SilentKnight SK-5217 User Manual

SK-5217 Zone Expander Installation Instructions
The following instructions are a quick reference guide, refer to the control panel installation manual for detailed system information.
The Model SK-5217 provides the SK-5208 with ten additional class B (style A) zones. The SK­5217 connects to the SK-5208 control panel via the SBUS as shown in Figure 1.
SK-5217
Maximum circuit Resistance - 50 ohms Maximum Total alarm current for all class B (style A) zones: 1 A Maximum Standby Current per Zone:3.0 mA Maximum Alarm Current per Zone:95 mA Input Voltage: 17.5 –27.4 VDC Standby Current: 60 Ma Detector Compatibility ID:24J
For a list of compatible detectors, refer to the SK-5208 installation manual (PN 151240).
Device ID Dip Switches
Control Panel
Figure 1: SBUS Connections
Supervised
Power Limited
Zone Inputs
Figure 2 shows how to wire the SK-5217. Use a
4.7k end of line resistor for each class B circuit. The EOL must be wired in parallel with the normally open contact farthest from the panel.
Supervised Power Limited
4.7k
Ω
UL Listed
EOL Resistor
P/N 7628
Figure 2: Model SK-5217 Class B Circuits
P/N 151236
SK-5217 Zone Expander Installation Instructions
Mounting Instructions
The SK-5217 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet.
Mounting the SK-5217 into SK-5208 Cabinet
Follow these steps to properly mount the SK­5217 zone expander into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3.
Mounting the SK-5217 into the SK-2190 Accessory Cabinet.
Follow these steps to properly mount the SK­5217 zone expander into the SK-2190 cabinet:
1. Mount the remote cabinet using the cabinet mounting holes. See Figure 4.
2. Remove power from the control panel.
3. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 4.
Mounting Holes
Figure 3: Installing the 5217 Into the 5208 Cabinet
3. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 1.
4. Wire the zone inputs to the zone expander as shown in Figure 2.
5. Reconnect power to the control panel.
Figure 4: Model SK-5217 Remote Installation
4. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 1.
5. Wire the zone inputs to the zone expander as shown in Figure 2.
Maple Grove, MN 55369-4927
763-493-6455 or 800-328-0103
2
© 2006 Silent Knight PN 151236 Rev B