1.3About This Manual ..................................................................................................................................1-1
1.4How to Contact Silent Knight ...................................... .................................... ........................................ 1-1
Section 2
Before You Begin Installing ............................................................................................... 2-1
2.1What’s in the Box? ...................................................................................................................................2-1
3.1AC Power ................................................................................................................................................. 3-1
3.3Connecting the 5496 to the FACP ...........................................................................................................3-3
3.3.1 Setting the Device ID ........................................................................................................................3-4
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
ii151276
Section 1
Overview
1.15496 Description
The Model 5496 Intelligent Power Module provides additional power and notification circuits
to a Silent Knight addressable FACP. The 5496 can power all IntelliKnight compatible
notification appliances and auxiliary power modules.
The 5496 is capable of performing single or dual interlocking operations for pre-action and
deluge releasing systems. See Section 8.6 of FACP installation manual.
The 5496 has four output circuits that can be configured as notification or auxiliary power
circuits. Outputs are rated 3.0 A (6.0 A total for each 5496).
The 5496 is optically isolated, providing ground loop isolation and transient protection.
The 5496 provides configuration options that eliminate the need for sychronization modules
when using AMSECO, Faraday, Gentex, System Sensor, or Wheelock synchronization
appliances.
1.2Agency Requirements
The 5496 has the same requirements as the main control panel. These requirements are listed
in Silent Knight addressable FACP Installation Manuals. Silent Knight Addressable FACP
Installation Manuals can be found on Silent Knight’s web site at www.silentknight.com.
1.3About This Manual
This manual covers installation of 5496 hardware. Software configuration information is
contained in a Silent Knight addressable FACP Installation Manuals. Silent Knight
Addressable FACP Installation Manuals can be found on Silent Knight’s web site at
www.silentknight.com.
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent
Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103 or (203) 484-7161.
1512761-1
Model 5496 Intelligent Power Module Installation and Oper ation Manual
1-2151276
Section 2
Before You Begin Installing
2.1What’s in the Box?
The Model 5496 ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the 5496 front door
•Ten 4.7K ohm end-of-line resistors
Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used.
•A battery wiring harness and jumper to wire batteries in series
2.2Environmental Specifications
It is important to protect the 5496 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the 5496, the unit should be mounted where it will NOT
be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside
the range of 10%-93% at 30°C (86°F) noncondensing.
2.3Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.
1512762-1
Model 5496 Intelligent Power Module Installation and Oper ation Manual
Dipswitches for
Setting ID
To AC
Regulated
SBUS Module
Connections
Battery
Connections
Output Circuits
All Circuits
Supervised Power
limited, except
Battery and AC
which are
supervised
non-power limited.
2.45496 Board and Terminal Strip Description
Figure 2-1 shows the 5496 circuit board including location of terminals and the dipswitch for
setting the module ID.
Figure 2-1 The 5496 Board Layout
2-2151276
Before You Begin Installing
Table 2-1 describes the 5496 connections and provides electrical ratings where appropriate.
Table 2-1: Terminal Strip Description and Electrical Ratings
* Regulated/special application when used for releasing.
BatteryBattery24 VDC0.75 A
I/O 4*Output circuit24 VDC
I/O 3*Output circuit24 VDC
I/O 2*Output circuit24 VDC
I/O 1*Output circuit24 VDC
SBUS power24 VDC1.0 A
SBUS
SBUS communication5 VDC100 mA
Description
2.5Earth Fault Resistance
Rating
VoltageCurrent
3.0 A
Notification Circuits
3.0 A
Notification Circuits
3.0 A
Notification Circuits
3.0 A
Notification Circuits
Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP.
Table 2-2: Earth Fault Resistance Values by Terminal
Function
Battery
Notification Appliance Circuit 4
Notification Appliance Circuit 3
Notification Appliance Circuit 2
Notification Appliance Circuit 1
Terminal
Number
12+0
3H44H4+0
5H36H3+0
7H28H2+0
9H110H1+0
Terminal Label
BATTERY
OUT4
OUT3
OUT2
OUT1
Value
(in ohms)
0
0
0
0
0
1512762-3
Model 5496 Intelligent Power Module Installation and Oper ation Manual
2.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your
installation.
2.6.1Worksheet Requirements
Follow the steps below to determine 5496 current draw and standby battery requirements.
Filling in the Current Draw Worksheet
Refer Table 2-4 in Section 2.6.2 to complete the following steps.
1. Add up the current draw for all auxiliary devices and record in the table at Line B.
2. Add up all notification appliance loads and record in the table at Line C.
3. For notification appliances and auxiliary devices not mentioned in the manual, refer to the
device manual for the current ratings.
4. Make sure that the total alarm current you calculated, including current for the panel itself,
does not exceed 6.0 A. This is the maximum alarm current allowable.
5. Complete the remaining instructions in Table 2-4 to determine battery size requirements.
2.6.1.1Maximum Battery Standby Load
Table 2-3 shows the maximum battery standby load for the 5496 based on 24 and 60 hours of
standby. The standby load calculations of line J in the Current Draw Calculation Worksheet
(Table 2-4) must be less than the number shown in Table 2-3 for the battery size used and
standby hours required.
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
7 AH270 mA105 mA
12 AH475 mA190 mA
18 AH685 mA270 mA
35 AH1370 mA540 mA
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and
Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/
Transmitter (DACT).
Note: 33 max battery size for FM (Factory Mutual) installations
Max. Load for 24 hrs. Standby ,
5 mins. Alarm
*Max. Load for 60 hrs. Standby , 5
mins. Alarm
2-4151276
Before You Begin Installing
2.6.2Current Draw Worksheet
For each 5496 in the installation, use this worksheet to determine current requirements during
alarm/battery standby operation. (Copy this page if additional space is required.)
Table 2-4: Current Draw Calculation Worksheet
Device
For each device use this formula:This column X This column= Current per number of devices.
5496 Intelligent Power Module
(Current draw from battery)
A
Auxiliary DevicesRefer to device manual for current ratings.
B
Notification appliancesRefer to device manual for current ratings.
C
Total current ratings of all devices in system (line A + line B + line C)
D
Total current ratings converted to amperes (line D x .001):
E
Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5).
F
Multiply lines E and F. Total standby AH
G
Alarm sounding period in hours.
H
(For example, 5 minutes = .0833 hours.)
Multiply lines E and H.Total alarm AH
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Notification Appliances Current
Standby
Current
0 mAmA
mAmA
AA
H
AH
AH
Alarm
Current
H
AH
1512762-5
Model 5496 Intelligent Power Module Installation and Oper ation Manual
5496 Board
To AC
Power
To Battery
To SBUS
Terminals
To NACs
2.6.3Wire Routing
You must follow power-limited wiring techniques, which include maintaining one-quarter
inch spacing between power-limited and non-power limited circuits and separating high and
low voltage circuits.
Figure 2-2 Wire Routing Example
2-6151276
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.