Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s,
modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until
manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper
system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in
site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or
software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are
not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum
of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for
operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes ar e adequate for
all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased
susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated
or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can
damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure.
When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal
removal. fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to
avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability
depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such
a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire.
Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type
of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located
on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to
reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit
alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following written procedures supplied with each device. System
inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written
records of all inspections should be kept.
Special Characters Lists .........................................................................................................B-1
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
Model 5700 Basic Operating Instructions
6
Section 1
Introduction
The 5700 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements
of UL 864.
1.1Overview of Basic System
1.1.1Hardware Features
•The 5700 has one signaling line circuit (SLC) that supports 50 SK detectors and 50 SK modules or 50 SD
protocol devices.
•2.5A of output power is available through 2 sets of terminals for notification appliance circuits or aux iliary
applications. Each circuit is power limited per UL 864 and can source up to 2.5A (total output power for
both circuits must not exceed 2.5A).
•Built-in dual phone line, digital alarm communicator/transmitter (D ACT).
•Reports events to central station by point or by zone.
•UL Listed for pre-action and deluge releasing systems.
•Two general purpose Form C program mab le relays.
•One Form C Trouble Relay.
•Basic system operation can be performed from the on-board, or any remote annunciator.
•Up to 20 user profiles can be programmed, each having custom access code, and main menu items.
•Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
•Can be used with Model 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one
control panel. See Sections 4.7 and 4.8 for additional information on these models.
•Printing of detector status, event history, and real time event log available through the Model 5824 Serial /
Parallel Interface (sold separately).
•125 software zones, 125 output groups.
•Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight 5895XLs per system).
See note below.
•Add four Notification/Auxiliary power circuits with each 5496 Intelligent Power Module (up to eight 5496s
per system). See note below.
Note: The system can support a maximum of eight intelligent power modules, either the 5895XL or 5496, in any
combination.
151295
1-1
Introduction151295
1.1.2Software Features
•Advanced smoke detector features:
–Automatic drift compensation
–Maintenance alert region
–Point status meets calibrated smoke test requirements for NFPA 72
•“JumpStart” feature for easy programming
•Non-volatile event history stores 1000 events
•A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal
•Built-in synchronization appliance support for Faraday, Gentex
®
, Wheelock®, or System Sensor
®
1.2About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the 5700. Please let
us know if the manual does not meet your needs in any way. We value your feedback!
1.2.1Terms Used in this Manual
The following terminology is used with the 5700 system:
Table 1-1 Manual Terminology
TermDescription
SLCSignaling Line Circuit
ModuleThe term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes
the 5700 panel itself.
Input PointAn addressable sensing device, such as a smoke or heat
detector or a contact monitor device.
Input ZoneA protected area made up of input points.
Output Point
(or Output Circuit)
Group (or “Output Group”)A group of output points. Operating characteristics are common
Output (or “Cadence”) PatternThe pattern that the output will use, for example, Constant,
MappingMapping is the process of specifying which outputs are activated
A notification point or circuit for notification appliances. Relay
circuits and auxiliary power circuits are also considered output
points.
to all output points in the group.
March Code, ANSI 3.41. Applies to zones and special system
events. See Section 7.6.3.2 for additional information.
when certain events occur in the system. Section 6.2 explains
mapping in detail.
1-2
Model 5700 Installation and Operation Manual
1.3Compatible Products
The chart below lists the products available from Silent Knight for use with the 5700.
Table 1-2 5700 Compatible Products
Type of
Device
SK
Addressable
SLC Devices
SD
Addressable
SLC Devices
Other
Modules
Software
Misc.
ModelDescription
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5824 Serial/Parallel Printer
Interface Module
5895XLProvides additional power, six Flexput circuits, and two Form C relays. Max 8 per
5496 Intelligent Power
Module
5860TG and 5860TR Trim
Ring
5865-3 and 5865-4 LED
Annunciator
5880 LED Driver ModuleDriver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition the
5883 General Purpose
Relay Module
5660 Silent Knight
Software Suite (SKSS)
5670 SKSS Facility
Management Software
7860 Telephone CordRJ31X cord for connecting phone line to the 5700.
7628UL Listed End-of-line resistor.
DF-50Dead Front insert.
Allows a printer to be attached for the system for on-site event logging, detector status
and event history reports. Two maximum per system.
system. See 5895XL Installation Manual (PN 151142) for more information.
Provides 4 additional Notification Appliance Circuits/Auxiliary power. (Up to 8 per 5700
system.)
Trim ring kits for surface mounting the 5860/5860R annunciator.
5860TG is gray; 5860TR is red.
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key
switches for silence and reset, and a system trouble LED.
5880 has eight generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can
be used with each 5880 module.
For communication and panel programming with a Windows-based computer and
modem (not sold by Silent Knight, see Table 1-3 for compatible modems). Enables
remote viewing of detector status and event history.
For remote viewing of detector status and event history. Requires a modem (not sold by
Silent Knight).
Note: 5865-3, 5865-4, and 5880 can be used in any combination, up to a total of eight devices on one panel.
1-3
Introduction151295
The following modems have been tested by Silent Knight for compatibility with the 5700 and the Silent Knight
Software Suite software packages:
Table 1-3: Compatible Modems
ManufacturerModel
US Robotics28.8
Lifestyle
Motorola
Multi-TechMT19321ZDX
28.8, 3400 series
Premier 33.6
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical
Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 80 0-328-0103.
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following
the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72
manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by
the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke
detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are
designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm
system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For
example:
),
•Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke
detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold stratify, and not reach the ceiling or upper walls where detectors are
located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another
level.
•The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to
alarm at various levels of smoke density. If such density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
•Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo
electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little
visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better
than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type of detector may not provide adequate warning of
a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users.
For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal
1-4
Model 5700 Installation and Operation Manual
operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to
falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do
not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing
with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas,
improper storage of flammable materials, etc.).
•Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their
sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to
protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are
located on the other side of closed or partially open doors. A warning device that activates on a different
floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake
may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other
appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to alert people with a
disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or
sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to
alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service
or temporarily out of service. For added protection against telephone line failure, backup radio transmission
systems are recommended.
•System components, though designed to last many years, can fail at any time. As a precautionary measure, it
is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s
recommendations.
•System components will not work without electrical power. If system batteries are not serviced or replaced
regularly, they may not provide battery backup when AC power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they
are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is
not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and
the people in their premises and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms
and areas of the house or building in accordance with the requirements and recommendations of the current
edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the
manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection
systems.
1-5
Introduction151295
Requirements and Recommendations include:
•Smoke Detectors shall be installed in sleeping rooms in new construction and it is recommended that they
shall also be installed in sleeping rooms in existing construction.
•It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet
long.
•It is recommended that there shall never be less then two smoke detectors per apartment or residence.
•It is recommended that smoke detectors be located in any room where an alarm control is located, or in any
room where alarm control connections to an AC source or phone lines are made. If detectors are not so
located, a fire within the room could prevent the control from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns, and/or strobes. In
residential applications, each automatic alarm initiating device when activated shall cause the operation of
an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise
levels (at least 15dB above noise) with all intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm) be located in every
bedroom and an additional notification device be located on each level of a residence.
•T o keep your fire alarm system in excellent working order, ongoing maintenance is required per the
manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter
14 of NFPA 72, 2010 Edition shall be followed. A maintenance agreement should be arranged through the
local manufacturer’s representative. Maintenance should be performed annually by authorized personnel
only.
•The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance.
As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working
properly.
1-6
Section 2
Agency Listings, Approvals, and Requirements
Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit.
Testing and maintenance should be performed according to NFPA 72.
2.1Federal Communications Commission (FCC)
The following information must be provided to the telephone company before the 5700 can be connected to the
phone lines:
AManufacturer:Silent Knight by Honeywell
BModel Number:5700
CFCC registration number:US: AC6AL05B205700
Ringer equivalence:0.5B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
FService Order Code:9.0F
151295
1.This device may not be directly connected to coin telephone or party line services.
2.This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing
company or return to:
3.If the 5700 causes harm to the telephone network, the telephone company will notify the user in advance that
temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the user as soon as possible. Users have the right to file complaints, if necessary, with the
Federal Communications Commission.
4.The telephone company may make changes in its facilities, equipment, operations, or procedures that could
affect the operation of the equipment. If this happens, the telephone company will provide advance notice to
allow you to make the necessary modifications to maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
This device may not cause radio interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
a)This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the
wiring diagram of this equipment is a label that contains, among other information, a product identifier in
the format US: AC6AL05B-205700. If requested, this number must be provided to the telephone company.
b) See Section 4.10 for phone jack information.
c)A plug and jack used to connect this equipment to the premises wiring and telephone network must comply
with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord
and modular plug is provided with this product. It is designed to be connected to a compatible modular jack
2-1
Agency Listings, Approvals, and Requirements151295
that is also compliant. See installation instructions for details.
d) The REN is used to determine the number of devices that may be connected to a telephone line. Excessive
RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but
not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may
be connected to a line, as determined by the total RENs, contact the local telephone company. For products
approved after July 23, 2002, the REN for this product is part of the product identifier that has the format
US: AC6AL05B-205700. The digits represented by ## are the REN without a decimal point (e.g., 03 is a
REN of 0.3). For earlier products, the REN is separately shown on the label.
e)If this equipment 5700 causes harm to the telephone network, the telephone company will notify you in
advance that temporary discontinuance of service may be required. But if advance notice isn't practical, the
telephone company will notify the customer as soon as possible. Also, you will be advised of yo ur right to
file a complaint with the FCC if you believe it is necessary.
f)The telephone company may make changes in its facilities, equipment, operations or procedures that could
affect the operation of the equipment. If this happens the telephone company will provide advance notice in
order for you to make necessary modifications to maintain uninterrupted service.
g) If trouble is experienced with this equipment 5700, for repair or warranty information, please contact Silent
Knight (see Section 1.4). If the equipment is causing harm to the telephone network, the telephone company
may request that you disconnect the equipment until the problem is resolved.
h) See warranty in back of this manual for repair and replacement information.
i)Connection to party line service is subject to state tariffs. Contact the state public utility commission, public
service commission or corporation commission for information.
j)If your home has specially wired alarm equipment connected to the telephone line, ensure the installation of
this 5700 does not disable your alarm equipment. If you have questions about what will disable alarm
equipment, consult your telephone company or qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiring AC power should consider including an advisory notice in their
customer information suggesting the customer use a surge arrestor. Telephone companies report that electrical
surges, typically lightning transients, are very destructive to customer terminal equipment connected to AC
power sources. This has been identified as a major nationwide problem.
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements. The following subsections list specific requirements for each
type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and
so on). See Section 8.6 for information on releasing operation.
1.All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2.Use the addressable smoke detectors specified in Section 5.2 of this manual.
3.Use UL listed notification appliances compatible with the 5700 from those specified in the Appendix at the
back of this manual.
4.A full system checkout must be performed any time the panel is programmed.
Restricted Options:
•The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL
certified installations this number must be set from 1 to 3 hours.
•The system allows the use of non-latching spot type smoke detectors. This feature may not be used in
commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding
2-2
Model 5700 Installation and Operation Manual 151295
applications, and hotel/motel room applications.
•The system allows the Alarm V erification time to be set from 1 to 255 seconds. For UL certified installations
the setting must be a maximum of 60 seconds.
•Call forwarding shall not be used.
•When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.
•P.A.S (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2Requirements for Central Station Fire Alarm Systems
1.Use both phone lines. Enable phone line monitors for both lines.
2.You must program a phone number and a test time so that the 5700 sends an automatic daily test to the central station.
3.The AC Loss Hours option must be set from 6-12 hours.
4.The Attempts to Report option must be set for 5.
2.2.3Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4Requirements for Remote Station Protected Fire Alarm
Systems
1.Do not exceed the current load restrictions shown in Section 3.6.
2.The AC Loss Hours option must be set from 1-3 hours.
2-3
Section 3
Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read
this section thoroughly, especially if you are installing a 5700 panel for the first time.
3.1What’s in the Box?
The 5700 ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Installation and Operation manual P/N 151295
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
3.2Environmental Specifications
151295
It is important to protect the 5700 control panel from water. T o prevent water damage, the following precautions
should be FOLLOWED when installing the units:
•Intended for indoor use in dry locations only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, productio n machi nery)
When selecting a location to mount the 5700 control panel, the unit should be mounted where it wil l NOT be
exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93%
at 30°C (86°F) noncondensing.
3-1
Before You Begin Installing151295
3.3Electrical Specifications
Table 3-1 list the terminal block on the 5700 as well as a description of the each individual terminal and their
respective electrical rating. For location of the terminals refer to Figure 3-2. See also Section 4 for installation.
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal No.
Terminal Block 1
Terminal Block 2
Label
Rating
Description
GroupIndividualVoltageCurrent
NONormally open relay contact
RELAY 1
RELAY 2
TELCO 1
PHONE 1
TELCO 2
PHONE 2
TROUBLE
SLC IN
SLC OUT
SLC PROG
SBUS
NAC1*
NAC2*
NCNormally closed relay contact
NONormally open relay contact
NCNormally closed relay contact
RINGPhone Line 1 Telco Ring
TIPPhone Line 1 Telco Tip
RINGPhone Line 1 Phone Ring
TIPPhone Line 1 Phone Tip
RINGPhone Line 2 Telco Ring
TIPPhone Line 2 Telco Tip
RINGPhone Line 2 Phone Ring
TIPPhone Line 2 Phone Tip
NONormally open relay contact
NCNormally closed relay contact
–
+
–
+
–
+
–
+
A
B
–
+
–
+
Used for Class A installations32 VDC100 mA
SLC terminals32 VDC100 mA
Used for programming SLC
Detectors
SBUS Power27.4 VDC0.5 A
SBUS Communication5 VDC100 mA
Notification Appliance Circuit/
Auxiliary power
Notification Appliance Circuit/
Auxiliary power
27.4 VDC2.5 A, resistiveCOMCommon terminal
27.4 VDC2.5 A, resistiveCOMCommon terminal
27.4 VDC2.5 A, resistiveCOMCommon terminal
32 VDC100 mA
27.4 VDC
27.4 VDC
2.5 Amp NAC or Aux
power
2.5 Amp NAC or Aux
power
*Regulated NAC application. When programmed for releasing, NAC are Special Application.
3-2
Model 5700 Installation and Operation Manual 151295
Relay
NAC/Aux Power
Outputs
SBUS
Phone
SLC IN/OUT
AC Power
Input
Devices
Lines
Outputs
Maintain at least 1/4” spacing
between power limited and
non-power limited circuits.
Battery
3.4Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone
communication or cause false alarms. To avoid induced noise, follow these guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for
the entire panel. Instead, separate the wiring as follows:
High voltageAC power Terminals
SLC loops
Audio input/output Phone line circuits
Notification circuitsNAC1 through NAC2
SBUS
Relay circuits
•Do not pull wires from different groups through the same conduit. If you must run them together, do so for
as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You
must route high and low voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it
could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed
circuits. See Figure 3-1 for an example.
•High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be
reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
Figure 3-1 Wire Routing Example
3-3
Before You Begin Installing151295
On-board
Annunciator
NAC/Aux
Power Circuits
Form C
Relays
Phone Lines
SLC In/Out,
SLC Programming
AC Power
Input
SBUS
Connections
Battery
Connector
Programming
Port
Form C
Trouble Relay
Terminal Block 2
Terminal Block 1
120 VAC,
60 Hz, 1.5A
24 VDC
3.5Board Assembly Diagram
Figure 3-2 Model 5700 Assembly
Figure 3-2 shows the circuit boards, and annunciator. If you should need to remove the control board for repair,
remove the three mounting screws which hold the control board in the cabinet. Then lift the control board out of
the cabinet.
3-4
Model 5700 Installation and Operation Manual 151295
3.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using SK
addressable devices (Table 3-2) or SD addressable devices (Table 3-3).
3.6.1Current Draw Worksheet Requirements
The following steps must be taken when determining 5700 current draw and standby battery requirements.
1.For the 5700, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of addressable devices that will be used in the system and compute the current draw
requirements for alarm and standby. Record this information in the Current Calculation Worksheet at Line
A.
2.Add up the current draw for all auxiliary devices and record in the table at Line B.
3.Add up all notification appliance loads and record in the table at Line C.
4.For notification appliance circuits and auxiliary devices not mentioned in the manual, refer to the device
manual for the current ratings.
5.Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
2.5 A. This is the maximum alarm current for the 5700 control panel.
If the current is above 2.5 A you will need to use a notification power expander(s) such as the Silent Knight
5496 intelligent power module, to distribute the power loads so that the 5700 or the power expanders do not
exceed their power rating. Refer to the current draw worksheets provided with the 5496 manual so you do
not exceed their power requirements.
6.Complete the remaining instructions in the Current Calculation Worksheet for determining battery size
requirements.
3-5
Before You Begin Installing151295
3.6.2Current Draw Worksheet for SK SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices
are installed. (Copy the page if additional space is required.) You can install up to 50 SK detectors and 50 SK
modules.
Table 3-2: Current Calculation Worksheet for SK Devices
Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
Table 3-2: Current Calculation Worksheet for SK Devices
Device
BAuxiliary Devices Current
Notification Appliance CircuitsRefer to device manual for current rating.
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
3
# of
Devices
Current per Device
Alarm: mA
Alarm: mA
Alarm: mA
Total ampere hours
required
Standby
Current
Alarm
Current
mA
mA
mA
mA
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed
during that time. However, during normal operation, door holders draw current and must be included in the 2.5A total current
that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-Beam-T draws a maximum of 500mA from auxiliary power only when the test feature is used. This should be considered
when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
5. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is calculated
by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.
6. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3.6.3Current Draw Worksheet for SD SLC Devices
Use Table 3-3 to determine current requirements during alarm/battery standby operation when SD SLC devices
are installed. (Copy the page if additional space is required).
Table 3-3: Current Calculation Worksheet for SD Devices
Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
Table 3-3: Current Calculation Worksheet for SD Devices
Device
BAuxiliary Devices Current
Notification Appliance CircuitsRefer to device manual for current rating.
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
4
# of
Devices
Current per Device
Alarm/Standby: mAmAmA
Alarm: mA
Alarm: mA
Alarm: mA
Alarm: mA
Total ampere hours
required
Standby
Current
Alarm
Current
mA
mA
mA
mA
mA
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or
240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3.6.4Maximum Battery Standby Load
The table below shows the maximum battery standby load for the 5700 based on 24 and 60 hours of standby. The
standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-3) must be less than the
number shown in the table below for the battery size used and standby hours required.
Table 3-4 Maximum Battery Standby Load
Rechargeable Battery Size
7 AH221 mA85 mA
18 AH675 mA250 mA
35 AH1.1 A450 mA
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).
Warning!
Silent Knight does not support the use of batteries smaller than those listed in table above. If you use a battery too small
for the installation, the system could overload the battery resulting in the installation having less than the required 24
hours standby power. Use the Current Calculation Worksheet to calculate the correct battery amperes/hour rating needed
for your installation.
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
3-10
Model 5700 Installation and Operation Manual 151295
3.7Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5700
system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks.
Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Task
See Sec.
(for more info.)
Main Panel Hardware Installation
Mount the control panel cabinet.4.1
Connect AC.4.2
Connect phone lines.4.10
Install 5860 Remote Fire Alarm Annunciator modules if used.4.5
Install 5865 or LED Annunciator modules if used.4.8
Install 5880 LED I/O module if customized LED annunciation will be used. 4.7
Install notification appliances.4.11
Install auxiliary power devices (if used).4.11.2
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.4.6
Connect batteries (typically last step).4.3
SLC Device Hardware Installation. Perform these steps before running JumpStart.
Connect device bases to the loop.SK 5.5
Set device addresses.SK 5.6
Physically connect detectors to their bases. Connect relay and contact monitor modules.5.4 & see device
install instructions
JumpStart
JumpStart is for initial system programming. JumpStart automatically selects some options for SLC
devices. See “Input Point Configuration” section of this chart for other options.
JumpStart makes selections for the following options. You can customize options, if necessary.
Device type (detector or switch) configured by JumpStart.To change, see 7.5
Program type of detector (heat, photoelectric, or ionization) selected by JumpStart.To change, see 7.5
6.1 & 7.7
System Software Configuration
Select low AC hours report time (3 hours by default).7.6.6.3
Select Auto Test Time (2:00 AM by default).7.6.1.2
Enable/disable automatic DST adjustment feature (enabled by default).7.6.6.4
Change clock display format (12-hour with AM/PM by default).7.6.6.4
Set up reporting accounts.7.6.1
Select options for phone lines.7.6.2
Select system-wide response to trouble conditions, if desired.7.6.3
Select system-wide cadence patterns for special conditions (fire drill, Aux1 and Aux2 alarms)
if desired.
Customize banner message (message that displays on LCD in normal mode) if desired. 7.6.9
Input Point (SLC Device) Configuration
SD 5.7
SD 5.7
7.6.3.2
3-11
Before You Begin Installing151295
Task
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart). You can change
options selected by JumpStart, if necessary and further customize input point options.
Select device type SK or SD). Only one device type can be used per control panel.7.2
Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns all
switches as Manual Pull type.)
If the installation includes duct detectors, program detector type. (JumpStart does not
distinguish duct detectors from ordinary smoke detectors.)
Assign a name (or description) to the point.7.5.4
Assign input points to zones, if necessary. (JumpStart assigns all input points to Zone 1.)7.5.4
See Sec.
(for more info.)
7.5
7.5
Zone Configuration
Add the zone to the system if it does not already exist. (Zone 1 created by JumpStart.)7.3.2
Program a name (or description) for the zone.7.3.1.1
Select alarm delay options (detection characteristics) for zone.7.3.1.1
Select heat detector trip temperature and/or. (JumpStart selects 150°F for heat detectors and
Enable circuits used for notification appliances through programming, if necessary.
(JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always output continuously
(constant pattern), even if assigned to an Output Group that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming.7.5
Select type of power (door holder, constant, or re-settable)7.5
Addressable relay modules
Assign addressable relay modules to output groups through programming. (JumpStart
assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming. 7.5.3
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused output circuits,
they will cause a trouble condition (unless an EOL resistor is used).
Select a name for the point, if desired.7.5.4
7.4.1
7.4.1
7.5
7.5
Output Group Configuration
Add the group to the system if it does not already exist.7.4.2
Assign output points to the group.7.5
Program a name (or description) for the group, if desired.7.4.1.1
Select “group properties” (see below).
Latching / non-latching7.4.1.2
Silencing option7.4.1.2
Select options for activation with system switches.7.4.1.2
Map zones to output groups that will activate when zone goes into alarm.7.3.1.3
Select a cadence pattern for outputs in the zone.7.3.1.4
3-12
Section 4
Control Panel Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while
installing or servicing.
4.1Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the 5700 panel.
The 5700 cabinet dimensions are: 12¾” W x 15-1/8” H x 3-3/8” D (32.39 cm W x 38.42 cm H x 8.57 cm D).
The 5700 panel should be located within a secured area, where it is accessible to main drop wiring runs and
where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear
alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and
trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete,
especially when moisture is expected, attach a piece of 3/4 inch plywood to the concrete surface and then attach
the 5700 to the plywood. Also mount any other desired components to the plywood.
151295
DO NOT flush-mount the 5700 cabinet in a wall designated as a fire break.
4.1.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.1.2Removing the 5700 Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by
removing the screws that hold the control panel in to the cabinet. Do not attempt to disassemble the circuit
boards.
4.1.3Dead Front Installation and removal
This section provides instructions to install and or remove the optional dead front (DF-50) for the control panel
cabinet.
4-1
Control Panel Installation151295
Dead Front
Panel
4.1.3.1Installing the Dead Front
Follow these steps to properly install the dead front panel into the control panel cabinet.
1.Remove the top two annunciator screws, do not discard them they will be reused. See Figure 4-1 for annunciator screw location.
2.Set the dead front into the cabinet as shown in Figure 4-1.
3.Reinsert the two annunciator screws as shown in Figure 4-1.
Figure 4-1 Dead Front Installation and Removal
4.Insert the two screws with the star washers into the bottom of the cabinet to secure the dead front into place.
See Figure 4-1.
4.1.3.2Dead Front Removal
Follow these steps to properly remove the dead front panel from the control panel cabinet.
1.Remove the two annunciator screws, do not discard them. See Figure 4-1.
2.Remove the two screws and star washers from the bottom of the cabinet. See Figure 4-1.
3.Remove the dead front panel from the control panel cabinet.
4.Reinsert the two annunciator screws. See Figure 4-1.
4-2
Model 5700 Installation and Operation Manual 151295
To AC
Ground
Supervised
4.2AC Connection
At installation, connect the AC terminals to the power source as shown in Figure 4-2. It may be necessary for a
professional electrician to make this connection.
The AC terminals are rated at 120 VAC, 60 Hz, 1.5 A.
Figure 4-2 120VAC Power Connection
4-3
Control Panel Installation151295
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Recognized
UL Recognized
Supervised
12V Battery
Battery 1
12V Battery
Battery 2
4.3Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 7
AH, larger capacity batteries can be housed in a Remote Battery Box (P/N RBB). See Section 4.3.1 for
deteails.Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load
calculation (see Section 3.6).
Maximum battery charging current 3.1 Amps.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
The following steps and diagram explain how to connect the batteries.
1.Connect the black wire from the control panel negative (–) battery terminal to the negative (–) side of Battery #2.
2.Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2 to the (–) negative
side of Battery #1.
3.Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1.
Figure 4-3 Battery Connection
4-4
Model 5700 Installation and Operation Manual 151295
Cabinet
Mounting Holes
4.3.1RBB Accessory Cabinet
The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries
that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size.
The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1.Mount the accessory cabinet. See figure Figure 4-4 for the four cabinet mounting holes.
•If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is neces-
sary because the weight of the batteries inside the accessory
cabinet could cause the cabinet to pull away from the drywall.
•When mounting on concrete , especially when mo isture is expected, attach a piece of ¾” plywood to the
concrete surface and then attach the RBB cabinet to the plywood.
•If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18"
away from the main control panel cabinet. This will ensure that the battery cables reach the battery terminals.
Figure 4-4 RBB Cabinet Mounting Holes
2.Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-5.
Figure 4-5 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
4-5
Control Panel Installation151295
Conduit
Conduit
Coupler
++
--
RBB Cabinet
Cover Screws
RBB Cabinet
Cover Screws
Cover Plate
Mounting Keyholes
3.Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-6.
Figure 4-6 Battery Connections in the RBB Cabinet
Note: Figure 4-6 is an example of how the wire connections can be routed. However, any other cabinet knock-
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets.
4.Connect battery leads to the backup battery terminals. See Figure 4-6.
Observe the proper polarity to prevent damage to the batteries or the control panel.
5.Insert the RBB cover screws into the cover mounting holes (see Figure 4-6).
Screw the cover screw 3/4 of the way into the cover mounting hole.
6.Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-7.
7.Slide the cover into place and tighten the cover mounting screws. See Figure 4-7.
4-6
Model 5700 Installation and Operation Manual 151295
4.4SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring configurations
(Class B).
4.4.1Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum wiring distance that
can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to
calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case
current draw is calculated by adding the individual worst case currents for each module. The individual worst
case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp.
Model NumberWorst Case Current Draw
5860 Fire Annunciator.100 amps
5824 Parallel/Serial Interface.040 amps
5880 LED Driver Module.200 amps
5865 LED Fire Annunciator.145 amps
5496 Notification Power Supply.010 amps
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance the modules can be
located from the panel on a single wire run. The table insures 6.0 volts of line drop maximum. In general, the
wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet,
regardless of gauge used. (The formula used to generate this chart is shown in the note below).
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.1001852 ft.4688 ft.* 6000 ft.* 6000 ft.
0.200926 ft.2344 ft.3731 ft.5906 ft.
0.300617 ft.1563 ft.2488 ft.3937 ft.
0.400463 ft.1172 ft.1866 ft.2953 ft.
0.500370 ft.938 ft.1493 ft.2362 ft.
0.600309 ft.781 ft.1244 ft.1969 ft.
0.700265 ft.670 ft.1066 ft.1687 ft.
0.800231 ft.586 ft.933 ft.1476 ft.
0.900206 ft.521 ft.829 ft.1312 ft.
1.000 (Max)185 ft.469 ft.746 ft.1181 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
4-7
Control Panel Installation151295
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire GaugeOhms per 1000 feet (Rpu)
2216.2
186.4
164.02
142.54
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules:
2 - Module 5860 Fire Annunciator
1 - 5496 Notification Power Expander
* 500
1 - 5865 LED Fire Annunciator
1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps
5496 Current Draw = 1 x .010 amps= .010 amps
5865 Current Draw= 1 x .200 amps= .145 amps
5824 Current Draw= 1 x .040 amps= .040 amps
Total Worst Case Current Draw= .395 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
4-8
Model 5700 Installation and Operation Manual 151295
Supervised
Power Limited
5495 or 5499
SBUS Device
Control
Panel
Supervised
Power Limited
4.4.2Wiring Configurations
Figure 4-8 illustrates Class B configuration.
Figure 4-8 SBUS Class B Wiring
4.4.2.1How to Power SBUS Devices From Auxiliary Power Supply
Figure 4-9 illustrates how to power SBUS devices from an Auxiliary Power Supply such as the 5495 or 5499,
when the maximum number of SBUS devices exceeds the SBUS power requirements.
Figure 4-9 Powering SBUS Devices From 5495 or 5499
Note: The earth ground jumper on the 5495/5499 must be removed in this configuratio n.
4-9
Control Panel Installation151295
4.55860emote Annunciator Installation
The optional Model 5860 Remote Annunciator, shown in Figure 4-10, performs the same functions as the onboard annunciator as well as initiate and end fire drills with a single key press and view event history by alarms,
supervisories, or troubles.
Up to 8 annunciators can be added to the 5700 system.
Figure 4-10 Model 5860 Remote Annunciator, Front View
5860 installation involves the following steps:
1.Make sure power is off at the panel.
2.Mount the 5860 in the desired location (see Section 4.5.1).
3.Connect the 5860 to the panel (see Section 4.5.2).
4.Use the dipswitches on the back of the 5860 to assign an ID# to the 5860 (see Section 4.9.1).
5.The new 5860 module must be added to the system through programming. JumpStart will add the module
automatically (see Section 6.1). You can also add it manually (see Section 7.2.2). Select a name, if desired
(see Section 7.2.1.1).
4-10
Model 5700 Installation and Operation Manual 151295
4.5.1Mounting the 5860
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surfacemounted.
Figure 4-11 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the
following pages.
Figure 4-11 Annunciator Parts
4-11
Control Panel Installation151295
Set screw location.
Loosen set screws to remove bezel
when disassembling annunciator.
Knockout holes
Holes for surface mounting.
Holes for inserting
wires for flush mounting
(located in all corners).
Stand-off
(throughout)
Screw for placement
of mounting wires
(top and bottom).
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the
annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel.
(See Figure 4-12 for location of the set screws.)
Figure 4-12 Annunciator Back Box and Bezel Details
4-12
Model 5700 Installation and Operation Manual 151295
Sheet rock
Sheet rock
Electrical Box
Annunciator
back box
1-3/8"
When flush-mounting using an
electrical box, the box must be
1-3/8" from face of wall.
Electrical box applications require
2 by 4 construction minimum.
studs
electrical
box
annunciator
back box
(outline)
wall
Examples of Electrical Box Use
Electrical Box Placement
4.5.1.1Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and doublegang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the
annunciator. Studs used with an electrical box must be two by fours (or larger).
Flush Mounting Steps
1.Cut a hole in the sheet rock to the following dimensions: 8-1/4” w x 6-5/8” h. If an electrical box is used, the
box must be 1-3/8” back from face of wall to accommodate the annunciator (see Figure 4-13).
2.Remove knockout holes as needed for wires.
3.Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the mounting wires into
the first hole past the sheet rock. Secure the wires behind the screws as shown in Figure 4-14. When all four
wires are in place, the back box should fit snugly into the hole in the sheet rock.
Figure 4-13 Placement of Electrical Box for Flush Mounting
4-13
Control Panel Installation151295
Insert wires at an angle into the first holes past the sheet rock.
Secure the wires behind this screw.
Attach second set of wires to top of back box.
Supervised
Power Limited
4.After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
Figure 4-14 Flush Mounting the Back Box
4.5.1.2Surface Mounting
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical
box. The Model 5860TG/TR trim ring kit is available for use when surface mounting.
1.Drill holes in the surface to match the screw holes on the back box.
2.Fit the trim ring over the back box.
3.Attach the back box to the surface using screws provided.
4.After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
4.5.2Model 5860 Connection to the Panel
Connect the 5860 to the panel as shown in Figure 4-15.
Figure 4-15 Model 5860 Connection to the Panel
4-14
Model 5700 Installation and Operation Manual 151295
Supervised
Power Limited
To Serial Printer
To Parallel Printer
4.65824 Serial/Parallel Printer Interface
Module Installation
The 5824 serial/parallel printer interface module allows you to connect a printer to the panel, so you can print a
real-time log of system events, a report of detector status, and event history.
5824 installation involves the following steps:
1.Make sure power is off at the panel.
2.Connect the 5824 to the panel as shown in Figure 4-16.
Note: Two 5824s per panel maximum.
3.Use the DIP switches on the back of the 5824 board to assign an ID# to the 5824 (see Section 4.9.1).
4.Configure the 5824 device through programming. See Section 4.6.1.
5.Connect a printer to the 5824 as shown in Figure 4-17.
Figure 4-16 5824 Connection to the Panel
Figure 4-17 Printer Connection
4-15
Control Panel Installation151295
4.6.1Selecting 5824 Options
Configuring the 5824 includes the following steps:
•Add the module to the system. JumpStart will add the module automatically (see Section 6.1). You can also
add it manually (see Section 7.2.2).
•Select a name, if desired (see Section 7.2.1.1).
•Select options for the printer and the output port. See below.
Printer and Output Port Options
1.From the Main Menu, select 7 for Program Menu.
2.Select 1 for Module.
3.Select 1 for Edit Module.
4.From the list that displays, select the 5824 module you want to configure.
5.Press
ENTER to bypass the next two screens. A screen similar to the one shown in Figure 4-18 will display.
Figure 4-18 Selecting Printer and Output Port Options
6.Select options for the printer as needed for your installation. Most printers are parallel.
7.If you are using a serial printer, use the next screen to select serial port options as required for your printer.
Refer to your printer manual if you need more information.
Model 5700 Installation and Operation Manual 151295
SBUS Connection
SBUS Address
DIPs
Dry Contact Inputs - Supervised/Power Limited
4.75880 LED Driver Module
The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with
most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller.
The 5880 also has eight inputs for dry contact monitoring. The following sub-sections describe hardware
installation. Refer to Section 6 for programming information.
4.7.15880 Board Layout
Figure 4-19 is a picture of the 5880 board showing locations of screw terminals for connection to the panel and
contact monitor wiring; pin connectors for connecting LEDs; and the DIP switch for selecting an SBUS ID
number.
Figure 4-19 5880 Board Layout
4-17
Control Panel Installation151295
Supervised
Power Limited
4.7.2FACP Connection
The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-20. After the 5880 is
connected to the panel, it must be added to the system. This programming step is described in Section 4.9.
Figure 4-20 5880 Connection to Main Control Panel Assembly
4-18
Model 5700 Installation and Operation Manual 151295
4.7.3LED Wiring
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11.
Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are
required. LED outputs can be mapped to output circuits. See Section 6 for programming details.
Wire the LEDs as shown in Figure 4-21.
On connector P1, Pin 12 is a programmable open collector output for controlling a PZT. If used, the 5880 PZT
will match the PZT pattern of the on-board (or 5860) annunciator.
Note: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that no more
than 100 mA of current is allowed to flow into the open collector transistor.
Figure 4-21 5880 Board Layout
4.7.4Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the
control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flo w,
tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-22. Notice grouping of terminals; power terminals are shared by two
4-19
Control Panel Installation151295
Model 7628
Supervised
4.7k EOL
inputs.
Figure 4-22 Dry Contact Wiring
4.85865-3 / 5865-4 LED Annunciator Installation
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key
switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15
pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs.
Installation of the 5865-3 and 5865-4 is identical. The key switches and the trouble LED follow the behavior of
other system annunciators and do not require any installation steps. The following sub-sections describe how to
install the 5865-3 and 5865-4 hardware. Refer to Section 6 for programming information.
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both
models.
Figure 4-23 5865-3 and 5865-4 Assembly (front view)
4-20
Model 5700 Installation and Operation Manual 151295
Supervised
Power Limited
4.8.1FACP Connection
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-24. After the 5865 is
connected to the panel, it must be added to the system. This programming step is described in Section 4.9.
Figure 4-24 5865 Connection to the FACP
4.8.25865 Mounting
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In
Figure 4-25, the 5865-4 attached to a 4-gang box is used as an example.
Figure 4-25 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These
labels can be used in a typewriter or can be written on by hand.
Slide the labels under the plexiglass as shown in Figure 4-26. The LEDs will show through the label when
4-21
Control Panel Installation151295
illuminated.
Figure 4-26 Inserting Zone Description Labels
4.9Configuring Modules
This section describes how to configure any system hardware modules that have been added to the system.
4.9.1Assigning Module IDs
When installing a hardware module (such as, 5824, 5860, 5496, 5865-3 or 5865-4), you must use the DIP
switches on the module to assign an ID# to the module. Figure 4-27 shows all possible DIP switch positions and
their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2 in the up position.
Figure 4-27 Possible module addresses
Refer to Section 7.2 to edit, add, delete, and view module list.
4-22
Model 5700 Installation and Operation Manual 151295
Supervised
4.10Telephone Connection
Connect the telephone lines as shown in Figure 4-28. The Model 7860 phone cord is available from Silent Knight
for this purpose.
A number of programmable options are available for customizing telephone lines. These options are described in
Section 7.6.
Figure 4-28 Connection of Telephone Lines
4.11Notification Appliance/Auxiliary Power Circuits
Two outputs are built-in to the 5700 FACP which can be programmed to be used as NACs (Class A or Class B)
or as Aux power.
This section of the manual explains how to install conventional notification appliances and how these terminals
can be used for auxiliary power.
4.11.1Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A (Style Z)
and Class B (Style Y) configurations.
4-23
Control Panel Installation151295
Supervised
Power Limited
Notification Wiring
4.11.1.1 Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class B notification appliance circuit:
1.Wire Class B Notification appliances as shown in Figure 4-29.
2.Configure the circuit through programming (see Section 7.5).
Figure 4-29 Class B Notification Appliance Circuit Wiring
4-24
Model 5700 Installation and Operation Manual 151295
Supervised
Power Limited
4.11.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual.
To install a Class A notification appliance circuit:
1.Wire the Class A notification appliances as shown in Figure 4-30.
Caution
For proper system supervision do not use looped wire under terminals marked – and + of the Flexput connectors.
Break wire runs to provide supervision of connections.
2.Configure the circuit for Class A in programming (see Section 7.5).
Figure 4-30 Class A Notification Appliance Circuit Configuration
4-25
Control Panel Installation151295
Non-Supervised
Power Limited
4.11.2Auxiliary Power Installation
NAC Circuits 1and 2 on the control panel can be used as auxiliary power circuits. The four types of auxiliary
power available are:
•Door Holder (see section 4.11.2.1)
•Constant (see section 4.11.2.2)
•Resettable Power (see section 4.11.2.3)
•Sounder Sync Power (see Section 4.11.2.4)
Auxiliary power circuits are power limited. Each circuit can source up to 2.5A (total current for system must not
exceed 2.5A).
To install an auxiliary power circuit:
1.Wire the NAC circuit(s) that will be used for auxiliary power. See Figure 3-2 for location of NAC circuits.
2.Configure the auxiliary power output through programming (see sect ion 7.5).
4.11.2.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel
has AC power, door holder circuits have 27.4 volt power present at their terminals. Any alarm will cause power
to disconnect. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds,
the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is
restored, power is immediately restored to the door holder circuits.
Figure 4-31 Example of an Auxiliary Power For Door Holder
Note: Figure 4-31 uses UL listed door holder Model 1400 from Door Control International as an example.
4-26
Model 5700 Installation and Operation Manual 151295
Connect to Power
Limited Sources only
4.11.2.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at
Constant circuits.
4.11.2.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke
detectors. For circuits selected as Resettable, 27.4 volt power is always present at the terminals unless a system
reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied.
4.11.2.4 Sounder Sync Power
Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is int e nded for use
with B200S sounder bases.
4.12On-Board Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated
at 2.5 A @ 27.4 VDC Resistive.
Figure 4-32 Location of Conventional Relay Circuits
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no alarm or
trouble conditions.
4.12.1Common Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals labeled TROUBLE. The relay
provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble
condition. Form C rated at 2.5 A @ 27.4 VDC Resistive.
4.12.2Programmable Relays
The control panel has two Form C programmable relays built into terminals labeled RELAY 1 or RELAY 2.
Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1.Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-32 for the location of the relay terminals.
2.Configure the relay through programming (see section 7.5).
4-27
Control Panel Installation151295
A 5496 Must Be Used
for NAC Circuits
Example
Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.
4.13Remote Station Applications
4.13.1Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The
3158 reports alarms, supervisories, and troubles. The 3158 is intended for connection to a polarity reversal circuit
of a remote station receiving unit having compatible ratings.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete
information.
1.Wire the 3158 to the control panel as shown in the connection list and Figure 4-33.
2.Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3.Program control panel Relay 2 for alarm.
4.Program NAC circuit 2 for alarm.
5.Program NAC circuit 1 for supervisory non latching.
Note: NACs must be programmed for continuous and non-silencing.
Figure 4-33 Keltron 3158 Connection to Control Panel
4-28
Model 5700 Installation and Operation Manual 151295
Non-Supervised
Non-Power Limited
Note:
NAC Circuit 2 Used
as an Example.
Either NAC Circuit
Can Be Used.
4.13.2City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a municipal fire alarm box or “city box” as required by
NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure
that contains a manually operated transmitter used to send an alarm to the municipal communication center
which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current
accounted for in control panel draw.)
Alarm Current:1 Amp for 1 second
Max Voltage:27.4 VDC
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box conn ection:
1.Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of
conduit (must not exceed 20 feet in length).
2.Wire the 5220 to the control panel as shown in Figure 4-34. This drawing also shows how to connect the city
box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the NAC circuit
used for this application.
3.Connect earth ground wire to the 5220 chassis with mounting screw.
4.Program the NAC circuit used as a continuous and non-silencing. Refer to Section 7.5 for point program-
ming, Section 7.4 for group settings, and Section 7.3 for zone settings and mapping.
It is not possible to reset the remote indication until you clear the condition and reset the control panel.
Figure 4-34 City Box Connection
4-29
Control Panel Installation151295
Note:
NAC circuit 1 and Relay 2
used as examples. Either
NAC circuit and Relay
Not suitable for remote station protected premises service
where separate transmission circuits are required for fire
supervisory (if applicable), and trouble signals.
circuit can be used.
Program Relay
for Alarm.
Max Voltage: 27.4 VDC
Max Current: 1 Amp
4.13.3NFPA 72 Polarity Reversal
4.13.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote
site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the
condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Standby Current:100 mA
Alarm:100 mA
Max. Voltage:27.4 VDC
To install the 5220 for polarity reversal, follo w the steps below:
1.Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of
conduit (must not exceed 20 feet in length).
2.Wire the 5220 to the control panel using the four-wire pigtail provided as shown in Figure 4-35. This dia-
gram also shows how to connect the 5220 to the remote indicator. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3.Connect earth ground wire to the 5220 chassis with mounting screw.
4.Program the NAC circuit used as continuous and non-silencing. Refer to Section 7.5 for point programming,
Section 7.4 for group settings, and Section 7.3 for zone settings and mapping.
5.If necessary, adjust loop current using the potentiometer (R10) on the 5220 board. Normal loop current is 2-
to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm.
Figure 4-35 Polarity Reversal Connection Using the 5220 Module
4-30
Model 5700 Installation and Operation Manual 151295
4.13.3.2 Using the 7644-L8 Module
When the 7644-L8 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site.
Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition
is cleared and the control panel is reset.
To install the 7644-L8 for polarity reversal:
1.Wire the 7644-L8 to the control panel as shown in Figure 4-36. Do not install an EOL resistor on the termi-
nals of the NAC circuit used.
Note: Use only NAC circuits on the control panel for reverse polarity.
2.Program the NAC circuit as a notification circuit. See Section 7.4.1.
3.Map the group to activate constant on from the zone event. See Section 7.4.1.2.
4.Program the output group characteristics as non-silenceable and reverse polarity. See Section 7.4.1.2.
Figure 4-36 Polarity Reversal Connection Using the 7644-L8
4.13.4Using the SD500-ARM Addressable Relay Module
When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms
will override trouble conditions and it will not be possible to reset the remote indicator until the condition is
cleared and the control panel is reset.
Relay 2 must be programmed for Alarm (default).
Max Current: 1A
Max. Voltage: 27.4 VDC
Note: If you need to transmit supervisories or trouble conditions, additional SD500-ARM modules must be added.
Use relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.
4-31
Control Panel Installation151295
UL Listed
EOL
Intended for Connection to a
Polarity Reversal Circuit of A
Remote Station Receiving Unit
Having Compatible Rating.
Supervised
Power Limited
To Remote
Receiving Station
UL Listed
EOL
Note: UL Listed EOL
must be permanently mounted
Wire the SD500-ARM as shown in Figure 4-37.
Figure 4-37 Polarity Reversal Connection Using the SD500-ARM Module
4-32
Model 5700 Installation and Operation Manual 151295
SupervisedPower Limited
Intended for Connection to
a Polarity Reversal Circuit
of A Remote Station
Receiving Unit Having
Compatible Rating.
Note: UL Listed Model 7642
must be permanently mounted
4.13.5Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote
site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the
condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current:15 mA max.
Operating Voltage:24 VDC nominal; 27.4 VDC max.
Resistance:4 K
To install the MR-201/T for polarity reversal, follow the steps below:
1.Wire the MR-201/T as shown in Figure 4-38.
2.Program the NAC circuit for non silence NAC circuit (see Section 7.5).
Note: If you need to transmit supervisories or trouble conditions, additional relay modules must be added . Use
relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.
Figure 4-38 Polarity Reversal Connection Using the MR-201/T Relay
4-33
Control Panel Installation151295
4.13.6Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the 5700 FACP dry
contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line
resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the remote
station transmitter manufacturer. Refer to the remote station transmitter manufacturer ’s manual for details.
4-34
151295
Section 5
SK and SD SLC Device Installation
Caution!
T o avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.
5.1List of SK SLC Devices
The following SK SLC devices can be used with the control panel. See the device installation instructions for
more information (packaged with the device).
Note: The control panel supports the use of either SK SLC devices or SD SLC devices. You cannot install both
SLC device types on the control panel.
SK Part NumberModel Name/Description
SK-PhotoPhotoelectric smo ke detector
SK-Photo-TPhotoelectric smoke detector with thermal (135°F)
SK-AcclimateMulti criteria photoelectric smoke detector with thermal (135°F)I56-3611-00
SK-BeamReflected beam smoke detector without test feature
SK-Beam-TReflected beam smoke detector with test feature
SK-IonIonization smoke detectorI56-3428-00
SK-DuctPhotoelectric duct smoke detector with extended air speed rangeI56-3432-000
SK-HeatFixed temperature thermal detector (135°F)
SK-Heat-RORRate-of-rise thermal detector with 135° fixed temperature
SK-Heat-HTFixed high temperature thermal detector (190°F)
SK-Pull-SAAddressable single action pull stationI56-3446-00
SK-Pull-DAAddressable dual action pull stationI56-3447-00
SK-ISOFault isolator moduleI56-3445-00
SK-MonitorMonitor moduleI56-3442-00
SK-MinimonMini monitor module I56-3444-00
SK-Monitor-2Dual input monitor moduleI56-3435-00
SK-Mon-1010 input monitor moduleI56-3443-00
SK-RelayAddressable relay moduleI56-3438-00
SK-Relay-6Six relay control moduleI56-3439-00
SK-RelayMon-2Dual relay/monitor moduleI56-3735-00
SK-ZoneAddressable zone interface moduleI56-3440-00
SK-Zone-6Six zone interface moduleI56-3441-00
SK-ControlSupervised control moduleI56-3436-00
SK-Control-6Six circuit supervised control moduleI56-3437-00
SK-Fire-COCO Smoke DetectorI56-3946-00
Low Frequency Sounder Base
Low Frequency Sounder Base
Section/ Install
Sheet PN
I56-4152-00
I56-4151-00
5.2List of SD SLC Devices
The following SD SLC devices can be used with the control panel. See the appropriate section number in this
manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot install both
SLC device types on this control panel.
Section No./
Model NumberModel Name/Description
SD505-APSPhotoelectric smoke detector.
SD505-AHSAbsolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
SD505-6AB6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS.150955
SD505-6IB6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-
APS
SD505-6RB6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS151192
SD505-6SB6" sounder base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SLC devices
SD505-DUCTDuct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths:
SD505-T2 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)
SD505-DUCTRDuct Detector housing with relay base. Duct housing with relay base including
SD505-APS Analog Photoelectric Smoke detector pre-installed
SD500-PS/-PSDASingle or dual action addressable pull station151177
SD500-AIMAddressable input module (switch input), standard size, DIP switch configurable 151071
SD500-MIM Mini input monitor module (switch input), small size, DIP switch configurable. Fits in
single-gang box with manual pull station switch.
SD500-ANMAddressable notification module151109
SD500ARMAddressable relay module DIP switch configurable.151091
SD500-SDMAddressable smoke detector module. Use to assign an address to a loop of
conventional devices.
SD500-LIMLine isolator module. Fits in a double gang box.151125
SD500-LEDAddressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-
LED Driver Modules can be used per SLC loop.
SD505-DTS-KRemote test switch & LED indicator for the SD505-DUCTR1700-09882
Installation
Instructions PN
Section 5.7SD505-AISIonization smoke detector
151175
151191
1700-09882
1700-09882
151071
151193
151232
5-2
Model 5700 Installation and Operation Manual 151295
5.3Maximum Number of Devices
The 5700 supports SK or SD devices on one5700ystem. The maximum number of devices per system varies
depending on device protocol. Device support is as follows:
•SK Devices–A 5700 system can support a total of 50 SK detectors and 50 SK modules.
OR
•SD Devices–A 5700 system can support a total of 50 SD SLC detectors and modules, in any combination.
5.4Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the type of device you
are installing for details.
5.4.1Wiring SLC in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as
long as it meets the National Electric Code 760-51 requirements for power limited fire protective signaling
cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms for SK device and 50 ohms for SD devices.
Maximum loop length depends on the wire gauge.
The following figures show how length is determined for out and back tap and T-Tap styl e wiri ng.
Figure 5-1 Calculating wire run length for a simple out and back
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement
must be met in addition to the maximum distance requirements for the various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
5-4
Model 5700 Installation and Operation Manual 151295
5.4.2Wiring SLC Devices in Style 6 & 7 (Class A)
Configuration
The following figure illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.
Note: Style 6 does not use short circuit isolator devices.
Figure 5-3 Class A SLC Configuration
Note: No t-taps allowed on class A SLC loops.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device
connectors. Break wire runs to provide supervision of connections.
5-5
SK and SD SLC Device Installation151295
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connec tions.
Class A wiring:
Class B wiring:
...............
5.5SK Detector Installation
This section describes how to install heat and smoke detectors. All detectors ship with installation instructions.
Refer to the detector’s installation instruction s fo r mo re detailed information.
This information applies to the following SK models:
•SK-Photo Photoelectric Smoke Detector
•SK-Photo-T Photoelectric Smoke Detector with Thermal
•SK-Acclimate Photoelectric Smoke Detector with Thermal
•SK-Heat Fixed Temperature Detector
•SK-Heat-T High Temperature Thermal Detector
•SK-Heat-ROR Rate-of-Rise Thermal Detector
•SK-Ion Ionization Smoke Detector
•SK-Fire-CO
5.5.1Wiring SK Detectors
1.Wire device bases as shown in Figure 5-4.
2.Set the address for each device as described in Section 5.6.
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
5-6
Model 5700 Installation and Operation Manual 151295
Example 1: Device Set to 01.
Example 2: Device Set to 42.
All dials labeled for ONES
or TENS position.
5.6Addressing SK SLC Devices
All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary
dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two
digit number.
SK device addresses are handled differently than SD device addresses. The control panel recognizes when an SK
detector or SK module is installed. For this reason, SK detectors can be assigned any unique address from 1 to
50, and SK modules can be assigned any unique address from 1 to 50. Unlike SD detectors and modules which
share addresses 1 through 50, there can be an SK detector using address 1 and an SK module using address 1. 0
is an invalid address.
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary dial to 0 as shown in
Figure 5-5.
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in
Figure 5-5.
Figure 5-5 SK SLC Device Addressing Using Rotary Dials
5-7
SK and SD SLC Device Installation151295
5.7SD Detector Installation
The information in this section applies to the following SD models: SD505-AHS Heat Detector, SD505-AIS
Ionization Smoke Detector, and SD505-APS Photoelectric Smoke Detector.
5.7.1Wiring SD Detectors
1.Wire device bases as shown in Figure 5-6.
2.Set the address for each device as described in Section 5.8.
Figure 5-6 Heat or Smoke Detector Connection to the FACP (Class B)
5-8
Model 5700 Installation and Operation Manual 151295
5.8Addressing SD SLC Devices
This section tells how to address detectors and modules.
5.8.1SD505-APS, SD505-AHS, & SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke
detector are easily addressed at the FACP. The Installer Code is required to perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1.Connect a detector base temporarily to the programming terminals as shown in
Figure 5-7. (You can use the same base for each detector.)
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2.Enter the Installer code, then press
3.Select 2 for Point Functions.
4.Select 3 for Set SLC Dev Addr.
5.Select “Yes” by pressing the up arrow, then press
You can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel reinitializes when you finish programming.)
6.When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detector’s address.
2- for Write Address. Use to program a single detector’s address.
3- for Seq. Programming. Use to program more than one detector in sequential order.
7.If you are changing addresses, write the programmed address on the back of the device.
8.T o exit press left arrow until fully exited.
ENTER.
ENTER. (The panel will go into trouble at this point.
5-9
SK and SD SLC Device Installation151295
5.8.2SLC Devices with DIP Switches
Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the
available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of
valid addresses is 1-50. 0 is an invalid address.
Figure 5-8 SLC Device Addressing Using DIP Switches
5-10
Section 6
Programming Overview
This section of the manual is intended to give you an overview of the programming process. Please read this
section of the manual carefully, especially if you are programming the control panel for the first time.
The JumpStart feature automates many programming tasks and selects default options for the system. You will
run JumpStart at least once when you are installing the system. See Section 6.1 for details. After you run
JumpStart, you may need to do some additional programming depending on your installat ion. Sect ion 7 of this
manual covers manual programmable options in detail.
Programming the panel can be thought of as a three part process. You must program:
•System options. These are options that affect general operation of the panel (see Section 7.6 for details).
•Options for input points and zones. These are primarily options that control detection behavior of devices
(see Sections 7.3 and 7.5 for details).
•Options for output points and groups. This includes selecting characteristics for output groups and mapping
output circuits to output groups (see Sections 7.4 and 7.5 for details).
6.1JumpStart Autoprogramming
151295
The JumpStart feature allows for faster system setup. When you run JumpStart (immediately after addressing
SLC devices), the system scans devices on all SLC loops and determines device type (for example, photoelectric
smoke detector or heat sensor) and selects some system options based on the device type. This saves the installer
from having to program options for each device. Depending on the application, the installer may need to make
some changes after JumpStart completes.
See Section 6.1.3 for complete details about running JumpStart.
IMPORTANT!
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected. JumpStart will reset
all manually programmed options to default settings. Do not run JumpStart after you have configured the system.
6.1.1Input Points
JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each
SLC loop. JumpStart assigns the correct detector type (heat, or photoelectric), so the installer does not need to
edit device type for detectors. Any contact monitor modules on the system will be assigned type “Manual Pull.”
The installer will need to manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1.
After JumpStart completes, you can re-map to configure a multiple zone/output group system (see Section
7.3.1.3). For a general explanation of mapping, see Section 6.2.
6.1.2Output Points
JumpStart creates three output groups and assigns output circuits as follows:
Circuits 1-2:
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone 1 to activate Group
1 using constant on output when an alarm condition occurs.
Circuit 3 (Relay 1):
Assigned to Group 124. JumpStart automatically programs Zone 1 to activate Group 124 using constant on
6-1
Programming Overview151295
output when a supervisory condition occurs.
Circuit 4 (Relay 2):
Assigned to Group 125. JumpStart automatically programs Zone 1 to activate Group 125 using constant on
output when an alarm occurs.
Addressable output points (Relay modules):
All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to
Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.1.3Running JumpStart
Run JumpStart immediately after addressing and connecting all input devices (detectors, pull stations, and so on)
and output devices (notification appliances, relays, and so on).
Note: To install a few devices manually after running JumpStart, see Section 7.
To run JumpStart:
1.Press
2.Select 7 for Program Menu.
3.From the next menu, select 6 for JumpStart.
4.When the message “WARNING Will DELETE all system options” displays, select Yes. A series of mes-
ENTER to view the Main Menu.
sages displays for the next several seconds. JumpStart scans the SLC loops for devices and can take several
minutes, depending on the number of devices attached.
5.When message “SLC Family” flashes, Press ENTER to accept SK, or press to change to SD and press
ENTER to accept
.
6.When the message “Configuring System Done” displays, press any key to continue.
7.Select one of the following options from the menu that displays.
1 - Review SystemPress 1 if you need to review the JumpStart configuration.
2 - Repeat JumpStartPress 2 if you need to rerun JumpStart for any reason.
1. If you are ready to make the JumpStart configuration permanent, select 3.
2. The system will ask you if the installation contains duct detectors. If there are none, select 2 for
No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and continue with
Step 3.
3. From the list, select the SLC device that contains the duct detectors.
4. The first photoelectric detector on the system will display. Select 1 for DUCT and 2 for NonDUCT.
3 - Accept Changes
4 - Enter Programming
5. Press to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue until all
duct detectors have been selected. (Note: You can move backwards through the list with .)
6. When you reach the last detector on this device, press .
7. T h e syst em will ask you if there are more duct detectors in the system. If there are, select 1 for
Yes and repeat from Step 3. If there are no more duct detectors, select 2 for No and continue with
Step 8.
8. The system will restart in 10 seconds, or press 1 to restart immediately.
9. After the system resets, it will use the new JumpStart configuration.
To go directly to Program Mode to configure any devices, press 4. The Programming Menu appears and you can
begin programming.
6-2
Model 5700 Installation and Operation Manual 151295
6.2Mapping Overview
This section of the manual is an overview of mapping. Details about how to select mapping options appear in the
appropriate subsections in Section 7.
Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events
to outputs that should activate when events occur. You do this by assigning input points to input zones, output
points to output groups and then linking or mapping zones and output gro ups.
Figure 6-1 is a brief overview of the concept of mapping. The next several pages of the manual show these
subjects in detail.
Figure 6-1 Mapping Overview
6-3
Programming Overview151295
6.2.1Input Point Mapping
Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be
assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned
to a zone.)
Figure 6-2 Input Point Assignment Example
6-4
Model 5700 Installation and Operation Manual 151295
6.2.2Output Circuit Mapping
Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an
example of a simple floor above/floor below application, see Figure 6-5.
Figure 6-3 Assigning Output Circuits to Groups (Example)
6-5
Programming Overview151295
6.2.3Zone Event Mapping
There are 11 types of events that can occur in zones (see below). For each event type, you can activate up to 8
output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may
be used (see Section 7.4.5 for information on output group templates). Event types are:
•Manual Pull Alarm
•Water Flow Alarm
•Detector Alarm (heat or smoke detectors)
•Aux 1 and Aux 2 Alarm (user-specified alarm types)
•Pre-alarm
•Supervisory
•Trouble
•Status Point
•CO Alarm
•CO Supervisory
Figure 6-4 Example of Zone Events Mapped to Output Groups and Patterns
6-6
Model 5700 Installation and Operation Manual 151295
Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns
6-7
Programming Overview151295
6.2.4Mapping LED Points
Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you
would create two output groups for each zone, one for alarms and one for troubles. (LED points are available
when Models 5865-3/4 and/or 5880 are used with the system).
Figure 6-6 Example of LED Points Mapped to Output Groups
(applies to Models 5865-3/4 and 5880)
6-8
Model 5700 Installation and Operation Manual 151295
6.3Programming Using the 5660 Silent Knight Software
Suite
You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely.
SKSS is an optional software package that lets you easily program the control panel using a Windows-based
computer and a modem* (not sold by Silent Knight). When using SKSS, you can set up the programming options
for the panel, save the options in a file, then download the file to the panel. You connect to the control panel
directly using the control panel’s onboard serial port or remotely using a modem. If you need to connect to an
older control panel that does not have a USB port, and your laptop does not have a serial port, use a USB to serial
converter. SKSS includes an Online help system and a manual. See the SKSS manual (PN 151240) for more
information.
*See Section 1.3 for a list of modems that have been tested for compatibility with the control panel and SKSS.
6.4Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel’s on-board
annunciator or a remote annunciator.
The following subsections describe programming basics, including a description of editing keys available for
programming and how to move through programming menus. Section 7 contains specific information about
individual programming options.
6.4.1Entering / Exiting the Program Menu
To enter the Program Mode:
1.Press
2.Enter the installer code if requested.
3.Select 7 for Program Menu.
The menus described in Section 7 of this manual will display. Section 7.6 of this manual is a quick reference
listing all programmable options and JumpStart defaults.
To Exit Program Mode:
When you have completed working with the menus, press Left Arrow button several times until you are exited
from programming mode. Two prompts will display. The first prompt is to make sure you intended to leave the
Program Menu (select Yes or No as appropriate). The second prompt is for accepting all changes. If you select
No, any changes you have made since you entered the Program Menu will have no effect.
or ENTER to display the main menu.
6-9
Programming Overview151295
6.4.2Moving through the Menus
Figure 6-7 shows how to move through Menu screens, using the System Options screen as an example.
Figure 6-7 Moving through Program Menu
6.4.3Selecting Options and Entering Data
There are several ways to make programming selections using the control panel depending on which screen you
are currently using. The chart below is a generic explanation.
ToPress
Select from a menu.Enter the number of the option.
Enter numeric data.Press the appropriate number on the annunciator.
Enter text (alphanumeric data).
Select from a scrolling list.
Enter each character individually by using and arrow keys until the one you
wish to select displays. Then press (right arrow) to select the character.
Use and to move through a list of available options. When the option you want
to select is displayed, press ENTER.
6-10
Model 5700 Installation and Operation Manual 151295
6.4.4Editing Keys
The keys shown in Figure 6-8 are available for use when you are in the Program Menu.
Figure 6-8 Editing Keys Available from Program Menu
6-11
Programming Overview151295
6.5Programming Menu Quick Reference
This section of the manual lists all Program Menu options in the order they appear on the sub-me nus. Default
settings are indicated in text or marked with an asterisk. The comments column provide quick information and a
reference to a section (if applicable) which has more detailed information.
MenuOptions/DefaultsComments
Edit ModuleSelect ModuleEnter Module ID
5824-Ser/Par/IO
5860-LCD Ann
Module
ZoneEdit ZoneSelect Zone to Edit
Add Module
Delete ModuleList of ModulesSection 7.2.3
View Module ListList of ModulesSection 7.2.4
5895XL Pwr Sup
5496-NAC Expand
5880-LED/IO Dev
5865-LED Annunc
MAN_PULL,
PAS_ACK,
DETECT SW,
MAN REL,
ILOCK, CO DET
SW
WATERFLOW,
SUPERVSY,
ZN_AUX1,
ZN_AUX2,
TAMPER
FIREDRILL,
SILENCE, RESET
SYS_AUX1,
SYS_AUX2
STATUS PT
6-16
Model 5700 Installation and Operation Manual 151295
MenuOptions/DefaultsComments
AUX CONST,
Point
(cont.)
Internal and External
5815XL, SK Devices
Internal and External
5815XL, SD Devices
Module Point #
Point #
AUX RESET,
AUX DOOR
OUTPUT PT
RELAY
DETECTOR2WIRE SMK
UNUSED
DETECTOR
AUX RESET,
AUX DOOR
PHOTO, ION,
HEAT
Point Name
Group # (*001)
Point Name
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
*NO
ACCESSORY,
SDR BAS, RLY
BAS
Single/Multi
Station: *NST,
SST, MST
Station Silenceable:
*SIL, NSL
Accessory Group #
(*001)
Point Name
Section 7.5.1
Section 7.5.2
6-17
Programming Overview151295
MenuOptions/DefaultsComments
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
*NO
ACCESSORY,
DCT RLY
Single/Multi
Station: *NST,
SST, MST
Station Silenceable:
*SIL, NSL
Accessory Group #
(*001)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
*NO
ACCESSORY,
SDR BAS, RLY
BAS
Single/Multi
Station: *NST,
SST, MST
Station Silenceable:
*SIL, NSL
Accessory Group #
(*001)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Section 7.5.1
Point
(cont.)
Internal and External
5815XL, SD Devices
PHOT DUCT, ION
DUCT
DETECTOR
2 WIRE SMK
Point #
PHOTO, ION,
HEAT
SUP DET
PHOT DUCT, ION
DUCT
6-18
Model 5700 Installation and Operation Manual 151295
MenuOptions/DefaultsComments
*NO
ACCESSORY,
DCT RLY
Single/Multi
Station: *NST,
SST, MST
Station Silenceable:
*SIL, NSL
Accessory Group #
(*001)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Point Name
Zone # (*001)Used to activate an
Point Name
Group # (*001)
Point Name
Point Name
Section 7.5.1
ancillary Output
Group that does
not activate alarm,
sound PZT,
display status or
report events.
Reset has no affect
on this point.
Section 7.5.1
Section 7.5.1
Point
(cont.)
Internal and External
5815XL, SD Devices
Point #
SUP DET
SWITCH
NOTIF
PHOT DUCT, ION
DUCT
MAN_PULL,
PAS_ACK, DET
SW, MAN REL,
ILOCK, CO DET
SW
WATERFLOW,
SUPERVSY,
ZN_AUX1,
ZN_AUX2,
TAMPER
FIREDRILL,
SILENCE, RESET
SYS_AUX1,
SYS_AUX2
STATUS PT
OUTPUT PT
AUX CONST,
AUX RESET,
AUX DOOR
6-19
Programming Overview151295
MenuOptions/DefaultsComments
Group # (*001)
Point Name
Point Name
UNUSED, NOTIF
Group # (*001)
Point Name
Group # (*001)
Point Name
Group # (*001)
Point Name
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Point Name
Section 7.5.2
Point
(cont.)
Internal and External
5815XL, SD Devices
Internal Pwr and
External Power
Point #
Point #
OUTPUT PT
RELAY
SLC LEDL ED # (01-80)
UNUSED
B NOTIF
A NOTIF
AUX PWR
B SWITCH
AUX RESET,
AUX DOOR
NOTIF OUT,
CTRL CKT
NOTIF OUT,
CTRL CKT
CONSTANT,
AUX RESET,
AUX DOOR,
AUX SYNC
MAN _PULL,
PAS_ACK, MAN
REL, ILOCK
WATERFLOW,
SUPERVSY,
ZN_AUX1,
ZN_AUX2,
TAMPER
FIREDRILL,
SILENCE, RESET
SYS_AUX1,
SUS_AUX2
6-20
Model 5700 Installation and Operation Manual 151295
MenuOptions/DefaultsComments
Zone # (*001)Used to activate an
ancillary Output
Group that does
not activate alarm,
sound PZT,
display status or
report events.
Reset has no affect
on this point.
Section 7.5.2
Section 7.5.2
Section 7.5.3
Point
(cont.)
Internal and External
Power Supply
5880Point #
5865Point #
Point #
B SWITCHSTATUS PT
A SWITCHSame as B SWITCH
2WIRE SMK,
B DETECT
A DETECT
UNUSED
NOTIF
SWITCH
UNUSED
NOTIF
4WIRE SMK,
CO 4WIRE
2WIRE SMK,
4WIRE SMK,
CO 4WIRE
NOTIF OUT,
CTRL CKT
MAN _PULL,
PAS_ACK, MAN
REL, ILOCK
WATERFLOW,
SUPERVSY,
ZN_AUX1,
ZN_AUX2,
TAMPER
FIREDRILL,
SILENCE, RESET
SYS_AUX1,
SUS_AUX2
STATUS PT
NOTIF OUT,
CTRL CKT
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
Group # (*001)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
Zone (*001)
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Point Name
*Silenceable (SI) or
Non-Silenceable
(NS)
Point Name
*Latching (LA) or
Non-Latching (NL)
*Silenceable (SI) or
Non-Silenceable
(NS)
Zone # (*001)
Point Name
Group # (*001)
Point Name
6-21
Programming Overview151295
MenuOptions/DefaultsComments
Account # (6-digit
number, identifies
account to central
station) Section
7.6.1.1
Reporting Format
(SIA, SIA20,
Contact ID)
Section 7.6.1.1
Section 7.6.1.1
Section 7.6.1.2
Section 7.6.2.3
*U, Section
7.6.2.4
*Y, Section 7.6.2.6
System
Options
Edit Acct.
Reporting Accounts
Auto Test Time
Phone LinesSelect Phone Line
Edit Account #*123456
Edit Format*CID, S20, SIA
Report Alarms
Choose Account
(1-4)
Set the Hour
Set the Minutes
Select AM/PM
Report Every
Dial Tone Detection
Disable
Dialing Prefix*noneUp to 9 digitsSection 7.6.2.1
# of Answer RingsRange: 00-15*6, Section 7.6.2.2
Select Dialing
Option *TT, TT/PL,
PULSE
Rotary Pulse Format
Line Monitor*Y or NSection 7.6.2.5
Answering Machine
Bypass
Rep. Alarm
Restore
Report Troubles,
Disables,
Supervisories and
their Restores
Report Test
Report Resets
Switch attempts (1-
5)
Edit Phone #
04, 06, 12, *24
hours
Y or *NSection 7.6.2
U = 60/40
E = 66/34
Y= Enabled
N= Disabled
Yes (Y), *No (N),
or Must (M)
Yes (Y), *No (N),
or Must (M)
Yes (Y), *No (N),
or Must (M)
Yes (Y), *No (N),
or Must (M)
Yes (Y), *No (N),
or Must (M)
*3
6-22
Model 5700 Installation and Operation Manual 151295
MenuOptions/DefaultsComments
Select Group
Select Cadence
Select Group
Select Cadence
Select Group
Select Cadence
Group Tr
SBUS Com
SBUS Pwr
SLC Loop
AC Loss
Battery
Gnd Flt
Phone Ln
Account
Printer
Aux Pwr
Sys Sw
00-21, 23*00 (Constant)
00-21, 23*00 (Constant)
*60 SecondsSection 7.6.6.2
*AM/PM
*DisabledSection 7.6.7.1
*EnabledSection 7.6.7.2
*ZoneSection 7.6.7.3
*DisabledSection 7.6.7.4
None selected
None selected
None selected
Section 7.6.3.1
Select Group
(*None)
Select Cadence
(*None)
Section 7.6.3.2
Water Flow delay is the number of sec.
before water flow alarm is generated.
Section 7.6.6.1
System Clock Format (AM/PM or
military). Section 7.6.6.4
Section 7.6.6.560 Hz
System
Options
(cont.)
System Event
Outputs
Time Options
Misc. Options
System Trouble
Alarm Silence
Trbl Silence
Trouble Events
User Selected
Fire Drill Cadence00-21, 23*00 (Constant)
System Aux1
Sys Alarm Cadence
Wa ter Flow Delay0 - 90 Seconds*01 sec
Alarm Verification
time
Low AC Delay0 - 30 hours*3 hrsLow AC Report Delay. Section 7.6.6.3
Clock
AC Freq:
SYNC Strbs w/ Sil
Auto Display Oldest
Report By
Single Key Ack
Cadence
System Aux2
Cadence
Enter time from 1 to
250 seconds
AM/PM
MIL
50 Hz
Neither
Y (Enabled)
N (Disabled)
Y (Enabled)
N (Disabled)
Zone
Point
Y (Enabled)
N (Disabled)
6-23
Programming Overview151295
MenuOptions/DefaultsComments
Automatic
Daylight Saving
Time enable or
disable. Section
7.6.8.1
Section 7.6.8.2
Section 7.6.9
Section 7.6.10
System
Options
(cont.)
JumpStart
AutoPrg
Computer
Account
DST
Daylight Savings
DST Start
DST End
Internal Message
Edit Banner
SLC Family
No
Yes
Computer Account # *123456
Computer Access
Code
Computer Phone #Up to 40 digits
Custom Message
SD
SK
*0
*Y es (Enabled) or No
(Disabled)
Select week: 1st,
*2nd, 3rd, 4th or Last
Select week: *1st,
2nd, 3rd, 4th or Last
Edit Line 1
Edit Line 2
Select month
(*Mar)
Select month
(*Nov)
Section 7.7
Section 7.8
6-24
Model 5700 Installation and Operation Manual 151295
MenuOptions/DefaultsComments
Edit Name
Edit Access Code
System Reset
System Silence
System ACK
Fire Drill Key
System Test
Fire Drill Menu
Indicator Test
Wa lk Test no Report
Walk Test with Report
Dialer Test
Clear History Buffer
Access
Codes
Access
Codes
Select Profile
(01-20)
Select Profile
(01-20)
Panel Functions
Panel FunctionsUpload/Download
Point Functions
Disable/Enable Point
Point Status
Set SLC Device Address
SLC Device Locator
SLC Mult-Device Locator
I/O Point Control
Event History
Set Time & Date
Printer Options
Event Logging
Print Event History
Print Detector Status
Print System Configuration
Reset Dialer
Program Menu
System Information
1. Use of multiple notification groups may not synchronize with each other.
Profile 1 is the profile that dictates what
functions the Firefighter Key has access
to. Because this is the profile for a key
the user name and the access code can
not be edited for this profile.
Profile 2 is the profile for the installer
and is referred to as the “Installer
Code”. This profile’s user name and
panel functions can not be edited.
Section 7.9
Profile 1 is the profile that dictates what
functions the Firefighter Key has access
to. Because this is the profile for a key
the user name and the access code can
not be edited for this profile.
Profile 2 is the profile for the installer
and is referred to as the “Installer
Code”. This profile’s user name and
panel functions can not be edited.
Section 7.9
6-25
Section 7
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using the Silent Knight Software Suite 5660.
Important!
Before any customized programming is done, JumpStart should be run first. After JumpStart is run,
thoroughly test the system. The reason the system should be tested after JumpStart is because Jumpstart
automatically programs the system, searching for and configuring all SLC and SBUS devices it finds.
JumpStart allows you to confirm the integrity of the installation prior to performing any custom
programming. After determining that the hardware is properly installed, custom programming can be
performed. Refer to Section 6.
7.1UL 864 Programming Requirements
151295
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION,
AND OTHER INVOLVED PARTIES: This product incorporates field
programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Programming
Option
Time OptionsLow AC Report Delay Yes0–30 hours 1–3
Display Oldest Event
Alarm VerificationAlarm VerificationYes1-2501-60
Menu Item
Y (Enabled)YesYes & NoYes
N (Disabled)NoY es & NoNo
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings
Permitted in
UL 864
7-1
Programming151295
7.2Modules
This section lists the options available under the module option in the program menu. The types of modules
available for the control panel are, 5860 (Keystation) 5824 (Serial/Parallel input/output), 5880 (LED Input/
Output module), 5496 (Intelligent Power Module), and a 5865 (LED Annunciator).
7.2.1Edit Modules
The features that can be edited when this option is selected are, module name, and class of wiring (Class A or
Class B).
T o edit an existing module, follow these steps:
1.Enter the installer code.
2.Select 7 for Program Menu.
3.Press 1 to enter module menu.
4.Press 1 to edit a module.
5.Use the or arrow to select the module you wish to edit.
7.2.1.1Naming Modules
You can assign an English name to a hardware module to make it easier to recognize on a display.
6.T o edit a module name, press the or arrow to select each character for the modules name (or press
to bypass name edit). Press the to move to the next character.
Figure 7-1 Edit module Name Programming Screen Example
7.2.1.2Module, Wiring Class
7.Choose the class of wiring you wish to use for this module by pressing the or arrow, then press
ENTER.
7.2.2Adding a Module
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code. If you need to add a
new hardware module to the system, follow the steps below.
1.Enter the installer code.
2.Select 7 for Program Menu.
7-2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.