SilentKnight SK-5808 User Manual

Page 1
INTELLIKNIGHT
MODEL 5808
Addressable Fire Control Panel
®
Installation and Operations Manual
Document 151274-L8 10/30/14 Rev:
P/N 151274-L8:V ECN: 14-0724
Page 2
Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) non­condensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes ar e adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written records of all inspections should be kept.
Page 3

Contents

Contents
Section 1
Introduction ..............................................................................................................................................1-1
1.1 Overview of Basic System ........................................................................................................1-1
1.1.1 Hardware Features ............................................................................................................1-1
1.1.2 Software Features ..............................................................................................................1-1
1.2 About this Manual .....................................................................................................................1-2
1.2.1 Terms Used in this Manual ................................................................................................1-2
1.3 Compatible Products ....................................... ... ... .... ... ... ....................................... ... ... ... .........1-3
1.4 How to Contact Silent Knight ....................................................................................................1-4
Section 2
Agency Listings, Approvals, and Requirements ...................................2-1
2.1 Federal Communications Commission (FCC) ..........................................................................2-1
2.2 Underwriters Laboratories (UL) ................................................................................................2-2
2.2.1 Requirements for All Installations ................... .... ... ... ... .... ... ... ... ... .... ... ...............................2-2
2.2.2 Requirements for Central Station Fire Alarm Systems ......................................................2-2
2.2.3 Requirements for Local Protected Fire Alarm Systems ......................... ............................2-3
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems ......... ............................ 2-3
2.2.5 Requirements for Auxiliary Protected Fire Alarm Systems for Fire Alarm Service ............2-3
Section 3
Before You Begin Installing ...............................................................................................3-1
3.1 What’s in the Box? ...................................................................................................................3-1
3.2 Environmental Specifications ....... ... ... ................................................................................. . ....3-1
3.3 Electrical Specifications ................... ... ......................................................................................3-2
3.4 Wiring Specifications ................................................................................................................3-3
3.5 Board Assembly Diagram ......................................................................................................3-4
3.6 Calculating Current Draw and Standby Battery ........................................................................3-5
3.6.1 Current Draw Worksheet Requirements ................... ......................................................... 3-5
3.6.1.1 Current Draw Worksheet for SK SLC Devices .........................................................3-5
3.6.1.2 Current Draw Worksheet for SD SLC Devices ....................................................... ..3-8
3.6.1.3 Maximum Battery Standby Load ............................................................................3-10
3.7 Installation Tasks Overview ....................................................................................................3-11
Section 4
Control Panel Installation ......................................................................................................4-1
4.1 Mounting the Control Panel Cabinet ........................................................................................4-1
4.1.1 Preventing Water Damage .................................................................................................4-1
4.1.2 Removing the 5808 Assembly from the Housing ...................... ......................................... 4-1
4.2 AC Connection ............................................. ... ... ... .... ... ... ....................................... ... ... ............4-2
1
Page 4
Contents
4.3 Battery Connection ...................................................................................................................4-2
4.3.1 RBB Accessory Cabinet .....................................................................................................4-3
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries ...............................................4-3
4.4 SBUS Wiring ...................... ... ....................................... ... ... .... ... ... ... .........................................4-5
4.4.1 Calculating Wiring distance for SBUS modules .................. ............................................... 4-5
4.4.2 Wiring Configurations .........................................................................................................4-7
4.5 5860 Remote Annunciator Installation .....................................................................................4-8
4.5.1 Mounting the 5860 .............................................................................................................4-9
4.5.1.1 Flush Mounting .......................................................................................................4-10
4.5.1.2 Surface Mounting ...................................................................................................4-12
4.5.2 Connecting the 5860 to the Panel ....................................................................................4-12
4.6 5824 Serial/Parallel Printer Interface Module
Installation ..............................................................................................................................4-12
4.6.1 Selecting 5824 Options ....................................................................................................4-13
4.7 5880 LED I/O Module .............................................................................................................4-14
4.7.1 5880 Board Layout ...........................................................................................................4-14
4.7.2 FACP Connection ............................................................................................................4-15
4.7.3 LED Wiring .......................................................................................................................4-16
4.7.4 Dry Contact Wiring ...........................................................................................................4-17
4.8 5865-3 / 5865-4 LED Annunciator Installation ........................ ................ ................ ................4-18
4.8.1 FACP Connection ............................................................................................................4-18
4.8.2 5865 Mounting .................................................................................................................4-19
4.9 Configuring Modules ..............................................................................................................4-20
4.9.1 Assigning Module IDs ......................................................................................................4-20
4.10 Telephone Connection ...........................................................................................................4-21
4.11 Notification Appliance/Auxiliary Power Circuits ......................................................................4-21
4.11.1 Conventional Notification Appliance ...............................................................................4-21
4.11.1.1 Class B Notification Wiring ....................................................................................4-21
4.11.1.2 Class A Notification Wiring ....................................................................................4-22
4.11.2 Auxiliary Power Installation .............................................................................................4-23
4.11.2.1 Door Holder Power ................................................................................................4-23
4.11.2.2 Constant Power .....................................................................................................4-24
4.11.2.3 Resettable Power ........................ ...................................... .................................... 4-24
4.11.2.4 Sounder Sync Power ............................................................................................4-24
4.12 On-Board Programmable Relays (Conventional) ...................................................................4-25
4.12.1 Trouble Relay .................................................................................................................4-25
4.12.2 Programmable Relays ....................................................................................................4-25
4.13 Remote Station Applications ..................................................................................................4-25
4.13.1 Keltron Model 3158 Installation ......................................................................................4-25
4.13.2 City Box Connection Using the 5220 Module .................................................................4-26
4.13.3 NFPA 72 Polarity Reversal .............................................................................................4-27
4.13.3.1 Using the 5220 Module .........................................................................................4-27
4.13.3.2 Using the 7644-L8 Module ....................................................................................4-28
4.13.4 Using the SD500-ARM Addressable Relay Module .......................................................4-30
4.13.5 Using a MR-201/T Control Relay From Air Products ............................... ....................... 4-31
4.13.6 Transmitter Activated by Dry Contacts ...........................................................................4-32
Section 5
SK and SD SLC Device Installation ..........................................................................5-1
5.1 List of SK SLC Devices ............................................................................................................5-1
5.2 List of SD SLC Devices ............................................................................................................5-2
2
Page 5
Contents
5.3 Maximum Number of Devices ..................................................................................................5-2
5.4 Wiring Requirements for SLC Devices ............................ ................................................ .........5-3
5.4.1 Wiring SLC in Style 4 (Class B) Configuration ....................... .......................................... ..5-3
5.4.2 Wiring SLC in Style 6 & 7 (Class A) Configuration ............................................................5-4
5.5 SK Detector Installation ............................................................................................................5-5
5.5.1 Wiring SK detectors: ..........................................................................................................5-5
5.6 Addressing SK SLC Devices ....................................................................................................5-7
5.7 SD Detector Installation ................ ... ... ....................................... ... ... ... .... ... ... ............................5-7
5.7.1 Wiring SD Detectors ..........................................................................................................5-7
5.8 Addressing SD Devices ............................................................................................................5-8
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS ...........................................................................5-8
5.8.2 SLC Devices with DIP Switches ........................................................................................5-9
Section 6
Programming Overview ...........................................................................................................6-1
6.1 JumpStart Autoprogramming ...................................................................................................6-1
6.1.1 Input Points ........................................................................................................................6-1
6.1.2 Output Points .....................................................................................................................6-1
6.1.3 Running JumpStart AutoProgramming ..............................................................................6-2
6.2 Mapping Overview ....................................................................................................................6-4
6.2.1 Input Point Mapping .................. ... ... ... .... ... ... ... .... ... ... ....................................... ... ... ... .........6-5
6.2.2 Output Circuit Mapping ......................................................................................................6-6
6.2.3 Zone Event Mapping ..........................................................................................................6-7
6.2.4 Mapping LED Points ..........................................................................................................6-9
6.3 Programming Using the 5660 Silent Knight Software Suite ................................ ...................6-10
6.4 Programming Using an Annunciator ......................................................................................6-10
6.4.1 Entering / Exiting the Programming Menu .......................................................................6-10
6.4.2 Moving through the Menus ..............................................................................................6-11
6.4.3 Selecting Options and Entering Data ...............................................................................6-11
6.4.4 Editing Keys .....................................................................................................................6-11
6.5 Programming Menu Quick Reference ....................................................................................6-12
Section 7
Programming .........................................................................................................................................7-1
7.1 UL 864 Programming Requirements ...................................... ................................................ ..7-1
7.2 Modules ................................. ............................................. ......................................................7-1
7.2.1 Edit Modules ......................................................................................................................7-2
7.2.1.1 Naming Modules ......................................................................................................7-2
7.2.1.2 Module, Wiring Class ...............................................................................................7-2
7.2.2 Adding a Module .................... ... ... ... ... .... ... ... ....................................... ... ... .... .....................7-2
7.2.3 Deleting a Module ..............................................................................................................7-3
7.2.4 View Module List ................................................................................................................7-3
7.3 Zone .........................................................................................................................................7-3
7.3.1 Edit Zone ............................................................................................................................7-3
7.3.1.1 Edit Zone Name .......................................................................................................7-4
7.3.1.2 Edit Zone Properties ................................................................................................7-4
7.3.1.3 Zone Outputs ...........................................................................................................7-6
7.3.1.4 Cadence Patterns ....................................................................................................7-8
7.3.1.5 Zone Accessory Options ..........................................................................................7-9
3
Page 6
Model 5808 Installation Manual
7.3.2 Add Zone ...........................................................................................................................7-9
7.3.3 Delete Zone .......................................................................................................................7-9
7.3.4 View Zone Points ...............................................................................................................7-9
7.4 Group .....................................................................................................................................7-10
7.4.1 Edit Group ........................................................................................................................7-10
7.4.1.1 Edit Group Name ...................................................................................................7-10
7.4.1.2 Edit Group Properties .............................................................................................7-10
7.4.2 Add Group ........................................................................................................................7-12
7.4.3 Delet e Group ... ... ... .... ... ....................................... ... ... ... ....................................... ... ..........7-12
7.4.4 View Group Points ...........................................................................................................7-13
7.4.5 Edit Output Group Templa tes ..........................................................................................7-13
7.5 Point .......................................................................................................................................7-14
7.5.1 Point Programming for the SLC ...................... .... ... ... ... .... ... ... ... ... .... ................................7-14
7.5.2 Point Programming For Internal or External Pow er Module ..................................... .... ...7-18
7.5.3 Point Programming For 5880 and 5865 Modules .................................. ... .... ... ... ... ... .... ...7-20
7.5.4 Assigning a Name to a Point ............................................................................................7-20
7.6 System Options .................................. ... ... .... ... ... ... .... ... ....................................... ... ... ... ..........7-21
7.6.1 Reporting Account ...........................................................................................................7-21
7.6.1.1 Edit Accounts .........................................................................................................7-21
7.6.1.2 Auto Test Time .......................................................................................................7-23
7.6.2 Phone Lines .....................................................................................................................7-23
7.6.2.1 Dialing Prefix ..........................................................................................................7-24
7.6.2.2 Number of Answer R ings ............. ... ... ... .... ... ... ....................................... ... ... ... .... ...7-24
7.6.2.3 Dial Option (TouchTone or Pulse) ..........................................................................7-24
7.6.2.4 Rotary Format ........................................................................................................7-25
7.6.2.5 Line Monitor ...........................................................................................................7-25
7.6.2.6 Answering Machine Bypas s ..... .... ... ... ....................................................................7-25
7.6.3 Sys tem Event Outputs ........................... ... ... ... .... ...................................... .... ... ... ... ... .... ...7-25
7.6.3.1 Trouble Events .......................................................................................................7-25
7.6.3.2 System Alarm Cadence ............... ... ... ....................................................................7-26
7.6.4 Time Options ....................................................................................................................7-27
7.6.4.1 Water Flow Delay ...................................................................................................7-27
7.6.4.2 Alarm Verification Time ..........................................................................................7-27
7.6.4.3 Low AC R eport Delay ......................... ... ....................................... ... .... ... ................ 7-28
7.6.4.4 Clock Display Format (AM/PM or Military) .............................................................7-28
7.6.4.5 Change AC Line Frequency ............................ ................................................ .......7-28
7.6.5 Miscellaneous Options .....................................................................................................7-28
7.6.5.1 Synchronize Strobes Active During Silence ...........................................................7-28
7.6.5.2 Auto Display Oldest Event .....................................................................................7-29
7.6.5.3 Report by Zone or by Point ....................................................................................7-29
7.6.5.4 Plex Door Option ....................................................................................................7-29
7.6.5.5 Single Key Acknowledge .......................................................................................7-29
7.6.6 Daylight Savings ..............................................................................................................7-29
7.6.6.1 Automatic Daylight Saving Time Adjustment .................................. .... ... ... .............7-29
7.6.6.2 Daylight Saving Time Start and End ......................................................................7-30
7.6.7 Edit Banner Message .......................................................................................................7-30
7.6.8 SLC Family ......................................................................................................................7-31
7.7 JumpStart Autoprogramming .................................................................................................7-32
7.8 Computer Account ..................................................................................................................7-32
7.9 Access Codes ........................................................................................................................7-32
7.9.1 Profile Edit Menu ..............................................................................................................7-33
7.9.1.1 Edit Name ..............................................................................................................7-34
7.9.1.2 Edit Access Code ...................................................................................................7-34
7.9.1.3 Panel Functions .....................................................................................................7-34
4
Page 7
Contents
Section 8
System Operation ............................................................................................................................8-1
8.1 Default User and Installer Codes .............................................................................................8-1
8.2 Annunciator Description ...........................................................................................................8-1
8.2.1 LCD Displays .....................................................................................................................8-2
8.2.2 Banner ...............................................................................................................................8-2
8.3 Key Operation ..........................................................................................................................8-2
8.4 Menu System .............. .... ...................................... .... ... ... ....................................... ... ... ............8-3
8.4.1 Main Menu Overview .........................................................................................................8-3
8.4.2 Using the Menus ................................................................................................................8-4
8.5 Basic Operation ........................................................................................................................8-4
8.5.1 Setting Time and Date .......................................................................................................8-4
8.5.2 Disable / Enable NACs by Group .......................................................................................8-4
8.5.3 Disable / Enable a Template ..............................................................................................8-4
8.5.4 Disable / Enable a Zone .....................................................................................................8-4
8.5.5 Disable / Enable a Point .....................................................................................................8-4
8.5.6 View Event History .............................................................................................................8-5
8.5.7 Clear Event History ............................................................................................................8-5
8.5.8 Conduct a Fire Drill ............................ .... ... ... ... .... ... ....................................... ... ... ... ... .........8-5
8.5.9 Conduct an Indicator Test ..................................................................................................8-5
8.5.10 Conduct a Walk Test ........................................................................................................8-6
8.5.11 Conduct a Dialer Test .......................................................................................................8-6
8.5.12 Silence Alarms or Troubles ..............................................................................................8-6
8.5.13 Reset Alarms ....................................................................................................................8-6
8.5.14 Check Detector Sensitivity Through Point Status .... ....................................................... ..8-7
8.5.15 View Status of a Point ......................................................................................................8-8
8.5.16 View Alarms, Supervisories or Troubles ...........................................................................8-8
8.5.17 View System Information ..................................................................................................8-8
8.5.18 Reset Items ......................................................................................................................8-8
8.5.18.1 Reset Dialer ............................................................................................................8-8
8.5.18.2 Reset DSP USB .....................................................................................................8-8
8.5.19 Communicating with a Remote Computer ........................................................................8-8
8.5.20 Working with a Printer ......................................................................................................8-9
8.6 Operation Mode Behavior ..................... ... .... ... ... ... .... ... ... ... ....................................................8-10
8.7 Releasing Operations ............................ ... .... ...................................... .... ... ... ... .... ... ................8-15
8.7.1 Single Interlock Zone Releasing ......................................................................................8-16
8.7.2 Double Interlock Zone Releasing . ... ... .... ...................................... .... ... ... ... .... ... ... ... ... .... ...8-17
8.8 Smoke Alarm Verification .......................................................................... ... ... .... ... ... ... ... .......8-18
Section 9
Reporting .....................................................................................................................................................9-1
9.1 Receivers Compatible with the Control Panel .................................... .... ... ... ... .... ... ... ... ............9-1
9.2 Reporting Formats Table ..........................................................................................................9-1
Section 10
Testing and Troubleshooting .........................................................................................10-1
10.1 Troubleshooting ........................................ ................. ................... ................ ..........................10-1
5
Page 8
Model 5808 Installation Manual
10.2 Common Problems .......................... ... ... ... .... ... ....................................... ... ... ... .... ... ... ... ... .......10-1
10.2.1 Periodic Testing and Maintenance .................................................................................10-2
10.2.2 Event History ..................................................................................................................10-3
10.3 Built-in Troubleshooting and Testing Tools ............................................................................10-3
10.3.1 SLC Device Locator ....................... .......................... .......................... .............................10-3
10.3.2 SLC Multi Locator ...........................................................................................................10-3
10.3.3 I/O Point Control .............................................................................................................10-4
10.4 Impedances that Cause Earth Ground Faults ....... .... ... ... ... .... ... ... ... ... .... ................................10-5
Section 11
Installation Records .................................................................................................................... 11-1
11.1 SLC Device Point Record .......................................................................................................11-1
Appendix A
Compatible Devices ..................................................................................................................... A-1
Appendix B
Special Characters Lists .........................................................................................................B-1
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability
Model 5808 Basic Operating Instructions
6
Page 9
151274-L8

Section 1 Introduction

The 5808 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 864.

1.1 Overview of Basic System

The 5808 base system is an addressable system with a built-in annunciator that can also be used to program the system.

1.1.1 Hardware Features

The 5808 has one signaling line circuit (SLC) that supports 99 SK detectors and 99 SK modules or 127 SD
protocol devices.
6.0A of output power is available through 4 sets of terminals for notification appliance circuits or aux iliary
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total output power for all 4 circuits must not exceed 6.0A).
Built-in dual phone line, digital alarm communicator/transmitter (D ACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Two general purpose Form C program mab le relays.
One Form C Trouble Relay.
Basic system operation can be performed using a key or a user code.
Can be used with up to 12 Model 5860 Remote Annunciators (sold separately).
Can be used with Model 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one
control panel. See Sections 4.7 and 4.8 for additional information on these models.
Printing of detector status, event history, and real time event log available through the Model 5824 serial/
parallel printer interface module (sold separately).
125 software zones, 125 output groups.
Add four notification/auxiliary power circuits with each 5496 Intelligent Power Module (u p to 8 per
system).

1.1.2 Software Features

Advanced smoke detector features:
–Automatic drift compensation –Maintenance alert region –Point status meets calibrated smoke test requirements for NFPA 72
“JumpStart” feature for easy programming
Non-volatile event history stores 1000 events
A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal
Built-in synchronization appliance support for AMSECO, Faraday, Gentex
®
Wheelock
.
1-1
®
, System Sensor®, and
Page 10
IntelliKnight 5808 Installation Manual 151274-L8

1.2 About this Manual

This manual is intended to be a complete reference for all installation and operation tasks for the 5808. Please let us know if the manual does not meet your needs in any way. We value your feedback!

1.2.1 Terms Used in this Manual

The following terminology is used with the 5808 system:
Table 1-1 Manual Terminology
Term Description
SLC Signaling Line Circuit Module The term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5808 panel itself.
Input Point An addressable sensing device, such as a smoke or heat detector or a
contact monitor device. Input Zone A protected area made up of input points. Output Point
(or Output Circuit) Group (or “Output Group”) A group of output points. Operating characteristics are common to all
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code,
Mapping Mapping is the process of specifying which outputs are activated when
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
output points in the group.
ANSI 3.41. Applies to zones and special system events. See Section
7.6.3.2 for additional information.
certain events occur in the system. Section 6.2 explains mapping in detail.
1-2
Page 11
Introduction 151274-L8

1.3 Compatible Products

The chart below lists the products available from Silent Knight for use with the 5808.
Table 1-2 5808 Compatible Products
Ty pe of
Device
SK
Addressable
SLC Devices
SD
Addressable
SLC Devices
Other
Modules
Software
Misc.
Model Description
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5824 Serial/Parallel Printer Interface Module
5496 Intelligent Power Module Add 4 Notification/Auxiliary power circuits with
5860 and 5860R Remote Fire Alarm Annunciator
5860TG and 5860TR Trim Ring Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray;
5865-3 and 5865-4 LED Annunciator
5880 LED I/O Module Driver for up to 40 LEDs. Interfaces with
5883 General Purpose Relay Module
5660 Silent Knight Software Suite (SKSS)
5670 Silent Knight Software Suite (SKSS)
7860 Telephone Cord RJ31X cord for connecting phone line to the 5808. RBB Remote Battery Box for mounting backup batteries that are too large to fit into
Allows a printer to be attached for the system for on-site event logging, detector status and event history reports. Two maximum per system.
5496s can be used in any each 5496 Intelligent Power Module (up to 8, 5496s per system).
Same operation, similar appearance as on-board annunciator. Up to 12 5860s per system. 5860 is gray; 5860R is red.
5860TR is red. LED annunciator can display up to 30 LEDs (15
red and 15 yellow). 5865-4 has key switches for silence and reset, and a system trouble LED.
customized annunciator boards. In addition the 5880 has eight generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be used with each 5880 module.
Facility management software. For communication and panel programming with a Windows-based computer and *modem (not sold by Silent Knight, see Table 1-3 for compatible modems). Enables remote viewing of detector status and event history. For remote viewing of detector status and event history. Requires a modem (not sold by Silent Knight).
the main control panel cabinet. Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
combination, up to a total of
12 devices on one panel.
5865-3, 5865-4, and 5880
can be used in any
combination, up to a total of
eight devices on one panel.
Note: 5865-3, 5865-4, and 5880 can be used in any combination, up to a total of eight devices on one panel.
1-3
Page 12
IntelliKnight 5808 Installation Manual 151274-L8
The following modems have been tested by Silent Knight for compatibility with the 5808 and the Silent Knight Software Suite software packages:
Table 1-3: Compatible Modems
Manufacturer Model
US Robotics 28.8
LifeStyle
Motorola
MultiTech MT19321ZDX
28.8, 3400 series Premier 33.6

1.4 How to Contact Silent Knight

If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 80 0-328-0103.
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72 manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
),
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are
located. Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to
1-4
Page 13
Introduction 151274-L8
falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
Please note that: i) Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly, they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems in­cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
1-5
Page 14
IntelliKnight 5808 Installation Manual 151274-L8
Smoke Detectors shall be installed in sleeping rooms in new construction and it is recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per apartment or residence.
It is recommended that smoke detectors be located in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire.
All fire alarm systems require notification devices, including sirens, bells, horns, and/or strobes. In residential applications, each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels (at least 15dB above noise) with all intervening doors closed.
It is recommended that a smoke detector with an integral sounder (smoke alarm) be located in every bedroom and an additional notification device be located on each level of a residence.
T o keep your fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter 14 of NFPA 72, 2010 Edition shall be followed. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance. As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
1-6
Page 15
151274-L8

Section 2 Agency Listings, Approvals, and Requirements

2.1 Federal Communications Commission (FCC)

The following information must be provided to the telephone company before the 5808 can be connected to the phone lines:
A Manufacturer: Silent Knight by Honeywell B Model Number: 5808 C FCC registration number: AC6 USA-34758-AL-E
Ringer equivalence: 0.8B D Type of jack: RJ31X E Facility Interface Codes: Loop Start: 02LS2 F Service Order Code: 9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is a label that contains, among other information, a product identifier. If requested, this information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of .8, the number of devices is limited. The REN number is embedded in the FCC registration number as 0.8B.
If the 5808 causes harm to the telephone network, the telephone company will notify you in advance that the temporarily discontinuance of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the 5808, for repair or warranty information, please contact Silent Knight technical support at 800-446-6444 or www.silentknight.com. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the 5808 until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service. This equipment is not designed for use with party line service. Connection to party line service is subject to state
tariffs. You may contact the state public utility commission, public service commission or corporation commission for information.
Since the 5808 is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone lines. If you have questions about the installation, contact your telephone company or a qualified
2-1
Page 16
Agency Listings, Approvals, and Requirements 151274-L8
installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.

2.2 Underwriters Laboratories (UL)

2.2.1 Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 5of this manual and or conventional detectors listed in the compatibility chart. (See Appendix A.)
3. Use UL listed notification appliances compatible with the 5808from those specified in the Appendix A at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm V erification time to be set from 1 to 255 seconds. For UL certified installations the setting must be a minimum of 60 seconds.
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
P.A.S feature shall be used only with automatic detectors.

2.2.2 Requirements for Central Station Fire Alarm Systems

Minimum system requirements are one Silent Knight addressable initiating device.
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5808 sends an automatic daily test to the cen­tral station.
3. The AC Loss Hours option must be set from 1-3 hours.
4. The Attempts to Report option must be set for 5.
2-2
Page 17
IntelliKnight 5808 Installation Manual 151274-L8

2.2.3 Requirements for Local Protected Fire Alarm Systems

At least one UL listed supervised notification appliance must be used. Minimum system requirements are one Silent Knight addressable initiating device.
2.2.4 Requirements for Remote Station Protected Fire Alarm
Systems
Minimum system requirements are one Silent Knight addressable initiating device and either a 5220, Keltron 3158 or the built-in Digital Alarm Communicator Transmitter (DACT).
1. Do not exceed the current load restrictions shown in Section 3.6.1.3.
2. The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for Auxiliary Protected Fire Alarm Systems
for Fire Alarm Service
The Model 5220 Direct Connect module must be installed (see Section 4.13.3.1 for wiring).
2-3
Page 18
151274-L8

Section 3 Before You Begin Installing

This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5808 panel for the first time.

3.1 What’s in the Box?

The 5808 ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Two keys for user operation of the on-board annunciator (installer operations require the In staller’s Code)
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series

3.2 Environmental Specifications

It is important to protect the 5808 control panel from water. To prevent water damage, the following conditions should be FOLLOWED when installing the units:
Mount indoors in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, productio n machi nery)
When selecting a location to mount the 5808 control panel, the unit should be mounted where it wil l NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity not exceeding 93% noncondensing.
3-1
Page 19
Before You Begin Installing 151274-L8

3.3 Electrical Specifications

Table 3-1 list the terminal block on the 5808 as well as a description of the each individual terminal and their respective electrical rating.
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal No.
Label
Description
Rating
Group Individual Voltage Current
Terminal Block 1 AC INPUT B AC input (hot) 120 VAC, 60 Hz 3.6 A
Earth Earth Ground N/A N/A W AC input (neutral) 120 VAC, 60 Hz 3.6 A
Terminal Block 2 SLC IN Used for Class A installations 32 VDC 150 mA
+
SLC OUT SLC terminals 32 VDC 150 mA
+
SLC PROG Used for programming SLC
+
Terminal Block 3 TELCO 1 RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1 RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2 RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2 RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
Terminal Block 4 TROUBLE NC Normally closed relay contact 24 VDC 2.5 A, resistive
COM Common terminal NO Normally open relay contact
RELAY 1 NC Normally closed relay contact 24 VDC 2.5 A, resistive
COM Common terminal NO Normally open relay contact
RELAY 2 NC Normally closed relay contact 24 VDC 2.5 A, resistive
COM Common terminal NO Normally open relay contact
NAC1* Notification Appliance Circuit/
+
NAC2* Notification Appliance Circuit/
+
NAC3* Notification Appliance Circuit/
+
NAC4* Notification Appliance Circuit/
+
Terminal Block 5 SBUS B SBUS Communication 5 VDC 100 mA
A + SBUS Power 24 VDC 1.0 A –
BATTERY + To Positive battery terminal 24 VDC Up to 35 Ah (see Section
To Negative battery terminal
Detectors
Auxiliary power
Auxiliary power
Auxiliary power
Auxiliary power
32 VDC 150 mA
24 VDC 3.0 Amp NAC or Aux
power
24 VDC 3.0 Amp NAC or Aux
power
24 VDC 3.0 Amp NAC or Aux
power
24 VDC 3.0 Amp NAC or Aux
power
4.3 for details)
* Regulated/special application when used for releasing.
3-2
Page 20
IntelliKnight 5808 Installation Manual 151274-L8
Relay Outputs
NAC/Aux Power Outputs
SBUS Devices
Phone Lines
SLC IN/OUT
AC Power Input
1/4” spacing must be maintained between each of these circuit types; as well as between power limited and non-power limited circuits.

3.4 Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage AC power Terminals SLC loops Audio input/output Phone line circuits Notification circuits NAC1 through NAC4 SBUS Relay circuits
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
Figure 3-1 Wire Routing Example
3-3
Page 21
Before You Begin Installing 151274-L8
On-board
Key Switch Input
Annunciator
NAC/Aux Power Circuits
Form C Relays
Phone lines
SLC In/Out
AC Power Input
SBUS Connections
Battery Connections
Programming Port
Form C Trouble Relay

3.5 Board Assembly Diagram

Figure 3-2 Model 5808 Assembly
Figure 3-2 shows the circuit boards and annunciator. If you should need to remove the control board for repair, remove the nine mounting screws (six on the circuit board and 3 on the heat-sink) which hold the control board in the cabinet. Then lift the control board out of the cabin e t.
3-4
Page 22
IntelliKnight 5808 Installation Manual 151274-L8

3.6 Calculating Current Draw and Standby Battery

This section is for helping you determine the current draw and standby battery needs if you are using SK addressable devices (Table 3-2) or SD addressable devices (Table 3-3).

3.6.1 Current Draw Worksheet Requirements

The following steps must be taken when determining 5808 current draw and standby battery requirements.
1. Use the Current Draw Worksheet to determine current draw and standby battery requirements. Use Table 3­2 if installing SK SLC Devices and Table 3-3 if installing SD SLC Devices to determine current draw. For the 5808, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of addressable devices that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in the Current Draw Worksheet on Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliance circuits and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the 5808 control panel. If the current is above 6.0 A you will need to use a notification power expander(s) such as the Silent Knight
5496 intelligent power module, to distribute the power loads so that the 5808 or the power expanders do not exceed their power rating. Refer to the current draw worksheets provided with the 5496 manual so you do not exceed their power requirements.
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for determining battery size requirements.
3.6.1.1 Current Draw Worksheet for SK SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up to 99 SK detectors and 99 SK modules. (Copy the page if additional space is required.)
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
For each device use this formula: This column X This column = Current per number of devices. Fire Panel (Current draw from
battery) Addressable SLC Detectors
of
Devices
1 Standby: 170 mA 170 mA
Alarm: 365 mA 365 mA
Current per Device
Standby
Current
Alarm
Current
3-5
Page 23
Before You Begin Installing 151274-L8
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
of
Current per Device
Devices
SK-Photo SK-Photo-T mA mA SK-Ion mA mA SK-Heat mA mA SK-Heat-HT mA mA
SK-Duct (includes PhotoR) SK-Acclimate mA mA SK-Heat-ROR mA mA SK-Beam (without integral test) SLC Standby/Alarm: 2 mA
SK-Beam-T (with integral test)
SK-FIRE-CO SLC Standby: .30 mA mA
Addressable SLC Devices SK-Monitor SK-Minimon mA mA SK-Pull-SA/SK-Pull-DA mA mA SK-Monitor-2 Standby/Alarm: .75 mA mA mA SK-Mon-10 Standby/Alarm: 3.5 mA mA mA SK-Control SLC Standby: .375 mA
SK-Control-6 SLC Standby: 2.25 mA
SK-Relay Standby/Alarm: .255 mA mA mA SK-Relay-6 Standby/Alarm: 1.45 mA mA mA SK-RelayMon-2 Standby: 1.3 mA mA
SK-Zone
SK-Zone-6
5
(99 max.)
4
(99 max.)
(99 max.)
Standby/Alarm: .30 mA
1
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA SLC Standby/Alarm: 2 mA Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
Alarm: 7.2 mA mA
Standby/Alarm: .375 mA mA mA
Alarm: .375 mA Aux.
Power
1
Aux. Pwr Standby: 8 mA
Alarm: 24 mA mA Aux Pwr Standby: 12 mA mA
SLC Standby/Alarm: .27 mA mA mA
1
Aux Pwr Standby: 50 mA mA
SLC Standby/Alarm: 2 mA mA mA
Standby: 1.7 mA mA
Alarm: 7 mA mA
Alarm: 2.25 mA
Alarm: 20 mA
Alarm: 90 mA mA
Alarm: 270 mA mA
Standby
Current
mA mA
6
mA
mA
mA
mA
mA
mA
Alarm
Current
3-6
Page 24
IntelliKnight 5808 Installation Manual 151274-L8
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
of
Current per Device
Devices
SLC Accessories
Aux Pwr Standby: .5 mA mA
B200SR Sounder Base
SLC Alarm: .7 mA Aux Pwr Standby: .5 mA mA
B200S Sounder Base
SLC Alarm: .7 mA
B200SR-LF Low Frequency Sounder Base
B200S-LF Low Frequency Sounder Base
B224RB Relay Base Standby/Alarm: .5 mA mA mA RTS151/151 KEY Alarm: 7.5 mA RA100Z Alarm: 10 mA SLC Isolator Devices SK-ISO (Isolator Module) B224BI Isolator Base Standby/Alarm: .5 mA Accessories Modules
5860 Remote Fire Alarm Annunciator (12 max) 5824 Serial / Parallel Module (2 max.) Standby/Alarm: 45 mA mA mA
5496 Notification Power Expander
(99 max.)
(100 max.)
(8 max.) Standby/Alarm: 10 mA mA mA
Aux Pwr Standby: 1 mA mA
Aux Standby .55 mA mA
SLC Standby .30 mA mA
Standby/Alarm: .45 mA mA mA
Standby: 20 mA mA Alarm: 25 mA mA
Alarm: 35 mA mA
Alarm: 35 mA mA
Alarm: 125 mA mA
Alarm (high vol) 140 mA mA
Standby
Current
mA
mA
mA mA
Alarm
Current
5895XL Intelligent Power expander (8 max.) Standby/Alarm: 10 mA mA mA 5865-4 LED Annunciator
(with reset and silence switches)
5865-3 LED Annunciator
5880 LED I/O Module
5883 Relay Interface (32 max.)
A Total System Current
Auxiliary Devices
B Auxiliary Devices Current
Notification Appliance Circuits Refer to devices manual for curre nt rating.
2
(8 max.)
Refer to devices manual for current rating.
Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 200 mA mA Standby: 0 mA mA Alarm: 220 mA
(22 mA per
relay)
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
Alarm: mA Alarm: mA
mA
mA mA
3-7
Page 25
Before You Begin Installing 151274-L8
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
of
Current per Device
Devices
Alarm: mA mA Alarm: mA
C Notification Appliances Current D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
3
Total ampere hours required AH
Standby
Current
Alarm
Current
mA mA
AH
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. This should be considered when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
5. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is calculated by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.
6. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3.6.1.2 Current Draw Worksheet for SD SLC Devices
Use Table 3-3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. (Copy the page if additional space is required.)
Device
For each device use this formula: This column X This column = Current per number of devices. 5808 Fire Panel (Current draw from
battery) Addressable SLC Devices
SD500-AIM SD500-MIM mA mA SD500-ARM mA mA SD500-PS SD505-AHS mA mA SD505-AIS mA mA SD505-APS mA mA SD500-ANM
Table 3-3: Current Draw worksheet for SD Devices
Number of
Devices
1 Standby: 170 mA 170 mA
Alarm: 365 mA 365 mA
1
(127 max.)
(127 max.)
Standby/Alarm: .55 mA
Aux. Pwr Standby: 8 mA mA
1
SLC Standby/Alarm: 55 mA mA mA
Current per Device
Alarm: 60 mA mA
Standby Current
mA mA
5
Alarm
Current
3-8
Page 26
IntelliKnight 5808 Installation Manual 151274-L8
Table 3-3: Current Draw worksheet for SD Devices
Device
SD500-LED
SD500-SDM
SLC Accessory Bases SD505-6RB (127 max.) Standby/Alarm: .082 mA mA mA SD505-6SB
SD505-DUCTR
SD505-DTS-K (127 max.) None, included with SD505-DUCTR worst case. SD505-DUCT (127 max.) SLC Standby/Alarm: .5 mA mA mA SLC Isolator Devices SD500-LIM (254 max.) Standby/Alarm: .092 mA mA mA SD505-6IB (127 max.) Accessories Modules 5860 Remote Fire Alarm
Annunciator 5824 Serial/Parallel Printer
Interface 5865-4 LED Annunciator
(with reset and silence switches) 5865-3 LED Annunciator Standby: 35 mA mA
5880 LED I/O Module Standby: 35 mA mA
5883 Relay Interface
5496 Notification Power Expander 5895XL Intelligent Power Expander Standby/Alarm: 10 mA mA mA 5865-4 LED Annunciator
(with reset and silence switches)
Number of
Devices
(40 max.)
(127 max.)
(127 max.)
(127 max.)
(12 max.)
(2 max.)
(8 max.)
(32 max.)
(8 max.) (8 max.)
1
Current per Device
Aux. Pwr Standby: 10 mA mA
Alarm: 220 mA mA
LED: 10 mA mA mA SLC Standby/Alarm: .55 mA mA mA SLC Standby/Alarm: .55 mA mA mA
1
Aux. Pwr Standby: 20 mA mA
Alarm: 106 mA mA
Aux. Pwr Standby: 1 mA mA
Alarm: 32 mA mA SLC Standby/Alarm: .082 mA mA mA Aux. Pwr
SLC Standby/Alarm: .5 mA mA mA
Standby: 20 mA mA Alarm: 65 mA mA Standby/Alarm: 45 mA mA mA
Standby: 35 mA mA Alarm: 145 mA mA
Alarm: 145 mA mA
Alarm: 200 mA mA Standby: 0 mA mA Alarm: 220 mA
Standby/Alarm: 10 mA mA mA
Standby: 35 mA mA Alarm: 145 mA mA
Standby: 20 mA
Alarm: 62 mA
(22 mA per relay)
2
mA
2
Standby Current
mA
mA
Alarm
Current
A Total System Current
Auxiliary Devices
B Auxiliary Devices Current
3
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
3-9
Page 27
Before You Begin Installing 151274-L8
Table 3-3: Current Draw worksheet for SD Devices
Device
Notification Appliance Circuits Refer to devices manual for current rating.
C Notification Appliances Current D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes =.0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
4
Number of
Devices
Current per Device
Alarm: mA Alarm: mA Alarm: mA Alarm: mA
Total ampere hours
required
Standby Current
mA mA mA mA mA
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3. If using door holders, you do not need to consider door ho lder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
Alarm
Current
3.6.1.3 Maximum Battery Standby Load
The table below shows the maximum battery standby load for the 5808 based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2 for SK devices and Table 3-3 for SD devices) must be less than the number shown in the Table 3-4 for the battery size used and standby hours required.
Table 3-4: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH 221 mA 85 mA 12 AH 475 mA 190 mA 18 AH 685 mA 270 mA 35 AH 1.1 A 450 mA
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Warning!
Silent Knight does not support the use of batteries smaller than those listed in table above. If you use a battery too small for the installation, the system could overload the battery resulting in the installation having less than the required 24 hours standby power. Use Table 3-4 to calculate the correct battery amperes/hour rating needed for your installation.
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
3-10
Page 28
IntelliKnight 5808 Installation Manual 151274-L8

3.7 Installation Tasks Overview

This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5808 system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks. Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Task
See Sec.
(for more info.)
Main Panel Hardware Installation
Mount the control panel cabinet. Connect AC. Install 5860 Remote Fire Alarm Annunciator modules if used. Install 5865 or LED Annunciator modules if used. Install 5880 LED I/O module if customized LED annunciation will be used. Connect phone lines. Install notification appliances. Install auxiliary power devices (if used). If using a printer, install the 5824 Serial/Parallel Printer Interface Module. Connect batteries (typically last step).
4.1
4.2
4.5
4.8
4.7
4.10
4.11
4.11.2
4.6
4.3
SLC Device Hardware Installation
Perform these steps before running JumpStart.
Connect device bases to the loop.
Set device addresses.
Physically connect detectors to their bases. Connect relay and contact monitor modules.
SK 5.5 SD 5.7
SK 5.6 SD 5.8
5.4 & see device install instructions
JumpStart
JumpStart is for initial system programming. JumpStart automatically selects some options for SLC devices. See “Input Point Configuration” section of this chart for other options. JumpStart makes selections for the following options. You can customize options, if necessary.
Device type (detector or switch) configured by JumpStart. To change, see 7.5 Program type of detector (heat, photoelectric, or ionization) selected by JumpStart. To change, see 7.5
6.1 & 7.7
System Software Configuration
Select low AC hours report time (3 hours by default). Select Auto Test Time (2:00 AM by default). Enable/disable automatic DST adjustment feature (enabled by default). Change clock display format (12-hour with AM/PM by default). Set up reporting accounts. Select options for phone lines. Select system-wide response to trouble conditions, if desired. Select system-wide cadence patterns for special conditions (fire drill, Aux1 and Aux2
7.6.4.3
7.6.1.2
7.6.4.4
7.6.4.4
7.6.1
7.6.2
7.6.3
7.6.3.2
alarms) if desired. Customize banner message (message that displays on LCD in normal mode) if desired.
7.6.7
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart). You can change options selected by JumpStart, if necessary and further customize input point options.
3-11
Page 29
Before You Begin Installing 151274-L8
Task
Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns all switches as Manual Pull type.)
If the installation includes duct detectors, program detector type. (JumpStart does not distinguish duct detectors from ordinary smoke detectors.)
Assign a name (or description) to the point. Assign input points to zones, if necessary. (JumpStart assigns all input points to Zone 1.)
Zone Configuration
Add the zone to the system if it does not already exist. (Zone 1 created by JumpStart.) Program a name (or description) for the zone. Select alarm delay options (detection characteristics) for zone. Select heat detector trip temperature and. (JumpStart selects 150°F for heat detectors
and.)
Output Point Configuration
Conventional notification circuits (circuits 1-6):
Enable circuits used for notification appliances through programming, if necessary. (JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always output continuously (constant pattern), even if assigned to an Output Group that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming. Select type of power (door holder, constant, or resettable, or sounder sync)
Addressable relay modules
Assign addressable relay modules to output groups through programming. (JumpStart assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming.
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused output circuits, they will cause a trouble condition (unless an EOL resistor is used).
Select a name for the point, if desired.
Output Group Configuration
Add the group to the system if it does not already exist. Assign output points to the group. Program a name (or description) for the group, if desired.
Select “group properties” (see below).
Latching / non-latching Silencing option Select options for activation with system switches. Map zones to output groups that will activate when zone goes into alarm. Select a cadence pattern for outputs in the zone.
See Sec.
(for more info.)
7.5
7.5
7.5.4
7.5.4
7.3.2
7.3.1.1
7.3.1.1
7.3.1.2
7.4.1
7.4.1
7.5
7.5
7.5
7.5.3
7.5
7.5.4
7.4.2
7.5
7.4.1.1
7.4.1.2
7.4.1
7.4.1
7.3.1.3
7.3.1.4
3-12
Page 30
151274-L8

Section 4 Control Panel Installation

Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.

4.1 Mounting the Control Panel Cabinet

Read the environmental specifications in Section 3.2 before mounting the 5808 panel. The 5808 cabinet dimensions are:
16" W x 26.4" H x 3.5" D (40.64 cm W x 67.06 cm H x 8.89 cm D).
The 5808 panel should be located within a secured area, where it is accessible to main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is expected, attach a piece of 3/4 inch plywood to the concrete surface and then attach the 5808 to the plywood. Also mount any other desired components to the plywood.
DO NOT flush-mount the 5808 cabinet in a wall designated as a fire break.

4.1.1 Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.

4.1.2 Removing the 5808 Assembly from the Housing

If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by removing the screws that hold the control panel in to the cabinet. Do not attempt to disassemble the circuit boards.
4-1
Page 31
Control Panel Installation 151274-L8
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel

4.2 AC Connection

At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection.
The AC terminals are rated at 120 VAC, 60 Hz, 3.6 A.
Figure 4-1 120VAC Power Connection

4.3 Battery Connection

The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 18 AH, larger capacity batteries can be housed in a RBB (see Section 4.3.1 for details). Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. The following steps and diagram explain how to connect the batteries.
1. Connect the black wire from the control panel negative (–) battery terminal to the negative (–) side of Bat-
tery #2.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2 to the (–) negative
side of Battery #1.
3. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1.
Figure 4-2 Battery Connection
4-2
Page 32
IntelliKnight 5808 Installation Manual 151274-L8
Cabinet
Mounting Holes

4.3.1 RBB Accessory Cabinet

The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See figure Figure 4-3 for the four cabinet mounting holes.
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is neces­sary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a piece of ¾”” plywood to the concrete surface and then attach the RBB cabinet to the plywood.
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the battery ter­minals.
Figure 4-3 RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-4.
Figure 4-4 Splicing Control Panel Battery Cable to RBB Battery Cable Extenders
4-3
Page 33
Control Panel Installation 151274-L8
Conduit
Conduit Coupler
+
+
-
-
RBB Cabinet Cover Screws
RBB Cabinet Cover Screws
Cover Plate
Mounting Keyholes
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5.
Figure 4-5 Battery Connections in the RBB Cabinet
Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be uti­lized to connect conduit between the two cabinets.
4. Connect battery leads to the backup battery terminals. See Figure 4-5. Observe the proper polarity to prevent damage to the batteries or the control panel.
5. Insert the RBB cover screws into the cover mounting holes (see Figure 4-5). Screw the cover screw ¾ of the way into the cover mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-6.
Figure 4-6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-6.
4-4
Page 34
IntelliKnight 5808 Installation Manual 151274-L8

4.4 SBUS Wiring

This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class B).

4.4.1 Calculating Wiring distance for SBUS modules

The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp.
Model Number Worst Case Current Draw
5860 Fire Annunciator .100 amps 5824 Serial/Parallel Printer Interface Module .040 amps 5880 LED I/O Module .250 amps 5865 LED Fire Annunciator .200 amps 5496 Intelligent Power Supply .010 amps
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance the modules can be located from the panel on a single wire run. The table insures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
Table 4-1: Wiring Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
22 Gauge 18 Gauge 16 Gauge 14 Gauge
4-5
Page 35
Control Panel Installation 151274-L8
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire Gauge Ohms per 1000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5496 Notification Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Serial/Parallel Printer Interface Module
* 500
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps 5496 Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .200 amps 5824 Current Draw = 1 x .040 amps = .040 amps Total Worst Case Current Draw = .450 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available options are: 370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire
4-6
Page 36
IntelliKnight 5808 Installation Manual 151274-L8
Supervised Power Limited

4.4.2 Wiring Configurations

Figure 4-7 illustrates Class B configuration.
Figure 4-7 SBUS Class B Wiring
4-7
Page 37
Control Panel Installation 151274-L8

4.5 5860 Remote Annunciator Installation

The optional Model 5860 Remote Annunciator, shown in Figure 4-8, performs the same functions as the on­board annunciator as well as initiate and end fire drills with a single key press and view event history by alarms, supervisories, or troubles.
Up to 12 annunciators can be added to the 5808 system.
Figure 4-8 Model 5860 Remote Annunciator, Front View
5860 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the 5860 in the desired location (see Section 4.5.1).
3. Connect the 5860 to the panel (see Section 4.5.2).
4. Use the DIP switches on the back of the 5860 to assign an ID# to the 5860 (see Section 4.9.1).
5. The new 5860 module must be added to the system through programming. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.2.2). Select a name, if desired (see Section 7.2.1.1).
4-8
Page 38
IntelliKnight 5808 Installation Manual 151274-L8

4.5.1 Mounting the 5860

This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface­mounted.
Figure 4-9 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages.
Figure 4-9 Annunciator Parts
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel.
4-9
Page 39
Control Panel Installation 151274-L8
Set screw location.
Loosen set screws to remove bezel
when disassembling annunciator.
Knockout holes
Holes for surface mounting.
Holes for inserting wires for flush mounting (located in all corners).
Stand-off
(throughout)
Screw for placement
of mounting wires
(top and bottom).
(See Figure 4-10 for location of the set screws.)
Figure 4-10 Annunciator Back Box and Bezel Details
4.5.1.1 Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double­gang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the
4-10
Page 40
IntelliKnight 5808 Installation Manual 151274-L8
Sheet rock
Sheet rock
Electrical Box
Annunciator
back box
1-3/8"
When flush-mounting using an
electrical box, the box must be
1-3/8" from face of wall.
Electrical box applications require
2 by 4 construction minimum.
studs
electrical
box
annunciator
back box
(outline)
wall
Examples of Electrical Box Use
Electrical Box Placement
Insert wires at an angle into the first holes past the sheet rock.
Secure the wires behind this screw.
Attach second set of wires to top of back box.
annunciator. Studs used with an electrical box must be two by fours (or larger).
Flush Mounting Steps
1. Cut a hole in the sheet rock to the following dimensions: 8-1/4” w x 6-5/8” h. If an electrical box is used, the box must be 1-3/8” back from face of wall to accommodate the annunciator (see Figure 4-11).
2. Remove knockout holes as needed for wires.
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the mounting wires into the first hole past the sheet rock. Secure the wires behind the screws as shown in Figure 4-12. When all four wires are in place, the back box should fit snugly into the hole in the sheet rock.
4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the elec­tronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
Figure 4-11 Placement of Electrical Box for Flush Mounting
Figure 4-12 Flush Mounting the Back Box
4-11
Page 41
Control Panel Installation 151274-L8
Supervised Power Limited Class B
4.5.1.2 Surface Mounting
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface mounting.
1. Drill holes in the surface to match the screw holes on the back box.
2. Fit the trim ring over the back box.
3. Attach the back box to the surface using screws provided.
4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the elec­tronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.

4.5.2 Connecting the 5860 to the Panel

Connect the 5860 to the panel as shown in Figure 4-13.
Figure 4-13 Model 5860 Connection to the Panel
4.6 5824 Serial/Parallel Printer Interface Module
Installation
The 5824 serial/parallel printer interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instructions for installing the 5824 appear below.
The 5824 and the printer connected to the 5824 are for ancillary use only. The printer must be a UL 864 listed printer.
To install the 5824:
1. Make sure power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4-14.
Note: Two 5824s per panel maximum.
3. Use the DIP switches on the back of the 5824 board to assign an ID# to the 5824 (see Section 4.9.1).
4. Configure the 5824 device through programming. See Section 4.6.1.
4-12
Page 42
IntelliKnight 5808 Installation Manual 151274-L8
Supervised Power Limited Class B Wiring
To Serial Printer
To Parallel Printer
5. Connect a printer to the 5824 as shown in Figure 4-15.
Figure 4-14 5824 Connection to the Panel
Figure 4-15 Printer Connection

4.6.1 Selecting 5824 Options

Configuring the 5824 includes the following steps:
Add the module to the system. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.2.2).
4-13
Page 43
Control Panel Installation 151274-L8
Select a name, if desired (see Section 7.2.1.1).
Select options for the printer and the output port. See below.
Printer and Output Port Options
The printer is for ancillary use only.
1. From the Main Menu, select 7 for Program Menu.
2. Select 1 for Module.
3. Select 1 for Edit Module.
4. From the list that displays, select the 5824 module you want to configure.
5. Press
ENTER to bypass the next two screens. A screen similar to the one shown in Figure 4-16 will display.
Figure 4-16 Selecting Printer and Output Port Options
6. Select options for the printer as needed for your installation. Most printers are parallel.
7. If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual if you need more information.
Option Choices
Baud Rate: 75 - 19200 Data Bits : 5 - 8 Stop Bits: .5, 1, 2 Parity: None, Even, Odd

4.7 5880 LED I/O Module

The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for dry contact monitoring. The following sub-sections describe hardware installation. Refer to Section 6 for programming information.

4.7.1 5880 Board Layout

Figure 4-17 is a picture of the 5880 board showing locations of screw terminals for connection to the panel and contact monitor wiring; pin connectors for connecting LEDs; and the DIP switch for selecting an SBUS ID
4-14
Page 44
IntelliKnight 5808 Installation Manual 151274-L8
SBUS Connection
Dry Contact Inputs - Supervised/Power Limited
SBUS Address DIPs
Supervised Power Limited
number.
Figure 4-17 5880 Board Layout

4.7.2 FACP Connection

The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-18. After the 5880 is connected to the panel, it must be added to the system. This programming step is described in Section 4.9.
Figure 4-18 5880 Connection to Main Control Panel Assembly
4-15
Page 45
Control Panel Installation 151274-L8
11
20
12 13 14
15 16 17 18 19
LED Power
no connection
Anode
Cathode
LEDs
P2
5880 LED Outputs
1
10
2
3
4 5 6 7 8
9
LED Power
Programmable Open Collector Output
Not mappable.
Matches PZT pattern
on on-board
annunciator
Anode
Cathode
LEDs
P1
Connectors P3 and P4 wired same as P2.

4.7.3 LED Wiring

There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to output circuits. See Section 6 for programming details.
Wire the LEDs as shown in Figure 4-19. On connector P1, Pin 12 is a common open collector output for controlling a PZT. If used, the 5880 PZT will
match the PZT pattern of the on-board (or 5860) annunciator.
Note: The circuit connected to common “Open Collector Output” (last pin on P1) must be current limited so that
no more than 100 mA of current is allowed to flow into the open collector transistor.
Figure 4-19 5880 Board Layout
4-16
Page 46
IntelliKnight 5808 Installation Manual 151274-L8
Model 7628
Supervised/Power Limited
4.7k EOL

4.7.4 Dry Contact Wiring

The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flo w, tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-20. Notice grouping of terminals; power terminals are shared by two inputs.
Figure 4-20 Dry Contact Wiring
4-17
Page 47
Control Panel Installation 151274-L8
SILENCE
TROUBLE
RESET
5865-4 Board Assembly
5865-3 Board Assembly
Plexiglass plate mounted to LED board at factory.
Do not remove.
5865-4 switches follow main FACP; no installation or programming required.
Numbers indicate point numbers for
5865. (They do not appear on board assembly.)
12
9
10
11 12
21 22
19 20
29 30
34
5
6
7
8
13
14
15
16
17
18
23
24
25 26
27
28
Supervised Power Limited Class B

4.8 5865-3 / 5865-4 LED Annunciator Installation

The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs.
Installation of the 5865-3 and 5865-4 is identical. The key switches and the trouble LED follow the behavior of other system annunciators and do not require any installation steps. The following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to Section 6 for programming information.
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both
models.
Figure 4-21 5865-3 and 5865-4 Assembly (front view)

4.8.1 FACP Connection

The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-22. After the 5865 is connected to the panel, it must be added to the system. This programming step is described in Section 4.9.
Figure 4-22 5865 Connection to the FACP
4-18
Page 48
IntelliKnight 5808 Installation Manual 151274-L8

4.8.2 5865 Mounting

Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4-23, the 5865-4 attached to a 4-gang box is used as an example.
Figure 4-23 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a typewriter or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4-24. The LEDs will show through the label when illuminated.
Figure 4-24 Inserting Zone Description Labels
4-19
Page 49
Control Panel Installation 151274-L8

4.9 Configuring Modules

This section describes how to configure any system hardware modules that have been added to the system.

4.9.1 Assigning Module IDs

When installing a hardware module (such as, 5824, 5860, 5496, 5865-3 or 5865-4), you must use the DIP switches on the module to assign an ID# to the module.
Figure 4-25 shows all possible DIP switch positions and their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2 in the up position.
Figure 4-25 Possible module addresses
4-20
Page 50
IntelliKnight 5808 Installation Manual 151274-L8
Supervised

4.10 Telephone Connection

Connect the telephone lines as shown in Figure 4-26. The Model 7860 phone cord is available from Silent Knight for this purpose.
A number of programmable options are available for customizing telephone lines. These options are described in Section 7.6.
Figure 4-26 Connection of Telephone Lines

4.11 Notification Appliance/Auxiliary Power Circuits

Note: These circuits are considered regulated unless used for releasing type service, in which case they are con-
sidered special applications.
Four outputs are built-in to the 5808 FACP which can be programmed to be used as NACs (Class A or Class B) or as Aux power.
This section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.

4.11.1 Conventional Notification Appliance

This sub-section of the manual explains how to install conventional notification appliances for Class A (Style Z) and Class B (Style Y) configurations.
4.11.1.1 Class B Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A. To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 4-27.
2. Configure the circuit through programming (see Section 7.5).
4-21
Page 51
Control Panel Installation 151274-L8
Alarm Polarity Shown
UL Listed EOL
Model 7628
4.7 k
Supervised Power Limited
Notification Wiring
Max. Impedance: 1.5
Figure 4-27 Class B Notification Appliance Circuit Wiring
4.11.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A. To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-28.
Caution
For proper system supervision do not use looped wire under terminals marked + and – of the Flexput connectors. Break wire runs to provide supervision of connections.
4-22
Page 52
IntelliKnight 5808 Installation Manual 151274-L8
Supervised Power Limited
Max. Impedance: 1.5
2. Configure the circuit for Class A in programming (see Section 7.5).
Figure 4-28 Class A Notification Appliance Circuit Configuration

4.11.2 Auxiliary Power Installation

NAC Circuits 1-4 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are:
Door Holder (see section 4.11.2.1)
Constant (see section 4.11.2.2)
Resettable Power (see section 4.11.2.3)
Sounder Sync Power (see Section Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all NAC circuits
must not exceed 6A). To install an auxiliary power circuit:
1. Wire the NAC circuit(s) that will be used for auxiliary power. See Figure 3-2 for location of NAC circuits.
2. Configure the auxiliary power output through programming (see sect ion 7.5).
4.11.2.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, do or hold er circ uits have 24-volt power present at their terminals. Any alarm will caus e power to disconnect. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored,
4-23
Page 53
Control Panel Installation 151274-L8
Supervised Power Limited. Special Application.
power is immediately restored to the door holder circuits.
Figure 4-29 Example of an Auxiliary Power For Door Holder
Note: Figure 4-29 uses UL listed door holder Model 1400 from Door Control International as an example.
4.11.2.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
4.11.2.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied.
4.11.2.4 Sounder Sync Power
Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is int e nded for use with B200S sounder bases.
4-24
Page 54
IntelliKnight 5808 Installation Manual 151274-L8
Connect to Power Limited Sources only

4.12 On-Board Programmable Relays (Conventional)

The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 24 VDC (resistive).
Figure 4-30 Location of Conventional Relay Circuits
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no alarm or
trouble conditions.

4.12.1 Trouble Relay

The control panel has a dedicated common Form C trouble relay built into terminals labeled TROUBLE. The relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble condition.

4.12.2 Programmable Relays

The control panel has two Form C programmable relays built into terminals labeled RELAY 1 and RELAY 2. Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-30 for the location of the relay ter­minals.
2. Configure the relay through programming (see section 7.5).

4.13 Remote Station Applications

4.13.1 Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-31.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 2 for alarm.
4-25
Page 55
Control Panel Installation 151274-L8
Not suitable for remote station protected premises service where separate transmission circuits are required for fire supervisory (if applicable), and tr ou ble signals.
Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ra ti ng s.
4. Program NAC circuit 2 for alarm.
5. Program NAC circuit 1 for supervisory non latching.
Note: NACs must be programmed for continuous and non-silencing.
Figure 4-31 Keltron 3158 Connection to Control Panel

4.13.2 City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current accounted for in control panel draw.)
Alarm Current: 1 Amp for 1 second
The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box conn ection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-32. This drawing also shows how to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the NAC circuit used as a continuous and non-silencing. Refer to 7.5 for point programming, Sec­tion 7.4 for group settings, and Section 7.3 for zone settings and mapping.
4-26
Page 56
IntelliKnight 5808 Installation Manual 151274-L8
Note: NAC Circuit 4 Used
Any NAC circuit could be used.
Non-Supervised Non-Power Limited
Intended for connection to a Polarity Reversal circuit of a Remote Station receiving unit having compatible ratings.
Note: The shunt connection is recognized only as a supple menta ry signaling unit as part of a local control unit and is not recognized as an auxiliary control unit connection per NFPA 72.
as an example.
It is not possible to reset the remote indication until you clear the condition and reset the control panel.
Figure 4-32 City Box Connection

4.13.3 NFPA 72 Polarity Reversal

Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having
compatible rating.
4.13.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Standby Current: 100 mA, 24 VDC Alarm: 100 mA, 24 VDC To install the 5220 for polarity reversal, follo w the steps below:
1. Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel using the four-wire pigtail provided as shown in Figure 4-33. This dia­gram also shows how to connect the 5220 to the remote indicator. Do not install an EOL resistor in the ter­minals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the NAC circuit used as continuous and non-silencing. Refer to Section 7.5 for point programming, Section 7.4 for group settings, and Section 7.3 for zone settings and mapping.If necessary, adjust loop cur-
4-27
Page 57
Control Panel Installation 151274-L8
Note: NAC circuit 1 and Relay 1 used as examples. Any NAC circuit and either relay 1 or relay 2 could be used.
Intended for connection to a Polarity Reversal circuit of a Remote Station receiving unit having compatible ratings.
rent using the potentiometer (R10) on the 5220 board. Normal loop current is 2-to-8 mA with a 1k ohm remote station protected premise unit. Maximum loop resistance is 3k ohm.
Figure 4-33 Polarity Reversal Connection Using the 5220 Module
4.13.3.2 Using the 7644-L8 Module
When the 7644-L8 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
To install the 7644-L8 for polarity reversal:
1. Wire the 7644-L8 to the control panel as shown in Figure 4-34. Do not install an EOL resistor on the termi­nals of the NAC circuit used.
Note: Use only NAC circuits on the control panel for reverse polarity.
2. Program the NAC circuit as a notification circuit. See Section 7.5.2.
3. Map the group to activate constant on from the zone event. See Section 7.3.1.3.
4-28
Page 58
IntelliKnight 5808 Installation Manual 151274-L8
4. Program the output group characteristics as non-silenceable and reverse polarity. See Section 7.4.1.2.
Figure 4-34 Polarity Reversal Connection Using the 7644-L8
4-29
Page 59
Control Panel Installation 151274-L8
UL Listed EOL
To Remote
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.
Supervised Power Limited
Receiving Station

4.13.4 Using the SD500-ARM Addressable Relay Module

When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
Relay 2 must be programmed for Alarm (default).
Note: If you need to transmit supervisories or trouble conditions, additional SD500-ARM modules must be added.
Use relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.
Wire the SD500-ARM as shown in Figure 4-35.
Figure 4-35 Polarity Reversal Connection Using the SD500-ARM Module
4-30
Page 60
IntelliKnight 5808 Installation Manual 151274-L8
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.

4.13.5 Using a MR-201/T Control Relay From Air Products

When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Current: 15 mA max. Operating Voltage: 24 VDC nominal Resistance: 4 K To install the MR-201/T for polarity reversal, follow the steps below:
1. Wire the MR-201/T as shown in Figure 4-36.
Figure 4-36 Polarity Reversal Connection Using the MR-201/T Relay
2. Program the NAC circuit for non silence NAC circuit (see Section 7.4.1).
Note: If you need to transmit supervisories or trouble conditions, additiona l relay modules must be added. Use
relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.
4-31
Page 61
Control Panel Installation 151274-L8

4.13.6 Transmitter Activated by Dry Contacts

This section describes the connection of a UL 864 listed remote station transmitter to the 5808 FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter manufacturer ’s manual for details.
4-32
Page 62
151274-L8

Section 5 SK and SD SLC Device Installation

Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.

5.1 List of SK SLC Devices

The following SK SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SK SLC devices or SD SLC devices. You cannot install both
SLC device types on the control panel
SK Model Number Model Name/De scription Install Sheet PN
SK-Photo
SK-Acclimate SK-Beam SK-Beam-T SK-ION SK-Duct SK-Heat
SK-Heat-HT SK-Pull-SA SK-Pull-DA SK-ISO SK-Monitor SK-Minimon SK-Monitor-2 SK-Mon-10 SK-Relay SK-RelayMon-2 SK-Relay-6 SK-Zone SK-Zone-6 SK-Control SK-Control-6 SK-FIRE-CO B200SR Sounder Base I56-3392-00 B200S Sounder Base I56-3687-00 B201LP 6" mounting base K200-07-00 B224BI 6" isolator base I56-0725-00 B200SR-LF B200S-LF B224RB 6" relay base I56-2815-00 B501 4" mounting base I56-0357-00
Photoelectric smoke detector Photoelectric smoke detector with thermal (135°F) Multi criteria photoelectric smoke detector with thermal (135°F) Reflected beam smoke detector without test feature Reflected beam smoke detector with test feature Ionization smoke detector Photoelectric duct smoke detector with extended air speed range Fixed temperature thermal detector (135°F) Rate-of-rise thermal detector with 135° fixed temperature Fixed high temperature thermal detector (190°F) Addressable single action pull station Addressable dual action pull station Fault isolator module Monitor module Mini monitor module Dual input monitor module 10 input monitor module Addressable relay module Dual relay/monitor module Six relay control module Addressable zone interface module Six zone interface module Supervised control module Six circuit supervised control module CO Smoke Detector
Low Frequency Sounder Base Low Frequency Sounder Base
I56-3426-00SK-Photo-T
I56-3433-00
I56-3428-001 I56-3432-000
I56-3429-000SK-Heat-ROR
I56-3446-001 I56-3447-001 I56-3445-000 I56-3442-000 I56-3444-000 I56-3435-000 I56-3443-000 I56-3438-000 I56-3735-000 I56-3439-000 I56-3440-000 I56-3441-000 I56-3436-000 I56-3437-000 I56-3945-000
I56-4152-00 I56-4151-00
5-1
Page 63
SK and SD SLC Device Installation 151274-L8

5.2 List of SD SLC Devices

The following SD SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot insta ll both
SLC device types on this control panel.
SD
Model Number
SD505-APS Photoelectric smoke detector. SD505-AIS Ionization smoke detector SD505-AHS Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C). SD505-6AB 6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS. 150955 SD505-6IB 6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SD505-6RB 6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151192 SD505-6SB 6" sounder base for use with the SD505-AHS, SD505-AIS, and SD505-APS SLC
devices SD505-DUCT Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths:
SD505-T2 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot) SD505-DUCTR Duct Detector housing with relay base. Duct housing with relay base including
SD505-APS Analog Photoelectric Smoke detector pre-installed SD500-PS/-PSDA Single or dual action addressable pull station 151177 SD500-AIM Addressable input module (switch input), standard size, DIP switch configured 151071 SD500-MIM Mini input monitor module (switch input), small size, DIP switch configured. Fits in
single-gang box with manual pull station switch. SD500-ANM Addressable notification module 151109 SD500ARM Addressable relay module DIP switch configured. 151091 SD500-SDM Addressable smoke detector module. Use to assign an address to a loop of
conventional devices. SD500-LIM Line isolator module. Fits in a double gang box. 151125 SD500-LED Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-
LED Driver Modules can be used per SLC loop. SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882
Model Name/Description
Section / Install
Sheet PN
Section 5.7
151175
151191
1700-09882
1700-09882
151071
151193
151232

5.3 Maximum Number of Devices

The 5808 supports SK or SD devices on one 5808 system. The maximum number of devices per system varies depending on device protocol. Device support is as follows:
SK Devices–A 5808 system can support a total of 99 SK detectors and 99 SK modules.
OR
SD Devices–A 5808 system can support a total of 127 SD SLC detectors and modules, in any combination.

5.4 Wiring Requirements for SLC Devices

The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details.
5-2
Page 64
IntelliKnight 5808 Installation Manual 151274-L8

5.4.1 Wiring SLC in Style 4 (Class B) Configuration

No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-51 requirements for power limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms for SK device and 50 ohms for SD devices. Maximum loop length depends on the wire gauge. See Table 5-1 and Table 5-2.
Table 5-1 Maximum wiring distance for SK Modules
Wire Gauge Max. Distance for SK
22 AWG 1200 feet 18 AWG 3100 feet 16 AWG 4900 feet 14 AWG 7900 feet 12 AWG 10,000 feet
Table 5-2 Maximum wiring distance for SD Devices
Wire Gauge Max. Distance for SD
22 AWG 1500 feet 18 AWG 3900 feet 16 AWG 6200 feet 14 AWG 10,000 feet
Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap and T-tap style wiring.
Figure 5-1 Calculating wire run length for a simple out and back tap
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement
5-3
Page 65
SK and SD SLC Device Installation 151274-L8
must be met in addition to the maximum distance requirements for the various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap

5.4.2 Wiring SLC in Style 6 & 7 (Class A) Configuration

Figure 5-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.
Note: Style 6 does not use short circuit isolator devices.
Figure 5-3 Class A SLC Configuration
5-4
Page 66
IntelliKnight 5808 Installation Manual 151274-L8
Note: No t-taps allowed on class A SLC loops.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors. Break wire runs to provide supervision of connections.

5.5 SK Detector Installation

This section describes how to install heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instruction s fo r mo re detailed information.
This information applies to the following SK models:
SK-Photo Photoelectric Smoke Detector
SK-Photo-T Photoelectric Smoke Detector with Thermal
SK-Acclimate Photoelectric Smoke Detector with Thermal
SK-Heat Fixed Temperature Detector
SK-Heat-T High Temperature Thermal Detector
SK-Heat-ROR Rate-of-Rise Thermal Detector
SK-ION Ionization Smoke Detector
SK-FIRE-CO CO Smoke Detector

5.5.1 Wiring SK detectors:

1. Wire device bases as shown in Figure 5-4.
2. Set the address for each device as described in Section 5.6.
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
5-5
Page 67
SK and SD SLC Device Installation 151274-L8
Example 1: Device Set to 01.
Example 2: Device Set to 42.
All dials labeled for ONES
or TENS position.

5.6 Addressing SK SLC Devices

All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
SK device addresses are handled differently than SD device addresses. The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any unique address from 1 to 99, and SK modules can be assigned any unique address from 1 to 99. Unlike SD detectors and modules which share addresses 1 through 127, there can be an SK detector using address 1 and an SK module using address 1. 0 is an invalid address.
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary dial to 0 as shown in Figure 5-5.
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 5-5.
Figure 5-5 SK SLC Device Addressing Using Rotary Dials

5.7 SD Detector Installation

The information in this section applies to the following SD models: SD505-AHS Heat Detector, SD505-AIS Ionization Smoke Detector, and SD505-APS Photoelectric Smoke Detector.

5.7.1 Wiring SD Detectors

1. Wire device bases as shown in Figure 5-6.
2. Set the address for each device as described in Section 5.8.
Figure 5-6 Heat or Smoke Detector Connection to the FACP (Class B)
5-6
Page 68
IntelliKnight 5808 Installation Manual 151274-L8

5.8 Addressing SD Devices

This section tells how to address detectors and modules.

5.8.1 SD505-APS, SD505-AHS, & SD505-AIS

The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer Code is required to perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in Figure 5-7. (You can use the same base for each detector).
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code, then press
3. Select 2 for Point Functions.
4. Select 3 for Set SLC Dev Addr.
5. Select “Yes” by pressing the up arrow, then press can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel reinitializes when you finish programming.)
6. When the wait message clears, the following options display: 1- for Read Address. Use to read (or check) a single detector’s address. 2 - for Write Address. Use to program a single detector’s address. 3 - for Seq. Programming. Use to program more than one detector in sequential order.
7. If you are changing addresses, write the programmed address on the back of the device.
8. T o exit press left arrow until fully exited.
ENTER.
ENTER. (The panel will go into trouble at this point. You
5-7
Page 69
SK and SD SLC Device Installation 151274-L8

5.8.2 SLC Devices with DIP Switches

Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid address.
Figure 5-8 SLC Device Addressing Using DIP Switches
5-8
Page 70
151274-L8

Section 6 Programming Overview

This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully, especially if you are programming the control panel for the first time.
The JumpStart feature automates many programming tasks and selects default options for the system. You will run JumpStart at least once when you are installing the system. See Section 6.1 for details. After you run JumpStart, you may need to do some additional programming depending on your installat ion. Sect ion 7 of this manual covers manual programmable options in detail.
Programming the panel can be thought of as a three part process. You must program:
System options. These are options that affect general operation of the panel (see Section 7.6 for details).
Options for input points and zones. These are primarily options that control detection behavior of devices (see Section 7.5 for details).
Options for output points and groups. This includes selecting characteristics for output groups and mapping output circuits to output groups (see Section 7.5 for details).

6.1 JumpStart Autoprogramming

The JumpStart feature allows for faster system setup. When you run JumpStart (immediately after addressing SLC devices), the system scans devices on all SLC loops and determines device type (for example, ionization smoke detector or heat sensor) and selects some system options based on the device type. This saves the installer from having to program options for each device. Depending on the application, the installer may need to make some changes after JumpStart completes.
See Section 6.1.3 for complete details about running JumpStart.
IMPORTANT
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected. JumpStart will reset all manually programmed options to default settings. Do not run JumpStart after you have configured the system.

6.1.1 Input Points

JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not need to edit device type for detectors. Any contact monitor modules on the system will be assigned type "Manual Pull." The installer will need to manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1. After JumpStart completes, you can re-map to configure a multiple zone/output group system (see Section
7.3.1.3). For a general explanation of mapping, see Section 6.2.

6.1.2 Output Points

JumpStart creates three output groups and assigns output circuits as follows: Circuits 1-4:
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone 1 to activate Group
6-1
Page 71
Programming Overview 151274-L8
1 using constant on output when an alarm condition occurs. Circuit 5 (Relay 1):
Assigned to Group 124. JumpStart automatically programs Zone 1 to activate Group 124 using constant on output when a supervisory condition occurs.
Circuit 6 (Relay 2): Assigned to Group 125. JumpStart automatically programs Zone 1 to activate Group 125 using constant on output when an alarm occurs.
Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases): All addressable relay devices will be configured as "Output Pt" (general purpose output point) and assigned to Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.

6.1.3 Running JumpStart AutoProgramming

Run JumpStart immediately after you have addressed and connected all input devices (detectors, pull stations, and so on) and output devices (notification appliances, relays, and so on).
Note: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow
instructions in Section 7 for configuration.
To run JumpStart, follow these steps.
1. Press
2. From the Main Menu Select 7 for the Program Menu.
3. From the next menu, select 6 for JumpStart.
4. The message "WARNING Will DELETE all system options" displays on the LCD. Select Yes to continue. A
5. When the message, “SLC FAMILY” flashes. Press
6. When the message “Configuring System Done” displays, press any key to continue.
ENTER to view the Main Menu.
series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can take several minutes, depending on the number of devices attached.
ENTER to accept SK, or press up arrow to change to SD and
press
ENTER to accept.
6-2
Page 72
IntelliKnight 5808 Installation Manual 151274-L8
7. Select one of the following options from the menu that displays.
1 - Review System Press 1 if you need to review the JumpStart configuration. 2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason. 3 - Accept Config. 1. If you are ready to make the JumpStart configuration permanent, select 3.
2. The system will ask you if the installation contains duct detectors. If there are none, select 2 for No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and continue with Step 3.
3. From the list that displays, select the SLC device that contains the duct detectors.
4. The first photoelectric or ionization detector on the system will display . Se lect 1 for DUCT and 2 for NonDUCT.
5. Press to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue until all duct detectors have been selected. (Note: You can move backwards through the list with
).
6. When you reach the last detector on this device, press .
7. The system will ask you if there are more duct detectors in the system. If there are, select 1 for Yes and repeat from Step 3. If there are no more duct detectors, select 2 for No and continue with Step 8.
8. The system will restart in 10 seconds. You can press 1 to restart immediately.
9. After the system resets, it will use the new JumpS tart configuration.
4 - Enter Programing To go directly to Prog ram mode to configure any devices, press 4. The Programming menu appears
and you can begin programming
6-3
Page 73
Programming Overview 151274-L8

6.2 Mapping Overview

This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7.
Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that should activate when events occur. You do this by assigning input points to input zones, output points to output groups and then linking or mapping zones and output gro ups.
Figure 6-1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
Figure 6-1 Mapping Overview
6-4
Page 74
IntelliKnight 5808 Installation Manual 151274-L8

6.2.1 Input Point Mapping

Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as "Unused," which means it has not been assigned to a zone.)
Figure 6-2 Input Point Assignment Example
6-5
Page 75
Programming Overview 151274-L8

6.2.2 Output Circuit Mapping

Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5.
Figure 6-3 Assigning Output Circuits to Groups (Example)
6-6
Page 76
IntelliKnight 5808 Installation Manual 151274-L8

6.2.3 Zone Event Mapping

There are 11 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may be used (see Section 7.4.5 for information on output group templates). Event types are:
Manual Pull Alarm
Water Flow Alarm
Detector Alarm (heat or smoke detectors)
Aux 1 and Aux 2 Alarm (user-specified alarm types)
Pre-alarm
Supervisory
Trouble
Status Point
CO Alarm
CO Supervisory
Figure 6-4 Example of Zone Events Mapped to Output Groups and Patterns
6-7
Page 77
Programming Overview 151274-L8
Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns
6-8
Page 78
IntelliKnight 5808 Installation Manual 151274-L8

6.2.4 Mapping LED Points

Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the system.)
Figure 6-6 Example of LED Points Mapped to Output Groups
(applies to Models 5865-3/4 and 5880)
6-9
Page 79
Programming Overview 151274-L8

6.3 Programming Using the 5660 Silent Knight Software Suite

You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely. SKSS is an optional software package that lets you easily program the control panel using a Windows-based computer and a modem* (not sold by Silent Knight). When using SKSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel. You connect to the control panel directly using the control panel’s onboard USB or serial port or remotely using a modem. If you need to connect to an older control panel that does not have a USB port, and your laptop does not have a serial port, use a USB to serial converter. SKSS includes an Online help system and a manual. See the SKSS manual (PN 151240) for more information.
* See Section 1.3 for a list of modems that have been tested for compatibility with the control panel
and SKSS.

6.4 Programming Using an Annunciator

You can program the control panel from a system annunciator, using either the control panel’s on-board annunciator or a remote annunciator.
The following subsections describe programming basics, including a description of editing keys available for programming and how to move through programming menus. Section 7 contains specific information about individual programming options.

6.4.1 Entering / Exiting the Programming Menu

To enter the Programming Menu:
1. Enter the Installer Code (factory programmed default code is 123456).
2. The display prompts you to press the
Figure 6-7 Keypad Enabled Screen
3. Press 7. The menus described in Section 7 of this manual will display. Section 6.5 of this manual is a quick
reference listing all programmable options and JumpStart defaults.
To exit the programming menu:
When you have completed working with the menus, press the left arrow several times until you are exited from programming mode. Two prompts will display. The first prompt is to make sure you intended to leave the Program Menu (select Yes or No as appropriate). The second prompt is for accepting all changes. If you select No, any changes you have made since you entered the Program Menu will have no effect.
or ENTER key to bring up the Main Menu (see Figure 6-7).
6-10
Page 80
IntelliKnight 5808 Installation Manual 151274-L8

6.4.2 Moving through the Menus

Figure 6-8 shows how to move through Program Menu screens, using the System Options screen as an example.
Figure 6-8 Moving through Program Menu

6.4.3 Selecting Options and Entering Data

There are several ways to make programming selections using the control panel depending on which screen you are currently using. The chart below is a generic explanation.
To Press
Select from a menu. Enter the number of the option. Enter numeric data. Press the appropriate number on the annunciator. Enter text (alphanumeric data). Enter each character individually using the UP and DOWN arrow keys until the one you
wish to select displays. Then press right arrow to select the character.
Select from a scrolling list. Use up arrow and down arrow to move through a list of available options. When the
option you want to select is displayed, press ENTER.

6.4.4 Editing Keys

The keys shown in Figure 6-9 are available for use when you are in the Program Menu.
Figure 6-9 Editing Keys Available from Program Menu
6-11
Page 81
Programming Overview 151274-L8

6.5 Programming Menu Quick Reference

This section of the manual lists all Program Menu options in the order they appear on the sub-me nus. Default settings are indicated in text or marked with an asterisk. The comments column provide quick information and a reference to a section (if applicable) which has more detailed information.
Menu Options/Defaults Comments
Edit Module Settings (If applicable)
*1 Count 2 Count Alarm Ver. PAS SNGL ILOCK DBL ILOCK
135° to 150°F*
135° to 190° 150°F*
*Groups 01, 125; Pattern 00
no groupAux 2 (A2)
(Group 124; Pattern 00)
no group
*Groups 01, 125; Pattern 00
* Group 124; Pattern 00
Section 7.2.1
Section 7.2.2
Section 7.3.1.2
SD Devices. Section
7.3.1.2 SK Devices. Section
7.3.1.2
Section 7.3.1.3 Section 7.3.1.4
SD Devices. Sections
7.3.1.4, 7.3.1.5 SK Devices. Sections
7.3.1.4, 7.3.1.5
Module
Zone
Edit Module Select Module Enter Module ID Enter Module Name
5824-Ser/Par/IO 5860-LCD Ann
Add Module
Delete Module List of Modules Section 7.2.3 View Module List List of Modules Section 7.2.4
Edit Zone Select Zone to Edit
Add Zone Section 7.3.2 Delete Zone Select Zone to Delete Section 7.3.3 View Zone Points Select Zone to View Section 7.3.4
5895XL-Pwr Sup 5496-NAC Expand 5880-LED/IO Dev 5865-LED Annunc
Edit Zone Name Section 7.3.1.1
Verification Type
Zone Properties
Heat Temp Set
Manual Pull (MP) Water Flow (WF) Detector Alarm (DE) Aux 1 (A1)
Pre-alarm (PR)
Zone Outputs
Zone Accessry Opt
Fire Supervisory (SU)
Trouble (TR) Status Point (SP)
CO Alarm (CO)
CO Supervisory (Sco)
Cadence 00-16, 23; *02
Fire Cadence 00, 01, *02, 23 CO Cadence 00, 01, 02, *23 Local Zone Y or *N Section 7.3.1.5
6-12
Page 82
IntelliKnight 5808 Installation Manual 151274-L8
Menu Options/Defaults Comments
Group Name Section 7.4.1.1
*Non-Latching (NL)
Latching (LA) *Silenceable Non-Silenceable Auto Unsilence SIL-INHIB SHUT-DOWN *No RP RP-TRB RP-NTR
Y or *N Section 7.4.1.2
*Y or N Section 7.4.1.2
Y or *N Section 7.4.1.2
Y or *N Section 7.4.1.2
Y or *N Section 7.4.1.2
Section 7.4.1.2
Section 7.4.3
Section 7.4.5
Group
Latching Options
Silencing Options
Edit Group Select Group to Edit
1
Add Group Section 7.4.2
Delete Group
View Group Points Select Group to View Section 7.4.4
Edit OPG Template
Select Group to Delete
Select Template to Edit
Group Properties
Select Group Include in template Yes or *N Select Pattern *00-21, 23 Section 7.4.5, Section 7.3. 1.4
Polarity
Group Activates for all Man. Pull
Group Activates for Fire Drill
Group Activates for Aux 1
Group Activates for Aux 2
Ignore Global Cadence
Delay 05 -60 Min (*15) Section 7.4.1.2
6-13
Page 83
Programming Overview 151274-L8
Menu Options/Defaults Comments
UNUSED
*Latching (LA) or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RLY BAS, I-SdrBa
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name
Section 7.5.1
Point
Internal and External 5815XL, SK Devices
Sensor Point #
PHOTO, ION, HEAT,ACCLIMATE HEAT HT, PHOT­HEAT, BEAM
DETECTOR
PHOT DUCT
6-14
Page 84
IntelliKnight 5808 Installation Manual 151274-L8
Menu Options/Defaults Comments
*Latching (LA) or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RLY BAS, I-SdrBa
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RLY BAS, I-SdrBa
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SK Devices
Sensor Point #
SUP DET
CO FIRE
PHOTO, ION, HEAT,ACCLIMATE, HEAT HT, PHOT­HEAT, BEAM
PHOT DUCT
ALRM Fire/ALRM CO, ALRM Fire/ SUPR CO, SUPR Fire/ALRM CO, SUPR Fire/SUPR CO
6-15
Page 85
Programming Overview 151274-L8
Menu Options/Defaults Comments
Single/Multi Station: *NST, SST, MST
Station Silenceable:*SIL , NSL
Accessory Group # (*001)
Point Name
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Silenceable (SI)
or Non­Silenceable (NS)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Point Name Zone # (*001) Used to activate an
Point Name
Group # (*001) Point Name
Point Name
Group # (*001) Point Name
Point Name
Section 7.5.1
ancillary output group that does not activate alarm, sound PZT, display status, or report events. Reset has no effect on this point Section 7.5.1
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SK Devices
Sensor Point #
Module Point #
CO FIRE
UNUSED
SWITCH
NOTIF
RELAY
ALRM Fire/ALRM CO, ALRM Fire/ SUPR CO, SUPR Fire/ALRM CO, SUPR Fire/SUPR CO
(cont.)
MAN_PULL, P AS_ACK, DETECT SW, MAN REL, ILOCK, CO DET SW
WATERFLOW, SUPERVSY, ZN_AUX1, ZN_AUX2, TAMPER
FIREDRILL, SILENCE, RESET
SYS_AUX1, SYS_AUX2
STATUS PT
OUTPUT PT
AUX CONST, AUX RESET, AUX DOOR
OUTPUT PT
AUX RESET, AUX DOOR
6-16
Page 86
IntelliKnight 5808 Installation Manual 151274-L8
Menu Options/Defaults Comments
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name
*Latching (LA) or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RLY BAS
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Silenceable (SI)
or Non­Silenceable (NS)
Zone # (*001) Point Name
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SK Devices
Internal and External 5815XL, SD Devices
Module Point # DETECTOR 2WIRE SMK
UNUSED
PHOTO, ION, H EA T ,
Point #
DETECTOR
PHOT DUCT, ION DUCT
2 WIRE SMK
6-17
Page 87
Programming Overview 151274-L8
Menu Options/Defaults Comments
*Latching (LA) or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RLY BAS
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Silenceable (SI)
or Non­Silenceable (NS)
Zone # (*001) Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SD Devices
Point #
SUP DET
SWITCH
PHOTO, ION, HEAT
PHOT DUCT, ION DUCT
MAN_PULL, P AS_ACK, DET SW , MAN REL, ILOCK, CO DET SW
WATERFLOW, SUPERVSY, ZN_AUX1, ZN_AUX2, TAMPER
6-18
Page 88
IntelliKnight 5808 Installation Manual 151274-L8
Menu Options/Defaults Comments
*Silenceable (SI) or Non­Silenceable (NS)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Point Name Zone # (*001) Used to activate an
Point Name
Group # (*001) Point Name
Point Name
Group # (*001) Point Name
Point Name
UNUSED, NOTIF
Group # (*001) Point Name
Group # (*001) Point Name Group # (*001) Point Name
Point Name
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # Point Name
Section 7.5.1
ancillary Output Group that does not activate alarm, sound PZT, display status or report events. Reset has no affect on this point. Section 7.5.1
Section 7.5.1
Section 7.5.2
Point (cont.)
Internal and External 5815XL, SD Devices
Internal Pwr and External Power
Point #
FIREDRILL, SILENCE, RESET
SYS_AUX1, SYS_AUX2
SWITCH
STATUS PT
OUTPUT PT
NOTIF
RELAY
SLC LED LED # (01-80)
UNUSED
B NOTIF
A NOTIF
AUX PWR
B SWITCH
AUX CONST, AUX RESET, AUX DOOR
OUTPUT PT
AUX RESET, AUX DOOR
NOTIF OUT, CTRL CKT
NOTIF OUT, CTRL CKT
CONSTANT, AUX RESET, AUX DOOR, AUX SYNC
MAN _PULL, PAS_ACK, MAN REL, ILOCK
WATERFLOW, SUPERVSY, ZN_AUX1, ZN_AUX2, TAMPER
6-19
Page 89
Programming Overview 151274-L8
Menu Options/Defaults Comments
*Silenceable (SI) or Non­Silenceable (NS)
Point Name *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Point Name Zone # (*001) Used to activate an
Point Name
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Silenceable (SI)
or Non­Silenceable (NS)
Zone # (*001) Point Name
Group # (*001) Point Name *Silenceable (SI)
or Non­Silenceable (NS)
Zone # (*001) Point Name Select zone *Latching (LA)
or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Point Name *Silenceable (SI)
or Non­Silenceable (NS)
Point Name
Section 7.5.2
ancillary Output Group that does not activate alarm, sound PZT, display status or report events. Reset has no affect on this point. Section 7.5.2
Section 7.5.2
Section 7.5.3
Point (cont.)
Internal and External Power Supply
5880
Point #
FIREDRILL, SILENCE, RESET
SYS_AUX1, SUS_AUX2
B SWITCH
STATUS PT
A SWITCH Same as B SWITCH
2WIRE SMK,
B DETECTOR
A DETECTOR
UNUSED
NOTIF
SWITCH
4WIRE SMK, CO 4WIRE
2WIRE SMK, 4WIRE SMK, CO 4WIRE
NOTIF OUT, CTRL CKT
MAN _PULL, PAS_ACK, MAN REL, ILOCK
WATERFLOW, SUPERVSY, ZN_AUX1, ZN_AUX2, TAMPER
FIREDRILL, SILENCE, RESET
6-20
Page 90
IntelliKnight 5808 Installation Manual 151274-L8
Menu Options/Defaults Comments
*Latching (LA) or Non-Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name
Group # (*001) Point Name
Yes (Y), *No (N), or Must (M)
Yes (Y), *No (N), or Must (M)
Yes (Y), *No (N), or Must (M)
Yes (Y), *No (N), or Must (M)
Yes (Y), *No (N), or Must (M)
*U Section 7.6.2.4
*Y Section 7.6.2.6
Section 7.5.3
Account # (6-digit number, identifies account to central station) Section 7.6.1.1
Reporting Format (SIA, S20, Contact ID) Section 7.6.1.1
Section 7.6.1.1
Section 7.6.1.2
Point (cont.)
System Options
5880
Point #
5865
Edit Acct.
Reporting Accounts
Auto Test Time
Phone Lines Select Phone Line
SYS_AUX1,
SWITCH
UNUSED
NOTIF
Choose Account (1-4)
Set the Hour Set the Minutes Select AM/PM Report Every 04, 06, 12, *24 hours Phone Line Disable Y or *N Section 7.6.2 Dial Tone Detection
Disable Dialing Prefix *none Up to 9 digits Section 7.6.2.1 # of Answer Rings Range: 00-15 *6 Section 7.6.2.2 Select Dialing Option *TT, TT/PL, PULSE Section 7.6.2.3
Rotary Pulse Format
Line Monitor *Y or N Section 7.6.2.5 Answering Machine
Bypass
SUS_AUX2
STATUS PT
NOTIF OUT, CTRL CKT
Edit Account # *123456
Edit Format *CID, S20, SIA
Report Alarms
Rep. Alarm Restore
Report Troubles, Disables, Supervisories and their Restores
Report Test
Report Resets
Switch attempts (1-5) *3 Edit Phone #
Y or *N Section 7.6.2
U = 60/40 E = 66/34
Y = Enabled N = Disabled
6-21
Page 91
Programming Overview 151274-L8
Menu Options/Defaults Comments
Select Group (*None) Select Cadence (*None) Select Group (*None) Select Cadence (*None) Select Group (*None) Select Cadence (*None) Group Trouble SBUS Comm SBUS Power SLC Loop AC Loss Battery Gnd Fault Phone Line Account Printer Aux Power System Switch
00-21, 23 *00 (Constant)
00-21, 23 *00 (Constant)
*60 Seconds Section 7.6.4.2
*AM/PM
*Zone Section 7.6.5.3
Select Group (*None)
Select Cadence (*None)
Water Flow delay is the number of sec. before water flow alarm is generated. Section 7.6.6.1
System Clock Format (AM/PM or military).
Section 7.6.3.1
Section 7.6.3.2
Section 7.6.4.4
Section 7.6.4.560 Hz
Section 7.6.5.1
Section 7.6.5.2
Section 7.6.5.4
Section 7.6.5.5
System Options
System Event Outputs
Time Options
Misc. Options
System Trouble
Alarm Silence
Trbl Silence
Trouble Events
User Selected
Fire Drill Cadence 00-21, 23 *00 (Constant) System Aux1
Sys Alarm Cadence
Water Flow Delay 0 - 90 Seconds *01
Alarm Verification time
Low AC Delay 0 - 30 hours *3 hrs Low AC Report Delay. Section 7.6.4. 3
Clock
AC Frequency
SYNC Strbs w/ Silence
Auto Display Oldest
Report By
Plexi Door
Single Key Ack
Cadence System Aux2
Cadence
Enter time from 1 to 250 seconds
AM/PM MIL 50 Hz
Neither Y (Enabled) or *N
(Disabled) *Y (Enabled) or N
(Disabled) Zone Point Y (Enabled) or *N
(Disabled) Y (Enabled) or *N
(Disabled)
6-22
Page 92
IntelliKnight 5808 Installation Manual 151274-L8
Menu Options/Defaults Comments
*Y (Enabled) or N (Disabled)
Select week: 1st, *2nd, 3rd, 4th or Last
Select week: *1st, 2nd, 3rd, 4th or Last
Edit Line 1 Edit Line 2
System Reset System Silence System ACK System Tests Fire Drill Menu Indicator Test WalkTest-No Rpt WalkTest-with Rpt Dialer Test Clear History Buf Point Functions Disable/Enable Pt Point Status Set SLC Dev Addr SLC Dev Locator SLC Multi Locator I/O Point Control Event History Set Time & Date Printer Options Event Loggings Print Event Hist. Print Det. Status Print System Cfg Reset Dialer Program Menu System Info Up/Download
System Options
(cont.)
JumpStart AutoProgra mming
Computer Account
Access Codes
DST
Daylight Savings
Edit Banner
SLC Family
No Yes Computer Account # *123456
Computer Access Code
Computer Phone # Up to 40 digits
Select Profile (01-20)
DST Start
DST End
Internal Message
Custom Message
SD SK
*0
Edit Name Edit Access Code
Panel Functions
1. Use of multiple notification groups may not synchronize with each other.
Select Month (*Mar)
Select Month (*Nov)
Automatic Daylight Saving Time enable or disable. Section 7.6.6.1
Section 7.6.6.2
Section 7.6.7
Section 7.6.8
Section 7.7
Section 7.8
Profile 1 is the profile that dictates what functions the Firefighter Key has access to. Because this is the profile for a key the user name and the access code can not be edited for this profile.
Profile 2 is the profile for the installer and is referred to as the “Installer Code”. This profile’s user name and panel functions can not be edited.. Section 7.9
6-23
Page 93

Section 7 Programming

This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using the Silent Knight Software Suite 5660.
Important!
Before any customized programming is done, Jump-start should be run first. After Jump-start is run, thoroughly test the system. The reason the system should be tested after Jump-start is because Jump-start automatically programs the system, searching for and configuring all SLC and SBUS devices it finds. Jump­start allows you to confirm the integrity of the installation prior to performing any custom programming. After determining that the hardware is properly installed, custom programming can be performed. Refer to Section 6.

7.1 UL 864 Programming Requirements

151274-L8
NOTICE TO USERS, INST ALLERS, AUTHORITIES HA VING JURISDICTION, AND OTHER INVOLVED PARTIES: This product incorporates field programmable
software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, cert ain programm ing features or options must be limited to specific values or not used at all as indicated below.
Settings
Permitted in
UL 864
Programming Option Menu Item
Time Options Low AC Report
Display Oldest Event
Alarm Verification Alarm
Delay Y (Enabled) Yes Yes & No Yes N (Disabled) No Yes & No No
Verification
Permitted in UL 864 (Y/N)
Yes 0–30 hours 1–3
Yes 1-250 1-60
Possible
Settings

7.2 Modules

This section lists the options available under the module option in the program menu. The following modules are available for the control panel: 5860 remote fire alarm annunciator, 5824 serial/parallel printer interface module, 5496 intelligent power module, 5880 LED I/O module, and 5865 LED annunciator.
7-1
Page 94
Programming 151274-L8

7.2.1 Edit Modules

The features that can be edited when this option is selected are, module name, and class of wiring (Class A or Class B).
T o edit an existing module, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 1 to enter module menu.
4. Press 1 to edit a module.
5. Use the or arrow to select the module you wish to edit.
7.2.1.1 Naming Modules
You can assign an English name to a system hardware module to make it easier to recognize on a display.
6. If you wish to edit the modules name press the or arrow to select each character for the modules
name (or press to bypass name edit).
Press the to move to the next character.
Figure 7-1 Edit module Name Programming Screen Example
7.2.1.2 Module, Wiring Class
This option applies only to the SLC loop. Each module has a unique set of option that specifically applies to the functionality of the module being edited.
7. Choose the class of wiring you wish to use for this module by pressing the or arrow, then press
ENTER.

7.2.2 Adding a Module

If you need to add a new hardware module to the system, follow these steps. You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code.
7-2
Page 95
IntelliKnight 5808 Installation Manual 151274-L8
2. Press 7 for Program Menu.
3. Press 1 to enter module menu.
4. Press 2 to add a module.
5. From the next screen, use the or arrow to choose a module type to add from the <New Module
Type> screen. The screen will display “Adding module [#]...” for a few moments. You will be returned to the <New Mod-
ule Type> screen where you can add additional modules if desired.
You must save changes when you exit the Program Menu or the new module will not be added.
Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it
reinitializes (when you exit the Program Menu). When the new module is attached, the trouble will correct itself automatically the next time you power up the system.

7.2.3 Deleting a Module

If you ever need to delete a module, follow these steps. You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code.
2. Press 7 for Program Menu.
3. Press 1 to enter module menu.
4. Press 3 to delete a module.
5. From the next screen, select a module to delete.
6. A warning screen will display. If you want to proceed with deleting the mo dule, select Yes. To cancel, select
No.

7.2.4 View Module List

1. Enter the installer code.
2. Press 7 for Program Menu.
3. Press 1 to enter module menu.
4. Press 4 to view module list.

7.3 Zone

Through the zone option in the program menu you can edit, add, delete, and view zone points. Selections made here affect all detectors and switches in the zone. Up to 125 zones can be used in the system.

7.3.1 Edit Zone

Features that can be edited through the edit zone option are zone name, zone properties (which includes, zone type, and detector sensitivity), zone output mapping, and zone accessory options.
To edit a zone, follow these steps:
1. Enter the installer code.
2. Press 7 for Program Menu.
7-3
Page 96
Programming 151274-L8
Detection type also selected from this screen (see Table 7-1).
3. Press 2 to enter zone menu.
4. Press 1 to edit a zone.
5. Enter the zone number, then press
ENTER.
7.3.1.1 Edit Zone Name
6. Press 1 to edit the selected zone’s name.
A screen similar to the one shown in Figure 7-2 displays.
Figure 7-2 Selecting Character for Zone Name
7. Select the characters for the zone name by pressing the or arrow until the desired character is shown
then press . or See Appendix B of this manual for a list of available characters and their numeric designa­tors.
8. Repeat step 8 until the name is complete.
9. Press
ENTER when the name is complete.
7.3.1.2 Edit Zone Properties
Zone properties consist of, alarm delay characteristics, and heat detector sensitivity.
1. Do steps 1 through 5 of Section 7.3.1.
2. Press 2 to edit the properties of the selected zone.
Figure 7-3 Editing Zone Properties
Alarm Delay Characteristics
3. Select the alarm delay characteristics by pressing the or arrow.
7-4
Page 97
IntelliKnight 5808 Installation Manual 151274-L8
Table 7-1 list the delay choices and a description of each.
Table 7-1: Alarm Delay Characteristics
Type of Delay Description
1-Count One Count (No Delay). When this option is enabled, an alarm occurs immediately when a
2-Count When this type of alarm delay is used, two or more detectors within the zone must go into
Alarm Ver. Alarm verification is an optional false alarm prevention feature that verifies an alarm condition
PAS This option is intended to be used with an acknowledge switch. An alarm is delayed for 15
single device of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is considered the most typical operation and is the default for all zones.
alarm in order for the zone to report an alarm. Switches of type manual pull, water flow, Aux1 and Aux2 are an exception; they will cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has occurred. If the zone has been mapped to an output group for the prealarm event, the output group will activate. The prealarm will not be reported to the central station.
by resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed, the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central station. The alarm verification sequence is ignored if the zone is already in alarm.
seconds, giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated within 15 seconds, an alarm occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
• The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the acknowledge switch.
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-sec­ond time-frame will begin counting down. This time-frame allows the operator to investigate the cause of the alarm.
If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does not perform a reset within 180 seconds, an alarm will occur auto-
matically.
• The P.A.S. feature will be overridden if another alarm occurs.
SNGL ILOCK See Section 8.7.1 for single interlock releasing operation.
DBL ILOCK See Section 8.7.2 for double interlock releasing operation.
Note: SK-FIRE-CO and other CO detectors can only be installed in a 1 count zone; they will operate
as a 1-count point regardless of the programmed zone type (i.e. Alarm Verification, 2 count, etc.).
4. Press
ENTER.
Heat Temperature Setting
Use this feature to set the temperature at which high temperature detectors will respond. All detectors in the zone will respond in the same way. The range for the SD505-AHS heat detector is from 135°F to 150°F. The range for SK-Heat-HT heat detector is from 135°F to 190°F.
The SD505-AHS and SK-Heat-HT heat detectors are absolute temperature devices. This means that they respond to an alarm immediately if the temperature in the zone goes above the programmed temperature.
5. Enter the temperature at which the heat detector will respond, or use the or keys to scroll through the range or enter directly from the number keys on the annunciator, then press
ENTER.
6. Use the or keys to scroll through the range.
7. Then press
ENTER.
7-5
Page 98
Programming 151274-L8
Indicates type of event (in this case, Manual Pull alarm). See Section 6.5 for choices.
Indicates output group 1, cadence pattern 00 has been selected. 00 is a constant output cadence.
“T” Indicates output group template 1. See Section 7.4.5 for more information on output group templates.
7.3.1.3 Zone Outputs
Output groups and cadence patterns are mapped to events. They can be programmed to output when an event occurs in a zone. Some system trouble events can be mapped for the entire system. Section 6.2 of this manual contains a general explanation of mapping. The following sections explain how to select mapping options.
Note: Use of multiple notification groups may not synchronize wit h each other.
Mapping to Zone Events
Eleven types of events can occur in zones. For each event type, you can activate up to 8 output groups or output group templates, specifying a pattern for each. The following is a list of all event types:
Note: Abbreviations in parentheses are the characters that are displayed in progra mming.
Manual Pull Alarm (MP)
Water Flow Alarm (WF)
Detector Alarm (DE). This applies to heat or smoke detectors.
Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.
Pre-alarm (PR)
Supervisory (SU)
Trouble (TR)
Status Point (SP)
CO Alarm (CO)
CO Supervisory (SCO)
To map zone events to outputs, follo w these steps:
1. From the Main Menu, select 7 for Program Menu.
2. From the Program Menu, select 2 for Zone.
3. From the next menu, select 1 for Edit Zone.
4. Enter the zone number you wish to edit.
5. From the next menu, select 3 for Zone Outputs.
6. A screen similar to the one shown in Figure 7-4 will display. Press
ENTER.
7. Press the or key to toggle the group letter to either G = Group or T = output group template depend­ing on want you need for this zone. Select the event type you want to program using the or key.
8. Select options for each event that could occur in this zone. Figure 7-4 is a complete example of how you might map a zone.
Figure 7-4 Selecting Output Groups/Templates and Cadence Patterns for a Zone Event
7-6
Page 99
IntelliKnight 5808 Installation Manual 151274-L8
Zone Mapping Example
Suppose you want to program Zone 1 so that:
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the ANSI cadence pattern.
Manual pull alarm would activate Output Group 3 using constant output.
Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output groups. Figure 7-5 shows how you would program this application.
Figure 7-5 Zone Mapping Example
7-7
Page 100
Programming 151274-L8
7.3.1.4 Cadence Patterns
The cadence patterns shown in Figure 7-6 are available for use with the control panel. Cadence patterns can be selected by event type for each zone or for the entire system. Special cadence patterns
can be selected for fire drills and any auxiliary system switches used with the system.
Figure 7-6 Cadence Patterns Available with the Control Panel
7-8
Loading...