Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s,
modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until
manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper
system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in
site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or
software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are
not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum
of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for
operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes ar e adequate for
all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased
susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated
or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can
damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure.
When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal
removal. Silent Knight fire alarm control panels contain static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive
packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to
avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability
depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such
a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire.
Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type
of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located
on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to
reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit
alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following written procedures supplied with each device. System
inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written
records of all inspections should be kept.
•Add four notification/auxiliary power circuits with each 5496 Intelligent Power Module (u p to 8 per
system).
1.1.2Software Features
•Advanced smoke detector features:
–Automatic drift compensation
–Maintenance alert region
–Point status meets calibrated smoke test requirements for NFPA 72
•“JumpStart” feature for easy programming
•Non-volatile event history stores 1000 events
•A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal
•Built-in synchronization appliance support for AMSECO, Faraday, Gentex
®
Wheelock
.
1-1
®
, System Sensor®, and
IntelliKnight 5808 Installation Manual151274-L8
1.2About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the 5808. Please let
us know if the manual does not meet your needs in any way. We value your feedback!
1.2.1Terms Used in this Manual
The following terminology is used with the 5808 system:
Table 1-1 Manual Terminology
TermDescription
SLCSignaling Line Circuit
ModuleThe term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5808
panel itself.
Input PointAn addressable sensing device, such as a smoke or heat detector or a
contact monitor device.
Input ZoneA protected area made up of input points.
Output Point
(or Output Circuit)
Group (or “Output Group”)A group of output points. Operating characteristics are common to all
Output (or “Cadence”) PatternThe pattern that the output will use, for example, Constant, March Code,
MappingMapping is the process of specifying which outputs are activated when
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
output points in the group.
ANSI 3.41. Applies to zones and special system events. See Section
7.6.3.2 for additional information.
certain events occur in the system. Section 6.2 explains mapping in detail.
1-2
Introduction151274-L8
1.3Compatible Products
The chart below lists the products available from Silent Knight for use with the 5808.
Table 1-2 5808 Compatible Products
Ty pe of
Device
SK
Addressable
SLC Devices
SD
Addressable
SLC Devices
Other
Modules
Software
Misc.
ModelDescription
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5824 Serial/Parallel Printer
Interface Module
5496 Intelligent Power ModuleAdd 4 Notification/Auxiliary power circuits with
5860 and 5860R Remote Fire
Alarm Annunciator
5860TG and 5860TR Trim Ring Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray;
5865-3 and 5865-4 LED
Annunciator
5880 LED I/O ModuleDriver for up to 40 LEDs. Interfaces with
5883 General Purpose Relay
Module
5660 Silent Knight Software
Suite (SKSS)
5670 Silent Knight Software
Suite (SKSS)
7860 Telephone CordRJ31X cord for connecting phone line to the 5808.
RBBRemote Battery Box for mounting backup batteries that are too large to fit into
Allows a printer to be attached for the system for on-site event logging, detector
status and event history reports. Two maximum per system.
5496s can be used in any
each 5496 Intelligent Power Module (up to 8,
5496s per system).
Same operation, similar appearance as on-board annunciator. Up to 12 5860s
per system. 5860 is gray; 5860R is red.
5860TR is red.
LED annunciator can display up to 30 LEDs (15
red and 15 yellow). 5865-4 has key switches for
silence and reset, and a system trouble LED.
customized annunciator boards. In addition the
5880 has eight generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four,
5883s can be used with each 5880 module.
Facility management software. For communication and panel programming
with a Windows-based computer and *modem (not sold by Silent Knight, see
Table 1-3 for compatible modems). Enables remote viewing of detector status
and event history. For remote viewing of detector status and event history.
Requires a modem (not sold by Silent Knight).
the main control panel cabinet. Dimensions: 16" W x 10" H x 6" D (40.64 cm W
x 25.4 cm H x 15.24 cm D)
combination, up to a total of
12 devices on one panel.
5865-3, 5865-4, and 5880
can be used in any
combination, up to a total of
eight devices on one panel.
Note: 5865-3, 5865-4, and 5880 can be used in any combination, up to a total of eight devices on one panel.
1-3
IntelliKnight 5808 Installation Manual151274-L8
The following modems have been tested by Silent Knight for compatibility with the 5808 and the Silent Knight
Software Suite software packages:
Table 1-3: Compatible Modems
ManufacturerModel
US Robotics28.8
LifeStyle
Motorola
MultiTechMT19321ZDX
28.8, 3400 series
Premier 33.6
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical
Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 80 0-328-0103.
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following
the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72
manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by
the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke
detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are
designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm
system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For
example:
),
•Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke
detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are
located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another
level.
•The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to
alarm at various levels of smoke density. If such density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
•Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering
fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users.
For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal
operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to
1-4
Introduction151274-L8
falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do
not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing
with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas,
improper storage of flammable materials, etc.).
•Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their
sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to
protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are
located on the other side of closed or partially open doors. A warning device that activates on a different
floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake
may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other
appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to alert people with a
disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or
sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to
alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service
or temporarily out of service. For added protection against telephone line failure, backup radio transmission
systems are recommended.
•System components, though designed to last many years, can fail at any time. As a precautionary measure, it
is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s
recommendations.
•System components will not work without electrical power. If system batteries are not serviced or replaced
regularly, they may not provide battery backup when AC power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they
are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is
not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and
the people in their premises and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms
and areas of the house or building in accordance with the requirements and recommendations of the current
edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the
manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection
systems.
Requirements and Recommendations include:
1-5
IntelliKnight 5808 Installation Manual151274-L8
•Smoke Detectors shall be installed in sleeping rooms in new construction and it is recommended that they
shall also be installed in sleeping rooms in existing construction.
•It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet
long.
•It is recommended that there shall never be less then two smoke detectors per apartment or residence.
•It is recommended that smoke detectors be located in any room where an alarm control is located, or in any
room where alarm control connections to an AC source or phone lines are made. If detectors are not so
located, a fire within the room could prevent the control from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns, and/or strobes. In
residential applications, each automatic alarm initiating device when activated shall cause the operation of
an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise
levels (at least 15dB above noise) with all intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm) be located in every
bedroom and an additional notification device be located on each level of a residence.
•T o keep your fire alarm system in excellent working order, ongoing maintenance is required per the
manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter
14 of NFPA 72, 2010 Edition shall be followed. A maintenance agreement should be arranged through the
local manufacturer’s representative. Maintenance should be performed annually by authorized personnel
only.
•The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance.
As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working
properly.
1-6
151274-L8
Section 2
Agency Listings, Approvals, and Requirements
2.1Federal Communications Commission (FCC)
The following information must be provided to the telephone company before the 5808 can be connected to the
phone lines:
AManufacturer:Silent Knight by Honeywell
BModel Number:5808
CFCC registration number:AC6 USA-34758-AL-E
Ringer equivalence:0.8B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
FService Order Code:9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside
cover of this equipment is a label that contains, among other information, a product identifier. If requested, this
information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with
the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not
provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that
is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of
devices that may be connected to the public switched telephone network. This number must not exceed 5.0.
Since this product has an REN of .8, the number of devices is limited. The REN number is embedded in the FCC
registration number as 0.8B.
If the 5808 causes harm to the telephone network, the telephone company will notify you in advance that the
temporarily discontinuance of service may be required. But if advance notice is not practical, the telephone
company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint
with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect
the operation of the equipment. If this happens the telephone company will provide advance notice in order for
you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the 5808, for repair or warranty information, please contact Silent Knight technical
support at 800-446-6444 or www.silentknight.com. If the equipment is causing harm to the telephone network,
the telephone company may request that you disconnect the 5808 until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state
tariffs. You may contact the state public utility commission, public service commission or corporation
commission for information.
Since the 5808 is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing
the phone lines. If you have questions about the installation, contact your telephone company or a qualified
2-1
Agency Listings, Approvals, and Requirements151274-L8
installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
This device may not cause radio interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements. The following subsections list specific requirements for each
type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and
so on). See Section 8.7 for information on releasing operation.
1.All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2.Use the addressable smoke detectors specified in Section 5of this manual and or conventional detectors
listed in the compatibility chart. (See Appendix A.)
3.Use UL listed notification appliances compatible with the 5808from those specified in the Appendix A at the
back of this manual.
4.A full system checkout must be performed any time the panel is programmed.
Restricted Options:
•The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL
certified installations this number must be set from 1 to 3 hours.
•The system allows the use of non-latching spot type smoke detectors. This feature may not be used in
commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding
applications, and hotel/motel room applications.
•The system allows the Alarm V erification time to be set from 1 to 255 seconds. For UL certified installations
the setting must be a minimum of 60 seconds.
•Call forwarding shall not be used.
•When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.
•P.A.S feature shall be used only with automatic detectors.
2.2.2Requirements for Central Station Fire Alarm Systems
Minimum system requirements are one Silent Knight addressable initiating device.
1.Use both phone lines. Enable phone line monitors for both lines.
2.You must program a phone number and a test time so that the 5808 sends an automatic daily test to the central station.
3.The AC Loss Hours option must be set from 1-3 hours.
4.The Attempts to Report option must be set for 5.
2-2
IntelliKnight 5808 Installation Manual151274-L8
2.2.3Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used. Minimum system requirements are one
Silent Knight addressable initiating device.
2.2.4Requirements for Remote Station Protected Fire Alarm
Systems
Minimum system requirements are one Silent Knight addressable initiating device and either a 5220, Keltron
3158 or the built-in Digital Alarm Communicator Transmitter (DACT).
1.Do not exceed the current load restrictions shown in Section 3.6.1.3.
2.The AC Loss Hours option must be set from 1-3 hours.
2.2.5Requirements for Auxiliary Protected Fire Alarm Systems
for Fire Alarm Service
The Model 5220 Direct Connect module must be installed (see Section 4.13.3.1 for wiring).
2-3
151274-L8
Section 3
Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read
this section thoroughly, especially if you are installing a 5808 panel for the first time.
3.1What’s in the Box?
The 5808 ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Two keys for user operation of the on-board annunciator (installer operations require the In staller’s Code)
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
3.2Environmental Specifications
It is important to protect the 5808 control panel from water. To prevent water damage, the following conditions
should be FOLLOWED when installing the units:
•Mount indoors in dry locations only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, productio n machi nery)
When selecting a location to mount the 5808 control panel, the unit should be mounted where it wil l NOT be
exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity not exceeding 93%
noncondensing.
3-1
Before You Begin Installing151274-L8
3.3Electrical Specifications
Table 3-1 list the terminal block on the 5808 as well as a description of the each individual terminal and their
respective electrical rating.
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal No.
Label
Description
Rating
GroupIndividualVoltageCurrent
Terminal Block 1AC INPUTBAC input (hot)120 VAC, 60 Hz3.6 A
EarthEarth GroundN/AN/A
WAC input (neutral)120 VAC, 60 Hz3.6 A
Terminal Block 2SLC IN–Used for Class A installations32 VDC150 mA
+
SLC OUT–SLC terminals32 VDC150 mA
+
SLC PROG–Used for programming SLC
+
Terminal Block 3TELCO 1RINGPhone Line 1 Telco Ring
TIPPhone Line 1 Telco Tip
PHONE 1RINGPhone Line 1 Phone Ring
TIPPhone Line 1 Phone Tip
TELCO 2RINGPhone Line 2 Telco Ring
TIPPhone Line 2 Telco Tip
PHONE 2RINGPhone Line 2 Phone Ring
TIPPhone Line 2 Phone Tip
Terminal Block 4TROUBLENCNormally closed relay contact24 VDC2.5 A, resistive
COMCommon terminal
NONormally open relay contact
RELAY 1NCNormally closed relay contact24 VDC2.5 A, resistive
COMCommon terminal
NONormally open relay contact
RELAY 2NCNormally closed relay contact24 VDC2.5 A, resistive
COMCommon terminal
NONormally open relay contact
NAC1*–Notification Appliance Circuit/
+
NAC2*–Notification Appliance Circuit/
+
NAC3*–Notification Appliance Circuit/
+
NAC4*–Notification Appliance Circuit/
+
Terminal Block 5SBUSBSBUS Communication5 VDC100 mA
A
+SBUS Power24 VDC1.0 A
–
BATTERY+To Positive battery terminal24 VDCUp to 35 Ah (see Section
–To Negative battery terminal
Detectors
Auxiliary power
Auxiliary power
Auxiliary power
Auxiliary power
32 VDC150 mA
24 VDC3.0 Amp NAC or Aux
power
24 VDC3.0 Amp NAC or Aux
power
24 VDC3.0 Amp NAC or Aux
power
24 VDC3.0 Amp NAC or Aux
power
4.3 for details)
* Regulated/special application when used for releasing.
3-2
IntelliKnight 5808 Installation Manual151274-L8
Relay Outputs
NAC/Aux Power
Outputs
SBUS Devices
Phone Lines
SLC IN/OUT
AC Power
Input
1/4” spacing must be
maintained between each
of these circuit types; as well
as between power limited
and non-power limited circuits.
3.4Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone
communication or cause false alarms. To avoid induced noise, follow these guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for
the entire panel. Instead, separate the wiring as follows:
High voltageAC power Terminals
SLC loops
Audio input/output Phone line circuits
Notification circuitsNAC1 through NAC4
SBUS
Relay circuits
•Do not pull wires from different groups through the same conduit. If you must run them together, do so for
as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You
must route high and low voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it
could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed
circuits. See Figure 3-1 for an example.
•High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be
reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
Figure 3-1 Wire Routing Example
3-3
Before You Begin Installing151274-L8
On-board
Key Switch
Input
Annunciator
NAC/Aux
Power Circuits
Form C
Relays
Phone lines
SLC
In/Out
AC Power
Input
SBUS
Connections
Battery
Connections
Programming
Port
Form C
Trouble
Relay
3.5Board Assembly Diagram
Figure 3-2 Model 5808 Assembly
Figure 3-2 shows the circuit boards and annunciator. If you should need to remove the control board for repair,
remove the nine mounting screws (six on the circuit board and 3 on the heat-sink) which hold the control board
in the cabinet. Then lift the control board out of the cabin e t.
3-4
IntelliKnight 5808 Installation Manual151274-L8
3.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using SK
addressable devices (Table 3-2) or SD addressable devices (Table 3-3).
3.6.1Current Draw Worksheet Requirements
The following steps must be taken when determining 5808 current draw and standby battery requirements.
1.Use the Current Draw Worksheet to determine current draw and standby battery requirements. Use Table 32 if installing SK SLC Devices and Table 3-3 if installing SD SLC Devices to determine current draw. For
the 5808, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders.
Fill in the number of addressable devices that will be used in the system and compute the current draw
requirements for alarm and standby. Record this information in the Current Draw Worksheet on Line A.
2.Add up the current draw for all auxiliary devices and record in the table at Line B.
3.Add up all notification appliance loads and record in the table at Line C.
4.For notification appliance circuits and auxiliary devices not mentioned in the manual, refer to the device
manual for the current ratings.
5.Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the 5808 control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as the Silent Knight
5496 intelligent power module, to distribute the power loads so that the 5808 or the power expanders do not
exceed their power rating. Refer to the current draw worksheets provided with the 5496 manual so you do
not exceed their power requirements.
6.Complete the remaining instructions in the appropriate Current Draw Worksheet for determining battery size
requirements.
3.6.1.1Current Draw Worksheet for SK SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices
are installed. You can install up to 99 SK detectors and 99 SK modules. (Copy the page if additional space is
required.)
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
SK-Duct (includes PhotoR)
SK-AcclimatemAmA
SK-Heat-RORmAmA
SK-Beam (without integral test)SLCStandby/Alarm: 2 mA
SK-Beam-T (with integral test)
SK-FIRE-COSLCStandby: .30 mA mA
Addressable SLC Devices
SK-Monitor
SK-MinimonmAmA
SK-Pull-SA/SK-Pull-DAmAmA
SK-Monitor-2Standby/Alarm: .75 mA mAmA
SK-Mon-10Standby/Alarm: 3.5 mA mAmA
SK-ControlSLCStandby: .375 mA
SK-Control-6SLCStandby: 2.25 mA
SK-RelayStandby/Alarm: .255 mA mAmA
SK-Relay-6Standby/Alarm: 1.45 mA mAmA
SK-RelayMon-2Standby: 1.3 mA mA
SK-Zone
SK-Zone-6
5
(99 max.)
4
(99 max.)
(99 max.)
Standby/Alarm: .30 mA
1
Aux. PwrStandby: 2 mA mA
Alarm: 8.5 mA mA
SLCStandby/Alarm: 2 mA
Aux. PwrStandby: 2 mA mA
Alarm: 8.5 mA mA
Alarm: 7.2 mA mA
Standby/Alarm: .375 mA mAmA
Alarm: .375 mA
Aux.
Power
1
Aux. PwrStandby: 8 mA
Alarm: 24 mAmA
Aux PwrStandby: 12 mA mA
SLCStandby/Alarm: .27 mA mAmA
1
Aux PwrStandby: 50 mA mA
SLCStandby/Alarm: 2 mA mAmA
Standby: 1.7 mA mA
Alarm: 7 mA mA
Alarm: 2.25 mA
Alarm: 20 mA
Alarm: 90 mAmA
Alarm: 270 mAmA
Standby
Current
mAmA
6
mA
mA
mA
mA
mA
mA
Alarm
Current
3-6
IntelliKnight 5808 Installation Manual151274-L8
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
of
Current per Device
Devices
SLC Accessories
Aux PwrStandby: .5 mA mA
B200SR Sounder Base
SLCAlarm: .7 mA
Aux PwrStandby: .5 mA mA
B200S Sounder Base
SLCAlarm: .7 mA
B200SR-LF Low Frequency Sounder
Base
B200S-LF Low Frequency Sounder
Base
B224RB Relay BaseStandby/Alarm: .5 mA mAmA
RTS151/151 KEYAlarm: 7.5 mA
RA100ZAlarm: 10 mA
SLC Isolator Devices
SK-ISO (Isolator Module)
B224BI Isolator BaseStandby/Alarm: .5 mA
Accessories Modules
5860 Remote Fire Alarm Annunciator (12 max)
5824 Serial / Parallel Module(2 max.)Standby/Alarm: 45 mA mAmA
5496 Notification Power Expander
(99 max.)
(100 max.)
(8 max.)Standby/Alarm: 10 mA mAmA
Aux PwrStandby: 1 mAmA
AuxStandby .55 mAmA
SLCStandby .30 mAmA
Standby/Alarm: .45 mA mAmA
Standby: 20 mA mA
Alarm: 25 mAmA
Alarm: 35 mAmA
Alarm: 35 mAmA
Alarm: 125 mAmA
Alarm (high vol) 140 mAmA
Standby
Current
mA
mA
mA
mA
Alarm
Current
5895XL Intelligent Power expander(8 max.)Standby/Alarm: 10 mA mAmA
5865-4 LED Annunciator
(with reset and silence switches)
5865-3 LED Annunciator
5880 LED I/O Module
5883 Relay Interface(32 max.)
ATotal System Current
Auxiliary Devices
BAuxiliary Devices Current
Notification Appliance CircuitsRefer to devices manual for curre nt rating.
2
(8 max.)
Refer to devices manual for current rating.
Standby: 35 mA mA
Alarm: 145 mAmA
Standby: 35 mA mA
Alarm: 145 mAmA
Standby: 35 mA mA
Alarm: 200 mAmA
Standby: 0 mA mA
Alarm: 220 mA
(22 mA per
relay)
Alarm/Standby: mA mAmA
Alarm/Standby: mA mAmA
Alarm/Standby: mA mAmA
Alarm/Standby: mA mAmA
Alarm: mA
Alarm: mA
mA
mA
mA
3-7
Before You Begin Installing151274-L8
Table 3-2: Current Draw Worksheet for SK Devices
Number
Device
of
Current per Device
Devices
Alarm: mAmA
Alarm: mA
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
3
Total ampere hours required AH
Standby
Current
Alarm
Current
mA
mA
AH
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed
during that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current
that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. This should be considered
when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
5. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is calculated
by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.
6. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3.6.1.2Current Draw Worksheet for SD SLC Devices
Use Table 3-3 to determine current requirements during alarm/battery standby operation when SD SLC devices are
installed. (Copy the page if additional space is required.)
Device
For each device use this formula: This column X This column = Current per number of devices.
5808 Fire Panel (Current draw from
SLC Accessory Bases
SD505-6RB(127 max.)Standby/Alarm: .082 mA mAmA
SD505-6SB
SD505-DUCTR
SD505-DTS-K(127 max.)None, included with SD505-DUCTR worst case.
SD505-DUCT(127 max.)SLCStandby/Alarm: .5 mA mAmA
SLC Isolator Devices
SD500-LIM(254 max.)Standby/Alarm: .092 mA mAmA
SD505-6IB(127 max.)
Accessories Modules
5860 Remote Fire Alarm
Annunciator
5824 Serial/Parallel Printer
Interface
5865-4 LED Annunciator
(with reset and silence switches)
5865-3 LED AnnunciatorStandby: 35 mA mA
5880 LED I/O ModuleStandby: 35 mA mA
5883 Relay Interface
5496 Notification Power Expander
5895XL Intelligent Power ExpanderStandby/Alarm: 10 mA mAmA
5865-4 LED Annunciator
(with reset and silence switches)
Number of
Devices
(40 max.)
(127 max.)
(127 max.)
(127 max.)
(12 max.)
(2 max.)
(8 max.)
(32 max.)
(8 max.)
(8 max.)
1
Current per Device
Aux. PwrStandby: 10 mA mA
Alarm: 220 mAmA
LED: 10 mA mAmA
SLCStandby/Alarm: .55 mA mAmA
SLCStandby/Alarm: .55 mA mAmA
1
Aux. PwrStandby: 20 mA mA
Alarm: 106 mAmA
Aux. PwrStandby: 1 mA mA
Alarm: 32 mAmA
SLCStandby/Alarm: .082 mA mAmA
Aux. Pwr
SLCStandby/Alarm: .5 mA mAmA
Standby: 20 mA mA
Alarm: 65 mAmA
Standby/Alarm: 45 mA mAmA
Standby: 35 mA mA
Alarm: 145 mAmA
Alarm: 145 mAmA
Alarm: 200 mAmA
Standby: 0 mA mA
Alarm: 220 mA
Standby/Alarm: 10 mA mAmA
Standby: 35 mA mA
Alarm: 145 mAmA
Standby: 20 mA
Alarm: 62 mA
(22 mA per relay)
2
mA
2
Standby
Current
mA
mA
Alarm
Current
ATotal System Current
Auxiliary Devices
BAuxiliary Devices Current
3
Refer to devices manual for current rating.
Alarm/Standby: mA mAmA
Alarm/Standby: mA mAmA
Alarm/Standby: mA mAmA
3-9
Before You Begin Installing151274-L8
Table 3-3: Current Draw worksheet for SD Devices
Device
Notification Appliance CircuitsRefer to devices manual for current rating.
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes =.0833 hours)H
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
4
Number of
Devices
Current per Device
Alarm: mA
Alarm: mA
Alarm: mA
Alarm: mA
Total ampere hours
required
Standby
Current
mA
mA
mA
mA
mA
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120
VAC or 240 VAC.
3. If using door holders, you do not need to consider door ho lder current for alarm/battery standby, because
power is removed during that time. However, during normal operation, door holders draw current and must
be included in the 6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm
current.
Alarm
Current
3.6.1.3Maximum Battery Standby Load
The table below shows the maximum battery standby load for the 5808 based on 24 and 60 hours of standby. The
standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2 for SK devices and
Table 3-3 for SD devices) must be less than the number shown in the Table 3-4 for the battery size used and
standby hours required.
Table 3-4: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH221 mA85 mA
12 AH475 mA190 mA
18 AH685 mA270 mA
35 AH1.1 A450 mA
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).
Warning!
Silent Knight does not support the use of batteries smaller than those listed in table above. If you use a battery too small for
the installation, the system could overload the battery resulting in the installation having less than the required 24 hours
standby power. Use Table 3-4 to calculate the correct battery amperes/hour rating needed for your installation.
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
3-10
IntelliKnight 5808 Installation Manual151274-L8
3.7Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5808
system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks.
Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Task
See Sec.
(for more info.)
Main Panel Hardware Installation
Mount the control panel cabinet.
Connect AC.
Install 5860 Remote Fire Alarm Annunciator modules if used.
Install 5865 or LED Annunciator modules if used.
Install 5880 LED I/O module if customized LED annunciation will be used.
Connect phone lines.
Install notification appliances.
Install auxiliary power devices (if used).
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.
Connect batteries (typically last step).
4.1
4.2
4.5
4.8
4.7
4.10
4.11
4.11.2
4.6
4.3
SLC Device Hardware Installation
Perform these steps before running JumpStart.
Connect device bases to the loop.
Set device addresses.
Physically connect detectors to their bases. Connect relay and contact monitor modules.
SK 5.5
SD 5.7
SK 5.6
SD 5.8
5.4 & see device
install instructions
JumpStart
JumpStart is for initial system programming. JumpStart automatically selects some options for SLC
devices. See “Input Point Configuration” section of this chart for other options. JumpStart makes selections
for the following options. You can customize options, if necessary.
Device type (detector or switch) configured by JumpStart.To change, see 7.5
Program type of detector (heat, photoelectric, or ionization) selected by JumpStart.To change, see 7.5
6.1 & 7.7
System Software Configuration
Select low AC hours report time (3 hours by default).
Select Auto Test Time (2:00 AM by default).
Enable/disable automatic DST adjustment feature (enabled by default).
Change clock display format (12-hour with AM/PM by default).
Set up reporting accounts.
Select options for phone lines.
Select system-wide response to trouble conditions, if desired.
Select system-wide cadence patterns for special conditions (fire drill, Aux1 and Aux2
7.6.4.3
7.6.1.2
7.6.4.4
7.6.4.4
7.6.1
7.6.2
7.6.3
7.6.3.2
alarms) if desired.
Customize banner message (message that displays on LCD in normal mode) if desired.
7.6.7
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart). You can change options
selected by JumpStart, if necessary and further customize input point options.
3-11
Before You Begin Installing151274-L8
Task
Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart
assigns all switches as Manual Pull type.)
If the installation includes duct detectors, program detector type. (JumpStart does not
distinguish duct detectors from ordinary smoke detectors.)
Assign a name (or description) to the point.
Assign input points to zones, if necessary. (JumpStart assigns all input points to Zone 1.)
Zone Configuration
Add the zone to the system if it does not already exist. (Zone 1 created by JumpStart.)
Program a name (or description) for the zone.
Select alarm delay options (detection characteristics) for zone.
Select heat detector trip temperature and. (JumpStart selects 150°F for heat detectors
Enable circuits used for notification appliances through programming, if necessary.
(JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always output
continuously (constant pattern), even if assigned to an Output Group that uses a different
output pattern.
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming.
Select type of power (door holder, constant, or resettable, or sounder sync)
Addressable relay modules
Assign addressable relay modules to output groups through programming. (JumpStart
assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming.
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused output
circuits, they will cause a trouble condition (unless an EOL resistor is used).
Select a name for the point, if desired.
Output Group Configuration
Add the group to the system if it does not already exist.
Assign output points to the group.
Program a name (or description) for the group, if desired.
Select “group properties” (see below).
Latching / non-latching
Silencing option
Select options for activation with system switches.
Map zones to output groups that will activate when zone goes into alarm.
Select a cadence pattern for outputs in the zone.
See Sec.
(for more info.)
7.5
7.5
7.5.4
7.5.4
7.3.2
7.3.1.1
7.3.1.1
7.3.1.2
7.4.1
7.4.1
7.5
7.5
7.5
7.5.3
7.5
7.5.4
7.4.2
7.5
7.4.1.1
7.4.1.2
7.4.1
7.4.1
7.3.1.3
7.3.1.4
3-12
151274-L8
Section 4
Control Panel Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while
installing or servicing.
4.1Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the 5808 panel.
The 5808 cabinet dimensions are:
16" W x 26.4" H x 3.5" D (40.64 cm W x 67.06 cm H x 8.89 cm D).
The 5808 panel should be located within a secured area, where it is accessible to main drop wiring runs and
where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear
alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and
trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete,
especially when moisture is expected, attach a piece of 3/4 inch plywood to the concrete surface and then attach
the 5808 to the plywood. Also mount any other desired components to the plywood.
DO NOT flush-mount the 5808 cabinet in a wall designated as a fire break.
4.1.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.1.2Removing the 5808 Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by
removing the screws that hold the control panel in to the cabinet. Do not attempt to disassemble the circuit
boards.
4-1
Loading...
+ 150 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.