SilentKnight SK-5824 User Manual

5824 Serial/Parallel Printer Interface Module Installation Instructions
The 5824 Serial/Parallel Printer Interface Module (5824) connects a compatible fire alarm control panel (FACP) directly to a printer to print event history. You can also print system event logs in real time and detector status from addressable FACPs.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Specifications
Operating Voltage: 24 VDC Current (Alarm and Standby): 50 mA Max Per FACP Addressable FACPs: 8; 5208 FACP: 1 Ambient Temperature: 32°F to 120°F (0°C to 49°C) Max Wiring Distance from FACP: 6000 ft. (1829 m) Mounting: Surface Dimensions: 6”W x 7-3/4”H x 1-7/16”D
(15.2 cm W x 19.7 cm H x 3.7 cm D) Parallel Port: Ancillary Serial Port: Primary Fire Signaling
2. Remove the 5824 circuit board from the base by pushing outward on the base snap retaining tabs and lifting the circuit board out.
Figure 1: 5824 Circuit Board And Plastic Base
3. Mount the plastic base into the appropriate accessory cabinet.
4. Replace the circuit board in the plastic base.
Note: It may be necessary to connect the wiring to the circuit
board before the board is replaced into the base.
Compatibility
The 5824 is compatible with all Silent Knight addressable FACPs and with the 5208 conventional FACP.
Mounting
The 5824 comes in a plastic enclosure which must be mounted inside the annunciator or accessory cabinet.
To mount the 5824 plastic enclosure into the appropriate cabinet:
1. Remove the 5824 cover. Use a small screw driver if necessary.
P/N 151392 Rev G2
ECN: 12-207
5824 Serial/Parallel Printer Interface Module Installation Instructions
5824
Wiring to a FACP
See Table 1 and Figure 2 to terminate the wiring.
Table 1: 5824 to FAC P Conn ections
5824 Terminals FACP SBUS Terminals
BB AA S+ + S-
Figure 3: 5824 DIP Switch Settings Used to Set the ID
Number
Connecting to a Printer
Figure 2: Wiring the 5824 to the FACP
Setting DIP Switches
Each 5824 connected to a compatible FACP requires an ID number which is set using the DIP switches on the 5824 circuit board. Refer to Figure 3 to see how to position the DIP switches for the desired ID number. See the FACP installation manual for specific information on device ID assignments.
You need to provide either a pass-through 9-pin serial cable or a 25-pin-to-Centronics® parallel
cable to connect the 5824 to the printer. Using the appropriate printer cable, connect the cable to the serial or parallel port on the 5824, and then connect it to the printer.
For More Information
This document is for quick reference. For more information, refer to the FACP installation
manual.