROL
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL
PANELS ONLY
FROM PANEL
OR PREVIOUS
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10
& 11. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
WA RNING
FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:
C0947-00
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
SK-460-005 2 I56-3436-001 ©2009 Honeywell International Inc.