1.3About This Manual ..................................................................................................................................1-1
1.4How to Contact Silent Knight ...................................... .................................... ........................................ 1-1
Section 2
Before You Begin Installing ............................................................................................... 2-1
2.1What’s in the Box? ...................................................................................................................................2-1
3.1AC Power ................................................................................................................................................. 3-1
3.3Connecting the 5496 to the FACP ...........................................................................................................3-3
3.3.1 Setting the Device ID ........................................................................................................................3-4
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
ii151276
Section 1
Overview
1.15496 Description
The Model 5496 Intelligent Power Module provides additional power and notification circuits
to a Silent Knight addressable FACP. The 5496 can power all IntelliKnight compatible
notification appliances and auxiliary power modules.
The 5496 is capable of performing single or dual interlocking operations for pre-action and
deluge releasing systems. See Section 8.6 of FACP installation manual.
The 5496 has four output circuits that can be configured as notification or auxiliary power
circuits. Outputs are rated 3.0 A (6.0 A total for each 5496).
The 5496 is optically isolated, providing ground loop isolation and transient protection.
The 5496 provides configuration options that eliminate the need for sychronization modules
when using AMSECO, Faraday, Gentex, System Sensor, or Wheelock synchronization
appliances.
1.2Agency Requirements
The 5496 has the same requirements as the main control panel. These requirements are listed
in Silent Knight addressable FACP Installation Manuals. Silent Knight Addressable FACP
Installation Manuals can be found on Silent Knight’s web site at www.silentknight.com.
1.3About This Manual
This manual covers installation of 5496 hardware. Software configuration information is
contained in a Silent Knight addressable FACP Installation Manuals. Silent Knight
Addressable FACP Installation Manuals can be found on Silent Knight’s web site at
www.silentknight.com.
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent
Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103 or (203) 484-7161.
1512761-1
Model 5496 Intelligent Power Module Installation and Oper ation Manual
1-2151276
Section 2
Before You Begin Installing
2.1What’s in the Box?
The Model 5496 ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the 5496 front door
•Ten 4.7K ohm end-of-line resistors
Note: For UL installations Model 7628 4.7k end-of-line resistor (ordered separately) must be used.
•A battery wiring harness and jumper to wire batteries in series
2.2Environmental Specifications
It is important to protect the 5496 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the 5496, the unit should be mounted where it will NOT
be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside
the range of 10%-93% at 30°C (86°F) noncondensing.
2.3Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.
1512762-1
Model 5496 Intelligent Power Module Installation and Oper ation Manual
Dipswitches for
Setting ID
To AC
Regulated
SBUS Module
Connections
Battery
Connections
Output Circuits
All Circuits
Supervised Power
limited, except
Battery and AC
which are
supervised
non-power limited.
2.45496 Board and Terminal Strip Description
Figure 2-1 shows the 5496 circuit board including location of terminals and the dipswitch for
setting the module ID.
Figure 2-1 The 5496 Board Layout
2-2151276
Before You Begin Installing
Table 2-1 describes the 5496 connections and provides electrical ratings where appropriate.
Table 2-1: Terminal Strip Description and Electrical Ratings
* Regulated/special application when used for releasing.
BatteryBattery24 VDC0.75 A
I/O 4*Output circuit24 VDC
I/O 3*Output circuit24 VDC
I/O 2*Output circuit24 VDC
I/O 1*Output circuit24 VDC
SBUS power24 VDC1.0 A
SBUS
SBUS communication5 VDC100 mA
Description
2.5Earth Fault Resistance
Rating
VoltageCurrent
3.0 A
Notification Circuits
3.0 A
Notification Circuits
3.0 A
Notification Circuits
3.0 A
Notification Circuits
Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP.
Table 2-2: Earth Fault Resistance Values by Terminal
Function
Battery
Notification Appliance Circuit 4
Notification Appliance Circuit 3
Notification Appliance Circuit 2
Notification Appliance Circuit 1
Terminal
Number
12+0
3H44H4+0
5H36H3+0
7H28H2+0
9H110H1+0
Terminal Label
BATTERY
OUT4
OUT3
OUT2
OUT1
Value
(in ohms)
0
0
0
0
0
1512762-3
Model 5496 Intelligent Power Module Installation and Oper ation Manual
2.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your
installation.
2.6.1Worksheet Requirements
Follow the steps below to determine 5496 current draw and standby battery requirements.
Filling in the Current Draw Worksheet
Refer Table 2-4 in Section 2.6.2 to complete the following steps.
1. Add up the current draw for all auxiliary devices and record in the table at Line B.
2. Add up all notification appliance loads and record in the table at Line C.
3. For notification appliances and auxiliary devices not mentioned in the manual, refer to the
device manual for the current ratings.
4. Make sure that the total alarm current you calculated, including current for the panel itself,
does not exceed 6.0 A. This is the maximum alarm current allowable.
5. Complete the remaining instructions in Table 2-4 to determine battery size requirements.
2.6.1.1Maximum Battery Standby Load
Table 2-3 shows the maximum battery standby load for the 5496 based on 24 and 60 hours of
standby. The standby load calculations of line J in the Current Draw Calculation Worksheet
(Table 2-4) must be less than the number shown in Table 2-3 for the battery size used and
standby hours required.
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
7 AH270 mA105 mA
12 AH475 mA190 mA
18 AH685 mA270 mA
35 AH1370 mA540 mA
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and
Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/
Transmitter (DACT).
Note: 33 max battery size for FM (Factory Mutual) installations
Max. Load for 24 hrs. Standby ,
5 mins. Alarm
*Max. Load for 60 hrs. Standby , 5
mins. Alarm
2-4151276
Before You Begin Installing
2.6.2Current Draw Worksheet
For each 5496 in the installation, use this worksheet to determine current requirements during
alarm/battery standby operation. (Copy this page if additional space is required.)
Table 2-4: Current Draw Calculation Worksheet
Device
For each device use this formula:This column X This column= Current per number of devices.
5496 Intelligent Power Module
(Current draw from battery)
A
Auxiliary DevicesRefer to device manual for current ratings.
B
Notification appliancesRefer to device manual for current ratings.
C
Total current ratings of all devices in system (line A + line B + line C)
D
Total current ratings converted to amperes (line D x .001):
E
Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5).
F
Multiply lines E and F. Total standby AH
G
Alarm sounding period in hours.
H
(For example, 5 minutes = .0833 hours.)
Multiply lines E and H.Total alarm AH
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Notification Appliances Current
Standby
Current
0 mAmA
mAmA
AA
H
AH
AH
Alarm
Current
H
AH
1512762-5
Model 5496 Intelligent Power Module Installation and Oper ation Manual
5496 Board
To AC
Power
To Battery
To SBUS
Terminals
To NACs
2.6.3Wire Routing
You must follow power-limited wiring techniques, which include maintaining one-quarter
inch spacing between power-limited and non-power limited circuits and separating high and
low voltage circuits.
Figure 2-2 Wire Routing Example
2-6151276
Section 3
To AC
To 120 VAC
Power Source
Supervised
Non-power limited
Hardware Installation
5496 installation involves the following steps:
•Connect AC power (Section 3.1) and backup battery (Section 3.2).
•Make physical connection to a Silent Knight addressable FACP (see Section 3.3).
•Set an ID for the 5496 (Section 3.3.1).
•Make physical connection to any outputs that will be powered by this 5496. See Section
3.4 for notification appliance wiring information. Refer to Silent Knight addressable
FACP Installation Manuals for software configuration information and other information
about installing outputs. Silent Knight Addressable FACP Installation Manuals can be
found on Silent Knight’s web site at www.silentknight.com.
3.1AC Power
At installation, connect the AC terminals to 120 VAC source as shown in Figure 3-1. It may
be necessary for a professional electrician to make this connection.
The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.5 A.
Figure 3-1 AC Power Connection
1512763-1
Model 5496 Intelligent Power Module Installation and Oper ation Manual
Red
To Panel
Black
UL Listed 12V BatteryUL Listed 12V Battery
Battery Jumper
(P/N 140694)
Shipped With 5496
Supervised
Non-Power Limited
Replace batteries every 5 years.
Gell CellGell Cell
3.2Battery Connection
The 5496 battery charge capacity is 7.0 AH not to exceed 35.0 AH. Use 12V batteries of the
same AH rating. It is recommended that you replace batteries every five years. Determine the
correct AH rating per your current load calculation (see Table 2-4).
Note: If you require the power of back up batteries that are too large for the 5496, you can use the RBB cabinet.
The RBB Remote Battery Box, holds batteries up to the 35 AH size. (Refer to P/N 151306 for RBB installation instructions.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
3-2151276
Figure 3-2 Battery Connection
Hardware Installation
5820XL
(Main SBUS)
5496 Board
Supervised
Power Limited
3.3Connecting the 5496 to the FACP
1. Connect the 5496 to the appropriate SBUS. The 5496 is connected directly to a Silent
Knight addressable FACP.
2. Use the on-board dipswitch to assign an ID number to the 5496. (See Section 3.3.1) Figure
2-1 shows the location of the dipswitches on the 5496 board.
3. Configure the 5496 module by adding it to the system (through JumpStart or manually).
You can also assign a name to the module. These procedures are described in Silent
Knight addressable FACP Installation Manuals. Silent Knight Addressable FACP
Installation Manuals can be found on Silent Knight’s web site at www.silentknight.com.
Figure 3-3 Class B 5496 Connection to FACP
1512763-3
Model 5496 Intelligent Power Module Installation and Oper ation Manual
3.3.1Setting the Device ID
All SBUS modules in the system must have a unique number (1-31) to identify them to the
FACP. Use the DIP switch on the 5496 board to set the module ID number. Figure 2-1 shows
the location of the dipswitch on the board. Figure 3-4 shows dipswitch setting and the
corresponding module ID numbers.
Figure 3-4 Possible Module Addresses
3-4151276
Hardware Installation
Power Limited
1.5max
3.4Notification Appliance Wiring
Note: Not all devices can use the Sync feature. Be sure to check Table A-1 in Appendix A to ensure the device
you have chosen will work with this feature.
3.4.1Class A Supervised Wiring
Figure 3-5 shows how to wire for Class A output supervision. Use in/out wiring methods for
proper supervision. Refer to Section 4 for notification appliances compatible with the 5496.
Class A Output Notification Circuits
The configuration shown in Figure 3-5 shows two, 3-amp devices wired as Class A circuits.
When you are using the outputs as Class A circuits, loop the wiring back to the corresponding
circuit pair. For Class A wiring, no external EOL is necessary since it is built into the 5496
board.
Figure 3-5 Class A Supervised Input/Output Connections
1512763-5
Model 5496 Intelligent Power Module Installation and Oper ation Manual
Power Limited
1.5max
3.4.2Class B Supervised Wiring
Figure 3-6 shows how to wire for Class B output supervision. Use in/out wiring methods for
proper supervision. Refer to Section 4 for notification appliances that must be used with the
5496.
Class B Output Notification Circuits
Figure 3-6 shows four, 1.5 amp devices wired as Class B circuits.
Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable supervision
when using all outputs as Class B notification appliance circuits. The 4.7k EOLs must be
wired to the terminals whether or not you are using all output terminals.
Figure 3-6 Regulated Class B Supervised Input/Output Connections
3.4.3Releasing Operations
Approved releasing solenoids are list in Table 3-1. Do not mix cross alarming zones with
smoke verification zones. There must be at least two automatic detection devices in each
protected space. Spacing must be reduced to 0.7 times the linear spacing in accordance with
NFPA 72.
Table 3-1: Approved Releasing Solenoids
ManufacturerPart NumberRatingCurrentFreq
AscoT8210A10724 VDC3A max0 Hz
8210G20724 VDC3A max0 Hz
3-6151276
Hardware Installation
Power Limited
Supervised when used with the
Power Supervision Relay (PN160150)
3.4.4Auxiliary Power Configuration
Output circuits 1-4 on the control panel can be used as auxiliary power circuits. The three
types of auxiliary power available are:
•Door Holder (see Section 3.4.4.1 for description)
•Constant (see Section 3.4.4.2 for description)
•Resettable (see Section 3.4.4.3 for description)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for
all output circuits must not exceed 6 A).
To configure an output circuit as auxiliary power:
1. Wire the output circuit(s) that will be used for auxiliary power . See Figure 3-7 for location
of the output circuits.
2. Configure the auxiliary power output through programming for Door Holder, Constant or
Resettable power.
Figure 3-7 Output Circuits Used as Auxiliary Power
1512763-7
Model 5496 Intelligent Power Module Installation and Oper ation Manual
3.4.4.1Door Holder Power
Door holder is intended for fire door applications. When there are no alarms in the system and
the panel has AC power, door holder circuits have 24-volt power present at their terminals.
Any alarm will cause power to discontinue. Power will be re-applied when the system is reset.
If AC power is off for more than 15 seconds the auxiliary door holder power will be
discontinued to conserve the battery backup power. When AC power is restored, power is
immediately restored to the door holder circuits.
3.4.4.2Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is
always present at Constant circuits.
3.4.4.3Resettable Power
Resettable power is typically used to power beam detectors, flame detectors, and conventional
4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at
the terminals unless a system reset occurs. If a system reset occurs, power is removed from the
terminals for 30 seconds, then re-applied.
3-8151276
Appendix A
Compatible Devices
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL
resistor on each circuit. All supervised notification appliances used with the IFP-FFT must be
polarized.
A.1Notification Appliances
Note: Not all devices can use the Sync feature, be sure to check A.1 to ensure the device you have chosen will
work with this feature. This control is UL listed for single circuit synchronization.
Table A-1 below lists notification appliances compatible with the fire alarm control panel.
Appliances which can be synchronized indicate the type of sync available in the columns
marked Audio and/or Visual
Model 5496 Intelligent Power Module Installation and Oper ation Manual
Table A-1: Compatible Notification Appliances
ManufacturerModelAudioVisualType
CHRChime
CHWChime
CHSR2-Wire Chime/Strobe
CHSW2-Wire Chime/Strobe
HRHorn
HWHorn
HRKHorn
P2R2-Wire Horn/Strobe
P2R-P2-Wire Horn/Strobe
PC2R2-Wire Horn/Strobe
PC2R-P2-Wire Horn/Strobe
P2RH2-Wire Horn/Strobe High Candela
P2RH-P2-Wire Horn/Strobe High Candela
PC2RH2-Wire Horn/Strobe High Candela
PC2RH-P2-Wire Horn/Strobe High Candela
System Sensor
P2W2-Wire Horn/Strobe
P2W-P2-Wire Horn/Strobe
PC2W2-Wire Horn/Strobe
PC2W-P2-Wire Horn/Strobe
P2WH2-Wire Horn/Strobe High Candela
P2WH-P2-Wire Horn/Strobe High Candela
PC2WH2-Wire Horn/Strobe High Candela
PC2WH-P2-Wire Horn/Strobe High Candela
P2RK2-Wire Horn/Strobe
PC2RK2-Wire Horn/Strobe
P2RHK2-Wire Horn/Strobe High Candela
PC2RHK2-Wire Horn/Strobe High Candela
P4R4-Wire Horn/Strobe
PC4R4-Wire Horn/Strobe
P4RH4-Wire Horn/Strobe High Candela
P4W4-Wire Horn/Strobe
A-6151276
Table A-1: Compatible Notification Appliances
ManufacturerModelAudioVisualType
PC4W4-Wire Horn/Strobe
P4WH4-Wire Horn/Strobe High Candela
PC4WH4-Wire Horn/Strobe High Candela
P4RK4-Wire Horn/Strobe
PC4RK4-Wire Horn/Strobe
P4RHK4-Wire Horn/Strobe High Candela
PC4RHK4-Wire Horn/Strobe High Candela
PC4RH4-Wire Horn/Strobe High Candela
SRStrobe
SR-PStrobe
SCRStrobe
SCR-PStrobe
SRHStrobe High Candela
System Sensor
con’t
SRH-PStrobe High Candela
SCRHStrobe High Candela
SCRH-PStrobe High Candela
SWStrobe
SW-PStrobe
SCWStrobe
SCW-PStrobe
SWHStrobe High Candela
SWH-PStrobe High Candela
SCWHStrobe High Candela
SCWH-PStrobe High Candela
SRKStrobe
SCRKStrobe
SRHKStrobe High Candela
SCRHKStrobe High Candela
Compatible Devices
151276A-7
Model 5496 Intelligent Power Module Installation and Oper ation Manual
RSSWP-24MCWHStrobe Weatherproof
ZRS-MCWHStrobe
ZRS-24MCCStrobe
ZRS-24MCCHStrobe
MB-G6-24 Motor Bell
MB-G10-24 Motor Bell
MB-G6-12 Motor Bell
MB-G10-12 Motor Bell
MIZ-24-R Mini-Horn
Door Holder Device
The following UL listed door holder can be used with the IFP-FFT: ESL DHS-1224
151276A-11
Model 5496 Intelligent Power Module Installation and Oper ation Manual
A-12151276
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•All new fire products manufactured by Silent Knight have a limited warranty period of
36 months from the date of manufacture against defects in materials and workmanship.
See limited warranty statement for details.
•This limited warranty does not apply to those products that are damaged due to misuse,
abuse, negligence, exposer to adverse environmental conditions, or have been modified in
any manner whatsoever.
Repair and RA Procedure
•All products that are returned to Silent Knight for credit or repair require a RMA (Return
Authorization) number. Call Silent Knight Customer Service at 800-328-0103 or
203-484-7161 between 8:00 A.M. and 5:00 P.M. EST , Monday through Friday to obtain a
return authorization number.
•Silent Knight Technical Support is available at 800-446-6444 between 8:00 A.M. and
5:00 P.M. CST, Monday through Friday.
•All returns for credit are subject to inspection and testing at the factory before actual
determination is made to allow credit.
•RMA number must be prominently displayed on the outside of the shipping box. See
return address example under Advanced Replacement Policy.
•Include a packing slip that has the RMA number, a content list, and a detailed description
of the problem should be included with each return.
•All products returned to Silent Knight must be sent freight pre-paid. After product is
processed, Silent Knight will pay for shipping product back to customer via UPS ground.
•Return the Silent Knight product circuit board only. Products that are returned in cabinets
will be charged an additional $50 to cover the extra shipping and handling costs over
board only returns. Do not return batteries. Silent Knight has the authority to determine
if a product is repairable. Products that are deemed un-repairable will be returned to the
customer.
•Product that is returned that has a board date code more than 36 months from date of
manufacture will be repaired and the customer will be assessed the standard Silent Knight
repair charge for that model.
Advanced Replacement Policy
•Silent Knight offers an option of advance replacement for fire product printed circuit
boards that fail during the first 6 months of the warranty period. These items must be
returned with transportation charges prepaid and must be accompanied by a return
authorization.
•For advance replacement of a defective board contact your local Silent Knight Distributor
or call Silent Knight at 203-484-7161 to obtain a RMA (Return Authorization) number
and request advanced replacement,
•A new or refurbished board will be shipped to the customer . The customer will initially be
billed for the replacement board but a credit will be issued after the repairable board is
received at Silent Knight. All returned products must comply with the guidelines
described under “General Terms and Conditions”.
•The defective board must be returned within 30 days of shipment of replacement board for
customer to receive credit. No credit will be issued if the returned board was damaged due
to misuse or abuse.
•Repairs and returns should be sent to:
Silent Knight / Honeywell
Attn: Repair Department
12 Clintonville Road
Northford, CT 06472
USA
RMA Number:___________________
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer
warrants that the Products manufactured by it in its Northford, Connecticut facility and
sold by it to its authorized Distributors shall be free, under normal use and service,
from defects in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The Products
manufactured and sold by Manufacturer are date stamped at the time of production.
Manufacturer does not warrant Products that are not manufactured by it in its
Northford, Connecticut facility but assigns to its Distributor, to extent possible, any
warranty offered by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced repaired by anyone other than Manufacturer or its
authorized Distributors.This warranty shall also be void if there is a failure to maintain
the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY
AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH
RESPECT TO THE PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES
RENDERED By MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY
PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS
A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS
PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its
products and replaces all previous warranties and is the only warranty made by
Manufacturer. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized. Manufacturer does not represent that its products will prevent
any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion,
each part returned by its authorized Distributor and acknowledged by Manufacturer to
be defective, provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed Manufacturer's
Return Material Authorization form. The replacement part shall come from
Manufacturer's stock and may be new or refurbished. THE FOREGOING IS
DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A
WARRANTY CLAIM
Warn-HL-08-2009.fm
Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203-484-7161
Fax: 203-484-7118
www.silentknight.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.