Adherence to the following will aid in problem-free installation with long-term reliability:
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s,
modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until
manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper
system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in
site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or
software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are
not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum
of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for
operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes ar e adequate for
all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased
susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated
or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can
damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure.
When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal
removal. fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to
avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability
depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such
a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire.
Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type
of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located
on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to
reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit
alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following written procedures supplied with each device. System
inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written
records of all inspections should be kept.
1.1Model SK-5208 Features ................................. ...................................................... ..................................1-1
1.2About This Manual ..................................................................................................................................1-1
1.3How to Contact Silent Knight .................................................................................................................. 1-1
3.5Mounting the SK-5208 .............................................................................................................................1-4
3.5.1 Preventing Water Damage ............................................................. ................................................... 1-4
3.15 Special Applications .............................................................................................................................. 1-27
3.15.1 Model 5220 Direct Connect Module .............................................................................................. 1-27
3.15.1.1 City Box Connection ............................................................................................................ 1-27
4.1Keypad Operation During Programming .................................................................................................1-1
4.1.1 Special Characters .............................................................................................................................1-2
4.1.2 Enabling Extended Programming List ..............................................................................................1-2
4.2.1 Zone Options .....................................................................................................................................1-4
4.2.2 Misc System Option ..........................................................................................................................1-5
4.2.6 User Code .........................................................................................................................................1-9
4.2.9 Line Options ................................................................................................................................... 1-12
5.1Installer & User Keys ...............................................................................................................................1-1
5.2On-board Touchpad and SK-5235 Operation ..........................................................................................1-2
5.2.1 View Control Panel Firmware Number and Revision ......................................................................1-2
5.7.1 Fire Drills ..........................................................................................................................................1-7
5.7.2 Walk Test ..........................................................................................................................................1-7
5.7.3 Automatic Self Test ..........................................................................................................................1-7
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
Model SK5208 Basic Operating Instructions
3
Page 6
151204
Section 1
Introduction
The Model SK-5208 is an 24-volt 10-zone fire alarm control panel (expandable up to 30 zones using SK-5217
Zone Expanders) with a digital communicator that meets NFPA 72 requirements. The SK-5208 cabinet can be
surface mounted or semi-flush mounted.
1.1Model SK-5208 Features
•Built-in two-line (16 Character each line) LCD display provides easy to read English language readouts
•10 Initiation inputs, 8 Class B (Style B) and 2 zones that can be configured as Class B (Style B) or Class A
(Style D), expandable to 30 zones
•Supervised zone expanders and I/O modules can be mounted remotely from the main control panel
•UL Listed
•Event History Buffer (approximately 150 events) with Date/Time stamp
•All zones are compatible with 2- and 4-wire detectors
•Built-in Digital Alarm Communicator Transmitter (DACT)
•4 Notification appliance circuits
•4 programmable general purpose relays
•Programmable smoke verification, pre-alarm delay, cross zoning and enhanced verification mode features
that can help minimize false alarms
•Capable of single or dual operation for water releasing services.
•Programmable from the built-in control panel touchpad, remote annunciator or Windows
software
•Built-in walk test
®
downloading
1.2About This Manual
This manual is intended to be a complete reference for all installation and operation tasks for the SK-5208.
Please let us know if the manual does not meet your needs in any way. We value your feedback!
1.3How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical
Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 80 0-328-0103.
1-1
Page 7
Model SK-5208 Installation Manual151204
1.3.1Optional Accessories
Table 1-1: Compatible Modules Manufactured by Silent Knight
ModelWhat It Does
SK-5217 Zone ExpanderAdds 10 zones to the SK-5208 for a total expansion of the system to 30 zones.
SK-2190 Accessory CabinetUsed for remote mounting of the SK-5217 Zone Expander.
Dimensions: 10-3/8”W x 10-3/16”H x 3”D (26.35 cm W x 25.88 cm H x 7.62 cm D)
5220 Direct Connect ModuleFor direct alarming and trouble transmission from the SK-5208 to a supervising
station.
SK-5235 Remote AnnunciatorFor remote annunciation, operation, and on-site programming.
SK-5280The Model SK-5280 Status Display module provides outputs and control functions for
remote annunciation of alarm, trouble, and supervisories for each zone.
5824Provides connectivity to a Serial or Parallel printer. (See Section 4.2.12 for
programming.)
SK-5499 Signal Power ExpanderNotification circuit power for additional notification appliances. Provides additional
9A of 24 VDC, supervised.
SK-5495 Signal Power ExpanderNotification circuit power for additional notification appliances. Provides additional
6A of 24 VDC, supervised.
SKSS Downloading Software
Model 5660
PLEX-2Optional door accessory for single button operation. (See Section 4.3 for
For remote programming of the SK-5208 using a personal computer.
programming.)
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following
the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72
manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the
Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by
the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke
detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are
designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm
system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For
example:
•Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke
detectors because:
-Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
-Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are
located.
-Smoke particles may be blown away from detectors by air outlets
-Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another
level.
•The amount of smokepresent may be insufficient to alarm smoke detectors. Smoke detectors are designed to
alarm at various levels of smoke density. If such density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
•Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering
),
1-2
Page 8
Introduction151204
fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users.
For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal
operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to
falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do
not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing
with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas,
improper storage of flammable materials, etc.).
•Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their
sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to
protect property, not life.
•Warning devices (including horns, sirens, and bells) ma y not alert people or wake up sleepers who are
located on the other side of closed or partially open doors. A warning device that activates on a different
floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake
may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other
appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to alert people with a
disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or
sleeping pills.
-Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to
alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service
or temporarily out of service. For added protection against telephone line failure, backup radio transmission
systems are recommended.
•System components, though designed to last many years, can fail at any time. As a precautionary measure, it
is recommended that smoke detectors be checked, maintained, and replaced per manufacturer's
recommendations.
•System components will not work without electrical power. If system batteries are not serviced or replaced
regularly, they may not provide battery backup when AC power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they
are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is
not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and
the people in their premises and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.
1-3
Page 9
Section 2
Agency Listings and Requirements
Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit.
Testing and maintenance should be performed according to NFPA 72.
2.1Federal Communications Commission (FCC)
1.If requested by the telephone company, the following information must be provided before the SK-5208 can
be connected to the phone lines:
4.If the SK-5208 causes harm to the telephone network, the telephone company will notify the user in advance
that temporary discontinuance of service may be required. When advance notice is not practical, the telephone company will notify the user as soon as possible. Users have the right to file complaints, if necessary ,
with the Federal Communications Commission.
5.The telephone company may make changes in its facilities, equipment, operations, or procedures that could
affect the operation of the equipment. If this happens, the telephone company will provide advance notice to
allow you to make the necessary modifications to maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the two following
conditions: (1) This device may not cause radio interference; and (2) This device must accept any
interference received including interference that may cause undesired operation.
2.2Underwriters Laboratories (UL)
The SK-5208 is UL Listed as a control unit for use in Central Station Protected Premises, Local Protected Fire
Alarm Systems, Auxiliary Protected Fire Alarm Systems for Fire Alarm Service (City Box), Remote Station
Protected Fire Alarm Systems and water releasing service. If the SK-5208 and its accessories are to be used as
part of a UL installation, carefully read the UL requirements in this section.
2-1
Page 10
Agency Listings and Requirements 151204
2.2.1Requirements for All Installations
General requirements are described below. The sections that follow describe additional requirements for the type
of installation (for example, Central Station Fire Al arm systems, Local Protected Fi re Alarm systems, and so on).
1.Use UL listed smoke detectors compatible with the SK-5208. Refer to Appendix A.
2.Use UL listed compatible notification devices. Refer to Appendix A.
Restricted Options:
•The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL
certified installations this number must be set from 1 to 3 hours.
•Call forwarding shall not be used.
•When cross zoning is used detector spacing shall be cut in half, you shall not use the alarm verification
feature, and no delay shall be used.
2.2.2Requirements for Central Station Fire Alarm Systems
1.The Phone Line “Line Dial Type” must be selected for anything other than “Not Used”. (See programming
Section 4.2.9).
2.On class A (style D) zones, the number of waterflow devices is limited to five.
3.Auxiliary relays may not be programmed to activate for Pre-Alarm. See programming Section 4.2.5.
2.2.3Requirements for Auxiliary Protected Fire Alarm Systems
for Fire Alarm Service
1.Follow the current load restrictions shown in Section 3.6.
2.The Model 5220 Direct Connect module must be installed (see Section 3.15.1 for wiring).
2.2.4Requirements for Remote Station Protected Fire Alarm
Systems, for Digital Communication or Polarity Reversal
1.Follow the current load restrictions shown in Section 3.6.
2.Use the SK-5208’s built-in dialer or install the Model 5220 Direct Connect Module (see Section 3.15.1).
2-2
Page 11
Section 3
Control Panel Installation
3.1Electrical Specifications
Table 3-1: Electrical Specifications
Primary AC120 Vrms at 60 Hz, 3A
To ta l DC Lo ad6A
Accessory Power27.4 VDC, 1A
Smoke Power27.4 VDC, 1A
Battery Charging Voltage27.4
Battery Charging Current.75 A max.
Class B (Style B) Circuit Current95 mA max.
Telepho ne Minimum Input Sensitivity35 dB
Good Phone Line Voltage3 V
Maximum Low Battery Detect20.4
Minimum Low AC Detect98
Notification Power3A max. per output (6A total)
151204
3.2Environmental Specifications
It is important to protect the SK-5208 control panel from water. To prevent water damage, the following
conditions should be AVOIDED when mounting the units:
•Do not mount directly on exterior walls, especially masonry walls (condensation).
•Do not mount directly on exterior walls below grade (condensation).
•Protect from plumbing leaks.
•Protect from splash caused by sprinkler system inspection ports.
•Do not mount in areas with humidity-generating equipment (such as dryers, production machinery).
When selecting a location to mount the SK-5208 control panel, the unit should be mounted where it will NOT be
exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity equal to or greater than 93% at
30°C (89°F) noncondensing.
See also the mounting recommendations in Section 3.5 for additional environmental specificati ons.
3.3Wiring Specifications
To avoid induced noise (transfer of electric al energy from one wire to another), keep input wiring isolated from
high current output and power wiring. Induced noise can interfere with telephone communication or even cause
3-1
Page 12
Control Panel Installation 151204
Tel. Line
Aux Relays
NACs
SBUS devices
or
Annunciator
To Zone
To AC
false alarms. Avoid pulling one multiconductor cable for the entire panel. Instead, separate the wiring as follows:
Input/Output TypeWiring
1/4" spacing must be maintained
between each of these circuit types;
as well as between power limited
and non-power limited circuits.
High Voltage:AC power
Low Voltage:Annunciator, zone circuit wiring, and notification devices
Audio:Speaker
TelcoSeparated
DO NOT pull wires from different groups through the same conduit. If you must run them together, do so for as
short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel only.
For the same reasons, wiring within the cabinet should be routed around the perimeter of the cabinet. It should
not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up
unwanted RF noise from the high speed circuits.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced
by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid. Figure 3-1 provides an
example.
Figure 3-1 Wire Routing Example
3-2
Page 13
Model SK-5208 Installation Manual151204
Phone Line 1
Connections
Phone Line 2
Connections
NAC
Circuit
Programmable
Output Relays
Backup
Battery
Connector
Connections
Remote
Annunciator
AC
Input
Class A
or
Class B
Zone
Inputs
Class B
Zone
Inputs
SBUS
Connections
RS232
Programming Connector
Mounting
Screw
Mounting
Screw
Mounting
Screw
Mounting
Screw
3.4Control Board Components
Figure 3-2 is a wiring diagram for wiring the Model SK-5208 panel.
Figure 3-2 Model SK-5208 Board La yout
Refer to Section 3.9 for complete description of control panel terminal connections.
Figure 3-2 shows the 5208 circuit board stack. If you should need to remove the control board for repair, remove
the four mounting screws which hold the control board in the cabinet. Then lift the control board out of the
cabinet.
3-3
Page 14
Control Panel Installation 151204
3.5Mounting the SK-5208
Read the environmental specifications in section 3.2 on page 1 before mounting the SK-5208 panel.
The SK-5208 cabinet dimensions are:
16" W x 26.4" H x 4" D (40.64 cm W x 67.06 cm H x 10.16 cm D).
The SK-5208 panel should be located within a secured area, where it is accessible to main drop wiring runs and
where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear
alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and
trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete,
especially when moisture can accumulate, the enclosure shall be placed or equipped so as to prevent moisture or
water from entering and accumulating within the cabinet, and shall be mounted so there is a least 1/4” space
between the enclosure and the concrete wall surface. A piece of plywood, standoffs, or other equivalent material
can be used to space the cabinet from the concrete surface and then attach the SK-5208 to that spacing surface.
Also mount any other desired components to the 1/4” spacing surface.
DO NOT flush-mount the SK-5208 cabinet in a wall designated as a fire break.
3.5.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
3.6Current Draw Calculations
3.6.1Worksheet Requirements
The following steps must be taken when determining SK-5208 current draw and standby battery requirements.
Filling in the Current Draw Worksheet, Table 3-2 (Section 3.6.2)
1.For the SK-5208, the worst case current draw is listed for the panel and panel accessories. Fill in the number
of devices that will be used in the system and compute the current draw requirements for alarm and standby .
Record this information in Table 3-2 at Line A.
2.Add up the current draw for all smoke detectors and record in the table at Line B.
3.Add up all notification appliance loads and record in the table at Line C.
4.For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for
the current ratings.
5.Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the SK-5208 control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as the 5495 to dis-
tribute the power loads so that the SK-5208 or the power expanders do not exceed their power rating. Refer
to the current draw worksheets provided with the 5495 manuals so you do not exceed their power requirements.
6.Complete the remaining instructions in Table 3-2 for determining battery size requirements.
3-4
Page 15
Model SK-5208 Installation Manual151204
3.6.2Current Draw Worksheet
Use Table 3-2 to determine current requirements during alarm/battery standby operation. (Copy the page if
additional space is required.)
Table 3-2: Current Draw Calculations
Device# of DevicesCurrent per Device
For each device use this formula: This column X This column = Current per number of devices.
SK-5208 Fire Panel (Current draw
from battery)
Panel Accessories
SK-5217 Zone Expander(2 max.)
5824 Serial/Parallel Interface
Gateway Module
5220 Direct Connect
SK-5235 Annunciator(6 max.)
SK-5280 Status Display Module(8 max.)
ATotal System Current
Smoke Detectors
BSmoke Detector CurrentmAmA
Notification Appliances
CNotification Appliances Current
Additional Devices
DAdditional Devices CurrentmA
ETotal current ratings of all devices in system (line A + line B + C +D)mAmA
FTotal current ratings converted to amperes (line E x .001):AA
GNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
HMultiply lines F and G.Total standby AHAH
IAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
JMultiply lines F and I.Total alarm AH
K
*Add lines H and J.
1
(1 max.)
Standby:140 mA140 mA
Alarm:**550 mA550 mA
Standby:60 mAmA
Alarm:150 mAmA
Standby:45 mAmA
Alarm:45 mAmA
Standby:15 mAmA
Alarm:15 mAmA
Standby:30 mAmA
Alarm:50 mAmA
Relay
(max.)
Standby:10 mAmA
Alarm:80 mAmA
Per output 100 mAmA
Max. 700 mA
Total ampere
hours required
Standby
Current
AH
Alarm
Current
mA
mA
mA
AH
*Use next size battery with capacity greater than required.
**The SK-5208 and SK-5217 limits alarm current to 95mA per zone. The SK-5208 alarm current includes
3-5
Page 16
Control Panel Installation 151204
10% of zones in alarm, but in no case less then three zones per UL864
3.6.3Maximum Battery Standby Load
Table 3-3 shows the maximum battery standby load for the SK-5208 based on 24 and 60 hours of standby. The
standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2) must be less than the
number shown in Table 3-3 for the battery size used and standby hours required.
Batteries larger then 18 AH will not fit into the SK-5208 cabinet and must be housed in the RBB remote battery
box cabinet. See Section 3.8 for battery installation.
Table 3-3: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH270 mA105 mA
12 AH475 mA190 mA
18 AH685 mA270 mA
35 AH1.1 A450 mA
*Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Tab le 3-3. If you use a battery too small
for the installation, the system could overload the battery resulting in the installa tion havi ng less than the required 24
hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for your installation.
3.7AC Wiring
The Model SK-5208 power supply delivers 24 VDC at 6A for smoke detector power, notification device power,
and accessory power. Figure 3-3 shows the AC connections to the SK-5208 control panel.
Figure 3-3 AC Wiring
3-6
Page 17
Model SK-5208 Installation Manual151204
Battery Jumper
(P/N 140694)
Shipped With Panel
RED
Black
UL Listed 12VDC
UL Listed 12VDC
Control Panel
Battery #2
Battery #1
Battery Gell Cell
Battery Gell Cell
Note: Replace batteries
every 5 years.
Warning
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected before attempting
to connect the Model SK-5208 control panel. Do NOT apply power to this panel until all accessories are properly
connected.
Note: Note: All conduit and wiring connected to the SK-5208 must meet the applicable National Electric Code,
NFPA Standards, state, and local building code requirements. In all cases, the authority having jurisdiction takes precedence.
3.8Backup Batteries
The control panel battery charge capacity is 7.0 to 35.0 AH. Use 12V batteries of the same AH rating. Determine
the correct AH rating as per your current load calculation (see 3.6.2).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
Batteries larger than 18 AH (not to exceed 35 AH) use the RBB Remote Battery Box. It is recommended that you
replace the batteries every five years. The following steps and diagram explain how to connect the batteries.
1.Connect the black wire to the negative (-) side of battery #1.
2.Connect the jumper wire provided (P/N 140694) from the positive (+) side of battery #1 to the negative side
of battery #2.
3.Connect the red wire to the positive (+) side of battery #2
3-7
Page 18
Control Panel Installation 151204
Caution
Apply AC power before connecting the batteries to the power supply to prevent arcing on battery terminals.
Note: The total current draw on smoke power, accessory power, and notification device outputs must not exceed
6A.
3.9Terminal Strip Description
The terminal strips on the PC board are non-removable. Table 3-4 lists the functions of each terminal. See
Section 3.4 for the board layout.
Table 3-4: Terminal Descriptions
Function
Zone 1 input.
Zone 2 input
Ground9GND
Zone 3 input10Z3Zone input Class B (Style B). Refer to Section 3.11.2.
Power (Zone 3 & 4)11PWR
Zone 4 input12Z4
Zone 5 input13Z5
Smoke Power14PWR
Zone 6 input15Z6
Zone 7 input16Z7
Smoke Power17PWR
Zone 8 input18Z8
Zone9 input19Z9
Smoke Power20PWR
Zone 10 input21Z10
Ground22GND
AC Power Connections
SBUS Connections
Terminal
Number
1A
2B
3C
4D
5A
6B
7C
8D
23B
24Earth
25W
26GNDUsed to connect SK-5217 Zone Expanders and 5280
27+24DC
28A
29B
Te rmina l La belComments
Zone 1 input Class A (Style D) or Class B (Style B). See
Section 3.11 for wiring configurations.
Z1
Zone 2 input Class A (Style D) or Class B (Style B). See
Section 3.11 for wiring configurations.
Z2
Power Limited at 100mA. Voltage 27.4 VDC.
Status Display Modules to the control panel. Accessory
Power (terminals 26 and 27) provides 1 Amp total
current.
3-8
Page 19
Model SK-5208 Installation Manual151204
Table 3-4: Terminal Descriptions
Function
Remote Annunciator
Connections
Notification Appliance
Circuit 4
Notification Appliance
Circuit 3
Notification Appliance
Circuit 2
Notification Appliance
Circuit 1
Auxiliary Relay 4
Auxiliary Relay 3
Auxiliary Relay 2
Auxiliary Relay 1
Telco Line 2
Telco Line 1
Terminal
Number
30SKIUsed to connect 5235 remote annunciators to the control
31SKO
32PWR
33GND
34+
35_
36+
37_
38+
39_
40+
41_
42NORelay contacts are rated at 2.5 A, 24 VDC/24VAC
43COM
44NC
45NO
46COM
47NC
48NO
49COM
50NC
51NO
52COM
53NC
54TIP
55RING
56TIP
57RING
58TIP
59RING
60TIP
61RING
Te rmina l La belComments
panel.
NAC4
3 Amp maximum per circuit. Voltage 27.4 VDC, 1.5
Ohms Maximum.
Note:Total control panel current is 6 Amps.
NAC3
NAC2
NAC1
(inductive rating). 5A, 24 VDC/24 VAC (resistive).
Connect to power limited source only.
P2
T2
P1
T1
Telephone line 2 connectio n te rminals (see Section 3.10
for wiring diagram).
Telephone line 1 connectio n te rminals (see Section 3.10
for wiring diagram).
3-9
Page 20
Control Panel Installation 151204
Supervised
3.10 Telephone Line Connection
The SK-5208 connects to two separate telephone lines to report data to the central station. An RJ31X jack should
be installed by the telephone company for each line. Figure 3-4 shows how to wire the telephone line
interconnect cords (not provided) to the SK-5208.
Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together
with initiation or notification device wires.
Figure 3-4 Telephone Line Connection
The letter designator on the phone input indicates whether it is the Telco or House side of the phone circuit. For
example terminals 60 and 61 are labeled T1, T = Telco side of the phone circuit and terminals 58 and 59 are
labeled P1, P = Premise (House) side of the phone circuit.
The SK-5208 has built-in dual phone line monitors. These circuits will detect any fault in the phone lines by
monitoring the DC voltage present on the lines. If phone line voltage drops below 3 VDC and is not corrected
within approximately 60 seconds, an audible trouble signal will sound and the panel will report a line fault
trouble over the remaining phone line.
A situation could occur where both phone lines appear to be good, but the dialer cannot get through to the central
station on the first line. In this case, the SK-5208 will switch phone lines and attempt the call again using the
second line. Make sure the phone lines are programmed properly (see Section 4).
Note: To comply with industry standards, this product is equipped with line seizure. Any time the system’s dialer
needs to communicate with the central station, it will not be possible to use any telephones that are on the
same line(s) as the system. Normally, this condition will last approximately one minute, but under adverse
telephone circuit conditions, could last for as long as 15 minutes.
3.11Detector Installation
3.11.1Class A (Style D) Zones
Zones 1 and 2 may be selected through programming as Class A (Style D) zones (see Section 4.2.2 for zone style
programming). See Section 3.11.2 for Class B (Style B) configuration.
Each class A zone is a four-wire circuit that allows an alarm to be detected even after a single open or ground
fault occurs. When a single open or ground fault occurs, the audible trouble signal will sound and the SK-5208
will report the trouble to the central station or remote station (if programmed to report troubles). If reporting to a
remote station troubles may be transmitted to a secondary location.
Figure 3-5 shows how to wire a Class A (Style D) circuit. No end-of-line (EOL) resistors are needed for these
3-10
Page 21
Model SK-5208 Installation Manual151204
Supervised
Power Limited
Supervised
Power Limited
4.7 k EOL
UL Listed
Model 7628
Note: Zones 1 and 2 can be
configured as either Class A
or Class B. See also Section
3.11.1.
zones. These zones must be wired using normally open contacts.
Figure 3-5 Class A (Style D) Supervised Fire Circuit
Maximum voltage:17.5 to 28 VDC Full Wave Rectified
Circuit Current:95 mA
Maximum circuit Resistance:50 ohms
3.11.2 Class B (Style B) Zones
Zones 3 through 10 are Class B (Style B) only fire zones. Zones 1 & 2 may also be programmed as Class A
(Style D) or Class B (Style B), see Section 4.2.2 for zone 1 & 2 zone programming.
Each Class B zone consists of a two-wire circuit that will detect the occurrence of an open in the circuit, but may
not be able to detect an alarm after such an occurrence. The detection of an open will cause the audible trouble
signal to sound and the SK-5208 will report the trouble to the central or remote station (if programmed to do so).
Figure 3-6 shows how to wire a Class B (Style B) circuit. One side of each Class B circuit connects to a zone
input terminal and the other side of each circuit connects to Smoke power. For each circuit, use a 4.7K-ohm EOL
resistor wired in parallel with the normally open contact farthest from the panel.
Figure 3-6 Model SK-5208 Class B (Style B) Circuits
3-11
Page 22
Control Panel Installation 151204
Supervised
Power Limited
Maximum circuit Resistance - 50 ohms
Maximum Total alarm current for all Class B (Style B) zones - 1 A
Maximum Standby Current per Zone:3.0 mA
Maximum Alarm Current per Zone:95 mA
3.11.3Four-Wire Smoke Detector Connection
Figure 3-7 illustrates how UL listed four-wire smoke detectors must be connected to Class B (Style B) zones.
When wiring a four-wire smoke detector to the Class B (Style B) zones, you must use a Power Supervision Unit,
such as Silent Knight’s 160150.
Note: Mount the PAM-2 and the end-of-line resistor at the last device on the circuit.
Figure 3-7 Four-Wire Smoke Detector Wiring
See Appendix A for a list of four-wire smoke detectors that may be used with the SK-5208.
3-12
Page 23
Model SK-5208 Installation Manual151204
–
+
–
+
Silent Knight
SLK-24F 2-wire detector
with HSB-224 base
4.7 k
UL Listed EOL
Model 7628
Supervised
Power Limited
3.11.4Two-Wire Smoke Detector Connection
Figure 3-8 shows how to connect two-wire smoke detectors to Class B (Style B) zones.
See Appendix A for a list of two-wire smoke detectors that may be used with the SK-5208.
Note: Two-wire detectors can be configured for Enhanced Mode. Enhanced mode is smoke verification for zones
3.12 Supervised Notification Appliance Outputs
Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together
The SK-5208 provides four Class B (Style Y) supervised notification circuit outputs to annunciate alarm
conditions. For proper operation, you must use polarized sounding devices with a 4.7k ohm end-of-line resistor
Figure 3-8 Two-Wire Smoke Detector Wiring
with 2-wire detectors and contact type devices, such as pull stations, used on the same circuit. If the alarm
current is greater than 78 mA, the smoke verification cycle will not occur. See Section 4.2.1 Verify Options
under the Zone Options Menu to program initiation circuits for enhanced mode.
with notification circuit wires.
3-13
Page 24
Control Panel Installation 151204
Supervised
Power Limited
4.7 k
UL Listed EOL
Model 7628
3 Amps Max. per circuit full
wave rectified, 27.5 VDC, 1.5
Ohms Maximum.
on each circuit. Figure 3-9 shows how to connect the notification circuits to the SK-5208.
3 Amp maximum current draw from any single NAC output (not to exceed a total current draw of 6 amps for the
control panel). See Appendix A for a list of the UL notification appliances that can be used with the SK-5208.
Contact Silent Knight if you have any questions about compatible notification circui ts.
All circuit are regulated unless used for releasing service in which case they are considered special applications.
See Section 5.5 for details on releasing.
The SK-5208 provides four programmable auxiliary relay outputs. Relays can be programmed to activate for the
following conditions, either for all zones or by individual zone: pre-alarm (not acceptable for NFPA 72 Central
Station), fire alarm, auxiliary alarm, alarm by zone, and system or circuit troubles (loss of AC, low battery, failed
to communicate, phone line troubles, fire drills, and notification circuit troubles).
Refer to the SK-5208 programming manual for more information. Figure 3-10 shows the relay contact
connections using a door holder application as an example.
Note: Relays programmed as “Trouble” will be active during normal state and deactivated during a trouble con-
dition.
Figure 3-10 Auxiliary Relays
3.14Accessory Devices
The section describes how to install the SK-5235 Remote Annunciato r, SK-5217 Zone Expander, the 5824
Serial/Parallel Printer Module, and the SK-5280 Status Display Module. All circuits are 24 VDC regulated.
All S-Bus devices are Style 1 Class B as per NFPA 72.
3.14.1Setting ID Codes
Before installing the SK-5235, SK-5217, 5824 or SK-5280, you must first set their identification codes. Each
device must be given its own identification code. For example: each SK-5235 needs a unique ID code, but a SK5235 can have the same ID code as a
SK-5217. Each type of device has it’s own device type programmed into it enabling the control panel to
distinguish between the different devices.
On the back of each device is a small 4-position dip switch used to set the ID code. Use the chart below to
3-15
Page 26
Control Panel Installation 151204
determine the dip switch positions for each possible ID code.
The SK-5235 performs all system operation. It also provides trouble and alarm information and can be used for
programming. The control panel can support up to six SK-5235 Remote Annunciators.
Upon initial power up, the address of each SK-5235 is displayed on the LCD. (Annunciators with address 0 will
not be supervised.)
3.14.2.1 Mounting the SK-5235 Remote Annunciator
The SK-5235 Remote Annunciators must be mounted on a dual gang electrical box.
To mount the annunciator:
1.Remove the rear mounting plate by inserting a #4 flat blade screwdriver into the slots on the bottom edge of
the annunciator. See Figure 3-11. Gently turn the screwdriver until the mounting plate pulls away from the
frame.
Figure 3-11 Rear Mounting Plate Removal
3-16
Page 27
Model SK-5208 Installation Manual151204
ID DIP switches
Supervised
Power Limited
Class B
2.Secure it to the wall using #6 or #8 screws. The mounting plate should be oriented so that the word TOP is
toward the top of the plate and facing you. A square hole is provided in the mounting plate to run the wiring
to the annunciator.
3.When all of the wires have been connected to the annunciator , set the top of the annunciator over the tabs on
the top of the mounting plate. Make sure the wires do not get pinched between the frame and the mounting
plate. Press each corner of the bottom side onto the annunciator mounting plate until you hear it click. You
may have to gently squeeze the annunciator (top to bottom) to align it while snapping the bottom edge into
place.
3.14.2.2 Wiring the SK-5235
Follow these steps to properly wire the SK-5235 to the control panel.
1.Remove power from the control panel.
2.Wire the SK-5235s as shown in Figure 3-12.
3.Set the ID number. See Table 3-5.
Note: The ID number of 7 is reserved for the built-in touchpad on the SK
4.Reapply power the control panel.
When the annunciator powers up, it will display its ID code and current status of the panel.
Figure 3-12 Model SK-5235 Connection
-5208.
Note: Each 5235 touchpad can be individually supervised. See Section 4.2.2 for programming touchpads as su-
pervised.
3-17
Page 28
Control Panel Installation 151204
Alarm Outputs
Trouble Outputs
ID Number
DIP Switch
SBUS Connector
4 On-board Relays
Relay Rating
2.5A @ 30 VDC/120 VAC
1/4” spacing must be maintained between power limited
& non-power limited wiring
3.14.3Model SK-5280 Status Display Module
The Model SK-5280 Status Display module provides outputs and control functions for remote annunciation of
alarm, trouble, and supervisories for each zone.The system can supervise up to eight SK-5280 Status Display
Modules.
Note: The driver outputs are non-supervised. Rel a ys must be connected to power limited sources only.
Figure 3-13 Model 5280 Board Layout
The SK-5280 has 1 connector which has 10 outputs for alarms and 10 outputs for trouble annunciation. These
outputs are active low. Each output can provide up to 100 mA of current, with a total limitation of 700 mA.
The module has 4 normally open non-dedicated relays that can be wired to be active with any of the outputs.
Wire the SK-5280 as shown in Figure 3-14. Maintain a physical separation of one-half inch or more between
field wires and connection points to prevent damage from transients.
Note: SILENCE does not affect SK-5280 outputs. To reset a SK-5280 output, the alarm or trouble condition must
be restored.
The SK-5280 can be used to interface to LED annunciator.
The SK-5280 can be programmed to indicate alarms and trouble status for; zones 1 - 10, zones 11 - 20, zones 21
3-18
Page 29
Model SK-5208 Installation Manual151204
Control
Panel
5280
Supervised
Power Limited
Class B
- 30, or system status outputs. See Section 4.2.11.
Figure 3-14 Model SK-5280 Connection to the Control Panel
3.14.3.1 Mounting the SK-5280
The SK-5280 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet.
Mounting the SK-5280 into SK-5208 Cabinet
Follow these steps to properly mount the SK-5280 into the SK-5208 cabinet:
1.Remove power from the control panel.
2.Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-15.
Figure 3-15 Installing the 5280 Into the 5208 Cabinet
3-19
Page 30
Control Panel Installation 151204
Mounting
Holes
Mounting
Holes
3.Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
4.Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for information on
setting ID numbers.
5.Reconnect power to the control panel.
Mounting the SK-5280 into the SK-2190 Accessory Cabinet.
Follow these steps to properly mount the SK-5280 into the SK-2190 cabinet:
1.Mount the remote cabinet using the cabinet mounting holes. See Figure 3-16.
Refer to Section 3.5 for proper cabinet mounting procedures.
2.Remove power from the control panel.
3.Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-16.
Figure 3-16 Model SK-5280 Remote Installation
4.Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
5.Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for information on
setting ID numbers.
6.Reconnect power to the control panel.
3.14.3.2 Wiring Relays
The four on-board relays can be triggered by the active low outputs. For example, the alarm outputs can all be
wired to relay 3 and the trouble outputs can be wired to relay 4
(see Figure 3-17).
3-20
Page 31
Model SK-5208 Installation Manual151204
Relay Rating
2.5A @ 30 VDC/120 VAC
C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and 4 respectively.
Figure 3-17 Relay Wiring on the SK-5280
Note: Figure 3-17 uses A7 and T7 to activate relays 3 and 4 as an example. However, any of the outputs can be
used to trip any of the relays.
3.14.3.3 Wiring LEDs to Outputs
The outputs (A1-A10 and T1-T10) can be used to operate LEDs used in a remote annunciator (see Figure 3-18).
Outputs A1-A10 are alarm outputs for the zones corresponding to those outputs. For example, if the SK-5280 is
programmed to output for zones 11-20, then outputs A1-A10 will correspond with zones 11 through 20.
Outputs T1-T10 are trouble outputs for the zones corresponding to those outputs. for example, if the SK-5280 is
programmed to output for zones 21-30, then outputs T1-T10 will correspond with zones 21-30.
Figure 3-18 LED Wiring on the SK-5280
3-21
Page 32
Control Panel Installation 151204
Control Panel
Supervised
Power Limited
SK-5217
Class B
3.14.4Model SK-5217 Zone Expander Installation
The Model SK-5217 provides the SK-5208 with ten additional Class B (style B) zones. The SK-5217 connects to
the SK-5208 control panel via the SBUS as shown in Figure 3-19.
Figure 3-19 SBUS Connections
3.14.4.1 Zone Inputs
Figure 3-20 and Figure 3-21 shows how to wire detectors to the SK-5217. Use a 4.7k end of line resistor for each
Class B circuit. The EOL must be wired in parallel with the normally open contact farthest from the panel. See
Appendix A for a list of the smoke detectors that can be used with the SK-5217.
Maximum circuit Resistance - 50 ohms
Maximum Total alarm current for all class B (style A) zones - 1 A
Maximum Standby Current per Zone:3.0 mA
Maximum Alarm Current per Zone:95 mA
3-22
Page 33
Model SK-5208 Installation Manual151204
Device ID Dip Switches
Supervised
Power Limited
4.7k
UL Listed
EOL Resistor
Model 7628
Voltage:17.5 to 28 VDC
Figure 3-20 Model SK-5217 Two-wire Detectors
Figure 3-21 4-Wire Detector Connections
3-23
Page 34
Control Panel Installation 151204
3.14.4.2 Mounting Instructions
The SK-5217 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet.
Mounting the SK-5217 into SK-5208 Cabinet
Follow these steps to properly mount the SK-5217 zone expander into the SK-5208 cabinet:
1.Remove power from the control panel.
2.Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-22.
Figure 3-22 Installing the SK-5217 Into the SK-5208 Cabinet
3.Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
4.Wire the zone inputs to the zone expander as shown in Figure 3-20.
5.Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6.Reconnect power to the control panel.
Mounting the SK-5217 into the SK-2190 Accessory Cabinet.
Follow these steps to properly mount the SK-5217 zone expander into the SK-2190 cabinet:
1.Mount the remote cabinet using the cabinet mounting holes. See Figure 3-23.
Refer to Section 3.5 for proper cabinet mounting procedures.
2.Remove power from the control panel.
3-24
Page 35
Model SK-5208 Installation Manual151204
Mounting
Holes
Mounting
Holes
3.Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23.
Figure 3-23 Model SK-5217 Remote Installation
4.Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
5.Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6.Wire the zone inputs to the zone expander as shown in Figure 3-20.
3.14.5Model 5824 Installation Instructions
The Model 5824 provides the 5208 with the ability to communicate to a serial or parallel printer to print the event
log. You can use one 5824 on the 5208. The 5824 is for ancillary use only.
3.14.5.1 Mounting the 5824 Module
The 5824 comes in a plastic enclosure, follow these steps to mount the 5824’s plastic enclosure:
1.Remove the 5824’s cover. Use a small screw driver if necessary.
3-25
Page 36
Control Panel Installation 151204
Snap
Base
Retaining Tabs
Mounting Holes
Mounting Holes
Supervised
Power Limited
5824
Control
Panel
2.Remove the 5824 circuit board from the base by pushing outward on the base snap retaining tabs and lifting
the circuit board out.
Figure 1: 5824 Circuit Board And Plastic Base
3.Mount the plastic base.
4.Replace the circuit board in the plastic base.
Note: It may be necessary to connect the wiring to the circuit board before the board is replaced in the base. See
5.Connect the 5824 to the 5208.
6.Set the device ID (see Section 3.14.1). See also Figure 3-25 for ID selector switch location.
3.14.5.2 5824 SBUS Connections
Figure 3-24 illustrates how the 5824 connects to the 5208 control panel.
Section 3.14.5.2.
Figure 3-24 5824 Connections
3-26
Page 37
Model SK-5208 Installation Manual151204
Serial Port
Parallel Port
ID Selector
Switches
5824
Figure 3-25 Model 5824 Serial/Parallel Port, and ID Selector Switch location
3.15Special Applications
3.15.1Model 5220 Direct Connect Module
The 5220 Direct Connect module can be used with the SK-5208 to meet NFPA 72 standards. The 5220 requires
four connections to the SK-5208 and provides outputs for city box and polarity reversal applicatio ns. The 5220
cannot be used for sprinkler supervisory.
The 5220 provides a current that reverses polarity during alarm or removes current during a trouble condition.
Maximum voltage 27.3 VDC.
Note: The 5220 Direct Connect Module will activate for alarm and trouble conditions during a Walk Test. To
disable alarm activation during Walk Test, bypass the NAC programmed for Direct Connect before entering the Walk Test mode. To bypass the NAC, press; 10 + NAC# + * + Code (repeat to un-bypass NAC).
The Direct Connect relay will indicate trouble until the NAC is un-bypassed.
3.15.1.1 City Box Connection
This section describes how to connect the SK-5208 to a municipal fire alarm box or “city box” as required by
NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure
that contains a manually operated transmitter used to send an alarm to the municipal communication center
which houses the central operating part of the fire alarm system.
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box conn ection:
1.Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2.Wire the 5220 to the SK-5208 as shown in Figure 3-26. This drawing also shows how to connect the city box
coil to terminals 3 and 4 on the 5220.
3-27
Page 38
Control Panel Installation 151204
5220
Control
Supervised for
Opens and Ground Faults
City Box
Coil Resistance
14.5
Panel
3.Program NAC #4 to be direct connect from the NAC Options menu. Relay #4 will automatically be configured to indicate system troubles.
Note: It is not possible to reset the remote indication until you clear the condition and reset the SK-5208.
Figure 3-26 City Box Connection
3.15.1.2 NFPA 72 Polarity Reversal
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote
site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the
condition is cleared and the SK-5208 panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
To install the 5220 for polarity reversal, follo w the steps below:
1.Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2.Wire the 5220 to the SK-5208 using the four-wire pigtail provided as shown in Figure 3-27 (next page). This
diagram also shows how to connect the 5220 to the remote indicator.
3.Program one of the notification circuits to be Direct Connect (Figure 3-27 uses NAC 4 and Relay 4). The
relay and NAC circuits are paired when selected as direct connect. For example, if NAC 4 is programmed as
Direct Connect then relay 4 used for the trouble output. Do not program the NAC for Silence or Supervision
(NACs with EOL).
3-28
Page 39
Model SK-5208 Installation Manual151204
All Other Wires
Trouble Contacts Supervised
For Opens and Ground Faults
Supervised, Power Limited
Intended for connection to a polarity
reversal circuit of a remote station
receiving unit having compatible ratings.
4.If necessary, adjust circuit current using potentiometer R10 on the 5220 board. Normal circuit current is 4to-8 mA with a 1k ohm remote station protected premise unit. Maximum circuit resistance is 3k ohm.
Figure 3-27 Polarity Reversal Connect io n
3.15.2Keltron 95M3158 Tones Transmitter Module
This section of the manual shows the specific connections you will make when wiring the SK-5208 to the
Keltron 95M3158 Tones Transmitter Module (3158). Refer to the installation sheet shipped with the 95M3158
for complete information. (Note: The 3158 is not available from Silent Knight.)
Note: The 3158 Keltron Module must be mounted within 3 feet of the control panel and all wiring must be run in
conduit. The Keltron Module shall be enclosed in the TBX1 enclosure.
1.Wire the 3158 to the SK-5208 as shown in the Figure 3-28.
2.Program NAC 4 for Direct Connect (see Section 4.2.4).
3.Program NAC 3 for Supervisory (see Section 4.2.4).
4.Program NACs 3 and 4 as unsupervised (NACs With EOL). See Section 4.2.4.
3-29
Page 40
Control Panel Installation 151204
All Other Circuits Supervised
Power Limited
See Table 3-4 for electrical
ratings.
Trouble Contacts Supervised For
Opens and Ground Faults
Note: The term FACP Term. refers to terminals on the SK-5208
5.Program NAC 3 cadence as Steady (see Section 4.2.3).
Figure 3-28 Wiring the Keltron 3158 to the SK-5208
3.15.3Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote
site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the
condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current:15 mA max.
Operating Voltage:24 VDC nominal
Resistance:4 K
To install the MR-201/T for polarity reversal, follow the steps below:
3-30
Page 41
Model SK-5208 Installation Manual151204
Intended for Connection to a Polarity Reversal
Circuit of a Remote Station Receiving Unit
Having Compatible Rating.
1.Wire the MR-201/T as shown in Figure 3-29.
Figure 3-29 Wiring the MR-201/T
2.Program the NAC circuit as a non silence NAC (see Section 4.3).
3-31
Page 42
Section 4
#
Programming
The SK-5208 control panel can be programmed from either the on-board annunciator or the SK-5235 remote
annunciator. You must be in Programming Mode to program the control panel.
4.1Keypad Operation During Programming
This section describes the function of the buttons on the keypad while in program mode.
Operation/ButtonOperation/Description
Enter Step Programming
mode
Moving through
programming
Exit Step Programming Press RESET. You are prompted to save programming changes. The default is No. Press the
Down Arrow
Enter Button
Left Arrow
Right Arrow
Silence Button
Up Arrow
* Button
# Button
Press 2, 7, ENTER, followed by installer level code (the factory programmed code is 123456
or 5208). See Section 4.2.6 for user code programming information.
When you have entered programming correctly, the display will show Zone 1 Options. Press
to move to next programming option. See Table 4-4 for list of programming options
(column 1) and their menu items (column 2).
When the display shows the option you wish to program press ENTER to program items in
this option.
If you receive a trouble beep and the message TRY AGAIN appears you are not using an
installer level code.
up or down arrow to select Yes to save programming changes. Press Enter to complete the
save and return to normal operation mode.
Accepts the entered data and scrolls down to the next menu item.
Accepts the entered data and scrolls down to the next menu item.
Scrolls backwards through the programmable items list for the currently selected option.
Scrolls forward through the programmable options list or choices for an the selected item.
Enables extended programming list so you can scroll through lists of items that have multiple
components such as, Zone 1 -30. See Section 4.1.2 for an example.
Accepts the entered data and scrolls up to the next menu item.
Used as shift key when entering special characters (A, B, C, D, or E characters). See Section
4.1.1 for more information.
Clear entry.
151204
4-1
Page 43
Programming 151204
1
234
Initial Display
Display After Silence Button Pressed
Right Arrow Pressed then
Display Moves to Next Zone Number
4.1.1Special Characters
Special characters are characters used while dialing such as pause, *, #, or 2nd dial tone. Table 4-1 list the
Special characters and what they mean.
Table 4-1: Special Characters
To Enter:PressLCD Display
Pause
*
#
2nd Dial Tone
A
B
C
D
4.1.2Enabling Extended Programming List
While programming there are several programming options that have multiple comp onents that can be
programmed within that menu item, such as Zones, NAC Cadence, User Codes, Accounts, etc. However when
you scroll through these options only the first one may be displayed (see Figure 4-1). In order to view and
program subsequent items the Silence button must be pressed. This enables you to move through the other
Zones, NAC Cadence, etc.
Example:
If the Zone 1 Options is displayed (see Figure 4-1) and you want to program zone 2 options, press the
button.
Figure 4-1 Extended Programming List Access Example
The display will add brackets around the zone number (see Figure 4-1). To move to the next zone number press
the right arrow to go forward through the zone numbers or the left arrow to go backward through the zone
numbers. Press the Silence button again to remove the bracket and lock the menu on this Zone number, NAC
number, or Relay, etc.
This Feature works for the following programming options: Zone Options, NAC Cadence, User Codes,
Accounts, Line Options, and SK-5280 Options.
SILENCE
4-2
Page 44
Model SK-5208 Installation Manual151204
4.2Programming Flow
Figure 4-2 provides an overview of the programming menu flow. Figure 4-3 through Figure 4-13 illustrate the
programming flow within each option. The arrows indicate how to maneuver through programming.
Figure 4-2 Programming Overview Flow Chart
4-3
Page 45
Programming 151204
4.2.1Zone Options
Figure 4-3 illustrates, in more detail, the programming flow when in the zone options menu.
Figure 4-3 Zone Options
4-4
Page 46
Model SK-5208 Installation Manual151204
4.2.2Misc System Option
Figure 4-4 illustrates, in more detail, the programming flow when in the misc system menu.
Figure 4-4 Miscellaneous System Options
4-5
Page 47
Programming 151204
4.2.3NAC Cadence
Figure 4-5 illustrates, in more detail, the programming flow when in the NAC cadence menu.
Figure 4-5 NAC Cadence
4.2.3.1Cadence Patterns
The cadence patterns shown in Table 4-2 can be selected for NAC outputs. Each NAC can select an output
pattern. Special cadence patterns can be selected for fire drill or an auxiliary input switches used with the system.
6System Sensor Sync.Provides Synchronization for visual and audible devices.
7Wheelock Sync.
8Gentex Sync.
9Faraday Sync.
10Amseco Sync.
4-6
Page 48
Model SK-5208 Installation Manual151204
4.2.4NAC Options
Figure 4-6 illustrates, in more detail, the programming flow when in the NAC options menu.
Figure 4-6 NAC Options Programming Menu
4-7
Page 49
Programming 151204
4.2.5Relay Options
Figure 4-7 illustrates, in more detail, the programming flow when in the relay options menu.
Figure 4-7 Relay Options Programming Menu
4-8
Page 50
Model SK-5208 Installation Manual151204
4.2.6User Code
Figure 4-8 illustrates, in more detail, the programming flow when in the user code menu.
Figure 4-8 User Code Programming Menu
4-9
Page 51
Programming 151204
4.2.7Account
Figure 4-9 illustrates, in more detail, the programming flow when in the account menu.
Figure 4-9 Account Programming Menu
MustThe dialer MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to the primary
account until it exceeds the “Account Tries” value. When the dialer has exceeded the Account Tries retry limit, it will
switch to a backup account (a “Can Report” or “Yes” account, see below). If the dialer cannot report the event to any of
the backup accounts, it will return to the primary account and repeat the process until it exceeds the a total of 10 attempts.
When the Account Tries limit is exceeded, an Account Trouble condition is generated and a local trouble will sound.
YesCan Report. Selecting Y makes this a backup account for this event family. The dialer will report to this account only if it
was previously unable to report the event to a Must account.
NoNo events in this family will ever be reported to this account.
Note: CIC and Phone number can also use special characters as described in Section 4.1.1.
4-10
Page 52
Model SK-5208 Installation Manual151204
4.2.8Computer Options
Figure 4-10 illustrates, in more detail, the programming flow when in the computer options menu.
Figure 4-10 Computer Options Programming Menu
Note: Computer CIC & Phone can also use special characters as described in Section 4.1.1.
4.2.8.1Computer Code
In order to remote download to a control, the computer code programmed in the panel, and the computer code
used in the downloading software must match.
! Important!
Remote downloading can only be used for Central Station Signaling Services, if this system does not
meet Central Station Signaling requirements, this feature must be set to zero.
4-11
Page 53
Programming 151204
4.2.9Line Options
Figure 4-11 illustrates, in more detail, the programming flow when in the line options menu.
Figure 4-11 Line Options Programming Menu
Note: Line prefix can also use special characters as described in Section 4.1.1.
4-12
Page 54
Model SK-5208 Installation Manual151204
4.2.10Misc Reporting
Figure 4-12 illustrates, in more detail, the programming flow when in the miscellaneous reporting menu.
Figure 4-12 Misc Reporting Programming Menu
4-13
Page 55
Programming 151204
4.2.115280 Outputs
Figure 4-13 illustrates, in more detail, the programming flow when in the SK-5280 ou tput s menu.
Figure 4-13 5280 Outputs Programming Menu
If Zones 1-10 is selected then the SK-5280 will output when alarms and troubles occur for zones 1 through 10. If
Zones 11-20 is selected then SK-5280 will output when alarms and troubles occur for zones 11 through 20. If
Zones 21-30 is selected then the SK-5280 will output when alarms and troubles occur for zones 21-30.
If System is selected then the SK-5280 will output as shown in Table 4-3 for the following system conditions:
T1Low AC
T2Low Battery
T3Relay 1 Active
T4Relay 2 Active
T5Relay 3 Active
T6Relay 4 Active
T7NAC 1 Active
T8NAC 2 Active
T9NAC 3 Active
T10NAC 4 Active
Output For:
4-14
Page 56
Model SK-5208 Installation Manual151204
4.2.125824 Expander Options
Figure 4-14 illustrates, in more detail, the programming flow for the 5824 serial/parallel module.
Figure 4-14
Figure 4-15 5824 Programming Options Flow Chart
4-15
Page 57
Programming 151204
4.2.13DST/Clk Options
Figure 4-16 illustrates the programming flow for the Daylight Saving Time (DST) and clock source options.
Figure 4-16 DST/Clk Options Flow Chart
4-16
Page 58
Model SK-5208 Installation Manual151204
4.3Programming Options
Table 4-4 list all the programming optio ns and the item s that can be mo dified within those programming option
menus.
Note: Programming options that have a # in the Programming Options column have multiple programmable
components. See Section 4.1.2 for additional information.
Table 4-4: Programming Options
Programming
Option
Zone (1-30) #
Options
Menu ItemChoicesDefaultComments
Programmable through SKSS downloading
software. To pro gram through On-board or remote
annunciator:
1. Press * to activate.
2. Press Up or Down arrow to move through char-
Zone # Location
Zone # Type
Zone # Local
Zone # Disable
Zone # Response
Not Used
FireX
Waterflow
Supervisory
Undefined
Heat
Cold
Water
AC Delay
Ext. Reset
Ext. Silence
NoXZone will report when activated.
YesLocal Zone, will not report when activated.
NoZone cannot be bypassed.
YesXZone can be bypassed.
1 SecX
4 sec
16 sec
40 sec
acter set.
3. Press Left or Right arrow to move cursor to
desired character location.
4. Repeat steps 2 and 3 until location name is
entered.
5. Press Enter when the desired location name is
complete.
Will generate an AC Trouble for either an open or
shorted input. The report to the receiver will be
delayed until the AC Delay timer expires. (See
Section 4.2.10 for AC Delay Time programming.)
A shorted input will reset active alarms. This type
of zone is local only. No troubles will be reported
to the central station receiver.
A shorted input will silence alarms and troubles.
This type of zone is local only. No trou bles will be
reported to the central station receiver.
4-17
Page 59
Programming 151204
Table 4-4: Programming Options
Programming
Option
Zone (1-30) #
Options
Misc System
Menu ItemChoicesDefaultComments
Note:Alarm verification feature must not
NoneX
be used if the FACP is being used for releasing.
Smoke verification for zones with 2- or 4-wire
Smoke
Prealarm
Verify # Options
Zone # Auto Sil
Zone # Man Sil
Zone # NAC
Zone # Relay
Prealarm Time
Sound Prealarm
Auto Silence
Latch Supervise
Class A Zone
5235 Keypads_ _ _ _ _ _
Crossalert A
Crossalert B
Interlock A
Interlock B
Manual Release A
Manual Release B
Enhanced Smoke
NoX
Yes
No
YesX
_ _ _ _
_ _ _ _
Enter a value from 0
to 60
No
YesX5235 and on-board PZTs will sound for prealarms.
Enter a value from 0
to 60
NoXSupervisory type zones will self restore.
Yes
1
2
40 seconds
8 minutes
Class A.
detectors. Do not use any other type of device on
this circuit if Smoke Verification is selected.
Activated zone will start a prealarm timer that
counts down from a user programmed value (see
Section 4.2.2 for prealarm time programming). If
the timer reaches zero before the panel is reset, a
general alarm will then be sounded.
See Section 5.5.
See Section 5.5.
Smoke verification for zones with 2-wire detectors
and contact type devices, such as pull stations,
used on the same circuit. If the alarm current is
greater than 78 mA, the smoke verification cycle
will not occur.
Alarm sounds for this zone cannot be
automatically silenced.
Alarm sounds for this zone can be automatically
silenced.
Alarm sounds for this zone cannot be manually
silenced.
Alarm sounds for this zone can be manually
silenced.
Select the number of each NAC to operate with
this zone in alarm.
Select the number of each Relay to operate with
this zone in alarm.
Enter time duration for prealarm verification.
No on-board or 5235 remote PZT sound for
prealarms.
This feature selects the time in minutes in which
the NAC will automatically silence. 0 = no
automatic silence
Supervisory type zones must be reset after any
supervisories conditions.
Touchpad numbers that are selected here will be
supervised.
4-18
Page 60
Model SK-5208 Installation Manual151204
Table 4-4: Programming Options
Programming
Option
5217 Expanders
Misc System
(cont.)
NAC (1-4) # Cadence
NAC Options
Plex Door
Silence NAC_ _ _ _
Fire NAC1 2 3 4
Prealarm NAC_ _ _ _
Aux NAC_ _ _ _
Waterflow NAC1 2 3 4
Supervisory NAC_ _ _ _
Crossalert A NAC _ _ _ _
Release A NAC_ _ _ _
Crossalert B NAC _ _ _ _
Release B_ _ _ _
Trouble NAC_ _ _ _
Direct Conn NAC _ _ _ _
NACs With EOL1 2 3 4
Menu ItemChoicesDefaultComments
1Enables zones 11-20.
2Enables zones 21-30
NoXIf Yes is selected you are not required to enter a
Code for operator level functions, such as Reset,
Yes
ConstantAdditional cadence patterns are programmable
March Code
ANSI S-3.41 CodeAll NACs
Single Stroke BI
California Code
System Sensor Sync.
Wheelock Sync.
Gentex Sync.
Faraday Sync.
Amseco Sync.
No NACs
selected
All NACs
selected
No NACs
selected
No NACs
selected
All NACs
selected
No NACs
selected
No NACs
selected
No NACs
selected
No NACs
selected
No NACs
selected
No NACs
selected
No NACs
selected
All NACs
selected
Silence, and Display Event History.
Note: If this option is enabled, the PLEX-2
accessory must be installed on the control panel.
only through down loading software. See also
Section 4.2.3.
If number is selected that NAC may be silenced.
If number is selected that NAC will activate for
any fire alarm.
If number is selected that NAC will activate during
the prealarm timer countdown.
If number is selected that NAC will activate for
undefined, heat, cold, and water alarms.
If number is selected that NAC will activate for
waterflow alarms.
If number is selected that NAC will activate for
sprinkler supervisories.
If you have a single zone, that is programmed for
crossalarm verification, in alarm, all NAC output
select for this option will activate.
Activates during the group “A” releasing action.
This circuit would be connected to a UL listed
releasing solenoid. See Table 5-4 for compatible
solenoids.
If you have a single zone, that is programmed for
crossalarm verification, in alarm, all NAC output
select for this option will activate.
Activates during the group “B” releasing action.
This circuit would be connected to a UL listed
releasing solenoid. See Table 5-4 for compatible
solenoids.
If number is selected that NAC will activate for
any trouble condition.
for alarms when using the 5220 module for city
box or polarity reversal. Corresponding relay
number will automatically be selected.
If number is selected that NAC output must be
supervised with an 4.7 k UL listed EOL.
4-19
Page 61
Programming 151204
Table 4-4: Programming Options
Programming
Option
NAC OptionsFire Drill NAC1 2 3 4
Relay Options
User (1-10) #
Code
Menu ItemChoicesDefaultComments
Silence Relay_ _ _ _
Fire Relay1 _ _ _
Prealarm Relay_ _ _ _
Aux Relay_ _ _ _
Waterflow Relay_ _ _ _
Superv Relay_ _ _ _
Crossalert A Relay _ _ _ _
Release A Relay_ _ _ _
Crossalert B Relay _ _ _ _
Release B Relay_ _ _ _
Trouble Relay_ _ _ 4X
Fire Drill Relay1 _ _ _
AC Trbl_ _ _ _
Installers
Code # Type
User # Code
Operators1111
Not Used
Enter 3 to 6 digit
number
All NACs
selected
No Relays
selected
Relay 1
selected
No Relays
selected
No Relays
selected
No Relays
selected
No Relays
selected
No Relays
selected
No Relays
selected
No Relays
selected
No Relays
selected
Relay 1
selected
No Relays
selected
5208 and
123456
If number is selected that NAC will activate during
a fire drill.
If a relay is selected, that relay can be silenced for
Trouble and Supervisory conditions only. (This
includes relays programmed for AC Trbl.)
If a relay is selected, that relay will activate for fire
alarm conditions.
If a relay is selected, that relay will activate for
prealarm conditions.
If a relay is selected, that relay will activate for
Auxiliary conditions.
If a relay is selected, that relay will activate for
waterflow conditions.
If a relay is selected, that relay will activate for
supervisory conditions.
If a relay is selected, that relay will activate for
crossalarm conditions.
If selected will activate for releasing group “A”.
If a relay is selected, that relay will activate for
crossalarm conditions.
If selected will activate for releasing group “B”.
Relay will be activated when no troubles exist and
will deactivate when a trouble condition occurs.
If a relay is selected, that relay will activate for fire
drills.
If a relay is selected, that relay will be activated
when AC is normal and will deactivate when a
Low AC condition exists.
Enter any value from 001 to 999999.
4-20
Page 62
Model SK-5208 Installation Manual151204
Table 4-4: Programming Options
Programming
Option
Account (1-4) #
Computer
Options
Menu ItemChoicesDefaultComments
1: 105208
Account <#> #
CIC <#> #Enter up to 8 digits
Phone <#> #Enter up to 16 digitsSee Section 4.1.1 for special characters.
Account # Format
Account # Tries1 to 53
Report # Alarm
Report # Restore
Report # Trouble
Report # Test
Computer Account Enter 6-digit number 505208
Computer CICUp to 8 digits.
Computer Phoneup to 16 digitsSee Section 4.1.1 for special characters.
Enter a 6-digits
number
SIA8X
SIA20
Contact ID
SK4/2 1400
3/1 1400
3/1 2300
Enter any value from 000001 to 999999. Account
numbers with less than 6 digits must use leading
zeros. For example, if the code 321 is used, it must
be entered as 000321.
Carrier Identification Code is the prefix that needs
to be dialed before a phone number to access a
particular long distance carrier. Use special
characters to add pauses, #, *, and “2nd dial tone”
characters into the phone number. See Section
4.1.1 for special characters.
Do not report sprinkler supervisory, system
troubles, zone troubles, zone bypasses, and zone
restores.
Can report sprinkler supervisory, system troubles,
zone troubles, zone bypasses, and zone restores.
Must report sprinkler supervisory, system troubles,
zone troubles, zone bypasses, and zone restores.
Do not report manual test, auto test, downloading
pass, downloading fail, data lest, and walk test.
Can report manual test, auto test, downloading
pass, downloading fail, data lest, and walk test.
Must report manual test, auto test, downloading
pass, downloading fail, data lest, and walk test.
Enter any value from 000001 to 999999. Account
numbers with less than 6 digits must use leading
zeros. For example, if the code 321 is used, it must
be entered as 000321.
Carrier Identification Code is the prefix that needs
to be dialed before a phone number to access a
particular long distance carrier. Use special
characters to add pauses, #, *, and “look for
second dial tone” characters into the phone
number. See Section 4.1.1 for special ch aracters.
4-21
Page 63
Programming 151204
Table 4-4: Programming Options
Programming
Option
Computer
Options
Line (1-2) #
Options
Misc Reporting
Menu ItemChoicesDefaultComments
The computer code must match the computer code
Computer Code1 to 6 digits0
Not UsedXThis disables the phone line.
DTMF/USA Rotary
USA Rotary Only
Line # Dial Type
Line # GS
Line # Rings0 - 15
Line # Ans Mach
Line # PrefixUp to 8 digitsSee Section 4.1.1 for special characters.
Test Time00:00 - 23:5912:00
Te st Interval
AC Delay0-30 Hours2
Report Walk Test
DTMF OnlyAttempts 1 through 10 will be DTMF only.
DTMF/Euro Rotary
Euro Rotary Only
NoXYes enables Ground Start phone functions. A
Yes
Line 1: 2
Line 2: 10
NoX
Yes
Every 4Selects the period to which the system performs an
Every 6
Every 12
Every 24X
NoX
By Zone
in the remote downloading computer in order to
perform a remote download. See also Section
4.2.8.1.
Attempts 1 through 6 will be DTMF, then the
dialer will alternate between Rotary and DTMF for
attempts 7 through 10, Rotary Make/Break ratio is
40/60.
Attempts 1 through 10 will be Rotary only, with a
Make/Break ratio of 40/60.
Attempts 1 through 6 will be DTMF, then the
dialer will alternate between Rotary and DTMF for
attempts 7 through 10, Rotary Make/Break ratio
33/67.
Attempts 1 through 10 will be Rotary only, with a
Make/Break ratio of 33/67.
ground start relay (Model 5211) is required if this
feature is enabled (see Figure 3-2).
Number of rings before the panel will answer an
incoming telephone call.
This feature is used in installations where an
answering machine is on the same phone line that
the control panel is on. The answering machine
may interfere with a computer download.
When enabled (Y es) the computer calls the control
panel and the phone line rings twice, hangs up and
calls again (within 10 to 60 seconds). When the
control panel see two more rings on the phone line
it will answer and acknowledge the calling
computer.
Selects the time of day the control will send an
automatic test signal to a central station receiver.
Automatic Self Test, keyed off the Test Time.
Selects the delay time (in hours) before the control
will report an AC power loss to the central station.
No zone information will be reported just test
begin and test end.
Test begin, test end, and all event s in betwee n will
be reported to central station.
0 - 9
* Event code for 3/1
and 4/2 reporting
formats.
Not UsedX
Zones 1_10
Zones 11_20
Zones 21_30
System
YesXIf yes then all events are sent to the printer.
No
YesXIf yes is selected then data is sent to the serial port.
No
9600XSelect the Baud rate at which your printer requires
19.2K
75
110
134.5
150
300
600
1200
2000
2400
4800
1800
8XSelect the number of data bits that your printer
5
6
7
1XSelect the number of stop bits that your printer
2
0
0
Alarms for Fire, Waterflow, Undefined, Heat,
Cold, and Water events.
Alarms restores for Fire, Waterflow, Undefined,
Heat, Cold, and Water events.
Restore reports for Troubles, Supervisories, and
unbypasses. The only exceptions are the restores
listed as alarm restores.
All system and zone troubles, and zone/NAC
bypasses, and NACs troubles.
Sets the serial bus address for the 5824. Use a 0 to
disable this feature.
Selects the number of seconds the printer can be
off line before a trouble is generated.
If no is selected then data is sent to the parallel
port.
to communicate properly. Consult installation
manual for the printer you are using.
requires for proper communication. Consult
installation manual for your printer.
requires for proper communication. Consult
installation manual for your printer.
4-23
Page 65
Programming 151204
Table 4-4: Programming Options
Programming
Option
5824 ExpanderParity
DST/Clk
Options
* This option is not recognized by the panel until January 1, 2007. Before January 1, 2007, the panel will recognize the values
described above in the Auto DST Adjust option.
Menu ItemChoicesDefaultComments
NoneXSelect the Parity that your printer requires for
Even
Odd
60 HzX
Clock Source
Auto DST Adjust
DST Start (Wk)*
DST Start (Mo)*Jan – DecMar
DST End (Wk)*
DST End (Mo)*Jan – DecNov
50 Hz
Internal
NoXNo automatic clock adjust for Daylight Saving.
Yes
1st SundaySetting determines the week of the month in which
2nd SundayX
3rd Sunday
4th Sunday
Last Sunday
1st SundayXSetting determines the week of the month in which
2nd Sunday
3rd Sunday
4th Sunday
Last Sunday
proper communication. Consult installation
manual for your printer.
The panel’s AC lin e frequency is selectable for 60,
50 Hz, or Internal. AC Frequency feature dictates
how the control panel will calculate time based on
the AC line frequency used in the installation site.
The “Internal” option can be used in areas where
the AC line frequency is not dependable and you
want the panel to calculate time from the internal
crystal. The internal crystal is not as accura te as
the AC power source and either 60 Hz or 50 Hz
should normally be selected. The panel defaults to
the 60 Hz. selection
Automatically changes system clock between
Daylight Saving Time (DST) and standard time.
Before January 1, 2007, the system clock will
switch to DST on the first Sunday in April at 2:00
a.m. and will revert to standard time on the last
Sunday in October at 2:00 a.m. On January 1,
2007, the system clock will be adjusted according
to the values set in the DST Start (Wk and Mo) and
DST End (Wk and Mo) options. Default values for
these fields match federal law: DST begins on the
second Sunday in March at 2:00 a.m. and reverts
to standard time on the first Sunday of November
at 2:00 a.m.
Daylight Saving Time is to start. If you always
want the change to occur on the last Sunday of the
month, select the Last Sunday option regardless of
whether there are four or five Sundays in the
month.
Setting determines the month in which Daylight
Saving Time is to end.
Daylight Saving Time is to end. If you always
want the change to occur on the last Sunday of the
month, select the Last Sunday option regardless of
whether there are four or five Sundays in the
month.
Setting determines the month in which Daylight
Saving Time is to start.
4-24
Page 66
Section 5
Normal Operation
User Operations
Enabled
Note: The key can not be removed
when in the user operations position.
Installer Key: Perform user
operations without a user
code and open panel door.
User Key: Perform user
operations without a user
code.
Operation
To operate the SK-5208 you can use either the on-board touchpad or the Model SK-5 235 Remote Annunciator.
151204
Important!Upon initial power up there is a 45 second delay before the initiation circuits become active.
The system will be ready to receive alarms once the display indicates “System Normal”
5.1Installer & User Keys
An installer key ships with the panel and an operator’s key ships with the SK-5235
(Figure 5-2). The installer key opens the panel door and can be used to perform user operations without a user
code at the panel and the SK-5235. The operator’s key can be used to perform user operations without a user
code but will not open the panel door. All installer operations require an installer code. To perform user
operations without a user code, insert and turn the key as shown in Figure 5-2. See Table 5-1 for a list of user and
installer operations.
Figure 5-1 Model SK-5235 Remote Annunciator
Figure 5-2 Keys & Key Operation
5-1
Page 67
Operation 151204
5.2On-board Touchpad and SK-5235 Operation
Basic operations for the on-board annunciator (touchpad) and SK-5235 are described in Table 5-1. If you are
using an annunciator key or the Flex Door option, you are not required to enter a code for operator level
functions.
If no keys are pressed for 4 minutes while in program mode, the system will time out and resume normal
operation.
Table 5-1: Basic Panel Operations Using the On-Board Annunciator and the SK-5235
Do This
How To
Test the system
Reset Alarms
Clear History
Reset the Dialer
Call Computer to Up/
Download
Display History
Events
Show Status
Silence Troubles or
Alarms
Set the Date
Set the Time
Disable/Enable a
Zone
Disable/Enable NAC
Conduct a Fire Drill
Reset Detectors
Walk Test the System
Menu of Options
0 ENTER
1 ENTER or RESETReset Alarm
2 ENTERClear History
3 ENTERReset Dialer
4 ENTERCall Computer
5 ENTER
6 ENTERShow Status
7 ENTER or SILENCE Silence
8 ENTER
9 ENTERSet Time
Zone # + * Disable Zone
10 NAC # *Disable NAC
20 ENTERFire Drill
21 ENTERRst Smk Pwr
22 ENTERWalk Test
Press or to
scroll through list.
Press
* Code = any valid operator or installer code.
Display
Message
System Test
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
History Events
Enter Code
Enter Code
Enter Code
Set Date
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Press*
Enter Code
Enter Code
Enter Installer
Code
Enter Code
Enter Installer
Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
System performs a display lamp test, a
communication test, and displays the
firmware number and revision. See 5.2.1 for
an example.
Resets system.
Clears event history of all events.
Resets the dialer and aborts the cal l to central
station.
Will dial the programmed phone number for
the computer to initiate an up or download.
Displays panel history, including alarms,
supervisories, troubles, reports, time and date
changes, etc.
View exis ti ng system status. List Alarms
first, supervisories and then troubles.
Enter 8 digits for the date. For example, to set
the date 08/31/1999 enter 08311999. Press #
to clear incorrect entries.
Enter the time in 24 hour increments. For
example, 1:00 pm = 13:00.
Repeat the process to enable the zone.
Repeat the process to enable the NAC.
To End the Fi re Dr ill pres s RESE T then code.
Resets all smoke detector power.
To En d the Walk Test press REST.
To exit press ENTER or wait 15 seconds.
Comments
5.2.1View Control Panel Firmware Number and Revision
When 0 ENTER and the code is entered The system will perform a display lamp test and a communication test.
5-2
Page 68
Model SK-5208 Installation Manual151204
Control Firmware
Number
Dialer Firmware
Number
Revision
Revision
Also displays Firmware number and revision as shown in Figure 5-3.
Figure 5-3 Firmware Numbers and Revisions
5.3Acknowledge Operation
To display an event, first press the ENTER, while the event is displayed the event can be acknowledged by
pressing the ENTER button again. No code is required to acknowledge events. The status LEDs (Alarm,
Supervisory and Trouble) will flash when an un-acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory , or T rouble LED) stop flashing
and turn on steady. When viewing system status the LCD displays “Acked” for each individual event once has
been acknowledged. The control panel piezo will silence after all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been
acknowledged. Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the
history buffer will be preceded with an asterisk “*”.
5.4LED Indicators
Five light emitting diodes (LEDs) appear in the SK-5208 built in annunciator and remote annunciator. The chart
below explains the meaning of these LEDs.
Table 5-2
LEDStatusCondition
OffNormal condition
ALARM (red)
SUPERVISORY (yellow)
TROUBLE (yellow)
SILENCED (yellow)
AC (green)
OnSystem in alarm and all alarms have been acknowledged.
FlashingLED will flash when a alarm condition exists that has not been acknowledged.
OffNormal condition
OnIf a supervisory condition exist on the system.
FlashingLED will flash when a supervisory condition exists that has not been acknowledged.
OffNormal condition
OnTrouble condition exists
FlashingLED will flash when a trouble condition exists that has not been acknowledged.
OffNormal condition.
OnAlarm or trouble cond ition has been silenced but condition still exists.
OnPanel is running on AC (normal condition); standby battery fully charged.
OffPanel has lost all power.
FlashingPanel is running on battery power only or AC power only.
5-3
Page 69
Operation 151204
5.5Releasing Operation
This system can perform two types of releasing operation, cross alarm releasing, and double interlock releasing
operations. Install in accordance with NFPA 72 paragraphs 3-8.3.2.3.3 and 3-8.3.2.3.3.2.
5.5.1Cross Alarm Operation
The fire alarm control panel has two cross alert groups to select from, Cross Alert A and Cross Alert B that
accommodate releasing water systems.
When two or more zones are programmed to one of these groups then a single activation of one zone in the group
will cause a cross alert condition at the local annunciator and the pre-alert signal output for that group. (Note: the
local annunciator and the pre-alert signal will continue to sound until it is silenced or until another cross alarm
zone within the same group activates.) If a second zone in the same group activates then both will become active
alarm zones.
If the second zone is not in the same group as the first zone then the cross alert zone will remain in the cross alert
condition and the system will signal the second by how it is programmed.
The fire alarm control panel has four NAC and relay options that allow NACs and relays to be selected to
indicate the cross alert condition and assign release circuits for each group.
5.5.1.1Default NAC Settings for Releasing
When “Cross Alert A” is selected in “Zone Options” the NACs are defaulted to the following settings:
A Model 7641 EOL resistor/diode assembly is required when connecting the FACP to releasing solenoids. The
7641 allows the FACP to supervise the wiring between its NACs and the releasing solenoid.
Table 5-4: Approved Releasing Solenoids
ManufacturerPart NumberRating
Asco
T8210A10724 VDC, 16.8 W
8210G20724 VDC, 10.6 W
Figure 5-4 Solenoid Wiring Configuration
Do not mix cross alarming zones with smoke verification zones. There must be at least two automatic detection
devices in each protected space. Spacing must be reduced to 0.7 tines the linear spacing in accordance with
NFPA72. See Section 4.2.1 for zone option programming.
Figure 5-5 is an example of how cross alarming may be programmed.
Figure 5-5 Example Showing Smoke Detector Cross Alarm Application
5-5
Page 71
Operation 151204
5.5.2Double Interlock Releasing Operation
A typical double interlock releasing system would be programmed with a minimum of two zones selected for
“Cross Alert A”, one zone selected as “Man. Release A”, and one selected as “Interlock A”. Additional zones
can be selected as Cross Alert or Manual Release.
This double interlock system requires both cross alert and manual release verification zones. A single manual
release and interlock zone can be used without any cross alert zones. In this system configuration an active
manual release and the interlock zone is required to initiate the release.
Table 5-5 illustrates what will cause a Pre-alert, General Alarm, and a Release.
Table 5-5: Double Interlock Operation
InputsOutput Results
Cross Zone 1
Cross Zone 2
Manual Release A
Interlock
If no zones are selected for “Interlock” verification then the system will operate as a standard cross alarm
releasing system (see Section 5.5.1).
See Section 5.5.1.1 for default NAC settings for releasing systems.
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
Normal
Pre-Alert
Pre-Alert
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
Release and General Alarm
5.6Smoke Alarm Verification
Release and General Alarm
Release and General Alarm
Release and General Alarm
Release and General Alarm
Figure 5-6 illustrates how the Smoke Alarm Verification cycle operates.
Figure 5-6 Smoke Verification Cycle
During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
5-6
Page 72
Model SK-5208 Installation Manual151204
5.7System Testing
This section describes operation of fire drills, zone testing, and the 24-hour automatic test.
5.7.1Fire Drills
Fire drills can be run from either the on-board touchpad or the Model SK-52 35 Remote Annunciator. To initiate
a fire drill, press 20 ENTER + Code. The system will sound an alarm and report a fire test. To end the fire drill,
press
RESET + Code.
5.7.2Walk Test
The walk test is designed to be used for on-site testing only.
To enter walk test mode, press 22 ENTER
Select the following test parameters:
T est FeatureEnable or DisableComments
Use Verify:Yes or NoIf Yes is selected then this option will be enabled during
Mapped Rlys:Yes or No
Mapped NACs:Yes or No
The LCD will indicate that you are in walk test mode. When a zone is tripped, the SK-5208 will activate the bell
outputs for approximately six second and will cycle smoke power off and on for the programmed time interval.
When smoke power is restored, there is a two-second power up delay before the zone will respond to additional
test inputs.
The system will time out and resume normal operation in 30 minutes if no keys are pressed or no zones are
tripped during the walk test.
To exit walk test mode, press
RESET.
+ Installer Code.
walk test. If No is selected this option will be disabled
during walk test.
5.7.3Automatic Self Test
The Model SK-5208 lets you select the time of day and the interval that the automatic that the test signal will be
sent to the central station. See Sections 4.2.10 and 4.3 for additional information on automatic test time.
5.7.4Watchdog Circuit
During normal operation, the control microprocessor of the SK-5208 is constantly running programs to check
inputs and carry out other routine functions. If the program should ever stop running, the watchdog circuit will
automatically detect this and attempt to resume normal operation by resetting the microprocessors. Each time the
watchdog circuit initiates a reset signal, it will also sound the audible trouble signal for approximately four
seconds.
5.8Communicating with a Programming Computer
An installer at the panel site can initiate communications between the panel and a computer running the Silent
Knight Software Suite SKSS. In order for this communication to function properly both the computer (running
the software) and the control panel must have matching computer account numbers and computer access codes.
Before you program in this location you should know how your control panel will commu nicate wi th the
downloading computer, either through direct connect (RS232) or via the phone lines (Internal Modem).
5-7
Page 73
Operation 151204
Download MenuUpload Menu
5.8.1Programming From a Remote Computer Location
The panel can communicate with a Up/Downloading computer using two methods. The control panel can call the
programming computer or the programming computer can call the control panel.
The programming information for the control panel will be stored in the queue of the downloading software
SKSS P/N 5660. This data packet will have been pre-configured for the control panel that you are about to
program. SKSS is available to download on www.silentknight.com. For more information also see SKSS Installation Manual P/N 151240.
5.8.1.1Having the Control Panel Call the Remote Computer
If the panel initiates the call to a downloading computer, a phone number must be pr ogrammed in the computer
accounts area (see Section 4.2.8).
To initiate communication:
1.From the SKSS Up/Downloading software File Menu, select the download or upload menu item you want to
perform.
2.In the appropriate locations in the dialog box, enter your information.
3.When ready, select “Wait for Call” in the “Call how often” drop down list.
4.Press “OK” to stage SKSS for an Up/Download.
5.Press the 4 ENTER or the ^ up arrow until the display reads Call Computer.
6.Enter the Installer Code.
The control panel will then begin the communication process with the remote computer.
5.8.1.2Having Remote Computer Call the Control Panel
If the computer initiates the call then answering machine bypass (see Section 4.2.8) may need to be selected.
To initiate communication:
1.From the SKSS Up/Downloading software File Menu, select the download or upload menu item you want to
schedule.
2.In the appropriate locations in the dialog box, enter your selections for the following options:
File Name:To download, select the file that you want to download. To upload assign a name to the file that
will be uploaded from the panel. You can use the Browse option to select from the list of available files. If
5-8
Page 74
Model SK-5208 Installation Manual151204
To Computer
Serial Port
you do not select a name for the file, it will be automatically named with the panel model and the date and
time of the download.
For downloads, the latest saved version of the file will be sent. This means if the file you want to send is
currently open and has been changed, save it before you attempt to download.
Account
Number:Enter the panel account number.
Computer Code:Enter the code that allows access to the panel from a PC.
Phone Number:Enter the panel phone number.
Call Option:Select how often and when the call should be placed.
Answering:Select the preferred options if the phone line used by the control panel has an answering machine
installed. This feature is not used when connecting directly to a panel.
3.Click OK to begin downloading/uploading or to post the job to the Queue.
5.8.2Directly Connecting to a Programming Computer
The control panel can be up or downloaded from a computer that is directly connected to the control panel.
Note: This connection is to be used as a temporary connection and should be disconnected after programming is
completed.
To initiate communication:
1.Connect a serial cable from the control panel to the computer.
2.Make sure SKSS software is running and that the up/download task is in the queue, by selecting the Call
Option to “Wait for Call”.
3. Initiate an up/download from SKSS
The control panel will then begin the communication process with the computer.
5-9
Page 75
Section 6
Reporting
The SK-5208 can transmit information in four different formats. This section describes the four basic reporting
formats of the SK-5208 and the codes that they send to a central station receiver. Of these four formats some of
the formats offer a more specific selection for that format. For example, you can select a 3/1 format that requires
a 1400 or 2300 Hz handshake, or SIA format that can handle 8 or 20 events per call. Selecting the correct format
depends on the type of receiver that will receive calls from the SK-5208.
The SK-5208 DACT is compatible with Silent Knight Model 9800 and 9500 Digital Receivers.
6.1Reporting Formats
This section gives a description of each of the SK-5208 reporting formats. Refer to Table 6-1.
Table 6-1: Reporting Formats Descriptions
Format Name
Category
Name
3/1
4/2SK4/2 1400
SIA
Contact IDContact ID
Programming
Name
3/1 14
3/1 23
SIA8
SIA20
Old format, transmits a 3-digit account number and a 1-digit event code.
Transmissions are acknowledged at 1400 Hz.
Old format, transmits a 3-digit account number and a 1-digit event code.
Transmissions are acknowledged at 2300 Hz.
Tone burst format, transmits a 4-digit account code and 2-digit event code.
Transmissions are acknowledged at 1400 Hz.
Security Industry Association standard communication format which send a
maximum of 8 events per call.
Security Industry Association standard communication format which send a
maximum of 20 events per call. Up to a 6-digit account number.
Ademco Contact ID format. DTMF (Dual Tone Multiple Frequenc y) format. Send a
4-digit account number. Transmission is acknowledged at both 1400 and 2300 Hz.
Description
151204
6-1
Page 76
Reporting 151204
6.2Reporting Codes
Table 6-2 list the events sent by the SK-5208 and the code that is sent for that event by the type of reporting
format used.
Note: Codes under in the SK4/2 and 3/1 1400 & 2300 column are the codes programmed for 3/1 reporting for-
mats in Misc Reporting. See Section 4.2.10 for Misc. Reporting options and Table 6-3 for default 3/1 format
reporting values.
automatic test signal to a central station
receiver.
performs an Automatic Self Test, keyed off the
Test Time.
Selects the delay time (in hours) before the
control will report an AC power loss to the
central station.
No zone information will be reported just test
begin and test end.
Test begin, test end, and all events in between
will be reported to central station.
Alarms for Fire, Waterflow, Undefined, Heat,
Cold, and Water events.
Alarms restores for Fire, Waterflow,
Undefined, Heat, Cold, and Water events.
Restore reports for Troubles, Supervisories,
and unbypasses. The only exceptions are the
restores listed as alarm restores.
All system and zone troubles, and zone/NAC
bypasses, and NACs troubles.
6-5
Page 80
Section 7
Troubleshooting
This section of the manual contains information that can be used to is o late and correct installation problems
encountered in the field.
7.1System Error Messages
Table 7-1 contains a list of possible error messages along with their meani ng and possible solution.
Table 7-1: Error Messages
Error MessageDescriptionSolution
FLASH DefaultedOn power up the SK-5208 will check the flash for an
“option record”.
Earth Fault TrbThe SK-5208 has built-in earth ground fault detection that
will detect an earth ground fault connection between earth
and any panel terminal. When an earth ground fault is
detected the SK-5208 display will indicate Earth Fault
Trb.
The SK-5208 will also add two events to the history
buffer Expand Trb 38 and Earth ###. The Earth ### is a
debug event number between 0 and 255.
Key BUS TroubleThis message will display when communication is lost
between the 5235 and the control panel.
NAC # TrbThis message indicates that a short or an open is detected
on a Notification Appliance Circuit. The # indicates which
NAC has the trouble.
Remote # TrbEach 5235 can be programmed to be supervised (see
Section 4.2.2). If the SK-5208 is unable to communicate
with the 5235 it will indicate this message. # indicates the
ID number of the faulted touchpad.
5217 Trb #If the SK-5208 is unable to communicate with a 5217
expander it will display this message. The # indicates the
ID number of the expander in trouble.
5280 Trb #If the control panel is unable to communicate with a SK-
5280 Status Display Module this message will be
displayed. # indicates the ID number of the SK-5280 in
trouble.
Smk Pwr TrbSmoke power terminals 11, 14, 17, and 20 are supervised.
If the voltage between circuit ground (terminals 9, 22, 26,
33) and loop power is less than 20VDC this message will
display.
5235 Pwr TrbThe power terminal for the 5235 is supervised and a
trouble indication will occur if the voltage between circuit
ground and terminal 32 drops below 20 VDC.
If an “option record” is not found
during power up, one will be created
and the display will indicate “Flash
Defaulted” for approximately one
second.
See Section 7.2 for earth ground fault
troubleshooting procedure.
Check for a short or an open on either
the SKI or SKO terminals.
Check for a short or an open on the
indicated NAC wire run.
Check the wire connections between
the indicated touchpad and the control
panel.
Check all wire connections between
the control panel and the 5217
expander in trouble.
Check all wire connections between
the control panel and the SK-5280 in
trouble.
This may occur when the maximum
current draw for the initiation circuit
is exceeded. See Section 3.1 1 for
initiation circuit current requirements.
This may occur if the maximum
current rating (1Amp) for this circuit
is exceeded.
151204
7-1
Page 81
T roubleshooting 151204
Table 7-1: Error Messages
Error MessageDescriptionSolution
Aux Pwr TrbThe SBUS power terminal (27) is supervised and will
display this message when the voltage between SBUS
power and circuit ground drops below 20 VDC.
AC TrbThis message is displayed when the AC voltage drops
below 98 VAC.
Battery TrbThis message will be displayed when the battery voltage
drops below 20.4 VDC under load. The control panel
performs a load test every minute.
Ph Line # TrbThis message is displayed when the phone line voltage
drops below 2 VDC or can not supply a minimum of 4
mA of current. The # indicates which phone line is in
trouble.
Data LostThis event will be reported to the central station if the
reporting buffer fills. This may occur if more that 24
events need to be reported. When the report buffer is full
and additional events are added to the report buffer, the
oldest event will be overwritten and the data lost event
will be added.
Com # TrbThe SK-5208 must use alternating phone lines (according
to NFPA) when reporting auto tests and manual tests. If
the control panel can not communicate using the selected
phone line, the Com # Trb message will be displayed. The
# indicates which line had the trouble.
This may occur if the maximum
current rating (1Amp) for this circuit
is exceeded.
Check the AC power connection. This
report will be sent to the central
station after the AC delay time has
expired. See Section 4.2.10 to
program AC delay time.
Check battery connection. Verify that
the control panel has AC power.
The trouble condition will clear after
the control panel is successful in
communicating using the phone line.
7.2Earth Ground Fault Troubleshooting
An Earth Fault Trb indicates that the panel has detected a short between any terminal on the panel and earth
ground. To determine the location of the short, place a DC volt meter with ground on terminal 22 (circuit ground)
and positive on any of the screws that secure the circuit board to the cabinet (earth ground).
A typical meter reading should alternate between 0 VDC and 11.7 VDC. Any other voltage will put the panel
into Earth Fault Trb (see also Table 7-1). Remove and leave off field wiring from the panel until the meter
alternates between 0 VDC and 11.7 VDC.
When an Earth Fault is indicated at the touchpad two messages will be added to the event history buffer, Earth
Fault 38 and Earth ###. This information can be very helpful to identify where an earth ground fault exists in an
intermittent earth ground situation.
If the Earth ### is lower than 133 this typically would indicate an earth ground short to a low voltage source
(13.1 VDC or less). For example, any circuit ground terminal or zone input terminal.
If the Earth ### is higher than 134 this typically would indicate an earth ground to a higher voltage source (13.1
VDC or higher). For example, any circuit power, standby battery, phone lines, or AC power.
7-2
Page 82
Model SK-5208 Installation Manual151204
7.3Earth Fault Resistance
Table 7-2 list the earth fault resistance values for each applicable terminal on the FACP.
Table 7-2: Earth Fault Resistance Values by Terminal
Function
Zone 1 input.
Zone 2 input
Ground9GND0K
Zone 3 input10Z30K
Power (Zone 3 & 4)11PWR0K
Zone 4 input12Z40K
Zone 5 input13Z50K
Smoke Power14PWR0K
Zone 6 input15Z60K
Zone 7 input16Z70K
Smoke Power17PWR0K
Zone 8 input18Z80K
Zone9 input19Z90K
Smoke Power20PWR0K
Zone 10 input21Z100K
Ground22GND0K
This section of the manual lists devices (smoke detectors and notification appliances) that are compatible with
the SK-5208. Contact Silent Knight if you have a question about whether a device not listed here is compatible.
A.1Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop.
All supervised notification appliances used with the control panel must be polarized. The table below lists notification appliances compatible with the FACP. Appliances which can be synchronized indicate the type of sync
available in the columns marked Audio and/or Visual.
Note: Not all devices can use the Sync feature, be sure to check table below to ensure the device you have chosen
will work with this feature. Synchronization is UL listed as a single circuit operation.
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Multi Candella Horn/Strobe Ceiling Mount
Multi Candella Horn/Strobe Ceiling Mount
Multi Candella Strobe Ceiling Mount
Multi Candella Strobe Ceiling Mount
Multi Candella Horn/Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Multi Candella Strobe
Multi Candella Strobe
Horn
Strobe
Strobe
Strobe
Strobe
Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe
4-Wire Horn/Strobe
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
4-Wire Horn/Strobe High Candela
Strobe
Strobe
Strobe
Strobe
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe
Strobe
Strobe
Strobe
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe High Candela
Strobe
Strobe
Strobe High Candela
Strobe High Candela
2-Wire Low Frequency Sounder Strobe
2-Wire Low Frequency Sounder Strobe
RSSWPG-24MCCH
RSSWPR-24MCCH
RSSWP-2475W
RSSWP-2475C
RSSWP-24MCWH
ZRS-MCWH
ZRS-24MCC
ZRS-24MCCH
MB-G6-24 Motor Bell
MB-G10-24 Motor Bell
MB-G6-12 Motor Bell
MB-G10-12 Motor Bell
MIZ-24-R Mini-Horn
MT-12/24-R x
MT4-12/2zx
ZRS-MCW
MTWPR-24MCCHx
NH-12/24RxHorn
HSR
HSW
STR
STW
HNR
HNW
This section of the manual contains information about smoke detectors that are compatible with the SK-5208.
SK-5208SK-5217
Identifier
Maximum Voltage
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped-
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum
reset time of the smoke detector.
24J24J
27.4 VDC27.4 VDC
A-10
Page 93
Model SK-5208 Installation Manual151204
A.2Two-Wire Smoke Detectors
The table below lists two-wire smoke detectors that are compatible with the SK-5208 and SK-5217 zone
expander. The table is organized by manufacturer. The columns show the number of detectors per loop that can
be used.
3425 (S10)N/AS0030
3425C (S10)N/AS0030
3425CR (S10)N/AS0030
3425CRT (S10)N/AS0030
3425CT (S10)N/AS0030
3429C (S10A)N/AS10A30
3429CRT (S11A)N/AS11A30
3429CST (S11A)N/AS11A30
3429CT (S10A)N/AS10A30
3521BN/AS10A/S11A40
3521BXTN/AS10A/S11A40
3609U01-11S10S0040
3609U02-11S10S00/S0340
3611U (601U or 602U)S10S00/S0340
3611UD (601U or 602U)S10S00/S0340
3611UT (601U or 602U)S 10S00/S0340
3612U (601U or 602U)S10S00/S0340
3612UD (601U or 602U)S10S00/S0340
Model Name or Number
(Base model name or number in
parentheses.)
55000-150, 151, 152, 153 55000-150,
151, 152, 153
55000-38055000-38045681-200, 220, 230,
DS200 (MB200-2W)BA24
DS200HD (MB200-2W)BA24
DS250 (MB2W or MB2WL)BA18
DS250HD (MB2W or MB2WL)BA18
DS250TH (MB2W or MB2WL)BA18
Compatibility ID# per Loop
HeadBase
45681-200, 220, 230,
231, 232
231, 232
231, 232
231, 232
45681-200, 220, 230,
232, 251, 252
40
40
25
15
15 / loop for
Ion Detectors
15 / loop for
Photoelectric
detectors
A-11
Page 94
Compatible Devices 151204
Manufactu
rer
ESL
FCI
Grinnell
Fire Protection
Enhanced
Mode
Compatible
3711U (701E or 701U)N/AS10A25
3712U (701E or 701U)N/AS10A25
3713-5U (702E or 701U)N/AS10A25
3713-6U (702E or 701U)N/AS10A25
3721-U (S10A)N/AS10A30
3721-UT (S10A)N/AS10A30
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the
date of manufacture against defects in materials and workmanship. See limited warranty statement for
details.
•This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence,
exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Repair and RMA Procedure
•All products that are returned to Silent Knight for credit or repair require a RMA (Return Authorizat ion)
number. Call Silent Knight Customer Service at
800-328-0103 or 203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday through Friday to obtain a
return authorization number.
•Silent Knight T echnical Support is available at 800-446-6444 between 8:00 A.M. and 5:00 P.M. CST,
Monday through Friday.
•All returns for credit are subject to inspection and testing at the factory before actual determination is made
to allow credit.
•RMA number must be prominently displayed on the outside of the shipping box. See return address example
under Advanced Replacement Policy.
•Included with each return should be: a packing slip that has the RMA number, a content list, and a detailed
description of the problem.
•All products returned to Silent Knight must be sent freight pre-paid. After product is processed, Silent
Knight will pay for shipping product back to customer via UPS ground.
•Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an
additional $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries. Silent Knight has the authority to determine if a product is repairable. Products that are deemed
un-repairable will be returned to the customer.
•Product that is returned that has a board date code more than 36 months from date of manufacture will be
repaired and the customer will be assessed the standard Silent Knight repair charge for that model.
Advanced Replacement Policy
•Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during
the first 6 months of the warranty period. These items must be returned with transportation charges prepaid
and must be accompanied by a return authorization.
•For advance replacement of a defective board, contact your local Silent Knight distributor or call Silent
Knight at 800-328-0103 to obtain a RMA (Return Authorization) number and request advanced
replacement.
•A new or refurbished board will be shipped to the customer. The customer will initially be billed for the
replacement board but a credit will be issued after the repairable board is received at Silent Knight. All
returned products must comply with the guidelines described under “General Terms and Conditions” and
“Repair and RMA Procedure”.
•The defective board must be returned within 30 days of shipment of replacement board for customer to
receive credit. No credit will be issued if the returned board was damaged due to misuse or abuse.
•Repairs and returns should be sent to:
Silent Knight / Honeywell
Attn: Repair Department / RA Number_______________________
12 Clintonville Road
Northford, CT 06472 USA
1
Page 98
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products
manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free,
under normal use and service, from defects in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by
Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not
manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to extent possible, any
warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, service
repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if
there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER
WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE
PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER
INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS
FOR ANY P AR TICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all
previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal,
of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any
loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its
authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have
been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock
and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY
IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
2
Page 99
Cut Along the Dotted Line
Model SK5208 Basic Operating Instructions
These Instructions must be framed and displayed next to the SK-5208 panel in
accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
OperationTask to Perform
Press 0 ENTER them enter a code if prompted.
Test the system
Reset AlarmsPress 1 ENTER or RESET then enter a code if prompted.
Reset the Dialer
Display History Events
Show Status
Silence Troubles or AlarmsPress 7 ENTER or SILENCE then enter a code if prompted. Silence LED will light.
Disable/Enable a Zone
Disable/Enable NAC
Conduct a Fire Drill
Reset Detectors1. Press 2 1 ENTER then enter a code. Resets all smoke detector power.
Walk Test the System
Acknowledge Events
LEDStatusCondition
ALARM (red)
SUPERVISORY
(yellow)
TROUBLE (yellow)
SILENCED (yellow)
AC (green)
The system will perform a display lamp test and a communication test. Displays Firmware
Revisions.
Press 3 ENTER, then enter a code if prompted
Resets the dialer and aborts the call to central station.
Press 5 ENTER then enter a code if prompted. Displays the panel history, which includes alarms,
supervisories, troubles, reports, time and date changes, etc.
Press 6 ENTER then enter a code if prompted. View existing system status. List Alarms first,
supervisories and then troubles.
1. Press Zone # + *
2. Enter Code. Repeat the process to enable the zone.
1. Press 1 0 NAC # + *
2. Enter Code. Repeat the process to enable the NAC.
1. Press 2 0 ENTER then enter a code
2. Press RESET then code to end the drill.
1. Press 2 2 ENTER then enter a code
2. Press RESET to end the Walk Test.
Events can be acknowledged by pressing the ENTER button. No code is required to
acknowledge events. The status LEDs (Alarm, Supervisory and Trouble) will flash when an unacknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble
LED) stop flashing and turn on steady. When viewing system st atus the LCD displays “Acked” for
each individual event once it has been acknowledged. The control panel piezo will silence after
all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after
the event has been acknowledged. Supervisories and troubles will silence once the event
is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged
events in the history buffer will be preceded with an asterisk “*”.
LED Meanings
OffNormal condition
OnSystem in alarm.
FlashingLED will flash when a alarm condition exists that has not been acknowledged.
OffNormal condition
OnIf a supervisory condition exist on the system.
OnAlarm or trouble condition has been silenced but condition still exists.
OnPanel is running on AC (normal condition); standby battery fully charged.
OffPanel has lost all power.
FlashingPanel is running on battery power only or AC power only.
LED will flash when a supervisory condition exists that has not been
acknowledged.
LED will flash when a trouble condition exists that has not been
acknowledged.
PN 151214 Rev B
ECN 14-00
Page 100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.