SilentKnight SK-5208 User Manual

Page 1
Model
SK-5208
Fire Control / Communicator
Installation and Operations Manual
Document 151204 05/15/2014 Rev:
M
Page 2
Installation Procedure
Adherence to the following will aid in problem-free installation with long-term reliability:
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) non­condensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes ar e adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written records of all inspections should be kept.
Page 3

Contents

Contents
Section 1
Introduction ..............................................................................................................................................1-1
1.1 Model SK-5208 Features ................................. ...................................................... ..................................1-1
1.2 About This Manual ..................................................................................................................................1-1
1.3 How to Contact Silent Knight .................................................................................................................. 1-1
1.3.1 Optional Accessories ......................................................................................................................1-2
Section 2
Agency Listings and Requirements ........................................................................1-1
2.1 Federal Communications Commission (FCC) ............. ............................................................................ 1-1
2.2 Underwriters Laboratories (UL) .............................................................................................................. 1-1
2.2.1 Requirements for All Installations .................................................................................................... 1-2
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 1-2
2.2.3 Requirements for Auxiliary Protected Fire Alarm Systems for Fire Alarm Service ........................ 1-2
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems, for Digital Communication or
Polarity Reversal ...............................................................................................................................1-2
Section 3
Control Panel Installation ......................................................................................................1-1
3.1 Electrical Specifications ........................................................................................................................... 1-1
3.2 Environmental Specifications ..................................................................................................................1-1
3.3 Wiring Specifications ........................................................ ....................................................................... 1-1
3.4 Control Board Components ..................................................................................................................... 1-3
3.5 Mounting the SK-5208 .............................................................................................................................1-4
3.5.1 Preventing Water Damage ............................................................. ................................................... 1-4
3.6 Current Draw Calculations ................................................ ....................................................................... 1-4
3.6.1 Worksheet Requirements .................................................................................................................. 1-4
3.6.2 Current Draw Worksheet .......... ..................................................... ................................................... 1-5
3.6.3 Maximum Battery Standby Load ......................................................................................................1-6
3.7 AC Wiring ................................................................................................................................................1-6
3.8 Backup Batteries .............................. ..................................................... ................................................... 1-7
3.9 Terminal Strip Description ....................................................................................................................... 1-8
3.10 Telephone Line Connection .............................................................. .................................................... 1-10
3.11 Detector Installation ...............................................................................................................................1-10
3.11.1 Class A (Style D) Zones ........................................................ ......................................................... 1-10
3.11.2 Class B (Style B) Zones ................................................................................................................. 1-11
3.11.3 Four-Wire Smoke Detector Connection ......................................................................................... 1-12
3.11.4 Two-Wire Smoke Detector Connection ......................................................................................... 1-13
3.12 Supervised Notification Appliance Outputs ......................................................................................... 1-13
3.13 Auxiliary Relays ....................................................................................................................................1-15
3.14 Accessory Devices ........................................................................ ......................................................... 1-15
3.14.1 Setting ID Codes ............................................................................................................................. 1-15
1
Page 4
Installation Manual
3.14.2 Model SK-5235 Remote Annunciator ............................................................................................ 1-16
3.14.2.1 Mounting the SK-5235 Remote Annunciator ......................................................................1-16
3.14.2.2 Wiring the SK-5235 ....... ..................................................... .................................................1-17
3.14.3 Model SK-5280 Status Display Module ......................................................................................... 1-18
3.14.3.1 Mounting the SK-5280 ......................................................................................................... 1-19
3.14.3.2 Wiring Relays ...................................................................................................................... 1-20
3.14.3.3 Wiring LEDs to Outputs ......................................................................................................1-21
3.14.4 Model SK-5217 Zone Expander Installation .................................................................................. 1-22
3.14.4.1 Zone Inputs .......................................................................................................................... 1-22
3.14.4.2 Mounting Instructions ..........................................................................................................1-24
3.14.5 Model 5824 Installation Instructions ..............................................................................................1-25
3.14.5.1 Mounting the 5824 Module .................................................................................................. 1-25
3.14.5.2 5824 SBUS Connections ...................................................................................................... 1-26
3.15 Special Applications .............................................................................................................................. 1-27
3.15.1 Model 5220 Direct Connect Module .............................................................................................. 1-27
3.15.1.1 City Box Connection ............................................................................................................ 1-27
3.15.1.2 NFPA 72 Polarity Reversal ..................................................................................................1-28
3.15.2 Keltron 95M3158 Tones Transmitter Module ................................................................................ 1-29
3.15.3 Using a MR-201/T Control Relay From Air Products ................................................................... 1-30
Section 4
Programming .........................................................................................................................................1-1
4.1 Keypad Operation During Programming .................................................................................................1-1
4.1.1 Special Characters .............................................................................................................................1-2
4.1.2 Enabling Extended Programming List ..............................................................................................1-2
4.2 Programming Flow .................................................................................................................................. 1-3
4.2.1 Zone Options .....................................................................................................................................1-4
4.2.2 Misc System Option ..........................................................................................................................1-5
4.2.3 NAC Cadence ................................................................................................................................... 1-6
4.2.3.1 Cadence Patterns .................................................................................................................... 1-6
4.2.4 NAC Options ....................................................................................................................................1-7
4.2.5 Relay Options ................................................................................................................................... 1-8
4.2.6 User Code .........................................................................................................................................1-9
4.2.7 Account ........................................................................................................................................... 1-10
4.2.8 Computer Options ........................................................................................................................... 1-11
4.2.8.1 Computer Code ....................................................................................................................1-11
4.2.9 Line Options ................................................................................................................................... 1-12
4.2.10 Misc Reporting ...............................................................................................................................1-13
4.2.11 5280 Outputs ...................................................................................................................................1-14
4.2.12 5824 Expander Options ..................................................................................................................1-15
4.2.13 DST/Clk Options ..................................................... .. ..................................................................... 1-16
4.3 Programming Options ............................................................................................................................ 1-17
Section 5
Operation .....................................................................................................................................................1-1
5.1 Installer & User Keys ...............................................................................................................................1-1
5.2 On-board Touchpad and SK-5235 Operation ..........................................................................................1-2
5.2.1 View Control Panel Firmware Number and Revision ......................................................................1-2
5.3 Acknowledge Operation .......................................................................................................................... 1-3
2
Page 5
Contents
5.4 LED Indicators .........................................................................................................................................1-3
5.5 Releasing Operation ..................................................................................................... ............................1-4
5.5.1 Cross Alarm Operation ..................................................................................................................... 1-4
5.5.1.1 Default NAC Settings for Releasing ......................................................................................1-4
5.5.2 Double Interlock Releasing Operation .............................................................................................1-6
5.6 Smoke Alarm Verification ............................................................... ........................................................ 1-6
5.7 System Testing .........................................................................................................................................1-7
5.7.1 Fire Drills ..........................................................................................................................................1-7
5.7.2 Walk Test ..........................................................................................................................................1-7
5.7.3 Automatic Self Test ..........................................................................................................................1-7
5.7.4 Watchdog Circuit ..............................................................................................................................1-7
5.8 Communicating with a Programming Computer ..................................................................................... 1-7
5.8.1 Programming From a Remote Computer Location .......................................................................... 1-8
5.8.1.1 Having the Control Panel Call the Remote Computer ........................................................... 1-8
5.8.1.2 Having Remote Computer Call the Control Panel ................................................................. 1-8
5.8.2 Directly Connecting to a Programming Computer ...........................................................................1-9
Section 6
Reporting .....................................................................................................................................................1-1
6.1 Reporting Formats ....................................................................................................................................1-1
6.2 Reporting Codes .......................................................................................................................................1-2
6.2.1 Default Settings for 3/1 Format ........................................................................................................1-5
Section 7
Troubleshooting ................................................................................................................................1-1
7.1 System Error Messages ............................................................................................................................1-1
7.2 Earth Ground Fault Troubleshooting .......................................................................................................1-2
7.3 Earth Fault Resistance ..............................................................................................................................1-3
Appendix A
Compatible Devices ..................................................................................................................... A-1
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability
Model SK5208 Basic Operating Instructions
3
Page 6
151204

Section 1 Introduction

The Model SK-5208 is an 24-volt 10-zone fire alarm control panel (expandable up to 30 zones using SK-5217 Zone Expanders) with a digital communicator that meets NFPA 72 requirements. The SK-5208 cabinet can be surface mounted or semi-flush mounted.

1.1 Model SK-5208 Features

Built-in two-line (16 Character each line) LCD display provides easy to read English language readouts
10 Initiation inputs, 8 Class B (Style B) and 2 zones that can be configured as Class B (Style B) or Class A (Style D), expandable to 30 zones
Supervised zone expanders and I/O modules can be mounted remotely from the main control panel
•UL Listed
Event History Buffer (approximately 150 events) with Date/Time stamp
All zones are compatible with 2- and 4-wire detectors
8 selectable/programmable output pattern for notification appliance circuits (Including ANSI 3.41)
Built-in Digital Alarm Communicator Transmitter (DACT)
4 Notification appliance circuits
4 programmable general purpose relays
Programmable smoke verification, pre-alarm delay, cross zoning and enhanced verification mode features that can help minimize false alarms
Capable of single or dual operation for water releasing services.
Programmable from the built-in control panel touchpad, remote annunciator or Windows software
Built-in walk test
®
downloading

1.2 About This Manual

This manual is intended to be a complete reference for all installation and operation tasks for the SK-5208. Please let us know if the manual does not meet your needs in any way. We value your feedback!

1.3 How to Contact Silent Knight

If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 80 0-328-0103.
1-1
Page 7
Model SK-5208 Installation Manual 151204

1.3.1 Optional Accessories

Table 1-1: Compatible Modules Manufactured by Silent Knight
Model What It Does
SK-5217 Zone Expander Adds 10 zones to the SK-5208 for a total expansion of the system to 30 zones. SK-2190 Accessory Cabinet Used for remote mounting of the SK-5217 Zone Expander.
Dimensions: 10-3/8”W x 10-3/16”H x 3”D (26.35 cm W x 25.88 cm H x 7.62 cm D)
5220 Direct Connect Module For direct alarming and trouble transmission from the SK-5208 to a supervising
station. SK-5235 Remote Annunciator For remote annunciation, operation, and on-site programming. SK-5280 The Model SK-5280 Status Display module provides outputs and control functions for
remote annunciation of alarm, trouble, and supervisories for each zone. 5824 Provides connectivity to a Serial or Parallel printer. (See Section 4.2.12 for
programming.) SK-5499 Signal Power Expander Notification circuit power for additional notification appliances. Provides additional
9A of 24 VDC, supervised. SK-5495 Signal Power Expander Notification circuit power for additional notification appliances. Provides additional
6A of 24 VDC, supervised. SKSS Downloading Software
Model 5660 PLEX-2 Optional door accessory for single button operation. (See Section 4.3 for
For remote programming of the SK-5208 using a personal computer.
programming.)
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72 manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
- Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
- Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are
located.
- Smoke particles may be blown away from detectors by air outlets
- Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smokepresent may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering
),
1-2
Page 8
Introduction 151204
fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) ma y not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
- Please note that: i) Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer's recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly, they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
1-3
Page 9

Section 2 Agency Listings and Requirements

Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of ­line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to NFPA 72.

2.1 Federal Communications Commission (FCC)

1. If requested by the telephone company, the following information must be provided before the SK-5208 can be connected to the phone lines:
A. Manufacturer: Silent Knight A. Model Number: SK-5208 B. FCC registration number: AC6USA-34758-AL-E
Ringer equivalence: 0.5B
C. Type of jack (to be installed by the telephone company): RJ31X
151204
2. This device may not be directly connected to coin telephone or party line services.
3. This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing company or return to:
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 or 800-328-0103
4. If the SK-5208 causes harm to the telephone network, the telephone company will notify the user in advance that temporary discontinuance of service may be required. When advance notice is not practical, the tele­phone company will notify the user as soon as possible. Users have the right to file complaints, if necessary , with the Federal Communications Commission.
5. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice to allow you to make the necessary modifications to maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the two following conditions: (1) This device may not cause radio interference; and (2) This device must accept any interference received including interference that may cause undesired operation.

2.2 Underwriters Laboratories (UL)

The SK-5208 is UL Listed as a control unit for use in Central Station Protected Premises, Local Protected Fire Alarm Systems, Auxiliary Protected Fire Alarm Systems for Fire Alarm Service (City Box), Remote Station Protected Fire Alarm Systems and water releasing service. If the SK-5208 and its accessories are to be used as part of a UL installation, carefully read the UL requirements in this section.
2-1
Page 10
Agency Listings and Requirements 151204

2.2.1 Requirements for All Installations

General requirements are described below. The sections that follow describe additional requirements for the type of installation (for example, Central Station Fire Al arm systems, Local Protected Fi re Alarm systems, and so on).
1. Use UL listed smoke detectors compatible with the SK-5208. Refer to Appendix A.
2. Use UL listed compatible notification devices. Refer to Appendix A.
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
Call forwarding shall not be used.
When cross zoning is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.

2.2.2 Requirements for Central Station Fire Alarm Systems

1. The Phone Line “Line Dial Type” must be selected for anything other than “Not Used”. (See programming Section 4.2.9).
2. On class A (style D) zones, the number of waterflow devices is limited to five.
3. Auxiliary relays may not be programmed to activate for Pre-Alarm. See programming Section 4.2.5.
2.2.3 Requirements for Auxiliary Protected Fire Alarm Systems
for Fire Alarm Service
1. Follow the current load restrictions shown in Section 3.6.
2. The Model 5220 Direct Connect module must be installed (see Section 3.15.1 for wiring).
2.2.4 Requirements for Remote Station Protected Fire Alarm
Systems, for Digital Communication or Polarity Reversal
1. Follow the current load restrictions shown in Section 3.6.
2. Use the SK-5208’s built-in dialer or install the Model 5220 Direct Connect Module (see Section 3.15.1).
2-2
Page 11

Section 3 Control Panel Installation

3.1 Electrical Specifications

Table 3-1: Electrical Specifications
Primary AC 120 Vrms at 60 Hz, 3A To ta l DC Lo ad 6A Accessory Power 27.4 VDC, 1A Smoke Power 27.4 VDC, 1A Battery Charging Voltage 27.4 Battery Charging Current .75 A max. Class B (Style B) Circuit Current 95 mA max. Telepho ne Minimum Input Sensitivity 35 dB Good Phone Line Voltage 3 V Maximum Low Battery Detect 20.4 Minimum Low AC Detect 98 Notification Power 3A max. per output (6A total)
151204

3.2 Environmental Specifications

It is important to protect the SK-5208 control panel from water. To prevent water damage, the following conditions should be AVOIDED when mounting the units:
Do not mount directly on exterior walls, especially masonry walls (condensation).
Do not mount directly on exterior walls below grade (condensation).
Protect from plumbing leaks.
Protect from splash caused by sprinkler system inspection ports.
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery).
When selecting a location to mount the SK-5208 control panel, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity equal to or greater than 93% at 30°C (89°F) noncondensing.
See also the mounting recommendations in Section 3.5 for additional environmental specificati ons.

3.3 Wiring Specifications

To avoid induced noise (transfer of electric al energy from one wire to another), keep input wiring isolated from high current output and power wiring. Induced noise can interfere with telephone communication or even cause
3-1
Page 12
Control Panel Installation 151204
Tel. Line
Aux Relays
NACs
SBUS devices or Annunciator
To Zone
To AC
false alarms. Avoid pulling one multiconductor cable for the entire panel. Instead, separate the wiring as follows:
Input/Output Type Wiring
1/4" spacing must be maintained between each of these circuit types; as well as between power limited and non-power limited circuits.
High Voltage: AC power Low Voltage: Annunciator, zone circuit wiring, and notification devices Audio: Speaker Telco Separated
DO NOT pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel only.
For the same reasons, wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid. Figure 3-1 provides an example.
Figure 3-1 Wire Routing Example
3-2
Page 13
Model SK-5208 Installation Manual 151204
Phone Line 1 Connections
Phone Line 2 Connections
NAC Circuit
Programmable Output Relays
Backup Battery
Connector
Connections
Remote Annunciator
AC Input
Class A
or
Class B
Zone
Inputs
Class B
Zone
Inputs
SBUS
Connections
RS232 Programming Connector
Mounting Screw
Mounting Screw
Mounting Screw
Mounting Screw

3.4 Control Board Components

Figure 3-2 is a wiring diagram for wiring the Model SK-5208 panel.
Figure 3-2 Model SK-5208 Board La yout
Refer to Section 3.9 for complete description of control panel terminal connections. Figure 3-2 shows the 5208 circuit board stack. If you should need to remove the control board for repair, remove
the four mounting screws which hold the control board in the cabinet. Then lift the control board out of the cabinet.
3-3
Page 14
Control Panel Installation 151204

3.5 Mounting the SK-5208

Read the environmental specifications in section 3.2 on page 1 before mounting the SK-5208 panel. The SK-5208 cabinet dimensions are:
16" W x 26.4" H x 4" D (40.64 cm W x 67.06 cm H x 10.16 cm D).
The SK-5208 panel should be located within a secured area, where it is accessible to main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture can accumulate, the enclosure shall be placed or equipped so as to prevent moisture or water from entering and accumulating within the cabinet, and shall be mounted so there is a least 1/4” space between the enclosure and the concrete wall surface. A piece of plywood, standoffs, or other equivalent material can be used to space the cabinet from the concrete surface and then attach the SK-5208 to that spacing surface. Also mount any other desired components to the 1/4” spacing surface.
DO NOT flush-mount the SK-5208 cabinet in a wall designated as a fire break.

3.5.1 Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.

3.6 Current Draw Calculations

3.6.1 Worksheet Requirements

The following steps must be taken when determining SK-5208 current draw and standby battery requirements.
Filling in the Current Draw Worksheet, Table 3-2 (Section 3.6.2)
1. For the SK-5208, the worst case current draw is listed for the panel and panel accessories. Fill in the number of devices that will be used in the system and compute the current draw requirements for alarm and standby . Record this information in Table 3-2 at Line A.
2. Add up the current draw for all smoke detectors and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the SK-5208 control panel. If the current is above 6.0 A you will need to use a notification power expander(s) such as the 5495 to dis-
tribute the power loads so that the SK-5208 or the power expanders do not exceed their power rating. Refer to the current draw worksheets provided with the 5495 manuals so you do not exceed their power require­ments.
6. Complete the remaining instructions in Table 3-2 for determining battery size requirements.
3-4
Page 15
Model SK-5208 Installation Manual 151204

3.6.2 Current Draw Worksheet

Use Table 3-2 to determine current requirements during alarm/battery standby operation. (Copy the page if additional space is required.)
Table 3-2: Current Draw Calculations
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices. SK-5208 Fire Panel (Current draw from battery) Panel Accessories
SK-5217 Zone Expander (2 max.) 5824 Serial/Parallel Interface
Gateway Module 5220 Direct Connect
SK-5235 Annunciator (6 max.)
SK-5280 Status Display Module (8 max.)
A Total System Current
Smoke Detectors
B Smoke Detector Current mA mA
Notification Appliances
C Notification Appliances Current
Additional Devices
D Additional Devices Current mA E Total current ratings of all devices in system (line A + line B + C +D) mA mA F Total current ratings converted to amperes (line E x .001): A A G Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H H Multiply lines F and G. Total standby AH AH I Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H J Multiply lines F and I. Total alarm AH K
*Add lines H and J.
1
(1 max.)
Standby: 140 mA 140 mA Alarm: **550 mA 550 mA
Standby: 60 mA mA Alarm: 150 mA mA Standby: 45 mA mA Alarm: 45 mA mA Standby: 15 mA mA Alarm: 15 mA mA Standby: 30 mA mA Alarm: 50 mA mA Relay (max.)
Outputs
Standby: mA mA Alarm: mA mA Standby: mA mA Alarm: mA mA Standby: mA mA Alarm: mA mA Standby: mA mA Alarm: mA mA
Alarm: mA mA Alarm: mA Alarm: mA mA
Standby: mA Alarm: mA Standby: mA Alarm: mA
Standby: 10 mA mA Alarm: 80 mA mA Per output 100 mA mA Max. 700 mA
Total ampere
hours required
Standby
Current
AH
Alarm
Current
mA
mA
mA
AH
* Use next size battery with capacity greater than required. ** The SK-5208 and SK-5217 limits alarm current to 95mA per zone. The SK-5208 alarm current includes
3-5
Page 16
Control Panel Installation 151204
10% of zones in alarm, but in no case less then three zones per UL864

3.6.3 Maximum Battery Standby Load

Table 3-3 shows the maximum battery standby load for the SK-5208 based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2) must be less than the number shown in Table 3-3 for the battery size used and standby hours required.
Batteries larger then 18 AH will not fit into the SK-5208 cabinet and must be housed in the RBB remote battery box cabinet. See Section 3.8 for battery installation.
Table 3-3: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH 270 mA 105 mA 12 AH 475 mA 190 mA 18 AH 685 mA 270 mA 35 AH 1.1 A 450 mA
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Tab le 3-3. If you use a battery too small for the installation, the system could overload the battery resulting in the installa tion havi ng less than the required 24 hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for your installation.

3.7 AC Wiring

The Model SK-5208 power supply delivers 24 VDC at 6A for smoke detector power, notification device power, and accessory power. Figure 3-3 shows the AC connections to the SK-5208 control panel.
Figure 3-3 AC Wiring
3-6
Page 17
Model SK-5208 Installation Manual 151204
Battery Jumper
(P/N 140694)
Shipped With Panel
RED
Black
UL Listed 12VDC
UL Listed 12VDC
Control Panel
Battery #2
Battery #1
Battery Gell Cell
Battery Gell Cell
Note: Replace batteries every 5 years.
Warning
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected before attempting to connect the Model SK-5208 control panel. Do NOT apply power to this panel until all accessories are properly connected.
Note: Note: All conduit and wiring connected to the SK-5208 must meet the applicable National Electric Code,
NFPA Standards, state, and local building code requirements. In all cases, the authority having jurisdic­tion takes precedence.

3.8 Backup Batteries

The control panel battery charge capacity is 7.0 to 35.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see 3.6.2).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. Batteries larger than 18 AH (not to exceed 35 AH) use the RBB Remote Battery Box. It is recommended that you
replace the batteries every five years. The following steps and diagram explain how to connect the batteries.
1. Connect the black wire to the negative (-) side of battery #1.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of battery #1 to the negative side of battery #2.
3. Connect the red wire to the positive (+) side of battery #2
3-7
Page 18
Control Panel Installation 151204
Caution
Apply AC power before connecting the batteries to the power supply to prevent arcing on battery terminals.
Note: The total current draw on smoke power, accessory power, and notification device outputs must not exceed
6A.

3.9 Terminal Strip Description

The terminal strips on the PC board are non-removable. Table 3-4 lists the functions of each terminal. See Section 3.4 for the board layout.
Table 3-4: Terminal Descriptions
Function
Zone 1 input.
Zone 2 input
Ground 9 GND Zone 3 input 10 Z3 Zone input Class B (Style B). Refer to Section 3.11.2. Power (Zone 3 & 4) 11 PWR Zone 4 input 12 Z4 Zone 5 input 13 Z5 Smoke Power 14 PWR Zone 6 input 15 Z6 Zone 7 input 16 Z7 Smoke Power 17 PWR Zone 8 input 18 Z8 Zone9 input 19 Z9 Smoke Power 20 PWR Zone 10 input 21 Z10 Ground 22 GND
AC Power Connections
SBUS Connections
Terminal
Number
1A 2B 3C 4D 5A 6B 7C 8D
23 B 24 Earth 25 W 26 GND Used to connect SK-5217 Zone Expanders and 5280 27 +24DC 28 A 29 B
Te rmina l La bel Comments
Zone 1 input Class A (Style D) or Class B (Style B). See Section 3.11 for wiring configurations.
Z1
Zone 2 input Class A (Style D) or Class B (Style B). See Section 3.11 for wiring configurations.
Z2
Power Limited at 100mA. Voltage 27.4 VDC.
Status Display Modules to the control panel. Accessory Power (terminals 26 and 27) provides 1 Amp total current.
3-8
Page 19
Model SK-5208 Installation Manual 151204
Table 3-4: Terminal Descriptions
Function
Remote Annunciator Connections
Notification Appliance Circuit 4
Notification Appliance Circuit 3
Notification Appliance Circuit 2
Notification Appliance Circuit 1
Auxiliary Relay 4
Auxiliary Relay 3
Auxiliary Relay 2
Auxiliary Relay 1
Telco Line 2
Telco Line 1
Terminal
Number
30 SKI Used to connect 5235 remote annunciators to the control 31 SKO 32 PWR 33 GND 34 + 35 _ 36 + 37 _ 38 + 39 _ 40 + 41 _ 42 NO Relay contacts are rated at 2.5 A, 24 VDC/24VAC 43 COM 44 NC 45 NO 46 COM 47 NC 48 NO 49 COM 50 NC 51 NO 52 COM 53 NC 54 TIP 55 RING 56 TIP 57 RING 58 TIP 59 RING 60 TIP 61 RING
Te rmina l La bel Comments
panel.
NAC4
3 Amp maximum per circuit. Voltage 27.4 VDC, 1.5 Ohms Maximum.
Note: Total control panel current is 6 Amps.
NAC3
NAC2
NAC1
(inductive rating). 5A, 24 VDC/24 VAC (resistive). Connect to power limited source only.
P2
T2
P1
T1
Telephone line 2 connectio n te rminals (see Section 3.10 for wiring diagram).
Telephone line 1 connectio n te rminals (see Section 3.10 for wiring diagram).
3-9
Page 20
Control Panel Installation 151204
Supervised

3.10 Telephone Line Connection

The SK-5208 connects to two separate telephone lines to report data to the central station. An RJ31X jack should be installed by the telephone company for each line. Figure 3-4 shows how to wire the telephone line interconnect cords (not provided) to the SK-5208.
Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together
with initiation or notification device wires.
Figure 3-4 Telephone Line Connection
The letter designator on the phone input indicates whether it is the Telco or House side of the phone circuit. For example terminals 60 and 61 are labeled T1, T = Telco side of the phone circuit and terminals 58 and 59 are labeled P1, P = Premise (House) side of the phone circuit.
The SK-5208 has built-in dual phone line monitors. These circuits will detect any fault in the phone lines by monitoring the DC voltage present on the lines. If phone line voltage drops below 3 VDC and is not corrected within approximately 60 seconds, an audible trouble signal will sound and the panel will report a line fault trouble over the remaining phone line.
A situation could occur where both phone lines appear to be good, but the dialer cannot get through to the central station on the first line. In this case, the SK-5208 will switch phone lines and attempt the call again using the second line. Make sure the phone lines are programmed properly (see Section 4).
Note: To comply with industry standards, this product is equipped with line seizure. Any time the system’s dialer
needs to communicate with the central station, it will not be possible to use any telephones that are on the same line(s) as the system. Normally, this condition will last approximately one minute, but under adverse telephone circuit conditions, could last for as long as 15 minutes.

3.11 Detector Installation

3.11.1 Class A (Style D) Zones

Zones 1 and 2 may be selected through programming as Class A (Style D) zones (see Section 4.2.2 for zone style programming). See Section 3.11.2 for Class B (Style B) configuration.
Each class A zone is a four-wire circuit that allows an alarm to be detected even after a single open or ground fault occurs. When a single open or ground fault occurs, the audible trouble signal will sound and the SK-5208 will report the trouble to the central station or remote station (if programmed to report troubles). If reporting to a remote station troubles may be transmitted to a secondary location.
Figure 3-5 shows how to wire a Class A (Style D) circuit. No end-of-line (EOL) resistors are needed for these
3-10
Page 21
Model SK-5208 Installation Manual 151204
Supervised Power Limited
Supervised Power Limited
4.7 k EOL UL Listed
Model 7628
Note: Zones 1 and 2 can be configured as either Class A or Class B. See also Section
3.11.1.
zones. These zones must be wired using normally open contacts.
Figure 3-5 Class A (Style D) Supervised Fire Circuit
Maximum voltage: 17.5 to 28 VDC Full Wave Rectified Circuit Current: 95 mA Maximum circuit Resistance: 50 ohms

3.11.2 Class B (Style B) Zones

Zones 3 through 10 are Class B (Style B) only fire zones. Zones 1 & 2 may also be programmed as Class A (Style D) or Class B (Style B), see Section 4.2.2 for zone 1 & 2 zone programming.
Each Class B zone consists of a two-wire circuit that will detect the occurrence of an open in the circuit, but may not be able to detect an alarm after such an occurrence. The detection of an open will cause the audible trouble signal to sound and the SK-5208 will report the trouble to the central or remote station (if programmed to do so).
Figure 3-6 shows how to wire a Class B (Style B) circuit. One side of each Class B circuit connects to a zone input terminal and the other side of each circuit connects to Smoke power. For each circuit, use a 4.7K-ohm EOL resistor wired in parallel with the normally open contact farthest from the panel.
Figure 3-6 Model SK-5208 Class B (Style B) Circuits
3-11
Page 22
Control Panel Installation 151204
Supervised Power Limited
Maximum circuit Resistance - 50 ohms Maximum Total alarm current for all Class B (Style B) zones - 1 A Maximum Standby Current per Zone:3.0 mA Maximum Alarm Current per Zone:95 mA

3.11.3 Four-Wire Smoke Detector Connection

Figure 3-7 illustrates how UL listed four-wire smoke detectors must be connected to Class B (Style B) zones. When wiring a four-wire smoke detector to the Class B (Style B) zones, you must use a Power Supervision Unit,
such as Silent Knight’s 160150.
Note: Mount the PAM-2 and the end-of-line resistor at the last device on the circuit.
Figure 3-7 Four-Wire Smoke Detector Wiring
See Appendix A for a list of four-wire smoke detectors that may be used with the SK-5208.
3-12
Page 23
Model SK-5208 Installation Manual 151204
– +
– +
Silent Knight
SLK-24F 2-wire detector
with HSB-224 base
4.7 k
UL Listed EOL
Model 7628
Supervised Power Limited

3.11.4 Two-Wire Smoke Detector Connection

Figure 3-8 shows how to connect two-wire smoke detectors to Class B (Style B) zones.
See Appendix A for a list of two-wire smoke detectors that may be used with the SK-5208.
Note: Two-wire detectors can be configured for Enhanced Mode. Enhanced mode is smoke verification for zones

3.12 Supervised Notification Appliance Outputs

Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together
The SK-5208 provides four Class B (Style Y) supervised notification circuit outputs to annunciate alarm conditions. For proper operation, you must use polarized sounding devices with a 4.7k ohm end-of-line resistor
Figure 3-8 Two-Wire Smoke Detector Wiring
with 2-wire detectors and contact type devices, such as pull stations, used on the same circuit. If the alarm current is greater than 78 mA, the smoke verification cycle will not occur. See Section 4.2.1 Verify Options under the Zone Options Menu to program initiation circuits for enhanced mode.
with notification circuit wires.
3-13
Page 24
Control Panel Installation 151204
Supervised Power Limited
4.7 k
UL Listed EOL
Model 7628
3 Amps Max. per circuit full wave rectified, 27.5 VDC, 1.5 Ohms Maximum.
on each circuit. Figure 3-9 shows how to connect the notification circuits to the SK-5208.
Figure 3-9 Supervised Notification Appliance Wiring
3 Amp maximum current draw from any single NAC output (not to exceed a total current draw of 6 amps for the control panel). See Appendix A for a list of the UL notification appliances that can be used with the SK-5208. Contact Silent Knight if you have any questions about compatible notification circui ts.
All circuit are regulated unless used for releasing service in which case they are considered special applications. See Section 5.5 for details on releasing.
3-14
Page 25
Model SK-5208 Installation Manual 151204
Relay contacts are rated at
2.5 A, 24 VDC/24VAC (inductive rating). 5A, 24 VDC/24 VAC (resistive).
Door Holder
ESL DHX 1224

3.13 Auxiliary Relays

The SK-5208 provides four programmable auxiliary relay outputs. Relays can be programmed to activate for the following conditions, either for all zones or by individual zone: pre-alarm (not acceptable for NFPA 72 Central Station), fire alarm, auxiliary alarm, alarm by zone, and system or circuit troubles (loss of AC, low battery, failed to communicate, phone line troubles, fire drills, and notification circuit troubles).
Refer to the SK-5208 programming manual for more information. Figure 3-10 shows the relay contact connections using a door holder application as an example.
Note: Relays programmed as “Trouble” will be active during normal state and deactivated during a trouble con-
dition.
Figure 3-10 Auxiliary Relays

3.14 Accessory Devices

The section describes how to install the SK-5235 Remote Annunciato r, SK-5217 Zone Expander, the 5824 Serial/Parallel Printer Module, and the SK-5280 Status Display Module. All circuits are 24 VDC regulated. All S-Bus devices are Style 1 Class B as per NFPA 72.

3.14.1 Setting ID Codes

Before installing the SK-5235, SK-5217, 5824 or SK-5280, you must first set their identification codes. Each device must be given its own identification code. For example: each SK-5235 needs a unique ID code, but a SK­5235 can have the same ID code as a SK-5217. Each type of device has it’s own device type programmed into it enabling the control panel to distinguish between the different devices.
On the back of each device is a small 4-position dip switch used to set the ID code. Use the chart below to
3-15
Page 26
Control Panel Installation 151204
determine the dip switch positions for each possible ID code.
Table 3-5: ID Dip Switch Settings
ID Number
1234
2
0 1 Up Down Down Down 2 Down Up Down Down 3 Up Up Down Down 4 Down Down Up Down 5 Up Down Up Down 6 Down Up Up Down 7 8
1.
Switch Settings: Up = On Down = Off
2. Not supervised.
3. ID number 7 and 8 are not valid ID settings.
Down Down Down Down
Not used
Switches
3
1

3.14.2 Model SK-5235 Remote Annunciator

The SK-5235 performs all system operation. It also provides trouble and alarm information and can be used for programming. The control panel can support up to six SK-5235 Remote Annunciators.
Upon initial power up, the address of each SK-5235 is displayed on the LCD. (Annunciators with address 0 will not be supervised.)
3.14.2.1 Mounting the SK-5235 Remote Annunciator
The SK-5235 Remote Annunciators must be mounted on a dual gang electrical box. To mount the annunciator:
1. Remove the rear mounting plate by inserting a #4 flat blade screwdriver into the slots on the bottom edge of the annunciator. See Figure 3-11. Gently turn the screwdriver until the mounting plate pulls away from the frame.
Figure 3-11 Rear Mounting Plate Removal
3-16
Page 27
Model SK-5208 Installation Manual 151204
ID DIP switches
Supervised Power Limited Class B
2. Secure it to the wall using #6 or #8 screws. The mounting plate should be oriented so that the word TOP is toward the top of the plate and facing you. A square hole is provided in the mounting plate to run the wiring to the annunciator.
3. When all of the wires have been connected to the annunciator , set the top of the annunciator over the tabs on the top of the mounting plate. Make sure the wires do not get pinched between the frame and the mounting plate. Press each corner of the bottom side onto the annunciator mounting plate until you hear it click. You may have to gently squeeze the annunciator (top to bottom) to align it while snapping the bottom edge into place.
3.14.2.2 Wiring the SK-5235
Follow these steps to properly wire the SK-5235 to the control panel.
1. Remove power from the control panel.
2. Wire the SK-5235s as shown in Figure 3-12.
3. Set the ID number. See Table 3-5.
Note: The ID number of 7 is reserved for the built-in touchpad on the SK
4. Reapply power the control panel. When the annunciator powers up, it will display its ID code and current status of the panel.
Figure 3-12 Model SK-5235 Connection
-5208.
Note: Each 5235 touchpad can be individually supervised. See Section 4.2.2 for programming touchpads as su-
pervised.
3-17
Page 28
Control Panel Installation 151204
Alarm Outputs
Trouble Outputs
ID Number DIP Switch
SBUS Connector
4 On-board Relays
Relay Rating
2.5A @ 30 VDC/120 VAC
1/4” spacing must be maintained between power limited
& non-power limited wiring

3.14.3 Model SK-5280 Status Display Module

The Model SK-5280 Status Display module provides outputs and control functions for remote annunciation of alarm, trouble, and supervisories for each zone.The system can supervise up to eight SK-5280 Status Display Modules.
Note: The driver outputs are non-supervised. Rel a ys must be connected to power limited sources only.
Figure 3-13 Model 5280 Board Layout
The SK-5280 has 1 connector which has 10 outputs for alarms and 10 outputs for trouble annunciation. These outputs are active low. Each output can provide up to 100 mA of current, with a total limitation of 700 mA.
The module has 4 normally open non-dedicated relays that can be wired to be active with any of the outputs. Wire the SK-5280 as shown in Figure 3-14. Maintain a physical separation of one-half inch or more between
field wires and connection points to prevent damage from transients. Note: SILENCE does not affect SK-5280 outputs. To reset a SK-5280 output, the alarm or trouble condition must
be restored. The SK-5280 can be used to interface to LED annunciator. The SK-5280 can be programmed to indicate alarms and trouble status for; zones 1 - 10, zones 11 - 20, zones 21
3-18
Page 29
Model SK-5208 Installation Manual 151204
Control Panel
5280
Supervised Power Limited Class B
- 30, or system status outputs. See Section 4.2.11.
Figure 3-14 Model SK-5280 Connection to the Control Panel
3.14.3.1 Mounting the SK-5280
The SK-5280 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet.
Mounting the SK-5280 into SK-5208 Cabinet
Follow these steps to properly mount the SK-5280 into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-15.
Figure 3-15 Installing the 5280 Into the 5208 Cabinet
3-19
Page 30
Control Panel Installation 151204
Mounting Holes
Mounting Holes
3. Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
4. Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for information on setting ID numbers.
5. Reconnect power to the control panel.
Mounting the SK-5280 into the SK-2190 Accessory Cabinet.
Follow these steps to properly mount the SK-5280 into the SK-2190 cabinet:
1. Mount the remote cabinet using the cabinet mounting holes. See Figure 3-16. Refer to Section 3.5 for proper cabinet mounting procedures.
2. Remove power from the control panel.
3. Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-16.
Figure 3-16 Model SK-5280 Remote Installation
4. Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
5. Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for information on setting ID numbers.
6. Reconnect power to the control panel.
3.14.3.2 Wiring Relays
The four on-board relays can be triggered by the active low outputs. For example, the alarm outputs can all be wired to relay 3 and the trouble outputs can be wired to relay 4 (see Figure 3-17).
3-20
Page 31
Model SK-5208 Installation Manual 151204
Relay Rating
2.5A @ 30 VDC/120 VAC
C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and 4 respectively.
Figure 3-17 Relay Wiring on the SK-5280
Note: Figure 3-17 uses A7 and T7 to activate relays 3 and 4 as an example. However, any of the outputs can be
used to trip any of the relays.
3.14.3.3 Wiring LEDs to Outputs
The outputs (A1-A10 and T1-T10) can be used to operate LEDs used in a remote annunciator (see Figure 3-18). Outputs A1-A10 are alarm outputs for the zones corresponding to those outputs. For example, if the SK-5280 is programmed to output for zones 11-20, then outputs A1-A10 will correspond with zones 11 through 20.
Outputs T1-T10 are trouble outputs for the zones corresponding to those outputs. for example, if the SK-5280 is programmed to output for zones 21-30, then outputs T1-T10 will correspond with zones 21-30.
Figure 3-18 LED Wiring on the SK-5280
3-21
Page 32
Control Panel Installation 151204
Control Panel
Supervised Power Limited
SK-5217
Class B

3.14.4 Model SK-5217 Zone Expander Installation

The Model SK-5217 provides the SK-5208 with ten additional Class B (style B) zones. The SK-5217 connects to the SK-5208 control panel via the SBUS as shown in Figure 3-19.
Figure 3-19 SBUS Connections
3.14.4.1 Zone Inputs
Figure 3-20 and Figure 3-21 shows how to wire detectors to the SK-5217. Use a 4.7k end of line resistor for each Class B circuit. The EOL must be wired in parallel with the normally open contact farthest from the panel. See Appendix A for a list of the smoke detectors that can be used with the SK-5217.
Maximum circuit Resistance - 50 ohms Maximum Total alarm current for all class B (style A) zones - 1 A Maximum Standby Current per Zone:3.0 mA Maximum Alarm Current per Zone:95 mA
3-22
Page 33
Model SK-5208 Installation Manual 151204
Device ID Dip Switches
Supervised Power Limited
4.7k
UL Listed
EOL Resistor
Model 7628
Voltage:17.5 to 28 VDC
Figure 3-20 Model SK-5217 Two-wire Detectors
Figure 3-21 4-Wire Detector Connections
3-23
Page 34
Control Panel Installation 151204
3.14.4.2 Mounting Instructions
The SK-5217 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190 accessory cabinet.
Mounting the SK-5217 into SK-5208 Cabinet
Follow these steps to properly mount the SK-5217 zone expander into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-22.
Figure 3-22 Installing the SK-5217 Into the SK-5208 Cabinet
3. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
4. Wire the zone inputs to the zone expander as shown in Figure 3-20.
5. Set the ID code (see Section 3.14.1). If ID code 1 is selected the SK-5217 will input zones 11 - 20. If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Reconnect power to the control panel.
Mounting the SK-5217 into the SK-2190 Accessory Cabinet.
Follow these steps to properly mount the SK-5217 zone expander into the SK-2190 cabinet:
1. Mount the remote cabinet using the cabinet mounting holes. See Figure 3-23. Refer to Section 3.5 for proper cabinet mounting procedures.
2. Remove power from the control panel.
3-24
Page 35
Model SK-5208 Installation Manual 151204
Mounting Holes
Mounting Holes
3. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23.
Figure 3-23 Model SK-5217 Remote Installation
4. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
5. Set the ID code (see Section 3.14.1). If ID code 1 is selected the SK-5217 will input zones 11 - 20. If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Wire the zone inputs to the zone expander as shown in Figure 3-20.

3.14.5 Model 5824 Installation Instructions

The Model 5824 provides the 5208 with the ability to communicate to a serial or parallel printer to print the event log. You can use one 5824 on the 5208. The 5824 is for ancillary use only.
3.14.5.1 Mounting the 5824 Module
The 5824 comes in a plastic enclosure, follow these steps to mount the 5824’s plastic enclosure:
1. Remove the 5824’s cover. Use a small screw driver if necessary.
3-25
Page 36
Control Panel Installation 151204
Snap
Base
Retaining Tabs
Mounting Holes
Mounting Holes
Supervised Power Limited
5824
Control
Panel
2. Remove the 5824 circuit board from the base by pushing outward on the base snap retaining tabs and lifting the circuit board out.
Figure 1: 5824 Circuit Board And Plastic Base
3. Mount the plastic base.
4. Replace the circuit board in the plastic base.
Note: It may be necessary to connect the wiring to the circuit board before the board is replaced in the base. See
5. Connect the 5824 to the 5208.
6. Set the device ID (see Section 3.14.1). See also Figure 3-25 for ID selector switch location.
3.14.5.2 5824 SBUS Connections
Figure 3-24 illustrates how the 5824 connects to the 5208 control panel.
Section 3.14.5.2.
Figure 3-24 5824 Connections
3-26
Page 37
Model SK-5208 Installation Manual 151204
Serial Port
Parallel Port
ID Selector Switches
5824
Figure 3-25 Model 5824 Serial/Parallel Port, and ID Selector Switch location

3.15 Special Applications

3.15.1 Model 5220 Direct Connect Module

The 5220 Direct Connect module can be used with the SK-5208 to meet NFPA 72 standards. The 5220 requires four connections to the SK-5208 and provides outputs for city box and polarity reversal applicatio ns. The 5220 cannot be used for sprinkler supervisory.
The 5220 provides a current that reverses polarity during alarm or removes current during a trouble condition. Maximum voltage 27.3 VDC.
Note: The 5220 Direct Connect Module will activate for alarm and trouble conditions during a Walk Test. To
disable alarm activation during Walk Test, bypass the NAC programmed for Direct Connect before enter­ing the Walk Test mode. To bypass the NAC, press; 10 + NAC# + * + Code (repeat to un-bypass NAC). The Direct Connect relay will indicate trouble until the NAC is un-bypassed.
3.15.1.1 City Box Connection
This section describes how to connect the SK-5208 to a municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box conn ection:
1. Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a short piece of con­duit (must not exceed 20 feet in length).
2. Wire the 5220 to the SK-5208 as shown in Figure 3-26. This drawing also shows how to connect the city box coil to terminals 3 and 4 on the 5220.
3-27
Page 38
Control Panel Installation 151204
5220
Control
Supervised for
Opens and Ground Faults
City Box
Coil Resistance
14.5
Panel
3. Program NAC #4 to be direct connect from the NAC Options menu. Relay #4 will automatically be config­ured to indicate system troubles.
Note: It is not possible to reset the remote indication until you clear the condition and reset the SK-5208.
Figure 3-26 City Box Connection
3.15.1.2 NFPA 72 Polarity Reversal
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the SK-5208 panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. To install the 5220 for polarity reversal, follo w the steps below:
1. Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a short piece of con­duit (must not exceed 20 feet in length).
2. Wire the 5220 to the SK-5208 using the four-wire pigtail provided as shown in Figure 3-27 (next page). This diagram also shows how to connect the 5220 to the remote indicator.
3. Program one of the notification circuits to be Direct Connect (Figure 3-27 uses NAC 4 and Relay 4). The relay and NAC circuits are paired when selected as direct connect. For example, if NAC 4 is programmed as Direct Connect then relay 4 used for the trouble output. Do not program the NAC for Silence or Supervision (NACs with EOL).
3-28
Page 39
Model SK-5208 Installation Manual 151204
All Other Wires
Trouble Contacts Supervised For Opens and Ground Faults
Supervised, Power Limited
Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.
4. If necessary, adjust circuit current using potentiometer R10 on the 5220 board. Normal circuit current is 4­to-8 mA with a 1k ohm remote station protected premise unit. Maximum circuit resistance is 3k ohm.
Figure 3-27 Polarity Reversal Connect io n

3.15.2 Keltron 95M3158 Tones Transmitter Module

This section of the manual shows the specific connections you will make when wiring the SK-5208 to the Keltron 95M3158 Tones Transmitter Module (3158). Refer to the installation sheet shipped with the 95M3158 for complete information. (Note: The 3158 is not available from Silent Knight.)
Note: The 3158 Keltron Module must be mounted within 3 feet of the control panel and all wiring must be run in
conduit. The Keltron Module shall be enclosed in the TBX1 enclosure.
1. Wire the 3158 to the SK-5208 as shown in the Figure 3-28.
2. Program NAC 4 for Direct Connect (see Section 4.2.4).
3. Program NAC 3 for Supervisory (see Section 4.2.4).
4. Program NACs 3 and 4 as unsupervised (NACs With EOL). See Section 4.2.4.
3-29
Page 40
Control Panel Installation 151204
All Other Circuits Supervised Power Limited
See Table 3-4 for electrical ratings.
Trouble Contacts Supervised For Opens and Ground Faults
Note: The term FACP Term. refers to terminals on the SK-5208
5. Program NAC 3 cadence as Steady (see Section 4.2.3).
Figure 3-28 Wiring the Keltron 3158 to the SK-5208

3.15.3 Using a MR-201/T Control Relay From Air Products

When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Current: 15 mA max. Operating Voltage: 24 VDC nominal Resistance: 4 K To install the MR-201/T for polarity reversal, follow the steps below:
3-30
Page 41
Model SK-5208 Installation Manual 151204
Intended for Connection to a Polarity Reversal
Circuit of a Remote Station Receiving Unit
Having Compatible Rating.
1. Wire the MR-201/T as shown in Figure 3-29.
Figure 3-29 Wiring the MR-201/T
2. Program the NAC circuit as a non silence NAC (see Section 4.3).
3-31
Page 42
Section 4
#
Programming
The SK-5208 control panel can be programmed from either the on-board annunciator or the SK-5235 remote annunciator. You must be in Programming Mode to program the control panel.

4.1 Keypad Operation During Programming

This section describes the function of the buttons on the keypad while in program mode.
Operation/Button Operation/Description
Enter Step Programming mode
Moving through programming
Exit Step Programming Press RESET. You are prompted to save programming changes. The default is No. Press the
Down Arrow
Enter Button
Left Arrow
Right Arrow
Silence Button
Up Arrow * Button
# Button
Press 2, 7, ENTER, followed by installer level code (the factory programmed code is 123456 or 5208). See Section 4.2.6 for user code programming information.
When you have entered programming correctly, the display will show Zone 1 Options. Press
to move to next programming option. See Table 4-4 for list of programming options (column 1) and their menu items (column 2). When the display shows the option you wish to program press ENTER to program items in this option. If you receive a trouble beep and the message TRY AGAIN appears you are not using an installer level code.
up or down arrow to select Yes to save programming changes. Press Enter to complete the save and return to normal operation mode.
Accepts the entered data and scrolls down to the next menu item.
Accepts the entered data and scrolls down to the next menu item.
Scrolls backwards through the programmable items list for the currently selected option.
Scrolls forward through the programmable options list or choices for an the selected item.
Enables extended programming list so you can scroll through lists of items that have multiple components such as, Zone 1 -30. See Section 4.1.2 for an example.
Accepts the entered data and scrolls up to the next menu item.
Used as shift key when entering special characters (A, B, C, D, or E characters). See Section
4.1.1 for more information. Clear entry.
151204
4-1
Page 43
Programming 151204
1
234
Initial Display
Display After Silence Button Pressed
Right Arrow Pressed then Display Moves to Next Zone Number

4.1.1 Special Characters

Special characters are characters used while dialing such as pause, *, #, or 2nd dial tone. Table 4-1 list the Special characters and what they mean.
Table 4-1: Special Characters
To Enter: Press LCD Display
Pause
*
#
2nd Dial Tone
A
B
C
D

4.1.2 Enabling Extended Programming List

While programming there are several programming options that have multiple comp onents that can be programmed within that menu item, such as Zones, NAC Cadence, User Codes, Accounts, etc. However when you scroll through these options only the first one may be displayed (see Figure 4-1). In order to view and program subsequent items the Silence button must be pressed. This enables you to move through the other Zones, NAC Cadence, etc.
Example:
If the Zone 1 Options is displayed (see Figure 4-1) and you want to program zone 2 options, press the
button.
Figure 4-1 Extended Programming List Access Example
The display will add brackets around the zone number (see Figure 4-1). To move to the next zone number press the right arrow to go forward through the zone numbers or the left arrow to go backward through the zone numbers. Press the Silence button again to remove the bracket and lock the menu on this Zone number, NAC number, or Relay, etc.
This Feature works for the following programming options: Zone Options, NAC Cadence, User Codes, Accounts, Line Options, and SK-5280 Options.
SILENCE
4-2
Page 44
Model SK-5208 Installation Manual 151204

4.2 Programming Flow

Figure 4-2 provides an overview of the programming menu flow. Figure 4-3 through Figure 4-13 illustrate the programming flow within each option. The arrows indicate how to maneuver through programming.
Figure 4-2 Programming Overview Flow Chart
4-3
Page 45
Programming 151204

4.2.1 Zone Options

Figure 4-3 illustrates, in more detail, the programming flow when in the zone options menu.
Figure 4-3 Zone Options
4-4
Page 46
Model SK-5208 Installation Manual 151204

4.2.2 Misc System Option

Figure 4-4 illustrates, in more detail, the programming flow when in the misc system menu.
Figure 4-4 Miscellaneous System Options
4-5
Page 47
Programming 151204

4.2.3 NAC Cadence

Figure 4-5 illustrates, in more detail, the programming flow when in the NAC cadence menu.
Figure 4-5 NAC Cadence
4.2.3.1 Cadence Patterns
The cadence patterns shown in Table 4-2 can be selected for NAC outputs. Each NAC can select an output pattern. Special cadence patterns can be selected for fire drill or an auxiliary input switches used with the system.
Table 4-2: Cadence Patterns
#Name
1 Constant Output Continuous sound 2 March Code Output
3 ANSI S-3.41 Code Output
4 Single Stroke BI
5 California Code
(Patterns repeat until condition is cleared)
Pattern Description
6 System Sensor Sync. Provides Synchronization for visual and audible devices. 7 Wheelock Sync. 8 Gentex Sync. 9 Faraday Sync. 10 Amseco Sync.
4-6
Page 48
Model SK-5208 Installation Manual 151204

4.2.4 NAC Options

Figure 4-6 illustrates, in more detail, the programming flow when in the NAC options menu.
Figure 4-6 NAC Options Programming Menu
4-7
Page 49
Programming 151204

4.2.5 Relay Options

Figure 4-7 illustrates, in more detail, the programming flow when in the relay options menu.
Figure 4-7 Relay Options Programming Menu
4-8
Page 50
Model SK-5208 Installation Manual 151204

4.2.6 User Code

Figure 4-8 illustrates, in more detail, the programming flow when in the user code menu.
Figure 4-8 User Code Programming Menu
4-9
Page 51
Programming 151204

4.2.7 Account

Figure 4-9 illustrates, in more detail, the programming flow when in the account menu.
Figure 4-9 Account Programming Menu
Must The dialer MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to the primary account until it exceeds the “Account Tries” value. When the dialer has exceeded the Account Tries retry limit, it will switch to a backup account (a “Can Report” or “Yes” account, see below). If the dialer cannot report the event to any of the backup accounts, it will return to the primary account and repeat the process until it exceeds the a total of 10 attempts. When the Account Tries limit is exceeded, an Account Trouble condition is generated and a local trouble will sound.
Yes Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this account only if it
was previously unable to report the event to a Must account.
No No events in this family will ever be reported to this account.
Note: CIC and Phone number can also use special characters as described in Section 4.1.1.
4-10
Page 52
Model SK-5208 Installation Manual 151204

4.2.8 Computer Options

Figure 4-10 illustrates, in more detail, the programming flow when in the computer options menu.
Figure 4-10 Computer Options Programming Menu
Note: Computer CIC & Phone can also use special characters as described in Section 4.1.1.
4.2.8.1 Computer Code
In order to remote download to a control, the computer code programmed in the panel, and the computer code used in the downloading software must match.
! Important!
Remote downloading can only be used for Central Station Signaling Services, if this system does not meet Central Station Signaling requirements, this feature must be set to zero.
4-11
Page 53
Programming 151204

4.2.9 Line Options

Figure 4-11 illustrates, in more detail, the programming flow when in the line options menu.
Figure 4-11 Line Options Programming Menu
Note: Line prefix can also use special characters as described in Section 4.1.1.
4-12
Page 54
Model SK-5208 Installation Manual 151204

4.2.10 Misc Reporting

Figure 4-12 illustrates, in more detail, the programming flow when in the miscellaneous reporting menu.
Figure 4-12 Misc Reporting Programming Menu
4-13
Page 55
Programming 151204

4.2.11 5280 Outputs

Figure 4-13 illustrates, in more detail, the programming flow when in the SK-5280 ou tput s menu.
Figure 4-13 5280 Outputs Programming Menu
If Zones 1-10 is selected then the SK-5280 will output when alarms and troubles occur for zones 1 through 10. If Zones 11-20 is selected then SK-5280 will output when alarms and troubles occur for zones 11 through 20. If Zones 21-30 is selected then the SK-5280 will output when alarms and troubles occur for zones 21-30.
If System is selected then the SK-5280 will output as shown in Table 4-3 for the following system conditions:
Table 4-3: System Outputs
SK-5280 Output
T erminal
A1 Fire Alarm A2 Waterflow Alarm A3 Supervisory A4 Aux Alarm A5 Prealarm A6 Trouble A7 Communications Fail A8 Communicating A9 Alarm Silenced
A10 Trouble Silenced
T1 Low AC T2 Low Battery T3 Relay 1 Active T4 Relay 2 Active T5 Relay 3 Active T6 Relay 4 Active T7 NAC 1 Active T8 NAC 2 Active T9 NAC 3 Active
T10 NAC 4 Active
Output For:
4-14
Page 56
Model SK-5208 Installation Manual 151204

4.2.12 5824 Expander Options

Figure 4-14 illustrates, in more detail, the programming flow for the 5824 serial/parallel module.
Figure 4-14
Figure 4-15 5824 Programming Options Flow Chart
4-15
Page 57
Programming 151204

4.2.13 DST/Clk Options

Figure 4-16 illustrates the programming flow for the Daylight Saving Time (DST) and clock source options.
Figure 4-16 DST/Clk Options Flow Chart
4-16
Page 58
Model SK-5208 Installation Manual 151204

4.3 Programming Options

Table 4-4 list all the programming optio ns and the item s that can be mo dified within those programming option menus.
Note: Programming options that have a # in the Programming Options column have multiple programmable
components. See Section 4.1.2 for additional information.
Table 4-4: Programming Options
Programming
Option
Zone (1-30) # Options
Menu Item Choices Default Comments
Programmable through SKSS downloading software. To pro gram through On-board or remote annunciator:
1. Press * to activate.
2. Press Up or Down arrow to move through char-
Zone # Location
Zone # Type
Zone # Local
Zone # Disable
Zone # Response
Not Used Fire X Waterflow Supervisory Undefined Heat Cold Water
AC Delay
Ext. Reset
Ext. Silence
No X Zone will report when activated. Yes Local Zone, will not report when activated. No Zone cannot be bypassed. Yes X Zone can be bypassed. 1 Sec X 4 sec 16 sec 40 sec
acter set.
3. Press Left or Right arrow to move cursor to desired character location.
4. Repeat steps 2 and 3 until location name is entered.
5. Press Enter when the desired location name is complete.
Will generate an AC Trouble for either an open or shorted input. The report to the receiver will be delayed until the AC Delay timer expires. (See Section 4.2.10 for AC Delay Time programming.)
A shorted input will reset active alarms. This type of zone is local only. No troubles will be reported to the central station receiver.
A shorted input will silence alarms and troubles. This type of zone is local only. No trou bles will be reported to the central station receiver.
4-17
Page 59
Programming 151204
Table 4-4: Programming Options
Programming
Option
Zone (1-30) # Options
Misc System
Menu Item Choices Default Comments
Note: Alarm verification feature must not
None X
be used if the FACP is being used for releas­ing.
Smoke verification for zones with 2- or 4-wire
Smoke
Prealarm
Verify # Options
Zone # Auto Sil
Zone # Man Sil
Zone # NAC
Zone # Relay
Prealarm Time
Sound Prealarm
Auto Silence
Latch Supervise
Class A Zone
5235 Keypads _ _ _ _ _ _
Crossalert A Crossalert B Interlock A Interlock B Manual Release A Manual Release B
Enhanced Smoke
No X
Yes
No
Yes X
_ _ _ _
_ _ _ _ Enter a value from 0
to 60 No Yes X 5235 and on-board PZTs will sound for prealarms. Enter a value from 0
to 60 No X Supervisory type zones will self restore. Yes 1
2
40 seconds
8 minutes
Class A.
detectors. Do not use any other type of device on this circuit if Smoke Verification is selected.
Activated zone will start a prealarm timer that counts down from a user programmed value (see Section 4.2.2 for prealarm time programming). If the timer reaches zero before the panel is reset, a general alarm will then be sounded.
See Section 5.5.
See Section 5.5. Smoke verification for zones with 2-wire detectors
and contact type devices, such as pull stations, used on the same circuit. If the alarm current is greater than 78 mA, the smoke verification cycle will not occur.
Alarm sounds for this zone cannot be automatically silenced.
Alarm sounds for this zone can be automatically silenced.
Alarm sounds for this zone cannot be manually silenced.
Alarm sounds for this zone can be manually silenced.
Select the number of each NAC to operate with this zone in alarm.
Select the number of each Relay to operate with this zone in alarm.
Enter time duration for prealarm verification.
No on-board or 5235 remote PZT sound for prealarms.
This feature selects the time in minutes in which the NAC will automatically silence. 0 = no automatic silence
Supervisory type zones must be reset after any supervisories conditions.
Touchpad numbers that are selected here will be supervised.
4-18
Page 60
Model SK-5208 Installation Manual 151204
Table 4-4: Programming Options
Programming
Option
5217 Expanders
Misc System (cont.)
NAC (1-4) # Cadence
NAC Options
Plex Door
Silence NAC _ _ _ _
Fire NAC 1 2 3 4
Prealarm NAC _ _ _ _
Aux NAC _ _ _ _
Waterflow NAC 1 2 3 4
Supervisory NAC _ _ _ _
Crossalert A NAC _ _ _ _
Release A NAC _ _ _ _
Crossalert B NAC _ _ _ _
Release B _ _ _ _
Trouble NAC _ _ _ _
Direct Conn NAC _ _ _ _
NACs With EOL 1 2 3 4
Menu Item Choices Default Comments
1 Enables zones 11-20. 2 Enables zones 21-30 No X If Yes is selected you are not required to enter a
Code for operator level functions, such as Reset,
Yes
Constant Additional cadence patterns are programmable March Code ANSI S-3.41 Code All NACs Single Stroke BI California Code System Sensor Sync. Wheelock Sync. Gentex Sync. Faraday Sync. Amseco Sync.
No NACs selected
All NACs selected
No NACs selected
No NACs selected
All NACs selected
No NACs selected
No NACs selected
No NACs selected
No NACs selected
No NACs selected
No NACs selected
No NACs selected
All NACs selected
Silence, and Display Event History. Note: If this option is enabled, the PLEX-2 accessory must be installed on the control panel.
only through down loading software. See also Section 4.2.3.
If number is selected that NAC may be silenced.
If number is selected that NAC will activate for any fire alarm.
If number is selected that NAC will activate during the prealarm timer countdown.
If number is selected that NAC will activate for undefined, heat, cold, and water alarms.
If number is selected that NAC will activate for waterflow alarms.
If number is selected that NAC will activate for sprinkler supervisories.
If you have a single zone, that is programmed for crossalarm verification, in alarm, all NAC output select for this option will activate.
Activates during the group “A” releasing action. This circuit would be connected to a UL listed releasing solenoid. See Table 5-4 for compatible solenoids.
If you have a single zone, that is programmed for crossalarm verification, in alarm, all NAC output select for this option will activate.
Activates during the group “B” releasing action. This circuit would be connected to a UL listed releasing solenoid. See Table 5-4 for compatible solenoids.
If number is selected that NAC will activate for any trouble condition.
for alarms when using the 5220 module for city box or polarity reversal. Corresponding relay number will automatically be selected.
If number is selected that NAC output must be supervised with an 4.7 k UL listed EOL.
4-19
Page 61
Programming 151204
Table 4-4: Programming Options
Programming
Option
NAC Options Fire Drill NAC 1 2 3 4
Relay Options
User (1-10) # Code
Menu Item Choices Default Comments
Silence Relay _ _ _ _
Fire Relay 1 _ _ _
Prealarm Relay _ _ _ _
Aux Relay _ _ _ _
Waterflow Relay _ _ _ _
Superv Relay _ _ _ _
Crossalert A Relay _ _ _ _
Release A Relay _ _ _ _
Crossalert B Relay _ _ _ _
Release B Relay _ _ _ _
Trouble Relay _ _ _ 4 X
Fire Drill Relay 1 _ _ _
AC Trbl _ _ _ _
Installers
Code # Type
User # Code
Operators 1111 Not Used Enter 3 to 6 digit
number
All NACs selected
No Relays selected
Relay 1 selected
No Relays selected
No Relays selected
No Relays selected
No Relays selected
No Relays selected
No Relays selected
No Relays selected
No Relays selected
Relay 1 selected
No Relays selected
5208 and 123456
If number is selected that NAC will activate during a fire drill.
If a relay is selected, that relay can be silenced for Trouble and Supervisory conditions only. (This includes relays programmed for AC Trbl.)
If a relay is selected, that relay will activate for fire alarm conditions.
If a relay is selected, that relay will activate for prealarm conditions.
If a relay is selected, that relay will activate for Auxiliary conditions.
If a relay is selected, that relay will activate for waterflow conditions.
If a relay is selected, that relay will activate for supervisory conditions.
If a relay is selected, that relay will activate for crossalarm conditions.
If selected will activate for releasing group “A”.
If a relay is selected, that relay will activate for crossalarm conditions.
If selected will activate for releasing group “B”.
Relay will be activated when no troubles exist and will deactivate when a trouble condition occurs.
If a relay is selected, that relay will activate for fire drills.
If a relay is selected, that relay will be activated when AC is normal and will deactivate when a Low AC condition exists.
Enter any value from 001 to 999999.
4-20
Page 62
Model SK-5208 Installation Manual 151204
Table 4-4: Programming Options
Programming
Option
Account (1-4) #
Computer Options
Menu Item Choices Default Comments
1: 105208
Account <#> #
CIC <#> # Enter up to 8 digits
Phone <#> # Enter up to 16 digits See Section 4.1.1 for special characters.
Account # Format
Account # Tries 1 to 5 3
Report # Alarm
Report # Restore
Report # Trouble
Report # Test
Computer Account Enter 6-digit number 505208
Computer CIC Up to 8 digits.
Computer Phone up to 16 digits See Section 4.1.1 for special characters.
Enter a 6-digits number
SIA8 X SIA20 Contact ID SK4/2 1400 3/1 1400 3/1 2300
No X Do not report alarm events. Yes Can report alarm events. Must Must report alarm events. No X Do not report alarm restores. Yes Can report alarm restores. Must Must report alarm restores.
No X
Yes
Must
No X
Yes
Must
2: 205208 3: 305208 4: 405208
Enter any value from 000001 to 999999. Account numbers with less than 6 digits must use leading zeros. For example, if the code 321 is used, it must be entered as 000321.
Carrier Identification Code is the prefix that needs to be dialed before a phone number to access a particular long distance carrier. Use special characters to add pauses, #, *, and “2nd dial tone” characters into the phone number. See Section
4.1.1 for special characters.
Do not report sprinkler supervisory, system troubles, zone troubles, zone bypasses, and zone restores.
Can report sprinkler supervisory, system troubles, zone troubles, zone bypasses, and zone restores.
Must report sprinkler supervisory, system troubles, zone troubles, zone bypasses, and zone restores.
Do not report manual test, auto test, downloading pass, downloading fail, data lest, and walk test.
Can report manual test, auto test, downloading pass, downloading fail, data lest, and walk test.
Must report manual test, auto test, downloading pass, downloading fail, data lest, and walk test.
Enter any value from 000001 to 999999. Account numbers with less than 6 digits must use leading zeros. For example, if the code 321 is used, it must be entered as 000321.
Carrier Identification Code is the prefix that needs to be dialed before a phone number to access a particular long distance carrier. Use special characters to add pauses, #, *, and “look for second dial tone” characters into the phone number. See Section 4.1.1 for special ch aracters.
4-21
Page 63
Programming 151204
Table 4-4: Programming Options
Programming
Option
Computer Options
Line (1-2) # Options
Misc Reporting
Menu Item Choices Default Comments
The computer code must match the computer code
Computer Code 1 to 6 digits 0
Not Used X This disables the phone line.
DTMF/USA Rotary
USA Rotary Only
Line # Dial Type
Line # GS
Line # Rings 0 - 15
Line # Ans Mach
Line # Prefix Up to 8 digits See Section 4.1.1 for special characters. Test Time 00:00 - 23:59 12:00
Te st Interval
AC Delay 0-30 Hours 2
Report Walk Test
DTMF Only Attempts 1 through 10 will be DTMF only.
DTMF/Euro Rotary
Euro Rotary Only No X Yes enables Ground Start phone functions. A Yes
Line 1: 2 Line 2: 10
No X
Yes
Every 4 Selects the period to which the system performs an Every 6 Every 12 Every 24 X
No X
By Zone
in the remote downloading computer in order to perform a remote download. See also Section
4.2.8.1.
Attempts 1 through 6 will be DTMF, then the dialer will alternate between Rotary and DTMF for attempts 7 through 10, Rotary Make/Break ratio is 40/60.
Attempts 1 through 10 will be Rotary only, with a Make/Break ratio of 40/60.
Attempts 1 through 6 will be DTMF, then the dialer will alternate between Rotary and DTMF for attempts 7 through 10, Rotary Make/Break ratio 33/67.
Attempts 1 through 10 will be Rotary only, with a Make/Break ratio of 33/67.
ground start relay (Model 5211) is required if this feature is enabled (see Figure 3-2).
Number of rings before the panel will answer an incoming telephone call.
This feature is used in installations where an answering machine is on the same phone line that the control panel is on. The answering machine may interfere with a computer download.
When enabled (Y es) the computer calls the control panel and the phone line rings twice, hangs up and calls again (within 10 to 60 seconds). When the control panel see two more rings on the phone line it will answer and acknowledge the calling computer.
Selects the time of day the control will send an automatic test signal to a central station receiver.
Automatic Self Test, keyed off the Test Time.
Selects the delay time (in hours) before the control will report an AC power loss to the central station.
No zone information will be reported just test begin and test end.
Test begin, test end, and all event s in betwee n will be reported to central station.
4-22
Page 64
Model SK-5208 Installation Manual 151204
Table 4-4: Programming Options
Programming
Option
Misc Reporting
5280 (1 - 8) # Outputs
5824 Expander
Menu Item Choices Default Comments
*3/1 Alarm
*3/1 Alarm Rst 2 *3/1 Supervisory 6 Sprinkler supervisories.
*3/1 Restore 7
*3/1 Trouble 8 *3/1 Test 9 All test events.
5280 #
5824 ID 0 - 7 0
Event Log
Prn Off Line 0 - 30 Seconds 20
Serial Prn
Baud Rate
Data Bits
Stop Bits
0 - 9 * Event code for 3/1 and 4/2 reporting formats.
Not Used X Zones 1_10 Zones 11_20 Zones 21_30 System
Yes X If yes then all events are sent to the printer. No
Yes X If yes is selected then data is sent to the serial port. No 9600 X Select the Baud rate at which your printer requires
19.2K 75 110
134.5 150 300 600 1200 2000 2400 4800 1800 8 X Select the number of data bits that your printer 5 6 7 1 X Select the number of stop bits that your printer 2 0
0
Alarms for Fire, Waterflow, Undefined, Heat, Cold, and Water events.
Alarms restores for Fire, Waterflow, Undefined, Heat, Cold, and Water events.
Restore reports for Troubles, Supervisories, and unbypasses. The only exceptions are the restores listed as alarm restores.
All system and zone troubles, and zone/NAC bypasses, and NACs troubles.
Sets the serial bus address for the 5824. Use a 0 to disable this feature.
Selects the number of seconds the printer can be off line before a trouble is generated.
If no is selected then data is sent to the parallel port.
to communicate properly. Consult installation manual for the printer you are using.
requires for proper communication. Consult installation manual for your printer.
requires for proper communication. Consult installation manual for your printer.
4-23
Page 65
Programming 151204
Table 4-4: Programming Options
Programming
Option
5824 Expander Parity
DST/Clk Options
* This option is not recognized by the panel until January 1, 2007. Before January 1, 2007, the panel will recognize the values
described above in the Auto DST Adjust option.
Menu Item Choices Default Comments
None X Select the Parity that your printer requires for Even Odd
60 Hz X
Clock Source
Auto DST Adjust
DST Start (Wk)*
DST Start (Mo)* Jan – Dec Mar
DST End (Wk)*
DST End (Mo)* Jan – Dec Nov
50 Hz
Internal
No X No automatic clock adjust for Daylight Saving.
Yes
1st Sunday Setting determines the week of the month in which 2nd Sunday X 3rd Sunday 4th Sunday
Last Sunday
1st Sunday X Setting determines the week of the month in which 2nd Sunday 3rd Sunday 4th Sunday
Last Sunday
proper communication. Consult installation manual for your printer.
The panel’s AC lin e frequency is selectable for 60, 50 Hz, or Internal. AC Frequency feature dictates how the control panel will calculate time based on
the AC line frequency used in the installation site. The “Internal” option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate time from the internal
crystal. The internal crystal is not as accura te as the AC power source and either 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz. selection
Automatically changes system clock between Daylight Saving Time (DST) and standard time. Before January 1, 2007, the system clock will switch to DST on the first Sunday in April at 2:00 a.m. and will revert to standard time on the last Sunday in October at 2:00 a.m. On January 1, 2007, the system clock will be adjusted according to the values set in the DST Start (Wk and Mo) and DST End (Wk and Mo) options. Default values for these fields match federal law: DST begins on the second Sunday in March at 2:00 a.m. and reverts to standard time on the first Sunday of November at 2:00 a.m.
Daylight Saving Time is to start. If you always want the change to occur on the last Sunday of the month, select the Last Sunday option regardless of whether there are four or five Sundays in the month.
Setting determines the month in which Daylight Saving Time is to end.
Daylight Saving Time is to end. If you always want the change to occur on the last Sunday of the month, select the Last Sunday option regardless of whether there are four or five Sundays in the month.
Setting determines the month in which Daylight Saving Time is to start.
4-24
Page 66
Section 5
Normal Operation
User Operations
Enabled
Note: The key can not be removed when in the user operations position.
Installer Key: Perform user
operations without a user
code and open panel door.
User Key: Perform user
operations without a user
code.
Operation
To operate the SK-5208 you can use either the on-board touchpad or the Model SK-5 235 Remote Annunciator.
151204
Important! Upon initial power up there is a 45 second delay before the initiation circuits become active.
The system will be ready to receive alarms once the display indicates “System Normal

5.1 Installer & User Keys

An installer key ships with the panel and an operator’s key ships with the SK-5235 (Figure 5-2). The installer key opens the panel door and can be used to perform user operations without a user code at the panel and the SK-5235. The operator’s key can be used to perform user operations without a user code but will not open the panel door. All installer operations require an installer code. To perform user operations without a user code, insert and turn the key as shown in Figure 5-2. See Table 5-1 for a list of user and
installer operations.
Figure 5-1 Model SK-5235 Remote Annunciator
Figure 5-2 Keys & Key Operation
5-1
Page 67
Operation 151204

5.2 On-board Touchpad and SK-5235 Operation

Basic operations for the on-board annunciator (touchpad) and SK-5235 are described in Table 5-1. If you are using an annunciator key or the Flex Door option, you are not required to enter a code for operator level functions.
If no keys are pressed for 4 minutes while in program mode, the system will time out and resume normal operation.
Table 5-1: Basic Panel Operations Using the On-Board Annunciator and the SK-5235
Do This
How To
Test the system
Reset Alarms
Clear History
Reset the Dialer Call Computer to Up/
Download Display History
Events
Show Status Silence Troubles or
Alarms
Set the Date
Set the Time Disable/Enable a
Zone Disable/Enable NAC
Conduct a Fire Drill
Reset Detectors
Walk Test the System
Menu of Options
0 ENTER
1 ENTER or RESET Reset Alarm
2 ENTER Clear History
3 ENTER Reset Dialer
4 ENTER Call Computer
5 ENTER
6 ENTER Show Status
7 ENTER or SILENCE Silence
8 ENTER
9 ENTER Set Time
Zone # + * Disable Zone
10 NAC # * Disable NAC
20 ENTER Fire Drill
21 ENTER Rst Smk Pwr
22 ENTER Walk Test
Press or to scroll through list.
Press
* Code = any valid operator or installer code.
Display
Message
System Test Enter Code
Enter Code
Enter Code
Enter Code
Enter Code History Events
Enter Code
Enter Code
Enter Code Set Date
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Press*
Enter Code
Enter Code Enter Installer
Code Enter Code Enter Installer
Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
Enter Code
System performs a display lamp test, a communication test, and displays the firmware number and revision. See 5.2.1 for an example. Resets system.
Clears event history of all events.
Resets the dialer and aborts the cal l to central station. Will dial the programmed phone number for the computer to initiate an up or download. Displays panel history, including alarms, supervisories, troubles, reports, time and date changes, etc. View exis ti ng system status. List Alarms first, supervisories and then troubles.
Enter 8 digits for the date. For example, to set the date 08/31/1999 enter 08311999. Press # to clear incorrect entries. Enter the time in 24 hour increments. For example, 1:00 pm = 13:00. Repeat the process to enable the zone.
Repeat the process to enable the NAC.
To End the Fi re Dr ill pres s RESE T then code.
Resets all smoke detector power.
To En d the Walk Test press REST.
To exit press ENTER or wait 15 seconds.
Comments

5.2.1 View Control Panel Firmware Number and Revision

When 0 ENTER and the code is entered The system will perform a display lamp test and a communication test.
5-2
Page 68
Model SK-5208 Installation Manual 151204
Control Firmware Number
Dialer Firmware Number
Revision
Revision
Also displays Firmware number and revision as shown in Figure 5-3.
Figure 5-3 Firmware Numbers and Revisions

5.3 Acknowledge Operation

To display an event, first press the ENTER, while the event is displayed the event can be acknowledged by pressing the ENTER button again. No code is required to acknowledge events. The status LEDs (Alarm, Supervisory and Trouble) will flash when an un-acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory , or T rouble LED) stop flashing and turn on steady. When viewing system status the LCD displays “Acked” for each individual event once has been acknowledged. The control panel piezo will silence after all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been
acknowledged. Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the history buffer will be preceded with an asterisk “*”.

5.4 LED Indicators

Five light emitting diodes (LEDs) appear in the SK-5208 built in annunciator and remote annunciator. The chart below explains the meaning of these LEDs.
Table 5-2
LED Status Condition
Off Normal condition
ALARM (red)
SUPERVISORY (yellow)
TROUBLE (yellow)
SILENCED (yellow)
AC (green)
On System in alarm and all alarms have been acknowledged. Flashing LED will flash when a alarm condition exists that has not been acknowledged. Off Normal condition On If a supervisory condition exist on the system. Flashing LED will flash when a supervisory condition exists that has not been acknowledged. Off Normal condition On Trouble condition exists Flashing LED will flash when a trouble condition exists that has not been acknowledged. Off Normal condition. On Alarm or trouble cond ition has been silenced but condition still exists. On Panel is running on AC (normal condition); standby battery fully charged. Off Panel has lost all power. Flashing Panel is running on battery power only or AC power only.
5-3
Page 69
Operation 151204

5.5 Releasing Operation

This system can perform two types of releasing operation, cross alarm releasing, and double interlock releasing operations. Install in accordance with NFPA 72 paragraphs 3-8.3.2.3.3 and 3-8.3.2.3.3.2.

5.5.1 Cross Alarm Operation

The fire alarm control panel has two cross alert groups to select from, Cross Alert A and Cross Alert B that accommodate releasing water systems.
When two or more zones are programmed to one of these groups then a single activation of one zone in the group will cause a cross alert condition at the local annunciator and the pre-alert signal output for that group. (Note: the local annunciator and the pre-alert signal will continue to sound until it is silenced or until another cross alarm zone within the same group activates.) If a second zone in the same group activates then both will become active alarm zones.
If the second zone is not in the same group as the first zone then the cross alert zone will remain in the cross alert condition and the system will signal the second by how it is programmed.
The fire alarm control panel has four NAC and relay options that allow NACs and relays to be selected to indicate the cross alert condition and assign release circuits for each group.
5.5.1.1 Default NAC Settings for Releasing
When “Cross Alert A” is selected in “Zone Options” the NACs are defaulted to the following settings:
NAC 1 Releasing Circuit NAC 3 Pre-Alert Signal Cir cuit NAC 4 General Alarm Circuit
When “Cross Alert B” is selected in “Zone Options” the NACs are defaulted to the following settings:
NAC 2 Releasing Circuit NAC 3 Pre-Alert Signal Cir cuit NAC 4 General Alarm Circuit
Table 5-3: Cross Alarm Operation
Inputs Output Results
Cross Zone 1 Cross Zone 2 Pull Station
XXXX
XX XX
XXXX
Normal
Pre-Alert
Pre-Alert
Release and
General Alarm
Release and
General Alarm
Release and
General Alarm
Release and
General Alarm
Release and
General Alarm
5-4
Page 70
Model SK-5208 Installation Manual 151204
A Model 7641 EOL resistor/diode assembly is required when connecting the FACP to releasing solenoids. The 7641 allows the FACP to supervise the wiring between its NACs and the releasing solenoid.
Table 5-4: Approved Releasing Solenoids
Manufacturer Part Number Rating
Asco
T8210A107 24 VDC, 16.8 W 8210G207 24 VDC, 10.6 W
Figure 5-4 Solenoid Wiring Configuration
Do not mix cross alarming zones with smoke verification zones. There must be at least two automatic detection devices in each protected space. Spacing must be reduced to 0.7 tines the linear spacing in accordance with NFPA72. See Section 4.2.1 for zone option programming.
Figure 5-5 is an example of how cross alarming may be programmed.
Figure 5-5 Example Showing Smoke Detector Cross Alarm Application
5-5
Page 71
Operation 151204

5.5.2 Double Interlock Releasing Operation

A typical double interlock releasing system would be programmed with a minimum of two zones selected for “Cross Alert A”, one zone selected as “Man. Release A”, and one selected as “Interlock A”. Additional zones can be selected as Cross Alert or Manual Release.
This double interlock system requires both cross alert and manual release verification zones. A single manual release and interlock zone can be used without any cross alert zones. In this system configuration an active manual release and the interlock zone is required to initiate the release.
Table 5-5 illustrates what will cause a Pre-alert, General Alarm, and a Release.
Table 5-5: Double Interlock Operation
Inputs Output Results
Cross Zone 1 Cross Zone 2 Manual Release A Interlock
If no zones are selected for “Interlock” verification then the system will operate as a standard cross alarm releasing system (see Section 5.5.1).
See Section 5.5.1.1 for default NAC settings for releasing systems.
XXXXXXXX
XX XX XX XX
XXXX XXXX
XXXXXXXX
Normal
Pre-Alert
Pre-Alert
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
General Alarm
Release and General Alarm

5.6 Smoke Alarm Verification

Release and General Alarm
Release and General Alarm
Release and General Alarm
Release and General Alarm
Figure 5-6 illustrates how the Smoke Alarm Verification cycle operates.
Figure 5-6 Smoke Verification Cycle
During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
5-6
Page 72
Model SK-5208 Installation Manual 151204

5.7 System Testing

This section describes operation of fire drills, zone testing, and the 24-hour automatic test.

5.7.1 Fire Drills

Fire drills can be run from either the on-board touchpad or the Model SK-52 35 Remote Annunciator. To initiate a fire drill, press 20 ENTER + Code. The system will sound an alarm and report a fire test. To end the fire drill, press
RESET + Code.

5.7.2 Walk Test

The walk test is designed to be used for on-site testing only. To enter walk test mode, press 22 ENTER Select the following test parameters:
T est Feature Enable or Disable Comments
Use Verify: Yes or No If Yes is selected then this option will be enabled during Mapped Rlys: Yes or No Mapped NACs: Yes or No
The LCD will indicate that you are in walk test mode. When a zone is tripped, the SK-5208 will activate the bell outputs for approximately six second and will cycle smoke power off and on for the programmed time interval. When smoke power is restored, there is a two-second power up delay before the zone will respond to additional test inputs.
The system will time out and resume normal operation in 30 minutes if no keys are pressed or no zones are tripped during the walk test.
To exit walk test mode, press
RESET.
+ Installer Code.
walk test. If No is selected this option will be disabled during walk test.

5.7.3 Automatic Self Test

The Model SK-5208 lets you select the time of day and the interval that the automatic that the test signal will be sent to the central station. See Sections 4.2.10 and 4.3 for additional information on automatic test time.

5.7.4 Watchdog Circuit

During normal operation, the control microprocessor of the SK-5208 is constantly running programs to check inputs and carry out other routine functions. If the program should ever stop running, the watchdog circuit will automatically detect this and attempt to resume normal operation by resetting the microprocessors. Each time the watchdog circuit initiates a reset signal, it will also sound the audible trouble signal for approximately four seconds.

5.8 Communicating with a Programming Computer

An installer at the panel site can initiate communications between the panel and a computer running the Silent Knight Software Suite SKSS. In order for this communication to function properly both the computer (running the software) and the control panel must have matching computer account numbers and computer access codes.
Before you program in this location you should know how your control panel will commu nicate wi th the downloading computer, either through direct connect (RS232) or via the phone lines (Internal Modem).
5-7
Page 73
Operation 151204
Download Menu Upload Menu

5.8.1 Programming From a Remote Computer Location

The panel can communicate with a Up/Downloading computer using two methods. The control panel can call the programming computer or the programming computer can call the control panel.
The programming information for the control panel will be stored in the queue of the downloading software SKSS P/N 5660. This data packet will have been pre-configured for the control panel that you are about to program. SKSS is available to download on www.silentknight.com. For more information also see SKSS Installation Manual P/N 151240.
5.8.1.1 Having the Control Panel Call the Remote Computer
If the panel initiates the call to a downloading computer, a phone number must be pr ogrammed in the computer accounts area (see Section 4.2.8).
To initiate communication:
1. From the SKSS Up/Downloading software File Menu, select the download or upload menu item you want to perform.
2. In the appropriate locations in the dialog box, enter your information.
3. When ready, select “Wait for Call” in the “Call how often” drop down list.
4. Press “OK” to stage SKSS for an Up/Download.
5. Press the 4 ENTER or the ^ up arrow until the display reads Call Computer.
6. Enter the Installer Code.
The control panel will then begin the communication process with the remote computer.
5.8.1.2 Having Remote Computer Call the Control Panel
If the computer initiates the call then answering machine bypass (see Section 4.2.8) may need to be selected. To initiate communication:
1. From the SKSS Up/Downloading software File Menu, select the download or upload menu item you want to schedule.
2. In the appropriate locations in the dialog box, enter your selections for the following options: File Name:To download, select the file that you want to download. To upload assign a name to the file that
will be uploaded from the panel. You can use the Browse option to select from the list of available files. If
5-8
Page 74
Model SK-5208 Installation Manual 151204
To Computer Serial Port
you do not select a name for the file, it will be automatically named with the panel model and the date and time of the download.
For downloads, the latest saved version of the file will be sent. This means if the file you want to send is
currently open and has been changed, save it before you attempt to download. Account Number:Enter the panel account number. Computer Code:Enter the code that allows access to the panel from a PC. Phone Number:Enter the panel phone number. Call Option:Select how often and when the call should be placed. Answering:Select the preferred options if the phone line used by the control panel has an answering machine
installed. This feature is not used when connecting directly to a panel.
3. Click OK to begin downloading/uploading or to post the job to the Queue.

5.8.2 Directly Connecting to a Programming Computer

The control panel can be up or downloaded from a computer that is directly connected to the control panel.
Note: This connection is to be used as a temporary connection and should be disconnected after programming is
completed.
To initiate communication:
1. Connect a serial cable from the control panel to the computer.
2. Make sure SKSS software is running and that the up/download task is in the queue, by selecting the Call Option to “Wait for Call”.
3. Initiate an up/download from SKSS
The control panel will then begin the communication process with the computer.
5-9
Page 75

Section 6 Reporting

The SK-5208 can transmit information in four different formats. This section describes the four basic reporting formats of the SK-5208 and the codes that they send to a central station receiver. Of these four formats some of the formats offer a more specific selection for that format. For example, you can select a 3/1 format that requires a 1400 or 2300 Hz handshake, or SIA format that can handle 8 or 20 events per call. Selecting the correct format depends on the type of receiver that will receive calls from the SK-5208.
The SK-5208 DACT is compatible with Silent Knight Model 9800 and 9500 Digital Receivers.

6.1 Reporting Formats

This section gives a description of each of the SK-5208 reporting formats. Refer to Table 6-1.
Table 6-1: Reporting Formats Descriptions
Format Name
Category
Name
3/1
4/2 SK4/2 1400
SIA
Contact ID Contact ID
Programming
Name
3/1 14
3/1 23
SIA8
SIA20
Old format, transmits a 3-digit account number and a 1-digit event code. Transmissions are acknowledged at 1400 Hz.
Old format, transmits a 3-digit account number and a 1-digit event code. Transmissions are acknowledged at 2300 Hz.
Tone burst format, transmits a 4-digit account code and 2-digit event code. Transmissions are acknowledged at 1400 Hz.
Security Industry Association standard communication format which send a maximum of 8 events per call.
Security Industry Association standard communication format which send a maximum of 20 events per call. Up to a 6-digit account number.
Ademco Contact ID format. DTMF (Dual Tone Multiple Frequenc y) format. Send a 4-digit account number. Transmission is acknowledged at both 1400 and 2300 Hz.
Description
151204
6-1
Page 76
Reporting 151204

6.2 Reporting Codes

Table 6-2 list the events sent by the SK-5208 and the code that is sent for that event by the type of reporting format used.
Note: Codes under in the SK4/2 and 3/1 1400 & 2300 column are the codes programmed for 3/1 reporting for-
mats in Misc Reporting. See Section 4.2.10 for Misc. Reporting options and Table 6-3 for default 3/1 format reporting values.
Table 6-2: Event and Reporting Code by Format
Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID
AC Trouble AT0 T0 Trouble Code 1 301 000 AC Restore AR0 R0 Restore Code 3 301 000 Annunciator Trouble 1-7 ET17 - ET23 T7 - T3 Trouble Code 1 330 017 - 1 330 023 Annunciator Restore 1-7 ER17 - ER23 R7 - R3 Restore Code 3 330 017 - 3 330 023 Bell Trouble 1-4 ET32-ET35 T2 - T5 Trouble Code 1 330 032 - 1 330 035 Bell Restore 1-4 ER32-ET35 R2 - R5 Restore Code 3 330 032 - 3 330 035 Smoke (Loop) Power Trouble ET36 T6 Trouble Code 1 320 036 Smoke (Loop) Power Restore ET36 R6 Restore Code 3 320 036 Aux Power Trouble ET37 T7 Trouble Code 1 330 037 Aux Power Restore ER37 R7 Restore Code 3 330 037 Earth Ground Trouble ET38 T8 Trouble Code 1 330 038 Earth Ground Restore ER38 R8 Restore Code 3 330 038 Keypad Power Trouble ET40 T0 Trouble Code 1 330 040 Keypad Power Restore ET40 R0 Restore Code 3 330 040 5217 Expander Trouble ET51-ET52 T1 - T2 Trouble Code 1 330 051 - 1 330 052 5217 Expander Restore ER51-ER52 R1 - R2 Restore Code 3 330 051 - 3 330 052 5280 Expander Trouble ET61-ET68 T1 - T8 Trouble Code 1-330 061 - 1 330 068 5280 Expander Restore ER61-ER68 R1 - R8 Restore Code 3-330 061 - 3 330 068 NAC Bypass ET101-ET104 T1 - T4 Trouble Code 1-330 101 - 1 330 104 NAC Restore ER101-ER104 R1 - R4 Restore Code 3-330 101 - 3 330 104 NAC Supervisory (See Note) SS101-SS104 S1 - S4 Supervisory Code 1 203 101 - 1 203 104 NAC Supervisory Restore (See Note) SR101-SR104 R1 - R4 Restore Code 3 203 101 - 3 203 104 Fire Alarm 1-30 FA1 - FA30 A1 - A0 Alarm Code 1 110 001 - 1 110 030 Fire Bypass FB1-FB30 T1 - T0 Trouble Code 1 571 001 - 1 571 030 Fire Alarm Restore 1-30 FH1 - FH30 AR1 - AR0 Alarm Restore Code 3 110 001 - 3 110 030 Fire Test Begin FI1 - FI10 Test 0 Test Code 1 604 000 Fire Trouble Restore 1-30 FJ1 - FJ30 R1 - R0 Restore Code 3 373 001 - 3 373 030 Fire Test End FK0 Test 0 Test Code 1 604 000 Fire Restore/Clean-Me Restore FR1-FR30 R1 - R0 Restore Code 3 110 001 - 3 110 030
Note: These reports are sent for Notification Appliance Circuits that are programmed for releasing operation.
6-2
Page 77
Model SK-5208 Installation Manual 151204
Table 6-2: Event and Reporting Code by Format
Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID
Fire Trouble/Clean-Me Trouble 1-30 FT1 - FT30 T1 - T0 Trouble Code 1 373 001 - 1 373 030 Fire Unbypass FU1-FU30 R1 - R9 Restore Code 3 571 011 - 3 571 030 Heat Alarm KA1-KA30 A1 - A9 Alarm Code 1 114 001 - 1 1 14 030 Heat Bypass KB1-KB30 T1 - T0 Trouble Code 1 570 011 - 1 570 030 Heat Alarm Restore KH1-KH30 AR1 - AR0 Alarm Restore Code 3 114 001 - 3 114 030 Heat Trouble KT1-KT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030 Heat Trouble Restore KJ1-KJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030 Heat Restoral KR1-KR30 R1 - R0 Restore Code 3 370 001 - 3 370 030 Heat Unbypass KU1-KU30 R1 - R0 Restore Code 3 570 001 - 3 570 030 Trouble Phone Line #1 LT1 T1 Trouble Code 1 351 000 01 Restore Phone Line #1 LR1 R1 Restore Code 3 351 000 01 Trouble Phone Line #2 LT2 T2 Trouble Code 1 352 000 02 Restore Phone Line #2 LR2 R2 Restore Code 3 352 000 02 Automatic Test (Normal) RP0 Test 0 Test Code 1 602 000 Automatic Test (Abnormal) RY0 Test 9 Test Code 1 608 000 Power Up RR0 T0 Test Code 1 305 000 Downloading Passed RS0 Test 0 Test Code 1 412 000 Data Lost RT0 Test 0 Trouble Code 1 354 000 Downloading Failed RU0 Test 0 Test Code 1 413 000 Manual T est RX1-RX10 Test 1 - Test 0 Test Code 1 601 001 - 1 601 010 Sprinkler Alarm SA1-SA30 A1 - A0 Alarm code 1 113 001 - 1 113 030 Sprinkler Bypass SB1-SB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030 Sprinkler Alarm Restore SH1-SH30 AR1 - AR0 Alarm Restore Code 3 113 001 - 3 113 030 Sprinkler Trouble Restore 1-30 SJ1 - SJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030 Sprinkler Supervisory Restore 1-30 SR1 - SR30 R1 - R0 Restore Code 3 203 001 - 3 203 030 Sprinkler Supervisory 1-30 SS1 - SS30 S1 - S0 Supervisory Code 1 203 001 - 1 203 030 Sprinkler Trouble 1-30 ST1 - ST30 T1 - T0 Trouble Code 1 370 001 - 1 370 030 Sprinkler Unbypass 1-30 SU1-SU30 R1 - R0 Restore Code 3 570 001 - 3 570 030 Untyped Zone Alarm 1-30 UA1-UA30 A1 - A0 Alarm Code 1 140 001 - 1 140 030 Untyped Bypass 1-30 UB1-UB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030 Untyped Alarm Restore 1-30 UH1-UH30 AR1 - AR9 Alarm Restore Code 3 140 001 - 3 140 030 Untyped Trouble Restore 1-30 UJ1-UJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030 Untyped Zone Trouble 1-30 UT1-UT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030 Untyped Zone Unbypass 1-30 UU1-UU30 R1 - R0 Restore Code 3 570 001 - 3 570 030 Water Alarm 1-30 WA1-WA30 A1 - A0 Alarm Code 1 154 001 - 1 154 030
6-3
Page 78
Reporting 151204
Table 6-2: Event and Reporting Code by Format
Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID
Water Bypass 1-30 WB1-WB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030 Water Alarm Restore 1-30 WH1-WH30 AR1 - AR0 Alarm Restore Code 3 154 001 - 3 154 030 Water Trouble Restore 1-30 WJ1-WJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030 Water Trouble 1-30 WT1-WT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030 Water Unbypass 1-30 WU1-WU30 R1 - R0 Restore Code 3 570 001 - 3 570 030 Communications Failure Line #1 YC1 T1 Trouble Code 1 354 001 Communications Restore Line #1 YK1 R1 Restore Code 3 354 001 Communications Failure Line #2 YC2 T2 Trouble Code 1 354 002 Communications Restore Line #2 YK2 R2 Restore Code 3 354 002 System Battery Restore YR0 R0 Restore Code 3 302 000 System Battery Trouble YT0 T0 Trouble Code 1 302 000 Cold Alarm 1-30 ZA1-ZA30 A1 - A0 Alarm Code 1 153 001 - 1 153 030 Cold Bypass 1-30 ZB1-ZB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030 Cold Alarm Restore 1-30 ZH1-ZH30 AR1 - AR0 Alarm Restore Code 3 153 001 - 3 153 030 Cold Trouble Restore 1-30 ZJ1-ZJ30 R1 - R0 Restore Code 2 370 001 - 3 370 030 Cold Trouble 1-30 ZT1-ZT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030 Cold Unbypass 1-30 ZU1-ZU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
6-4
Page 79
Model SK-5208 Installation Manual 151204

6.2.1 Default Settings for 3/1 Format

Table 6-3 displays the default settings which are set in the Misc. Reporting section of Prog ramming.
Table 6-3: Default Settings for 3/1 Format
Programming
Option
Misc Reporting
Menu Item Choices Default Comments
Selects the time of day the control will send an
Test Time 00:00 - 23:59 12:00
Every 4 Selects the period to which the system
Te st Interval
AC Delay 0-30 Hours 2
Report Walk Test
*3/1 Alarm
*3/1 Alarm Rst 2 *3/1 Supervisory 6 Sprinkler supervisories.
*3/1 Restore 7
*3/1 Trouble 8 *3/1 Test 9 All test events.
Every 6 Every 12 Every 24 X
No X
By Zone 0 - 9
* Event code for 3/1 and 4/2 reporting formats.
0
automatic test signal to a central station receiver.
performs an Automatic Self Test, keyed off the Test Time.
Selects the delay time (in hours) before the control will report an AC power loss to the central station.
No zone information will be reported just test begin and test end.
Test begin, test end, and all events in between will be reported to central station.
Alarms for Fire, Waterflow, Undefined, Heat, Cold, and Water events.
Alarms restores for Fire, Waterflow, Undefined, Heat, Cold, and Water events.
Restore reports for Troubles, Supervisories, and unbypasses. The only exceptions are the restores listed as alarm restores.
All system and zone troubles, and zone/NAC bypasses, and NACs troubles.
6-5
Page 80

Section 7 Troubleshooting

This section of the manual contains information that can be used to is o late and correct installation problems encountered in the field.

7.1 System Error Messages

Table 7-1 contains a list of possible error messages along with their meani ng and possible solution.
Table 7-1: Error Messages
Error Message Description Solution
FLASH Defaulted On power up the SK-5208 will check the flash for an
“option record”.
Earth Fault Trb The SK-5208 has built-in earth ground fault detection that
will detect an earth ground fault connection between earth and any panel terminal. When an earth ground fault is detected the SK-5208 display will indicate Earth Fault Trb. The SK-5208 will also add two events to the history buffer Expand Trb 38 and Earth ###. The Earth ### is a debug event number between 0 and 255.
Key BUS Trouble This message will display when communication is lost
between the 5235 and the control panel.
NAC # Trb This message indicates that a short or an open is detected
on a Notification Appliance Circuit. The # indicates which NAC has the trouble.
Remote # Trb Each 5235 can be programmed to be supervised (see
Section 4.2.2). If the SK-5208 is unable to communicate with the 5235 it will indicate this message. # indicates the ID number of the faulted touchpad.
5217 Trb # If the SK-5208 is unable to communicate with a 5217
expander it will display this message. The # indicates the ID number of the expander in trouble.
5280 Trb # If the control panel is unable to communicate with a SK-
5280 Status Display Module this message will be displayed. # indicates the ID number of the SK-5280 in trouble.
Smk Pwr Trb Smoke power terminals 11, 14, 17, and 20 are supervised.
If the voltage between circuit ground (terminals 9, 22, 26,
33) and loop power is less than 20VDC this message will display.
5235 Pwr Trb The power terminal for the 5235 is supervised and a
trouble indication will occur if the voltage between circuit ground and terminal 32 drops below 20 VDC.
If an “option record” is not found during power up, one will be created and the display will indicate “Flash Defaulted” for approximately one second.
See Section 7.2 for earth ground fault troubleshooting procedure.
Check for a short or an open on either the SKI or SKO terminals.
Check for a short or an open on the indicated NAC wire run.
Check the wire connections between the indicated touchpad and the control panel.
Check all wire connections between the control panel and the 5217 expander in trouble.
Check all wire connections between the control panel and the SK-5280 in trouble.
This may occur when the maximum current draw for the initiation circuit is exceeded. See Section 3.1 1 for initiation circuit current requirements.
This may occur if the maximum current rating (1Amp) for this circuit is exceeded.
151204
7-1
Page 81
T roubleshooting 151204
Table 7-1: Error Messages
Error Message Description Solution
Aux Pwr Trb The SBUS power terminal (27) is supervised and will
display this message when the voltage between SBUS power and circuit ground drops below 20 VDC.
AC Trb This message is displayed when the AC voltage drops
below 98 VAC.
Battery Trb This message will be displayed when the battery voltage
drops below 20.4 VDC under load. The control panel performs a load test every minute.
Ph Line # Trb This message is displayed when the phone line voltage
drops below 2 VDC or can not supply a minimum of 4 mA of current. The # indicates which phone line is in trouble.
Data Lost This event will be reported to the central station if the
reporting buffer fills. This may occur if more that 24 events need to be reported. When the report buffer is full and additional events are added to the report buffer, the oldest event will be overwritten and the data lost event will be added.
Com # Trb The SK-5208 must use alternating phone lines (according
to NFPA) when reporting auto tests and manual tests. If the control panel can not communicate using the selected phone line, the Com # Trb message will be displayed. The # indicates which line had the trouble.
This may occur if the maximum current rating (1Amp) for this circuit is exceeded.
Check the AC power connection. This report will be sent to the central station after the AC delay time has expired. See Section 4.2.10 to program AC delay time.
Check battery connection. Verify that the control panel has AC power.
The trouble condition will clear after the control panel is successful in communicating using the phone line.

7.2 Earth Ground Fault Troubleshooting

An Earth Fault Trb indicates that the panel has detected a short between any terminal on the panel and earth ground. To determine the location of the short, place a DC volt meter with ground on terminal 22 (circuit ground) and positive on any of the screws that secure the circuit board to the cabinet (earth ground).
A typical meter reading should alternate between 0 VDC and 11.7 VDC. Any other voltage will put the panel into Earth Fault Trb (see also Table 7-1). Remove and leave off field wiring from the panel until the meter alternates between 0 VDC and 11.7 VDC.
When an Earth Fault is indicated at the touchpad two messages will be added to the event history buffer, Earth Fault 38 and Earth ###. This information can be very helpful to identify where an earth ground fault exists in an intermittent earth ground situation.
If the Earth ### is lower than 133 this typically would indicate an earth ground short to a low voltage source (13.1 VDC or less). For example, any circuit ground terminal or zone input terminal.
If the Earth ### is higher than 134 this typically would indicate an earth ground to a higher voltage source (13.1 VDC or higher). For example, any circuit power, standby battery, phone lines, or AC power.
7-2
Page 82
Model SK-5208 Installation Manual 151204

7.3 Earth Fault Resistance

Table 7-2 list the earth fault resistance values for each applicable terminal on the FACP.
Table 7-2: Earth Fault Resistance Values by Terminal
Function
Zone 1 input.
Zone 2 input
Ground 9 GND 0K Zone 3 input 10 Z3 0K Power (Zone 3 & 4) 11 PWR 0K Zone 4 input 12 Z4 0K Zone 5 input 13 Z5 0K Smoke Power 14 PWR 0K Zone 6 input 15 Z6 0K Zone 7 input 16 Z7 0K Smoke Power 17 PWR 0K Zone 8 input 18 Z8 0K Zone9 input 19 Z9 0K Smoke Power 20 PWR 0K Zone 10 input 21 Z10 0K Ground 22 GND 0K
AC Power Connections
SBUS Connections
Remote Annunciator Connections
Notification Appliance Circuit 4
Notification Appliance Circuit 3
Notification Appliance Circuit 2
Notification Appliance Circuit 1
Terminal
Number
1A 2B 0K 3C 0K 4D 0K 5A 6B 0K 7C 0K 8D 0K
23 B NA 24 Earth NA 25 W NA 26 GND 0K 27 +24DC 0K 28 A 0K 29 B 0K 30 SKI 0K 31 SKO 0K 32 PWR 0K 33 GND 0K 34 + 35 _ 0K 36 + 37 _ 0K 38 + 39 _ 0K 40 + 41 _ 0K
Te rmina l La be l
Z1
Z2
NAC4
NAC3
NAC2
NAC1
Earth Fault Resistance
Value (in Ohms)
0K
0K
0K
0K
0K
0K
7-3
Page 83

Appendix A Compatible Devices

This section of the manual lists devices (smoke detectors and notification appliances) that are compatible with the SK-5208. Contact Silent Knight if you have a question about whether a device not listed here is compatible.
A.1 Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. The table below lists notifi­cation appliances compatible with the FACP. Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and/or Visual.
Note: Not all devices can use the Sync feature, be sure to check table below to ensure the device you have chosen will work with this feature. Synchronization is UL listed as a single circuit operation.
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
AMSECO
SH24W-153075 SAD24-153075 SAD24-75110 SL24W-75110 SL24C-3075110 SLB24-75 RSD24-153075 RSD24-75110 SH24W-75110 SH24W-3075110 SHB24-75 SCM24W-153075 SCM24W-75110 SCM24C-3075110 SCM24C-177 H24W H24R
xx
x x x x x x
x xx xx xx x x x x x x
Horn/Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Horn/Strobe Horn/Strobe Horn/Strobe Chimes/Strobe Chimes/Strobe Chimes/Strobe Chimes/Strobe Horn Horn
151204
A-1
Page 84
Compatible Devices 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M. -R, -T, -Y, -Z Strobe 2701 Series Strobe 2705 Series Strobe
Faraday
2820 x x Snyc Temporal Horn/Strobe 2821 x x Snyc Temporal Horn/Strobe 2824 x x Horn Strobe 5333 Multi-Tone Horn) 5336 Multi-Tone Horn/Strobe 5337 Multi-Tone Horn/Strobe 5338 Multi-Tone Horn/Strobe 5343 Single Tone Horn/Strobe
A-2
Page 85
Model SK-5208 Installation Manual 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
5346 Electronic Horn with Strobe 5347 Electronic Horn with Strobe 5348 Single Tone Horn/Strobe 5373 8-Tone Horn/Strobe 6321 Sync Mini Horn/Strobe 6322 Mini Horn/Sync Strobe 6380 8-Tone Electronic Signal/Strobe 5376 8-Tone Horn/Strobe 5377 8-Tone Horn/Strobe 5378 8-Tone Horn/Strobe 5383 8-Tone Horn/Strobe with Sync Strobe 5386 8-Tone Horn/Strobe with Sync Strobe 5387 8-Tone Horn/Strobe with Sync Strobe 5388 8-Tone Horn/Strobe with Sync Strobe 5508 Single Gang Sync Strobe 5509 Strobe 5510 Strobe
Faraday (cont.)
5511 Strobe 5512 Strobe 5516 Strobe 5517 Strobe 5518 Strobe 5519 Strobe 5521 4” Square Sync Strobe 5522 4” Square Sync Strobe 6120 Horn 6140 Horn 6223 Horn 6226 Horn/Strobe 6227 Horn/Strobe 6228 Horn/Strobe 6243 Electron-Mechanical Horn 6244 Electron-Mechanical Horn 6245 Electron-Mechanical Horn 6246 Electron-Mechanical Horn/Strobe 6247 Electron-Mechanical Horn/Strobe 6248 Electron-Mechanical Horn/Strobe
A-3
Page 86
Compatible Devices 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
6300 Mini-Horn 6301 Mini-Horn 6302 Mini-Horn
Faraday (cont.)
FCI
6310 Mini-Horn/Strobe 6311 Mini-Horn/Strobe 6312 Mini-Horn/Strobe 6314 Series -M, -R, -T, -Y, -Z Strobe 6320 Sync Mini Horn/Strobe S2415-FC Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe P241575-FC Horn/Strobe P241575W-FC Horn/Strobe P241575F-FC Horn/Strobe P241575K-FC Horn/Strobe P2430-FC Horn/Strobe P2430W-FC Horn/Strobe P2430K-FC Horn/Strobe P2475-FC Horn/Strobe P2475W-FC Horn/Strobe P2475K-FC Horn/Strobe P24110-FC Horn/Strobe P24110W-FC Horn/Strobe P24110K-FC Horn/Strobe S2430W-FC Strobe S2430K-FC Strobe S2475-FC Strobe S2475W-FC Strobe S2475K-FC Strobe
A-4
Page 87
Model SK-5208 Installation Manual 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
FCI (cont.)
Federal Signal
Gentex
S24110-FC Strobe S24110W-FC Strobe S24110K-FC Strobe 450 Horn VALS Horn/Strobe GEC-24-15
GEC-24-30 GEC-24-60 GEC-24-75 GEC-24-177 GEC-24-110 GEC-24-15/75 x x Horn/Strobe
GX91 GX93 HG124 Horn HS24-15 HS24-30 HS24-60 HS24-75 HS24-110 HS24-1575 GCC24 GCCR24 GCS24 GCSR24 GECR-24 GES24-15 GES24-30 GES24-60 GES24-75 GES24-110 GES24-15/75 GES24-177 GES3-24 GESR-24 GEH-24 ST24-30 ST24-60 ST24-75 ST24-110 ST24-1575
xx xx xx xx xx xx
x x
xx xx xx xx xx xx xx xx
x x
xx
x x x x x x x x x
x
x x x x x
Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe
MiniHorn Steady Tone MiniHorn Temporal Tone
Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Multi Candella Horn/Strobe Ceiling Mount Multi Candella Horn/Strobe Ceiling Mount Multi Candella Strobe Ceiling Mount Multi Candella Strobe Ceiling Mount Multi Candella Horn/Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Multi Candella Strobe Multi Candella Strobe Horn Strobe Strobe Strobe Strobe Strobe
A-5
Page 88
Compatible Devices 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Gentex (cont.)
System Sensor
WGEC24-75W WGES24-75W WGMS-24-X x x Horn/Strobe
CHR CHW CHSR CHSW HR HW HRK P2R P2R-P PC2R PC2R-P P2RH P2RH-P PC2RH PC2RH-P P2W P2W-P PC2W PC2W-P P2WH P2WH-P PC2WH PC2WH-P P2RK PC2RK P2RHK PC2RHK P4R
xx
x
x x xx xx xx
x
x xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
Weatherproof Horn/Strobe Weatherproof Strobe
Chime Chime 2-Wire Chime/Strobe 2-Wire Chime/Strobe Horn Horn Horn 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe 2-Wire Horn/Strobe 2-Wire Horn/Strobe High Candela 2-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe
A-6
Page 89
Model SK-5208 Installation Manual 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
System Sensor (cont.)
PC4R P4RH P4W PC4W P4WH PC4WH P4RK PC4RK P4RHK PC4RHK PC4RH SR SR-P SCR SCR-P SRH SRH-P SCRH SCRH-P SW SW-P SCW SCW-P SWH SWH-P SCWH SCWH-P SRK SCRK SRHK SCRHK P2RH-LF P2WH-LF HR-LF x Low Frequency Sounder HW-LF x Low Frequency Sounder
xx xx xx xx xx xx xx xx xx xx xx
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x xx xx
4-Wire Horn/Strobe 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe 4-Wire Horn/Strobe 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe 4-Wire Horn/Strobe 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe High Candela Strobe Strobe Strobe Strobe Strobe High Candela Strobe High Candela Strobe High Candela Strobe High Candela Strobe Strobe Strobe Strobe Strobe High Candela Strobe High Candela Strobe High Candela Strobe High Candela Strobe Strobe Strobe High Candela Strobe High Candela 2-Wire Low Frequency Sounder Strobe 2-Wire Low Frequency Sounder Strobe
A-7
Page 90
Compatible Devices 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Horn Horn Horn Weatherproof Horn Weatherproof Multi-Tone Horn Strobe Mutli-Tone Horn Strobe Multi-Tone Horn Strobe Multi-tone Horn Multi-tone Horn Horn/Strobe Horn Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Weatherproof Horn/Strobe Weatherproof Horn/Strobe Horn/Strobe Chime Chime Chime/Strobe Chime/Strobe Chime/Strobe Chime/Strobe Chime/Strobe Horn Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Mini Horn Strobe MultitoneHorn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe
Wheelock
AH-12 AH-24 AH-12WP AH-24WP AMT-241575W AMT-24MCW AMT-241575W-NYC AMT-12/24 AMT-12/24 NYC AS-121575W NH-12/24 AS-241575W AS-24MCC AS-24MCCH AS-24MCW AS-24MCWH ASWP-2475W ASWP-2475C ASWP-24MCWH ASWP-24MCCH CH-70 CH-90 CH70-241575W CH70-24MCW CH70-24MCWH CH90-24MCC CH90-24MCCH HS-24 HS4-241575W HS4-24MCW HS4-24MCWH HS4-24MCC MIZ-24S MT-121575W MT-241575W x MT-24MCW MTWP-2475W MTWP-2475C MTG-121575W MTR-121575W
x x x x xx
x xx x x
x xx xx xx xx xx xx xx xx xx xx x x
x
x
x
x
x x xx xx xx xx xx
x
x
x
x
x xx xx
A-8
Page 91
Model SK-5208 Installation Manual 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Multitone Horn Strobe Horn Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Strobe Multi-Cd Strobe Multi-Cd Strobe Multi-Cd Strobe Multi-Cd Strobe Strobe Weatherproof Strobe Weatherproof
Wheelock (cont.)
MTWPA-2475W MTWPB-2475W MTWPG-2475W MTWPR-2475W MTWPA-24MCCH ZNH NS-121575W NS-241575W NS-24MCW NS-24MCC NS-24MCCH ZNS-MCW ZNS-MCWH ZNS-24MCC ZNS-24MCCH RSS-121575W RSS-241575W RSS-24MCC RSS-24MCCR RSS-24MCCH RSS-24MCCHR RSS-24MCW RSS-24MCWH RSSP-121575W RSSP-241575W RSSR-2415W RSSR-2415C RSSR-2475W RSSR-2475C RSSR-24110C RSSA-24110W RSSB-24110W RSSG-24110W RSSR-24110W RSSA-24MCC RSSB-24MCC RSSG-24MCC RSSR-24MCC RSSWPA-2475W RSSWPA-24MCCH
xx xx xx xx xx x xx xx xx xx xx xx xx xx xx
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
A-9
Page 92
Compatible Devices 151204
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
Wheelock (cont.)
RSSWPG-24MCCH RSSWPR-24MCCH RSSWP-2475W RSSWP-2475C RSSWP-24MCWH ZRS-MCWH ZRS-24MCC ZRS-24MCCH MB-G6-24 Motor Bell
MB-G10-24 Motor Bell MB-G6-12 Motor Bell MB-G10-12 Motor Bell MIZ-24-R Mini-Horn MT-12/24-R x MT4-12/2z x ZRS-MCW MTWPR-24MCCH x NH-12/24R x Horn HSR HSW STR STW HNR HNW
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Weatherproof Strobe Strobe Strobe
Multitone Horn Multitone Horn Strobe Multitone Horn Strobe
Horn/Strobe Horn/Strobe Strobe Strobe Horn Horn
Smoke Detectors
This section of the manual contains information about smoke detectors that are compatible with the SK-5208.
SK-5208 SK-5217 Identifier Maximum Voltage
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped-
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur. Do not mix different models of detectors on any zone; false alarms could occur. Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum
reset time of the smoke detector.
24J 24J
27.4 VDC 27.4 VDC
A-10
Page 93
Model SK-5208 Installation Manual 151204
A.2 Two-Wire Smoke Detectors
The table below lists two-wire smoke detectors that are compatible with the SK-5208 and SK-5217 zone expander. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used.
Manufactu
rer
Apollo
Detection Systems
ESL
Enhanced
Mode
Compatible
3 55000-250 55000-350 45681-200, 220, 230,
3 55000-350 55000-250 45681-200, 220, 230,
3 55000-225 55000-225 45681-255, 256 3 55000-226 55000-226 3 55000-227 55000-227 3 55000-325 55000-325 3 55000-328 55000-328 3 55000-326 55000-326 3 55000-327 55000-327
3 425 (S10) N/A S00 30 3 425C (S10) N/A S00 30 3 425CR (S10) N/A S00 30 3 425CRT (S10) N/A S00 30 3 425CT (S10) N/A S00 30 3 429C (S10A) N/A S10A 30 3 429CRT (S11A) N/A S11A 30 3 429CST (S11A) N/A S11A 30 3 429CT (S10A) N/A S10A 30 3 521B N/A S10A/S11A 40 3 521BXT N/A S10A/S11A 40 3 609U01-11 S10 S00 40 3 609U02-11 S10 S00/S03 40 3 611U (601U or 602U) S10 S00/S03 40 3 611UD (601U or 602U) S10 S00/S03 40 3 611UT (601U or 602U) S 10 S00/S03 40 3 612U (601U or 602U) S10 S00/S03 40 3 612UD (601U or 602U) S10 S00/S03 40
Model Name or Number
(Base model name or number in
parentheses.)
55000-150, 151, 152, 153 55000-150,
151, 152, 153
55000-380 55000-380 45681-200, 220, 230,
DS200 (MB200-2W) B A 24 DS200HD (MB200-2W) B A 24 DS250 (MB2W or MB2WL) B A 18 DS250HD (MB2W or MB2WL) B A 18 DS250TH (MB2W or MB2WL) B A 18
Compatibility ID # per Loop
Head Base
45681-200, 220, 230, 231, 232
231, 232
231, 232
231, 232
45681-200, 220, 230, 232, 251, 252
40
40
25
15
15 / loop for
Ion Detectors
15 / loop for
Photoelectric
detectors
A-11
Page 94
Compatible Devices 151204
Manufactu
rer
ESL
FCI
Grinnell Fire Protec­tion
Enhanced
Mode
Compatible
3 711U (701E or 701U) N/A S10A 25 3 712U (701E or 701U) N/A S10A 25 3 713-5U (702E or 701U) N/A S10A 25 3 713-6U (702E or 701U) N/A S10A 25 3 721-U (S10A) N/A S10A 30 3 721-UT (S10A) N/A S10A 30
Model Name or Number
(Base model name or number in
parentheses.)
301I (301B) A A 20 301IL (301BL/SS B401BH) N/A N/A 20 301P (301B) A N/A 20 301PL (301BL/SS B401BH) A N/A 20 301PT (301B) A N/A 20 301P (301DH-2) A N/A 20 301I-DH (301DH-2) A N/A 20 2100S A N/A 20 2100TS A N/A 20 2100TR A N/A 20 2100AT A N/A 20 SBS-1101 A N/A 20 SBS-1201 A N/A 20 SBS-1201T N/A N/A 20 PSD-7155 (2WB/2WRLT/2WRB) P55FE1 FE51A 40 PSD-7155 (CPD-001/-002/-003/-005) P56FE1 FE51A 40 PSD-7156 (2WB/2WRLT/2WRB) P55FE1 FE01A 40 PSD-7156 (CPD-001/-002/-003/-005) P56FE1 FE01A 40 CPD-7051 (2WB/2WRLT/2WRB) CPD7051 FE51A 40 CPD-7051 (CPD-001/-002/-003/-005) CPD7051 FE51A 40 DH100P (Duct Housing) N/A N/A 40 612H (4B, 6B, 612/912) 612H 4B, 6B, 612/912 15 612HP (4B, 6B, 612/912) 612HP 4B, 6B, 612/912 15 612I (4B, 6B, 612/912) 612I 4B 4B, 6B, 612/912 15 612P (4B, 6B, 612/912) 612P 4B, 6B, 612/912 15 622HP (4B, 6B, 612/912) 622HP 4B, 6B, 612/912 15 632H(4B, 6B, 612/912) 632H 4B, 6B, 612/912 15 MD612 (4B, 6B, 612/912) MD612 4B, 6B, 612/912 15 MD622 (4B, 6B, 612/912) MD622 4B, 6B, 612/912 15 MD632 (4B, 6B, 612/912) MD632 4B, 6B, 612/912 15 MF612 (4B, 6B, 612/912) MF612 4B, 6B, 612/912 15 MR612 (4B, 6B, 612/912) MR612 4B, 6B, 612/912 15 MR612T (4B, 6B, 612/912) MR612T 4B, 6B, 612/912 15 ISC—350I (IBC-350, 351, 353) ISC—350I IBC-350, 351, 353 24 ISC—350P (IBC-350, 351, 353) ISC—350P IBC-350, 351, 353 24
Compatibility ID # per Loop
Head Base
A-12
Page 95
Model SK-5208 Installation Manual 151204
Manufactu
rer
Hochiki
Kidde­Fenwal
System Sensor
Enhanced
Mode
Compatible
Model Name or Number
(Base model name or number in
parentheses.)
SIH-24F (HS-224D or HSB-224) N/A N/A 25 SLK-12 N/A N/A 25 SLK-24F (HS-224D) N/A N/A 25 SLK-24FH (HS-224D) N/A N/A 25 (HS224L) Heat Detector base N/A N/A 30 SLR-8358B N/A N/A 25 PSD-7155 (70-201000-001) P55FE1,
P56FE1 PSD-7156 (70-201000-001) P56FE1 FE01A 40 CPD-7051 (70-201000-001) CPD 7051,
I51FE1 1100T 20 1151 (B110LP) 20 1400 A N/A 20 1451 (B401B) A A 20 2100 A N/A 20 2100AT A N/A 20 2100D A N/A 20 2100T A N/A 20 2100TR A N/A 20 2100TS A N/A 20 2151 (B401) A N/A 16 2151T (B401) A N/A 16 2151 (B110LP) 20 2300 A N/A 20 2300T A N/A 20 2300TB A N/A 20 2400 A N/A 20 2400TH 20 2400 (DH400) A N/A 20 2451 (B401B) A N/A 20 2451DH (DH 400) A N/A 20 2451TH (B401B) A N/A 20 2W-B A N/N 25 2WT-B A N/A 25 2WTR-B A N/A 25
Compatibility ID # per Loop
Head Base
FE51A, FE01A 40
FE51A, FE01A 40
A-13
Page 96
Compatible Devices 151204
A.3 Four Wire Smoke Detectors
Manufacturer Model
Hochiki ESL
System Sensor
SLR-835B with HD-6 Base 445C Series
449C Series 1851B
2851/2851BTH DH400AC/DC
A-14
Page 97

Silent Knight Fire Product Warranty and Return Policy

General Terms and Conditions
All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details.
This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposure to adverse environmental conditions, or have been modified in any manner whatsoever.
Repair and RMA Procedure
All products that are returned to Silent Knight for credit or repair require a RMA (Return Authorizat ion) number. Call Silent Knight Customer Service at 800-328-0103 or 203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday through Friday to obtain a return authorization number.
Silent Knight T echnical Support is available at 800-446-6444 between 8:00 A.M. and 5:00 P.M. CST, Monday through Friday.
All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit.
RMA number must be prominently displayed on the outside of the shipping box. See return address example under Advanced Replacement Policy.
Included with each return should be: a packing slip that has the RMA number, a content list, and a detailed description of the problem.
All products returned to Silent Knight must be sent freight pre-paid. After product is processed, Silent Knight will pay for shipping product back to customer via UPS ground.
Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an additional $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries. Silent Knight has the authority to determine if a product is repairable. Products that are deemed un-repairable will be returned to the customer.
Product that is returned that has a board date code more than 36 months from date of manufacture will be repaired and the customer will be assessed the standard Silent Knight repair charge for that model.
Advanced Replacement Policy
Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the first 6 months of the warranty period. These items must be returned with transportation charges prepaid and must be accompanied by a return authorization.
For advance replacement of a defective board, contact your local Silent Knight distributor or call Silent Knight at 800-328-0103 to obtain a RMA (Return Authorization) number and request advanced replacement.
A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Silent Knight. All returned products must comply with the guidelines described under “General Terms and Conditions” and “Repair and RMA Procedure”.
The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit. No credit will be issued if the returned board was damaged due to misuse or abuse.
Repairs and returns should be sent to: Silent Knight / Honeywell Attn: Repair Department / RA Number_______________________ 12 Clintonville Road Northford, CT 06472 USA
1
Page 98

Manufacturer Warranties and Limitation of Liability

Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to extent possible, any warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, service repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY P AR TICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
2
Page 99
Cut Along the Dotted Line

Model SK5208 Basic Operating Instructions

These Instructions must be framed and displayed next to the SK-5208 panel in
accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
Operation Task to Perform
Press 0 ENTER them enter a code if prompted.
Test the system
Reset Alarms Press 1 ENTER or RESET then enter a code if prompted. Reset the Dialer
Display History Events
Show Status Silence Troubles or Alarms Press 7 ENTER or SILENCE then enter a code if prompted. Silence LED will light. Disable/Enable a Zone
Disable/Enable NAC
Conduct a Fire Drill Reset Detectors 1. Press 2 1 ENTER then enter a code. Resets all smoke detector power. Walk Test the System
Acknowledge Events
LED Status Condition
ALARM (red)
SUPERVISORY (yellow)
TROUBLE (yellow)
SILENCED (yellow)
AC (green)
The system will perform a display lamp test and a communication test. Displays Firmware Revisions.
Press 3 ENTER, then enter a code if prompted Resets the dialer and aborts the call to central station.
Press 5 ENTER then enter a code if prompted. Displays the panel history, which includes alarms, supervisories, troubles, reports, time and date changes, etc.
Press 6 ENTER then enter a code if prompted. View existing system status. List Alarms first, supervisories and then troubles.
1. Press Zone # + *
2. Enter Code. Repeat the process to enable the zone.
1. Press 1 0 NAC # + *
2. Enter Code. Repeat the process to enable the NAC.
1. Press 2 0 ENTER then enter a code
2. Press RESET then code to end the drill.
1. Press 2 2 ENTER then enter a code
2. Press RESET to end the Walk Test. Events can be acknowledged by pressing the ENTER button. No code is required to
acknowledge events. The status LEDs (Alarm, Supervisory and Trouble) will flash when an un­acknowledged alarm, supervisory, or trouble condition exists. After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble LED) stop flashing and turn on steady. When viewing system st atus the LCD displays “Acked” for each individual event once it has been acknowledged. The control panel piezo will silence after all alarms have been acknowledged. Note: The control panel piezo will continue to sound for Supervisories and Troubles even after
the event has been acknowledged. Supervisories and troubles will silence once the event
is restored. After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the history buffer will be preceded with an asterisk “*”.
LED Meanings
Off Normal condition On System in alarm. Flashing LED will flash when a alarm condition exists that has not been acknowledged. Off Normal condition On If a supervisory condition exist on the system.
Flashing Off Normal condition
On Trouble condition exists Flashing Off Normal condition.
On Alarm or trouble condition has been silenced but condition still exists. On Panel is running on AC (normal condition); standby battery fully charged. Off Panel has lost all power. Flashing Panel is running on battery power only or AC power only.
LED will flash when a supervisory condition exists that has not been acknowledged.
LED will flash when a trouble condition exists that has not been acknowledged.
PN 151214 Rev B
ECN 14-00
Page 100
Loading...