SilentKnight SK-5220 User Manual

5220 Direct Connect Module Installation Instructions
The 5220 is a direct connect module used to connect a fire alarm control panel (FACP) to a city box or polarity reversal communicator. The following instruction are generic installation instructions, refer to the FACP installation manual for compatibility and usage.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Specifications
Operating Voltage: 19.4 to 28 VDC
City Box Current : 1 A for 1 Second, max coil resistance 30 ohms
Polarity Reversal: 20 mA max., max loop resistance 3 k ohms
Ambient Temperature: 32°F to 120°F (0°C to 49°C), or humidity within the range of 10%-93% at 30°C (86°F) noncondensing.
Dimensions: 6-1/2”W x 1-5/16”H x 2-1/8”D (16.51 cm W x 3.33 cm H x 5.40 cm D)
Terminal Wire Rating: 12 - 24 AWG
Mounting
The 5220 comes equipped with its own cabinet assembly. The 5220 is intended for indoor use only in a dry location.
1. Remove the cover from the 5220.
2. Mount the 5220 with four screws in the holes shown in Figure 1.
Cover Screw Hole
Figure 1: Mounting the 5220
3. Wiring the 5220 as shown in Figure 2.
4. Replace the 5220 cover and secure it with the two self-tapping screws supplied.
Mounting Holes
Mounting Holes
Cover Screw Hole
P/N 151409
5220 Direct Connect Module Installation Instructions
Wiring
1. Connect the 5220 as shown in Figure 2.
Figure 2: 5220 Wiring Connections