SilentKnight SK-5865-3, SK-5865-4 User Manual

Silent Knight
By Honeywell
®
5865-3 and 5865-4 Installation
Supervised Power Limited
Instructions
The 5865-3 and 5865-4 are LED Annunciators that provide you with 30 programmable LED’s (15 red, 15 yellow). 5865 connects to the panel via the SBUS.

Wiring the 5865-3 or 5865-4

Note: Installation and wiring of these devices must be
done in accordance with NFPA 72 and local ordinances.
Terminate the wiring as shown in Figure 1. See also Table 1.

Table 1: Wire Connections

Specifications

Table 2 lists the operating specifications for the 5865-3 and 5865-4.

Table 2: 5865-3 and 5865-4 Specifications

Specifications

Max. Line Resistance 50Ω Max. Alarm Current 145 mA Standby Current 35 mA Max. Voltage 24 VDC Operating Temperature 0° to 49° C

(32° to 120° F)

Indoor Use Only

5865-3 &
5
Terminals
FACP Terminals
865-4
B B A A
S+ +
S- -
Label

Figure 1: 5865-3 or 5864-4 Connection to the FACP

P/N 151088
Models 5865-3 and 5865-4 Installation Instructions
Cover Plate
5865-3
3-gang Electrical Box
Cover Plate Screw

Setting the Device Address

Refer to Figure 2 to set the DIP switches to the desired address.

2. Place the 5865-3 into the 3-gang electrical box. See Figure 3.

Figure 3: 5865-3 Mounting

3. Place cover plate over the top of the 5865-3 and align the holes. See Figure 3.

4. Insert the six cover plate screws into six screw holes on the 3-gang electrical box.

5. Screw the six cover plate screws all the way in until the cover plate fits firmly against the 5865-3 and the electrical box. Do Not over tighten.

Figure 2: Setting the Device Address

Mounting the 5865-3

The 5865-3 mounts into a standard 3-gang electrical box.
Follow these steps to mount the 5864-3:

1. Make sure that the 5865-3 is properly wired to the control panel. See Figure 1.

Mounting the 5865-4

The 5865-4 mounts into a standard 4-gang electrical box.
Use the same procedure as used for mounting the 5865-3.
Note: The 5865-4 uses 8 cover plate screws.
P/N 151088 Rev C