SilentKnight SK-5600 User Manual

Page 1
INTELLIKNIGHT
5600/5600C/
5600HV
Addressable Fire Control Panel
®
Installation and Operations Manual
Document 151450 03/08/2013 Rev: E2
151450:E2 ECN: 13-0232
ECN: 13-0232
Page 2
Page 3
Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free
installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFP A 72 af ter any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Remove DC power prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
Page 4
These instructions must be followed to avoid damage to the control panel and associated equipment. FACP (Fire Alarm Control Panel) operation and reliability depend upon proper installation.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written records of all inspections should be kept.
Page 5

Contents

Contents
Section 1
Introduction ..................................................................................................................................................1
1.1 Overview of Basic System ...........................................................................................................1
1.1.1 Hardware Features ...............................................................................................................1
1.1.2 Software Features .................................................................................................................1
1.2 About this Manual ........................................................................................................................2
1.2.1 Terms Used in this Manual ...................................................................................................2
1.3 Compatible Products .............................................................................. ... ... ... .... ... ... ... ... ............2
1.4 How to Contact Silent Knight .......................................................................................................2
Section 2
Agency Listings, Approvals, and Requirements .......................................1
2.1 Federal Communications Commission (FCC) .............................................................................1
2.2 Underwriters Laboratories (UL) ...................................................................................................3
2.2.1 Requirements for All Installations .................................................... ... ..................................3
2.2.2 Requirements for Central Station Fire Alarm Systems .........................................................4
2.2.3 Requirements for Local Protected Fire Alarm Systems ................................ ... ... ... ... .... ........ 4
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems ......... ...............................4
2.3 ULC Requirements ......................................................................................................................4
Section 3
Before You Begin Installing ...................................................................................................1
3.1 What’s in the Box? ......................................................................................................................1
3.2 Environmental Specifications ............................................. .... ... ... ... ... .... ... ... ... .... ... ... ..................1
3.3 Electrical Specifications ................... ... .........................................................................................2
3.4 Wiring Specifications ...................................................................................................................3
3.5 Board Assembly Diagram ...................... ... .... ...............................................................................5
3.6 Calculating Current Draw and Standby Battery ...........................................................................6
3.6.1 Worksheet Requirements .....................................................................................................6
3.6.1.1 Current Draw Worksheet for 5600 for UL 864 .............................................................7
3.6.1.2 Current Draw Worksheet for 5600 ULC ......................................................................9
3.6.2 Maximum Battery Standby Load for UL 864 .......................................................................11
3.6.3 Maximum Battery Standby Load for ULC ...........................................................................11
Section 4
Control Panel Installation ..........................................................................................................1
4.1 Mounting the Control Panel Cabinet ...........................................................................................1
4.1.1 Preventing Water Damage ....................................................................................................1
4.1.2 Removing the 5600 Assembly from the Housing ......................... ....................................... .. 1
4.1.3 Dead Front Installation and removal .....................................................................................2
1
Page 6
Installation Manual
4.1.3.1 Installing the Dead Front ................. ... ... .... ... ... ... .........................................................2
4.1.3.2 Dead Front Removal ...................................................................................................3
4.2 AC Power Connection ..................... ... ................................................................. ........................4
4.2.1 AC Power Connection for UL 864 applications ............ .... ... ... ... ... .... ... ... ... .... ... ... ... ... .... ... ... ..4
4.2.2 AC Power Connection for Canadian Applications ............................................... ... ... .... ... ... ..5
4.3 Battery Connection ......................................................................................................................6
4.3.1 RBB Accessory Cabinet ........................................................................................................7
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries ..................................................7
4.4 SBUS Wiring ...................... ... ............................................................. .... ... ... ... .... ... ... ..................9
4.4.1 Calculating Wiring distance for SBUS modules ............... ..................................................... 9
4.4.2 Wiring Configurations ..........................................................................................................12
4.5 5635 Remote Annunciator Installation ......................................................................................13
4.5.1 Mounting the 5635 ..............................................................................................................14
4.6 Model 5635 Connection to the Panel .............................................. ... .... ...................................15
4.7 Configuring Module ...................................................................................................................16
4.7.1 Assigning Module IDs .........................................................................................................16
4.8 Telephone Connection ..............................................................................................................17
4.9 Notification Appliance/Auxiliary Power Circuits .........................................................................18
4.9.1 Conventional Notification Appliance Circuit ........................................................................ 18
4.9.2 Auxiliary Power Installation .................................................................................................19
4.9.2.1 Door Holder Power ....................................................................................................19
4.9.2.2 Constant Power .........................................................................................................20
4.9.2.3 Resettable Power ......................................................................................................20
4.10 On-Board Relays (Conventional, Power Limited) ......................................................................21
4.10.1 Common Trouble Relay .....................................................................................................21
4.10.2 Programmable Relays .......................................................................................................21
4.11 Remote Station Applications .....................................................................................................22
4.11.1 City Box Connection Using the 5220 Module .................................................................... 22
4.11.2 NFPA 72 Polarity Reversal ................................................................................................24
4.11.2.1Alarm, Supervisory and Trouble Reverse Polarity Outputs .................... ... ... ... .......... 24
Section 5
SLC Device Installation ................................................................................................................1
5.1 List of SLC Devices .....................................................................................................................1
5.2 Maximum Number of Devices .....................................................................................................1
5.3 Wiring Requirements for SLC Devices ........................................................................................2
5.3.1 Wiring SLC in Style 4 (Class B) Configuration ....................... ....................................... ........ 2
5.4 Wiring SLC Detectors ..................................................................................................................5
5.5 Addressing SLC Devices .............................................................................................................6
Section 6
Programming .............................................................................................................................................1
6.1 UL 864 Programming Requirements ...................................... ................................................ ..... 1
6.2 Control Panel Programming ........................................................................................................2
6.3 Default Control Panel Configuration. .................. ................................................. ........................2
6.3.1 Default Mapping of SLC Inputs to Outputs ...........................................................................2
6.3.2 Mapping of SLC Inputs to Outputs. ......................................................................................3
6.3.3 Default Mapping for the 2 built-in Notification Circuits. .........................................................4
6.3.4 Maximum SLC address point count ......................................................................................5
2
Page 7
Contents
6.3.5 Installer Code ........................................................................................................................5
6.4 JumpStart AutoProgramming ......................................................................................................5
6.5 Modifying Panel Programming using a PC ................... ... ... .... ... ... ... ... .... .....................................6
6.5.1 Connecting the panel to a PC ...............................................................................................6
6.6 Panel Programming Options .......................................................................................................7
6.6.1 System Options ............................................................................................. ... ... ... ...............7
6.6.1.1 Synchronized Strobes Active When Horns Silenced ..................................................7
6.6.1.2 Silence/Reset Inhibit Enabled .....................................................................................7
6.6.1.3 Water Flow Delay ........................................................................................................7
6.6.1.4 Installer Code (User ID) ..............................................................................................7
6.6.1.5 Alarm Verification Time ...............................................................................................7
6.6.1.6 Auto Test .....................................................................................................................7
6.6.1.7 Low AC Report Delay ................... ... ... ... .... ... ... ... .... .....................................................7
6.6.1.8 Walk Test Reporting ....................................................................................................8
6.6.1.9 Walk Test duration ......................................................................................................8
6.6.1.10 Walk Test NAC Time out ............................................................................................8
6.6.1.11 Clock Source ..............................................................................................................8
6.6.1.12 Auto Daylight Savings Time .......................................................................................8
6.6.1.13 Remote Annunciator ..................................................................................................8
6.6.2 Zone Programming ...............................................................................................................9
6.6.2.1 SLC Addresses Within Each Zone ..............................................................................9
6.6.2.2 Zone Silenceable ........................................................................................................9
6.6.2.3 Zone Type ...................................................................................................................9
6.6.3 Output Point Programming ...................................................................................................9
6.6.4 Notification Appliance Circuit (NAC) Programming .......................... ......... .......... .......... ......10
6.6.4.1 Circuit Function .........................................................................................................10
6.6.4.2 Conventional Notification Circuit Mapping ................................................................10
6.6.5 Relay Programming Options ...............................................................................................11
6.6.5.1 General System Relay Silence Option ......................................................................11
6.6.6 Dialer Phone Line Programming Options ...........................................................................11
6.6.6.1 Line Prefix .................................................................................................................11
6.6.6.2 Dial Tone Detection ...................................................................................................11
6.6.6.3 Line Monitoring Enabled (Y/N) ..................................................................................12
6.6.6.4 Dialing Option ............................................................................................................12
6.6.6.5 Pulse Dialing Format ................................................. ... ... ... .... ... ................................12
6.6.7 Dialer Account programming Options .................................................................................13
6.6.7.1 Account Number .......................................................................................................13
6.6.7.2 Phone Number ............................................................................. ... .... ... ...................13
6.6.7.3 Reporting Format ......................................................................................................13
6.6.7.4 Reporting Filters ........................................................................................................13
Section 7
System Operation ................................................................................................................................1
7.1 System Reset ........... ... .... ... ... ... .... ... ............................................................. ... .... ... .....................1
7.2 Lamp Test ................... .... ............................................................. ... ... .... .....................................1
7.3 System Silence ................... ... ... .... ... ... ... ... .... ............................................................. ..................1
7.4 Acknowledge ...............................................................................................................................1
7.5 Viewing Active Alarm Points ........................................................................................................1
7.6 Viewing Active Supervisory Points ..............................................................................................2
7.7 Viewing Active Trouble Points ................................... ................................................ ..................2
7.8 Walk Test ....................................................................................................................................2
3
Page 8
Installation Manual
7.9 Fire Drill .......................................................................................................................................2
7.10 Zone Disable Feature ...................................................... ... .... ... ... ... ... .... ... ..................................3
7.11 Disabling Notification Circuits ......................................................................................................3
7.12 Loss of AC power ........................................................................................................................3
7.13 Remote Connection Feature (ULC Installations Only) 3
7.14 Low Battery .............. ... .... ... ... ... .............................................................. ... ... ... ............................4
7.15 Ground Fault ................... ... ... ... .... ... ............................................................. ... .... ... .....................4
7.16 Phone Line Monitoring ...............................................................................................................4
7.17 Reporting Account Monitoring .....................................................................................................4
7.18 SLC Fault ....................................................................................................................................4
7.19 Dialer Error ..................................................................................................................................4
7.20 Annunciator Description ..............................................................................................................5
7.20.1 LCD Displays .......................................................................................................................5
7.20.2 Banner .................................................................................................................................6
7.21 Basic Operation ...........................................................................................................................7
7.21.1 Conduct a Fire Drill ..............................................................................................................7
7.21.2 Conduct an Indicator Test ...................................................................................................7
7.21.3 Silence alarms or troubles ...................................................................................................7
7.21.4 Reset alarms .......................................................................................................................7
7.21.5 View Alarms or Troubles .....................................................................................................7
7.22 Operation Mode Behavior .................. ... ... .... ... ... ... .... ... ... ... .... .....................................................8
Section 8
Reporting .........................................................................................................................................................1
8.1 Receivers Compatible with the Control Panel .............. ... ... .... ... ... ... ... .... .....................................1
8.2 Reporting Formats Dialer Outputs ...................... ................ .................... ................... ..................1
Section 9
Trouble Shooting and Quick Tips ..................................................................................1
9.1 Troubleshooting .................................. ................ ................ .................... ................ .....................1
9.1.1 JumpStart ..............................................................................................................................1
9.1.2 View Active Points ................................................................................................................1
9.1.3 Disable Or Re-Enable A Zone ..............................................................................................1
9.1.4 Silence the Board PZT ..........................................................................................................1
9.1.5 Silence the Notification Appliances .......................................................................................1
9.1.6 To Initiate a Fire Drill ........................................................... ..................................................2
9.1.7 For a Dialer Test ...................................................................................................................2
9.1.8 For a Lamp Test ....................................................................................................................2
9.1.9 AC LED .................................................................................................................................2
9.1.10 Walk Test .............................................................................................................................2
9.1.11 Seven Segment Display ......................................................................................................2
9.2 Web Server Menus ................... .... ... ... ... ... .... ... ... ... ......................................................................3
9.2.1 To add a smoke detector: ............................................................ .... ... ..................................3
9.2.2 To add a notification appliance (fire bell) .................................................. .... ... ... ... ... .... ... .....3
9.2.3 To add a Remote Annunciator (DIP switch address 1 or 2) ................... .......... ......... .......... ..3
9.2.4 To add custom Zone name .......................................... .... ... ... ... ... .... ... ... ... .... ........................4
9.2.5 To trip an SLC notification appliance ........... ... .... ... ... ... .... ... ... ... ... .... .....................................4
9.2.6 To trip a Door Holder ............................................................................................................4
4
Page 9
Appendix A
Contents
Compatible Devices
..........................................................................................................................1
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability Model 5600/5600C/5600HV Basic Operating Instructions
5
Page 10
Installation Manual
6
Page 11

Section 1 Introduction

The 5600 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 864, ULC 527, and ULC 559. Unless otherwise indicated, all references to 5600 also refer to 5600C and 5600HV.

1.1 Overview of Basic System

1.1.1 Hardware Features

The 5600 has one signaling line circuit (SLC) that supports 25 Honeywell Fire
Systems (HFS) or SK SLC devices, and one SBUS circuit that supports two remote annunciators.
2.0A of output power is available through 2 sets of terminals for notification
appliance circuits or 1.0A for auxiliary power applications. Each circuit is power limited per UL 864 and can source up to 2.0A
Note: Total output power for all three circuits must not exceed 2.0A.
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
Reports events to central station by zone.
Two general purpose Form C programmable relays.
One Form C Trouble Relay.

1.1.2 Software Features

The 5600 is an addressable panel that operates like a 5 zone conventional panel.
Advanced addressable smoke detector features:
–Automatic drift compensation –Maintenance alert region –Point status meets calibrated smoke test requirements for NFPA 72
Auto learn “JumpStart” feature for easy programming.
A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal.
Built-in synchronization appliance support for Amseco, Gentex®, Wheelock®, or
System Sensor
®
.
151450 1-1
Page 12
Model 5600 Installation and Operation Manual

1.2 About this Manual

This manual is intended to be a complete reference for all installation and operation tasks for the 5600. Please let us know if the manual does not meet your needs in any way. We value your feedback!

1.2.1 Terms Used in this Manual

The following terminology is used with the 5600 system:
Term Description
SLC Signaling Line Circuit Input Point An addressable sensing device, such as a smoke or heat
detector or a contact monitor device. Input Zone A protected area made up of input points. Output Point
(or Output Circuit)
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant
A notification point or circuit for notification appliances.
Relay circuits and auxiliary power circuits are also
considered output points.
or ANSI 3.41.

1.3 Compatible Products

See Section 5.1 for a list of compatible SLC devices from Silent Knight for use with the 5600.
See Appendix A for a list of compatible notification appliances.

1.4 How to Contact Silent Knight

If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Customer Service at 800-328-0103 or 203-484-7161.
1-2 151450
Page 13
Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located.
Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density . If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused
151450 1-3
Page 14
Model 5600 Installation and Operation Manual
by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability, deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
Please note that: i) Strobes can, under certain circumstances, cause seizures in people with con-
ditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm sig-
nal, do not respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly, they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance.
1-4 151450
Property owners should
Page 15
Introduction
continue to act prudently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems in­cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
Smoke Detectors shall be installed in sleeping rooms in new construction and it is recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per apartment or residence.
It is recommended that smoke detectors be located in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire.
All fire alarm systems require notification devices, including sirens, bells, horns, and/or strobes. In residential applications, each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels (at least 15dB above noise) with all intervening doors closed.
It is recommended that a smoke detector with an integral sounder (smoke alarm) be located in every bedroom and an additional notification device be located on each level of a residence.
T o keep your fire alarm system in excellent working order , ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter 14 of NFPA 72, 2010 Edition shall be followed. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance. As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
151450 1-5
Page 16
Model 5600 Installation and Operation Manual
1-6 151450
Page 17

Section 2 Agency Listings, Approvals, and Requirements

Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of -line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to NFPA 72.

2.1 Federal Communications Commission (FCC)

The following information must be provided to the telephone company before the 5600 can be connected to the phone lines:
A Manufacturer: Honeywell International Inc. B Model Number: 5600 C FCC registration number: US: AC6AL05B205600
Ringer equivalence: 0.5B D Type of jack: RJ31X E Facility Interface Codes: Loop Start: 02LS2
Ground Start: 02GS2
F Service Order Code: 9.0F
1. This device may not be directly connected to coin telephone or party line services.
2. This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing company or return to:
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161
3. If the 5600 causes harm to the telephone network, the telephone company will notify the user in advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the user as soon as possible. Users have the right to file complaints, if necessary , with the Federal Communications Commission.
151450 2-1
Page 18
Model 5600 Installation and Operation Manual
4. The telephone company may make changes in its facilities, equipment, opera­tions, or procedures that could affect the operation of the equipment. If this hap­pens, the telephone company will provide advance notice to allow you to make the necessary modifications to maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any inter­ference received, including interference that may cause undesired operation.
a) This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the ACTA. On the wiring diagram of this equipment is a label that contains, among other information, a product identifier in the format US: AC6AL05B-205600. If requested, this number must be provided to the telephone company.
b) See Section 4.8 for phone jack information. c) A plug and jack used to connect this equipment to the premises wiring and
telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACT A. A compliant telephone cord and modular plug is provided with this product. It is designed to be connected to a compatible modular jack that is also compliant. See installation instructions for details.
d) The REN is used to determine the number of devices that may be connected to a
telephone line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. For products approved after July 23, 2002, the REN for this product is part of the product identifier that has the format US: AC6AL05B-205600. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of
0.3). For earlier products, the REN is separately shown on the label.
e) If this equipment 5600 causes harm to the telephone network, the telephone
company will notify you in advance that temporary discontinuance of service may be required. But if advance notice isn't practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
f) The telephone comp any may make changes in its facilities, equipment, operations
or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
g) If trouble is experienced with this equipment 5600, for repair or warranty
information, please contact Silent Knight. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the problem is resolved.
h) See warranty in back of this manual for repair and replacement information.
2-2 151450
Page 19
Agency Listings, Approvals, and Requirements
i) Connection to party line service is subject to state tariffs. Contact the st ate public
utility commission, public service commission or corporation commission for information.
j) If your home has specially wired alarm equipment connected to the telephone
line, ensure the installation of this 5600 does not disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your telephone company or qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiring AC power should consider including an advisory notice in their customer information suggesting the customer use a surge arrestor. Telephone companies report that electrical surges, typically lightning transients, are very destructive to customer terminal equipment connected to AC power sources. This has been identified as a major nationwide problem.

2.2 Underwriters Laboratories (UL)

2.2.1 Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on).
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use ONLY the addressable smoke detectors specified in Section 5.1 of this man­ual.
3. Use UL listed notification appliances compatible with the 5600, choose from those specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL certified installations the setting must be a maximum of 60 seconds.
Call forwarding shall not be used.
Waterflow and Supervisory have to be set to Latching as shown in the restricted options table in Section 6. See Table 6-1:.
151450 2-3
Page 20
Model 5600 Installation and Operation Manual
2.2.2 Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5600 sends an automatic daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours.

2.3 ULC Requirements

Install in accordance with the Canadian Electrical Code, C22.1, Part 1, Section 32.
2-4 151450
Page 21

Section 3 Before You Begin Installing

This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly , especially if you are inst alling a 5600 panel for the first time.

3.1 What’s in the Box?

The 5600 ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Installation and Operation manual P/N 151450.
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series

3.2 Environmental Specifications

It is important to protect the 5600 control panel from water . To prevent water damage, the following conditions should be AVOIDED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the 5600 control panel, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C­49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.
151450 3-1
Page 22
Model 5600 Installation and Operation Manual

3.3 Electrical Specifications

Table 3-1 list the electrical specifications for the 5600 field wiring as well as a description of the each individual terminal and their respective electrical rating. For location of the terminals refer to 3.5. See also Section 4 for installation.
Table 3-1: Terminal Descriptions
Terminal
Block
TB 1 SBUS SBUS Power 27.4 VDC 100 mA 0
SLC Out SLC Terminals 24 VDC 100 mA 0
*NAC1 Notification Appliance
*NAC2 Notification Appliance
TROUBLENO Normally open relay
RELAY 1 NO Normally open relay
RELAY 2 NO Normally open relay
TB 2 TELCO 1 RING Phone Line 1 Telco Ring N/A N/A N/A
PHONE 1 RING Phone Line 1 Phone Ring
TELCO 2 RING Phone Line 2 Telco Ring
PHONE 2 RING Phone Line 2 Phone Ring
Label
Description
Group Individual V oltage Current Ohms
+ A SBUS Communication 3.3 VDC 10 mA 0 B
+
24 VDC 2.0 Amp 0
Circuit
+ Auxiliary power 1.0 Amp
24 VDC 2.0 Amp 0
Circuit
+ Auxiliary power 1.0 Amp
24 VDC 2.5 A, resistive N/A
contact COM Common terminal NC Normally closed relay
contact
24 VDC 2.5 A, resistive N/A
contact COM Common terminal NC Normally closed relay
contact
24 VDC 2.5 A, resistive N/A
contact COM Common terminal NC Normally closed relay
contact
TIP Phone Line 1 Telco Tip
TIP Phone Line 1 Phone Tip
TIP Phone Line 2 Telco Tip
TIP Phone Line 2 Phone Tip
Rating
Earth Ground
Fault Impedance
* Regulated for NAC circuits * Special application when used for auxiliary power circuits.
3-2 151450
Page 23
Before You Begin Installing

3.4 Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage AC power Terminals SLC loops Phone line circuits Notification circuits NAC1 through NAC2 Relay circuits SBUS Wiring
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield
151450 3-3
Page 24
Model 5600 Installation and Operation Manual
1/4” spacing must be maintained between power limited and Non­power limited
wiring
beads or by wrapping it around a ferrite toroid.
Figure 3-1 Wire Routing Example
3-4 151450
Page 25

3.5 Board Assembly Diagram

Form C Trouble
On-board
Annunciator
Battery Connector
AC Power Input
Form C
Programmable
Relays
AC Power Input
Battery Connector 24VDC
Ethernet Programming Port
Mounting screw
Location Mounting Pin
Mounting screws
Slide-In Stand-offs
SBUS
SLC Out
NAC/AUX
Power
Circuits
Phone Lines
Before You Begin Installing
Figure 3-2 Model 5600 Assembly
Figure 3-2 shows the 5600 circuit board stack. If you should need to remove the control board for repair, remove the three mounting screws which hold the control board in the cabinet, slide out of slot from slide-in standoff. Then lift the control board off the location mounting pin and out of the cabinet.
151450 3-5
Page 26
Model 5600 Installation and Operation Manual

3.6 Calculating Current Draw and Standby Battery

This section is for helping you determine the current draw and standby battery requirements (Table 3-2).

3.6.1 Worksheet Requirements

The following steps must be taken when determining 5600 current draw and standby battery requirements.
1. For the 5600, the worst case current draw is listed for the panel and all address­able devices. Fill in the number of addressable devices that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in the Current Calculation Worksheet at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliance circuits and auxiliary devices not mentioned in the man­ual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed 2.0 A. This is the maximum alarm current for the 5600 control panel.
If the current is above 2.0 A you will need to use a notification power expander(s) such as the Silent Knight 5495 power module to distribute the power loads so that the 5600 or the power expanders do not exceed their power rating.
6. Complete the remaining instructions in the Current Calculation Worksheet for determining battery size requirements.
3-6 151450
Page 27
Before You Begin Installing
3.6.1.1 Current Draw Worksheet for 5600 for UL 864
Use Table 3-2 to determine amp-hour requirements during alarm/battery standby operation. (Copy the page if additional space is required.) You can install up to 25 SLC devices and two 5635 Remote Annunciator.
Table 3-2: Current Calculation Worksheet for SLC Devices
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery)
Accessory Modules 5635 Remote Annunicator
Addressable SLC Detectors HFS-P HFS-PT mA mA HFS-D mA mA HFS-T mA mA SK-Photo mA mA SK-Photo-T mA mA SK-DUCT mA mA SK-Heat mA mA Addressable SLC Modules HFS-MM SK-Pull-SA Standby/Alarm: .375 mA mA mA SK-PULL-DA Standby/Alarm: .375 mA mA mA
HFS-MR SK-Minimon Standby/Alarm: .375 mA mA mA
SK-Relay Standby/Alarm: .375 mA mA mA SK-ISO 10 max. St andby/Alarm: .45 mA mA mA
A Total System Current
Auxiliary Devices Refer to devices manual for current rating.
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
C Notification Appliances Current D Total current ratings of all devices in system (line A + line B + C) mA mA
1
2
(25 max.
detectors or
modules in
any combina-
tion)
(25 max.
detectors or
modules in
any combina-
tion)
Standby: 135 mA 135 mA Alarm: 220 mA 220 mA
Standby: 37 mA mA Alarm: 40 mA mA
Standby: 0.27 mA Alarm: 6.5 mA
Standby/Alarm: .375 mA mA mA
Standby/Alarm:
0.255mA
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
Alarm: mA mA Alarm: mA Alarm: mA Alarm: mA
Standby
Current
mA mA
mA mA
Alarm
Current
mA mA mA mA
151450 3-7
Page 28
Model 5600 Installation and Operation Manual
Table 3-2: Current Calculation Worksheet for SLC Devices
Device # of Devices Current per Device
E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. Total st andby AH AH H Alarm sounding pe riod in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH AH J
Add lines G and I.
1. Use next size battery with capacity greater than required.
1
Total ampere
hours required
Standby
Current
AH
Alarm
Current
3-8 151450
Page 29
Before You Begin Installing
3.6.1.2 Current Draw Worksheet for 5600 ULC
Use to determine amp-hour requirements during alarm/battery standby operation. (Copy the page if additional space is required.) You can install up to 25 SLC devices and two 5635 Remote Annunciator. The maximum battery size for ULC inst allations is 18 Amp/hr.
Table 3-3: Current Calculation Worksheet for SLC Devices for ULC
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery)
Accessory Modules 5635 Remote Annunicator
Addressable SLC Detectors HFS-PA HFS-PTA mA mA HFS-DA mA mA HFS-TA mA mA SK-Photo mA mA SK-Photo-T mA mA SK-DUCT mA mA SK-Heat mA mA Addressable SLC Modules HFS-MMA SK-Pull-SA Standby/Alarm: .375 mA mA mA SK-PULL-DA Standby/Alarm: .375 mA mA mA HFS-MRA Standby/Alarm: .255mA mA mA SK-Minimon Standby/Alarm: .375 mA mA mA SK-Relay Standby/Alarm: .375 mA mA mA SK-ISO 10 max Standby/Alarm: .45 mA mA mA
A Total System Current
Auxiliary Devices Refer to devices manual for current rating.
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
C Notification Appliances Current D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A
1
2
25 max.
25 max
Standby: 165 mA 165 mA Alarm: 220 mA 220 mA
Standby: 37 mA mA Alarm: 40 mA mA
Standby: .27 mA Alarm: 6.5 mA
Standby/Alarm: .375 mA mA mA
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
Alarm: mA Alarm: mA Alarm: mA
Standby
Current
mA mA
Alarm
Current
mA mA mA mA
151450 3-9
Page 30
Model 5600 Installation and Operation Manual
Table 3-3: Current Calculation Worksheet for SLC Devices for ULC
Device # of Devices Current per Device
F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. Total st andby AH AH H Alarm sounding pe riod in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
1. Use next size battery with capacity greater than required.
1
Total ampere
hours required
Standby
Current
AH
Alarm
Current
AH
3-10 151450
Page 31
Before You Begin Installing

3.6.2 Maximum Battery Standby Load for UL 864

Table 3-4 shows the standby load calculations for the 5600 based on 24 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet must be less than the number shown in Table 3-4 for the selected battery size, standby hour and alarm time. The numbers below have a built in 20% de-rating factor for the battery amp hour capacity.
Table 3-4: Maximum Battery Standby loads for 24 Hour Standby
Rechargeable
Battery Size
7 AH 226 mA 213 mA 206 mA 12 AH 393 mA 379 mA 372 mA 18 AH 593 mA 579 mA 572 mA 24 AH 793 mA 779 mA 772 mA 33 AH 1.09 A 1.08 A 1.07 A
24 hr Standby,
5 mins. Alarm
24 hr Standby,
15 min alarm
24 hr Standby,
20 min alarm

3.6.3 Maximum Battery Standby Load for ULC

Table 3-5 shows the ULC standby load calculations for the 5600C based on 24 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet must be less than the number shown in Table 3-5 for the selected battery size, standby hour and alarm time. The numbers below have a built in 40% derating factor for the battery amp hour capacity.
Table 3-5: Maximum Battery Standby loads for ULC 24 Hour Standby
Rechargeable
Battery Size
7 AH 226 mA 213 mA 206 mA 12 AH 393 mA 379 mA 372 mA 18 AH 529 mA 515 mA 508 mA
24 hr Standby,
5 mins. Alarm
24 hr Standby,
15 min alarm
24 hr Standby,
20 min alarm
Warning
Silent Knight does not support the use of batteries smaller than those listed in Table 3-4. If you use a battery too small for the installation, the system could overload the battery resultin g in the installation having less than the required 24 hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for your installation. It is recommended that you replace batteries every five years.
151450 3-11
Page 32
Model 5600 Installation and Operation Manual
3-12 151450
Page 33

Section 4 Control Panel Installation

Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.

4.1 Mounting the Control Panel Cabinet

Read the environmental specifications in Section 3.2 before mounting the 5600 panel.
The 5600 cabinet dimensions are:
12-3/4” W x 15-1/8” H x 3-3/8” D (32.39 cm W x 38.42 cm H x 8.57 cm D).
The 5600 panel should be located within a secured area, where it is accessible to main drop wiring runs and where it can be easily tested and serviced. Building occupants are responsible for maintaining the panel should be able to hear alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is expected, attach a piece of 3/4 inch plywood to the concrete surface and then attach the 5600 to the plywood. Also mount any other desired components to the plywood.
DO NOT flush-mount the 5600 cabinet.

4.1.1 Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.

4.1.2 Removing the 5600 Assembly from the Housing

If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by removing the screws that hold the control panel in to the cabinet. Do not attempt to disassemble the circuit boards.
151450 4-1
Page 34
Model 5600 Installation and Operation Manual
Dead Front Panel

4.1.3 Dead Front Installation and removal

This section provides instructions to install and or remove the dead front for the control panel cabinet.
4.1.3.1 Installing the Dead Front
Follow these steps to properly install the dead front panel into the control panel cabinet.
1. Remove the top two annunciator screws, do not discard them they will be reused. See Figure 4-1 for annunciator screw location.
2. Set the dead front into the cabinet as shown in Figure 4-1.
3. Reinsert the two annunciator screws as shown in Figure 4-1.
Figure 4-1 Dead Front Installation and Removal
4-2 151450
Page 35
Control Panel Installation
4.1.3.2 Dead Front Removal
Follow these steps to properly remove the dead front panel from the control panel cabinet.
1. Remove the two annunciator screws, do not discard them. See Figure 4-1.
2. Tilt the dead front forward to clear the top of the cabinet and left the dead front out of the cabinet. See Figure 4-1.
3. Reinsert the two annunciator screws. See Figure 4-1.
151450 4-3
Page 36
Model 5600 Installation and Operation Manual
Ground
To AC
Supervised AC Connection

4.2 AC Power Connection

4.2.1 AC Power Connection for UL 864 applications

At installation, connect the AC terminals to the power source as shown in Figure 4-2. It may be necessary for a professional electrician to make this connection. Connect black and white wires from transformer to 120V power. Connect ground wire from 120V power to screw labeled G on the 5600 circuit board.
The AC power input is rated at 120 VAC, 60 Hz, 1.5A for 5600 and 230 VAC, 50/ 60Hz,.75A for 5600HV.
Figure 4-2 120/230 VAC Power Connection
4-4 151450
Page 37
Control Panel Installation

4.2.2 AC Power Connection for Canadian Applications

For Canadian applications, an AC terminal block is supplied standard with the 5600C. The AC terminal block is factory installed on the left of the circuit board chassis as shown in Figure 4-3.
Figure 4-3 AC terminal Block Connections
151450 4-5
Page 38
Model 5600 Installation and Operation Manual
Red
Battery Jumper
(P/N 140694)
Shipp e d With P a ne l
Black
Supervised
Battery 2Battery 1
12V Battery
12V Battery

4.3 Battery Connection

The control panel battery charge capacity is 7.0 to 33 AH or 18 AH for ULC installations. The main control cabinet can house batteries up to 7 AH, larger capacity batteries can be housed in a Remote Battery Box (P/N RBB). See Section 4.3.1 for details. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6). Maximum charging current for batteries is 3.1A @ 27 VDC.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
The following steps and diagram explain how to connect the batteries.
1. Connect the black wire from the control panel negative (–) battery terminal to the negative (–) side of Battery #2.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of Bat­tery #2 to the (–) negative side of Battery #1.
3. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1.
4-6 151450
Figure 4-4 Battery Connection
Page 39
Control Panel Installation
Cabinet
Mounting Holes

4.3.1 RBB Accessory Cabinet

The Model RBB Accessory cabinet can be used when your backup batteries are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See figure Figure 4-5 for the four cabinet mounting holes.
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch
plywood. This is necessary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a
piece of ¾ inch plywood to the concrete surface and then attach the RBB cab­inet to the plywood.
If using the battery cable extenders provided (P /N 140643), mount the RBB
cabinet no more than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the battery terminals.
Figure 4-5 RBB Cabinet Mounting Holes
151450 4-7
Page 40
Model 5600 Installation and Operation Manual
RB B Ca bine t Cover Screws
Conduit
Conduit Coupler
RB B Ca bin e t Cover Screws
+
+
-
-
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-6.
Figure 4-6 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-7.
Figure 4-7 Battery Connections in the RBB Cabinet
Note: Figure 4-7 is an example of how the wire connections can be routed. However, any other cabinet
knock-outs (on either the main control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets.
4. Connect battery leads to the backup battery terminals. See Figure 4-7. Observe the proper polarity to prevent damage to the batteries or the control
panel.
5. Insert the RBB cover screws into the cover mounting holes (see Figure 4-7). Screw the cover screw ¾ of the way into the cover mounting hole.
4-8 151450
Page 41
Control Panel Installation
Cover Plate
Mounting Keyholes
6. Align the cover plate mounting keyhole over the cover mounting screws. See Fig­ure 4-8.
Figure 4-8 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-8.

4.4 SBUS Wiring

This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class B).

4.4.1 Calculating Wiring distance for SBUS modules

The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4- conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 500 mA.
Model Number Worst Case Current Draw
5635 Remote Fire Annunciator .04 amps
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance the modules can be located from the panel on a single wire run. The table insures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
151450 4-9
Page 42
Model 5600 Installation and Operation Manual
Table 4-1: Wire Distance Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
Note: The following formulas were used to generate the wire distance chart:
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms) * 500
6.0 Volts
Rpu
Table 4-2: Typical Wire Resistance per 1000 ft. using Copper Wire
Wire Gauge
22 16.2 18 6.4 16 4.02 14 2.54
Ohms per 1000 feet
(Rpu)
4-10 151450
Page 43
Control Panel Installation
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 1 - Module 5635 Fire Annunciator The total worst case current is calculated as follows:
5635 Current Draw = 1 x .04 amps = .04 amps
Total Worst Case Current Draw = .04 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
1852 feet maximum using 22 Gauge wire 4688 feet maximum using 18 Gauge wire 6000 feet maximum using 16 Gauge wire 6000 feet maximum using 14 Gauge wire
151450 4-11
Page 44
Model 5600 Installation and Operation Manual
Supervised Power Limited
5635

4.4.2 Wiring Configurations

Figure 4-9 illustrates Class B configuration.
Figure 4-9 SBUS Class B Wiring
4-12 151450
Page 45
Control Panel Installation

4.5 5635 Remote Annunciator Installation

The optional Model 5635R (red) and 5635W (white) Remote Annunciator is shown in Figure 4-10.
Figure 4-10 Model 5635 Remote Annunciator, Front View
5635 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the 5635 in the desired location (see Section 4.5.1).
3. Connect the 5635 to the panel (see Section 4.6).
4. Use the DIP switches on the back of the 5635 to assign an ID# to the 5635 (see Section 4.7.1).
5. The new 5635 module must be added to the system through programming. Jump­St art will add the module automatically (see Section 6.4). You can also add it man­ually (see installation sheet PN 53958).
151450 4-13
Page 46
Model 5600 Installation and Operation Manual
Back Box
Inside Cover LCD Display

4.5.1 Mounting the 5635

This section of the manual describes mounting the remote annunciator. Figure 4-11 shows the parts of the annunciator.
Figure 4-11 5635 Annunciator Parts
The 5635 Series plastic enclosures can be surface or semi-flush mounted in a single, double or 4” square electrical box.
To mount the 5635 Series enclosure:
1. Open the 5635 Series cover by turning the key switch counterclockwise to the ON (Unlocked) position.
2. Push in the snap latch tab located on the right side while pulling the cover open.
3. Pull wire through 7/8” hole in backplate and feed through wire channel to lower left corner of backplate before routing to terminal block.
4. The cover must remain attached to the backplate while mounting the annunciator to the electrical box/ wall. The cover cannot be reattached or removed after the annunciator has been mounted.
5. Surface or Semi-flush mount the 5635 to a single, double or 4" square electrical box. The ANN-SB80KIT(-R/-B/-W) is an available kit that contains two plastic backboxes that can be used to surface mount the 5635.
4-14 151450
Page 47
Control Panel Installation
Supervised Power Limited

4.6 Model 5635 Connection to the Panel

Connect the 5635 to the panel as shown in Figure 4-12.
Figure 4-12 Model 5635 Connection to the Panel
151450 4-15
Page 48
Model 5600 Installation and Operation Manual
ID Number (Address)
(not valid) 00
01
DIP Switch

4.7 Configuring Module

This section describes how to configure the 5635 Annunciator that has been added to the system. Each SBUS device requires a unique address. 5635 Series DIP switch S21 is used to set the address. This address will be displayed on the LCD display as the Station ID number.

4.7.1 Assigning Module IDs

When installing the 5635 you must use the DIP switches on the module to assign an ID# to the module. A maximum of 2 devices can be connected to the FACP SBUS communication circuit. The SBUS device address needs to be set to 01or 02.
Note: Note that 00 is not a valid address.
Figure 4-13 shows the DIP switch positions and their correlation to a numerical ID.
Figure 4-13 DIP switch settings
4-16 151450
Page 49
Control Panel Installation
Use Minimum of 26 AWG Telephone Line cord

4.8 Telephone Connection

Connect the telephone lines as shown in Figure 4-14. The Model 7860 phone cord is available from Silent Knight for this purpose.
Figure 4-14 Connection of Telephone Lines
151450 4-17
Page 50
Model 5600 Installation and Operation Manual

4.9 Notification Appliance/Auxiliary Power Circuits

The two outputs of the 5600 FACP can be programmed to be used as NACs or as Aux power.
This section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.

4.9.1 Conventional Notification Appliance Circuit

The 5600 supports Class B (Style Y) configurations for notification appliance applications.
Y ou must use an appliance from the list of comp atible appliances in the Appendix A at the back of this manual. Each circuit can source up to 2.0A (total current for the system must not exceed 2.0A)
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 4-15.
2. Configure the circuit through programming.
Figure 4-15 Class B Notification Appliance Circuit Wiring
4-18 151450
Page 51
Control Panel Installation
Non-Supervised Power Limited
+
Special Application DC Circuit

4.9.2 Auxiliary Power Installation

NAC Circuits 1 and 2 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are:
Door Holder (see section 4.9.2.1)
Constant (see section 4.9.2.2)
Resettable Power (see section 4.9.2.3)
Auxiliary power circuits are power limited. Each circuit can source up to 1.0A (total current for system must not exceed 2.0A).
To install an auxiliary power circuit:
1. Wire the NAC circuit(s) that will be used for auxiliary power. See 3.5 for location of NAC circuits.
2. Configure the auxiliary power output through programming.
4.9.2.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 24 volt power present at their terminals. Any alarm will cause power to disconnect. Power will be re­applied when the system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits.
Figure 4-16 Example of an Auxiliary Power For Door Holder
Use a UL listed door holder see list from Appendix A-3, for this application.
151450 4-19
Page 52
Model 5600 Installation and Operation Manual
4.9.2.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
4.9.2.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24 volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re­applied.
4-20 151450
Page 53
Control Panel Installation

4.10 On-Board Relays (Conventional, Power Limited)

The control panel has two built-in programmable relays and a built-in trouble relay . All relays are Form C rated at 2.5 A @ 24 VDC Resistive.

4.10.1 Common Trouble Relay

The control panel has a dedicated Form C trouble relay built into terminals labeled TROUBLE. The relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble condition. Form C rated at 2.5 A @ 24 VDC Resistive.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no
alarm or trouble conditions.

4.10.2 Programmable Relays

The control panel has two Form C programmable relays built into terminals labeled RELAY 1 or RELAY 2. Each relay provides a normally open and a normally closed contact.
To configure one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See 4.10.1 for the location of the relay terminals.
2. Default programming causes Relay 1 to activate for any supervisory. Relay 2 will activate for any alarm. For relay applications that require different behavior see Section 6.
151450 4-21
Page 54
Model 5600 Installation and Operation Manual

4.11 Remote Station Applications

4.11.1 City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current
accounted for in control panel draw.) Alarm Current: 1 Amp for 1 second Max Voltage: 24 VDC The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the
5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-17. This drawing also
shows how to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program NAC1 as auxiliary and power constant on. Program NAC2 as a non-
silencing, constant on notification circuit.
4-22 151450
Page 55
Control Panel Installation
Note: NAC Circuit 2 Used as an Example. Either NAC Circuit Can Be Used.
Supervised for Opens and Ground faults only Non-Power Limited
It is not possible to reset the remote indication until you clear the condition and reset the control panel.
151450 4-23
Figure 4-17 City Box Connection
Page 56
Model 5600 Installation and Operation Manual

4.11.2 NFPA 72 Polarity Reversal

4.11.2.1 Alarm, Supervisory and Trouble Reverse Polarity Outputs
Three HFS-MR or SK-Relay modules are required to independently report alarm, supervisory and trouble. SLC addresses 141, 143, and 147 must be used as shown in Figure 4-18.
Figure 4-18 Reverse Polarity output wiring
4-24 151450
Page 57

Section 5 SLC Device Installation

Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.

5.1 List of SLC Devices

The following SLC devices can be used with the control panel. See the device installation instructions for more information (packaged with the device).
Part Number Model Name/Description Install Sheet PN
HFS-P, HFS-PA, SK-Photo Photoelectric smoke detector HFS-PT, HFS-PTA,
SK-Photo-T HFS-D, HFS-DA, SK-Duct Photoelectric duct smoke detector with extended air
HFS-T, HFS-TA, SK-Heat Fixed temperature thermal detector (135°F) I56-3485-00, I56-3429-00 SK-Pull-SA Addressable single action pull station I56-3446-001 SK-Pull-DA Addressable dual action pull station I56-3347-001 HFS-MM, HFS-MMA,
SK-Minimon HFS-MR, HFS-MRA, SK-Relay Addressable relay module I56-3486-000, I56-3438-
SK-ISO Addressable Isolator Module I56-3445-001
Photoelectric smoke detector with thermal (135°F)
speed range
Mini monitor module I56-3487-000, I56-3444-
I56-3483-00, I56-3426-00
I56-3488-00, I56-3432-00
00
00

5.2 Maximum Number of Devices

A 5600 system supports a maximum of 25 SLC detectors and modules, in any
combination.
5-1 151450
Page 58
Model 5600 Installation and Operation Manual

5.3 Wiring Requirements for SLC Devices

The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details.

5.3.1 Wiring SLC in Style 4 (Class B) Configuration

No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-121 requirements for power limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms to the farthest SLC device. Maximum loop length depends on the wire gauge. All SLC wiring is Supervised, and Power-limited.
Table 5-1: Maximum wiring distance for SLC devices
Wire Gauge Max. Distance for SLC devices
22 AWG 1200 feet 18 AWG 3100 feet 16 AWG 4900 feet 14 AWG 7900 feet 12 AWG 10,000 feet
5-2 151450
Page 59
SLC Device Installation
The following figures show how length is determined for out and back tap and T-Tap style wiring.
Figure 5-1 Calculating wire run length for a simple out and back
151450 5-3
Page 60
Model 5600 Installation and Operation Manual
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
5-4 151450
Page 61
SLC Device Installation
Supervised Power limited

5.4 Wiring SLC Detectors

This section describes how to install heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information.
This information applies to the following HFS or SK models:
HFS-P, HFS-PA, SK-Photo - Photoelectric Smoke Detector
HFS-PT, HFS-PTA, SK-Photo-T - Photoelectric Smoke Detector with Thermal
HFS -D, HFS-DA, SK-Duct - Photoelectric Duct Detector
HFS-T, HFS-TA, SK-Heat - Fixed Temperature Detecto r
To wire HFS or SK detectors:
1. Wire device bases as shown in Figure 5-3.
2. Set the address for each device as described in Section 5.5.
Figure 5-3 Heat and Smoke Detector Connection to the Panel.
151450 5-5
Page 62
Model 5600 Installation and Operation Manual
All dials labeled for ONES
or TENS position
Example 1: Device Set to 35
Example 2: Device set to 105

5.5 Addressing SLC Devices

All HFS/SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in Figure 5-4.
Example 2: To select device address 105, turn the ONES rotary dial to 5 and the TENS rotary dial to 10 as show in Figure 5-4.
Figure 5-4 HFS/SK SLC Device Addressing Using Rotary Dials
5-6 151450
Page 63

Section 6 Programming

This section of the manual describes how to change the control panel programming options from the built-in web page of the control panel. All options described in this section are edited via the panel’s built in web page
Important!
Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart is because JumpStart automatically programs the system, searching for and configuring all SLC devices and SBUS annunciators it finds. JumpStart allows you to confirm the integrity of the installation prior to performing any custom programming. After determining that the hardware is properly installed, custom programming can be performed. Refer to Section 6.

6.1 UL 864 Programming Requirements

Table 6-1: Standards in Requirements for Control Units and Accessories
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES: This product incorporates field programmable software.
In order for the product to comply with the requirements in the S t andard for Control Unit s and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
Programming Option Menu Item
System Options Low AC Report
Delay Zone Options Supervisory Yes Latching/Non Latching Zone Options Waterflow Yes Latching/Non Latching System Options Alarm Verification Yes 1-250 seconds 60-250 seconds Dialer Phone line Programming
option
Line Monitor
Enabled
Permitted in UL 864 (Y/N)
Yes 0–30 hours 1–3
Yes Y/N Y*
Possible Settings
Settings Permitted in UL 864
*Only needs to be enabled if using the DACT.
151450 6-1
Page 64
Model 5600 Installation and Operation Manual

6.2 Control Panel Programming

The 5600 is an addressable control panel that has the characteristics of a 5 zone conventional fire alarm control panel.

6.3 Default Control Panel Configuration.

The panel ships from the factory in a defaulted configuration that may allow the installer to use the panel without doing any custom programming.

6.3.1 Default Mapping of SLC Inputs to Outputs

The panel mapping configuration for the 5600 is fixed with regards to SLC addresses, zone assignments and output points. The relationship between input points and output points follows the rules defined in 6.3.2 below. For input points, the SLC address determines the zone assignment and alarm characteristics. For output points, the SLC address determines the output function for the point.
6-2 151450
Page 65

6.3.2 Mapping of SLC Inputs to Outputs.

Table 6-2: Input Points
INPUT POINTS
Programming
Zone Input Point Types Function Qty
Zone 1 HFS-P. HFS-PT, HFS-D,
HFS-T, SK-Photo, SK-Photo­T, SK-Duct, SK-Heat, SK­Pull-SA, SK-Pull-DA, HFS­MM, SK-Minimon
Zone 2 HFS-P. HFS-PT, HFS-D,
HFS-T, SK-Photo, SK-Photo­T, SK-Duct, SK-Heat, SK­Pull-SA, SK-Pull-DA, HFS­MM, SK-Minimon
Zone 3 HFS-P. HFS-PT, HFS-D,
HFS-T, SK-Photo, SK-Photo­T, SK-Duct, SK-Heat, SK­Pull-SA, SK-Pull-DA, HFS­MM, SK-Minimon
Zone 4 HFS-P. HFS-PT, HFS-D,
HFS-T, SK-Photo, SK-Photo­T, SK-Duct, SK-Heat, SK­Pull-SA, SK-Pull-DA, HFS­MM, SK-Minimon
Zone 5 HFS-P. HFS-PT, HFS-D,
HFS-T, SK-Photo, SK-Photo­T, SK-Duct, SK-Heat, SK­Pull-SA, SK-Pull-DA, HFS­MM, SK-Minimon
Alarm 15 1 15 Alarm Zone 1 Supervisory 5 16 20 Supervisory Zone 1
Alarm 15 21 35 Alarm Zone 2 Supervisory 5 36 40 Supervisory Zone 2
Alarm 15 41 55 Alarm Zone 3 Supervisory 5 56 60 Supervisory Zone 3
Alarm 15 61 75 Alarm Zone 4 Supervisory 5 76 80 Supervisory Zone 4
Alarm 15 81 95 Alarm Zone 5 Supervisory 5 96 100 Supervisory Zone 5
Start SLC ID
End SLC ID
Description
151450 6-3
Page 66
Model 5600 Installation and Operation Manual
Table 6-3: Output Points
OUTPUT POINTS
Group Output Point Type
OPG 1 HFS-MR, HFS-MRA, SK-Relay 2 111 112 Zone 1 Alarm OPG 2 HFS-MR, HFS-MRA, SK-Relay 2 113 114 Zone 2 Alarm OPG 3 HFS-MR, HFS-MRA, SK-Relay 2 115 116 Zone 3 Alarm OPG 4 HFS-MR, HFS-MRA, SK-Relay 2 117 118 Zone 4 Alarm OPG 5 HFS-MR, HFS-MRA, SK-Relay 2 119 120 Zone 5 Alarm OPG 6 HFS-MR, HFS-MRA, SK-Relay 2 121 122 Zone 1 Supervisory OPG 7 HFS-MR, HFS-MRA, SK-Relay 2 123 124 Zone 2 Supervisory OPG 8 HFS-MR, HFS-MRA, SK-Relay 2 125 126 Zone 3 Supervisory OPG 9 HFS-MR, HFS-MRA, SK-Relay 2 127 128 Zone 4 Supervisory OPG 10 HFS-MR, HFS-MRA, SK-Relay 2 129 130 Zone 5 Supervisory OPG 11 HFS-MR, HFS-MRA, SK-Relay 2 131 132 Zone 1 Trouble OPG 12 HFS-MR, HFS-MRA, SK-Relay 2 133 134 Zone 2 Trouble OPG 13 HFS-MR, HFS-MRA, SK-Relay 2 135 136 Zone 3 Trouble OPG 14 HFS-MR, HFS-MRA, SK-Relay 2 137 138 Zone 4 Trouble OPG 15 HFS-MR, HFS-MRA, SK-Relay 2 139 140 Zone 5 Trouble OPG 16 HFS-MR, HFS-MRA, SK-Relay 2 141 142 General Alarm OPG 17 HFS-MR, HFS-MRA, SK-Relay 2 143 144 General Supervisory OPG 18 HFS-MR, HFS-MRA, SK-Relay 2 145 146 General Zone Trouble OPG 19 HFS-MR, HFS-MRA, SK-Relay 2 147 148 General Trouble OPG 20 HFS-MR, HFS-MRA, SK-Relay 2 149 150 Alarm Silenced OPG 21 HFS-MR, HFS-MRA, SK-Relay 2 151 152 Trouble Silenced OPG 22 HFS-MR, HFS-MRA, SK-Relay 2 153 154 AC Loss OPG 23 HFS-MR, HFS-MRA, SK-Relay 2 155 156 Resettable Aux Relay OPG 24 HFS-MR, HFS-MRA, SK-Relay 2 157 158 Aux Door Holder
QtyStart
SLC ID
End SLC IDOutput Activates
For
Table 6-2: shows that any input SLC device with an address set within the range 1-15 will be assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111 or 112 will activate for an alarm in zone 1.

6.3.3 Default Mapping for the 2 built-in Notification Circuits.

There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the System Sensor synchronization pattern. To change the behavior of the default mapping of these circuits refer to Section 6.5.
6-4 151450
Page 67
Programming

6.3.4 Maximum SLC address point count

The 5600 control panel supports a maximum of 25 SLC points to be used within the 159 point address range. The points can be all inputs, all outputs or any combination of inputs and output points. When more than 25 SLC devices are added to the control panel, any excess points will indicate a trouble and not be recognized by the panel.

6.3.5 Installer Code

The installer code is factory programmed as 123456. The installer code is required to learn and remember which SLC devices are connected to the panel. The installer code can be changed when a PC is used to modify the default programming options.

6.4 JumpStart AutoProgramming

Once the physical installation of SLC devices is finished, the panel will need to learn which SLC devices and SBUS annunciators are present.
IMPORTANT
There is no limit to how often you can run JumpStart. Each time you run this process it starts fresh and does not remember previously installed devices that are no longer present.
To run JumpSt art:
1. Press and hold the “JumpStart” key,
2. Press the installer code after PIN is displayed.
3. During JumpStart, the panel will briefly light up all LEDs and then display “SLC
Prg” on the 7 segment display.
4. When complete the display will be off and programming is complete.
If changes are required that affect address settings for the SLC devices, device types or number of SLC devices installed you will need to repeat JumpStart to re-learn which devices are supposed to be present on the system.
151450 6-5
Page 68
Model 5600 Installation and Operation Manual

6.5 Modifying Panel Programming using a PC

6.5.1 Connecting the panel to a PC

Modifications to the default panel programming can only be done using the embedded web server of the control panel. There are two ways to connect to the panel for the purpose of programming. It can be connected through a DHCP (Dynamic Host Configuration Protocol) router or it can also be plugged in using a Standard CAT5e Ethernet cable without a router. Both methods of connecting the panel to the PC are for local connection only.
By default, the panel is configured to search for a DHCP server. If there is a DHCP server present, the panel receives the IP configuration offered by the DHCP server and displays the IP address on the seven segment display.
If the panel is connected to a PC without a router , it assigns it self a default class B IP address of the format (169.254.X.X). Each panel will have a unique IP address and it will also be displayed on the 7 segment display. When direct connected, it will normally take about 40 seconds to display the IP address. The panel displays “IP” while the IP address is being determined during this 40 second search period.
A PC with the Windows operating system may take up to 1 minute to fallback to the APIPA (Automatic Private IP Addressing) which enables the PC to communicate to the panel. Whether using either the PC direct connect or the PC connected to the panel via DHCP router , you are ready to view and edit the panel programming options once the panel shows the IP address on the seven segment display.
The embedded web page programming tool is accessed by typing in the panel IP address in a web browser. MS Internet explorer 6 and Mozilla Firefox 3.0.5 are the only two web browsers tested and recommended.
6-6 151450
Page 69
Programming

6.6 Panel Programming Options

All customized programming options for the 5600 control panel are described in this section and are available to be edited using the embedded web server of the control panel.

6.6.1 System Options

6.6.1.1 Synchronized Strobes Active When Horns Silenced
The default configuration for this option is No. If set to Yes, strobes will remain on when horns are silenced until a panel reset is issued.
6.6.1.2 Silence/Reset Inhibit Enabled
The default configuration for this option is NO. If set to Yes, Pressing either Reset or Silence Buttons will be ignored for the duration of the delay (set to 30 seconds). The inhibit feature delay is only active for the first alarm/supervisory signal.
6.6.1.3 Water Flow Delay
The water flow delay is a debounce time that is generally used to help reduce false alarms during brief periods of water pressure fluctuation in a water riser. The default setting is 1 second which is the minimum debounce time. You can set the water flow delay within the range 1-90 seconds.
6.6.1.4 Installer Code (User ID)
This is the password used to lock the list of SLC devices found during the JumpStart auto learn process. It is defaulted to 123456 and can be changed to any 4 to 8 digit number.
6.6.1.5 Alarm Verification Time
Alarm verification is an optional false alarm prevention feature for smoke detectors that verifies an alarm condition by resetting the smoke detector. The alarm verification time can be set within the range of 1-250 seconds. For UL 864 installations this option must be greater than 59 seconds. The default setting is 60 seconds.
6.6.1.6 Auto Test
Enter the hour/minutes (in 24 hour format) that you desire the control panel to send the automatic test report.
6.6.1.7 Low AC Report Delay
This option determines the number of delay hours before a loss of AC is reported to
151450 6-7
Page 70
Model 5600 Installation and Operation Manual
the central station. It is defaulted to 3 hours and must be within the range 0-30 hours. For U.L. 864 installation this option must be set within the range 1-3 hours.
6.6.1.8 Walk Test Reporting
The default configuration for this option is No. If set to Yes, the panel generates a TEST report to the central station when the walk test begins. During a walk test, the panel’s normal fire alarm function is completely disabled, placing the panel in a local trouble condition. All zones respond as 1-Count zones (respond when a single detector is in alarm) during a walk test. Each alarm initiated during the walk test will be reported.
6.6.1.9 Walk Test duration
Enter the amount of time, in minutes, for the walk test duration. When the programmed amount of time expires, the Walk Test will end automatically.
6.6.1.10 Walk Test NAC Time out
Enter the amount of time, in seconds, for the walk test NAC active duration. During a walk test alarm activation, the NACs will automatically deactivate after the programmed amount of time expires.
6.6.1.11 Clock Source
The panel’s AC line frequency is selectable for 60 Hz, 50 Hz, or Internal Clock Source. AC frequency feature dictates how the control panel will calculate time based on the AC line frequency used in the installation site. The “Internal Clock” option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC power source. The panel defaults to the 60 HZ selection.
6.6.1.12 Auto Daylight Savings Time
Select this feature to “Yes” if you want the panel to automatically adjust the clock to track with daylight savings time.
6.6.1.13 Remote Annunciator
Select this feature to “Yes” if a 5635 Remote Annunciator is to be used. A customized banner can also be added to the Remote Annunciator. The Remote Annunciator allows for the top 2 lines to be programmed as a custom banner.
6-8 151450
Page 71
Programming

6.6.2 Zone Programming

6.6.2.1 SLC Addresses Within Each Zone
Each zone has 15 alarm SLC addresses and 5 supervisory SLC addresses assigned to it as described in table 6.1. For each SLC address within a zone, the SLC device type choices are Unused, Detector, Manual Pull Switch, Latching Water Flow Switch or Non-Latching Water Flow Switch. The default setting is that all points are unused.
6.6.2.2 Zone Silenceable
When an alarm occurs within a zone, there is a programming option that allows the outputs to be silenceable or not. If you want the SILENCE key to be able to silence outputs triggered by active alarms within the zone select YES for this option. The default setting is Yes.
6.6.2.3 Zone Type
A zone can be either a one count zone or an alarm verification zone. The default setting is one count. A one count zone has an immediate alarm when a single detector goes into alarm.
Alarm verification is an optional false alarm prevention feature for smoke detectors that verifies an alarm condition by resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed, the detector will go into alarm. If the detector is no longer in alarm, the initial alarm is ignored. The alarm verification sequence for a detector does not occur if the zone is already in alarm.

6.6.3 Output Point Programming

For each output SLC address you can select that a device is present or unused. The default setting for all output points is unused.
151450 6-9
Page 72
Model 5600 Installation and Operation Manual

6.6.4 Notification Appliance Circuit (NAC) Programming

6.6.4.1 Circuit Function
The two notification circuits are both defaulted to activate the System Sensor synchronization pattern when any of the five zones are in alarm. You can define each of the notification circuits to be either a conventional notification circuit or an auxiliary power type circuit.
6.6.4.2 Conventional Notification Circuit Mapping
When defined as a conventional notification circuit, the circuit can be configured to activate for any combination of zone alarms and/or supervisories. Select all the categories you wish to have the circuit activate under.
Conventional Notification Circuit Cadence Pattern
When a conventional notification circuit activates, it can be configured to produce one of six output patterns.
1. Constant On - 24V DC power
2. ANSI - ANSI temporal pattern
3. AMSECO Sync - Strobe synchronization for AMSECO appliances
4. Gentex Sync - Strobe synchronization for Gentex appliances
5. System Sensor Sync - Strobe synchronization for System Sensor appliances
6. Wheelock Sync - Strobe synchronization for Wheelock appliances
Auxiliary Power Options
Each of the notification circuits can be configured as an auxiliary power circuit in one of three options.
1. Constant - Always on, 24V DC power.
2. Door Holder - 24V DC when in standby, Off if any alarm device activates, or loss
of AC power.
3. Resettable - 24V DC except for 30 seconds off during panel reset.
6-10 151450
Page 73
Programming

6.6.5 Relay Programming Options

The two on-board relays of the control panel can be programmed for Auxiliary Resettable and Auxiliary Door Holder applications. Relay 1 can be selected to activate for General Supervisory. Relay 2 can be selected to activate for General Alarm. See Figure 6-1.
Figure 6-1 Relay Programming Option
6.6.5.1 General System Relay Silence Option
This option defaults to silenceable. This option controls the silencing behavior for Relay 1, Relay 2 and the general output relays at SLC addresses 141 through 148.

6.6.6 Dialer Phone Line Programming Options

The programming options below are available for each of the two phone lines.
6.6.6.1 Line Prefix
This option allows the insertion of digits, delays and special tone characters to be dialed before the phone number stored in the account option is dialed. The default setting is to not have any prefix.
6.6.6.2 Dial Tone Detection
The default configuration for this option is “Enabled”. If set to “Disabled”, the dialer will not check for the presence of dial tone on the associated phone line prior to making a call.
151450 6-11
Page 74
Model 5600 Installation and Operation Manual
6.6.6.3 Line Monitoring Enabled (Y/N)
This option is used to enable phone line voltage supervision. It defaults to No.
6.6.6.4 Dialing Option
The dialer can use touch tone or pulse dialing when calling the central station. The options for dialing are touch tone only, dial pulse only or alternating touch tone/dial pulse when multiple attempts are used to connect with the central station. The default setting is touch tone only.
6.6.6.5 Pulse Dialing Format
There are two duty cycle options for the pulse dialing. US format is 60/40. European format is 66/34. The default setting is the US format.
6-12 151450
Page 75
Programming

6.6.7 Dialer Account programming Options

Up to two accounts can be used for reporting events to the central station. A typical reason to use multiple reporting accounts might be to have one account for reporting alarms and a different account for reporting supervisories and troubles. The programming options for each account are described below.
6.6.7.1 Account Number
Up to six digits allowed for SIA formats or up to four digits for contact ID format. Default account numbers are blank.
6.6.7.2 Phone Number
Enter the phone number to call the central station. Default setting is blank. The following special characters are available:
Table 6-4:: Special Dialing Characters
# Pound (or number) key on the telephone * Star key on the telephone , Comma (character for 2-second pause)
6.6.7.3 Reporting Fo rmat
Choose SIA8 (up to 8 events per call), SIA20 (up to 20 events per call) or contact ID reporting format. Default setting is contact ID.
6.6.7.4 Reporting Filters
Selecting the Must option forces the event type to be reported to the account even if it was already reported to another account. Selecting the Yes option will insure that the event type gets to at least one account. Selecting the No option means that the event type will not be reported to this account. The default setting is No.
Selecting No for all report filters in both accounts effectively disables the dialer.
151450 6-13
Page 76
Model 5600 Installation and Operation Manual
6-14 151450
Page 77

Section 7 System Operation

The operation of the 5600 control panel is similar to a conventional 5 zone Fire Alarm Control Panel. System status and control is segmented into zones even though the panel supports addressable SLC devices for input and output functions.
Note: ULC version of the panel (5600C) has a built in Alarm Reset and Alarm Silence inhibit of 30 sec-
onds

7.1 System Reset

To reset the system press the RESET key once. All LEDs will light while the system is being reset. Alarms and Supervisories that were latched will be reset to their normal state. Outputs that had been activated by any Alarms and Supervisories will be deactivated.

7.2 Lamp Test

For Lamp test in accordance with ULC-527-99, see 5600C Basic Operating Instructions.

7.3 System Silence

To Silence the PZT and all silenceable outputs that are active, press the SILENCE key once. Any silenceable trouble, supervisory or alarm that is silenced will automatically unsilence if left silenced for 24 hours or if a new trouble, supervisory or alarm event occurs.

7.4 Acknowledge

Use the ACK key to acknowledge alarm, supervisory and trouble events

7.5 Viewing Active Alarm Points

When one or more SLC points within a zone are in alarm, the alarm LED for that zone will blink and outputs will activate that are mapped to alarms within the zone. To display the SLC address of an input point that is in alarm, press the ALARM ID key once and use the PREV (previous) or NEXT key to scroll through the alarm points. All points that are in alarm spanning all zones on the control panel will be displayed when using the scroll keys.
151450 7-1
Page 78
Model 5600 Installation and Operation Manual

7.6 Viewing Active Supervisory Points

When one or more SLC points within a zone are in supervisory alarm, the supervisory LED for that zone will blink and outputs will activate that are mapped to supervisories within the zone. To display the SLC address of an input point that is in supervisory, press the SUPERVS ID key once and use the PREV (previous) or NEXT key to scroll through the supervisory points. All points that are in supervisory spanning all zones on the control panel will be displayed when using the scroll keys.

7.7 Viewing Active Trouble Points

When one or more SLC points within a zone are in trouble, the trouble LED for that zone will blink and outputs will activate that are mapped to troubles within the zone. To display the SLC address of an input point that is in trouble, press the TROUBLE ID key once and use the PREV (previous) or NEXT key to scroll through the trouble points. All addressable points that are in trouble throughout the control panel will be displayed when using the scroll keys.
Note: If there are any system level troubles active, the LED corresponding to the system level trouble
will blink also. However, system level troubles are not displayed on the 7 segment display after using the TROUBLE ID key and the PREV or NEXT to scroll addressable troubles. Only point troubles are displayed.

7.8 Walk Test

Walk test is enabled by holding the WALK TEST key until the PZT stops. This takes about 5 seconds. Once in walk test the 7 segment display will show that the walk test is active. During walk test, inputs can be activated and the outputs that are mapped to the input will be activated for 3 seconds. The input will automatically be reset when the outputs are deactivated.
The exit walk test, hold the WALK TEST key until the PZT stops. The panel is now in normal standby mode.

7.9 Fire Drill

A fire drill is activated by holding the DRILL key until the 7 segment display shows drl on. All outputs will be active. To stop the fire drill, press the RESET key. If the reset key is not pressed within 10 minutes, the fire drill will automatically reset.
7-2 151450
Page 79
System Operation

7.10 Zone Disable Feature

To disable a zone, press the disable zone key that corresponds to the zone number you wish to disable. When a zone is disabled all alarm events that occur while the zone is disabled will be ignored. Zones that are disabled will be in trouble. The PZT will sound the trouble cadence. The trouble LED for the specific zone along with the general trouble LED will blink indicating that the zone is in trouble. If the silence key is pressed after a zone is disabled, the trouble LEDs will be continuously on and the PZT will silence.
To enable a zone which had been previously disabled, press the disable zone key that corresponds to the zone number you wish to enable. Each pressing of the zone disable key will toggle the disable/enable state for the zone.
Note: Followed by the Installers code in ULC installations. See Basic Operating Instructions.

7.11 Disabling Notification Circuits

There are 2 notification circuits on the 5600 control panel (NAC1 and NAC2). You can disable them individually by pressing the NAC1 or NAC2 disable keys. A disabled notification circuit will cause a trouble on the circuit. The PZT will sound the trouble cadence. The trouble LED for the circuit along with the general trouble LED will blink indicating trouble. If the silence key is pressed, the trouble LEDs will be continuously on and the PZT will silence.
Pressing the NAC disable key when the circuit is already disabled will enable the circuit. Each pressing of a NAC disable key will toggle the disable/enable state for the circuit.

7.12 Loss of AC power

When AC is present and above the brown out threshold, the AC LED will be on continuously. When AC power is off or below the brown out threshold, the AC LED will blink. The GENERAL TROUBLE LED will blink also. The trouble relay will activate for loss of AC once the reporting delay for reporting loss of AC power has been reached. The default setting for this delay is 3 hours. If the silence key is pressed, the trouble LEDs will be continuously on and the PZT will silence.
7.13 Remote Connection Feature
(ULC Installations Only)
To disconnect the communication paths to the Central St ation and/or remote stations, press the walk test button and the Acknowledge button at the same time. The PZT on the panel will sound and the General Trouble LED will be flashing. This feature will remain active until you press the Walk Test and Acknowledge buttons again.
151450 7-3
Page 80
Model 5600 Installation and Operation Manual

7.14 Low Battery

The battery voltage is continuously monitored during normal standby. When the battery is not present or the voltage is too low, the control panel will indicate a low battery trouble. Both the LOW BATTERY and GENERAL TROUBLE LED will blink when there is a low battery condition. The PZT will also sound the trouble cadence. If the silence key is pressed, the trouble LEDs will be continuously on and the PZT will silence.

7.15 Ground Fault

The control panel monitors the SLC and notification circuits for wiring shorts to earth ground. If any wire from these circuits is connected to earth ground the control panel will indicate a ground fault by blinking both the GROUND FAULT and GENERAL TROUBLE LED. The PZT will also sound the trouble cadence. If the silence key is pressed, the trouble LEDs will be continuously on and the PZT will silence.

7.16 Phone Line Monitoring

The control panel monitors the phone line voltage at TELCO1 and TELCO2 when line monitoring is enabled (see programming section 6.5.6.3). When line monitoring is enabled and there is not sufficient voltage at TELCO1 or TELCO2, the 7 segment display will indicate “Ln1” and/or “Ln2” for phone line 1 and phone line 2 troubles.

7.17 Reporting Account Monitoring

When the control panel is configured to use the dialer, the reporting accounts will indicate trouble if the panel has failed to communicate to the central station after 10 attempts. Account 1 trouble is indicated on the 7 segment display as “AC1”. Account 2 trouble is indicated on the 7 segment display as “AC2”. Once the communication path to the central station is restored, the account troubles will self restore.

7.18 SLC Fault

In the event that the SLC circuit is shorted or drawing too much current, the panel will indicate this by displaying “SLC err” on the 7 segment display. Remove the fault and the trouble will self restore.

7.19 Dialer Error

In the event that the dialer microprocessor is unable to communicate with the main microprocessor the panel will indicate this by displaying “dlr” on the 7 segment display. If this trouble is ever displayed, the panel needs to be returned to the factory for repair.
7-4 151450
Page 81
System Operation

7.20 Annunciator Description

Operation of the Remote Annunciator is simple. See 5635 Installation instructions PN 53958 for more information. Figure 7-1: shows the Remote Annunciator.
Figure 7-1: 5635 Remote Annunciato r

7.20.1 LCD Displays

The Remote Annunciator's LCD displays system messages, annunciates alarms, supervisories and troubles; provides status information; and prompts for input. These messages can be up to 80 characters, displaying over four lines of 20 characters each. Annunciator keys beep when they are pressed.
151450 7-5
Page 82
Model 5600 Installation and Operation Manual
Text of Internal Banner
Custom Banner example

7.20.2 Banner

The banner is the message that displays on the Annunciator when the system is in normal mode (no alarm, trouble or supervisory condition exists). You can create a customized message that will display instead of the internal (default) message. See
6.6.1.13 for information on customizing the banner.
Figure 7-2: Banner Display Examples
7-6 151450
Page 83
System Operation

7.21 Basic Operation

7.21.1 Conduct a Fire Drill

1. Activate the key by turning it to the ON position.
2. Press and hold the Drill key for 2 seconds.
3. The drill will begin after the key has been held down for 2 seconds.
4. Press the Reset key to end the Fire Drill. (If you do not press the Reset Key to end
the Fire Drill manually, it will time out automatically after 10 minutes.)

7.21.2 Conduct an Indicator Test

The indicator test checks the annunciator LEDs, PZT, and LCD display.
1. Activate the key by turning it to the ON position.
2. Press the Reset Key to conduct an indicator test. The system turns on all LEDs for
several seconds, beeps the PZT, and displays a message on the LCD display. A problem is indicated if any of the following occurs:
An LED does not turn on
You do not hear the beep
The LCD is unable to annunciate the message correctly

7.21.3 Silence alarms or troubles

1. Activate the key by turning it to the ON position.
2. Press the Silence Key.
Note: Alarm and trouble signals that have been silenced but the detector remains un-restored and will
un-silence every 24 hours until it is restored.

7.21.4 Reset alarms

1. Activate the key by turning it to the ON position.
2. Press the Reset key.

7.21.5 View Alarms or Troubles

When the system is in alarm or trouble, you can press the Down key to view the location of an alarm or trouble. The Point ID, and time stamp of when the condition occurred will also be displayed.
151450 7-7
Page 84
Model 5600 Installation and Operation Manual

7.22 Operation Mode Behavior

The remote annunciator can be in one of six conditions at any given moment: Normal, Alarm, Supervisory, Trouble, Silenced, and Reset. Table 7-1 describes the behavior of the Remote Annunciator in each of these modes.
Table 7-1: Operation Modes of Remote Annunciator
Operation
Mode
Normal No alarm or
Alarm A smoke
Supervisory The system
Occurs When System Behavior In This Mode You Can
trouble condition exists.
detector goes into alarm or a pull station is activated.
detects a supervisory condition.
AC POWER LED is on. The All Systems Normal display
indicates that the system is in normal mode.
The current date and time display on the last line of the LCD.
The dialer seizes control of the phone line and calls the central station.
The Remote Annunciator sounds a loud, steady beep (any notification devices attached to the system will also sound).
ALARM LED flashes. The LCD displays a screen similar to
this one.
The dialer seizes control of the phone line and calls the central station.
The Remote Annunciator sounds a loud, pulsing beep in the sequence one second on, one second off.
SUPERVISORY LED flashes. The LCD displays a screen similar to
this one. The LCD displays a screen similar to
this one.
Press the down arrow to view the alarm. A screen similar to this one displays.
Activate the key by turning it to the ON position then press the Silence key to silence the Remote Annunciator (and any notification devices attached to the system).
When the alarm condition clears, activate the key and press Reset to restore the panel to normal.
Press down arrow to view the supervisory condition. A screen similar to this one displays.
Activate the key by turning it to the ON position then press the Silence key to silence the Remote Annunciator.
Once the supervisory condition has been corrected, the system will restore itself automatically.
7-8 151450
Page 85
Table 7-1: Operation Modes of Remote Annunciator
System Operation
Operation
Mode
Trouble A system
Reset
Silenced An alarm or
Occurs When System Behavior In This Mode You Can
trouble condition occurs.
The button is
pressed while the key is activated.
trouble condition has been silenced but still exists. To silence alarms and troubles, press
The dialer seizes control of the phone line and calls the central station.
The remote annunciator sounds a loud, pulsing beep in the sequence one second on, nine seconds off.
TROUBLE LED flashes. The LCD displays a screen similar to
this one.
All LEDs are on briefly then the LCD displays “RESET IN PROGRESS”. If the reset process completes normally, the date and time normal mode screen displays.
SILENCE LED is on. TROUBLE, SUPERVISORY or GENERAL ALARM LED (depending on condition) is on. The annunciator (and any notification devices attached to the system) will be silenced.
Press down arrow to view the trouble. A screen similar to this one displays.
Activate the key by turning it to the ON position then press the Silence key to silence the Remote Annunciator.
Once the trouble condition has been fixed, the system will restore itself automatically.
Press down arrow to view the location of the alarm or trouble. When the condition no lo n ge r exists, the SYSTEM SILENCED and SYSTEM TROUBLE LED, SUPERVISORY or GENERAL ALARM LEDs turn off.
while the key is activated.
151450 7-9
Page 86
Model 5600 Installation and Operation Manual
7-10 151450
Page 87

Section 8 Reporting

This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Contact ID formats.

8.1 Receivers Compatible with the Control Panel

Table 8-1 shows receivers compatible with the control panel.
Table 8-1: Receivers Compatible with the Control Panel
Manufacturer Model Format
Silent Knight Model 9800 SIA and Contact ID
Model 9000 (SIA formats) SIA Ademco Model MX8000 (Contact ID) Contact ID Sur-Gard SG-MLR2-DG (V. 1.64 or higher) SIA and Contact ID Osborne Hoffman Quickalert SIA and Contact ID

8.2 Reporting Formats Dialer Outputs

SIA Reporting Format Contact ID Reporting Format
Event Description
System Events
AC power restore Trouble System Event AR 3 301
AC power lost Trouble System Event AT 1 301
Short circuit removed from SLC commu­nication loop
Short circuit detected on SLC communi­cation loop
Fire drill has begun Test System Event FI 1 604
Fire drill ended Test Syste m Event FK 3 604
Panel date has been changed Trouble System Event JD 1 625
Event
Family
System events are reported when either “Report by Zone” is selected.
Trouble System Event ER 33 3 332
Trouble System Event ET 33 1 332
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA Event Code
Parameter
(if any)
Qualifier
Event
Code
Group#Contact
#
00 000
00 000
00 Exp. ID
00 Exp. ID
00 000
00 000
00 000
Panel time has been changed Trouble System Event JT 1 625
Local programming begin Trouble System Event LB 1 627
151450 8-1
00 000
00 000
Page 88
Model 5600 Installation and Operation Manual
Phone line 1 trouble restore Trouble System Event LR 1 3 351
Phone line 2 trouble restore Trouble System Event LR 2 3 352
Phone line 1 trouble detected Trouble System Event LT 1 1 351
Phone line 2 trouble detected Trouble System Event LT 2 1 352
Periodic test event – normal Test System Event RP 1 602
Periodic test event – off normal Test System Event RY 1 608
Initial power up Trouble System Event RR 1 305
Unable to report to an account Trouble System Event RT Acct # 1 354
User has initiated dialer test Test System Event RX 1 601
Walk test end Test System Event TE 3 607
Walk test begin Test System Event TS 1 607
Auto dialer test communication trouble Trouble System Event YC Line # 1 350
Report to an account successful Trouble System Event YK Acct # 3 354
00 001
00 002
00 001
00 002
00 000
00 000
00 000
Acct # Acct #
00
00 000
00 000
00 Line #
Acct # Acct #
Auto dialer test communication trouble restore
Ground fault condition detected Trouble System Event YP 34 1 310
Ground fault condition restore Trouble System Event YQ 34 3 310
Battery voltage restore Trouble System Event YR 34 3 302
Battery voltage low Trouble System Event YT 34 1 302
Zone Events
Manual pull switch alarm Alarm Zone Event FA Zone 1 115
Detector alarm Alarm Zone Event FA Zone 1 11 0
Manual pull switch alarm restore Restore Zone Event FH Zone 3 115
Detector alarm restore Restore Zone Event FH Zone 3 110
Manual pull switch trouble restore Trouble Zone Event FJ Zone 3 373
Detector trouble restore Trouble Zone Event FJ Zone 3 373
Auxiliary power trouble restore Trouble Zone Event FJ 0000 3 320
Trouble System Event YK Line # 3 350
Zone events are reported only when “Report by Zone” is selected.
00 Line #
00 Exp. ID
00 Exp. ID
00 Exp. ID
00 Exp. ID
00 Zone
00 Zone
00 Zone
00 Zone
00 Zone
00 Zone
00 000
Notification output trouble restore Trouble Zone Event FJ 1000+
Group #
3320
8-2 151450
00 Group #
Page 89
Reporting
Manual pull switch trouble Trouble Zone Event FT Zone 1 373
Detector trouble Trouble Zone Event FT Zone 1 373
Auxiliary power trouble Trouble Zone Event FT 0000 1 320
Notification trouble Trouble Zone Event FT 1000+
Group#
User initiated a system reset Reset Zone Event OR 1 401
Water flow switch alarm Alarm Zone Event SA Zone 1 113
Water flow switch alarm restore Restore Zone Event SH Zone 3 113
Water flow switch trouble restore Trouble Zone Event SJ Zone 3 373
Supervisory/Tamper switch trouble restore
Supervisory condition restore Trouble Zone Event SR Zone 3 203
Supervisory condition Trouble Zone Event SS Zone 1 203
Water flow switch trouble Trouble Zone Event ST Zone 1 373
Supervisory/Tamper switch trouble Trouble Zone Event ST Zone 1 373
Trouble Zone Event SJ Zone 3 373
1320
00 Zone
00 Zone
00 000
00 Group #
00 000
00 Zone
00 Zone
00 Zone
00 Zone
00 Zone
00 Zone
00 Zone
00 Zone
151450 8-3
Page 90
Model 5600 Installation and Operation Manual
8-4 151450
Page 91

Section 9 Trouble Shooting and Quick Tips

9.1 Troubleshooting

This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem when installing the control panel. If these suggestions do not solve your problem or if you encounter a problem that is not listed here, contact Silent Knight Technical Support for assistance.

9.1.1 JumpStart

Jumpstart will learn all of the SLC devices and SBUS annunciators attached to the system. Do a JumpStart first and any customization second.
1. Press and hold the JumpStart key until “PIN” is displayed
2. Enter the installers code on the 10 digit keypad
3. “SLC” “Prg” will be displayed until the JumpStart is complete

9.1.2 View Active Points

View Active Points (alarm, non-system trouble, and supervisory conditions) Press the corresponding ID key (e.g. Alarm ID) Use Prev and Next to view more active points of that type

9.1.3 Disable Or Re-Enable A Zone

1. Press the Zone x Disable button on the keypad
2. The PZT will sound a trouble Can be silenced by pressing Signal Silence (ALL points in that zone are affected)

9.1.4 Silence the Board PZT

Press ACK

9.1.5 Silence the Notification Appliances

1. Press SIGNAL SILENCE
151450 9-1
Page 92
Model 5600 Installation and Operation Manual
2. If Silence/Reset Inhibit Enabled is selected in programming, that button and the SYSTEM RESET button are ignored for the first 30 seconds of the first alarm or supervisory signal

9.1.6 To Initiate a Fire Drill

1. Press Drill until “DRL” is displayed
2. Press SYSTEM RESET to end the drill

9.1.7 For a Dialer Test

Press JumpStart and Next at the same time

9.1.8 For a Lamp Test

Press JumpStart and Prev at the same time

9.1.9 AC LED

The AC LED will blink for the loss of AC and the Trouble Relay will activate after the programmed delay time (default = 3 hours).

9.1.10 Walk Test

1. Press and hold Walk Test for about 5 seconds to start a walk test
2. Press SYSTEM RESET to end the test

9.1.11 Seven Segment Display

On the 7 segment display:
“AC1” indicates dialer account 1 failed to report “AC2” indicates dialer account 2 failed to report “dlr” indicates a problem with the dialer. The panel must be returned to the factory
for repair “drL” indicates a fire drill is taking place
“Ln1” indicates low/no voltage on phone line 1 “Ln2” indicates low/no voltage on phone line 2 “CE1” indicates Autotest Comm Error Line 1 “CE2” indicates Autotest Comm Error Line 2 “SLC err” indicates an over current condition on the SLC loop “bAt” indicates battery trouble
9-2 151450
Page 93
Trouble Shooting and Quick Tips
“rA1” indicates remote annunciator 1 trouble “rA2” indicates remote annunciator 2 trouble “gnd” indicates ground fault trouble “AC” indicates AC power supply trouble “nC1” indicates notification appliance circuit 1 trouble “nC2” indicates notification appliance circuit 2 trouble “tSt” indicates a trouble for the duration of a walk test
Correct the fault and the trouble will restore

9.2 Web Server Menus

The System Summary and Mapping Table sections are not editable, but are populated based on the entries in the other sections.

9.2.1 To add a smoke detector:

Which zone will it be in (e.g. the Lunchroom, Zone 2)?
1. Click on Zone Programming, under Zone 2
2. Click Alarm Points
3. Find an Unused SLC Address and click on the detector type (e.g. address 24 Photo)
4. Click Accept
Note: Remember to choose to Download to Panel after all of your changes are done AND set the rotary
switches on the back of the smoke detector (e.g. tens=2 and ones=4)

9.2.2 To add a notification appliance (fire bell)

1. Click on NAC Programming
2. Click on the NAC circuit you want to activate (e.g. NAC 1)
3. Click to check the box for either Alarm and/or Supervisory events to cause that NAC to activate.
9.2.3 To add a Remote Annunciator (DIP switch address 1
or 2)
1. Click on System Options
151450 9-3
Page 94
Model 5600 Installation and Operation Manual
2. Click on yes option for Remote Annunciator Installed 1/ Remote Annunciator Installed 2
3. Click Accept
Note: Remember to choose to Download to Panel after all of your changes are done

9.2.4 To add custom Zone name

1. Click on Zone Programming
2. Click on Zone Options. Enter custom Zone name (20 characters max) in the cor­responding field
3. Click Accept
Note: Remember to choose to Download to Panel after all of your changes are done

9.2.5 To trip an SLC notification appliance

1. Click on Output Point Programming
2. Click on the tab for the event type you want to activate the notification appliance
3. Click the circle for Present across from one or both of the SLC device(s) addresses for the Zone which has the initiation devices that you want to trip the appliance
Note: Be sure to set your SLC notification device address to match

9.2.6 To trip a Door Holder

1. Click on Output Point Programming
2. Click on the System tab
3. Click on the circle for Present across from the SLC Address of the door holder (e.g. 158)
4. Set the Door Holder device address accordingly (e.g. 158)
The Door Holder will provide 24VDC when in standby, 0V during alarms or loss of AC An on board relay can also be used for Door Holder power. See Section 6.6.5.
Help to reduce false alarms
In the System Options section, Water Flow Delay can be adjusted to account for brief periods of water pressure fluctuation
Alarm Verification Time verifies an alarm condition by resetting the smoke detectors before activating alarms (U.L. 864 installations must not exceed 60 seconds).
9-4 151450
Page 95

Appendix A Compatible Devices

A.1 Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized.
Note:Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you
have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
Table A-1 below lists notification appliances compatible with the fire alarm control panel. Appliances which can be synchronized indicate the type of SYNC available in the columns marked Audio and/or Visual.
Table A-1 Compatible Notification Appliances
Manufacturer Model Audio Visual Type
SH24W-153075 X X Horn/Strobe SAD24-153075 X Strobe SAD24-75110 X Strobe SL24W-75110 X Strobe SL24C-3075110 X Strobe SLB24-75 X Strobe RSD24-153075 X Strobe RSD24-75110 X Strobe
AMSECO
SH24W-75110 X X Horn/Strobe SH24W-3075110 X X Horn/Strobe SHB24-75 X X Horn/Strobe SCM24W-153075 X Chimes/Strobe SCM24W-75110 X Chimes/Strobe SCM24C-3075110 X Chimes/Strobe SCM24C-177 X Chimes/Strobe H24W X Horn H24R X Horn
151450 1
Page 96
Model 5600 Installation and Operation Manual
Manufacturer Model Audio Visual Type
GEC-24-15 X X Horn/Strobes GEC-24-30 X X Horn/Strobes GEC-24-60 X X Horn/Strobes GEC-24-75 X X Horn/Strobes GEC-24-177 X X Horn/Strobes GEC-24-110 X X Horn/Strobe GEC-24-15/75 X X Horn/Strobe GX91 X MiniHorn Steady Tone GX93 X MiniHorn Temporal Tone HG124 Horn HS24-15 X X Horn/Strobe HS24-30 X X Horn/Strobe HS24-60 X X Horn/Strobe HS24-75 X X Horn/Strobe HS24-110 X X Horn/Strobe HS24-1575 X X Horn/Strobe GCC24 X X Multi Candela Horn/Strobe Ceiling Mount GCCR24 X X Multi Candela Horn/Strobe Ceiling Mount GCS24 X Multi Candela Strobe Ceiling Mount
Gentex
GCSR24 X Multi Candela Strobe Ceiling Mount GECR-24 X X Multi Candela Horn/Strobe GES24-15 X Strobes GES24-30 X Strobes GES24-60 X Strobes GES24-75 X Strobes GES24-1 10 X Strobes GES24-15/75 X Strobes GES24-177 X Strobes GES3-24 X Multi Candela Strobe GESR-24 X Multi Candela Strobe GEH-24 X Horn ST24-30 X Strobe ST24-60 X Strobe ST24-75 X Strobe ST24-110 X Strobe ST24-1575 X Strobe WGEC24-75W X X Weatherproof Horn/Strobe WGES24-75W X Weatherproof Strobe WGMS-24-X Horn/Strobe
2 151450
Page 97
Manufacturer Model Audio Visual Type
CHR X Chime CHW X Chime CHSR X X 2-Wire Chime/Strobe CHSW X X 2-Wire Chime/Strobe HR X X Horn HW X Horn HRK X Horn P2R X X 2-Wire Horn/Strobe P2R-P X X 2-Wire Horn/Strobe PC2R X X 2-Wire Horn/Strobe PC2R-P X X 2-Wire Horn/Strobe P2RH X X 2-Wire Horn/Strobe High Candela P2RH-P X X 2-Wire Horn/Strobe High Candela PC2RH X X 2-Wire Horn/Strobe High Candela
System Sensor
PC2RH-P X X 2-Wire Horn/Strobe High Candela P2W X X 2-Wire Horn/Strobe P2W-P X X 2-Wire Horn/Strobe PC2W X X 2-Wire Horn/Strobe PC2W-P X X 2-Wire Horn/Strobe P2WH X X 2-Wire Horn/Strobe High Candela P2WH-P X X 2-Wire Horn/Strobe High Candela PC2WH X X 2-Wire Horn/Strobe High Candela PC2WH-P X X 2-Wire Horn/Strobe High Candela P2RK X X 2-Wire Horn/Strobe PC2RK X X 2-Wire Horn/Strobe P2RHK X X 2-Wire Horn/Strobe High Candela PC2RHK X X 2-Wire Horn/Strobe High Candela P4R X X 4-Wire Horn/Strobe PC4R X X 4-Wire Horn/Strobe P4RH X X 4-Wire Horn/Strobe High Candela P4W X X 4-Wire Horn/Strobe
151450 3
Page 98
Model 5600 Installation and Operation Manual
Manufacturer Model Audio Visual Type
PC4W X X 4-Wire Horn/Strobe P4WH X X 4-Wire Horn/Strobe High Candela PC4WH X X 4-Wire Horn/Strobe High Candela P4RK X X 4-Wire Horn/Strobe PC4RK X X 4-Wire Horn/Strobe P4RHK X X 4-Wire Horn/Strobe High Candela PC4RHK X X 4-Wire Horn/Strobe High Candela PC4RH X X 4-Wire Horn/Strobe High Candela SR X Strobe SR-P X Strobe SCR X Strobe SCR-P X Strobe SRH X Strobe High Candela
System Sensor
SRH-P X Strobe High Candela SCRH X Strobe High Candela SCRH-P X Strobe High Candela SW X Strobe SW-P X Strobe SCW X Strobe SCW-P X Strobe SWH X Strobe High Candela SWH-P X Strobe High Candela SCWH X Strobe High Candela SCWH-P X Strobe High Candela SRK X Strobe SCRK X Strobe SRHK X Strobe High Candela SCRHK X Strobe High Candela
4 151450
Page 99
Manufacturer Model Audio Visual Type
AH-12 X Horn AH-24 X Horn AH-12WP X Horn Weatherproof AH-24WP X Horn Weatherproof AMT-241575W X X Multi-Tone Horn Strobe AMT-24MCW X Multi-Tone Horn Strobe AMT-241575W-NYC X X Multi-Tone Horn Strobe AMT-12/24 X Multi-tone Horn AMT-12/24 NYC X Multi-tone Horn AS-121575W X Horn/Strobe NH-12/24 X Horn AS-241575W X X Horn/Strobe
Wheelock
AS-24MCC X X Horn/Strobe AS-24MCCH X X Horn/Strobe AS-24MCW X X Horn/Strobe AS-24MCWH X X Horn/Strobe ASWP-2475W X X Horn/Strobe Weatherproof ASWP-2475C X X Horn/Strobe Weatherproof ASWP-24MCWH X X Horn/Strobe ASWP-24MCCH X X Horn/Strobe CH-70 X Chime CH-90 X Chime CH70-241575W X Chime/Strobe CH70-24MCW X Chime/Strobe CH70-24MCWH X Chime/Strobe CH90-24MCC X Chime/Strobe
151450 5
Page 100
Model 5600 Installation and Operation Manual
Manufacturer Model Audio Visual Type
CH90-24MCCH X Chime/Strobe HS-24 X Horn HS4-241575W X X Horn/Strobe HS4-24MCW X X Horn/Strobe HS4-24MCWH X X Horn/Strobe HS4-24MCC X X Horn/Strobe MIZ-24S X X Mini Horn Strobe MT-121575W X MultitoneHorn Strobe MT-241575W X X Mul titon e Horn Strobe MT-24MCW X Multitone Horn Strobe MTWP-2475W X Multitone Horn Strobe MTWP-2475C X Multitone Horn Strobe MTG-121575W X X Multitone Horn Strobe MTR-121575W X X Multitone Horn Strobe MTWPA-2475W X X Multitone Horn Strobe MTWPB-2475W X X Multitone Horn Strobe MTWPG-2475W X X Multitone Horn Strobe MTWPR-2475W X X Multitone Horn Strobe MTWPA-24MCCH X X Multitone Horn Strobe
Wheelock (con’t)
ZNH X Horn NS-121575W X X Horn/Strobe NS-241575W X X Horn/Strobe NS-24MCW X X Horn/Strobe NS-24MCC X X Horn/Strobe NS-24MCCH X X Horn/Strobe ZNS-MCW X X Horn/Strobe ZNS-MCWH X X Horn/Strobe ZNS-24MCC X X Horn/Strobe ZNS-24MCCH X X Horn/Strobe RSS-121575W X Strobe RSS-241575W X Strobe RSS-24MCC X Strobe RSS-24MCCR X Strobe RSS-24MCCH X Strobe RSS-24MCCHR X Strobe RSS-24MCW X Strobe RSS-24MCWH X Strobe RSSP-121575W X Strobe RSSP-241575W X Strobe RSSR-2415W X Strobe RSSR-2415C X Strobe
6 151450
Loading...