Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s,
modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until
manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper
system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in
site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or
software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are
not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum
of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for
operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes are adequate for
all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased
susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated
or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can
damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure.
When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal
removal. fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to
avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability
depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such
a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire.
Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type
of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located
on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to
reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit
alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following written procedures supplied with each device. System
inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written
records of all inspections should be kept.
Special Characters Lists .............................................................................................................1
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
IntelliKnight 5820XL Basic Operating Instructions
5820XL-EVS Basic Operating Instructions
8
LS10061-001SK-E
Section 1
Introduction
The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets
the requirements of UL 864.
The 5820XL/EVS integrates an Emergency Voice System that meets the requirements of UL 864 and UL 2572.
1.1Overview of Basic System
The IntelliKnight 5820XL and 5820XL-EVS base system is packaged as an assembled stack of 3 circuit boards
mounted to an aluminum housing.
1.1.1Addressable Fire Alarm Control/Communicator Hardware
Features
•The IntelliKnight 5820XL and 5820XL-EVS panel has one signaling line circui t (SLC). Up to three
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) supports SK addressable
detectors and modules or SD protocol detectors and modules.
•Each SLC supports 99 SK detectors and 99 SK modules for a total of 396 SK detectors and 396 SK modules
per 5820XL/EVS or 127 SD devices for a total of 508 SD devices per 5820XL/EVS.
•6.0A of output power is available through 6 sets of terminals for notification and auxiliary applications.
Each circuit is power limited per UL 864 and can source up to 3.0A (total output power must not exceed
6.0A).
•Built-in dual phone line, digital alarm communicator/transmitter (D ACT).
•Reports events to central station by point or by zone.
•UL Listed for pre-action and deluge releasing systems.
•Dedicated Form C trouble relay and two general purpose Form C programmable relays.
•Basic system operation can be performed using a key or a user code.
•Can be used with up to twelve Model 5860s Remote Annunciators (sold separately).
•Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one control panel.
•Printing of detector status, event history, and real time event log available through the Model 5824 Serial/
•Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
•Add six Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight 5895XLs per system).
See note below.
•Add four notification/auxiliary power circuits with each 5496 Intelligent Power Module. See note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any
combination.
1.1.25820XL-EVS Emergency Voice Hardware Features
•The EVS-VCM has a built-in Digital Message Repeater.
•15 EVS messages.
•Single enclosure for system control components.
•SBUS addressable amplifier. The system can support a combination of up to four EVS-50W, EVS-125W,
EVS-INT50W or EVS-100W amplifiers for a maximum of 500 watts per system.
•On-board supervised microphone.
•5820XL/EVS can support up to four EVS-RCU's (Remote Command Units).
1-1
Model 5820XL/ 5820XL-EVS Installation ManualLS10061-001SK-E
•Up to 32 mappable speaker circuits using a combination of EVS-50W, EVS-100W, EVS-125W, EVS-
INT50W and EVS-CE4's.
•Supports 25 Vrms or 70.7 Vrms speaker circuits using EVS-50W or EVS-100W.
•Supports 25 Vrms speaker circuits using EVS-125W.
1.1.3Software Features
•Advanced smoke detector features:
Automatic drift compensation
Maintenance alert region
Point status meets calibrated smoke test requirements for NFPA 72
•“JumpStart” feature for easy programming.
•125 software zones, 250 output groups.
•Non-volatile event history stores 1000 events.
•A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal.
•Built-in synchronization appliance support for AMSECO, Faraday, Gentex
Wheelock.
®
®
, System Sensor®, and
1.2About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the 5820XL* and
5820XL/EVS**. Please let us know if the manual does not meet your needs in any way. We value your feedback!
* All references to 5820XL within this manual are applicable to the 5820XL-EVS.
** Further installation instructions for the 5820XL-EVS and accessories can be found in the EVS Series
installation manual P/N LS10062-001-SK-E.
1.2.1Terms Used in this Manual
The following terminology is used with the above mentioned control panels:
TermDescription
SLCSignaling line circuit
ModuleThe term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5820XL/
EVS panel itself and the built-in 5897 power supply. It also refers to any
(optional) 5815XL SLC expansion modules.
Input PointAn addressable sensing device, such as a smoke or heat detector or a
contact monitor device.
Input ZoneA protected area made up of input points.
Output Point
(or “Output Circuit”)
Output Group (OPG)A group of output points. Operating characteristics are common to all output
Output (or “Cadence”) PatternThe pattern that the output will use, for example, Constant, March Code,
MappingMapping is the process of specifying which outputs are activated when
EVSEmergency Voice System.
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
points in the group.
ANSI 3.41. Applies to zones and special system events. See Section 7.6.3.2
for additional information.
certain events occur in the system. Section 6.3 explains mapping in detail.
1-2
LS10061-001SK-EIntroduction
1.3Compatible Products
Table 1-1 lists the products available from Silent Knight for use with the 5820XL and 5820XL-EVS.
Table 1-1: 5820XL/EVS Compatible Products
Type of DeviceModelDescription
SK Addressable
SLC Devices
SD Addressable
SLC Devices
Other Modules
Misc.
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5815XL SLC ExpanderAllows an additional 127 SD devices or 99 SK detectors and 99 SK modules to
5824 Serial/Parallel Printer
Interface Module
5895XL Intelligent Power
Module
5496 Intelligent Power Module Provides 4 additional Notification Appliance Circuits/
5860 and 5860R Remote Fire
Alarm Annunciator
5860TG and 5860TR Trim
Ring Kit
5865-3 and 5865-4 LED
Annunciator
5880 LED I/O ModuleDriver for up to 40 LEDs. Interfaces with customized
5883 General Purpose Relay
Module
EVS-VCMVoice Control Module used with the 5820XL-EVS.
EVS-SW2424 switch expander used with the 5820XL-EVS.
EVS-50W50 watt audio amplifier.
EVS-125W125 watt audio amplifier.
EVS-100W50/100 watt Intelligent amplifier
EVS-50WBUExternal backup amplifier
EVS-CE4Provides 4 additional audio circuits for the EVS-50W or
EVS-INT50W50 watt Internal amplifier
EVS-RVMRemote Voice Microphone used with the
7860 Telephone CordRJ31X cord for connecting phone line to the 5820XL/EVS.
5660 Silent Knight Software
Suite (SKSS)
5670 Silent Knight Software
Suite (SKSS)
RBBRemote Battery Box for mounting backup batteries that are too large to fit into
be added to the system. Up to three 5815XLs per system.
Allows a printer to be attached for the system for on-site event logging, detector
status and event history reports. Two maximum per system.
Provides additional power, six Flexput™ circuits, and
two Form C relays. Max. 8 per system see Model 5895XL Installation Instructions P/N 151142.
Auxiliary power. (Up to 8 per system).
Same operation, similar appearance as on-board
annunciator. Up to 12 5860s per system. 5860 is gray;
5860R is red.
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray;
5860TR is red.
LED annunciator can display up to 30 LEDs (15 red
and 15 yellow). 5865-4 has key switches for silence
and reset, and a system trouble LED.
annunciator boards. In addition, the 5880 has eight
generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four,
5883s can be used with each 5880 module.
EVS-125W.
5820XL-EVS.
“For communication and panel programming with a Windows-based computer.
Remote access requires a modem.” (not sold by Silent Knight, see Table 1-2 for
compatible modems). Enables remote viewing of detector status and event
history.
Facility management software. For remote viewing of detector status and event
history. Remote access requires a modem (not sold by Silent Knight).
the main FACP cabinet. Dim.: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x
15.24 cm D)
5895XLs and 5496s
can be used in any
combination, up to a
total of twelve devices
on one system.
up to a total of 12
5860s on one system.
5865-3, 5865-4, and
5880 can be used in
any combination, up to
a total of eight devices
on one panel.
For use with 5820XLEVS only. Refer to the
EVS-Series
Installation Manual P/
N LS10062-001SK-E
for more information
on these accessories.
1-3
Model 5820XL/ 5820XL-EVS Installation ManualLS10061-001SK-E
The following modems have been tested by Silent Knight for compatibility with the IntelliKni ght 5820XL and
5820XL-EVS and the Silent Knight Software Suite software packages:
Table 1-2: Compatible Modems
ManufacturerModel
US Robotics28.8
LifeStyle
Motorola
MultiTechMT19321ZDX
28.8, 3400 series
Premier 33.6
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical
Support at 800-446-6444.
To order parts, contact Silent Knigh t Sal e s at 800-328-0103.
IntelliKnight
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following
the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72
manufacturer’s recommendations, state and local codes, and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by
the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke
detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are
designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm
system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For
example:
®
is a registered trademark of Silent Knight; Flexput™ is a trademark of Silent Knight
Limitations of Fire Alarm Systems
),
•Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke
detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are
located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another
level.
•The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to
alarm at various levels of smoke density. If such density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
•Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering
fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users.
For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal
operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to
falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do
1-4
LS10061-001SK-EIntroduction
not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing
with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas,
improper storage of flammable materials, etc.).
•Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their
sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to
protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are
located on the other side of closed or partially open doors. A warning device that activates on a different
floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake
may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other
appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to alert people with a
disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or
sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to
alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service
or temporarily out of service. For added protection against telephone line failure, backup radio transmission
systems are recommended.
•System components, though designed to last many years, can fail at any time. As a precautionary measure, it
is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s
recommendations.
•System components will not work without electrical power. If system batteries are not serviced or replaced
regularly, they may not provide battery backup when AC power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they
are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is
not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and
the people in their premises and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms
and areas of the house or building in accordance with the requirements and recommendations of the current
edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the
manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection
systems.
Requirements and recommendations include:
•Smoke detectors shall be installed in sleeping rooms in new construction and it is recommended that they
shall also be installed in sleeping rooms in existing construction.
1-5
Model 5820XL/ 5820XL-EVS Installation ManualLS10061-001SK-E
•It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet
long.
•It is recommended that there shall never be less then two smoke detectors per apartment or residence.
•It is recommended that smoke detectors be located in any room where an alarm control is located, or in any
room where alarm control connections to an AC source or phone lines are made. If detectors are not so
located, a fire within the room could prevent the control from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns, and/or strobes. In
residential applications, each automatic alarm initiating device when activated shall cause the operation of
an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise
levels (at least 15dB above noise) with all intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm) be located in every
bedroom and an additional notification device be located on each level of a residence.
•T o keep your fire alarm system in excellent working order, ongoing maintenance is required per the
manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter
7 of NFPA 72 shall be followed. A maintenance agreement should be arranged through the local
manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
•The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance.
As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working
properly.
1-6
LS10061-001SK-E
Section 2
Agency Listings, Approvals, and Requirements
2.1Federal Communications Commission (FCC)
1.The following information must be provided to the telephone company before the 5820XL or 5820XL-EVS
can be connected to the phone lines:
AManufacturer:Silent Knight by Honeywell
BModel Number:IntelliKnight 5820XL and
5820XL-EVS
CFCC registration number:AC6USA-23901-AL-E
Ringer equivalence:0.8B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
FService Order Code:9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside
cover of this equipment is a label that contains, among other information, a product identifier. If requested, this
information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with
the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not
provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that
is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of
devices that may be connected to the public switched telephone network. This number must not exceed 5.0.
Since this product has an REN of .8, the number of devices is limited. The REN number is embedded in the FCC
registration number as 10B.
If the 5820XL or 5820XL-EVS causes harm to the telephone network, the telephone company will notify you in
advance that the temporarily discontinuance of service may be required. But if advance notice is not practical,
the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to
file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect
the operation of the equipment. If this happens the telephone company will provide advance notice in order for
you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the 5820XL or 5820XL-EVS, for repair or warranty information, please contact
Silent Knight at 1-800-328-0103 or www.silentknight.com. If the equipment is causing harm to the telephone
network, the telephone company may request that you disconnect the 5820XL or 5820XL-EVS until the problem
has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state
tariffs. You may contact the state public utility com mission, public service commission or corporation
commission for information.
Since the 5820XL/5820XL-EVS is a commercial fire alarm panel, it must be connected upstream of all other
equipment utilizing the phone lines. If you have questions about the installation, contact your telephone company
2-1
LS10061-001SK-EAgency Listings, Approvals, and Requirements
or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
This device may not cause radio interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements. The following subsections list specific requirements for each
type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and
so on). See Section 8.7 for information on releasing operation.
1.All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2.Use the addressable smoke detectors specified in Section 5.2 (SD devices) or
Section 5.1 (SK devices) of this manual and/or conventional detectors listed in the compatibility chart. (See
Appendix A).
3.Use UL listed notification appliances compatible with the 5820XL/EVS from those specified in Appendix A
of this manual.
4.A full system checkout must be performed any time the panel is programmed.
Restricted Options:
•The loss of AC signal is defaulted to 3 hours, however the system allows settings from 0 - 30 hours. For UL
certified installations this number must be set from 1 to 3 hours.
•The system allows the use of non-latching spot type smoke detectors. This feature may not be used in
commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding
applications, and hotel/motel room applications.
•The system allows the Alarm V erification time to be set from 1 to 255 seconds. For UL certified installations
the setting must be a minimum of 60 seconds.
•Call forwarding shall not be used.
•When two count is used: detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.
•P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2Requirements for Central Station Fire Alarm Systems
1.Use both phone lines. Enable phone line monitors for both lines.
2.You must program a phone number and a test time so that the 5820XL/5820XL-EVS sends an automa ti c
daily test to the central station.
3.The AC Loss Hours option must be set from 1-3 hours.
4.The Attempts to Report option must be set for 5.
2-2
Model 5820XL/ 5820XL-EVS Installation ManualLS10061-001SK-E
2.2.3Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4Requirements for Remote Station Protected Fire Alarm
Systems
1.Do not exceed the current draw load restrictions shown in Section 3.6.
2.The AC Loss Hours option must be set from 15-30 hours.
2-3
LS10061-001SK-E
Section 3
Before You Begin Installation
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read
this section thoroughly, especially if you are installing a 5820XL/EVS panel for the first time.
3.1What’s in the Box?
The IntelliKnight 5820XL ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Two keys for user operation of the on-board annunciator (i nstaller operations require the Installer’s Code)
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
The IntelliKnight 5820XL-EVS ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Two keys for user operation of the on-board annunciator (i nstaller operations require the Installer’s Code)
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
•T en 15K ohm end-of-line resistors
• EVS-VCM Voice Control Module
•Supervised microphone
3.2Environmental Specifications
It is important to protect the IntelliKnight 5820XL/5820XL-EVS control panel from water. To prevent water
damage, the following precautions should be FOLLOWED when installing the units:
•Intended for indoor use in dry locations only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, productio n machi nery)
When selecting a location to mount the IntelliKnight 5820XL/ 5820XL-EVS control panel, the unit should be
mounted where it will NOT be exposed to: temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity exceeding 93% noncondensing.
3-1
LS10061-001SK-EBefore You Begin Installation
3.3Electrical Specifications
Table 3-1: Terminal Descriptions and Electrical Specification
power circuits
5O100 mA for initiation circuits
6X*I/O 5Flexput™ Circuits24 VDC3.0A notification and auxiliary
power circuits
7O100 mA for initiation circuits
8X*I/O 4Flexput™ Circuits24 VDC3.0A notification and auxiliary
power circuits
9O100 mA for initiation circuits
10X*I/O 3Flexput™ Circuits24 VDC3.0A notification and auxiliary
power circuits
11O100 mA for initiation circuits
12X*I/O 2Flexput™ Circuits24 VDC3.0A notification and auxiliary
13O100 mA for initiation circuits
14X*I/O 1Flexput™ Circuits24 VDC3.0A notification and auxiliary
15O100 mA for initiation circuits
16BSBUS OUTSBUS communication5 VDC100 mA0
17A
18+SBUS power24 VDC1.0 A
1920BSBUS INUsed for Class A installations0
21A
22+
2324N.C.RELAY 1General Purpose Relay 124 VDC2.5 A, resistiveN/A
25C
26N.O.
27N.C.RELAY 2General Purpose Relay 224 VDC2.5 A, resistiveN/A
28C
29N.O.
30N.C.TROUBLETrouble Relay24 VDC2.5 A, resistiveN/A
31C
32N.O.
33SC-L1
34SC+
* Regulated for NAC circuits, special applications when used for releasing or auxiliary power circuits
SLC OUT
SLC terminals32 VDC150 mA0
power circuits
power circuits
Earth Ground
Faults
0
0
0
0
0
0
3-2
Model 5820XL / 5820XL-EVS Installation ManualLS10061-001SK-E
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal # and LabelDescription
Rating
VoltageCurrent
35SC-L2
36SC+
37RingPhone Line 1 Telco RingN/A0
38TipPhone Line 1 Telco Tip
39RingPhone Line 1 Premises Ring
40TipPhone Line 1 Premises Tip
41RingPhone Line 2 Telco RingN/A0
42TipPhone Line 2 Telco Tip
43RingPhone Line 2 Premises Ring
44TipPhone Line 2 Premises Tip
45SC-SLC Programming Terminal
46SC+SLC Programming Terminal
SLC IN
Used for Class A installations0
32 VDC150 mA0
(-)
32 VDC150 mA
(+)
Earth Ground
Faults
3.4Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone
communication or cause false alarms. To avoid induced noise, follow these guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for
the entire panel. Instead, separate the wiring as follows:
High voltageAC power, Terminals 1-3
SLC loopsTerminals 33-36
Audio input/output Phone line circuits, Terminals
•Do not pull wires from different groups through the same conduit. If you must run them together, do so for
as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You
must route high and low voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it
could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed
circuits. See Figure 3-1 for an example.
•High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be
reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
3-3
LS10061-001SK-EBefore You Begin Installation
Figure 3-1 Wire Routing Example
3-4
Model 5820XL / 5820XL-EVS Installation ManualLS10061-001SK-E
Chassis
Mounting
Nuts
Chassis
Mounting
Nuts
To ACOn-board Annunciator
Key Switch
Input
Programming
Ports
3.5Board Assembly Diagram
Figure 3-2 Model 5820XL / 5820XL-EVS Assembly
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL / 5820XL-EVS
assembly to the cabinet. If you should need to remove the board assembly for repair, remove the four mounting
nuts which hold the assembly in the cabinet. Then lift the entire assembly out of the cabinet. Do not attempt to
remove the circuit boards from the metal bracket.
3-5
LS10061-001SK-EBefore You Begin Installation
3.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using SK
addressable devices (Table 3-2) or SD addressable devices (Table 3-3).
3.6.1Current Draw Worksheet Requirements
The following steps must be taken when determining 5820XL/5820XL-EVS current draw and standby battery
requirements.
1.You will use the Current Draw Worksheet to determine current draw and standby battery requirements. Use
Table 3-2 if installing SK SLC Devices and Table 3-3 if installing SD SLC Devices. For the 5820XL /
5820XL-EVS, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the
current draw requirements for alarm and standby. Record this information in the Current Draw Worksheet on
Line A.
2.Add up the current draw for all auxiliary devices and record in the table on Line B.
3.Add up the current draw for all notification appliances and record in the table on Line C.
4.For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for
the current ratings.
5.Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the 5820XL / 5820XL-EVS control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as the Silent Knight
5495 or the 5895XL intelligent power expander, to distribute the power loads so that the 5820XL / 5820XLEVS or the power expanders do not exceed their power ratings. Refer to the current draw worksheets provided with the 5495 or the 5895XL manuals so you do not exceed their power ratings.
6.Complete the remaining instructions in the appropriate Current Draw Works heet for determining battery size
requirements.
3.6.2Current Draw Worksheet for SK SLC Devices
Use to determine current requirements during alarm/battery standby operation SK
SLC devices are installed. when SD SLC devices are installed. You can install up 99 SK detectors SD per loop
(396 points max per panel) and 99 SK modules per loop (396 points max per panel). Copy this section if
additional space is required.
Table 3-2 Current Draw Worksheet for SK SLC Devices
Device# of DevicesCurrent per Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (battery current draw)1Standby: 275 mA275 mA
Alarm: 440 mA440 mA
Standby
Current
Alarm
Current
3-6
Model 5820XL / 5820XL-EVS Installation ManualLS10061-001SK-E
Table 3-2 Current Draw Worksheet for SK SLC Devices
Notification Appliance CircuitsRefer to device manual for current rating.
Total current ratings of all devices in system (line A + line B + C)mAmA
Total current ratings converted to amperes (line D x .001):AA
Number of standby hours:H
Multiply lines E and F.Total standby AHAH
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
Multiply lines E and H.Total alarm AH
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be
considered when determining auxiliary power capacity but not calculated into current requirements for day to day
operation.
5. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY
is calculated by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SKDUCT.
6. The F ACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3-9
LS10061-001SK-EBefore You Begin Installation
3.6.3Current Draw Worksheet for SD SLC Devices
Use to determine current requirements during alarm/battery standby operation when SD SLC devices are
installed. You can install up SD devices per loop (Max per panel). Copy this section if additional space is
required.
Table 3-3: Current Draw Worksheet for SD SLC Devices
5
2
2
Standby
Current
mAmA
mA
mAmA
Device# of DevicesCurrent per Device
For each device use this formula: This column X This column = Current per number of devices.
IntelliKnight 5820XL Fire Panel (Current
SD505-DTS-K(508 max.)None, included with SD505-DUCTR worst case.
SD505-DUCT(508 max.)None, included with detector current.
SLC Isolator Devices
SD500-LIM(1024 max.)
SD505-6IB(508 max.)
Accessories Modules
5815XL SLC Expander(3 max.)Standby/Alarm: 55 mAmAmA
5860 Remote Fire Alarm Annunciator.
*EVS-RCU contains one 5860 and must
be added to the calculation here.”.
5824 Serial/Parallel Printer Interface (2 max.)Standby/Alarm: 45 mAmAmA
5895XL IntelliKnight Power Expander
5496 Intelligent Power ModuleStandby/Alarm: 10 mAmAmA
5865-4 LED Annunciator
(with reset and silence switches)
5865-3 LED AnnunciatorStandby: 35 mAmA
5880 LED I/O ModuleStandby: 35 mAmA
1
(508 max.)
(508 max.)
(508 max.)
(100 max.)
(508 max.)
(508 max.)
(12 max.)
(8 max.)
(8 max.)
Standby: 275 mA275 mA
Alarm: 440 mA440 mA
1
Standby/Alarm: .55 mA
Aux. Pwr
1
SLCS t andby/Alarm: .55 mAmAmA
SLCS t andby/Alarm: .55 mAmA
1
Aux. Pwr
Aux. Pwr
1
SLCS tandby/Alarm: .55 mAmAmA
Aux. Pwr
SLCS tandby/Alarm .082 mAmAmA
Aux. Pwr
SLCS t andby/Alarm: .5 mAmAmA
Standby/Alarm .092 mA
Standby: 20 mAmA
Alarm: 25 mA
Standby/Alarm: 10 mAmAmA
Standby: 35 mAmA
Alarm: 145 mAmA
Alarm: 145 mAmA
Alarm: 200 mAmA
Standby: 8 mAmA
Alarm: 60 mAmA
Standby: 20 mAmA
Alarm: 106 mAmA
Standby: 10 mAmA
Alarm: 220 mAmA
LED: 10 mAmAmA
Standby: 1 mAmA
Alarm: 32 mAmA
Standby: 20 mA
Alarm: 62 mA
Alarm
Current
mA
mA
3-10
Model 5820XL / 5820XL-EVS Installation ManualLS10061-001SK-E
Table 3-3: Current Draw Worksheet for SD SLC Devices
Device# of DevicesCurrent per Device
5883 Relay Interface
EVS-VCM Voice Control Module
EVS-SW24 Switch Expander
EVS-50W or EVS-125W Audio Amplifier
with/without EVS-CE4
EVS-INT50W Internal Amplifier(4 max.)
Notification DevicesRefer to devices manual for number of devices and current rating.
EVS-RVM Remote Voice Module
* The EVS-RCU contains one EVS-RVM
and must be added to the calculation
here
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours:H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
3
4
(32 max.)
(1 max.)
(5 max.)
(4 max.)
(4 max.)
Standby: 0 mAmA
Alarm: 220 mA
Standby: 70 mAmA
Alarm: 100 mAmA
Standby: 10 mAmA
Alarm: 25 mAmA
Standby: 10 mAmA
Alarm: 10 mAmA
Standby: 52 mAmA
Alarm @ 25V: 275 mAmA
Alarm @ 70V: 310 mA
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120
VAC or 240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because
power is removed during that time. However, during normal operation, door holders draw current and must
be included in the 6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. The FACP can only support 2 devices w/LED’s on. This current draw has been added to the panels alarm
current.
3-11