SilentKnight SK-5495 User Manual

MODEL 5495
Distributed Power Module
Installation and Operations Manual
Document 151161 08/12/13 Rev M
151161:M ECN 13-0708
Section 1
Introduction ..................................................................................................................................1
Section 2
UL Requirements ....................................................................................................................2
Section 3
System Overview ....................................................................................................................3
3.1 Terminal Descriptions and Electrical Ratings ......................................................... ... ... ... .... ........3
3.2 Signal Input Terminals .................................................................................................................4
3.3 Notification Appliance Circuit Terminals ......................................................................................5
Section 4
Installation ......................................................................................................................................7
4.1 Mounting ............................. ................ ................ ................ ................ ................. ........................7
4.1.1 Preventing Water Damage ....................................................................................................7
4.2 Wire Routing ................................................................................................................................8
4.3 Current Requirements (Standby and Alarm) .......................................... ... ... ... .... ... ... ... ... .... ... ... ..9
4.3.1 Current Drawn From Host Panel ...........................................................................................9
4.3.2 Current Drawn from Battery ............ .......................................... ... .... ... ... ... .... ... ... ..................9
4.4 Connecting the 5495 to a Control Panel ............................................ .... ... ... ... .... ... ... ................11
4.4.1 Common Trouble Relay ............ ... ... ... .... ... ... ... .... ... ... ... .... ... ... ... ... .... ...................................12
4.5 Notification Appliance Wiring .....................................................................................................13
4.5.1 Class A Supervised Wiring ....................................................... ... .... ... ... ... .... ... ...................13
Class A Output Notification Circuits .................................................................................13
Class A Supervised Input Circuits ...................................................................................13
4.5.2 Class B Supervised Wiring ....................................................... ... .... ... ... ... .... ... ...................14
Class B Output Notification Circuits .................................................................................14
Class B Supervised Input Circuits ...................................................................................15
4.6 Ground Fault Detection Enable/Disable Jumper ....................................................................... 15
4.7 Battery Connection ....................................................................................................................16
4.8 DIP Switch Settings ...................................................................................................................17
4.8.1 Selecting the Standard Input/Output Configurations ................. ..........................................18
4.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded Outputs ................19
4.8.2 Selecting Synchronized Output Configurations ..................................................................20
4.8.2.1 Selecting Synchronized Faraday Configurations ......................................................20
4.8.2.2 Selecting Synchronized Gentex Configurations ........... .............................................20
4.8.2.3 Selecting Synchronized System Sensor Configurations ........................................... 21
4.8.2.4 Selecting Synchronized Wheelock Configurations ....... ....................... ......................21
4.8.2.5 Selecting Synchronized AMSECO Configurations .......... .......................................... 21
4.8.3 Setting the Loss of AC Delay .......... ... .................................................................................22
151161 i
Model 5495 Distributed Power Module Installation Manual
4.8.4 Setting the Auxiliary Output ................................................ ... ... ... .......................................22
Section 5
Sample Applications .........................................................................................................23
5.1 Notification Power Applications .................................................................................................23
5.2 Non-Resettable Power Application ............................................................................................25
5.3 Door Holder Application ............................................................................................................26
Section 6
Troubleshooting .....................................................................................................................27
6.1 LEDs ................................ ................ ............. ................ ................ ................ .............................27
6.2 Trouble Conditions ....................................................................................................................28
6.3 Earth Fault Resistance ..............................................................................................................29
6.4 Removing and Replacing the Control Panel .............................................................................30
6.4.1 Removing the Control Panel ...............................................................................................30
6.4.2 Replacing the Control Panel ...............................................................................................30
Appendix A UL Listed Notification Appliances
A.1 Notification Appliances ..............................................................................................................33
......................................................................33
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability
ii 151161

Section 1 Introduction

The 5495 is a notification appliance circuit and auxiliary power expander that provides up to 6 amps of filtered, 24 volt power for powering notification appliances and auxiliary devices. The 5495 provides its own AC power connection, battery charging circuit, and battery connections. Used with security and fire alarm control panels, the 5495 enables you to connect and distribute power to many more devices than your panel may normally allow.
Input Configurations The 5495 has two optically isolated signaling inputs that provide the signal
connection from the main control panel to the 5495 (see Section 3.2 for more details).
Output Configurations The 5495 has four power-limited notification appliance circuits that can be
configured in various combinations of Class A and Class B circuits (see Section
3.3 for details).
Auxiliary Power Configurations The 5495 has a dedicated, power-limited, auxiliary output that can be configured
in two different ways. The auxiliary output can either be non-resettable (always on), or configured to switch off during the AC power failure to conserve the battery standby power. When the auxiliary power is configured to switch off, there is a 30 second delay before the auxiliary power is turned off after the AC power fails (see Section 4.8.4 for details).
Form C Trouble Relay The 5495 includes a general trouble relay that will de-energize for any trouble
situation. (see Section 4.4.1 for details).
Earth Fault Detection The 5495 monitors for earth faults to the system power or system ground. When
detected, the system de-energizes the trouble relay and the input supervision relays (see Section 5.2 for details).
ANSI Temporal Code The 5495 provides two configuration options that will drive outputs with the ANSI
temporal code if the inputs are on constantly (see Section 4.8.1 for details).
Supports Synchronized appliances The 5495 provides configuration options that will eliminate the need for
synchronized modules when using AMSECO, Faraday, Gentex, System Sensor, or Wheelock synchronization appliances.
151161 1
Model 5495 Distributed Power Module Installation Manual

Section 2 UL Requirements

When installed in accordance with NFPA 70 and NFPA 72 standards, the 5495 can be connected to UL Listed devices.
The 5495 is also listed to meet UL 864, UL 2572 and power limiting requirements. The 5495 is compatible with any UL listed control unit utilizing reverse polarity
supervised notification appliance circuits, using 24 VDC regulated outputs.
2 151161
System Overview

Section 3 System Overview

CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut down (power limit). The circuit will automatically reset once you remove the overload condition.

3.1 Terminal Descriptions and Electrical Ratings

Terminal # Description Ratings
TB1
1 AC (black–“hot”)
120 VAC 60 Hz, 2 A2 Earth Ground
3 AC (white–“neutral”)
TB2
1 Auxiliary Power (-) 2 Auxiliary Power (+) 3 Notification 4 Output (-) 4 Notification 4 Output (+) Although each output 5 Notification 3 Output (-) 6 Notification 3 Output (+) total current draw from 7 Notification 2 Output (-) 8 Notification 2 Output (+) auxiliary power must
9 Notification 1 Output (-) 10 Notification 1 Output (+) 11 Normally Closed contact 2.5 A @ 250 VAC 12 Common 13 Normally Open contact 14 Input 2
16 Input 2 (+) 17 Input 1
19 Input 1 (+)
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
or
2.5 A @ 30 VDC
9 - 30 VDC15 Input 2 (-)
9 - 30 VDC18 Input 1 (-)
is rated for 3 amps, the
the 4 outputs and the
not exceed 6 amps.
151161 3
Model 5495 Distributed Power Module Installation Manual

3.2 Signal Input Terminals

Terminals 14 through 19 are polarized signal input terminals. They provide the signaling connection from the main panel to the 5495. See Figure 4-2 for more details.
The main panel supervises its notification appliance circuits used for communicating with the 5495 the same way it supervises ordinary notification appliance circuits. The signal inputs on the 5495 monitor the polarity of the voltage coming from the main panel’s notification appliance circuits to determine when to operate the notification appliance circuits on the 5495. The 5495 emulates the trouble behavior of a normal notification appliance circuit by interrupting the EOL supervision current for internal or output trouble conditions on the 5495.
Note that the 5495 will accurately sense the polarity of the main panel’s notification appliance circuits to drive the outputs whether or not the supervision connection is intact. The following situations will disconnect the EOL supervision at the signal inputs and indicate a trouble condition:
Low AC power
Low Battery condition
Earth ground fault to the system power or system ground
Auxiliary output power-limited condition
EOL supervision trouble or power-limited condition at an output Trouble conditions will not necessarily occur for both inputs when the trouble is
specific to a particular output. Only the signal input controlling the output circuit that is in trouble will indicate a trouble condition. Below are examples where both inputs do NOT indicate trouble for a trouble occurring at only one output circuit.
Example 1: If input 1 controls all four outputs, a fault on any output will cause
input 1 to indicate trouble. The fault does not affect input 2.
Example 2: If input 1 controls outputs 1 and 2, and input 2 controls outputs 3
and 4, a fault condition on output 3 or 4 will cause input 2 to indicate trouble. The fault does not affect input 1.
Note:Once the inputs are driven with forward polarity to activate the outputs, the main control panel will
not be able to sense trouble conditions through its notification appliance circuit connected to the 5495 input circuits. Use the 5495 trouble relay when it is necessary to monitor trouble conditions and active alarm conditions at the same time.
Section 6 explains the significance of each trouble condition in more detail.
4 151161
System Overview

3.3 Notification Appliance Circuit Terminals

Terminals 3 through 10 are the notification appliance circuit output terminals. Each of the four circuits are rated at 3 amps, although you can only draw a total of 6 amps from the 5495. The 5495 outputs are short-circuit protected (power limited) according to UL 864 standards. Overcurrent indicators are yellow LEDs. The output voltage can vary depending on the load and input voltage.
The four power-limited NAC outputs can be configured as follows:
Four Class B circuits Faraday synchronized outputs
Two Class A circuits Gentex synchronized outputs
One Class A and two Class B circuits System Sensor synchronized outputs
Class B, ANSI temporal-coded circuits Wheelock synchronization outputs
• AMSECO synchronized outputs One or both 5495 signal inputs control the NAC outputs, depending on the specific
configuration setup. Possible configurations for the 5495 are:
For Option: These Inputs: Control These Outputs: As:
1 Input 1 All outputs Class B circuits 2
3
4 5 Input 1 Outputs 1-2 and 3-4 Class A circuit pairs
6
7
8
9
10
11
12
Input 1 or Input 2 coded circuits Input 1 Outputs 1 and 2 Class B circuits Input 2 Outputs 3 and 4 Class B circuits Input 1 Output 1 Class B circuits Input 2 Outputs 2, 3, and 4 Class B circuits
Input 1 Outputs 1 and 2 Class B ANSI temporal-coded
Input 2 Outputs 3 and 4 Class B circuits Input 1 Outputs 1-2 Class A circuit pair Input 2 Outputs 3-4 Class A circuit pair Input 1 Outputs 1-2 Class A circuit pair Input 2 Outputs 3 and 4 Class B circuits Input 1 (Strobe
Control) Input 2 (Audio Control) Faraday Sync. Output Input 1 (Strobe
Control) Input 2 (Audio Control) Gentex Sync. Output Input 1 (Strobe
Control) Input 2 (Audio Control) System Sensor Sync. Output Input 1 (Strobe
Control) Input 2 (Audio Control) Wheelock Sync. Output
Outputs 1, 2, 3, and 4
All outputs
All outputs
All outputs
All outputs
Class B ANSI temporal-
circuits
Class A or Class B
Class A or Class B
Class A or Class B
Class A or Class B
151161 5
Model 5495 Distributed Power Module Installation Manual
For Option: These Inputs: Control These Outputs: As:
13
Input 1 (Strobe Control)
Input 2 (Audio Control) Amseco Sync. Output
All outputs
Class A or Class B
You can select which input controls which output, and which inputs are Class A and Class B using the 7-position DIP switch on the printed circuit board. Section 4.8 for DIP switch settings.
6 151161
Installation

Section 4 Installation

Before installing the 5495, the AC input must first be wired into the building’s main electrical power through the TB1 terminals (see Figure 4-2). Shut off the electrical power to the 5495, and then complete the general installation of the 5495 using the information in this section.

4.1 Mounting

Mount the 5495 in locations that meet the following temperature and humidity requirements. Do not expose the panel to conditions outside these ranges. For use in indoor, dry environments.
Temperature Humidity
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is expected, first attach a piece of 3/ 4-inch plywood to the concrete surface. Attach the 5495 to the plywood.
o
C-49o C (32o F-120o F)
0 10%-93% at 30o C (86o F) noncondensing

4.1.1 Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
151161 7
Model 5495 Distributed Power Module Installation Manual
Note: The use of this knock out will reduce the number and/or size of batteries this cabinet can contain. Evaluation of space is important before using.

4.2 Wire Routing

To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from high current output and power-limited wiring. Induced noise can interfere with telephone communication or even cause false alarms. Avoid pulling a single multiconductor cable for the entire system. Instead, separate high current input/output from low current. Separate power-limited from non-power-limited wiring. Non-power-limited wiring must be enclosed in conduit.
Wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the switching power supply circuit.
Figure 4-1 Sample Wire Routing
Ground fault and wire to wire short impedance to any terminal is 0 
8 151161
Installation

4.3 Current Requirements (Standby and Alarm)

4.3.1 Current Drawn From Host Panel

Table 4-1 shows the 5495 current draw requirements from the main control panel when the panel’s notification appliance circuit is in alarm. The current draw from the main panel when it is supervising the 5495 is the same current draw that would be present when the main panel supervises an ordinary notification appliance circuit.
Table 4-1: Alarm Current Drawn From Main Control Panel
Panel Voltage Current
Alarm Current (for typical voltages) drawn from main panel’s notification
appliance
circuits.

4.3.2 Current Drawn from Battery

12 VDC 6.5 mA 24 VDC One input circuit: 15 mA
Both input circuits: 30 mA
Batteries used with the 5495 must not exceed 35AH. (33AH max. for FM (Factory Mutual) Installations). Batteries larger than 7 AH will not fit into the 5495 cabinet and must be housed in the RBB Remote Battery Box. See Section 4.7 for battery installation.
The following is the maximum current draw from the auxiliary power terminals for standby calculations. These currents assume 24 or 60 hours of standby time, followed by 5 minutes of maximum alarm current.
195 mA for 24 Hour Standby Current
39 mA for 60 Hours of Auxiliary Standby Current The above numbers were calculated assuming the use of 7 AH batteries at 100% of
rated capacity. The total current of the 5495, plus all items powered from it, must not exceed 6 A
when the panel is in alarm. Use Table 4-2 to ensure that the current does not exceed 6 A and, that the desired amount of standby is possible for the battery intended for use with the 5495.
151161 9
Model 5495 Distributed Power Module Installation Manual
Table 4-2: Battery Calculation Worksheet
Device
For each device use this formula: This column
5495 Distributed Power Module (Current draw from battery)
A
Auxiliary Devices Refer to device manual for current ratings.
B
Notification appliances Refer to device manual for current ratings.
C
Total current ratings of all devices in system (line A + line B + line C)
D
Total current ratings converted to amperes (line D x .001):
E
Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). 24 Hrs. for
F
NBC, section 3.2.7.8 Multiply lines E and F. Total standby AH
G
Alarm sounding period in hours. In accordance with NBC and ULC. (For example, 5 minutes = .0833 hours, or for ULC installations 30 minutes = 0.5
H
hours.) Multiply lines E and H. Total alarm AH
I
Add lines G and I. Total standby and alarm AH
J
Multiply line J by 1.20. (20% extra insurance to meet desired performance) Tot al ampere-hours
K
required
Number of
Devices
1
Current per Device
X This column = Current per number of
devices.
Standby: 75 mA 75 mA Alarm: 205 mA 205 mA
5495 Current 75 mA 205 mA
Alarm/Standby mA mA mA Alarm/Standby mA mA mA Alarm/Standby mA mA mA Alarm/Standby mA mA mA
Auxiliary Device Current mA mA
Alarm: mA 0 mA mA Alarm: mA 0 mA mA Alarm: mA 0 mA mA Alarm: mA 0 mA mA
Notification Appliance Current
Standby
Current
0 mA mA
mA mA
AA
H
AH
AH
AH
Alarm
Current
H
AH
10 151161
Installation

4.4 Connecting the 5495 to a Control Panel

Figure 4-2 shows the general layout of the 5495 PC board. This section also provides specific wiring details for accessories.
Figure 4-2 The Model 5495 PC Board Layout
Consult the installation manual for specific wiring information for the control panel being used.
151161 11
Model 5495 Distributed Power Module Installation Manual
Must be connected to a power limited source

4.4.1 Common Trouble Relay

The 5495 has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any trouble condition.
A typical application of the trouble relay is to connect the 5495 normally closed (N.C.) contacts in series with the EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control panel when the 5495 opens its trouble contacts.
Note:The N.C. contact is the contact that is closed when the 5495 has po wer and the re are no trou ble
conditions.
Figure 4-3 Trouble Relay Connection Example
12 151161
Loading...
+ 36 hidden pages